Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download
Convenient library of standard custom label terms
Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST™ silent or audible system test**
Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points
are available (see page 3 for details)**
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
Selectable for Simplex® SmartSync™ two-wire
horn/strobe control or synchronized strobe control**
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC
Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Two auxiliary relays
NACs, Relay outputs, and communications circuits are
power limited per NFPA 72® (AC input, battery circuits,
and City Circuit Module outputs are non-power limited)
UL listed to Standard UL 864, 9th Edition
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
model)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILENCED
AC
POWER
1ABC
2DEF
3
GHI
4JKL
5MNO
6
PQRS
7TUV
8WXYZ
9
0
MENU
PREVIOUS
NEXTENTER
FUNCTION
DISABLE
ENABLE
EXIT
CLEAR
CAUTION
DISCONNECT
BATTERY ANDA. C. POWER
BEFORESERVICING
4008-9101 Standard Control Panel
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILENCED
AC
POWER
1ABC
2DEF
3
GHI
4JKL
5MNO
6
PQRS
7TUV
8WXYZ
9
0
MENU
PREVIOUS
NEXTENTER
FUNCTION
DISABLE
ENABLE
EXIT
CLEAR
F i re A lar m A nn un cia to r
CAUTION
DISCONNECT
BATTERY ANDA. C. POWER
BEFORESERVICING
4008-9121 Control Panel with 24 LED Annunciator (required for ULC applications)
Description
For areas requiring up to 200 addressable input devices and up
to 4 NACs, the Simplex 4008 Series fire alarm control panels
provide flexible initiating circuit monitoring, extensive
programmable control capability, and LCD annunciated
circuit-specific 20 character custom labels.
* See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
** TrueAlarm analog smoke detection is protected by one or more of the following U.S.
Patents: 5,155,468; 5,173,683; 5,543,777. IDNet addressable communications are protected by U.S. Patent No. 4,796,025. IDNet duplicate device detection is protected under U.S. Patent No. 6,034,601. WALKTEST system test is protected under US Patent No. 4,725,818. SmartSync horn/strobe operation is protected under U.S. Patent No. 6,281,789. Two-wire synchronization circuit operation is protected by U.S. patent No. 5,559,492.
TrueAlarm® Addressable Fire Alarm Control Panels
UL, ULC Listed; FM, CSFM, Model 4008 Fire Alarm Control Panel for IDNet™ Addressable and MEA (NYC) Approved* Devices and TrueAlarm Addressable Smoke Detection
S4008-0001-3 7/2005
Standard Feature Details
Addressable operation is provided by an IDNet
signaling line circuit (SLC) capable of communicating to up
to 200 addressable devices (points). Addressable devices
include: TrueAlarm smoke detection, heat detection, and
duct detection; supervised addressable modules for single
and multiple contact monitoring, manual stations, isolation
modules, and a remote signal module (see list on page 4.)
(Please note that this panel provides a limited TrueAlarm
operation feature set. For larger applications that require the
full complement of TrueAlarm features, contact your local
Simplex product supplier.)
Two, 2 A On-Board NACs provide conventional reverse
polarity operation, selectable as Class A or Class B, with
electronic control and overcurrent protection. Operation is
selectable for synchronized strobe or SmartSync™
horn/strobe two wire operation. Horn control can be
selected at the panel for: Temporal pattern coding, Steady
On, Slow March Time (20 beats per minute), or Fast March
Time (120 beats per minute). Note: When selected for
SmartSync horn/strobe control, March Time produces 60
beats per minute.
The 24 VDC Auxiliary output provides up to 500 mA
for system use. (Auxiliary output current is counted for
total power supply capacity.)
Standard Auxiliary Relay Outputs. Two relay
outputs are available, selectable as normally open or
normally closed, rated 2 A @ 30 VDC per below:
Aux Relay 1 is normally assigned to General Alarm
operation but is programmable (see page 7)
Aux Relay 2 (Trouble) is energized when Normal and is
de-energized with a Trouble condition.
Standard Feature Details (Continued)
On-Board Dual Line DACT. Operation can be selected for Contact ID, SIA, 3/1, 4/2, and BFSK formats.Reporting includes Alarm, Supervisory, Trouble, and AC Failure. Operation includes automatic 24 hour test and programmable power fail report delay.
Power Supply and Battery Charger. DC power output is 3 A @ 24 VDC for panel use. The temperature compensated battery charger (sealed lead-acid batteries only) is rated for up to 25 Ah batteries per UL 864 and up to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in the cabinet, larger batteries require an external cabinet.) Panel electronics can measure and display voltage and current for the power supply, batteries and the battery charger (standard and expansion power supply). Depleted battery trouble is monitored and annunciated and depleted battery cutout can be selected. Active battery status monitor supervises charger operation.
Optional Feature Details
Expansion Power Supply. Provides 3 A total @ 24 VDC, two additional 2 A NACs, and an additional auxiliary power output of 500 mA. Output operation is the same as on the standard power supply.
Expansion Relay Module. Provides three relays, one each for Alarm, Supervisory, and Trouble conditions. Each is jumper selectable as N.O. or N.C. Contacts are rated 2 A @ 30 VDC. Location is the same as for the City Circuit Modules.
City Circuit Modules. These modules are available with or without on-board disconnect switches, depending on local requirements (either type can be disconnected through the front panel under password control). Connections are for Remote Station (reverse polarity) or Municipal Master (local energy). Reporting includes Alarm, Supervisory, and Trouble.
2 S4008-0001-3 7/2005
Control Panel
Model Description Listings Box Depth Standard Features
4008-9101 Standard fire alarm control panel MEA4-1/4”
(108 mm)
4008-9121 Fire alarm control panel with 24 LED Annunciator on front door
UL, FM, & CSFM
ULC4-5/8”
(117 mm)
Red cabinet; SLC with 200 addressable points, 2 Class B/Class A NACs, 3 A power supply with battery charger; on-board DACT; for input voltage of 120/240 VAC, 50/60 Hz (autoselect)
Option Modules
Model Description
4008-9801 Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz Select one if required
4008-9802 Expansion Relay Module; 3 relays selectable as either N.O. or N. C.
4006-9805* City Circuit Modules with disconnect switch
4006-9806* City Circuit Modules without disconnect switch
Select one if required
* These City Circuit modules are also used on the 4006 Series control panels.
Accessories
Model Description
2975-9812 Red Semi-Flush Trim; 1-7/16” wide (37 mm)
4009-9801 Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet; dimensions = 16-1/4” W x 13-1/2” H x 5-3/4” D (413 mm x 343 mm x 146 mm) [depth increased for 25 Ah effective 7/2005]
Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two)
Model Size Model Size Location Model Size Location
2081-9272 6.2 Ah 2081-9288 12.7 Ah 2081-9275 18 Ah
2081-9274 10 Ah For cabinet mount
2081-9827 25 Ah
Requires 4009-9801 External Battery Cabinet (UL listed only)
Product Selection
TrueAlarm Smoke Detection
TrueAlarm Addressable Detection. IDNet addressable device compatibility includes Simplex TrueAlarm photoelectric smoke and temperature sensors. The 4008 fire alarm control panel provides a subset of the complete analog TrueAlarm features. TrueAlarm sensors appear to the panel essentially as addressable detectors and that term is used for 4008 documentation.
Approximately every four seconds the addressable smoke detectors transmit an output value based on their smoke chamber condition. The panel CPU internally maintains a current value, peak value, and an average value for each detector’s output. Status is determined by comparing the current value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
Alarm Determination. Photoelectric detection sensitivity is 2.5%/ft obscuration. All detectors can be selected for a reduced sensitivity detection mode that satisfies the city of Boston requirements. Addressable heat detectors provide a fixed temperature alarm at 135° F (57° C) and may be individually selected to also provide rate-of-rise alarm of 15° F (8.3° C) per minute where applicable.
Diagnostics and Default Device Type
Status Monitoring. 4008 TrueAlarm operation provides the ability to automatically indicate when an addressable detector is dirty or excessively dirty. The NFPA 72 (National Fire Alarm Code) requirement for a test of the sensitivity range of the detectors is fulfilled by the TrueAlarm ability to maintain the sensitivity level of each addressable detector.
Modular Addressable Detector/Base Combination.Modular TrueAlarm addressable detectors use the same base which allows different detector head types (photoelectric smoke, or heat) to be easily interchanged to meet specific application requirements. This feature also allows intentional detector (sensor head) substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke detectors (causing them to be disabled), heat detector heads may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect detector type, the heat detector will operate at a default setting to provide heat detection for building protection at that location.
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILENCED
AC
POWER
1ABC
2DEF
3
GHI
4JKL
5MNO
6
PQRS
7TUV
8WXYZ
9
0
MENU
PREVIOUS
NEXTENTER
FUNCTION
DISABLE
ENABLE
EXIT
CLEAR
FIVE STATUS INDICATOR LEDs provide system status indications in
addition to LCD information, LEDs flash to indicate the condition and
then when acknowledged, remain on until reset
2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal
operating conditions, provides up to 20 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first
alarm until acknowledged
THREE PROGRAMMABLE LEDs
provide custom labeling (labels insert into
a pocket), the top two LEDs are
selectable as red or yellow, the bottom
LED is selectable as green or yellow
CONTROL
PANEL VIEW
with door closed
ALARM SILENCE causes audible notification appliances
to be silenced, used after evacuation is complete and
while alarm source is being investigated
SYSTEM RESET restores
control panel to normal when
all alarmed inputs are
returned to normal
ALARM ACK acknowledges a Fire
Alarm condition, logs the
acknowledge, silences the operator
panel and all annunciator tone-alerts,
and steps through the active Alarm list
SUPV ACK acknowledges system
supervisory conditions, logs the
acknowledge, silences the operator
panel and all annunciator tone-alerts,
and steps through the active
Supervisory list TROUBLE ACK acknowledges
system troubles, logs the
acknowledge, silences the
operator panel and all annunciator
tone-alerts, and steps through the
active Trouble list
FIVE NAVIGATION KEYS: MENU selects
the on-screen programming menu; left
and right arrows moves the position on the
screen, and PREVIOUS and NEXT
navigate screen selections
ALPHANUMERIC
KEYPAD provides
programming entry of
numbers and letters
FOUR EXTENDED FUNCTION KEYS: ENTER confirms
selections, EXIT/CLEAR backs out of the present screen menu
and clears information that has not been entered, FUNCTION
enables the active function menu, DISABLE/ENABLE toggles
the function or circuit status as appropriate per the selected
screen
3 S4008-0001-3 7/2005
Keyboard Reference
The 4008 supports up to four annunciator options
including:
Door Mounted 24 LED Annunciator
4610-9111 Remote LED/Switch Annunciators
4606-9101 Remote LCD Annunciators
Annunciators communicate at a rate of 9600 baud with
power supplied by separate wiring.
4610-9111 LED Annunciator Features:
16 LEDs with programmable functions and dedicated
LEDs for Alarm Silenced, Lost Communications,
Trouble, and Power-on
Keyswitch access controlled switches for
Acknowledge, Alarm Silence, Reset, and Lamp Test
Local tone-alert
4610-9111 LED/Switch Annunciator
4606-9101 LCD Annunciator Features:
LCD readout with two lines of 40 characters each and
LED backlighting
Wide viewing angle, super-twist design
Keyswitch access controlled
Control switches and status LEDs for:
Alarm, supervisory, or trouble acknowledge
Alarm silence and System Reset
Three programmable LED indicators:
Two LEDs are selectable as red or yellow
One LED is selectable as green or yellow
With provisions for custom labeling
4606-9101 LCD Annunciator
4 S4008-0001-3 7/2005
Detector Heads and Addressable Bases (refer to page 3 for 4008 detector/sensor terminology)
Model Detector Head Type Compatible Addressable Base Data Sheet
4098-9792, Standard detector base
4098-9789, Base for remote LED or relay
4098-9791, Features of 4098-9789 and remote supervised relay
S4098-0019
4098-9794, Sounder base S4098-0028
4098-9714
4098-9733
Photoelectric
Heat, 135° F (57° C)
4098-9793, IDNet Isolator base S4098-0025
4098-9795, Dual address sounder base 4098-9754 Photo and Heat
4098-9796, Dual address standard base
NOTE: These bases require two addresses
S4098-0033
Duct Detection
Model Description Data Sheet
4098-9755 Addressable Duct Detector Housing with 4098-9714 detector, no relay control
4098-9756 Addressable Duct Detector Housing with 4098-9714 detector, with remote relay control S4098-0030
Addressable Devices
Model and Description Data Sheet Model and Description Data Sheet Model and Description Data Sheet
4090-9001 Supervised IAM 4090-9101 CL B ZAM 4090-9007 Signal IAM S4090-0010
4090-9051 Supervised IAM S4090-0001
4090-9106 CL A ZAMS4090-0003
4090-9002 Relay IAM S4090-0002 4090-9116 IDNet Isolator S4090-0005
4099-9001, 4099-9002, & 4099-9003 Manual
Stations
S4099-0001
Compatible System Expansion Panels
Model Type Description Data Sheet
4003 Series Voice Control Panel Provides a remote voice control panel with on-board NACs, internal microphone, and remote microphone input
S4003-0001
4009 Series Remote NAC Extender Provides remote NACs; includes power supply and battery charger; 4 extenders max/NAC; 4008 uses NAC output to provide control
S4009-0002
Note: Contact your local Simplex Product Supplier for additional compatible peripherals.
F i r e A l a rm A n n u n c ia t or
ACK
RESET
ALARM
SILENCE
LAMP
TEST
ALARM
SILENCED
LOST COM
TROUBLE
POWER
CONTROL
ENABLE
CONTROLENABLE
SYSTEM
RESET
ON
ALARM
SILENCE
ALARMSILENCED
TROUBLE
ACK
SYSTEMTROUBLE
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARMPOWER
Compatible Simplex Peripherals (see specifications on page 5 for notification appliances)
Remote Annunciator Options
5 S4008-0001-3 7/2005
Input Voltage 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
Input Current, Standard 2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input AC Input Input Current with
Expansion Power Supply 4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input
Power Supply Output 3 A maximum @ 24 VDC in alarm
Battery Charger Temperature compensated charger is rated for up to 25 Ah per UL 864; up to 12.7 Ah per ULC-S527
Notification Appliance Circuits (NACs) (NOTE: Total DC current = 3 A maximum per power supply)
General Rating 2 A maximum @ 24 VDC, per NAC; available as Class A or Class B; Class B end-of-line resistor = 10 k , 1/2 W; Model 4081-9008 (P/N 733-894)
Simplex 4901 Series (horns) and the following 4906 Series Multi-Candela: strobes, horn/strobes, and speaker/strobes (see data sheets S4906-0001, S4906-0002, & S4906-0003 )
Special Application Rating = 2 A per NACStrobe synchronization is UL listed across all four system NACs for these 4906 Series appliances 4906-9101
4906-9102 4906-91034906-9104
4906-91274906-9128
4906-9129 4906-9130
4906-91514906-9153
4906-9154
Regulated 24 VDC Rating = 1.5 A per NAC
NOTE: Maximum strobe load on main power supply or expansion power supply is 1.35 Aper power supply (2.7 A total); remainder of power supply rating is available for other loading
All other UL Listed Notification Appliances; use associated external synchronization modules where required
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum per power supply)
Auxiliary Power Output 500 mA maximum @ 24 VDC
Relay 1 Programmable operation Standard Auxiliary Relay Outputs
Relay 2 Trouble operation
Contacts rated 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
Wiring Connections Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm
2 )
IDNet Communications
Quantity Up to 200 addressable devices (see list on page 4)
Suppression For wiring external to building, use Overvoltage Protector 2081-9044 at each end of the connection; refer to data sheet S2081-0016 for details
Wire Size 18 AWG (0.82 mm2)
Unshielded twisted pair (UTP) Acceptable for most applications; not for use with wiring in conduit with either NAC or AC power wiring (or similar)
Wire Types
Shielded twisted pair (STP) Shielded wire may provide protection from unexpected sources of interference and may be required for some applications; review system with your local Simplex product supplier
Up to 4000 feet (1219 m) with 125 devices; 32 Distance from Control Panel to Farthest Device Up to 2500 feet (762 m) with 200 devices; 51
Total Wire Length Allowed With “T” Taps for Class B Wiring
Up to 10,000 ft (3 km)
Total Capacitance Allowed 0.6 µF (600 nF)
Annunciator Communications
Quantity Supported Up to four annunciator modules per panel (see page 4 for details)
Wiring Size and Type See description for IDNet wiring above
Bus-Style Wiring Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35 max. Wiring Distances
“T-Tap” Wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
Bus-Style Wiring Connect one at panel Line Matching Resistor
“T-Tap” Wiring Connect one at panel and one at end of line
100 , 1/2 W; 4081-9011; (part number 733-974)
Suppression Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building (refer to data sheet S2081-0016)
Option Module Ratings
Contact Ratings 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C. Expansion Relay Module 4008-9802 Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm
2 to 3.31 mm
2)
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Specifications (Refer to Installation Instructions 579-716 for additional information)
6 S4008-0001-3 7/2005
Model Module Supervisory Alarm
4008-9101 Standard fire alarm control panel with 50 IDNet devices
175 mA 200 mA
4008-9121 Control panel with 24 LED Annunciator 193 mA + 1 mA per IDNet device 250 mA+ 1 mA per IDNet device
4008-9801 Expansion Power Supply 50 mA 60 mA
4008-9802 Expansion Relay Module 10 mA per energized relay 10 mA per energized relay
4008-9805 City Circuit Module with disconnect switch 30 mA 60 mA
4008-9806 City Circuit Module without disconnect switch
30 mA 60 mA
4606-9101 Remote LCD Annunciator (see data sheet S4606-0001)
100 mA 150 mA
4610-9111Remote LED/Switch Annunciator (see data sheet S4610-0001)
40 mA70 mA
(all LEDs and tone-alert on)
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads.
Available Fire Detection Device Types
Device Description Options
Sounder base (selectable for single station operation)
With communications isolator Photoelectric Addressable Detector
TrueAlarm operation with sensitivity = 2.5%/ft
With relay output Selectable for all detectors to be at city of Boston sensitivity of 3.7%/ft
Sounder base (selectable for single station operation)
With communications isolator
Heat Detector Fixed temperature thermal detection at 135° F (57.2° C)
With relay output Individually selectable to add rate-of-rise heat detection of 15° F/minute (8.3° C/minute)
Addressable Hardware Point Types
Function Type Description Function Type Description
FIRE Fire monitor device WSO Combination waterflow and water supervisory device
WATER Waterflow monitor device SUPV Supervisory monitor
HEAT Heat detector device UTIL Supervised utility monitor
DUCT Duct detector device TROUBLE Trouble monitor
PULL Manual (pull) station device VSMOKE Verified fire alarm; an alarm level causes the alarm verification cycle to start
SMOKE Smoke detector device STYLEC Style C fire monitor
SO Sprinkler Supervisory LATSUPV Latching supervisory monitor (supervisory latches until system is reset)
Addressable Device Information
The following addressable device types and hardware point types are provided. A combination of autoprogram, and either
front panel or PC programming allows the operation to be selected per application.
Supervisory and Alarm Currents
7 S4008-0001-3 7/2005
Common Fire Alarm Operations
Function Type Relay Activates Upon Relay Deactivates Upon
SRELAY General Alarm Silence
RRELAY General Alarm Reset
SUPV Supervisory condition Clear
TRBL Trouble condition Acknowledged
Special Functions
Function Type Description
UTILITY Utility input in the same alarm group activates
PRIMARY General alarm; relay is tied to Primary Elevator Recall contacts
ALTERN General alarm; relay is tied to Alternate Elevator Recall contacts
DRESET Relay provides 24 VDC power to 4-wire addressable detectors; relay turns off for 5 seconds on System Reset
DHOLDER Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general alarm to remove power to door holder relay and close doors
Function Details
Custom labels Up to 20 characters per point; a built-in message library provides for commonly used words for easy front panel programming
For front panel label creation convenience, the following words can be selected as part of a custom label ( _designates a built-in space; typing the first letter of a word/number will select the closest word in alphabetical/numerical sequence)
Message Library North SouthEastWestFront
Centerrear5thFlr_1Flr_2
Flr_3Flr_4Flr_5RM_
Basement FloorGarageHallway HVAC_Room Kitchen
Lobby Office Patientupperlower
main first 2nd3rd4th
Boiler_RM Classroom Closet_ Corridor Elect_RM
Elevator EntranceRestroomRoomStairway
StoreroomWingZone
History logs Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232 service port
Autoprogram
Automatically scans system for installed option modules and configures panel programming accordingly; modes are available to detect new modules only, recreate default programming and then add all modules found; Scans of addressable loop adds addressable devices, displays total added; checks for duplicate addresses and identifies errors
Alarm Groups Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay operation to be associated with inputs according to local response requirements
WALKTEST Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm zone is sounded out by associated audible notification or the response is silently logged into the Alarm log
Manual Control Allows selection of individual relays or NACs for system testing
Passcode Protection
(4-digit number)
Level 1 = Acknowledge, Silence, System Reset, View logs, View point information, and Lamp Test
Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points
Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST
Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level
Relay Operation Modes
The following relay operations are selectable from either the front panel or the PC programmer.
Additional Programming Feature Details
Tyco, Simplex, the Simplex logo, TrueAlarm, IDNet, WALKTEST, and SmartSync are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other
countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4008-0001-3 7/2005
www.tycosafetyproducts-usa-wm.com
© 2005 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
* Indicates optional modules
11-1/4" (286 mm)
13-1/2"
(343 mm)
13-1/4" (337 mm)
Battery Area
No conduit or wiring in this area
AC Input TerminalsCity Module*
or Expansion
Relay Module*
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIREALARM
SYSTEMSUPERVISORY
SYSTEMTROUBLE
ALARMSILENCED
ACPOWER
1ABC
2DEF
3
GHI
4JKL
5MNO
6
PQRS
7TUV
8WXYZ
9
0
MENU
PREVIOUS
NEXTENTER
FUNCTION
DISABLE
ENABLE
EXIT
CLEAR
Main board
Main board
Expansion
Power Supply*
Display
Assembly
Box depth =
4-1/4" (108 mm) standard
4-5/8" (117 mm) w/annunciator door
16"
(406 mm)
Door thickness
5/8" (16 mm)
NOTE: For semi-flush mounting, cabinet
must extend 1-1/2" (38 mm)
minimum from wall surface
Box width 15-5/8" (397 mm)
(Top and side views are
shown with door installed)Knockouts are
located on top
and sides
F i r e A l a r m An n un c i a t o r
RED LEDYELLOW LED
NAC 1
NAC 2
NAC 3
NAC 4
FOUR YELLOW LEDs provide default NAC
Trouble annunciation (shown labeled as NAC 1-4)
14 CUSTOM LABEL AREAS are
available, typically for location
identification and NAC
annunciation (shown labeled for
reference, blank labels are
provided); dual LED locations have
a Red LED (top) and a Yellow LED
(bottom); labels insert into pockets
behind the overlay; LED operation
is programmable to track other
monitored status conditions
AREA 1
AREA 2
AREA 3
AREA 4
AREA 5
AREA 6
AREA 7
AREA 8
AREA 9
AREA 10
Installation and Module Placement Reference
Door LED Annunciator Details
Features
Standard features include:
Up to 250 addressable TrueAlarm sensor or addressable device points using IDNet communications that operate with either shielded or unshielded twisted pair wiring**
Four, 2 A notification appliance circuits (NACs) with solid state current protection
Internal event reporting DACT module (standard on models 4010-9101, 4010-9102, & 4010-9150)
UL listed to Standard 864
Installation convenience features:
Power-limited design with electronic modules contained on one-piece chassis
Up-front terminal blocks for wiring access
Compact NEMA 1 rated cabinet is available in beige or red and can be pre-shipped for early installation
Setup, programming, and maintenance features:
Device level ground fault search, locate and isolate
Auto Program for general alarm operation
TrueAlarm individual analog sensing with front panel information and selection access
“Dirty” TrueAlarm sensor maintenance alerts, service and status reports including “almost dirty”
Default TrueAlarm sensor device type operation
Duplicate address error detection
Front panel or PC programming
TrueAlarm sensor peak value performance report
WALKTEST™ silent or audible system test†
Software verification simulation mode
Supports the following IDNet devices:
Addressable manual stations
Quad-state zone adapter modules (ZAMs) for initiating device monitoring
IDNet ground fault/short circuit isolator base for TrueAlarm sensors
Quad-state line powered individual addressable modules (IAMs) for initiating device monitoring and relay control
Available option modules include:
Door mounted 24 LED annunciator (std. on ULC models)
Network, or Point Reporting DACT
Class A NAC adapter module
RS-232 ports for printer and maintenance PC
Additional power supply; Auxiliary Relay Module or City Interface
Equipment for Suppression Release Applications (refer to data sheet S4010-0003)
Compatible with Simplex® auxiliary panels:
TrueAlert® Addressable Controllers and NAC power extenders (IDNet controlled and conventional)
4003 Voice Control Panel
4081 Battery Cabinet with charger for 50 Ah batteries
4010 Fire Alarm Control Panel (with standard door)
Description
TrueAlarm fire alarm control panels have the ability to provide location accuracy for monitoring and control. When equipped with TrueAlarm analog sensing for smoke and heat detection, the processing power of the control panel also has the ability to analyze conditions at each location to provide accurate detection with significantly reduced maintenance costs.
The 4010 TrueAlarm Fire Alarm Control Panel has been specifically designed to provide addressable operation and analog detection in a cost-effective package for application sizes that previously were considered only appropriate for conventional zoned monitoring.
Installation and Service Ease. The 4010 mounts on a single chassis for quick installation and removal. Terminal blocks are large and up-front for easy access and inspection. Optional modules are easily and quickly installed and programmed as required.
The 4010 cabinet provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting. Smooth cabinet surfaces are provided for locally cutting conduit entrance holes exactly where required. 4010 cabinets and electronics can be ordered separately, allowing early cabinet installation.
Ground Fault Assistance. Ground fault problems often occur during installation. The 4010 provides isolating circuitry and software-controlled sequencing to isolate ground faults to specific identified locations. This assistance helps the installer to accurately locate the wiring problem for quicker repair.
* Refer to page 6 for listing details. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7170-0026:226 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
** TrueAlarm analog smoke detection and IDNet addressable devices are protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777; 5,400,014; 5,552,765; 5,552,763; DES. 377,460.
† WALKTEST system test is protected under U.S. patent # 4,725,818.
TrueAlarm® Fire Alarm Controls
UL, ULC Listed; FM, CSFM, Model 4010 Fire Alarm Control Panel for TrueAlarmand MEA (NYC) Approved* Analog Sensors and IDNet™ Addressable Devices
S4010-0001-9 10/2004
4010 Operator Control Summary
Extensive Feature List. The 4010 Fire Alarm Control
Panel provides access to an extensive feature list that
includes:
Providing easy and powerful operator information with
a logical, menu-driven display
Extensive and automatic diagnostics for maintenance
reduction
History Logs available from the LCD or capable of
(optionally) being printed
Software Verification, allowing detailed logic
programming simulation to be conducted without
activating connected outputs
Control Panel (or service PC) label editing
Password access control
Auto Program Quick Configuration (Quick-CFIG) of
connected modules and IDNet devices for general alarm
operation to quickly get the system up and running
4010 Display Panel and Diagnostic Mode
Convenient Status Information. With the locking
door closed, a window allows viewing of the status
display. The 4010 status panel provides a two line by 40
character, super-twist LCD information display and eight
status LED indicators as shown in the illustration below.
From this display, the LED indicators will describe the
general category of activity being displayed with the LCD
providing more detail. For the authorized user, unlocking
the door will provide access to the control switches and
allow further inquiry by scrolling the display for
additional detail. (Refer to control panel functional
illustration below.)
WALKTEST Diagnostic Operation Mode. The
patented WALKTEST process allows a single person to
perform system test. The system records test inputs such
as intentional alarms or trouble and either logs the
response (silent WALKTEST operation) or outputs a
brief, recognizable audible notification signal (audible
WALKTEST operation).
2 S4010-0001-9 10/2004
SUPVAC
K
SYSTEM
SUPERVISORY
ALARMAC
K
FIREALAR
M
TROUBLEAC
K
SYSTEM
TROUBLE
ALAR
MSILENCE
ALAR
MSILENCED
SYSTEM
RESET
A
CPOWER
MENU FUNCTION ENTERDISABLE
ENABLE
EXIT
CLEARPREVIOUS NEXT
FIVE STATUS INDICATOR LEDs provide system status indications in
addition to LCD information, LEDs flash to indicate the condition and
then when acknowledged, remain on until reset
2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal
operating conditions, provides up to 40 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first
alarm until acknowledged
THREE PROGRAMMABLE LEDs
provide custom labeling (labels insert into
a pocket), the top two LEDs are
selectable as red or yellow, the bottom
LED is selectable as green or yellow
CONTROL
PANEL VIEW with
4010 door closed
ALARM ACK acknowledges a Fire Alarm condition,
logs the acknowledge and silences the operator
panel and all annunciator tone-alerts
SUPV ACK acknowledges system supervisory
conditions, logs the acknowledge, and silences the
operator panel and all annunciator tone-alerts
TROUBLE ACK acknowledges system troubles,
logs the acknowledge, and silences the operator
panel and all annunciator tone-alerts
ALARM SILENCE causes audible notification appliances
to be silenced, used after evacuation is complete and
while alarm source is being investigated
NINE EXTENDED FUNCTION KEYS (accessible with
door open) select and scroll through display prompts for
locating additional system information, performing
maintenance functions, or for front panel programming
SYSTEM RESET restores
control panel to normal when
all alarmed inputs are
returned to normal
Extended Operator Control Panel Functions
IDNet Addressable Interface
Overview. The 4010 provides IDNet addressable device communications. Using a two wire circuit, individual devices such as manual fire alarm stations, TrueAlarm sensors, and sprinkler waterflow switches can be directly connected (or interfaced) to the IDNet controller to communicate their identity and status. This addressability allows the location and condition of the connected device to be displayed on the 4010 panel LCD and on system annunciators. Additionally, control circuits (fans, dampers, etc.) may be individually controlled by using a relay IAM (individual addressable module). The 4009 IDNet NAC Extender or the TrueAlert Addressable controller can be controlled for local or remote notification appliance expansion. (Refer to individual device documentation for further details.)
Capacity. A total of 250 addressable monitor and control points may be intermixed on the same pair of wires. By using Zone Adaptor Modules (ZAMs) or Individual Addressable Modules (IAMs), conventional initiating devices can be connected to the IDNet circuit.
IDNet Addressable Operation. The IDNet controller continuously interrogates each addressable device on the communication channel for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuit for Class B (Style 4) operation.
Wiring Requirements. Refer to the specifications chart below. Distances are for shielded or unshielded wire. Shielded wire may provide protection from unexpected sources of interference and may be required for some applications.
Wiring Specifications
Size 18 AWG minimum
Preferred Shielded twisted pair (STP) Wire
Acceptable Unshielded twisted pair (UTP)
Farthest Distance from Control Panel to Device
Up to 2500 feet (762 m)
Total Wire Length Allowed With “T” Taps for Class B Wiring
Up to 10,000 ft (3 km).
TrueAlarm Analog Sensors
TrueAlarm System Operation. IDNet communications are used for TrueAlarm smoke and temperature sensors. Every four seconds, smoke sensors transmit an output value based on their smoke chamber condition. The 4010 CPU maintains a current value, peak value, and an average value of each sensor's output. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
Programmable Sensitivity. The sensitivity of each sensor can be field programmed at the 4010 Control Panel for different levels of smoke obscuration (in percent) or for specific heat detection levels. In order to evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read and compared to the alarm threshold directly in percent.
TrueAlarm Analog Sensors (Continued)
TrueAlarm heat sensors can be selected for rate-of-rise detection as either 15° F (8.3° C) or 20° F (11.1° C) per minute with an independent fixed limit of 135° F (57° C) or 155° F (68° C). TrueAlarm heat sensors can also be programmed as a utility device to monitor for temperature extremes in the range from 32° F to 155° F (0° C to 68° C). This feature can provide freeze warnings or alert to HVAC system problems.
ALARMFIRE
PULL DOWN
SIMPLEX TIM E RECORDER CO.
4090-9002RELAY IAM
INSTAL. INSTR. 574-184DATE CODE:
1
5
6
7
8
1
2
3
4
Addressable station
Monitor ZAMs and
Relay IAMs
Supervised IAM
Quick-Connect
TrueAlarm sensor
Modular TrueAlarm
sensor with base
Modular TrueAlarm sensor
with IDNet isolator base
To additional IDNet
devices, up to 250 total
POWERBEFORE
SERVIC ING
CAUTIOND ISCONNECT
4009 IDNet NAC EXTENDERTM
4009 IDNet NAC
Extender
TrueAlert Addressable Controller
POW ER
BEFORE SERVICING
CAUTIONDISCONNECT
TrueAlert Addressable ControllerTM
FIRE ALARM
CONTROL
DISCONNECTPOWER BEFORE
SERVICING
CAUTION
ZONE 1
ZONE 8
ZONE 2
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 3
ZONE 9
ZONE 16
ZONE 10
ZONE 12
ZONE 13
ZONE 14
ZONE 15
ZONE 11
ZONE 17
ZONE 24
ZONE 18
ZONE 20
ZONE 21
ZONE 22
ZONE 23
ZONE 19
** SYSTEM IS NORMAL **
12:02:15pm Mon 9-Sep-02
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
POWER
4010 Fire Alarm
Control Panel with
annunciator door
4010 Control Panel with Typical IDNet Devices
Diagnostics and Default Device Type
TrueAlarm operation gives the 4010 system the ability to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 (National Fire Alarm Code) requirement for a test of the sensitivity range of the sensors is fulfilled by the TrueAlarm ability to maintain the sensitivity level of each sensor.
Modular TrueAlarm sensors use the same base and different sensor types (photoelectric smoke sensor, or heat sensor) can be easily interchanged to meet specific location requirements. This feature also allows intentional sensor substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect sensor type, the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.
3 S4010-0001-9 10/2004
TrueAlarm Information Details
True Alarm sensor data can be displayed on the
system LCD, on a remote maintenance PC, or printed on a
remote printer. With the proper operator access, a
TrueAlarm Service Report can be generated to list the
specific details of each TrueAlarm device. This report, as
well as the Status Report can either be displayed on the
remote maintenance PC or captured permanently by using
a remote 80 character printer.
The report samples below illustrate the format provided
on either the remote maintenance PC or a printer. This
information is available at the system LCD by identifying
the specific point of interest and reading one point at a
time.
Model 4190-9013 is a UL Standard 864 listed 80 column,
24 pin dot matrix printer (refer to data sheet S4190-0011).
(Model 2190-9039, a 24 VDC, 40 column printer, is
compatible with the 4010 for event printing only. Refer to
data sheet S2190-0014.)
4010 Fire Alarm
Control Panel
Printer (Simplex
model 4190-9013)
Remote authorized maintenance
computer connected via dial-up
Service Modem Connection
FIRE ALARM
CONTROL
DISCONNECT
POWER BEFORE
SERVICING
CAUTION
** SYSTEM IS NORMAL **12:02:15pm Mon 8-Mar-99
SUPV
ACK
S YSTEMSUPE RVISORY
ALARMACK
FIRE
ALARM
TROUBLEACK
SYSTEMTROUBLE
ALARM
SILENCE
ALARMSILE NCED
SYSTEM
RESET
AC
POWER
Local
maintenance
computer
One connection type per 4010,
selected by module choice; max.
wiring distance is 300 ft (91 m)
@ 9600 baud
RS-232 Connection Options (refer to module selection on page 6)
4 S4010-0001-9 10/2004
Simplex 4010 Fire Alarm System Page 1
REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 18-Oct-04
Dev
Num Custom Label
Alarm
at:
Avg
val
Current/
% alarm
Peak/
% alarm
State
1 ANALOG PHOTO - CLEAN ROOM 0.5/ 83 67 68/ 1% 72/ 10% NOR
2 ANALOG ION - CLEAN ROOM 1.3/209 94 97/ 2% 101/ 1% NOR
3 ANALOG PHOTO - MAIN LOBBY 2.5/185 117 117/ 0% 125/ 42% NOR
4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/161 93 93/ 0% 93/ 0% NOR
10 HEAT DETECTOR - GARAGE 135F/253 –-- 63/-67F 66/ 69F NOR
11 ANALOG PHOTO - KITCHEN 3.7/216 116 116/ 1% 110/ 36% NOR
END OF REPORT
Typical TrueAlarm Service Report Information Printout and/or Maintenance PC Screen
Simplex 4010 Fire Alarm System Page 1
REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 18-Oct-04
Zone
Name Custom Label
Sensi-
tivity Device Status
Almost
Dirty
M1-1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL
M1-2 ANALOG ION CLEAN ROOM 1.3 % NORMAL
M1-3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES*
M1-4 ANALOG PHOTO CONFERENCE ROOM 1 2.5 % NORMAL
M1-10 HEAT DETECTOR GARAGE 135 F NORMAL
M1-11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES*
END OF REPORT
Typical TrueAlarm Status Report Information Printout and/or Maintenance PC Screen
TrueAlarm Status and Service Report Samples
Standard Panel Features
N2 Communications for Serial Annunciator Control.
Control for up to 6 remote Simplex Annunciator products including 24 Point I/O Module, and LCD Annunciator. Includes extensive troubleshooting diagnostics.
Access Port. RS-232 service port for connecting PC tools for service diagnostics and for programming the CPU Flash EPROM memory.
IDNet Addressable Communications Channel.
Addressable channel provides communications for up to 250 remote addressable devices, including TrueAlarm analog sensors and isolator bases (see descriptions on page 3).
Four NACs. Class B output is standard, rated for 2 A @ 24 VDC nominal, with solid state current protection. Class A operation is optional with the addition of an adapter module.
NAC operation can be selected for “on-until-Silence” or “on-until-Reset,” and can be Temporal pattern, 20 or 120 bpm March Time pattern, or continuous. Each NAC is also individually selectable to control Simplex synchronized visible notification appliances and to control audible notification appliances using SmartSync™ control, allowing separate audible and visible appliance operation using a common 2-wire circuit. (Class A , Style Z, SmartSync circuits require SmartSync Control Module 4905-9938, refer to data sheet S4903-0010 for details.)
Two Auxiliary Output Circuits. Operation is programmable for trouble, alarm, supervisory, or other fire response functions. Output is one Form “C” dry contact each, rated 2 A @ 24 VDC. An optional relay kit is available for switching up to 1/2 A at 120 VAC.
Power Supply. Standard output is 4 A @ 28 VDC, filtered, non-regulated. Internal system power is provided separately, allowing the 4 A to be available for NAC and auxiliary power tap functions. Over-current protection is solid state and self-resetting.
Auxiliary Power Tap. Provides up to 1/2 A of the standard power supply voltage, over-current protected.
Battery Charger. Capable of charging up to 25 Ah sealed lead-acid batteries (4010 cabinet mounted). A recharge time of 24 hours is typical with stable 120 VAC input. For applications requiring larger batteries, external charger/cabinet assemblies are available.
A depleted battery cutout feature is programmable to advise and/or to reduce current when battery voltage is low.
Optional Expansion Slot Modules
(The 4010 is available with a Simplex Network Interface. 4010 points can be declared “public.”)
Network Interface, Fixed Media. Available for wired applications.
Network Interface, Modular Media. Available for wired connections or fiber optic. Require separate media modules. May be both wired, both fiber optic, or one of each.
DACT, Point Reporting Module. Provides serial output information that can send location details to a remote receiving station.
Optional Expansion Slot Modules (Cont’d)
DACT, Event Reporting Module. For applications where simple event status information is required (Alarm, Trouble, Supervisory, and AC power failure).
Dual RS-232 Module. Available for interfacing to a printer and a maintenance PC.
Single RS-232 Module with Service Modem Connection.
Provides one port dedicated for connection to a printer, and a second port dedicated for dial-in from a service computer, typically located off-site. With an off-site computer, programming changes and system diagnostics can be performed remotely, reducing service time for repair or reprogram. Security is maintained by password protection.
Optional Chassis Mount Modules
Standard 4 A Expansion Module provides two taps of
2 A each, 28 VDC, filtered, non-regulated, similar to the
standard power supply capacity.
Suppression Release Power Supply provides two taps
of 2 A each, regulated at 24 VDC ± 10%. May also be
used for other applications requiring regulated voltage.
Use for suppression release requires a front panel
mounted release appliqué that is provided with this power
supply and also may be ordered separately.
Battery Meter Module provides panel mounted ammeter
and voltmeter for power supply monitoring.
Dual Circuit Class A NAC Adapter Module mounts on the
main 4010 printed circuit assembly and provides the
additional circuitry needed for Class A operation.
Dual Circuit City Connect Module provides the interface
required for direct wired reporting to conventional city
connection circuits. (Available with or without disconnect
switches.)
Expansion Power Distribution Module provides two
additional termination points for the 1/2 A auxiliary power
output, or for one tap of the expansion power supply.
Relay Option Module. Provides three relays, one each for Alarm, Supervisory, and Trouble. Relay contacts are selectable for normally open or normally closed and are rated 2 A @ 32 VDC maximum.
N2 Communications Modules
Up to six of the following modules may be connected to the Simplex N2 serial communications bus.
4606-9101 LCD Annunciators provide remote acknowledge, reset, and alphanumeric status display. (Refer to data sheet S4606-0001.)
24 LED Annunciator Doors are standard on ULC listed models and are available as door-only assemblies for electronics only packages or other aftermarket applications. This option uses the 24 Point I/O module with all points pre-assembled as LED outputs, with individual labels and each LED is selectable as red or yellow.
4605 Series 24 Point I/O Modules are available for remote mounting and provide 24 points that can be programmed as either general purpose switch inputs or system controlled outputs. Typical applications are for remote annunciators and monitoring and control of other related processes. (Refer to data sheet S4010-0002.)
5 S4010-0001-9 10/2004
6 S4010-0001-9 10/2004
Category Model Description Voltage Color
4010-9101 Beige
4010-9102 120 VAC
Red
4010-9201 Beige
4010-9202
UL Listed 4010 Fire Alarm Control Panel with: door, cabinet, power supply/battery charger, IDNet interface, 4 NACs, 2 auxiliary relays, and external N2 communications interface; 4010-9101 and 4010-9102 include internal common event reporting DACT 240 VAC
Red
4010-9101C English
4010-9101CF French
ULC Listed 4010 Fire Alarm Control Panel; same as above except: with 24 LED Annunciator door; and without DACT
120 VAC Beige
4010-9150 UL Listed
4010-9150C English
Control Panel Assembly(select one)
4010-9150CF
ULC Listed French
4010 Fire Alarm Control Panel electronics only,for pre-shipped cabinets, requires door and cabinet ordered separately; -9150 has event reporting DACT
120 VAC NA
Optional Expansion Slot Features (two slots are available, select modules as required)
Category Model Description
4010-9810 DACT Module (Common Event Reporting)
4010-9816 DACT Module (Point Reporting) Includes two, 7 ft (2.1 m) long RJ45 cables
4010-9821 Network Interface Module with fixed, wired connections
Reporting and Network Modules
(select one)
4010-9817 Network Interface Module, Modular; requires 2 (In/Out) media modules (see below)
4010-9811 Dual RS-232 Interface Module RS-232Communications
(select one) 4010-9812 Single RS-232 Interface Module with Service Modem connection
4010-9818 Network Wired Media Module Media Modules
4010-9819 Network Fiber Optic Media Module
Media modules mount on the 4010-9817 module without impact to slot allocation space.
Chassis Mounted Expansion Modules (select as required)
Category Model Description
4010-9813 120 VAC input
4010-9823 4 A Expansion Power Supply
240 VAC input
4010-9814(CF) 120 VAC input
Additional Power Supply
(select one)
4010-9824
Suppression Release Power Supply; 4 A @ 24 VDC, regulated ± 10%; includes front panel suppression appliqué; CF suffix selects French 240 VAC input
4010-9820 Battery Meter Module (ammeter and voltmeter) Optional Features
(select one) 4010-9825 24 VDC Expansion Power Distribution Module, provides two additional termination points for an expansion power supply tap or the auxiliary power output
4010-9806 Dual Circuit Class A (Style Z) NAC Adapter Module, two maximum
4010-9809 Dual Circuit City Connect Module
4010-9829* Dual Circuit City Connect Module w/o disconnect switches
Optional Features (select as indicated)
4010-9803 Relay Option Module
Select one maximum
Accessories
Category Model Description
4010-9826 120 VAC Auxiliary Relay Kit, allows one auxiliary relay to control up to 1/2 A @120 VAC, select as required; 2 maximum
4010-9830 (CAF)
Suppression Release Appliqué, required for suppression release applications; suffix CAF selects a French appliqué
2975-9801 Semi-flush trim, beige, 1-7/16” (37 mm) wide
Optional Features
2975-9802 Semi-flush trim, red, 1-7/16” (37 mm) wide
2081-9272 6.2 Ah Battery, 12 VDC
2081-9274 10.0 Ah Battery, 12 VDC
2081-9288 12.7 Ah Battery, 12 VDC
2081-9275 18 Ah Battery, 12 VDC; NOTE: This battery size will not allow bottom entry conduit
Batteries (required if
batteries are internal; select one size; two batteries
are required) 2081-9287 25 Ah Battery, 12 VDC
2975-9215 Red Cabinet Cabinets (select one if pre-shipped)
2975-9214(CF) Beige Cabinet; CF suffix has French labels
Dimensions: 22” H x 18” W x 5-3/8” D(559 mm x 457 mm x 137 mm)
4010-9858 Red Door with dress panel
4010-9857(CF) Beige Door with dress panel; CF has French labels
Dimensions: 22” H x 18” W x 5/8” D (559 mm x 457 mm x 16 mm)
4010-9860 (CAF)*
Beige Door with 24 LED Annunciator and dress panel; CAF suffix selects French for ULC applications
Doors (select one if pre-shipped or
for use with 4010-9150)
4010-9861* Red Door with 24 LED Annunciator and dress panel
Dimensions: 22” H x 18” W x 1-23/32”D (559 mm x 457 mm x 44 mm) [see also S4010-0002]
* As of document revision date: 4010-9829 is not ULC listed; 4010-9860 and 4010-9861 are listed by UL and ULC and approved by CSFM and FM; 4010-9860CAF is ULC listed and FM approved only.
4010 Fire Alarm Control Selection Chart and Module Location Rules (refer to diagrams on page 8)
7 S4010-0001-9 10/2004
Input Power Requirements Voltage Range Frequency Maximum Current
AC Input, 120 VAC base models 102 to 132 VAC 60 Hz 2 A
AC Input, 240 VAC base models 204 to 264 VAC 50/60 Hz 1 A
AC Input with 120 VAC expansion power supply 102 to 132 VAC 60 Hz 4 A
AC Input with 240 VAC expansion power supply 204 to 264 VAC 50/60 Hz 2 A
Environmental
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Output Ratings
Standard Power Supply Output 4 A total @ nominal 28 VDC
Auxiliary Power Tap 1/2 A maximum of standard power supply voltage
Expansion Power Supply Output * Additional 4 A @ nominal 28 VDC
Suppression Release Power Supply Output * Additional 4 A @ 24 VDC ±10%
Output switches to battery backup during mains failure or brownout conditions
* Each power supply provides two output taps of 2 A each.
Current Ratings for Optional Modules and Remote LCD Annunciator
Model Module Supervisory
CurrentAlarm
Current
4010-9810 DACT (Common Event Reporting) 40 mA 40 mA
4010-9816 DACT (Point Reporting) 40 mA 40 mA
4010-9821 Network, wired communications 125 mA 125 mA
4010-9817 Network Modular, add media cards separately 24 mA 24 mA
4010-9818 Network Wired Media 47 mA 47 mA
4010-9819 Network Fiber Optic Media 36 mA 36 mA
4010-9811 Dual RS-232 75 mA 75 mA
4010-9812 Single RS-232 with Service Modem 100 mA 100 mA
4010-9806 Dual Class A NAC Adapter 0 mA 0 mA
4010-9809 Dual Circuit City Connect 20 mA 36 mA
4010-9829 Dual Circuit City Connect w/o disconnect switches 20 mA 36 mA
4010-9803 Relay Option Module 10 mA 37 mA
4010-9860 4010-9861
& ULC 4010s 24 LED Annunciator door 60 mA
83 mA
(all LEDs on)
4606-9101 Remote LCD Annunciator (refer to data sheet S4606-0001) 65 mA 140 mA
System Current (supplied separate from power supply output)
Base System with: Supervisory
Current**Alarm
Current**
no IDNet devices 195 mA 295 mA
50 IDNet devices 230 mA 330 mA
100 IDNet devices 265 mA 365 mA
150 IDNet devices 300 mA 400 mA
200 IDNet devices 335 mA 435 mA
250 IDNet devices 370 mA 470 mA
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads.
4010 Operating Specifications
Tyco, Simplex, the Simplex logo, TrueAlarm, WALKTEST, IDNet, SmartSync, and TrueAlert are trademarks of Tyco International AG or its affiliates in the U.S. and/or other
countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
4010-9806
Class A
Module
4010-9806
Class A
Module
TB4TB3
P2TB1
NAC 1 NAC 2 NAC 3 NAC 4
SH
LD
SH
LD
EXT N2 IDNet
———— A +
A -
B +
B -
NC C NO
AUX2AUX1 BATTERYAUX
POWER
NC C NO
4010-9813,
4098-9814
4010-9823,
or 4010-9824
Expansion Power Supply
4010-9809
or -9829
City Module
or
4010 -9803
Relay Module
4010-9820
Meter Module
or
4010-9825
24 VDC Power
Distribution
Block
TB5 TB6 TB7 TB8
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARMSILENCE
ALARMSILENCED
SYSTEMRESET
AC
POWER
MENU FUNCTION ENTERDISABLE
ENABLE
EXIT
CLEARPREVIOUS NEXT
Expansion
Slots 1 & 2
—
——
Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4010-0001-9 10/2004
www.tycosafetyproducts-usa-wm.com
© 2004 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Typical conduit entry area
(cut holes as required)
Battery Area
No conduit entry or wiring in this area
18" (457 mm)
21"
(533 mm)
14-1/2" (368 mm)
W ATERFLO W -LEFT W ING
GRO UND FAULT
W ATERFLO W -
RIGHT W ING6839$&.
6<67( 0683( 59,62 5<
$/ $50$&.
) ,5($/ $50
� 752 8%/ ($&.
6<67( 07528%/ (
$/ $506,/ ( 1&(
$/ $506,/ ( 1&( '
6<67( 05( 6( 7
$&32 : ( 5
MENU FUNCTION ENTERDISABLE
ENABLE
EXIT
CLEARPREVIOUS NEXT
7%�7%�3�7%�
7%� 7%� 7%� 7%�
Shaded area is for non-power limited wiring
Knockout screw/nail holes
(for semi-flush mount)
Wall thickness guides for
5/8" (16 mm) wall board)
Wall thickness guides for
1/2" (13 mm) wall board
Annunciator Door,
1-23/32" (44 mm) thick
7-3/32"
(180 mm)
5-1/2"
(140 mm)
1-19/32"
(40 mm)
Door and exposed
cabinet dimension
for semi-flush mount
2-15/32" (63 mm)
Wall board position reference
for semi-flush mount
Internal straps are
provided for wiring
management
(2 each side)
Standard Door,
5/8" (16 mm) thick
6-1/4"
(159 mm)
3/4"
(19 mm)
Standard
door profile
Annunciator
door profile
4010 Module Layout Reference
Mounting Information
Features
Master Controller (top) bay:
Master controller assembly with operator interface and
4100 Software Revision 11.10
Enhanced CPU with dual configuration programs,
convenient service port access, and capacity for up to
2000 points
System power supply (SPS) and charger (9 A total) with
on-board: NACs, IDNet™ addressable device interface,
and programmable auxiliary output and alarm relay
Operator interface that is conveniently color coded with
raised switches providing high confidence feedback
Module level ground fault search locates and isolates
faults to assist installation and service
Available with redundant CPU (requires two bays)
Standard addressable interfaces include:
IDNet addressable device interface with 250 points
Remote annunciator module support via RUI (remote
unit interface) communications port
Optional modules include:
MAPNET II® or IDNet addressable interfaces that
support TrueAlarm® analog sensing operation and operate
with either shielded or unshielded twisted pair wiring**
Panel mounted SLC quad isolators and TrueAlert®
addressable notification appliance power supplies
DACT, City Connect, and Network interfaces
RS-232 ports for printers or maintenance terminals
Alarm relays, auxiliary relays, additional power
supplies, IDC modules, and NAC expansion modules
Service modems, VESDA® Air Aspiration Systems
interface, and coded manual station interface
LED/switch modules (refer to data sheet S4100-0032)
Audio amplifiers, firefighter master phones, and control
modules (refer to data sheet S4100-0034)
Compatible with Simplex® remotely located:
TrueAlert Addressable Controllers and both
Addressable and Conventional NAC Extenders
4003 Voice Control Panels and the BACpac®
BACnet® portal
Master controller upgrade kits are available for existing fire alarm control panels
4100U and upgrade kits are UL Listed to: UL Std. 864, Fire Detection and Control (UOJZ), and Smoke Control Service (UUKL)
UL Std. 2017, Process Management Equipment (QVAX)
UL Std. 1076, Proprietary Alarm Units-Burglar (APOU)
UL Std. 1730, Smoke Detector Monitor (UULH)
ULC Std. S527-99
** Simplex fire alarm technology is protected by the following U.S. Patent Numbers:
TrueAlarm analog smoke detection: 5,155,468; 5,173,683 and 5,543,777. IDNet and MAPNET II addressable communications; 4,796,025. TrueAlert addressable notification; 6,313,744 and 6,426,697. SmartSync horn/strobe control; 6,281,789.
Press ACK located under flash ing indicator.
Repeat operation unti l al l events are acknowledged.
Local tone wi ll silence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMS
Fire Alarm Prior ity 2 Alarm
SYSTEM WARNINGS
Supervisory Trouble Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building Signals
System indicator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress System Reset.
Press Ack to silence tone device.
ZONE
1SI G
2AUX
3
FB
4IO
5I DNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire AlarmAck
Priority 2Ack
SupvAck
TroubleAck
AlarmSilence
SystemReset
Event
Time
EnableOn
Arm
DisableOff
DisarmAuto
LampTest
More
Info
Menu
Previous
Next
SYSTEM IS NORMAL08:23:43 am MON 11-DEC-00
Fire Control
Press ACK located under flashing indicator.
Repeat operation unti l al l events are acknowledged.
Local tone wi ll si lence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMS
Fire Alarm Priority 2 Alarm
SYSTEM WARNINGS
Supervisory Trouble Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building Signals
System indicator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress S ystem Reset.
Press Ack to si lence tone device.
ZONE
1SIG
2AUX
3
F B
4IO
5IDNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire Alarm
Ack
P riority 2
Ack
S upv
Ack
Trouble
Ack
Alarm
Silence
System
Reset
Event
Time
EnableOn
Arm
DisableOff
DisarmAuto
Lamp
Test
More
Info
M enu
Previous
Next
SYSTEM IS NORMAL08:23:43 am MON 11-DEC-00
Fire Control
4100U Cabinets are Available with Two or Three Bays
Software Feature Summary
CPU provides two on-board configuration programs:
Two programs allow for reduced service programming time with one active program and one reserve
Downtime is reduced because the system stays running during download
PC based programmer features:
Convenient front panel access port for quick and easy download of site-specific programming
Modifications can be uploaded as well as downloaded for greater service flexibility
AND, firmware enhancements are made via software downloads to the EPROM – service personnel are not required to exchange board level components
Introduction
Building on the established success of the 4100 Series products, the 4100U Series offers additional operator, installation, and service features. These new features include both new hardware and new software designs that provide high performance and convenient operation, installation, and maintenance. (Additional features are found in documents referenced on page 7.)
Module Bay Description
4100U Control Panels provide point and module capacities that are suitable for a wide range of small to medium size applications. They accept a variety of interface modules and can be configured for either Stand-Alone or Networked fire control panel operation.
* See pages 5 and 6 for product that is UL or ULC listed. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251 (non-high rise) and 7170-0026:250 (high rise) for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
Fire Control Panels
UL, ULC Listed; FM, CSFM, Addressable Fire Detection and Controland MEA (NYC) Approved* Basic Panel Modules and Accessories
S4100-0031-9 4/2005
Module Bay Description (Continued)
The Master Controller Bay (top) includes a standard
multi-featured system power supply, the master controller
board, and operator interface equipment.
The Expansion Bays include a Power Distribution
Interface (PDI) for new 4” x 5” flat design option
modules and also accommodate 4100-style modules.
The Battery Compartment (bottom) accepts two
batteries, up to 50 Ah, to be mounted within the cabinet
without interfering with module space.
The following illustration identifies bay locations using a
three bay cabinet for reference.
PDI
4x5 Module
Expansion Power
Supply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
41
00 O
ptio
n
41
00 O
ptio
n
41
00 O
ptio
n
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
System Power
Supply
(SPS)
IDNetNACs 1, 2 & 3
Aux PwrAux
Relay
Btry
+-
Ma
ste
r C
ontr
olle
r
Bo
ard
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
Slot 1
Slot 2
Slot 4
Slot 3
PDI
4x5 Module
Expansion Power
Supply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
41
00 O
ptio
n
41
00 O
ptio
n
41
00 O
ptio
n
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
Master
Controller Bay
Expansion Bay 1
Battery Compartment
System power supplyMaster controller with
dual slot motherboard
Expansion Bay 2
Typical bays with
mixed module sizes
4100U Module Bay Reference
Mechanical Description
Optional modules are easily and quickly installed and
programmed
New design modules are mechanically secured in place
and then electrically plugged into the PDI module
reducing the need for wiring harnesses
Boxes can be close-nippled; each box provides
convenient stud markers for drywall thickness and
nail-hole knockouts for quicker mounting
Smooth box surfaces are provided for locally cutting
conduit entrance holes exactly where required
Mechanical Description (Continued)
The latching dress panel (retainer) assembly easily
lifts off for internal access
NACs are mounted directly on power supply
assemblies providing minimized wiring loss, compact
size, and readily accessible terminations
Packaging supports traditional 4100-style
motherboard with daughter cards
Modules are power-limited (except as noted, such as
relay modules)
The NEMA 1 box is ordered separately and available
for early installation
Boxes, doors, and dress panels are available in beige
or red (ordered separately)
Doors are available with tempered glass inserts or
solid, in beige or red
Refer to document S4100-0037 for enclosure details
Operator Interface Detail Reference
The following illustration identifies the primary functions
of the operator interface.
Press ACK located under flashing indicator.
Repeat operation until all events are acknowledged.
Local tone will silence.
A B C
AC Power
D E FG H
I
J K L M N O P Q R
'SP' ( ), 0
:
S T UV W
X
Y Z
/
ALARMS
Fire Alarm Priority 2 Alarm
SYSTEM WARNINGS
Supervisory Trouble Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building Signals
System indicator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress System Reset.
Press Ack to silence tone device.
ZONE
1SIG
2AUX
3
FB
4IO
5IDNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire Alarm
Ack
Priority 2
Ack
Supv
Ack
Trouble
Ack
Alarm
Silence
System
Reset
Event
Time
EnableOn
Arm
DisableOff
DisarmAuto
Lamp
Test
More
Info
Menu
Previous
Next
Upload/Download
port access (under
sliding cover)
Basic operator instructions
are printed on the interface
mounting plate
Panel sounder
Operator interface panel is directly
viewable and accessible (no access door)
Software Feature Summary
TrueAlarm individual analog sensing with front panel
information and selection access
“Dirty” TrueAlarm sensor maintenance alerts, service
and status reports including “almost dirty”
TrueAlarm magnet test indication appears as distinct
“test abnormal” message on display when in test mode
TrueAlarm sensor peak value performance report
Selectable service override allows authorized operators
to clear alarm conditions during System Reset even if
status has gone to trouble before reset occurred
Module level ground fault searching assists installation
and service by locating and isolating modules with
grounded wiring
WALKTEST™ silent or audible system test performs
an automatic self-resetting test cycle (WALKTEST
operation is protected under U.S. patent No. 4,725,818)
NOTE: If new features require software revisions,
updates will be performed on-site by the authorized
Simplex product representative.
2 S4100-0031-9 4/2005
Operator Interface
Convenient Status Information. With the locking
door closed, the glass window allows viewing of the
display, status LEDs, and available operator switches.
Features include a two-line by 40-character, wide viewing
angle (super-twist) LCD with status LEDs and switches as
shown in the illustration below.
LED indicators describe the general category of activity
being displayed with the LCD providing more detail. For
the authorized user, unlocking the door provides access to
the control switches and allows further inquiry by
scrolling the display for additional detail.
Operator Interface Features
Convenient and extensive operator information is provided using a logical, menu-driven display
Multiple automatic and manual diagnostics for maintenance reduction
Alarm and Trouble History Logs (up to 1200 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer
Convenient PC programmer label editing
Password access control
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMS
Fire Alarm Priority 2 Alarm
SYSTEM WARNINGS
Supervisory Trouble Alarm Silenced
ZONE
1SIG
2AUX
3
FB
4IO
5IDNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire Alarm
Ack
Priority 2
Ack
Supv
Ack
Trouble
Ack
Alarm
Silence
System
Reset
Event
Time
EnableOn
Arm
DisableOff
DisarmAuto
Lamp
Test
More
Info
Menu
Previous
Next
SIX SYSTEM STATUS INDICATOR LEDs
provide system status indications in addition
to LCD information, LEDs flash to indicate
the condition and then when acknowledged,
remain on until reset :
Fire Alarm & Priority 2 Alarm, red LED
Supervisory & Trouble, yellow LED
Alarm Silenced, yellow LED
AC Power, green LED (on for normal)
FIVE PROGRAMMABLE
FUNCTION SWITCHES,
each with a yellow LED
indicator
POINT STATUS
CONTROL KEYS:
Point Enable and
Disable
Force On or Arm
Force Off or Disarm
Return On/Off or
Arm/Disarm to Auto
Mode
NUMERIC KEYPAD for
point category and point
selection (alphabet
characters are not used at
this time)
ADDITIONAL
FUNCTION KEYS:
Event Time Request
More Information Request
Lamp Test
Elevator Recall
City Disconnect
Manual Evac
Ground Fault
Waterflow-West
Waterflow-East
Custom label insert
LCD NAVIGATION
CONTROL:
Menu selection
Vertical and
Horizontal position
selection buttons
FIRE ALARM ACK acknowledges a Fire Alarm
condition, logs the acknowledge, and silences the
operator panel and all annunciator tone-alerts
PRIORITY 2 ACK acknowledges a Priority 2 Alarm
condition, logs the acknowledge, and silences the
operator panel and all annunciator tone-alerts
SUPV ACK acknowledges system supervisory
conditions, logs the acknowledge, and silences the
operator panel and all annunciator tone-alerts
TROUBLE ACK acknowledges system troubles, logs
the acknowledge, and silences the operator panel and
all annunciator tone-alerts
ALARM SILENCE causes audible notification
appliances to be silenced (depending on panel
programming) typically after evacuation is complete and
while alarm source is being investigated; may allow
visible notification to continue (strobes still flashing)
SYSTEM RESET restores control panel to normal when
all alarmed inputs are returned to normal
2 X 40 LCD READOUT, LED backlighted
during normal conditions and abnormal
operating conditions, provides up to 40
characters for custom label information
FIRST ALARM DISPLAY: Operation can
be selected for maintained display of first
alarm until acknowledged
THREE PROGRAMMABLE LEDs
provide custom labeling, the top
two LEDs are selectable as red or
yellow, the bottom LED is
selectable as green or yellow
ULC SYSTEMS
require designating
a Ground Fault
indicator
3 S4100-0031-9 4/2005
Compatible Peripheral Devices
The 4100U is compatible with an extensive list of 4100
Series peripheral devices including printers, CRT/keyboards,
and both conventional and addressable devices including
TrueAlarm analog sensors.
Addressable Device Control
Overview. The 4100U provides standard addressable
device communications for IDNet compatible devices and
accepts optional modules for communications with
MAPNET II compatible devices. Using a two wire
communications circuit, individual devices such as
manual fire alarm stations, TrueAlarm sensors,
conventional IDC zones, and sprinkler waterflow
switches can be interfaced to the addressable controller to
communicate their identity and status.
Addressability allows the location and condition of the
connected device to be displayed on the operator interface
LCD and on remote system annunciators. Additionally,
control circuits (fans, dampers, etc.) may be individually
controlled and monitored with addressable devices.
Addressable Operation. Each addressable device on
the communication channel is continuously interrogated
for status condition such as: normal, off-normal, alarm,
supervisory, or trouble. Both Class A (Style 6) and
Class B (Style 4) operation are available. Sophisticated
poll and response communication techniques ensure
supervision integrity and allow for "T-tapping" of the
circuit for Class B (Style 4) operation. Devices with LEDs
pulse the LED to indicate receipt of a communications
poll and can be turned on steady from the panel.
IDNet Channel Capacity. The CPU bay system power
supply (SPS) provides an IDNet signaling line circuit
(SLC) that supports up to 250 addressable monitor and
control points intermixed on the same pair of wires.
Additional IDNet circuit modules are available for 64,
127, or 250 addressable devices.
MAPNET II Channel Capacity. A total of 127
addressable monitor and control points may be intermixed
on the same pair of wires supporting a single MAPNET II
signaling line circuit (SLC).
Wiring Requirements for MAPNET II or IDNet Communications. Refer to the specifications chart
below. Distances are for shielded or unshielded wire.
Shielded wire may provide protection from unexpected
sources of interference.
Wiring Specifications
Size 18 AWG minimum (0.82 mm2 )
Preferred Shielded twisted pair (STP) Type
Acceptable* Unshielded twisted pair (UTP)
Farthest Distance from Control Panel to Device
Up to 2500 feet (762 m)
Total Wire Length Allowed With “T” Taps for Class B Wiring
Up to 10,000 ft (3 km).
* Some applications may require shielded wiring. Review system with your local Simplex product supplier.
TrueAlert Addressable Notification
The 4100U can be equipped with a TrueAlert Power Supply
that provides three 3 A Signaling Line Circuits (SLCs) for
both controlling and powering addressable notification
appliances. With addressable appliances, Class B wiring
can be “T-tapped” for both easier wiring and reduced wire
run lengths. Extensive details concerning TrueAlert
addressable notification are found on data sheet
S4009-0003. Appliances are documented separately and
include horns, strobes, and combination units.
TrueAlarm System Operation
Addressable device communications include operation of
TrueAlarm smoke and temperature sensors. Smoke
sensors transmit an output value based on their smoke
chamber condition and the CPU maintains a current
value, peak value, and an average value for each sensor.
Status is determined by comparing the current sensor
value to its average value. Tracking this average value as
a continuously shifting reference point filters out
environmental factors that cause shifts in sensitivity.
Programmable sensitivity of each sensor can be field
selected at the control panel for different levels of smoke
obscuration (shown directly in percent) or for specific
heat detection levels. In order to evaluate whether the
sensitivity should be revised, the peak value is stored in
memory and can be easily read and compared to the alarm
threshold directly in percent.
TrueAlarm heat sensors can be selected for a fixed
temperature detection, with or without rate-of-rise
detection. Utility temperature sensing is also available,
typically to provide freeze warnings or alert to HVAC
system problems. The temperature readings can be
programmed to be read in either Fahrenheit or Celsius.
TrueSense® Early Fire Detection. Multi-sensor
4098-9754 provides photoelectric and heat sensor data
using a single 4100U IDNet address. The panel evaluates
smoke activity, heat activity, and their combination, to
provide TrueSense early detection. For more details on
this patented operation, refer to data sheet S4098-0024.
Diagnostics and Default Device Type
Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72® (National Fire Alarm Code®) requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor.
Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.
4 S4100-0031-9 4/2005
CPU Bay Module Details
Master Controller & Motherboard:
The master controller mounts in Slot 4 of a two slot motherboard (Slots 3 and 4 of the Master Controller Bay) and provides a standard RUI communications channel, selectable as Style 4 or Style 7, available at Slot 4
RUI communications control up to 31 remote annunciators/MINIPLEX® transponders per channel including the 4603-9101 LCD Annunciator, the 4602-9101 Status Command Unit (SCU), and 4602-9102 Remote Command Unit (RCU)
Up to four RUI channels are supported; use up to three 4100-1291 RUI expansion modules as required
Optional Service Modem 4100-6030 mounts onto the master controller board with its own on-board connections
Slot 3 of the motherboard is primarily used for the 4100-6014 Network Interface Board with media modules, and secondarily can accommodate the 4100-6038 Dual RS-232 Board
System Power Supply:
Rating is 9 A total, including module currents
Outputs are power-limited, except for the battery charger
Provides system power, battery charging, auxiliary power, auxiliary relay, earth detection, on-board IDNet communications channel for 250 points, three on-board NACs, and provisions for either an optional City Connect Module or an optional Alarm Relay Module
Dual rate, temperature compensated battery charger charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment
System Power Supply (Continued):
The charger is UL listed for charging up to 110 Ah batteries mounted in an external cabinet (refer to data sheet S2081-0012 for batteries and cabinet details)
Performs battery monitor including low battery warning
Provides status information to the master controller and analog values for battery voltage, charger voltage and current, actual system voltage and current, and individual NAC currents
2 A Auxiliary Power Output is selectable for detector reset, door holder, or coded output operation
Auxiliary Relay is selectable as N.O. or N.C., rated 2 A @ 32 VDC, and is programmable as a trouble relay, either normally energized or normally de-energized, or as an auxiliary control
Optional City Connect Module (4100-6031, with disconnect switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections
Optional Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC
IDNet SLC Output provides Style 4 or Style 6 communications for up to 250 addressable devices (as described on page 4)
Three, 3 A On-Board NACs, conventional reverse polarity operation, selectable as Class A or Class B, with electronic control and overcurrent protection; operation is selectable for synchronized strobe or SmartSync™ horn/strobe operation over two wires
NACs can be selected as auxiliary power outputs derated to 2 A for continuous duty; the total of all auxiliary power output per SPS is limited to 5 A maximum
Master Controller and Expansion Bay Selection (Canadian models have low battery cutout)
Model Model Type/Listing Description Supv. Alarm
4100-9111 120 VAC Input UL
4100-9112 English
4100-9113 French120 VAC, Canadian ULC
4100-9211 220-240 VAC Input UL
4100U Master Controller Assembly with LCD and operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface
373 mA 470 mA
4100-9131 120 VAC Input UL
4100-9132 English
4100-9133 French 120 VAC, Canadian ULC
4100-9230 220-240 VAC Input UL
4100U Master Controller Assembly, no display, no operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface
363 mA 425 mA
4100-9121
Redundant Master Controller, two bay assembly; top bay contains LCD and operator interface, CPU card assembly, and 4100U, 9 A system power supply/battery charger (SPS); second bay contains CPU card in Slot 2, and LCD and operator interface; 120 VAC, 60 Hz input; NOTE: RUI connections require use of 4100-1291 RUI expansion modules
574 mA 793 mA
4100-2300 Expansion Bay Assembly; order for each required expansion bay (not required for 4100-9121)
Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels
Model Description 4100 Panel Type Details
4100-7150 Master Controller Upgrade with LCD and operator interface assembly
4100-7151 Master Controller Upgrade without LCD or operator interface1000 point
4100-7152 Master Controller Upgrade with LCD, operator interface, and power supply 512 point
Upgrades existing 4100 panel to 4100U operation
4100-2301 Expansion Bay Upgrade Kit for mounting 4100U style (4” x 5” modules) in existing 4100 style panels
Master Controller Upgrades for Existing 4020 Series Fire Alarm Control Panel
Model Description
4100-9833 4020 Master Controller Upgrade with LCD & operator interface assembly; mounts as an adjunct panel; single bay size with locking glass door and retainer; cabinet dimensions are 24” W x 22” H x 8-3/8” D (610 mm x 559 mm x 213 mm)
5 S4100-0031-9 4/2005
Master Controller Selection Information
6 S4100-0031-9 4/2005
Communication Modules
Model Description Size Supv. Alarm
4100-6014 For Master Controller; mounts in Slot 3 1 Slot 28 mA 28 mA
4100-6061
Modular Network Interface; each requires two media modules (below) For Redundant Master Controller 1 Slot 28 mA 28 mA
4100-6056 Wired Media Module N.A. 55 mA 55 mA
4100-6057 Fiber Optic Media Module
Select two media cards as required; mounts on 4100-6014 or 4100-6061 N.A. 25 mA 25 mA
4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6014 or 4100-6061 Network Interface Card, requires telephone line connection
N.A. 75 mA 75 mA
4100-1291 Remote Unit Interface Module (RUI); up to three maximum per control panel 1 Slot 85 mA 85 mA
4100-6030Service Port Modem, local panel access only, mounts to Master Controller Module, requires telephone line connection, accesses same information as front panel port
N.A. 70 mA 70 mA
4100-6031 City Circuit, with disconnect switches N.A. 20 mA 36 mA
4100-6032 City Circuit, w/o disconnect switches
For use with SPS only, not RPS N.A. 20 mA 36 mA
4100-6033
Select one per SPS (fits on SPS)
Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS N.A. 15 mA 37 mA
4100-6036 Physical Bridge, Style 4, includes 1 modem module and 2 wired modules 1 Slot 260 mA 260 mA
4100-6037 Physical Bridge, Style 7, includes 2 modem and 2 wired modules 2 Slots 304 mA 304 mA
4100-6038 Dual Port RS-232 Interface, mounts in Slot 3 or Slot 2; 3 max. RS-232 type per panel 1 Slot 132 mA 132 mA
4100-6045 Decoder Module 3 Slots 85 mA 163 mA
4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-9816 Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 1 Slot 132 mA 132 mA
4100-6052DACT, Point or Event Reporting; one shipped standard unless 4100-7908 is selected; maximum of 2 per system; includes two 2080-9047 cables, 14 ft (4.3 m) long with RJ45 plug on one end, spade lugs on wire ends
1 Slot 30 mA 40 mA
Expansion, System, Remote, and TrueAlert Power Supplies and Accessories*
Model Description/Listing Size Supv. Alarm
4100-5101 120 VAC UL
4100-5103 120 VAC, Canadian ULC
4100-5102 220-240 VAC UL
Expansion Power Supply (XPS); 9 A output, 3 built-in Class A/B NACs
2 Blocks 50 mA 50 mA
4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA
4100-5111 120 VAC UL
4100-5112 120 VAC, Canadian ULC
4100-5113 220-240 VAC UL
Additional System Power Supply (SPS); 9 A power supply/charger with 250 point IDNet channel, 3 Class A/B NACs, add IDNet device currents separately
4 Blocks 175 mA 225 mA
4100-5125 120 VAC UL
4100-5126 120 VAC, Canadian ULC
4100-5127 220-240 VAC UL
Remote Power Supply (RPS); 9 A power supply/charger similar to SPS except no IDNet channel or City Circuits, will accept one 4100-6033
4 Blocks 150 mA 185 mA
4100-5120 120 VAC UL
4100-5121 120 VAC, Canadian ULC
4100-5122 220-240 VAC UL
TrueAlert Power Supply (TPS); 3 Class B SLCs rated 3 A each for up to 63 TrueAlert addressable appliances per channel, 189 per TPS; built-in battery charger; 2 A aux. power output; add device current separately, 0.2 mA standby (see S4009-0003 for additional detail)
4 Blocks 88 mA 100 mA
4100-5124 TrueAlert SLC Class A Adapter for all 3 SLCs, mounts on TPS only N.A. 7 mA 7 mA
4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block 1.5 A maximum
4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from SPS
Miscellaneous Accessories
Model Description
4100-1279 Single blank 2” display cover, order as required (8 are required to fill a bay front)
4100-2210 Appliqué, Canadian French, 4100U Fire Control
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-6029 Smoke Management Application Guide; required for UUKL listing
4100-6034 Door Tamper Switch with built-in addressable IDNet IAM, one per cabinet assembly if required
2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm
2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)
Initiating Device Circuits (IDCs)
Model Description Size Supv. Alarm
4100-5005 Eight zones, Class B 1 Slot 75 mA 195 mA
4100-5015 Eight zones, Class A 1 Slot 75 mA 195 mA
* Canadian models have low battery cutout. XPS and RPS NACs operate like SPS, see page 5. Continued on next page
Module Selection Information
7 S4100-0031-9 4/2005
120 VAC Models 3.5 A maximum @ 102 to 132 VAC, 60 Hz InputPower
System Power Supplies (SPS) Expansion Power Supplies (XPS)
Remote Power Supplies (RPS) TrueAlert Power Supplies (TPS)
220-240 VAC Models
1.75 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC
Total Power Supply Output Rating
9 A total @ nominal 28 VDC, including module currents and auxiliary power outputs
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
Power Supply Output Ratings, System, Expansion, and Remote Power Supplies NACs Programmed
for Auxiliary Power2 A maximum per NAC, 5 A maximum total @ nominal 28 VDC
Output switches to battery backup during mains AC failure or brownout conditions
Battery capacity range
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is UL listed for up to 110 Ah battery charging for remotely located batteries Battery Charger,
System and Remote Power Supply
Chargercharacteristics and
performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Operating Temp. 32° to 120°F (0° to 49° C) Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Addressable Interface Modules (refer to location reference on page 8)
Model Description Supv. Alarm
4100-3101 IDNet Module, 250 point capacity With 250 IDNet devices, add 200 mA 250 mA
4100-3104 IDNet Module, 127 point capacity With 127 IDNet devices, add 102 mA 127 mA
4100-3105 IDNet Module, 64 point capacity With 64 IDNet devices, add 51 mA 64 mA
Module without devices 75 mA 115 mA IDNet Modules, Specifications for each capacity; Module size = 1 Block Loading per IDNet device 0.8 mA 1 mA
Model Description Supv. Alarm
Module without devices 270 mA 290 mA 4100-3102
MAPNET II Module, 127 point capacity, add devices separately; Module size = 2 Slots; Loading per MAPNET II device = 1.7 mA Fully loaded module, total 470 mA 490 mA
4100-3103
Isolator Module for MAPNET II or IDNet; converts a single connected SLC into four isolated outputs selectable as Class A or Class B; up to two Isolator Modules can be connected to one SLC; Module size = 1 Slot;
NOTE: Compatible with MAPNET II Remote Isolators only; for quad isolation with IDNet Remote Isolators, use 4100-3107 IDNet+ Module (refer to data sheet S4100-0046 for details)
50 mA 50 mA
Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on page 8)
Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA
4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC 1/2 A 30 VDC/120 VAC 1 Block 18 mA 70 mA
4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1-1/2 A 30 VDC/120 VAC 1 Block 16 mA 200 mA
Current Calculation Notes:
1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered by panel power supplies.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all external loads powered from panel power supplies.
Subject Data Sheet Subject Data Sheet
Enclosures S4100-0037 MINIPLEX Transponders S4100-0035
LED/Switch Modules S4100-0032 Network Display Unit (NDU) S4100-0036
4100U Audio/Phone Modules S4100-0034 Remote Annunciators S4100-0038
TFX Interface Module S4100-0042 Remote Battery Charger S4081-0002
TrueAlert Addressable Products S4009-0003 IDNet+ Module with Quad Isolator S4100-0046
Module Selection Information (Continued)
General Specifications
Additional 4100U Data Sheet Reference
Tyco, Simplex, the Simplex logo, MAPNET II, IDNet, TrueAlarm, SmartSync, WALKTEST, MINIPLEX, TrueAlert, TrueSense and BACpac are trademarks of Tyco International
Services AG or its affiliates in the U.S. and/or other countries. Microsoft and Windows are registered trademarks of Microsoft Corporation. VESDA is a trademark of Vision
Products Pty Ltd. NFPA 72, and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). BACnet is a registered trademark of
the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE).
Door thickness
1-3/8"(35 mm)
Exposed cabinet
for semi-flush
mounting
1-3/8" (35 mm)
minimum
Exposed door
and cabinet for
semi-flush
mounting
2-3/4" (70 mm)
minimum
PDI
4x5 Module
Expansion Power
Supply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
410
0 O
ptio
n
410
0 O
ptio
n
410
0 O
ptio
n
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
System Power
Supply
(SPS)
IDNetNACs 1, 2 & 3
Aux PwrAux
Relay
Btry+-
City Circuit
4100-6031
4100-6032
Alarm Relay
4100-6033
Ma
ste
r C
on
tro
ller
Boa
rd
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
*System power supply*Master controller
with motherboard
24" (610 mm)
Optional semi-flush trim kit
4100-6031 or 4100-6032
City Circuit or 4100-6033
Alarm Relay
4100-6030 Service Modem mounts
only on master controller board
Slot 3, one 2" card: either 4100-6014 Network Module
with media cards or 4100-6038 Dual RS-232
Slot 1
Slot 2
Slot 3
Cabinet height:
(2 bay shown
for reference)
2 Bay = 40"
(1016 mm)
3 Bay = 56"
(1427 mm)
8-3/8"(213 mm)
6-29/32"
(175 mm)
Stud
alignment
markers,
each side
Knockout
screw/nail
holes (for
semi-flush
mounting)
4" stud
6" stud
Two, 2", or one, 4" slot for
one or two modules installed
per the following:
4100-6052 DACT, Slot 1
4100-6036 Physical Bridge,
Slot 2
4100-6037 Physical Bridge
(4" module) Slots 1 and 2
4100-6048 VESDA Interface,
Slot 1 or 2
4100-5005/5115 IDC Modules,
Slot 1 or 2
4100-6038 Dual RS-232,
Slot 2, if Network Module is
in Slot 3
Master Controller Bay
Typical Expansion Bay
(showing mixed module sizes)
Battery Compartment
Door can be hung
hinged left or right
Wall board
reference for
semi-flush
mounting,
6" stud
Two bay cabinet
shown without retainer
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Expansion Bay Chassis
Block A
Block B
Block C
Block D
Block E
Block F
Block G
Block H
Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area
Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card
Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4100-0031-9 4/2005
www.tycosafetyproducts-usa-wm.com
© 2005 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Expansion Bay Module Loading Reference
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
Mounting and CPU Bay Module Reference (* indicates supplied modules)
Description Mounting
IDNet Modules 1 Block
4, 2 A Relays 1 block
4, 10 A Relays 4”, 2 slots
8, 3 A Relays
NONPower-limited
1 block
VESDA Interface 2”, 1 Slot
Class B IDC 2”, 1 Slot
Class A IDC 2”, 1 Slot
MAPNET II Module 4”, 2 Slots
MAPNET II/IDNet Isolator 2”, 1 Slot
Style 4 Physical Bridge 2”, 1 Slot
Style 7 Physical Bridge 4”, 2 Slots
Decoder Module 6”, 3 Slots
System, Remote, or TrueAlert Power Supply
Blocks E, F, G & H ONLY
Expansion Power Supply Blocks G & H ONLY
NAC Expansion Module On XPS ONLY