PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
PRECISION DIGITAL CORPORATION 233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
Rate/Totalizer
Two (2) 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs Displays Two Flow Inputs Simultaneously Displays Rate and Total Simultaneously Math Functions Capabilities Isolated 24 VDC @ 200 mA Transmitter Power Supply Count Up or Down, Total & Grand Total Open Chanel Flow with Programmable Exponent Non-Resettable Grand Total 32-Point Linearization Dual-Line Display NEMA 4X and IP65 Rated Front Panel UL Listed & CE Marked Display Features 0.6" & 0.46" Digits Six Full Digits on Each Line Optional Superluminous Sunlight Readable Display Free USB Programming Software & Cable 2 or 4 Relays + Isolated 4-20 mA Output Options Modbus® RTU Communication Protocol Standard
PR VUSERIES
®
USB Install
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
2
Disclaimer The information contained in this document is subject to change without notice. Precision Digital makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
CAUTION: Read complete instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning! This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages resulting from such improper use.
Limited Warranty Precision Digital Corporation warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Precision Digital’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks PROVU® and MeterView® Pro are registered trademarks of Precision Digital Corporation. Modbus® is a Registered Trademark of Schneider Automation Inc. All other trademarks mentioned in this document are the property of their respective owners. © 2017 Precision Digital Corporation. All rights reserved.
www.predig.com
!
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
3
Table of Contents Table of Contents ----------------------------------------- 3 Table of Figures ------------------------------------------- 4 Introduction ------------------------------------------------- 4 Ordering Information ------------------------------------ 5 Specifications ---------------------------------------------- 6
General ------------------------------------------------------------ 6 Dual Process Input -------------------------------------------- 6 Dual Rate/Totalizer -------------------------------------------- 7 Relays ------------------------------------------------------------- 8 Isolated 4-20 mA Transmitter Output ------------------- 8 Modbus® RTU Serial Communications ---------------- 8 MeterView Pro -------------------------------------------------- 8
Compliance Information -------------------------------- 9 Safety -------------------------------------------------------------- 9 Electromagnetic Compatibility ---------------------------- 9
Safety Information -------------------------------------- 10 Installation ------------------------------------------------ 10
Unpacking ------------------------------------------------------ 10 Panel Mounting Instructions ----------------------------- 10 Mounting Dimensions -------------------------------------- 11 Transmitter Supply Voltage Selection (P+, P-) ---- 11 Connections --------------------------------------------------- 12
Connectors Labeling -------------------------------------- 12 Power Connections --------------------------------------- 12 Signal Connections --------------------------------------- 13 Modbus RTU Serial Communications ---------------- 14 Relay Connections ---------------------------------------- 14 Switching Inductive Loads ------------------------------- 14 F4 Digital Input Connections ---------------------------- 15 4-20 mA Output Connections --------------------------- 15 Analog Output Transmitter Power Supply ----------- 15 External Relay, Analog Output, & Digital I/O Connections ------------------------------------------------- 16 Interlock Relay Feature ---------------------------------- 16
Setup and Programming ------------------------------ 17 Front Panel Buttons and Status LED Indicators -- 17 MeterView® Pro Software --------------------------------- 18
MeterView Pro Installation ------------------------------ 18 Display Functions & Messages ------------------------- 19 Main Menu ----------------------------------------------------- 22 Setting Numeric Values ----------------------------------- 22 Setting Up the Meter (setup) ----------------------------- 23
Setting the Input Signal (Input) ----------------------- 23 Setting the Totalizer Features (total) --------------- 24 Setting the Rate, Total, & Grand Total Units/Tags (units) ------------------------------------------------------- 24 Setting the Decimal Point (dEc pt) ------------------- 25 Programming the Rate/Totalizer (prog) ------------- 26
Input Calibration Method (InCAL) ------------------ 26 Scaling the Meter without a Signal Source (SCAL-
A, SCAL-B) ----------------------------------------- 27 Error Message (Error) ------------------------------- 27 Calibrating the Meter with External Source ------ 28 Total and Grand Total Setup ------------------------ 29 Total & Grand Total Reset --------------------------- 29
Setting the Display Parameters & Intensity (dsplay)
----------------------------------------------------------------- 30 Setting the Relay Operation (relay) ----------------- 31
Setting the Relay Assignment (asSign) --------- 32 Setting the Relay Action (Act) ---------------------- 32 Programming Set and Reset Points -------------- 33 Setting Fail-Safe Operation ------------------------- 33 Programming Time Delay---------------------------- 33 Relay Action for Loss of 4-20 mA Input (Loop
Break) ----------------------------------------------- 33 Relay and Alarm Operation Diagrams ---------------- 34
High Alarm Operation (Set > Reset) ------------------ 34 Low Alarm Operation (Set < Reset) ------------------ 34 High Alarm with Fail-Safe Operation (Set > Reset) ----------------------------------------------------------------- 34 Low Alarm with Fail-Safe Operation (Set < Reset) 34 Pump Alternation Control Operation ------------------ 35 Relay Sampling Operation ------------------------------ 35 Signal Loss or Loop Break Relay Operation ------- 36 Time Delay Operation ------------------------------------ 36
Relay Operation Details ----------------------------------- 37 Overview ----------------------------------------------------- 37 Relays Auto Initialization -------------------------------- 37 Fail-Safe Operation --------------------------------------- 37 Front Panel LEDs ----------------------------------------- 37 Latching and Non-Latching Relay Operation ------- 38 Non-Latching Relay (Auto) ----------------------------- 38 Non-Latching Relay (A-man) ------------------------- 38 Latching Relay (LatcH) ---------------------------------- 38 Latching Relay (Lt-Clr) --------------------------------- 38 Acknowledging Relays ----------------------------------- 39 Pump Alternation Control Applications (Altern) -- 39
Application #1: Pump Alternation Using Relays 1 & 2 --------------------------------------------------- 39
Setting Up the Interlock Relay (Force On) Feature 40 Scaling the 4-20 mA Analog Output (Aout) --------- 40 Reset Menu (reset) ----------------------------------------- 41 Control Menu (Contrl) ------------------------------------- 41 Setting Up the Password (pass) ------------------------ 41
Protecting or Locking the Meter Functions ---------- 41 Total Reset Password & Non-Resettable Total ---- 42 Making Changes to a Password Protected Meter - 42 Disabling Password Protection ------------------------ 42
Advanced Features Menu -------------------------------- 43 Advanced Features Menu & Display Messages --- 43 Noise Filter (filter) ------------------------------------- 45 Noise Filter Bypass (bypass) --------------------------- 45 Rounding Feature (round) ------------------------------ 45 Modbus RTU Serial Communications (serial) --- 46 Select Menu (SElect) ------------------------------------ 46 Signal Input Conditioning (Functn) ------------------- 47 Square Root Linearization (Square) ------------------ 47 Programmable Exponent Linearization (Prog E) - 47 Multi-Point Linearization (Linear) -------------------- 47 Math Function (nmath) ----------------------------------- 48 Math Constants (Const) --------------------------------- 48 Low-Flow Cutoff (CutofF) ------------------------------- 49 Totalizer Count Up/Down (Count)--------------------- 49 Analog Output Programming (AoutPr) -------------- 49 Programmable Function Keys User Menu (user) - 50
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
4
Internal Calibration (ICAL) ------------------------------- 52 Meter Operation ----------------------------------------- 53
Front Panel Buttons Operation ------------------------- 53 Function Keys Operation --------------------------------- 53 F4 Operation -------------------------------------------------- 53 Maximum/Minimum Readings --------------------------- 53
Troubleshooting ----------------------------------------- 54
Diagnostics Menu (diag) ---------------------------------- 54 Determining Software Version ------------------------- 54
Reset Meter to Factory Defaults ------------------------ 54 Factory Defaults & User Settings ---------------------- 55
Troubleshooting Tips -------------------------------------- 57 EU Declaration of Conformity ----------------------- 59
Table of Figures Figure 1. 1/8 DIN Panel Cutout Dimensions .............. 10 Figure 2. Panel Mounting Details ............................... 10 Figure 3. Meter Dimensions - Side View ................... 11 Figure 4. Meter Dimensions - Top View .................... 11 Figure 5. Transmitter Supply Voltage Selection ....... 11 Figure 6. Connector Labeling for Fully Loaded
PD6262 ................................................................. 12 Figure 7. Power Connections ..................................... 12 Figure 8. Transmitters Powered by Internal Supply . 13 Figure 9. Transmitter Powered by Ext. Supply or Self-
Powered ................................................................ 13 Figure 10. Voltage Input Connections ........................ 13 Figure 11. Relay Connections ..................................... 14 Figure 12. AC and DC Loads Protection .................... 14 Figure 13. Low Voltage DC Loads Protection ........... 14 Figure 14. F4 Digital Input Connections .................... 15 Figure 15. 4-20 mA Output Connections .................... 15 Figure 16. Interlock Connections ............................... 16 Figure 17. Acknowledge Relays w/Function Key or
Digital Input .......................................................... 39
Introduction The PROVU® PD6262 is a multipurpose, easy to use digital dual analog input rate/totalizer ideal for flow rate, total, and flow control applications. Its superluminous LED digits make it easily readable in smoke, dust, fog, and, with the optional SunBright® display, even direct sunlight.
It accepts two current or voltage signals (e.g. 4-20 mA, 0-10 V). Various math functions may be applied to the rate, total, or grand totals of the two channels; including addition, difference, average, minimum, maximum, draw, ratio and more. This is in addition to the signal input conditioning functions; linear, square root, or programmable exponent.
The displays, relays, and the analog output may be assigned to the rate, total, or grand total of input channels A or B; or math result channel C. Three of the front panel buttons can be custom-programmed for a specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitters or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded PD6262 meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power supplies. The PD6262 capabilities may be enhanced by adding the following external expansion modules: four SPST relays –creating an eight-relay dual-input process meter, two digital I/O modules with four inputs and four outputs each, serial communication adapters for use with MeterView Pro or Modbus RTU, and a dual isolated 4-20 mA output expansion module.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
5
Ordering Information Standard Models
85-265 VAC Model 12-24 VDC Model Options Installed
PD6262-6R0 PD6262-7R0 No options PD6262-6R2 PD6262-7R2 2 relays (PD1102*) PD6262-6R3 PD6262-7R3 4-20 mA output (PD1103*) PD6262-6R4 PD6262-7R4 4 relays (PD1104*) PD6262-6R5 PD6262-7R5 2 relays & 4-20 mA output (PD1105*) PD6262-6R7 PD6262-7R7 4 relays & 4-20 mA output (PD1107*) *Model number for replacement option card.
SunBright Display Models
85-265 VAC Model 12-24 VDC Model Options Installed
PD6262-6H0 PD6262-7H0 No options PD6262-6H2 PD6262-7H2 2 relays (PD1102*) PD6262-6H3 PD6262-7H3 4-20 mA output (PD1103*) PD6262-6H4 PD6262-7H4 4 relays (PD1104*) PD6262-6H5 PD6262-7H5 2 relays & 4-20 mA output (PD1105*) PD6262-6H7 PD6262-7H7 4 relays & 4-20 mA output (PD1107*) *Model number for replacement option card.
Accessories Model Description PDA1002 DIN rail mounting kit for two expansion modules PDA1004 4 SPST (Form A) relays PDA1011 Dual isolated 4-20 mA output expansion module PDA1044 4 digital inputs & 4 digital outputs (2 may be connected) PDA1232 RS-232 serial adapter PDA1485 RS-485 serial adapter PDA7485-I RS-232 to RS-422/485 isolated converter PDA7485-N RS-232 to RS-422/485 non-isolated converter PDA8232-N USB to RS-232 non-isolated converter PDA8485-I USB to RS-422/485 isolated converter PDA8485-N USB to RS-422/485 non-isolated converter PDX6901 Suppressor (snubber): 0.01 µF/470 , 250 VAC
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
6
Specifications Except where noted all specifications apply to operation at +25°C.
General Display Line 1: 0.60" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs 6 digits each (-99999 to 999999), with lead zero blanking
Display Intensity
Eight user selectable intensity levels
Display Update Rate
5/second (200 ms)
Overrange Display flashes 999999
Underrange Display flashes -99999
Display Assignment
Display lines 1 & 2 may be assigned to show:
One or more rate channels: Channel A (Ch-A), B (Ch-B), or C (Ch-C)
Toggle between rate channels: Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C
Total or grand total: Ch-A or Ch-B
Rate and total or grand total: Ch-A, Ch-B
Relay set points
Max and/or min values: Ch-A, Ch-B, or Ch-C
Toggle between any rate channel & units
Total and units: Ch-A or Ch-B
Toggle between totals: Ch-A & Ch-B; Ch-A, Ch-B, and sum of Ch-A and Ch-B
Modbus input
Line 2 may also be set to show engineering units or be off, with no display.
Programming Methods
Four front panel buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
Max/Min Display
Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
Noise Filter Programmable from 2 to 199 (0 will disable filter)
Filter Bypass Programmable from 0.1 to 99.9% of calibrated span
Recalibration All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Non-Volatile Memory
All programmed settings are stored in non-volatile memory for a minimum of ten years.
Power Options
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC 10%, 15 W max
Powered over USB for configuration only
Fuse Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Isolated Transmitter Power Supply
Terminals P+ & P-: 24 VDC 10%. Selectable for 24, 10, or 5 VDC supply (internal jumper J4).
85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Normal Mode Rejection
Greater than 60 dB at 50/60 Hz
Isolation 4 kV input/output-to-power line 500 V input-to-output or output-to-P+ supply
Overvoltage Category
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental Operating temperature range: -40 to 65°C Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
Connections Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting 1/8 DIN panel cutout required: 3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
Tightening Torque
Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight 9.5 oz (269 g)
Warranty 3 years parts & labor
Dual Process Input Two Inputs Two non-isolated inputs, each separately
field selectable: 0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
Channels Channel A, Channel B, Channel C (Math channel)
Programmable Constants
Constant P (Adder): -99.999 to 999.999, default: 0.000 Constant F (Factor): 0.001 to 999.999, default: 1.000
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
7
Math Functions
Name Function Setting
Addition (A+B+P)*F Sunm Difference (A-B+P)*F diF Absolute diff. ((Abs(A-B))+P)*F diFAbS Average (((A+B)/2)+P)*F AvG Multiplication ((A*B)+P)*F nmulti Division ((A/B)+P)*F divide Max of A or B ((AB-Hi)+P)*F Hi-Ab Min of A or B ((AB-Lo)+P)*F Lo-Ab Draw ((A/B)-1)*F drAuw Weighted avg. ((B-A)*F)+A uw avg Ratio (A/B)*F ratio
Ratio 2 ((B-A)/A)+P)*F ratio2 Concentration (A/(A+B))*F Concen
Total Addition (tA+tB+P)*F Sunm t
G. Tot. Addition (GtA+GtB+P)*F SunmGT
Total Difference (tA-tB+P)*F Dif t
G. Tot. Difference (GtA-GtB+P)*F Dif GT
Total Ratio (tA/tB)*F Tratio
Total Ratio 2 ((tB-tA)/tA)*F t-rat2
Total Percent (tA/(tA+tB))*100 T PCT
Note: The F constant can be any value from 0.001 to 999.999. If the value is less than 1, it will have the same effect as a divider. For example, the average could also be derived by using (A+B)*F, where F = 0.500.
Sequence of Operations for Input Programming
1. Select Input for A and B 2. Set up the rate, total, and grand total
engineering units for channels A & B, and units for math channel C
3. Set up rate, total, and grand total decimal points for channels A & B, and decimal point for math channel C
4. Program channel A & B rate parameters
5. Program channel A & B total and reset parameters
6. Set up display lines 1 and 2 7. Select the transfer function for A & B
(e.g. Linear) 8. Select Math function for Channel C 9. Program constants for Factor (F) and
Adder (P). 10. Program cutoff values for A and B
Accuracy ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
Temperature Drift
0.005% of calibrated span/C max from 0 to 65C ambient, 0.01% of calibrated span/C max from -40 to 0C ambient
Signal Input Conditioning
Linear, square root, or programmable exponent
Multi-Point Linearization
2 to 32 points for channel A and B
Programmable Exponent
1.0001 to 2.9999
Low-Flow Cutoff
0-999999 (0 disables cutoff function)
Decimal Point Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration Range
Input Range 4-20 mA 10 V
Minimum Span Input 1 & Input 2 0.15 mA 0.01 V
An error message will appear if the input 1 and input 2 signals are too close together.
Input Impedance
Voltage ranges: greater than 500 k Current ranges: 50 - 100 (depending on resettable fuse impedance)
Input Overload
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
F4 Digital Input Contacts
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Dual Rate/Totalizer Rate Display Indication
-99999 to 999999, lead zero blanking.
Total Display & Total Overflow
0 to 999,999; automatic lead zero blanking. Up to 999,999,999 with total-overflow feature. “oF” is displayed to the left of total overflow and LED is illuminated.
Total Decimal Points
Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd Total decimal point is independent of rate decimal point. Channel A and B decimal points programmed independently.
Dual Totalizer Calculates total for channels A and B based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Channel A and B totalizer parameters programmed independently.
Totalizer Rollover
Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display.
Total Overflow Override
Program total A or B total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Alarm Presets
Up to eight, user selectable under setup menu. Any set point can be assigned to channel A or B total or grand total (or C) and may be programmed anywhere in the range of the meter for total alarm indication.
Total Reset Password
Total and grand total passwords may be entered to prevent resetting the totals or grand totals from the front panel.
Total & Grand Total Reset
Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications. Channel A and B total and grand total reset parameters programmed independently.
Programm-able Delay On Release
0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
8
Non-Resettable Total
The grand totals can be programmed as non-resettable totals by entering the password “050873”. Both channels are set to non-resettable when this password is entered.
Caution!
Once the Grand Totals have been programmed as “non-resettable” the feature cannot be disabled.
Relays Rating 2 or 4 SPDT (Form C) internal and/or 4
SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise Suppression
Noise suppression is recommended for each relay contact switching inductive loads; see page 14 for details.
Relay Assignment
Relays may be assigned to channel A or B rate, total, or grand total; channel C; or Modbus control.
Deadband 0-100% of span, user programmable
High Or Low Alarm
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
Relay Operation
Automatic (non-latching) Latching (requires manual acknowledge) Sampling (based on time) Pump alternation control (2 to 8 relays) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
Relay Reset User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when the input passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
Time Delay 0 to 999.9 seconds, on & off relay time delays Programmable and independent for each relay
Fail-Safe Operation
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization
When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output Output Source
Input channels A or B, rate, total, or grand total; channel C; max or min for channel A or B; highest or lowest max or min of A and B; set points 1-8; Modbus input; or manual control mode
Scaling Range
1.000 to 23.000 mA for any display range
Calibration Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Out Programming
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy ± 0.1% of span ± 0.004 mA
Temperature Drift
0.4 µA/C max from 0 to 65C ambient, 0.8 µA/C max from -40 to 0C ambient Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply
Terminals I+ & R: 24 VDC 10%. May be used to power the 4-20 mA output or other devices. Refer to Figure 6 on page 12 and Figure 15 on page 15.
All models rated @ 40 mA max.
External Loop Power Supply
35 VDC maximum
Output Loop Resistance
Power supply Minimum Maximum
24 VDC 10 700
35 VDC (external)
100 1200
Modbus® RTU Serial Communications Slave Id 1 – 247 (Meter address)
Baud Rate 300 – 19,200 bps
Transmit Time Delay
Programmable between 0 and 199 ms
Data 8 bit (1 start bit, 1 or 2 stop bits)
Parity Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte Timeout
0.01 – 2.54 second
Turn Around Delay
Less than 2 ms (fixed)
Note: Refer to the PROVU® Modbus Register Tables located at www.predig.com for details.
MeterView Pro System Requirements
Microsoft® Windows® XP/Vista/7/8/10
Communications
USB 2.0 (Standard USB A to Micro USB B)
Configuration Configure meters one at a time
!
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
9
Compliance Information Safety UL & c-UL Listed USA & Canada
UL 508 Industrial Control Equipment
UL File Number E160849
Front Panel UL Type 4X, NEMA 4X, IP65; panel gasket provided
Low Voltage Directive
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use
Electromagnetic Compatibility Emissions EN 55022:2010
Class A ITE emissions requirements
Radiated Emissions
Class A
AC Mains Conducted Emissions
Class A
Immunity EN 61326-1:2013 Measurement, control, and laboratory equipment EN 61000-6-2:2005 EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz) 1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz) 2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients
±2kV AC mains, ±1kV other
Electrostatic Discharge
±4kV contact, ±8kV air
RFI - Conducted 10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge ±2kV Common, ±1kV Differential
Surge 1KV (CM)
Power-Frequency Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips 40%V for 5 & 50 periods 70%V for 25 periods
Voltage Interruptions
<5%V for 250 periods
Note: Testing was conducted on PD6200 Series meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.predig.com
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
10
Safety Information
CAUTION: Read complete instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
WARNING! Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
Installation There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications. Instructions are provided for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 11.
Unpacking Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier. If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1
below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm). Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Figure 2. Panel Mounting Details
!
3.622" (92 mm)
1.772" (45mm) Panel Cutout
to DIN 43700
Square Corners to 0.060"(1.5mm) Max Radius
A
B
Tolerances:A: +0.032 (+0.8mm) -0.000 (-0.0mm)B: +0.024 (+0.6mm) -0.000 (-0.0mm)
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
11
Mounting Dimensions
Figure 3. Meter Dimensions - Side View
Figure 4. Meter Dimensions - Top View
Transmitter Supply Voltage Selection (P+, P-) All meters, including models equipped with the 12-24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor. If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly. To access the voltage selection jumper:
1. Remove all the wiring connectors. 2. Unscrew the back cover. 3. Slide out the back cover by about 1 inch. 4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation
voltage as shown.
Figure 5. Transmitter Supply Voltage Selection
NO NCNCC NOCNO NCNCC NOC+ -R
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
12
Connections All connections are made to removable screw terminal connectors located at the rear of the meter.
Caution!
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
Connectors Labeling The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Warning!
Do not connect any equipment other than Precision Digital’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 6. Connector Labeling for Fully Loaded PD6262
Power Connections Power connections are made to a two-terminal connector labeled POWER on Figure 6. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
Figure 7. Power Connections
AC or DCPOWER
Required External Fuse:5 A max, 250 V Slow Blow
POWER
+ -
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
13
Signal Connections Signal connections are made to a nine-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminals are the return for the 4-20 mA and the 10 V input signals. The two COM terminals connect to the same common return, and are not isolated.
Current and Voltage Connections The following figures show examples of current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs. Setup and programming is performed through the front panel buttons.
Figure 8. Transmitters Powered by Internal Supply
Figure 9. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload. The fuse limits the current to a safe level when it detects a fault condition, and automatically resets itself when the fault condition is removed.
Figure 10. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
14
Modbus RTU Serial Communications Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. For interfacing to the PROVU®, use the PDA1232 for RS-232 or the PDA1485 for RS-485. The same port is used for interfacing with all expansion modules (e.g. external relays, additional 4-20 mA outputs, digital I/O).
Relay Connections Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 6. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
Figure 11. Relay Connections
Switching Inductive Loads The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
Figure 12. AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 Ω for each volt across the contacts C: 0.5 to 1 µF for each amp through closed contacts Notes: 1. Use capacitors rated for 250 VAC. 2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation. 3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed
across the load. Experiment for best results.
Figure 13. Low Voltage DC Loads Protection
C NONO NC NC C
RELAY4 RELAY34 36 5 2 1
C NONO NC NC C
RELAY2 RELAY14 36 5 2 1
C
RC
R
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
15
RC Networks Available from Precision Digital RC networks are available from Precision Digital and should be applied to each relay contact switching an inductive load. Part number: PDX6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
F4 Digital Input Connections A digital input, F4, is standard on the meter. This digital input connected with a normally open closure across F4 and COM, or with an active low signal applied to F4.
Figure 14. F4 Digital Input Connections
4-20 mA Output Connections Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
Figure 15. 4-20 mA Output Connections
Analog Output Transmitter Power Supply The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
12-35 VDCPowerSupply
+
4-20 mAInput Meter
-+
RI- I+13 2
RELAY13 2 1
24 V
-
4-20 mA InputRemote Display,
Chart Recorder, Etc.
-+
RI- I+MA OUT
13 2
RELAY13 2 1
24 V
MA OUT
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
16
External Relay, Analog Output, & Digital I/O Connections The relay, analog out, and digital I/O expansion modules PDA1004, PDA1011, and PDA1044 are connected to the meter using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system. Note: The jumper located between the RJ45 connectors of the PDA1044 must be removed on the second
digital I/O module in order for the system to recognize it as module #2.
Warning!
Do not connect or disconnect the expansion modules with the power on! More detailed instructions are provided with each optional expansion module.
Interlock Relay Feature As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page 40). In one example, dry interlock contacts are connected in series to one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 16. Interlock Connections
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
17
Setup and Programming
The meter is factory calibrated prior to shipment to read in milliamps and volts, depending on the input selection. The calibration equipment is certified to NIST standards.
Overview There are no jumpers to set for the meter input selection. Setup and programming is done through the front panel buttons. After power and input signal connections have been completed and verified, apply power to the meter.
Front Panel Buttons and Status LED Indicators
Button Symbol
Description LED Status
Menu 1-8 Alarm 1-8 indicator
Right arrow/F1
1-8 M
Flashing: Relay in manual control mode
Up arrow/F2
A B C
Channel displayed
Enter/F3 1-4
Flashing: Relay interlock switch open
Notes: F4 is a digital input. Alarms 5-8 are enabled when relay expansion module installed.
Note: LEDs for relays in manual mode flash with the “M” LED every 10 seconds.
Press the Menu button to enter or exit the Programming Mode at any time.
Press the Right arrow button to move to the next digit during digit or decimal point programming.
Press or hold the Up arrow button to scroll through the menus, decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
18
MeterView® Pro Software The meter can also be programmed using the PC-based MeterView Pro software included with the meter. This software can be installed on any Microsoft® Windows® (XP/Vista/7/8/10) computer by connecting the meter’s onboard USB. The meter is powered by the USB connection, so there is no need to wire anything prior to programming the meter, though USB is intended only for meter configuration.
MeterView Pro Installation 1. Connect one end of the provided USB cable to the meter and the other end to the computer.
The computer will automatically install the driver software it needs to talk to the meter. Only one meter may be connected at a time. Attaching multiple meters will cause a conflict with the meter software.
2. Once the driver is installed, an AutoPlay dialog should appear for the drive “MAINSTAL.” Click “Open folder to view files.” If the computer does not display an AutoPlay dialog for the drive “MAINSTAL,” you should open My Computer and double-click on the drive labeled “MAINSTAL.”
3. Double-click on the file named “MAStart.” The program will open a few windows and install two programs on your computer. Simply follow the onscreen instructions until you see one of the dialogs below. If you receive a “User Account Control” warning, click “Yes.”
4. If there is an update available, click the “Update” button to install the new version. Otherwise, click “Configure” to begin programming your meter.
Note: If you decide to update your MeterView Pro software, once the installation has completed, you will be asked if you want to update the setup files located on the meter itself. This way, you will always have the most current version on the meter for future installs.
Warning!
Do not unplug the meter while the new installation files are being written to it. The meter will display uwrite during the process and you will receive an onscreen notification once the process is complete.
Data logging for one meter at a time is available with MeterView Pro software. More advanced data acquisition may be accomplished by using any Modbus RTU compliant software. Additional information regarding configuration and monitoring of the meter using MeterView Pro software is available online. Go to www.predig.com/meterview-pro.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
19
Display Functions & Messages The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting Description
setup Setup Enter Setup menu
Input Input Enter Input selection menu
Ch-A* Input Set input type for channel A (*or B)
mA 4-20 mA Set meter for 4-20 mA input
volt 0-10 VDC Set meter for 10 VDC input
total Total Enable/disable totalizer functions
YES Yes Enable totalizer functions
No No Disable totalizer functions
units Unit Select the display units/tags
Ch-A* Rate unit Set rate unit or tag for channel A (*or B)
Ch-C Math unit Set unit or tag for math channel C
Tot-A* Total unit Set total unit or tag for channel A (*or B)
Gtot-A* Grand total unit
Set grand total unit or tag for channel A (*or B)
Dec pt Decimal point
Set decimal point
Ch-A* Decimal point
Set decimal point for channel A (*or B or C)
Rate* Rate Set rate decimal point (*channel A and B only)
Total* Total Set total decimal point (*channel A and B only)
Gtotal* Grand total Set grand total decimal point (*channel A and B only)
prog Program Enter the Program menu
InCAL Input calibration
Enter the Input Calibration menu
SCAL A Scale A Enter the Scale menu for channel A
SCAl B Scale B Enter the Scale menu for channel B
Cal A Calibrate A Enter the Calibration menu for channel A
Display Parameter Action/Setting Description
Cal B Calibrate B Enter the Calibration menu for channel B
Inp 1 Input 1 Calibrate input 1 signal or program input 1 value
Dis 1 Display 1 Program display 1 value
Inp 2 Input 2 Calibrate input 2 signal or program input 2 value (up to 32 points)
Dis 2 Display 2 Program display 2 value (up to 32 points)
Error Error Error, calibration not successful, check signal or programmed value
tsetup Total setup Enter the Total Setup menu
Ch-A* Channel A Setup the total for channel A (*or B)
tbase Time base Program total time base
T Cf Total conversion factor
Program total conversion factor
Gt CF Grand total conversion factor
Program grand total conversion factor
treset Total reset Program total reset mode: auto or manual
Ch-A* Channel A Set total reset modes for channel A (*or B)
T rst Total reset Program total reset mode: auto or manual
Gt rst Grand total reset
Program grand total reset mode: auto or manual
T dly Time delay Program automatic reset time delay
dsplay Display Enter the Display menu
Line 1 Line 1 Assign the upper display parameter
Line 2 Line 2 Assign the lower display parameter
D Ch-A Display Ch-A
Assign display to channel A
D Ch-B Display Ch-B
Assign display to channel B
D Ch-C Display Ch-C
Assign display to channel C (math)
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
20
Display Parameter Action/Setting Description
D Ab Display AB Alternate display of channel A & B
D AC Display AC Alternate display of channel A & C
D BC Display BC Alternate display of channel B & C
D AbC Display ABC
Alternate display of channel A, B, & C
D t-a Display total A
Assign display to channel A total
D t-b Display total B
Assign display to channel B total
D gt-a Display grand total A
Assign display to channel A grand total
D gt-b Display grand total B
Assign display to channel B grand total
D rt-a Display rate and total A
Alternate display of channel A rate and total
D rt-b Display rate and total B
Alternate display of channel B rate and total
Drgt-a Display rate and grand total A
Alternate display of channel A rate and grand total
Drgt-b Display rate and grand total B
Alternate display of channel B rate and grand total
D set1* Display Set 1*
Displays relay 1(*through 8) set point.
D Hi-A Display high A
Display high value of channel A
D Lo-A Display low A
Display low value of channel A
D HL-A Display high/low A
Alternate between high/low value of channel A
D Hi-B Display high B
Display high value of channel B
D Lo-B Display low B
Display low value of channel B
D HL-B Display High/low B
Alternate between high/low value of channel B
Display Parameter Action/Setting Description
D Hi-C Display high C
Display high value of channel C
D Lo-C Display low C
Display low value of channel C
D HL-C Display High/low C
Alternate between high/low value of channel C
D a-u Display A and units/tags
Alternate display of channel A and the unit/tag
D B-u Display B and units/tags
Alternate display of channel B and the unit/tag
D C-u Display C and units/tags
Alternate display of channel C and the unit/tag
D ta-u Display total A and total units A
Alternate display of channel A total and total units
D tb-u Display total B and total units B
Alternate display of channel B total and total units
D tab Display total A and B
Alternate display of channel A total and channel B total
D TAbC Display total A, B, and math channel C
Alternate display of channel A total, channel B total, and math result channel C
m bus Display Modbus
Display Modbus input register
D off Display off Display blank line 2
D unit Display unit Display line 1 channel units
d-Inty Display intensity
Set display intensity level from 1 to 8
RELaY Relay Enter the Relay menu
Assign Assignment Assign relays to channels or Modbus
Asign1* Assign 1 Relay 1 (*through 8) assignment
Ch-A* Channel A* Assign relay to channel A (*or B or C)
Rate* Rate Assign relay to rate (*channel A and B only)
Total* Total Assign relay to total (*channel A and B only)
Gtotal* Grand total Assign relay to grand total (*channel A and B only)
m bus Modbus Assign relay to Modbus register
RLY 1* Relay 1 Relay 1 (*through 8) setup
Act 1 Action 1 Set relay 1 action
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
21
Display Parameter Action/Setting Description
Auto Automatic Set relay for automatic reset
Set 1 Set 1 Enter relay 1 set point
RST 1 Reset 1 Enter relay 1 reset point
A-nman Auto-manual Set relay for auto or manual reset any time
LatCH Latching Set relay for latching operation
Lt-CLr Latching-cleared
Set relay for latching operation with manual reset only after alarm condition has cleared
Altern Alternate Set relay for pump alternation control
SAmpl Sample Set relay for sample time trigger control
Off Off Turn relay off
FaiLSF Fail-safe Enter Fail-safe menu
FLS 1* Fail-safe 1 Set relay 1 (*through 8) fail-safe operation
on On Enable fail-safe operation
off Off Disable fail-safe operation
DeLAY Delay Enter relay Time Delay menu
DLY 1* Delay 1 Enter relay 1 (*through 8) time delay setup
On 1 On 1 Set relay 1 On time delay
OFF 1 Off 1 Set relay 1 Off time delay
break Loop break Set relay condition if loop break detected
Break1* Break 1 Set relay 1 (*through 8) break condition
ignore Ignore Ignore loop break condition (Processed as a low signal condition)
On On Relay goes to alarm condition when loop break detected
Off Off Relay goes to non-alarm condition when loop break detected
Aout Analog output
Enter the Analog output scaling menu
Aout 1* Aout Channel
Analog Output source channel (*1-3)
Dis 1 Display 1 Program display 1 value
Display Parameter Action/Setting Description
Out 1 Output 1 Program output 1 value (e.g. 4.000 mA)
Dis 2 Display 2 Program display 2 value
Out 2 Output 2 Program output 2 value (e.g. 20.000 mA)
reset Reset Press Enter to access the Reset menu
Rst Hi Reset high Press Enter to reset max display
Rst Lo Reset low Press Enter to reset min display
Rst HL Reset high & low
Press Enter to reset max & min displays
Tot a Reset total A
Press Enter to reset channel A total
Tot b Reset total B
Press Enter to reset channel B total
Gtot a Reset grand total A
Press Enter to reset channel A grand total
Gtot b Reset grand total B
Press Enter to reset channel B grand total
Tot ab Reset totals A and B
Press Enter to reset channels A and B totals
Gt ab Reset grand totals A and B
Press Enter to reset channels A and B grand totals
Contrl Control Enter Control menu
Auto Automatic Press Enter to set meter for automatic operation
mAn Manual Press Enter to manually control relays or analog output operation
pass Password Enter the Password menu
Pass 1 Password 1 Set or enter Password 1
Unlock Unlocked Program password to lock meter
Locd Locked Enter password to unlock meter
Pass 2 Password 2 Set or enter Password 2
Pass 3 Password 3 Set or enter Password 3
Total Total reset password
Set or enter a total reset password
Gtotal Grand total password
Set or enter a grand total reset password
999999 -99999
Flashing Over/under range condition
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
22
Main Menu The main menu consists of the most commonly used functions: Reset, Control, Setup, and Password.
Press Menu button to enter Programming Mode then press the Up arrow button to scroll main menu.
Press Menu, at any time, to exit and return to Run Mode. Changes made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to memory only after pressing Enter.
The display moves to the next menu every time a setting is accepted by pressing Enter.
Setting Numeric Values The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value. The digit being changed is displayed brighter than the rest. Press and hold up arrow to auto-increment the display value. Press the Enter button, at any time, to accept a setting or Menu button to exit without saving changes.
00 4.000 00 4 .000 00 5 .000
dis 1 dis 1 dis 1
Next Setting
Select Next Digit
IncrementDigitalValue
AcceptSetting
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
23
Setting Up the Meter (setup) The Setup menu is used to select:
1. Input signal the meter will accept for channel A and channel B
2. Units for A & B rate, total & grand total, and C
3. Decimal positions for A & B rate, total, and grand total, and C
4. Program the meter using the scale, calibrate, & total functions
5. Display parameters and intensity
6. Relay assignments and operation
7. 4-20 mA analog output scaling
Press the Menu button to exit at any time.
Setting the Input Signal (Input) Enter the Input menu to set up the meter to display current (mA) or voltage (volt) inputs for channel A and channel B. The current input is capable of accepting any signal from 0 to 20 mA. Select current input to accept 0-20 mA or 4-20 mA signals. The voltage input is capable of accepting any signal from -10 to +10 VDC. Select voltage input to accept 0-5, 1-5, 0-10, or 10 VDC signals. Channel C is the Math Function calculation, which is set up in the Advanced Features menu.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
24
Setting the Totalizer Features (total) To simply not display the total, select alternative display parameters in the display (dsplay) menu. Enable or disable the totalizer features by selecting “Yes” or “no” after the input type has been set up for each channel. If the totalizer features are disabled, all the totalizer features and functions are hidden from the menus. Level and process meter features and functions are added to the menus. If disabling the total parameter by selecting no, please refer to the PD6060 manual available at www.predig.com for instructions on setting up the meter parameters. Notes: 1. The totalizer continues working in the background.
2. When selecting "no" for Total for a channel, the meter now functions as a PD6060 Dual-Input Process Meter for parameters that affect that channel. We strongly suggest that you download and use the PD6060 instruction manual from our website (www.predig.com) while in this mode of operation.
Setting the Rate, Total, & Grand Total Units/Tags (units) Enter the channel A and B rate, total, grand total, and math channel C units (or custom tags) that will be displayed if alternating units is selected in the units menu, or d unit is selected as the lower display parameter. See the flow chart on page 23 for details on accessing the Units menu and parameters. Ch-A and Ch-B set the rate units, tot-A and tot-B the total units, and Gtot-A and Gtot-B the grand total units. Ch-C sets the units for the math channel C. See the flow chart on page 30 to access the display menu to show the unit or tag on the lower display. The engineering units or custom legends can be set using the following 7-segment character set:
Display Character Display Character Display Character Display Character
0 0 C C k K v V
1 1 c c l L uw w
2 2 d d nm m x X
3 3 e E n n y Y
4 4 f F O O z Z
5 5 g G o o - -
6 6 9 g p P / /
7 7 H H q q [ ]
8 8 h h r r ] [
9 9 I I s S = =
A A I i t t ! Degree(<)
b b j J u u Space
Notes: Degree symbol represented by (<) if programming with MeterView® Pro. The letters “m” and “w” use two 7-segment LEDs each; when selected the characters to the right are shifted one position. Press and hold up arrow to auto-scroll the characters in the display.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
25
Setting the Decimal Point (dEc pt) The decimal point for any channel, rate, total, or grand total, may be set with up to five decimal places or with no decimal point at all. Pressing the Right arrow moves the decimal point one place to the right until no decimal point is displayed, and then it moves to the leftmost position. Pressing the Up arrow moves the decimal point one place to the left. There are seven decimal points to set up for three channels: Ch-A rate, total, and grand total; Ch-B rate, total, and grand total; and Ch-C. After the decimal points are set up, the meter moves to the Program menu.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
26
Programming the Rate/Totalizer (prog) It is very important to read the following information, before proceeding to program the meter:
The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards.
Use the Scale menu to scale the process input (e.g. 4-20 mA). A calibrated signal source is not needed to scale the meter.
Use the Calibrate menu to apply a signal from a calibrator or a flowmeter. The Program menu contains the following menus:
1. Scale channel A and B without a signal source 2. Calibrate channel A and B with a calibrated signal source 3. Channel A and B total time base & conversion factors 4. Channel A and B grand total time base & conversion factors 5. Channel A and B reset modes for total & grand total
The process inputs may be calibrated or scaled to any display value within the range of the meter.
Additional parameters, not needed for most applications, are found in the Advanced Features menu; see Advanced Features Menu, page 43.
Input Calibration Method (InCAL) There are two methods of calibrating (or scaling) the display for each input channel to show the correct engineering units.
Use the Scale menu to enter the scaling without a signal source.
Use the Calibrate menu to apply a signal from a signal source. Note: The Scale and Calibrate functions are exclusive of each other. The meter uses the last function programmed. Only one of these methods can be employed at a time. The Scale and Calibrate functions can use up to 32 points (default is 2). The number of points should be set in Scale and Calibrate accordingly under the Number of Points (nopts) menu selection prior to scaling and calibration of the meter, see page 47 for details.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
27
Scaling the Meter without a Signal Source (SCAL-A, SCAL-B) The process inputs (4-20 mA, 10 VDC) can be scaled to display the process variables in engineering units. A signal source is not needed to scale the meter; simply program the inputs and corresponding display values. From the INCAL menu, select channel A or B, followed by SCal-A or SCal-B, and then set the signal input value and display value for each of the scaling points (default is two).
Scaling the Meter for Channel A (SCal-A)
Scaling the Meter for Channel B (SCal-B)
For instructions on how to program numeric values see Setting Numeric Values, page 22.
Error Message (Error) An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to input 2 during calibration or scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or programmed. The error message might be caused by any of the following conditions: 1. Input signal is not connected to the proper terminals or it is connected backwards. 2. Wrong signal selection in Setup menu. 3. Minimum input span requirements not maintained. 4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
Input Range Input 1 & Input 2 Span
4-20 mA 0.15 mA
10 VDC 0.01 VDC
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
28
Calibrating the Meter with External Source
To scale the meter without a signal source, refer to Scaling the Meter without a Signal Source (SCAL-A, SCAL-B), page 27.
Warm up the meter for at least 15 minutes before performing calibration to ensure specified accuracy.
The meter can be calibrated to display the process variables in engineering units by applying the appropriate input signal and following the calibration procedure. The use of a calibrated signal source is strongly recommended to calibrate the meter.
Calibrating the Meter for Channel A (CAL-A)
Calibrating the Meter for Channel B (CAL-B)
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
29
Total and Grand Total Setup The time base and total conversion factor, and grand total conversion factor for input channels A and B are located in the Totalizer Setup menu. The time base is based on the rate of flow. Total & grand total conversion factors for channel A and B are programmed independently. The total and grand total have their own independent settings. This means that one can be displaying the value in gallons while the other displays in million gallons, liters, m3, etc.
Total & Grand Total Reset Total reset menus are located in the Program menu. The totals can be programmed for manual or automatic reset. In the automatic reset mode, a programmable time delay is available to reset the total or grand total after the assigned preset is reached.
Password Protected and Non-Resettable Total The total and grand total can be password-protected to prevent unauthorized resets. The grand total can be programmed as a non-resettable total, see page 42 for details.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
30
Setting the Display Parameters & Intensity (dsplay) Display line 1 (line 1) can be programmed to display:
1. Ch-A rate (D Ch-A) 2. Ch-B rate (D Ch-B) 3. Ch-C math channel (D Ch-C) 4. Toggle Ch-A & Ch-B rate (D
AB) 5. Toggle Ch-A rate and Ch-C (D AC) 6. Toggle Ch-B rate and Ch-C (D BC) 7. Toggle Ch-A & Ch-B rate, and Ch-C (D ABC) 8. Ch-A total (D T-A) 9. Ch-B total (D T-B) 10. Ch-A grand total (D GT-A) 11. Ch-B grand total (D GT-B) 12. Toggle Ch-A rate and total (D RT-A) 13. Toggle Ch-B rate and total (D RT-B) 14. Toggle Ch-A rate and grand total (DRGT-A) 15. Toggle Ch-B rate and grand total (DRGT-B)s 16. Relay set points (1-8) (DSET 1 to DSET 8) 17. Max, min, and max & min values for
Ch-A, Ch-B, or Ch-C (D Hi-A to d HL-C) 18. Toggle Ch-A rate & units (d A-u) 19. Toggle Ch-B rate & units (d B-u) 20. Toggle Ch-C & units (d C-u) 21. Toggle Ch-A total & units (d TA-u) 22. Toggle Ch-B total & units (d TB-u) 23. Toggle Ch-A total and Ch-B total (d tAb) 24. Toggle Ch-A total, Ch-B total, and the sum of total A and
total B (d tABC). Notes: The sum of total A and B for t ABC is independent of channel C programming. Channel C may be used normally by a different display selection even when D tABC is selected for one of the two displays.
25. Modbus input (nm bus) Display line 2 (Line 2) can be programmed to display:
1. All options for display line 1 2. Off, with no display (d ofF) 3. Engineering units for any single channel, total, or grand total
Display Intensity: The meter has eight display intensity levels to give the best performance under various lighting conditions. Select intensity 8 for outdoor applications. The default intensity setting is 8. After setting up the input and display, press the Menu button to exit programming and skip the rest of the setup menu.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
31
Setting the Relay Operation (relay) This menu is used to set up the assignment and operation of the relays.
Caution!
During setup, the relays do not follow the input and they will remain in the state found prior to entering the Relay menu.
1. Relay assignment
a. Channel A rate, total, or grand total b. Channel B rate, total, or grand total c. Channel C (Math channel) d. Modbus
2. Relay action a. Automatic reset only (non-latching) b. Automatic + manual reset at any time (non-latching) c. Latching (manual reset only) d. Latching with Clear (manual reset only after alarm condition has cleared) e. Pump alternation control (automatic reset only) f. Sampling (the relay is activated for a user-specified time) g. Off (relay state controlled by Interlock feature)
3. Set point 4. Reset point 5. Fail-safe operation
a. On (enabled) b. Off (disabled)
6. Time delay a. On delay (0-999.9 seconds) b. Off delay (0-999.9 seconds)
7. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
!
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
32
Setting the Relay Assignment (asSign) Relays may be assigned to Channel A (rate, total, or grand total), Channel B (rate, total, or grand total), Channel C (Math channel), or Modbus input.
Setting the Relay Action (Act) Operation of the relays is programmed in the Action menu. The relays may be set up for any of the following modes of operation:
1. Automatic reset (non-latching) 2. Automatic + manual reset at any time (non-latching) 3. Latching (manual reset only, at any time) 4. Latching with Clear (manual reset only after alarm condition has cleared) 5. Pump alternation control (automatic reset only) 6. Sampling (the relay is activated for a user-specified time) 7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
33
Programming Set and Reset Points High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset points. Minimum deadband is one display count. If the set and reset points are programmed with the same value, the relay will reset one count below the set point. Note: Changes are not saved until the reset point has been accepted.
Setting Fail-Safe Operation In fail-safe mode of operation, the relay coil is energized when the process variable is within safe limits and the relay coil is de-energized when the alarm condition exists. The fail-safe operation is set independently for each relay. Select on to enable or select off to disable fail-safe operation.
Programming Time Delay The On and Off time delays may be programmed for each relay between 0 and 999.9 seconds. The relays will transfer only after the condition has been maintained for the corresponding time delay. The On time delay is associated with the set point. The Off time delay is associated with the reset point.
Relay Action for Loss of 4-20 mA Input (Loop Break) The loop break feature is associated with the 4-20 mA input. Each relay may be programmed to go to one of the following conditions when the meter detects the loss of the input signal (i.e. < 0.005 mA):
1. Turn On (Go to alarm condition) 2. Turn Off (Go to non-alarm condition) 3. Ignore (Processed as a low signal condition)
Note: This is not a true loop break condition; if the signal drops below 0.005 mA, it is interpreted as a “loop break” condition.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
34
Relay and Alarm Operation Diagrams The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To detect a new alarm condition, the signal must go below the set point, and then go above it.
Low Alarm Operation (Set < Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back “on”, signal must go above set point and then go below it.
High Alarm with Fail-Safe Operation (Set > Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will go to alarm state.
Low Alarm with Fail-Safe Operation (Set < Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will go to alarm state.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
35
Pump Alternation Control Operation
Relay Sampling Operation
When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms. The sample time can be programmed between 0.1 and 5999.9 seconds.
Set
Reset
Relay
LED
Input
SampleTime
SampleTime
SampleTime
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
36
Signal Loss or Loop Break Relay Operation The following graph shows the loop break relay operation for a high alarm relay.
When the meter detects a break in the 4-20 mA loop, the relay will go to one of the following selected actions:
1. Turn On (Go to alarm condition) 2. Turn Off (Go to non-alarm condition) 3. Ignore (Processed as a low signal condition)
Time Delay Operation The following graphs show the operation of the time delay function.
When the signal crosses the set point, the On time delay timer starts and the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the On time delay timer resets and the relay does not change state. The same principle applies to the Off time delay. Note: If “Automatic or Manual (A-mAn)” reset mode is selected, the LED follows the reset point and not
the relay state when the relay is acknowledged.
Relay
LED
Input
Loop Break = Ignore
de-energized energized
off on
Relay
LED
Loop Break = Off
Relay
LED
Loop Break = On
Set
Reset
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
37
Relay Operation Details Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2 or 4 optional internal relays and/or 4 external relays expansion module. Typical applications include high or low temperature, level, pressure or flow alarms, control applications such as simple on/off pump control, and pump alternation control for up to 8 pumps. There are four basic ways the relays can be used: 1. High or Low Alarms with Latching or Non-Latching Relays 2. Simple On/Off Control with 100% Adjustable Deadband 3. Sampling (Based on Time) 4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization When power is applied to the meter, the front panel LEDs and alarm relays will reflect the state of the input to the meter. The following table indicates how the alarm LEDs and relays will react on power-up based on the set and reset points:
Fail-Safe Operation The following table indicates how the relays behave based on the fail-safe selection for each relay: Note: NO = Normally Open,
NC = Normally Closed. This refers to the condition of the relay contacts when the power to the meter is off.
Front Panel LEDs
The LEDs on the front panel provide status indication for the following: The meter is supplied with four alarm points that include front panel LEDs to indicate alarm conditions. This standard feature is particularly useful for alarm applications that require visual-only indication. The LEDs are controlled by the set and reset points programmed by the user. When the display reaches a set point for a high or low alarm, the corresponding alarm LED will turn on. When the display returns to the reset point the LED will go off. The front panel LEDs responds differently for latching and non-latching relays. For non-latching relays, the LED is always off during normal condition and always on during alarm condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition). For latching relays, the alarm LEDs reflects the status of the relays, regardless of the alarm condition. The following tables illustrate how the alarm LEDs function in relation to the relays and the acknowledge button (Default: F3 key assigned to ACK).
Alarm # HI or LO
Alarm Set
Point Reset Point
Power-Up Reading
Relay & LED
1 HI 1000 500 499 Off
2 LO 700 900 499 On
3 LO 250 400 499 Off
4 HI 450 200 499 On
Fail-Safe Selection
Non-Alarm State Alarm State Power Failure
NO NC NO NC Off Open Closed Closed Open Relays go to
non-alarm state
On Closed Open Open Closed Relays go to alarm state
LED Status LED Status
1 Alarm 1 5 Alarm 5
2 Alarm 2 6 Alarm 6
3 Alarm 3 7 Alarm 7
4 Alarm 4 8 Alarm 8
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
38
Latching and Non-Latching Relay Operation The relays can be set up for latching (manual reset) or non-latching (automatic reset) operation.
The On and Off terminology does not refer to the status of the relay’s coil, which depends on the fail-safe mode selected.
Warning!
In latching relay mode, latched relays will reset (unlatch) when power is cycled.
Non-Latching Relay (Auto)
In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm finally goes away, the relay automatically resets and the LED also goes off.
Non-Latching Relay (A-man)
In this application, the meter is set up for automatic and manual reset at any time (non-latching relay). The LED and the relay automatically reset when the meter returns to the normal condition. The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm condition still exists. This causes the relay to reset, but the LED stays on until the meter returns to the normal condition.
Latching Relay (LatcH)
In this application, the meter is set up for manual reset at any time. Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off the LED.
Latching Relay (Lt-Clr)
In this application, the meter is set up for manual reset only after the signal passes the reset point (alarm condition has cleared). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm is acknowledged after it returns to the normal state, the LED and the relay go off. Notice that the LED remains on, even after the meter returns to the normal condition. This is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the alarm condition.
Relay terminology for following tables
Terminology Relay Condition On Alarm (Tripped)
Off Normal (Reset)
Ack Acknowledged
Automatic reset only
Condition LED Relay Normal Off Off
Alarm On On
Ack (No effect) On On
Normal Off Off
Automatic + manual reset at any time
Condition LED Relay Normal Off Off
Alarm On On
Normal Off Off
Next Alarm On On
Ack On Off
Normal Off Off
Manual reset any time Condition LED Relay Normal Off Off Alarm On On Ack Off Off
Manual reset only after alarm condition has cleared
Condition LED Relay Normal Off Off Alarm On On Ack (No effect) On On Normal On On Ack Off Off
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
39
Acknowledging Relays There are two ways to acknowledge relays programmed for manual reset:
1. Via the programmable front panel function keys F1-F3 (Default: F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of the digital inputs and the +5 V terminals on the digital I/O modules, or using the F4 digital input, which is triggered with a contact closure to COM, or with an active low signal (see page 15).
When the ACK button or the assigned digital input is closed, all relays programmed for manual reset are acknowledged.
Figure 17. Acknowledge Relays w/Function Key or Digital Input
Pump Alternation Control Applications (Altern) For pump control applications where two or more similar pumps are used to control the level of a tank or a well, it is desirable to have all the pumps operate alternately. This prevents excessive wear and overheating of one pump over the lack of use of the other pumps. Up to 8 relays can be set up to alternate every time an on/off pump cycle is completed. The set points and reset points can be programmed, so that the first pump on is the first pump off.
Application #1: Pump Alternation Using Relays 1 & 2 1. Relays 1 and 2 are set up for pump alternation. 2. Relays 3 and 4 are set up for low and high alarm indication. Set and Reset Point Programming with Pump Alternation
Relay Set Point Reset Point Function 1 30.000 10.000 Controls pump 1 & 2
2 35.000 5.000 Sets dual pump trigger
3 4.000 9.000 Controls low alarm
4 40.000 29.000 Controls high alarm
Pump Alternation Operation 1. Pump #1 turns on when level reaches 30.000, when level drops below 10.000 pump #1 turns off. 2. The next time level reaches 30.000, pump #2 turns on, when level drops below 10.000, pump #2
turns off. 3. If the level doesn’t reach 35.000 pump #1 and pump #2 will be operating alternately. 4. If pump #1 cannot keep the level below 35.000 pump #2 will turn on at 35.000, then as the level drops
to 10.000 pump #1 turns off, pump #2 is still running and shuts off below 5.000. 5. Notice that with the set and reset points of pump #2 outside the range of pump #1, the first pump on
is the first pump to go off. This is true for up to 8 alternating pumps, if setup accordingly. 6. Relay #3 will go into alarm if the level drops below 4.000 and relay #4 will go into alarm if the level
exceeds 40.000. 7. Adding the 4 external relays expansion module allows using the 4 SPDT internal relays for pump
alternation and the 4 SPST external relays for high, high-high, low, and low-low alarm indication.
+5 I1 I2 I3 I4 O1 O2 O3 O4 G
DO 1-4 GND
ACK
PDA1044 Digital I/O Module1 2 3 4 5 6 7 8 9 10
DI 1-4
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
40
Setting Up the Interlock Relay (Force On) Feature Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature: 1. Access the Setup – Relay – Action menu and set the action to off. 2. In the Advanced features – User menu program any of the digital inputs to Force On any of the
internal relays (1-4). 3. Connect a switch or dry contact between the +5V terminal and the corresponding digital input (dI-1 to
dI-4) terminal. Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) – i.e. both switches must be closed to trip the relay.
Scaling the 4-20 mA Analog Output (Aout) The 4-20 mA analog outputs can be scaled to provide a 4-20 mA signal for any display range selected. To select the channel and source assignments the analog outputs are assigned to, see Analog Output Source on page 50. No equipment is needed to scale the analog outputs; simply program the display values to the corresponding mA output signal. The Analog Output menu is used to program the 4-20 mA outputs based on display values.
For instructions on how to program numeric values see
Setting Numeric Values, page 22.
* *
* I f Installed
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
41
Reset Menu (reset) The Reset menu is used to reset the maximum (peak) value of Ch-A and Ch-B rate (rst Hi), minimum (valley) reading of Ch-A and Ch-B rate (rst Lo), both high and low value of Ch-A and Ch-B rate (rst HL), Ch-A total (tot A) or Ch-B total (tot B), Ch-A grand total (Gtot A) or Ch-B grand total (Gtot B), both Ch-A and Ch-B totals (tot AB), or both Ch-A and Ch-B grand totals (Gt AB).
Control Menu (Contrl) The Control menu is used to control the 4-20 mA analog output (Aout 1 only) and the relays manually, ignoring the input. Each relay and analog output can be programmed independently for manual control. Selecting automatic control sets all relays and analog output for automatic operation.
Setting Up the Password (pass) The Password menu is used for programming three levels of security to prevent unauthorized changes to the programmed parameter settings, to restrict the ability to reset the totals and grand totals, and to program the non-resettable totalizer.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
Protecting or Locking the Meter Functions Enter the Password menu and program a six-digit password. For instructions on how to program numeric values see Setting Numeric Values, page 22.
Once Manual mode is initiated on any relay or
analog output, an LED labeled “M” is turned
on. Every few seconds, all LEDs representing
outputs that are in Manual mode, as well as
the “M” LED flash. This process will continue
as long as any output is in manual mode.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
42
Total Reset Password & Non-Resettable Total The total and the grand total can be password-protected to prevent unauthorized total resets. The grand total can be programmed as a non-resettable total by entering the password “050873”.
Caution!
Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled.
Making Changes to a Password Protected Meter If the meter is password protected, the meter will display the message Locd (Locked) when the Menu button is pressed. Press the Enter button while the message is being displayed and enter the correct password to gain access the menu. After exiting the programming mode, the meter returns to its password protected condition.
Disabling Password Protection To disable the password protection, access the Password menu and enter the correct password twice, as shown below. The meter is now unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the message unLoc (unlocked) and the protection is disabled until a new password is programmed. If the password entered is incorrect, the meter displays the message Locd (Locked) for about two seconds, and then it returns to Run Mode. To try again, press Enter while the Locked message is displayed.
Did you forget the password? The password may be disabled by entering a master password once. If you are authorized to make changes, enter the master password 508655 to unlock the meter.
!
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
43
Advanced Features Menu To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu. Press and hold the Menu button for three seconds to access the advanced features of the meter.
Advanced Features Menu & Display Messages The following table shows the functions and messages of the Advanced Features menu in the order they appear in the menu.
Display Parameter Action/Setting
filtEr Filter Set noise filter value
Ch-A Channel A Set filter value for channel A
Ch-b Channel B Set filter value for channel B
bypASs Bypass Set filter bypass value
Ch-A Channel A Set filter bypass value for channel A
Ch-b Channel B Set filter bypass value for channel B
Round Round Set the rounding value for display variables
seriAl Serial Set serial communication parameters
SlaveId Slave ID Set slave ID or meter address
Baud Baud rate Select baud rate
Tr dLY Transmit delay
Set transmit delay for serial communication
Parity Parity Select parity Even, Odd, or None with 1 or 2 stop bits
t-byt Time byte Set byte-to-byte timeout
Display Parameter Action/Setting
SelEct Select Enter the Select menu (function, cutoff, out)
Functn Signal input conditioning
Select linear, square root, programmable exponent, or round horizontal tank function
Ch-A Channel A Select menu for channel A
Ch-b Channel B Select menu for channel B
Linear Linear Set meter for linear function and select number of linearization points
No pts Number of points
Set the number of linearization points (default: 2)
Square Square root Set meter for square root extraction
Prog E Programmable exponent
Set meter for programmable exponent and enter exponent value
nmath Math Enter the setup menu for channel C math functions
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
44
Display Parameter Action/Setting
Sunm Sum C = (A+B+P)*F
Dif Difference C = (A-B+P)*F
difabs Absolute difference
C = ((Absolute value of (A-B))+P)*F
Avg Average C = (((A+B)/2)+P)*F
nmulti Multiplication
C = ((A*B)+P)*F
Divide Divide C = ((A/B)+P)*F
Hi-ab Max of A or B
C = ((High value of channel A or B)+P)*F
Lo-ab Min of A or B
C = ((Low value of channel A or B)+P)*F
Drauw Draw C = ((A/B)-1)*F
uw Avg Weighted avg.
C = ((B-A)*F)+A
ratio Ratio C = (A/B)*F
Ratio2 Ratio 2 C = ((B-A)/A)+P)*F
Concen Concentration
C = (A/(A+B))*F
Sunm t Sum total C = (tA+tB+P)*F
Sunmgt Sum grand total
C = (GtA+GtB+P)*F
Dif t Difference of total
C = (tA-tB+P)*F
Dif gt Diff. of grand total
C = (GtA-GtB+P)*F
Tratio Total ratio C = (tA/tB)*F
t-rat2 Total ratio 2 C = ((tB-tA)/tA)*F
T pct Total percent
C = (tA/(tA+tB))*100
Const Constant Enter math equation constants
adder Adder Addition constant used in channel C math calculations (P)
factor Factor Multiplication constant used in channel C math calculations (F)
CutofF Cutoff Set low-flow cutoff
Ch-A Channel A Set low-flow cutoff for Channel A
Ch-b Channel B Set low-flow cutoff for Channel B
Count Count Set total count direction
Display Parameter Action/Setting
Ch-A Channel A Set total count direction for Channel A
Ch-b Channel B Set total count direction for Channel B
Tot C Total count Set direction of total count
Gtot C Grand total count
Set direction of grand total count
up Count up Count up
Douwn Count down
Count down
C strt Count start Enter count down start value
AoutPr Analog output programming
Program analog output parameters
Aout 1* Analog output 1
Program analog output 1 (*1-3) parameters
Source Source Select source for the 4-20 mA output
break Loop break Set analog output if loop break detected
Calib Calibrate Calibrate 4-20 mA output (internal reference source used for scaling the output)
4 nmA 4 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
20 nmA 20 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
O-rang Overrange Program mA output for display overrange
u-rang Underrange Program mA output for display underrange
nmAx Maximum Program maximum mA output allowed
nmin Minimum Program minimum mA output allowed
User User I/O Assign function keys and digital I/O
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
45
Display Parameter Action/Setting
F1* F1* function key
Assign F1 function key (*F1/F2/F3)
F4 F4 digital input
Assign F4 function (digital input)
dI I Digital input 1
Assign digital input 1 – 8, if expansion modules are connected
dO 1 Digital output 1
Assign digital output 1 – 8, if expansion modules are connected
ICal Internal calibration
Enter internal calibration (used for recalibrating the meter with a calibrated signal source)
Ch-A Channel A Perform calibration on channel A
Ch-b Channel B Perform calibration on channel B
Display Parameter Action/Setting
C CAL Current calibration
Calibrate 4-20 mA current input (internal reference source used for scaling the input)
C lo Current low Calibrate low current input (e.g. 4 mA)
C Hi Current high
Calibrate high current input (e.g. 20 mA)
v CAL Voltage calibration
Calibrate voltage input
v Lo Voltage low Calibrate low voltage input (e.g. 0 V)
v Hi Voltage high
Calibrate high voltage input (e.g. 10 V)
Diag Diagnostics Display parameter settings
LED t LED test Test all LEDs
Info Information Display software and S/N information
erase Erase Erase MeterView Pro software stored in meter’s memory
Noise Filter (filter) The noise filter is available for unusually noisy signals that cause an unstable process variable display. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged. The filter level can be set between 2 and 199. The higher the filter level, the longer the averaging time and so the longer it takes the display to settle to its final value. Setting the filter level to zero disables the filter function.
Noise Filter Bypass (bypass) The noise filter bypass changes the behavior of the meter so that small variations in the signal are filtered out but large abrupt changes in the input signal are displayed immediately. The bypass value determines the minimum amount of signal change to be displayed immediately. All signal changes smaller than the bypass value are filtered or averaged by the meter. The noise filter bypass may be set between 0.1 and 99.9% of full scale.
Rounding Feature (round) The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used in addition to the filter function. Rounding causes the display to round to the nearest value according to the rounding selected. This setting affects the last two digits, regardless of decimal point position.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
46
Modbus RTU Serial Communications (serial) The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol. The meter may be connected to a PC for initial configuration via the onboard micro USB connection. For ongoing digital communications with a computer or other data terminal equipment, an RS-232, or RS-485 option is required; see Ordering Information on page 5 for details.
Warning!
Do not connect any equipment other than Precision Digital’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Note: More detailed instructions are provided with each optional serial communications adapter.
Note: Refer to the ProVu® Modbus Register Tables located at www.predig.com for details. When using more than one meter in a multi-drop mode, each meter must be provided with its own unique address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
Changes made to the Serial menu are initialized after the MENU key is pressed or after navigating through the t-byte parameter.
Select Menu (SElect) The Select menu is used to select the signal input conditioning function applied to the inputs (linear, square root, or programmable exponent), math function for A & B, constants, low-flow cutoff, total count direction (up or down from a preset amount), and analog output programming. Multi-point linearization is part of the linear function selection.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
47
Signal Input Conditioning (Functn) The Function menu is used to select the input-to-output transfer function applied to the input signal: linear, square root, or programmable exponent. Multi-point linearization is part of the linear function selection. Each input channel signal input conditioning function is programmed independently. Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a display that is linear with respect to the input signal.
Square Root Linearization (Square) The square root function is used to calculate flow measured with a differential pressure transmitter. The flow rate is proportional to the square root of the differential pressure. Scale the meter so that the low input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the maximum flow.
Programmable Exponent Linearization (Prog E) The programmable exponent function is used to calculate open-channel flow measured with a level transmitter in weirs and flumes. The flow rate is proportional to the head height. Scale the meter so that the low input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the maximum flow. This method works well for all weirs and flumes that have a simple exponent in the flow calculation formula. For weirs and flumes with complex exponents it is necessary to use a strapping table and the 32-point linearization of the meter.
Multi-Point Linearization (Linear) Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected for each channel under the linear function. The multi-point linearization can be used to linearize the display for non-linear signals such as those from level transmitters used to measure volume in odd-shaped tanks or to convert level to flow using weirs and flumes with complex exponent.
Note: After Scale is displayed continue pressing the Enter button until the meter completes the
scaling of the input and display values.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
48
Math Function (nmath) The Math menu is used to select the math function that will determine the channel C value. These math functions are a combination of input channels A and B, and will display when channel C is selected in the Display menu. A and B refer to the rate of channel A and B. tA and tB refer to the totals of channel A and B. GtA and GtB refer to the grand totals of channel A and B. The following math functions are available.
Function Display Description Sunm Sum C = (A+B+P)*F Dif Difference C = (A-B+P)*F difabs Absolute difference C = ((Absolute value of (A-B))+P)*F Avg Average C = (((A+B)/2)+P)*F nmulti Multiplication C = ((A*B)+P)*F Divide Divide C = ((A/B)+P)*F Hi-ab Max of A or B C = ((High value of channel A or B)+P)*F Lo-ab Min of A or B C = ((Low value of channel A or B)+P)*F Drauw Draw C = ((A/B)-1)*F uw Avg Weighted avg. C = ((B-A)*F)+A ratio Ratio C = (A/B)*F Ratio2 Ratio 2 C = ((B-A)/A)+P*F Concen Concentration C = (A/(A+B))*F Sunm t Sum total C = (tA+tB+P)*F Sunmgt Sum grand total C = (GtA+GtB+P)*F Dif t Difference of total C = (tA-tB+P)*F Dif gt Diff. of grand total C = (GtA-GtB+P)*F Tratio Total ratio C = (tA/tB)*F t-rat2 Total ratio 2 C = ((tB-tA)/tA)*F T pct Total percent C = (tA/(tA+tB))*100
Math Constants (Const) The Math Constants menu is used to set the constants used in channel C math. The math functions include adder constant P, and factor constant F. The Adder constant (P) may be set from -99.999 to 999.999. The Factor constant (F) may be set from 0.001 to 999.999. The chart on page 48 details the math functions that may be selected in the Math Function menu.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
49
Low-Flow Cutoff (CutofF) The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter. The low-flow cutoff for each channel is programmed independently. The cutoff value may be programmed from 0 to 999999. The meter will display zero below the cutoff value. Programming the cutoff value to zero disables the cutoff feature.
Totalizer Count Up/Down (Count) The totalizer count up/down menu may be used to program the total and grand total to either count up from 0 when reset or count down from a programmed value when reset. Total and grand total may have their countdown numbers programmed individually from 0 to 999999.
Analog Output Programming (AoutPr) The Analog Output Programming menu is used to program the behavior of the 4-20 mA output. The following parameters and functions are programmed in this menu: 1. Source: Source for generating the 4-20 mA output 2. Overrange: Analog output value with display in overrange condition 3. Underrange: Analog output value with display in underrange condition 4. Break: Analog output value when loop break is detected 5. Max: Maximum analog output value allowed regardless of input 6. Min: Minimum analog output value allowed regardless of input
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
50
Analog Output Source The analog output source can be based on either of the input channel rate, total, or grand totals (Ch-A, Ch-B), the math channel (Ch-C), maximum stored value of either input channel (Hi-A, Hi-B), minimum stored value of either input channel (Lo-A, Lo-B), relay set points, or the Modbus input.
To base an analog output on the rate, total, or grand total of channels A or B, select the channel in the Analog Output Source menu. Then select the rate, total, or grand total as the source reference for the output, and program the output scale.
Programmable Function Keys User Menu (user) The User menu allows the user to assign the front panel function keys F1, F2, and F3, the digital input F4 (a digital input located on the signal input connector), and up to eight additional digital inputs to access most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states, etc.). This allows the meter to be greatly customized for use in specialized applications.
Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter (i.e. alarms, relay acknowledgement, reset max, min, or max & min, tare, and reset tare). The digital outputs can be used to trigger external alarms or lights to indicate these specific events.
*If installed
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
51
Function Keys & Digital I/O Available Settings Refer to the following table for descriptions of each available function key or digital I/O setting. Display Description
Rst Hi Reset the stored maximum display values for all channels
Rst Lo Reset the stored minimum display values for all channels
Rst HL Reset the stored maximum & minimum display values for all channels
relay Directly access the relay menu Set 1 Directly access the set point menu
for relay 1 (*through 8) Rly d Disable all relays until a button
assigned to enable relays (Rly E) is pressed
Rly E Enable all relays to function as they have been programmed
O Hold Hold current relay states and analog output as they are until a button assigned to enable relays (Rly E) is pressed
d Hold Hold the current display value, relay states, and analog output momentarily while the function key or digital input is active. The process value will continue to be calculated in the background.
D AbC
Scrolls values for A, B & C when activated. Keeps the last value for 10 seconds and then it returns to its assignment. Values are displayed on display line 1 and the corresponding channel and units on display line 2.
d tot
Scrolls through totals for channels A, B, and C (which is the sum of A and B). Values are displayed on display line 1.
D gtot
Scrolls through grand totals for channels A, B, and C (which is the sum of A and B). Values are displayed on display line 1.
Ln1 Hi Display maximum channel A display value on line 1
Ln1 Lo Display minimum channel A display value on line 1
Ln1 HL Display maximum & minimum channel A display values on line 1
Display Description
Ln2 Hi Display maximum channel B display value on line 2
Ln2 Lo Display minimum Channel B display value on line 2
Ln2 HL Display maximum & minimum channel B display values on line 2
Ln2 HC Display minimum channel C display value on line 2
Ln2 HC Display maximum & minimum channel C display values on line 2
LitHLC Display maximum channel C display value on line 2
F On 1 Force relay 1 (*through 4) into the on state. This function is used in conjunction with a digital input expansion module to achieve interlock functionality. See page 40 for details about interlock relays.
Contrl Directly access the control menu disabl Disable the selected function key or
digital I/O AcH Acknowledge all active relays that
are in a manual operation mode such as auto-manual or latching
Reset Directly access the reset menu Rst t Reset totals for all channels Rst gt Reset grand totals for all channels Rst ta Reset total for channel A Rst ga Reset grand total for channel A Rst tb Reset total for channel B Rst gb Reset grand total for channel B nmenu Mimic the menu button functionality
(digital inputs only) rigHt Mimic the right arrow/F1 button
functionality (digital inputs only) up Mimic the up arrow/F2 button
functionality (digital inputs only) Enter Mimic the enter/F3 button
functionality (digital inputs only) Alnm 1 Provide indication when alarm 1
(*through 8) has been triggered (digital outputs only)
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
52
Internal Calibration (ICAL) The meter is factory calibrated prior to shipment to read in milliamps and volts depending on
the input selection. The calibration equipment is certified to NIST standards.
The use of calibrated signal sources is necessary to perform the internal calibration of the meter. Check calibration of the meter at least every 12 months. Each input and input type must be recalibrated separately.
Notes: 1. If meter is in operation and it is intended to accept only one input type (e.g. 4-20 mA),
recalibration of other input is not necessary. 2. Allow the meter to warm up for at least 15 minutes before performing the internal calibration
procedure.
The Internal calibration menu is part of the Advanced Features menu. 1. Press and hold the Menu button for three seconds to access the advanced features of the meter. 2. Press the Up arrow button to scroll to the Internal calibration menu (ICAL) and press Enter. 3. Select channel A (Ch-A) or channel B (Ch-b) and press enter. 4. The meter displays either current calibration (C CAL) or voltage calibration (v CAL), according to the
input setup. Press Enter to start the calibration process. Example of Internal Calibration for current input:
5. The meter displays low input current message (C lo). Apply the low input signal and press Enter. The display flashes for a moment while the meter is accepting the low input signal.
6. After the display stops flashing, a number is displayed with the leftmost digit brighter than the rest. The bright digit is the active digit that can be changed by pressing the Up arrow button. Press the Right arrow button to move to the next digit.
7. Set the display value to correspond to the input signal being calibrated, typically 4.000 mA.
8. The display moves to the high input calibration (C Hi). Apply the high input signal and press Enter.
9. Set the display for the high input calibration, in the same way as it was set for the low input calibration, typically 20.000 mA.
The graphic above shows the calibration of the current input. The voltage input is calibrated in a similar way. Tips:
Low and high input signals can be any valid values within the range of the meter.
Observe minimum input span requirements between input 1 and input 2.
Low input should be less than high input signal.
Error Message (Error) An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to input 2 during calibration or scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or programmed. The error message might be caused by any of the following conditions: 1. Input signal is not connected to the proper terminals, or it is connected backwards. 2. Wrong signal selection in Setup menu. 3. Minimum input span requirements not maintained (see page 27).
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
53
Meter Operation The meter is capable of accepting two input channels (A and B) of either current (0-20 mA, 4-20 mA) or voltage signals (0-5 V, 1-5 V, 0-10 V, 10 V) and displaying these signals in engineering units from -99999 to 999999 (e.g. a 4-20 mA signal could be displayed as -50.000 to 50.000). A totalizer can be programmed to count the scaled engineering units, interpreting it as count per second, minute, hour, or day. The scaled rate and total for each channel can be displayed on the top or bottom displays. A math function channel (C) is available to perform operations on channel A and B rates or totals, with adder and factor constants, and display the results. Engineering units or tags may be displayed with these three channels. The dual-line display can be customized by the user. Typically, display line 1 is used to display the math channel C, while line 2 is used to alternate between displaying input channels A and B rate or total. Additionally, the meter can be set up to display any input or math channel on line 1 and a unit or tag on line 2. The relays and analog output can be programmed to operate based on any input or math channel.
Front Panel Buttons Operation Button Symbol Description
Press to enter or exit Programming Mode, view settings, or exit max/min readings
Press to reset max/min readings or other parameter/function assigned through the User menu
Press to display max/min readings for channel A or other parameter/function assigned through the User menu
Press to acknowledge relays or other parameters/function assigned through the User menu
Function Keys Operation During operation, the programmable function keys operate according to the way they have been programmed in the Advanced Features – User menu. The table above shows the factory default settings for F1, F2, and F3.
F4 Operation A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal. During operation, F4 operates according to the way is has been programmed in the Advanced Features – User menu.
Maximum/Minimum Readings The max & min readings (peak & valley) reached by the process can be displayed either continuously or momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the digital inputs in the User menu. 2. Display continuously by assigning either display to max/min through the Display menu.
Any of the F1-F3 function keys (buttons) and the digital inputs can be programmed to reset the max & min readings. The meters are set at the factory to display the max/min reading by pressing the Up arrow/F2 button and to use the Right arrow/F1 button to reset the max/min. To display max and min channel A reading using function key with factory defaults: 1. Press Up arrow/F2 button to display minimum reading of channel A since the last reset/power-up.
The display will then display the maximum reading of channel A since the last reset/power-up. 2. To reset max/min press Right arrow/F1 button. The max & min displays are reset to actual values. 3. Press Menu to exit max/min display reading.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
54
Troubleshooting The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see. If the meter is not working as expected, refer to the Diagnostics menu and recommendations below.
Diagnostics Menu (diag) The Diagnostics menu is located in the Advanced Features menu. To access the Diagnostics menu, see Advanced Features Menu, page 43. This menu allows the user to test the functionality of all the meter LEDs, check the meter’s software and version information, and erase the MeterView Pro software installation files from the meter. Press the Enter button to view the settings and the Menu button to exit at any time. For a description of the diagnostic messages, see Advanced Features Menu & Display Messages, page 43.
Determining Software Version To determine the software version of a meter:
1. Go to the Diagnostics menu (diAG) and press Enter button. 2. Press Up arrow button and scroll to Information menu (Info). 3. Press Enter to access the software number (SFT) and version (UER) information. Write down the
information as it is displayed. Continue pressing Enter until all the information is displayed. 4. The meter returns to Run Mode after displaying all the settings.
Reset Meter to Factory Defaults When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults. Instructions to load factory defaults: 1. Enter the Advanced Features menu. See Advanced Features Menu, page 43. 2. Press Up arrow to go to Diagnostics menu 3. Press and hold Right arrow for three seconds, press
Enter when display flashes reset. Note: If Enter is not pressed within three seconds, the display returns to Run Mode.
4. The meter goes through an initialization sequence (similar as on power-up), and loads the factory default settings.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
55
Factory Defaults & User Settings The following table shows the factory setting for most of the programmable parameters on the meter.
Parameter Display Default Setting
Input type Input
Input type, channel A
Ch-A 4-20 mA
Input type, channel B
Ch-B 4-20 mA
Total, channel A Ch-A Yes
Total, channel B Ch-B Yes
Units units
Rate unit, channel A Ch-A mA-A
Rate unit, channel B Ch-B mA-b
Unit, channel C Ch-C mA-C
Total unit, channel A Tot-A tot-A
Grand total unit, ch-A
Gtot-A Gtot-A
Total unit, channel B Tot-b tot-b
Grand total unit, ch-B
Gtot-b Gtot-B
Decimal Point Dec pt
Rate, channel A rate 3
Total, channel A Total 1
Grand total, channel A
gtotal 0
Rate, channel B rate 3
Total, channel B Total 1
Grand total, channel B
gtotal 0
Channel C Ch-C 3
Number of points No pts
Number of points, ch A
Ch-A 2
Number of points, ch B
Ch-B 2
Scaling, (channel A) Scal a
Input 1, channel A InP 1 4.000 mA
Display 1, channel A Dis 1 4.000
Input 2, channel A InP 2 20.000 mA
Display 2, channel A Dis 2 20.000
Scaling (channel B) Scal b
Input 1, channel B InP 1 4.000 mA
Display 1, channel B Dis 1 4.000
Parameter Display Default Setting
Input 2, channel B InP 2 20.000 mA
Display 2, channel B Dis 2 20.000
Total setup Tsetup
Time base, channel A
Tbase Sec
Total conversion factor, Ch-A
T CF 1.000
Grand total conversion factor, Ch-A
Gt CF 1.000
Time base, channel B
Tbase Sec
Total conversion factor, Ch-B
T CF 1.000
Grand total conversion factor, Ch-B
Gt CF 1.000
Total reset Treset
Total reset, channel A
T rst Manual
Grand total reset, Ch-A
Gt rst Manual
Total reset, channel B
T rst Manual
Grand total reset, Ch-B
Gt rst Manual
Display assignment Dsplay
Display line 1 D Ch-A Channel A
Display line 2 d Ch-B Channel B
Display intensity d-Inty 8
Relay Relay
Relay 1 assignment Ch-A Channel A total
Relay 1 action Act 1 Automatic
Relay 1 set point Set 1 100.0
Relay 2 assignment Ch-A Channel A total
Relay 2 action Act 2 Automatic
Relay 2 set point Set 2 200.0
Relay 3 assignment Ch-A Channel A rate
Relay 3 action Act 3 Automatic
Relay 3 set point Set 3 3.000
Relay 3 reset point RSt 3 2.500
Relay 4 assignment Ch-A Channel A rate
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
56
Parameter Display Default Setting
Relay 4 action Act 4 Automatic
Relay 4 set point Set 4 4.000
Relay 4 reset point RSt 4 3.500
Fail-safe relay 1 to 4 Fls 1 Off
On delay relay 1 to 4 On 1 0.0 sec
Off delay relay 1 to 4 Off 1 0.0 sec
Loop break relay 1 to 4
ignore Ignore
Analog output Aout
Display 1 analog out Dis 1 4.000
Output 1 value Out 1 4.000 mA
Display 2 analog out Dis 2 20.000
Output 2 value Out 2 20.000 mA
Source analog output
Source Channel A
Overrange output O-rang 21.000 mA
Underrange output u-rang 3.000 mA
Loop break output break 3.000 mA
Maximum output mAx 23.000 mA
Minimum output min 3.000 mA
Filter Filter
Filter, channel A Ch-A 70
Filter, channel B Ch-B 70
Bypass, channel A bypass 0.2
Bypass, channel B bypass 0.2
Round Round 1
Cutoff Cutoff
Cutoff value, channel A
Ch-a 0.000 (disabled)
Cutoff value, channel B
Ch-b 0.000 (disabled)
Serial Serial
Slave ID (Address) SlavId 247
Parameter Display Default Setting
Baud rate baud 9600
Transmit delay Tr dly 50 ms
Parity Parity Even
Byte-to-byte timeout t-byt 010 (0.1 sec)
Math math
Math, channel C Sum Sum
Adder (constant P) Adder 0.000
Factor (constant F) Factor 1.000
User user
F1 function key F1 Reset max & min
F2 function key F2 Line 1 Max & Min
F3 function key F3 Acknowledge relays
F4 function
(digital input)
F4 Acknowledge relays
Digital input 1 DI 1 Menu
Digital input 2 DI 2 Right arrow
Digital input 3 DI 3 Up arrow
Digital input 4 DI 4 Enter
Digital output 1 DO 1 Alarm 1
Digital output 2 DO 2 Alarm 2
Digital output 3 DO 3 Alarm 3
Digital output 4 DO 4 Alarm 4
Password pass
Password 1 Pass 1
000000 (unlocked)
Password 2 Pass 2
000000 (unlocked)
Password 3 Pass 3
000000 (unlocked)
Total Total
000000 (unlocked)
Grand total gtotal
000000 (unlocked)
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
57
Troubleshooting Tips Symptom Check/Action No display at all Check power at power connector
Not able to change setup or programming, Locd is displayed
Meter is password-protected, enter correct six-digit password to unlock
Meter displays error message during calibration (Error)
Check: 1. Signal connections 2. Input selected in Setup menu 3. Minimum input span requirements
Meter displays 1. 999999 2. -99999
Check: 1. Input selected in Setup menu 2. Corresponding signal at Signal connector
Display is unstable Check: 1. Input signal stability and value 2. Display scaling vs. input signal 3. Filter and bypass values (increase)
Display response is too slow Check filter and bypass values
Display reading is not accurate Check: 1. Signal input conditioner selected: Linear, square root, etc. 2. Scaling or calibration
Display does not respond to input changes, reading a fixed number
Check: 1. Display assignment, it might be displaying max, min, or set
point. Display alternates between 1. Hi and a number 2. Lo and a number
Press Menu to exit max/min display readings.
Relay operation is reversed Check: 1. Fail-safe in Setup menu 2. Wiring of relay contacts
Relay and status LED do not respond to signal
Check: 1. Relay action in Setup menu 2. Set and reset points
Flashing relay status LEDs Relays in manual control mode or relay interlock switches opened.
Meter not communicating with application programs
Check: 1. Serial adapter and cable 2. Serial settings 3. Meter address and baud rate
If the display locks up or the meter does not respond at all
Cycle the power to reboot the microprocessor.
Other symptoms not described above
Call Technical Support for assistance.
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
58
This Page Intentionally Left Blank
EU Declaration of Conformity Issued in accordance with ISO/IEC 17050-1:2004.
We, Precision Digital Corporation 233 South Street Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
Model PD6262 ProVu Series Dual-Input Analog Rate/Totalizer
to which this declaration relates, is in conformity with the European Union Directives shown below:
2014/35/EU Low Voltage Directive 2014/30/EU EMC Directive 2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable technical standards and, when applicable or required, a European Union notified body certification.
Standards: EN 55022:2003 EN 61000-6-2:2001 EN 61010-1:2001 EN 61326:2006 The standards EN 55022:2003, EN 61000-6-2:2001, EN 61010-1:2001, and EN 61326:2006 are no longer harmonized. The requirements of these standards have been checked against the harmonized standards EN 55022:2010, EN 61000-6-2:2005, EN 61010-1:2010, and EN 61326:2013 and there were no major technical changes affecting the latest technical knowledge for the products listed above.
Product Markings:
Signed for and on behalf of Precision Digital Corporation:
Name: Jeffrey Peters Company: Precision Digital Corporation Title: President Date: 04/20/2016 Document No: DoC PD6262 042016
PROVU PD6262 Dual Analog Input Rate/Totalizer Instruction Manual
PRECISION DIGITAL CORPORATION 233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
LIM6262_E
SFT065 Ver 4.010 & up 03/17
How to Contact Precision Digital
For Technical Support, please
Call: (800) 610-5239 or (508) 655-7300
Fax: (508) 655-8990
Email: [email protected]
For Sales Support or to place an order, please contact your local distributor or
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
Email: [email protected]
For the latest version of this manual, please visit
www.predig.com