Monkeytoe Duct SupportAdjustable roof-mounted duct support system ensuring the correct installation of condenser
units, fans and other lightweight equipment on the roof.
TYPICAL USES / APPLICATIONS • Ideally suited as a support for a series of condenser units
• Supports for fans and flues and other lightweight
equipment
• Supports for cable trays, pipes and other services
• Support for equipment up to 250kg
CHARACTERISTICS / ADVANTAGES • Kitset componentry ensures easy on site assembly
• Lightweight, high strength T6 aluminum components
• Increased safe working load of 250kg
see Load Capacities below)
• Unique extrusion design accepts M10 Stainless Steel
spring nuts for ease of install
• Low maintenance and neat appearance
• Suitable for all Steel and Membrane roof profile design
• Roof angle adjustment can be achieved from 4°- 45° (extra bracing may be required at higher
angles).
PRODUCTDESCRIPTION
TECHNICAL DATA / MATERIALS
All componentry manufactured from Marine grade high tensile aluminium with polyethylene
clips and stainless steel fixings.
Extrusion: High strength T6 Aluminium with options of powder coating.
Fixings: Stainless Steel 304 Grade
Roof Connections:
• Roofing Clips High density Polyethylene - UV resistant
• Galvanised Roofing Tek screws,
• Neoprene Sealing Washers.
Monkeytoe Duct Support1/5
PRODUCT SPECIFICATION SHEET
TESTS APPROVALS / STANDARDS• Structural design action B1
• AS/NZS 1170 Standards Australia / New Zealand
• Aluminium Structures, Part 1: Limit State Design AS/NZS 1664.1 Standards Australia / New
Zealand NZS/AS 1657
WARRANTY Lifetime Warranty (25 years)
MAINTENANCE • Visual inspection for any damage or loose fixings must be done periodically and prior to use.
• No certified maintenance is required.
• Basic wear and tear preventative maintenance is recommended.
Monkeytoe Duct Support2/5
Monkeytoe Duct Support
A3
DWG No:
DO NOT SCALE DIMENSIONS IN MILLIMETERS0800 658 637 - www.monkeytoe.co.nz
Th
is dra
win
g a
nd
asso
ciate
d d
esig
n is th
e co
pyrig
ht a
nd
pro
pe
rty of M
on
keyto
e L
td. It sh
all n
ot b
e u
sed
for a
ny p
urp
ose
or p
roje
ct, with
ou
t prio
r writte
n co
nse
nt o
the
r tha
t de
sign
ate
d b
y Mo
nke
ytoe
Ltd
.©
A
B
C
F
E
D
8764 51 2 3
18/06/2018
SHEET 1 OF 1
REV:01
MONKEYTOE
2004-DSA-1
TYPE A DUCT SUPPORT
SCALE: 1:40
Strap Duct or Bolt Flange to Support Rail (By Others)
DS001 Fully Adjustable Swivel Bracket With M10 s/s Bolts and Spring nuts
DS004 Vertical Support
DS003 Roof Rail
DS005 Support Rail Comes with 6 x 25 mm s/s Teks
Monkeytoe Roof Clip: Top Fix And Concealed Fix Roof Clip Availible See Clip Details
Marine Grade Aluminum
30
0-1
00
0 m
m
C
'P' Purlin SpacingMAX 2500 mm
'C' H
eig
ht
to D
uct
Cen
tre L
ine
MA
X 2
120
mm
'S' Support SpacingMax 2000mm
'H' D
uct H
eig
ht
MA
X 2
240
mm
'W' Duct WidthMAX 2240 mm
Braced Bay(Brace Part no. PA50.50.5) Specify Length For Order
STANDARD DUCT SUPPORT PARTS OTHER LENGTHS AVAILABLE ON REQUEST
Standard PartNo.
'R' DS003 RoofRail Length in
mm
'V' DS004 VerticalSupport length in mm
'L' DS005 SupportRail Length in mm
DS003.11 1100
DS003.13 1300
DS003.19 1900
DS004.11 1100
DS004.13 1300
DS004.16 1600
DS004.19 1900
DS005.10 1000
DS005.12 1200
DS005.15 1500
DS005.18 1800
Swivel Bracket Adjusts To Suit Roof Pitch And Duct Size
'L' Support RailLength
'V'
Vert
ical S
upp
ort
Len
gth
'R' Roof RailLength
* ()Denotes No. Of Bays Before Bracing Is Required Includes Braced BayDESIGN CONDITIONS:Building Importance Level - 2Seismic 'Z' Factor - 0.4Site Wind Speed - 37 m/s (Does Not Include Lee Zones or Offshore Locations About The North And South Islands)
TYPE A DUCT SUPPORT DESIGN GUIDEContact Product Support For Any Variations
'GL' ToDuctCentreLine
'P' Purlin Spacing 'W' Duct Width Max 'H'Duct Height Max 'S' Support SpacingInsulated DuctMass (Kg/M)
≤6000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) ≤1750(1) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) ≤1250(2) 106.6
≤2500 ≤2240 ≤2240 ≤1000(2) 141.5
≤9000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) 106.6
≤12000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) 74.2
Ground Level
A3
DWG No:
DO NOT SCALE DIMENSIONS IN MILLIMETERS0800 658 637 - www.monkeytoe.co.nz
Th
is dra
win
g a
nd
asso
ciate
d d
esig
n is th
e co
pyrig
ht a
nd
pro
pe
rty of M
on
keyto
e L
td. It sh
all n
ot b
e u
sed
for a
ny p
urp
ose
or p
roje
ct, with
ou
t prio
r writte
n co
nse
nt o
the
r tha
t de
sign
ate
d b
y Mo
nke
ytoe
Ltd
.©
A
B
C
F
E
D
8764 51 2 3
19/06/2018
SHEET 1 OF 1
REV:01
MONKEYTOE
2004-DSB-1
TYPE B DUCT SUPPORT
SCALE: 1:40
Strap Duct or Bolt Flange to Support Rail (By Others)
DS001 Fully Adjustable Swivel Bracket With M10 s/s Bolts and Spring nuts
DS004 Vertical Support
DS003 Roof Rail
DS005 Support Rail Comes with 6 x 25 mm s/s Teks
Monkeytoe Roof Clip: Top Fix And Concealed Fix Roof Clip Availible See Clip Details
Marine Grade Aluminum
10
00
-15
00 m
m
C
'P' Purlin SpacingMAX 2500 mm
'GL
' Heig
ht to
Du
ct C
entr
e L
ine
MA
X 2
120
mm
'S' Support SpacingMax 2000mm
'H' D
uct H
eig
ht
MA
X 2
240
mm
'W' Duct WidthMAX 2240 mm
Braced Bay(Brace Part no. PA50.50.5) Specify Length For Order
TYPE B DUCT SUPPORT DESIGN GUIDEContact Product Support For Any Variations
'GL'Height ToDuctCentreLine
'P' Purlin Spacing 'W' Duct Width Max 'H'Duct Height Max 'S' Support SpacingInsulated DuctMass (Kg/M)
≤6000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) ≤1750(1) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) ≤1250(2) 106.6
≤2500 ≤2240 ≤2240 ≤1000(2) 141.5
≤9000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) 106.6
≤12000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) 74.2
STANDARD DUCT SUPPORT PARTS OTHER LENGTHS AVAILABLE ON REQUEST
Standard PartNo.
'R' DS003 RoofRail Length in
mm
'V' DS004 VerticalSupport length in mm
'L' DS005 SupportRail Length in mm
DS003.11 1100
DS003.13 1300
DS003.19 1900
DS004.11 1100
DS004.13 1300
DS004.16 1600
DS004.19 1900
DS005.10 1000
DS005.12 1200
DS005.15 1500
DS005.18 1800
Swivel Bracket Adjusts To Suit Roof Pitch And Duct Size
'L' Support RailLength
'V'
Vert
ical S
upp
ort
Len
gth
'R' Roof RailLength
* ()Denotes No. Of Bays Before Bracing Is Required Includes Braced BayDESIGN CONDITIONS:Building Importance Level - 2Seismic 'Z' Factor - 0.4Site Wind Speed - 37 m/s (Does Not Include Lee Zones or Offshore Locations About The North And South Islands)
PA25.25.3 BraceAnd 25 mm s/s Tek Screws Specify Length For Order
Ground Level
A3
DWG No:
DO NOT SCALE DIMENSIONS IN MILLIMETERS0800 658 637 - www.monkeytoe.co.nz
Th
is dra
win
g a
nd
asso
ciate
d d
esig
n is th
e co
pyrig
ht a
nd
pro
pe
rty of M
on
keyto
e L
td. It sh
all n
ot b
e u
sed
for a
ny p
urp
ose
or p
roje
ct, with
ou
t prio
r writte
n co
nse
nt o
the
r tha
t de
sign
ate
d b
y Mo
nke
ytoe
Ltd
.©
A
B
C
F
E
D
8764 51 2 3
19/06/2018
SHEET 1 OF 1
REV:01
MONKEYTOE
2004-DSC-1
TYPE C DUCT SUPPORT
SCALE: 1:40
Strap Duct or Bolt Flange to Support Rail (By Others)
DS001 Fully Adjustable Swivel Bracket With M10 s/s Bolts and Spring nuts
DS004 Vertical Support
DS003 Roof Rail
DS005 Support Rail Comes with 6 x 25 mm s/s Teks
Monkeytoe Roof Clip: Top Fix And Concealed Fix Roof Clip Availible See Clip Details
Marine Grade Aluminum
15
00
-20
00 m
m
C
'P' Purlin SpacingMAX 2500 mm
'GL
' Heig
ht to
Du
ct C
entr
e L
ine
MA
X 2
120
mm
'S' Support SpacingMax 2000mm
'H' D
uct H
eig
ht
MA
X 2
240
mm
'W' Duct WidthMAX 2240 mmTYPE B DUCT SUPPORT DESIGN GUIDE
Contact Product Support For Any Variations
'GL'Height ToDuctCentreLine
'P' Purlin Spacing 'W' Duct Width Max 'H'Duct Height Max 'S' Support SpacingInsulated DuctMass (Kg/M)
≤6000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) ≤1750(1) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) ≤1250(2) 106.6
≤2500 ≤2240 ≤2240 ≤1000(2) 141.5
≤9000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) ≤1500(2) 74.2
≤2000 ≤1800 ≤1800 ≤1000(3) 106.6
≤12000≤1000 ≤800 ≤800 ≤1000(7) ≤1250(5) ≤1500(3) ≤1750(2) ≤2000(2) 43.4
≤1500 ≤1250 ≤1250 ≤1000(4) ≤1250(3) 74.2
STANDARD DUCT SUPPORT PARTS OTHER LENGTHS AVAILABLE ON REQUEST
Standard PartNo.
'R' DS003 RoofRail Length in
mm
'V' DS004 VerticalSupport length in mm
'L' DS005 SupportRail Length in mm
DS003.11 1100
DS003.13 1300
DS003.19 1900
DS004.11 1100
DS004.13 1300
DS004.16 1600
DS004.19 1900
DS005.10 1000
DS005.12 1200
DS005.15 1500
DS005.18 1800
Swivel Bracket Adjusts To Suit Roof Pitch And Duct Size
'L' Support RailLength
'V'
Vert
ical S
upp
ort
Len
gth
'R' Roof RailLength
* ()Denotes No. Of Bays Before Bracing Is Required Includes Braced BayDESIGN CONDITIONS:Building Importance Level - 2Seismic 'Z' Factor - 0.4Site Wind Speed - 37 m/s (Does Not Include Lee Zones or Offshore Locations About The North And South Islands)
Ground Level
Braced Bay(Brace Part no. PA50.50.5) Specify Length For Order
PA50.50.5 BraceAnd 25 mm s/s Tek Screws Specify Length For Order