The Airedale Air Conditioning Data Centre Masterclass took place at Airedale, Leeds, 20th and 21st March 2013. During the course of the two days, over 100 delegates attended the event. The Masterclass looked at ‘best practice’ and explored containment options with full CFD analysis to increase data centre efficiency. The following slides were presented at the event. Should you have any queries or questions having viewed the presentation, please email [email protected], telephone +44 (0) 113 238 7817.

Citation preview

Page 1: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

A Masterclass in Data Centre Cooling Solutions

Paul Oliver / UK Sales Director

Page 2: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Agenda:11:00 – 12:20 Best practice IT Cooling12:20 – 12:30 Short Break12:30 – 13:30 Meet the product experts13:30 – 15:00 Lunch, Networking & Factory tour

Connect with Airedale:

Follow Airedale on Twitter - Search for @AiredaleACWatch Airedale on YouTube - Search for AiredaleCoolingConnect with Airedale on LinkedIn - Search for Airedale International Air Conditioning

Wi-Fi Access:SSID name: AIACTCPassword: Airedale3

Page 3: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

• Quality

• Innovation

• Experience

• Support

• Service

What the Airedale brand means?

Page 4: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

What our brand means to us…

“Our brand is more than just our logo, it’s how our

customers perceive us, it’s our reputation, the way we

work and our company ethos.”

Clive Parkman

Managing Director, Airedale

Page 5: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Continually improving – why we are here!

Page 6: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Predicting the future of ITC is hard…

1997 – the world’s fastest super-computerSANDIA National Laboratories ‘ASCI RED’

1.8 teraflops150m² raised floor

60+ Cabinets800kW cooling required

2006Sony PlayStation31.8 teraflops0.08m²<0.2kW

+ 9 years

Today's smartphones have about the same raw processing

power as a laptop from 10 years ago.

Page 7: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Page 8: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Some of our customers

Page 9: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Why do they choose Airedale?

Global provider of efficient cooling solutions

40 years experience in IT industry

Largest UK manufacturer of IT cooling solutions

A pioneer in free-cooling technology

An industry leader in rack level cooling

Page 10: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

What do we do?

6-180kW

Multiple system types

Class A EER’s

Market leading kW/m2

Page 11: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

What do we do?

Concurrent Free-

cooling

Class A efficiency

Award winning range

6-1400kW

Page 12: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Award winning

Page 13: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Cooling solution provider

Page 14: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Who are we?

Page 15: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Better by design, exploring containment options to optimise every cooling kW

George Hannah / Product Development Director

Page 16: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Footprint & Density

Operational Costs

Capital Costs

Efficiency

Uptime

Business issues

Page 17: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Types of containment

ECHO – Compact Hot Aisle

OnRak Compact Hot Aisle

Open Aisle Cold Aisle Hot Aisle

InRak Hot Aisle

Page 18: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

The 2nd law of thermodynamics

“The second law states that spontaneous natural processes increase entropy overall, or in another formulation that heat can spontaneously be conducted or radiated only

from a higher-temperature region to a lower-temperature region, but not the other way around.”

TH TC

TW

Page 19: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Open aisle (500 kW facility)

Temperature (oC)

Total heat load 5 kW per rack

Total number of cabinets 100

40

35

15

5

10

30

25

20

Return

45

Supply

Page 20: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Cold aisle containment (500 kW facility)

Temperature (oC)

40

35

15

5

10

30

25

20

45

Total heat load 5 kW per rack

Total number of cabinets 100

Page 21: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Hot aisle containment (500 kW facility)

Temperature (oC)

Additional IT opportunity =

420kW

Total heat load 10 kW per rack

Total number of cabinets 50

40

35

15

5

10

30

25

20

45

Page 22: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

InRakTM hot aisle containment (500 kW facility)

Temperature (oC)

Additional IT opportunity =

420kW

Total heat load 9.8 kW per rack

Total number of cabinets 51

40

35

15

5

10

30

25

20

45

Page 23: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

OnRakTM compact hot aisle (500 kW facility)

Temperature (oC)

Additional IT opportunity

=1880kW

Total heat load 20 kW per rack

Total number of cabinets 25

40

35

15

5

10

30

25

20

45

Page 24: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

ECHO – compact hot aisle (500 kW facility)

Temperature (oC)

40

35

15

5

10

30

25

20

45

AdditionalIT opportunity

= 894kW

Total heat load 20 kW per rack

Total number of cabinets 25

Page 25: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Supply and return temperatures

Temperature (oC)

40

35

15

5

10

30

25

20

45Supply Return

OnRakTM

ECHO

InRakTM

Hot aisle

Cold aisle

Open aisle

Page 26: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Supply and Return Temperatures

Open Aisle

Cold Aisle

Hot Aisle

InRak OnRak ECHO

45

0

35

15

5

10

20

25

30

40

Temperature oC Return Air

Supply Air

Page 27: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

What is free-cooling

OUT

IN

Indirect - Air Direct - Air Indirect - Water

Page 28: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

Hours per year

600

300

Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30

48% 51%

1%

Open aisle

Free-cooling Concurrent Mode Mechanical

Page 29: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

Cold aisle

Free-cooling Concurrent Mode Mechanical

Hours per year

600

300

-6 -2 2 6 10 14 18 22 26 30

62% 32%6%

Ambient Temperature (ºC)

Page 30: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

Hot aisle

Free-cooling Concurrent Mode Mechanical

600

300

Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26

67% 18%25%

Hours per year

Page 31: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

InRakTM

Free-cooling Concurrent Mode Mechanical

600

300

Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26

67% 18%25%

Hours per year

Page 32: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

OnRakTM

Free-cooling Concurrent Mode Mechanical

Hours per year

600

300

-6 -2 2 6 10 14 18 22 26 30

69% 11%20%

Ambient Temperature (ºC)

Page 33: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

ECHO

Free-cooling Concurrent Mode Mechanical

Hours per year

600

300

Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30

89% 10%

1%

Page 34: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Free-cooling

Free-cooling

Concurrent Mode

MechanicalOpen aisle Cold aisle Hot aisle

InRakTM OnRakTM ECHO

Page 35: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

InRakHot aisle

Cold aisle

Open aisle

Increased IT opportunity

0

20

100

40

60

80

Space m2

30m² 32m² 56m² 45m²

Cooling equipment (m2)

Rack (m2) Additional space (m2)

OnRak Echo

Page 36: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

1.45 1.38 1.30 1.29 1.26 1.24

3 year lifecycle cost

0

0.2

1.2

0.4

0.6

0.8

1.0

£ (millions)

Operating costs (over 3 years)

Total capital cost

PUE

InRakHot aisle

Cold aisle

Open aisle

OnRak Echo

Page 37: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Case study: Open aisle containment

The chillers give us 1500kW n + 1 cooling plus a stunning reduction in electricity consumption i.e.

2.5 times cooling capacity for 100 – 150kW less power consumption per day.

Mark Ford

Data Centre Manager

Page 38: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Case study: Hot aisle containment

Airedale provides us with a fully integrated cooling solution designed for maximum efficiency and

critical redundancy…Our carbon neutral status helps our clients take huge steps towards their own

environmental goals and carbon reduction commitments.

Rob Garbutt

Chief Executive Officer

Page 39: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Case study: InRakTM hot aisle containment

The InRakTM is perfectly designed…the units are very clever; they ‘talk’ to each other and maintain

pressure in the room. ACIS gives us 24/7 control of the operation and peace of mind.

Mike Marchant

Data Centre Manager

Page 40: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Case study: OnRakTM compact hot aisle

Our HPC facility at Leeds is growing …by meeting our space constraints and slotting into our existing cooling loop, the OnRakTM units from Airedale have

saved us space in an already densely packed environment

Dr Jon Summers

Senior Lecturer, School of Mechanical Engineering

Page 41: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Business issues

Footprint & Density

Operational Costs

Capital Costs

Efficiency

Uptime

Page 42: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

Driving efficiency improvements in your data centre

www.airedale.com

Page 43: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

What is PUE ?

UTILITYCOMPANY Power

•Switchgear•UPS•Battery BackupCooling•Chillers•CRACs

IT EQUIPMENTPOWER•Servers•Storage

Power Usage EffectivenessPower Usage Effectiveness

PowerEquipmentIT

PowerFacilityTotalPUE

..

..

Power In Power In

TOTAL FACILITY POWER

Page 44: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Low density cooling - < 5kW per rack

Open Aisle Cold Aisle Hot Aisle

One kilowatt of power saved every hour 24/7,represents a saving of £876* a year, equivalent

to over 4 tonnes of CO2 * £0.10/kWh

A 50% drop in air volume gives an 83%reduction in fan power input

Page 45: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Efficient Fan Use

Fan speed

51%

13%

£6,000

£3,000

£ 800

100%80%50%

Power

Page 46: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Precision Air Conditioning - SmartCool

+ 16-200kW+ Up to 4.7kW/m2 ↑ market

leading competitor + ↓ fan power on the market + ETL Listed (ECA)

Page 47: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Precision Air Conditioning - EasiCool

+ 6-60kW+ > 8% more kW/m2+ 70%↓ energy EC fans+ 30% ↑ in EER

Page 48: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Medium density cooling – 6-20kW per rack

Up to10% more cooling kW/m2

SmartCool™ CW 93 –162kW** Ideal for large data centres

49% less fan power running five CRACunits at 80% air flow rather than four run

and one standby

InRak Hot AisleCold Aisle Hot Aisle

Page 49: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

IT Cooling - InRak

+ 10-60kW+ 17-100% variable control+ Ch Water & DX versions+ EER up to 90.3

Page 50: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

88% less annual power consumption than a traditional CRAC unit

High density cooling – >20kW per rack

The OnRak™ adds only200mm to the depth of the rack

OnRak

Page 51: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

IT Cooling - OnRak

+ 3-33kW+ Slim configuration+ Can fit any OEM’s rack+ EER up to 109

Page 52: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

A 7°C increase in watertemperatures gives 45%

saving in energy

Pushing the boundaries of Chiller technology

Up to 109% of nominal capacity in free-cooling

Page 53: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Chillers – DeltaChill & DeltaChill FreeCool

+ 110-1030kW+ ESEER up to 4.79+ Single, dual & triple circuits+ 50% energy savings with concurrent free-cooling

Page 54: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Chillers – TurboChill & TurboChill FreeCool

+ 200-1100kW+ ESEER up to 5.69+ Class A EER up to 4.14+ EER >10 at part load+ Up to 116% of nominal capacity in free-cooling

Page 55: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Chillers – TurboChill & TurboChill FreeCool

+ 200-1100kW+ ESEER up to 5.69+ Class A EER up to 4.14+ EER >10 at part load+ Up to 116% of nominal capacity in free-cooling

Page 56: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Questions?

Page 57: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Do I still need mechanical cooling in my data centre?

Page 58: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

When is adiabatic cooling right for me?

Page 59: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

What operating temperature should I run my data centre at?

Page 60: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

How can I get maximum benefit out of EC fans?

Page 61: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Efficient Fan Use

Fan speed

51%

13%

£6,000

£3,000

£ 800

100%80%50%

Power

Page 62: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

How do I select a chiller, which benchmark is right for me?

Page 63: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

Seasonal Affects & ESEER Values

EnergyEfficiency

Ratio

Temperatures (ºC)-10 -5 0 5 10 3530252015

25%

50%

75%

0%

100%

Chiller loading factor

ESEER

Page 64: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

How do I get the most out of my Building Management System?

Page 65: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com

How can I ensure my capital investment continues to operate as efficiently as when purchased?

Page 66: Data Centre Cooling Masterclass 20 & 21 March 2013 - Airedale Air Conditioning

www.airedale.com