25
Product Overview

Abtech - Hazardous Area Solutions

Embed Size (px)

Citation preview

Product Overview

Hazardous & Industrial Enclosures

ATEX & IECEx Compliant

BPG Enclosures• GRP enclosure in standard (Grey)

or Carbon loaded (black anti-static)

• IP66/67 to IEC/EN 60529• DTS01 (Shell/ERA deluge test)• Ambient temp range:

– -65 to +130°C (Hazardous)– -70 to +130°C (Non-Hazardous)

• Holes can be drilled on any side including rear face

• High impact strength: IK09 (10 Joules)

• Fire rated• Various accessories available:

– Mounting feet– Security screws

BPGA Range

• Pre-assembled GRP range (BPG6 & BPG8 sizes)• Complete with terminals and entries (2 x Side A & C)• Dual labelled ATEX & IECEx

SX Enclosures• 316L Stainless Steel • IP66/67 to IEC/EN 60529• DTS01 (Shell/ERA deluge test)• Ambient temp range:

– -50 to +175°C (Hazardous)– -60 to +200°C (Non-Hazardous)

• High impact strength: IK10 (20 Joules)• Holes can be drilled on any side

including rear face• Custom sizes available

– Ex certified up to 2m x 2m x 2m• Windows can be added to enclosure

door• ATEX certified Ex de sockets can be

fitted to enclosure• Fire rated

Fire Rated Enclosures – SX & BPGIEC331 Fire Test• 750°C for 3 hours followed by visual inspection• Then 5kV insulation resistance test

BS6387 Fire Test - 3 separate tests1. Fire alone: Category C

• Flame at 950°C for 3 hours, cables powered2. Fire with Water: Category W

• Flame at 650°C for 15 minutes then flame and water spray for 15 minutes

3. Fire with Mechanical shock: Category Z• Flame at 950°C with mechanical shock applied at 15s

intervals for 15minutes

• Note: All fire rated enclosures must be fitted with ceramic terminals

ZAG Enclosures• Marine grade Aluminium• Can be painted to customer

specification• IP66/67 to IEC/EN 60529• Holes can be fitted to any side

including rear face• Available as Apparatus and

Component certified enclosures• Large number of terminal types

to choose from• Use Power dissipation method for

calculating terminal population

SSD Enclosure• Stainless Steel Ex d Enclosure• Used for containing transformers,

circuit breakers, motor controls, PLC’s etc

• ATEX & IECEx IIB or IIB+H2 certified• Ambient range -20°C to +55°C• Can be fitted with pushbuttons,

selector switches & windows• Custom sizes available:

– Almost any size dictated by surface area: from 560cm² to 18000cm²

• Maximum voltage 660V ac 120V dc

Nautilus IP68• Stainless Steel 316 Ex e Enclosures• Terminal boxes only - based on the

same permitted terminal lists as the SX, BPG and ZAG range

• ATEX & IECEx Ex e, Ex ia or Ex ib certified

• Certified IP68 to EN60529• 100m for 5 days • 50m for 14 days

• T5 rated with an ambient temperature range of -50ºC to +55ºC

• Hinged cover with handle and lifting eye straps fitted as standard

• Optional mild steel or stainless steel mounting plates available

Hazardous High Voltage Enclosures

High Voltage Enclosures• Ex certified HV range based

on SX enclosure• From 3.3kV up to 45kV and

3.2kA• Suitable for -50°C• Typical applications:

– Umbilical connection– Down hole pumps– Water injection pumps– Fire suppression systems– Temporary power supply

connections

HVJB 125• A unique solution for the

termination of offshore umbilical cables or onshore distribution systems.

• The power conductor compartment houses the HV cables. A separate control compartment is used for terminating fibre optic or control cables.

• Ex e or Ex e op is

• Other ratings same as HVJB series

Hazardous Area & Marine Lighting

Hazardous and Marine Lighting

Hazardous & Marine Lighting

• Zone 1, Zone 2 and Safe Area luminaires for harsh environments

• LED, Fluorescent and HID lamp options• Designed for simple installation and low

maintenance• Low Glare (patent pending) LED technology• Dark sky asymmetric floodlight design reduces

light pollution and glare

Nimbus• Panel luminaire supplied

with satellite power supply• Zone 1, Zone 2 & Safe Area• ATEX & IECEx compliant• Extremely thin profile

>12mm• Significant weight and

energy saving over traditional recessed fluorescent

• Excellent uniformity and colour rendering

• Dimmable option

Gamma LG• Zone 2, 21 & 22 • ATEX & IECEx compliant• Utilises patent pending light

guide technology for low glare solution

• Designed for lower mounting heights where visual discomfort glare is an issue

• Marine grade stainless steel construction

• Built in junction box for simple installation

APC Photocell• A zone 1 & 2 photocell for

the control of luminaires• On-load switching up to 10

& 16Amps.• Can be used as combined

photocell/junction box• Zone1, 2 and 22 areas • ATEX and IEC Ex certified• Ambient temperature

range: -40°C to +55°C• Ingress protection IP66/67

to IEC 529

Hazardous Area Controls

Control Station Range

PCS Range ABCS Range SXCS Range

Control Station Range

• PCS (Polycarbonate) – ATEX Compliant• ABCS (GRP) & SXCS (Stainless Steel) – ATEX &

IECEx Compliant• IP66 to IEC/EN 60529• Range of sizes and operator options available:

– Pushbuttons, e-stops, indicator lamps, illuminated pushbuttons, selector switches & ammeters

Hazardous Area Cable Glands and Connection Accessories

Cable Connection Solutions

Wide Range Available

• Non-armored single compression cable gland Ex d / Ex e

• SWA/Braid type double compression cable gland Ex d / Ex e

• Adaptors, Reducers & Stopping plugs for NPT or Metric thread types

• Accessories – locknuts, washers, earth tags, shrouds• All products manufactured in nickel plated brass• Stainless steel option available

For more information visit:www.abtech.eu