OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Embed Size (px)

Citation preview

Page 1: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Welcome

Page 2: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

OVER VIEW OF 2*800 MW SRI DAMODARAM SANJEEVAIAH THERMAL

POWER STATION

Page 3: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

contents

Page 4: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
Page 5: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Location Nellore, Andhra

Pradesh

Status Under Construction

Construction cost 8432/- crores

Owner(s) APPDCL

Operator(s) APGENCO

Primary fuel Coal-fired

Units operational 1*800 MW

Name plate capacity 1600 MW

Page 6: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
Page 7: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fuel

• Domestic washed coal & imported coal in 70:30 ratio with 27.5% Ash

• GCV(gross calorific value) of 4,800 kCal/kg shall be used as a fuel during normal operation

• LDO(light diesel oil) as well as HFO(heavy fuel oil) shall be used as a startup as well as support fuel

Page 8: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fuel • Coal is mined from Kalinga ghat , Talcher Coalfield,

Angul district , Orissa

• shipped to krishnapatnam port by MGR trains and Coal barges and loaded to conveyer belt by stacker

Page 9: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

stacker

Fuel

Page 10: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Pulverisation Fine powder of coal ,grinded by millers is fed

into furnace by hot air(primary air). Secondary air is fed into furnace to complete

combustion. Amount of primary air depends on load(>3%) High thermal efficiency Better control over load fluctuations Free from clinker and slagging troubles

Page 11: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

MILLSA Mill is a mechanical device for the grinding coal upto

desired finenessThere are 6 mills , located adjacent to furnace at ‘0’ M

level

Page 12: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Furnace• Tangential firing-flame envelope rotates ensuring

through mixing within the furnace

• Heat energy is transferred through radiation (80%) and convection(20%).

Page 13: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Furnace

• Heat generating rates of 1.5x 106 kJ/m3/hr can be achieved

• Maximum amount of coal can be achieved with min . space and time

• Through tip(vertical arc) temperature can be varied upto 1000c

• So constant superheat temperature can be maintained

Page 14: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Ash handling plant

• Ash generated is about 30-40%of fuel consumption.

• Must be removed time to time • due to hotness , difficult to handle

Page 15: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Bottom ash removal system• Non combustible residue of combustion of furnace is

bottom ash• Bottom ash falls from furnace to ash sluice trench and discarded to ash pond after mixing with water

Page 16: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Electrostatic precipitator An ESP is a filtration device that removes fine

particles from a flowing gas using the force of an induce electrostatic charge minimally impeding the flow of gases through the unit.

Page 17: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Electrostatic precipitator• Dirt particles are negatively charged

• They are attracted to the positively charged plates and stick there

• From time to time, the collecting plates are shaken to empty away the soot (rapping mechanism)

Page 18: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

ESP

Page 19: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

• collected in ESP hoppers

• We have 8X8 hoppers

Fly ash removal system

Page 20: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fly ash removal system• Pneumatically send to silo and then to trucks• Fly ash is used in 1.production of cement clinkers, concrete, ceilings 2.structural fills , agricultural purposes, floor etc

Page 21: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Water treatment plant

• Through ion exchange process , RO and filtration by resin beds water is demineralised

Page 22: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Water treatment plant

Page 23: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

DEMINERALISED(DM) Waterparameter valueConductivity <0.2 μS / Cm at 25 Deg.C

pH value 9 - 10 at 25 Deg.c

Total silica <0.02 ppm as SiO2

Iron as Fe Not detectable as per ASTM methods

Free CO2 ppm (as CO2 )

Total Hardness “

Page 24: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Sea water

PARAMETERS AS VALUE

pH - 7.6

Turbidity NTU 10

P-alk / M- alk as CaCO3 ppm 98

Ca hardness as CaCO3 ppm 1100

Mg hardness as CaCO3 ppm 5050

Chloride as Cl % 1.89

Silica SiO2 ppm 3.8

Page 25: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Babcock and Wilcox boiler• Boiler is a device for generating steam for power,

processing and heating purposes• Supercritical boiler operates above critical point

Page 26: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
Page 27: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Supercritical boiler• steam turbine efficiency improves significantly

compared to the typical subcritical cycle.

• The load change rate capability of the system is not restricted by the turbine

• Steam temperature at the inlet and outlet of the reheater is nearly constant over a wide load range

• The boiler feedwater pump power is significantly reduced at lower loads

• Short startup times

Page 28: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Classification Supercritical boiler

Page 29: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

UP

Page 30: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Universal Pressure (UP®) boiler.• The original B&W boiler for supercritical applications was the

Universal Pressure (UP®) boiler. • These boilers, nine of which are in operation, are among the largest

capacity fossil fuel boilers in the world. SPECIFICATIONS• Capacity, steam output: 700,000 lb/h (90 kg/s)• Pressure: Subcritical, usually 1800 to 2400 psi throttle pressure with 5%

overpressure capability. • Superheater and reheater outlet temperatures: 538 to 566C • Fuel:Pulverized coal.

Page 31: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

SWUP

Page 32: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Spiral Wound Universal Pressure Boiler

• Designed for both base load and variable pressure load cycling operation as well as on-off cycling operation.

• The unique feature of this boiler, compared to other boilers, is that the tubes in the furnace, from the lower furnace inlet headers to a location near the furnace arch, are wound around the furnace circumference rather than being vertical.

• This design allows the fluid in the tubes to pass through the various heat flux zones around the furnace providing a more uniform outlet enthalpy.

Page 33: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Spiral Wound Universal Pressure Boiler

SPECIFICATIONS• Capacity, steam output: From 2,000,000 lb/h (252 kg/s) to more than

10,000,000 lb/h (1260 kg/s).

• Operating pressure: 3500 psi (24.1 MPa) throttle pressure with 5%

overpressure; higher pressures available.

• Superheater steam temperatures: As required, currently in the 595C range.

• Fuel:Pulverized coal.

Page 34: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Vertical Tube Universal Pressure Boiler

• A once-through boiler, applied to systems with a capacity of 400 MW or larger

SPECIFICATIONS

• Capacity, steam output: 252 kg/s to more than 1260 kg/s. • Operating pressure: 3500 psi throttle pressure with 5% overpressure;

higher pressures available. • Superheater steam temperatures: currently in the 595C range. • Fuel:Pulverized coal.

Page 35: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

BOILER

Main steam flow..........2600 T/hr SH steam press..............255 kg/cm2 (g) SH steam temp..............568° C Feedwater temp............307° C RH steam flow...............2052 T/hr RH steam press.............57.8 kg/cm2 (g) RH steam temp..............596° CHeight............................

Page 36: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

BOILER

Fuel Design RangeGCV, kCal/kg 4800 4000-5000

Moisture, % 9.5 6.0-20.0

Ash, % 27.5 25.0-34.0

Volatile matter,% 28.5 20.0-33.0

Fixed carbon,% 34.5 24.0-40.0

HGI 50 5-55

Page 37: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Boiler accessories Economizer Waste heat of the flue gases is utilized for heating the

feed water Air Pre-heater Transfers heat from flue gases to primary/secondaryAir by means of rotating heating surface elements

Super heater Increases the temperature of the steam above its

saturation point

Page 38: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Boiler accessories P.A.Fan (two per unit-50% capacity each) designed for handling atmospheric air upto a

temperature of 500c

F.D.Fan (two per unit-50% capacity each) designed for handling secondary air for the boiler

I.D.Fan (two per unit-50% capacity each) 1. located between ESP and chimney. 2.used for sucking flue gas from furnace

Page 39: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Boiler accessories• SCR technology 1.Converts NOX into N 2 and water . 2.Anhydrous/aqueous NH3 or urea is added to

stream of ………flue gases and is adsorbed onto a catalyst

4NO + 4NH3 + O2 → 4N2 + 6H2O

3.They reduce NOx by 70-95%

Page 40: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

SCR

• SCR incorporating Ammonia Injection Grid (AGI) and IsoSwirl Mixing system

economizer

Page 41: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Steam Turbine• Being a form of engine , requires in order to function a

suitable working fluid a source of high grade energy and sink of low grade energy

Low presure module of sft 100 alstom

Page 42: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Steam Turbine• Greater heat drop• Absence of internal lubrication(no filters)• Develops many times the power compared to

reciprocating engines

3 stage turbine(tandem compounded)

Page 43: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Steam Turbine• The cylinder(stator) contains fixed blades , vanes and

nozzles that direct steam into moving blades(rotor)

• The rotor are completely enclosed in a alloy steel outer case (one capable of withstanding high pressures and temperatures).

Page 44: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Steam Turbine• The rotor of large steam turbine consists of large ,

intermediate and low pressure sections.• change in direction of motion gives rise to a change of

momentum or force• this is driving force of the primemover

Four Cylinder Turbines

Page 45: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Turbine name plate details

Output 800,000kW Speed 3000rpm HP STEAM PRESS. 24.2MPa(a) HP STEAM TEMP 565 deg

Page 46: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS
Page 47: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Cooling tower(hyperbolic)

• Required when positive control of temperature is required

• Rate of evaporation of water depends on 1 amount of water surface area exposed 2 time of exposure and R .H of air 3 (inlet air WBT-water inlet temperature)

Page 48: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Cooling tower(hyperbolic)• It is necessary to precool the hot water from condenser

So (Two-Ts ) Is high • Vacuum at condenser can be maintained

• It comprises of 30% of budget

• Due to large base , withstands hurricanes

• No fanes are needed

• Chimney shape creates it own draught • No Ground fogging and warm air recirculation

Page 49: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Cooling tower(hyperbolic)• Height = Plan------circular• Diameter= Profile---hyperbolic

• (inside)

Page 50: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Cooling tower(hyperbolic)• Steel reinforced concrete structure

• Mostly hollow inside• Bottom is 10m above air-intake

• Force causing air to flow F=H(w0-wi)

Page 51: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Active power – 604.35MWReactive power – 46.35MVAR

Generator kV : R-Y – 24.32kV : Y-B – 24.32kV : B-R – 24.23kV Generator Amps : R-ph – 14.14kA : Y-ph – 14.33kA : B-ph – 14.61kA

Frequency : 49.97Hz P.F : 1.00

GENERATOR PARAMETERS

Page 52: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

FIELD PARAMETERS

• Field voltage : 288.33V• Field current : 3452.6A• Rotor temperature : 65.13’c• POS 90R(AUTO) : 101.36%• POS 70E(MANUAL) : 147.89%

Page 53: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fig. 19 Switchyard

Switchyard is a part of electrical generation, transmission and distribution

system.

Switchyard generally have circuit breakers, CT’s ,PT’s, Bus bars,

Transformers, Protection control equipments, Switches etc.,.

Page 54: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fig. 20 Circuit Breaker

Circuit breaker: A circuit breaker is an automatically operated electrical

switch designed to protect an electrical current from damage caused by

overload or short circuit. The basic function of CB is to detect a fault

condition and, by interrupting continuity to immediately discontinue

electrical flow.

Page 55: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fig. 21 Lightning arrester

Insulators: The insulators provide necessary insulation between line

conductors and supports and thus prevent any leakage current from

conductors to earth.

Lightning Arrester: It is a device used on electrical power systems and

telecommunication systems to protect insulation and conductors of the

system from the damaging effects of lightning.

Page 56: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fig. 22 Voltage transformer

Voltage transformer: These are necessary for isolating the protection,

control and measurement equipment from the high voltages of the power

system. These are used to supply appropriate values of voltages to the

equipment.

Page 57: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS

Fig. 23 Current transformer

Current transformer: To feed the current circuits in protection systems

employing secondary relays current transformers are used.

Bus coupler: Two different bus sections of two different power

transformers are connected by means of a bus coupler.

Relay: It gives a tripping signal in case of any irregularity or faults.

Page 58: OVERVIEW OF SUPERCRITICAL THERMAL POWERPLANT , DPSTS