FIRE PROTECTION SYSTEM AX 272 F

c.) PRE-ACTION SYSTEM

(For Electrical Substation)

b.) STANDPIPE SYSTEM

a.) SPINKLER SYSTEM 4 ZONE

Page 2: Fire protection system ax 272 f

SPRINKLER SYSTEM 4 ZONES

Page 3: Fire protection system ax 272 f

ALARM VALVE STATION

Page 4: Fire protection system ax 272 f

STANDPIPE SYSTEM

Page 5: Fire protection system ax 272 f

CLASS III SYSTEM IS PROVIDED

Class III Systems Provided 1 ½”

hose stations to supply water for use

by trained building occupants and

2½” hose connections to supply a

larger volume of water for use by

Fire Department.

Page 6: Fire protection system ax 272 f

FIRE HOSE STATION ADVANTAGES

• Quick Suppression

• One Person Operation

• Minimal Water Damage

• Occupant Safety and Rescue

Page 7: Fire protection system ax 272 f

TYPICAL CLASS III FIRE HOSE STATION

Page 8: Fire protection system ax 272 f

OPERATION OF FIRE HOSE STATIONS

1. Open valve completely

2. Pull hose entirely off rack

3. Open nozzle

THREE STEPS FOR OPERATION

Page 9: Fire protection system ax 272 f

1. Open valve completely.

Page 10: Fire protection system ax 272 f

2. Pull hose entirely off rack(or else water will not flow)

Page 11: Fire protection system ax 272 f

3. Open nozzle. Water will flow when hose is entirely off rack & nozzle is open.

Page 12: Fire protection system ax 272 f

PREACTION SYSTEMFOR

ELECTRICAL SUBSTATION

Page 13: Fire protection system ax 272 f

• Preaction System Control Panel

• Smoke detectors

• Manual Pull Station (Electric)

• Alarm Bell

• Sounder cum flasher

PREACTION SYSTEMCOMPONENTS

Page 14: Fire protection system ax 272 f

• Deluge Valve w/ Double Interlock Trim

• Isolation Valve• Pressure Switch (Air)• Pressure Switch (Water)• Air Compressor• Air Maintenance Device

PREACTION SYSTEM COMPONENTS

Page 15: Fire protection system ax 272 f
Page 16: Fire protection system ax 272 f

PREACTION SYSTEM

SEQUENCE OF OPERATION

Smoke Detectors (Zone-1) and Pressure Switch (Zone-2) Monitoring the System Air Pressure in the piping are wired in a cross zoned configuration

Page 17: Fire protection system ax 272 f

Activation of smoke detector or operation

of a sprinkler causes following.

• A visual indication on the System Control Panel

• Audible alarm from bell

• Send “Fire” indication to the Fire Alarm System

PREACTION SYSTEM SEQUENCE OF OPERATION

Page 18: Fire protection system ax 272 f

PREACTION SYSTEM SEQUENCE OF OPERATION

Activation of smoke detector & operation

of a sprinkler causes following.

• Visual indications on the System Control Panel

• Audible alarm from bell & sounder cum flasher

• Deluge valve operates

• Water flows in to the system piping and discharges through the ‘opened’ sprinkler.

Page 19: Fire protection system ax 272 f

Manual Operation

• System can be operated manually by operating the Pull Station (Electric or Hydraulic)

• Visual indications on the System Control Panel

• Audible alarm from bell & sounder cum flasher

• Deluge valve operates

• Water flows in to the system piping (if sprinkler is not activated, piping will be filled with water)

PREACTION SYSTEM SEQUENCE OF OPERATION

Page 20: Fire protection system ax 272 f

Operation of Air Compressor

Air compressor maintains constant air pressure

in the system piping.

PREACTION SYSTEM SEQUENCE OF OPERATION