Who to decide on the nos. of wet riser main/Dry riser system to be installed ?

• Architect

Where to locate the wet/dry riser ?

• To be decided by Architect

Page 3: Dry & Wet Riser Systems

Design Criteria

Numbers of rising mains depend on :

• Each rising main serves not more than 930m2 of floor area

• Cover a distance of 38m from a landing valve

Page 4: Dry & Wet Riser Systems

The riser and landing valves shall be housed in:

• A protected area or lobby or shaft

Page 5: Dry & Wet Riser Systems

Where to locate the breeching inlet

Design Criteria

Breeching inlet shall be less than 18m from the fire engine hard standing

Conspicuous position and accessible to the fireman

Page 6: Dry & Wet Riser Systems

TYPE OF THE SYSTEMTYPE OF THE SYSTEM

LANDING LANDING VALVEVALVE

Dry Riser SystemDry Riser System

BREECHING INLETBREECHING INLET

AIR AIR RELEASEDVALVERELEASEDVALVE

Page 7: Dry & Wet Riser Systems

Requirement of dry riser installation

• For residential building height more than 45m but less than 60m, or with basement or commercial building

• Ø100mm dry riser main pipe is for building height from 10m to 45m

• Ø150mm dry riser main pipe is for building height from 45m to 60m

Page 8: Dry & Wet Riser Systems

Requirement of dry riser installation

•2- way breeching inlet for Ø100mm rising main

•4- way breeching inlet for Ø 150mm rising main

Page 9: Dry & Wet Riser Systems

Breeching Inlet

Page 10: Dry & Wet Riser Systems
Page 11: Dry & Wet Riser Systems

Air Release valve

Hand Wheel

Landing Valve

Anti-Thief Device

Page 12: Dry & Wet Riser Systems

FSSB SUBMISSION IS NOT REQUIRED FSSB SUBMISSION IS NOT REQUIRED

LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION

Submission

Page 13: Dry & Wet Riser Systems
Page 14: Dry & Wet Riser Systems
Page 15: Dry & Wet Riser Systems

ConventionalConventional

PUMP FEED

GRAVITY FEED

TRANSFER PUMP

WET RISER PUMPS

JOCKEY PUMP

FROM PUB SUPPLY

4 WAY BREECHING INLET

LANDING VALVE

Page 16: Dry & Wet Riser Systems

Old designOld design

• Non conventional - phase out

FROM PUB SUPPLY

AIR RELEASE VALVE

LANDING VALVE

DOMESTIC FEED

Tanks

WET RISER PUMP

4 WAY BREECHING INLET WET RISER TANK

Page 17: Dry & Wet Riser Systems

Down Comer System Down Comer System

DOMESTIC

21 ST STOREY

25TH STOREY

BREECHING INLET

Ø100mm GI PIPE

1ST STOREY

Between 60m to 70 m

WET RISER

Phase out for New Building (17 Sep’01)

Page 18: Dry & Wet Riser Systems

Transfer Water Tank Design

• One rising main = 11.5 m3 (15min) @ 27 l/s

• Two rising main = 23 m3 (15min) @ 38 l/s

Page 19: Dry & Wet Riser Systems

Roof top wet riser tank layoutRoof top wet riser tank layout

DIA 3.621m 1m

2m

3m length for pump set

1mRing tanks

3-Rings Tank

3 nos. = 49 m3

5 nos. =75 m3

ACOUSTIC SOUND INSULATION

3

1

12m

7m

4-Rings Tank

2 nos. = 49 m3

3 nos. =75 m3

Page 20: Dry & Wet Riser Systems

Wet riser tank capacity

• One rising main capacity = 49 m3 for half hours + 1.1 m3 fire hose reel

• Two rising main capacity=74 m3 for half hours +1.1 m3 fire hose reel

Page 21: Dry & Wet Riser Systems

Building Above 120mBuilding Above 120m

FROM PUB SUPPLY

1ST STOREY

Mid-Storey

Roof Storey

WET RISER PUMPHOSEREEL PUMPTRANSFER PUMP

Down feed

Down feed

Transfer tanks

Page 22: Dry & Wet Riser Systems

Power required

• PUB supply• Generator - supply to 4 blocks per generator

Page 23: Dry & Wet Riser Systems

FSSB SUBMISSION IS REQUIRED FSSB SUBMISSION IS REQUIRED

LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION

Submission

Page 24: Dry & Wet Riser Systems
Page 25: Dry & Wet Riser Systems

50TH STOREY HEIGHT BUILDING50TH STOREY HEIGHT BUILDING

Page 26: Dry & Wet Riser Systems

WET RISER AND HOSEREEL SERVICE WET RISER AND HOSEREEL SERVICE DUCTDUCT

Page 27: Dry & Wet Riser Systems

TESTING AND TESTING AND

COMMISSIONING OF WET COMMISSIONING OF WET

RISERRISER

Page 28: Dry & Wet Riser Systems

WET RISER REQUIREMENTSWET RISER REQUIREMENTS

RESIDENTIAL COMMERCIAL & ANY MIXED BUILDING FLOW RATE 27L/S FOR FIRST 38L/S FOR THE FIRST RISING MAIN RISING MAIN 19L/S FOR EACH ADDITIONAL 13.5L/S FOR EACH RISING MAIN ADDITIONAL RISING MAIN MAXIMUM SUPPLY RATE OF 190L/S MAXIMUM SUPPLY RATE OF 135 L/S

RUNNING PRESSURE 3.5BAR TO 5.5 BAR 3.5 BAR TO 5.5 BAR

STATIC PRESSURE 8 BAR 8 BAR

Page 29: Dry & Wet Riser Systems

PLAN VIEW FOR WET RISER AND PLAN VIEW FOR WET RISER AND HOSE REELHOSE REEL

Page 30: Dry & Wet Riser Systems

Check Valve

Gate Valve

Drain Cock

Page 31: Dry & Wet Riser Systems

Check Valve

Rubber Expansion Joint

Gate Valve c/w

limit switch

Page 32: Dry & Wet Riser Systems

Pilot Valve

Page 33: Dry & Wet Riser Systems

Motorize Valve

Pressure Relief Valve

Bypass system

Page 34: Dry & Wet Riser Systems

Flow Meter

Page 35: Dry & Wet Riser Systems

Motorize Valve

Gate Valve

Down feed

Page 36: Dry & Wet Riser Systems

Pilot Valve

Page 37: Dry & Wet Riser Systems

Check Valve

Flow Switch

Down feed Pipe

Page 38: Dry & Wet Riser Systems

Duty Pump

Standby Pump

Page 39: Dry & Wet Riser Systems

Fire Pump

Page 40: Dry & Wet Riser Systems

Jockey Pump

Page 41: Dry & Wet Riser Systems

Level Indicator

Page 42: Dry & Wet Riser Systems

Landing ValveStrap Lock

Page 43: Dry & Wet Riser Systems

Air Release

valve

Page 44: Dry & Wet Riser Systems

Drain Cock

Limit Switch

Butterfly valve

Page 45: Dry & Wet Riser Systems

Check Valve

Page 46: Dry & Wet Riser Systems

Piping

Page 47: Dry & Wet Riser Systems

Pressure Switches

Pressure Gauge

Page 48: Dry & Wet Riser Systems
Page 49: Dry & Wet Riser Systems

Limit Switch Indicator Panel

Alarm Bell

Fire Extinguisher

Page 50: Dry & Wet Riser Systems

Wet Riser Control Panel