35
© 2015 Mirus International | All Rights Reserved Harmonic and Energy Saving Solutions Power Quality You Can Trust | Real World Experience | A History of Innovation

Preventing circulating current in parallel generator applications

Embed Size (px)

Citation preview

Page 1: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Harmonic and Energy Saving Solutions

Power Quality You Can Trust | Real World Experience | A History of Innovation

Page 2: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

Preventing Circulating Currents in Parallel Generator Applications

Today’s Presenter

•  Prior to joining Mirus, Tony was the Chief Facilities Electrical Engineer at an IBM manufacturing facility in Toronto

•  Tony is a professional engineer •  Tony is also a member of IEEE,

and has published multiple research papers on power quality

Page 3: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Preventing Circulating Current in Parallel Generator Applications

Page 4: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

Scope of Presentation •  Generator Pitch and Harmonics •  How paralleling dissimilarly pitched generators creates

neutral circulating current •  Traditional methods used to prevent generator circulating

current •  GENLINK Dissimilar Pitch Neutral Limiter (DPNL) •  Case Studies:

–  Martin Brower Distribution Facility •  750kW and 1000kW Generators

–  Arkansas University •  2 x 800kW Generators with 1500kVA Utility Transformer

–  City of Waterloo Power Plant Expansion •  New 7200kW 13.8kV Turbine Generator

•  Summary

Page 5: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Generator Pitch and Harmonics Coil Pitch:

The angular distance between the two sides of an individual coil of an AC armature winding

Pole Pitch: The angular distance between centers of adjacent field poles

Winding Pitch: The ratio of Coil Pitch to Pole Pitch

Full Pitch Winding: When Coil Pitch is exactly equal to Pole Pitch Full Pitch Generator

Coil Pitch = 90°, Pole Pitch = 90°

Generator  Pitch  &  Harmonics  

Circula4ng  Currents  problems  

Preven4ng  Generator  Circula4ng  Current   GENLINK  DPNL   Case  Studies  

Page 6: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Generator Pitch and Harmonics

Fractional Pitch Winding: When Coil Pitch is less than Pole Pitch

Advantages of Fractional

Pitch Generators: –  Shorter end

connections to reduce copper

–  More sinusoidal waveform and therefore, less harmonics

2/3 Pitch Generator Coil Pitch = 60°, Pole Pitch = 90°

Page 7: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Generator Pitch and Harmonics •  Voltage waveform produced by a generator will vary

slightly with respect to winding pitch •  Harmonic content in voltage will also vary based on

winding pitch –  Pitch factors below are used to predict harmonic

voltages based on respective harmonic fluxes

Reference: ‘Generator Winding Pitch and Harmonics, Engine Data Sheet EDS 70.4, Caterpillar, March 1993 ’

Pitch Fund. 3rd 5th 7th 9th 2/3 0.866 0.0 0.866 0.866 0.866 4/5 0.951 0.588 0.0 0.588 0.951 5/6 0.966 0.707 0.259 0.259 0.966 6/7 0.975 0.782 0.434 0.0 0.782

Page 8: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Generator Pitch and Zero Sequence Impedance

•  Generator impedances vary with respect to winding pitch, especially zero sequence impedance

•  Generator zero sequence impedance directly impacts the amount of circulating neutral current

•  Many claim that a 2/3rd pitch generator is better for 3rd harmonic, but this is not entirely true –  it has very low zero sequence impedance which

results in less 3rd harmonic voltage distortion under non-linear loading, but

–  the low zero sequence impedance presents little resistance to the flow of circulating currents

Page 9: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

How Paralleling Dissimilarly Pitched Generators creates Neutral Circulating Current

•  Generators with different pitch configurations will have slightly different voltage waveshapes

•  Differences in Phase-Neutral (Ph-N) instantaneous voltages will appear as triple frequency

•  Can also apply when paralleling alternate energy sources with the Utility

5/6P Gen1

2/3P Gen2

Generator  Pitch  &  Harmonics  

Circula4ng  Currents  problems  

Preven4ng  Generator  Circula4ng  Current   GENLINK  DPNL   Case  Studies  

Page 10: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

How Paralleling Dissimilarly Pitched Generators creates Neutral Circulating Current (cont.)

•  Difference in instantaneous voltages drives neutral circulating current

•  Flow is restricted only by zero sequence impedance of generators and cables which is usually quite low

Page 11: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Traditional Methods for limiting Circulating Currents

•  Ensure that generators are of similar pitch –  This is not always possible or even preferred when

expanding a site with older, existing generators –  Can be difficult when sourcing from different suppliers or a

supplier that has changed their pitch design –  Even identically pitched generators can have slightly

different voltage waveshapes

Generator  Pitch  &  Harmonics  

Circula4ng  Currents  problems  

Preven4ng  Generator  Circula4ng  Current   GENLINK  DPNL   Case  Studies  

Page 12: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Traditional Methods for limiting Circulating Currents (cont.)

•  Add impedance in the common neutral –  Neutral Grounding Resistors or Neutral Reactors can be

used but the impedance required to limit circulating current might reduce 1-ph faults to unacceptable levels

(ie. such that breakers do not trip) –  These devices must be rated for the residual steady state

circulating current –  If NGR’s are required for fault limiting, this can be an

effective method but the requirement to handle steady state current will increase size and cost

Page 13: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Traditional Methods for limiting Circulating Currents (cont.)

•  An ungrounded system can be used where neutrals are not connected together or grounded –  Ground fault monitoring is required and no neutral return

path is available for 1-ph loads –  Sometimes zigzag reactors are used to provide a ground

reference •  Internal generator faults may be a problem

Page 14: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

GENLINK Dissimilar Pitch Neutral Limiter •  Multiple winding reactor installed in the common

neutral of paralleled generators or generators paralleled with Utility

•  Inserts ~ 48% impedance in neutral current circulating path at triple frequency –  Reduces neutral circulating

current by 70% or more •  Minimal effect on fault level

–  Adds < 1% saturated impedance to 1-Ph fault level

–  No impedance to 3-Ph fault level

•  Designed to meet IEEE Std 32 Requirements for Neutral Grounding Devices

Generator  Pitch  &  Harmonics  

Circula4ng  Currents  problems  

Preven4ng  Generator  Circula4ng  Current   GENLINK  DPNL   Case  Studies  

Page 15: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

•  Paralleled generators with dissimilar pitches in stand-alone or emergency stand-bye operation

•  Generator or other Alternative Energy source that is paralleled with a Utility transformer that can have its neutral-ground bond routed through the DPNL –  Cascaded DPNL’s can be used where there are more

than two connected supplies •  Examples are alternative

energy generators, standby generators, islanded supplies for drilling rigs, production platforms, pumping stations, etc.

Applications for GenLink DPNL

Page 16: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Application of GENLINK DPNL in 4-Wire System

•  DPNL is used when 2 or more generators of dissimilar pitch are paralleled together or a generator is paralleled with an alternate source, such as the Utility

•  DPNL is inserted in the neutral between the dissimilar groups •  Neutral should be grounded in only 1 location

–  Preferred location is neutral bus in switchboard

Page 17: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Application of GenLink DPNL on 4-Wire System with Utility Transformer

•  Utility transformer neutral should be grounded through DPNL

•  Ground at only 1 location

Page 18: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Cascaded System for Multiple Generators

•  DPNL’s can be cascaded in applications where there are more than 2 types of dissimilar pitch generators or dissimilarly pitched generators are paralleled with Utility

•  Size each DPNL based on the total generator load connected to it

Page 19: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

DPNL Fault Current Path •  Fault current passes through the shoulder of the DPNL

(Z-X or Y-X) –  Shoulder impedance is typically 4% – 5%

•  During a fault, reactor steel saturates, significantly reducing the impedance

Fault current path

Page 20: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

GENLINK Effect on 1-Ph Fault Level

3000A DPNL •  1-ph impedance

–  Normal Operation ~ 5% –  Above 8000A (saturated condition) < 1%

Page 21: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

GENLINK Dissimilar Pitch Neutral Limiter •  Circulating current inductance (Y-Z) is almost 4x the

shoulder inductance •  Since the frequency of the circulating current is 3x the

fundamental current (180 Hz vs 60 Hz), circulating current impedance is 3x greater

•  Net impedance to circulating current is around 48%

Page 22: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Application of GENLINK DPNL in 3-Wire System

•  In a 3-Wire application where there is no return neutral current from 1-Ph loads, a smaller size DPNL can be used

•  Terminal X may or may not be grounded –  If ungrounded, Ground Fault monitoring will be required

Page 23: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

•  Paralleled generators with dissimilar pitches that are tied to a Utility grid supplied by a transformer or multiple transformers that cannot have neutral grounded through DPNL –  DPNL prevents circulating current between the generators –  NGI helps block circulating current between the generators and

the Utility transformers –  NGI is not necessary if Neutral-Ground bond on Utility

transformers can be routed through DPNL •  Examples are Generating Stations with Alternative Energy

sources, Co-generation sites, Peak Shaving generators, etc. •  Also NGI alone can be

useful in applications with Alternative Energy sources and Utility when neutral is inaccessible

Applications for GenLink DPNL + NGI

Page 24: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

How to Size GENLINK for a Specific Application •  Determine total capacity in

kW or kVA of all generators connected in parallel

•  Select DPNL that corresponds to this value in the appropriate system voltage column

Page 25: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

How to Size GENLINK (cont.) •  This will size the DPNL for a return neutral current that

will be at least 50% of full phase current rating –  85% for 208V-240V or 380V-440V systems

•  It is the Users responsibility to ensure that actual return neutral current will not exceed DPNL rating –  If return neutral current is expected to exceed DPNL

rating then a larger DPNL should be selected –  A larger DPNL will be slightly less effective in reducing

circulating current •  For 3-Wire applications or where return neutral current is

known to be very low, smaller DPNLs can be selected

Page 26: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Total neutral current = 160A

Case Study: Martin Brower Distribution Facility Two Dissimilarly Pitched Generators

Generator  Pitch  &  Harmonics  

Circula4ng  Currents  problems  

Preven4ng  Generator  Circula4ng  Current   GENLINK  DPNL   Case  Studies  

Page 27: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: Martin Brower Distribution Facility

Neutral Grounded at one location only

Page 28: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: Martin Brower Distribution Facility

•  1-Ph load return neutral current = 38.4A •  Most of the current from generators to DPNL is return

neutral current from 1- ph loads •  Almost all generator circulating current was eliminated

Page 29: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: Boca Hospital, S. Florida •  Generator configuration

–  2 x 1375kVA 0.8667 Pitch

–  1 x 1200kVA .0667 Pitch

•  Calculation of expected circulating neutral current provided by Caterpillar Distributor

•  Circulating 3rd harmonic current –  Ga and Gb ~ 97A –  Gc ~ 194A

Page 30: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: Boca Hospital, S. Florida

“Reading went from 400 amp to zero on all three generators and system has functioned with no problems since then.” Hassan Entezari, Pantropic Power Inc.

2500A GenLink DPNL

Page 31: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: 13.8kV System, Waterloo Illinois - Differently pitched Generators and Multiple Utility Trans.

•  New Generator different pitch than existing –  Existing 6600kW (.722P) –  New 7200kW (.814P)

•  No access to Utility transformer neutrals but Mirus was not initially informed of this

Page 32: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: 13.8kV System, Waterloo Illinois

•  Virtually no neutral circulating current between Generators •  Residual current to Utility transformers still too high however

Page 33: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved

Case Study: 13.8kV System, Waterloo Illinois •  Required continuously rated Neutral Grounding Resistor

(NGR) or additional Neutral Grounding Inductor (NGI) between DPNL and ground

•  NGR recommended for this application: –  60A continuous duty, Z = 19 Ohms –  36”W x 36”D x 66”H –  Residual circulating current estimated to be < 50A

•  NGI recommended for this application: –  100A continuous duty, Z = 6.6 Ohms at 60Hz –  44”W x 38”D x 66”H –  Residual circulating current estimated to be < 25A

•  Advantages of NGI over NGR –  More effective in reducing circulating current –  Less effect on fault level –  Much lower losses

•  NGR power dissipation is entirely kW –  Lower cost

Page 34: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

Summary •  Paralleling of different power sources can cause neutral

circulating current –  Dissimilarly pitched generators –  Generator or other alternative energy source with Utility supply –  Different alternative energy sources

•  Neutral circulating current is predominantly triple frequency •  Application of GenLink DPNL can reduce triple frequency

circulating current by 70% or more without significantly affecting fault levels

•  Neutral should be grounded at only one location –  Recommended grounding at Switchboard

•  If Utility transformer neutrals are not accessible, Neutral Grounding Inductor will also be needed

Page 35: Preventing circulating current in parallel generator applications

© 2015 Mirus International | All Rights Reserved Private and Confidential | Mirus International

Questions