PREDICTING MISMATCH LOSSES IN UTILITY-SCALE PHOTOVOLTAIC SYSTEMS
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
2
• Background: Module and string-level electrical mismatch.
• Motivation
• Model & Methods
• Model validation
• Simulations, Results, & Discussion
• Future Work
• Q & A
OVERVIEW
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
3
1. For a 1 MW array, mismatch losses increase gradually below a bin width of 6W, and more drastically
at higher distributions. At 5W, a common tolerance for DC arrays, mismatch loss is 0.501 ± 0.003%
of power.
2. For an effective bin distribution of 5W, mismatch loss decreases as the array size increases, with a
diminishing effect. Mismatch loss remains relatively constant for arrays above 1 .5MW.
3. The difference in mismatch losses between two arrays of the same size, one with a central inverter
and the other with 60kW string inverters, remains constant as array size increases. String inverter
designs offer a constant, minimal advantage over central inverters with respect to mismatch.
4. For a ~2 MW array, the difference in mismatch losses between an array with string inverters and an
array with a central inverter decreases rapidly as the string inverters rating approaches that of the
central inverter (as the number of string inverters decreases). This is an expected result that further
validates the model’s behavior.
EXECUTIVE SUMMARY
ELECTRICAL MISMATCH
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
5
Module Mismatch
variations in the current-voltage characteristics of photovoltaic modules
Mismatch Loss [Ploss]
the overall loss in power when modules are connected together in a network, compared to the sum of their individual maximum power points
𝑃𝑙𝑜𝑠𝑠 % = 𝑃𝑚𝑎𝑥,𝑚𝑜𝑑𝑢𝑙𝑒 − 𝑃𝑚𝑎𝑥,𝑎𝑟𝑟𝑎𝑦
𝑃𝑚𝑎𝑥,𝑎𝑟𝑟𝑎𝑦
ELECTRICAL MISMATCH: A BRIEF BACKGROUND
SERIES PARALLEL
I = constant
Ploss α σI
V = constant
Ploss α σV
MOTIVATION
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
7
PREVIOUS WORK
• Bucciarelli’s statistical approach… mismatch loss is proportional to the variance of module electrical characteristics within a bin [1]
• F. Iannone et al. Monte Carlo approach…validates Bucciarelli’s work, especially at low standard deviations [2]
• Chamberlin et al. achieves mismatches of 0.1-0.53% for randomly arranged small arrays [3]
• S. MacAlpine et al. suggests that 1-2% derate is applicable for mismatch at the string-level [4]
MOTIVATION
…to study mismatch at the utility-scale with the most recent technology, and reevaluate industry wide energy prediction assumptions.
MOTIVATION
[1] L.L. Buciarelli Jr., “Power loss in photovoltaic arrays due to mismatch in cell characteristics,” Solar Energy, vol. 23, no. 4, pp. 277-288, 1979.[2] F. Iannone, G. Noviello, A. Sarno, “Monte Carlo techniques to analyse the electrical mismatch losses in large-scale photovoltaic generators,” Solar Energy Vol. 62, No. 2, pp. 85-92, 1998. [3] C.E. Chamberlin, P. Lehman, J. Zoellick, G. Pauletto, “Effects of mismatch losses in photovoltaic arrays,” Solar Energy, Vol. 54, No. 3, 1995. [4] S. MacAlpine, M. Brandemuehl, R. Erickson, “Beyond the Module Model and Into the Array: Mismatch in Series Strings,” 38th IEEE PVSC, Austin, TX, 2012.
MODELING METHODS
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
9
• the “distribution” of all module I-V characteristics is that of Pmp… σ(P) = σ(IV)
• NO secondary contributions to mismatch (shading, DC losses, degradation, etc.)
• uniform distribution of maximum power points
• all DC analysis – no inverter clipping considered
• I-V curve data at STC
ASSUMPTIONS
~3 bins
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
10
MODEL FLOWCHART
Query
SQL DBInputs
Create
‘modules’ from
raw I-V data
Configure
array
layout
Sum I-V curves
in series to get
string I-V
curves
Sum string I-V
curves in
parallel to get
single array I-V
curve
Pmp of
each I-V
Take sum of
Pmp’s
Pmp of
array I-V
Calculate
Mismatch Loss
INPUTS
- number of strings
- number of modules per string
- I-V data query parameters: nameplate power, bin distribution
- string inverter rating (optional)
𝑃𝑙𝑜𝑠𝑠 % = 𝑃𝑚𝑎𝑥,𝑚𝑜𝑑𝑢𝑙𝑒 − 𝑃𝑚𝑎𝑥,𝑎𝑟𝑟𝑎𝑦
𝑃𝑚𝑎𝑥,𝑎𝑟𝑟𝑎𝑦
MODEL VALIDATION
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
12
1. flash-test 3 individual modules, measure I-V curves
2. connect modules in parallel
3. measure “array” I-V curve
4. take individual I-V curve data and use tool to generate simulated “array” I-V curve
5. calculate error (simulated – measured)
SMALL-SCALE VALIDATION
SIMULATIONS & RESULTS
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
14
IMPACT OF BIN DISTRIBUTION
Module First Solar Series 4V3
Bin 112.5 W (+/- ? W)
# Simulation Runs Averaged 5
Inverter Rating ≈ 1 MW
# Strings in Array 592
Modules Per String 15(2 W, 0.211 ± 0.002%)
(5 W, 0.501 ± 0.003%)
For a 1 MW array, mismatch losses increase gradually below a bin width of 6W, and more drastically at higher distributions. At 5W (a common tolerance within a given array) mismatch loss is 0.501 ± 0.003% of total power.
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
15
# Strings Inverter Rating [kW]
0 0
100 168.75
200 337.5
300 506.25
400 675
500 843.75
600 1012.5
700 1181.25
800 1350
900 1518.75
1000 1687.5
IMPACT OF DC ARRAY SIZE
Module First Solar Series 4V3
Bin
110.0 W (-0/+2.5W) & 112.5 W (-0/+2.5 W)
Effectively 5.0W bin.
# Simulation Runs Averaged 5
Inverter Rating ?
# Strings in Array ?
Modules Per String 15
For an effective bin distribution of 5W, mismatch loss decreases as the array size
increases, with a diminishing effect. Mismatch loss remains relatively constant for arrays above 1.5MW.
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
16
STRING INVERTERS VS. CENTRAL INVERTER (PART 1)
Module First Solar Series 4V3
Bin
110.0 W (-0/+2.5W) &
112.5 W (-0/+2.5 W)
Effectively 5.0W bin.
String Inverter Rating
60 kW
(36 strings)
# String Inverters ?
Central Inverter Rating ?
# Strings in Array ?
Modules Per String 15
The difference in mismatch losses between two arrays of the same size, one with a central inverter and the other with 60kW string inverters, remains constant as array size increases. String inverter designs offer a constant, minimal advantage over central inverters with respect to mismatch.
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
17
STRING INVERTERS VS. CENTRAL INVERTER (PART 2)
Module First Solar Series 4V3
Bin
110.0 W (-0/+2.5W) & 112.5 W (-0/+2.5 W)
Effectively 5.0W bin.
String Inverter Rating ?
# String Inverters ?
Central Inverter Rating ≈ 1.98 MW
# Strings in Array 1080
Modules Per String 15
For a constant 1.98 MW array, the difference in mismatch losses between an array with string inverters and an array with a central inverter decreases rapidly as the string inverter rating approaches that of the central inverter, and subsequently the number of string inverters decreases. This expected result further validates the model’s behavior.
FUTURE WORK
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
19
• comparative analysis: CdTe vs. c-Si
• utility-scale validation
— measure string currents, and isolate mismatch losses from resistive losses
• secondary mismatch effects
— shading (in progress)
— temperature gradient (and temperature correction in general)
— resistive (DC) losses
— module degradation
• please contact with any thoughts or suggestions … [email protected]
-
FUTURE WORK
ACKNOWLEDGEMENTS
© C
op
yri
gh
t F
irs
t S
ola
r, I
nc
. 2
3 O
cto
be
r 2
01
6
21
• Fraunhofer Institute for Solar Energy Systems
• Sandia National Laboratories
• Sara MacAlpine, NREL
• Kendra Passow, Mitchell Lee, Mark Grammatico, & Bodo Littman of First Solar
• Alex Panchula, Tesla Motors (formerly of First Solar)
THANK YOU!
QUESTIONS?