Product brochure
Generator circuit-breaker HVS-63SSystem type GCB with innovative built-in monitoring
2 HVS-63S Generator circuit-breaker | ABB
ABB is a leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact.
100%75%50%
25%
0%
ABB | HVS-63S Generator circuit-breaker 3
HVS-63S with increased functionality and built-in monitoring features
Built-in mechanical erosion monitoring with direct measurement of the arcing contact length for the highest safety and reliability and for cost-effective planning of service activities
Low SF6 content of only 5.1 kg for 3 poles and lowest leakage rate < 0.1 percent per year
Pressure relief device installed as a standard feature for higher safety
Well-proven hydro-mechanical spring drive operating mechanism type HMB-1* for higher reliability Greatly improved system-type
functionality for simpler and more economic power plant layouts
Key benefits
ABB is a leader in the design and manufacturing of generator circuit-breakers (GCBs) since 1954 with more than 8,000 deliveries in over 100 countries. We offer the widest and most modern portfolio of GCBs in SF6 and vacuum technology with a range of short-circuit ratings from 50 kA to 300 kA and nominal currents from 3,150 A to over 50,000 A to meet the demand of all types of power plants around the globe.
HVS-63S is a complete three phase system
Capable to interrupt short-circuit currents up to 63 kA with rated
continuous current up to 7,150 A
Type tested exceeding the mandatory requirements of the latest GCB
standard and IEEE C37.013
Capability to interrupt fault currents with high degree of asymmetry up to
130 percent
Type tested for out-of-phase fault with full phase opposition (180 degree)
exceeding the standards’ minimum requirements
* Most reliable drive as per paper A3- 206 presented at CIGRE 2012.
4 HVS-63S Generator circuit-breaker | ABB
The most reliable system solution with a contact erosion indicator
HMB-1 drive
Line disconnector
Erosion monitoring device
Circuit-breaker
Capacitor
Surge arrester
Current transformer
Earthing switch
Pressure relief device
ABB | HVS-63S Generator circuit-breaker 5
Current transformer
SFC (static frequency converter) connection
Disconnector for SFC (static frequency converter)
Voltage transformer
Earthing switch
Key locks system for interlocking
Pressure relief device
6 HVS-63S Generator circuit-breaker | ABB
Innovative breaking chamberThe breaking chamber of HVS-63S is based on the highly reliable technology of open-type GCB HVR-63. The breaking chamber includes the double main contacts for double current commutation for higher stability of resistance to ensure the maintenance span of 20 years or 10,000 close-open operations. Featuring the advantage of a hydraulic spring operating mechanism, HMB-1, it uses 50 percent less energy compared to mid-sized GCBs for a more compact design and lower lifecycle costs.
Pressure relief device Standard feature in the breaking chamber to improve satefy and availability.
Erosion monitoring systemThe breakthrough application of head-to-head contact system in HVS-63S enables an innovative built-in mechanical solution for a direct measurement and indication of arcing contact erosion. This real-time indication of the remaining time to service enables a timely planning of maintenance and increases the availability and reliability of the plant.
The most reliable spring drive HMB-1CIGRE study (conducted in 2012) on high-voltage circuit breaker failures and defects in service revealed that the availability of the circuit breakers depends primarily on the reliability of the operating mechanism. These results from the study have endorsed the hydro mechanical spring drive as the most reliable operating mechanism for GCB applications. The hydraulic spring operating mechanism combines the advantages of a hydraulic operating mechanism with those of spring energy storage system with higher stability in the full range of the GCB operating temperatures and high consistency of timing during the enitre lifespan for a safe performance.
Combined disconnector-earthing switch and earthing switch-starting switch
Combination of line disconnector with earthing switch and earthing switch with starting switch by three-positions disconnector allows the use of only one drive per disconnector for the lowest lifecycle cost, simplification of the switchgear and leaner management of the spare parts.
Low environmental impact Only 5.1 kg of SF6 in three poles and a leakage rate lower than 0.1 percent per year. The advanced functions of GMS600 monitoring system, such as SF6 and temperature monitoring and trending (available on request), facilitates the control of such parameters.
Compact design and easy handlingHVS-63S is fully assembled and tested at the factory for substantial cost and time saving in installation and commissioning process. Its compact design fits into a standard 20-feet container for easy transportation, handling and storage. Combined with its plug-in system it leads to a simpler and quicker installation on-site.
HVS-63S is the cost-optimized solution for power plant units of up to 200 MW
F1
-1-2
TDT 2235-10
(1) See note (1) on page 5.
This Certificate applies only to the apparatus tested. The responsibility for conformity of any apparatus having the same designations with that tested rests with the Manufacturer. This Certificate consists of 104 sheets in total. This Certificate falls under the scope of the accreditation certificate L 020 of the Dutch Council for Accreditation. See information sheet (page 2). © Copyright: Only integral reproduction of this Certificate is permitted without written permission from KEMA. Electronic copies in e.g. PDF-format or scanned version of this Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
KEMA Nederland B.V.
S.A.M. Verhoeven Director Testing, Inspections & Certification The Netherlands
Arnhem, 7 June 2011
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE
APPARATUS A three-phase SF6 generator circuit-breaker, three-pole operated
DESIGNATION HVX-63 SERIAL No. 1HC210024022 and 1HC210024023
Rated maximum voltage 24 kV, rms (1) Rated continuous current 6300 / 8000 A, rms Rated short-circuit current 63 kA, rms Rated power frequency 50/60 Hz
MANUFACTURER ABB Switzerland Ltd., Zürich, Switzerland
TESTED FOR ABB Switzerland Ltd., Zürich, Switzerland
TESTED BY KEMA HIGH-POWER LABORATORY Utrechtseweg 310 - 6812 AR Arnhem - The Netherlands
DATE(S) OF TESTS 9 December 2010
The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Certificate, has been subjected to the series of proving tests in accordance with
IEEE C37.013a (2007) subclause 6.2.3.1 (Test duties 1, 2, 3, 4-A and 4-B). The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard and to justify the ratings assigned by the manufacturer as listed on page 5.
Ve
rsio
n: 1
F1
-1-2
TDT 2235-10
(1) See note (1) on page 5.
This Certificate applies only to the apparatus tested. The responsibility for conformity of any apparatus having the same designations with that tested rests with the Manufacturer. This Certificate consists of 104 sheets in total. This Certificate falls under the scope of the accreditation certificate L 020 of the Dutch Council for Accreditation. See information sheet (page 2). © Copyright: Only integral reproduction of this Certificate is permitted without written permission from KEMA. Electronic copies in e.g. PDF-format or scanned version of this Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
KEMA Nederland B.V.
S.A.M. Verhoeven Director Testing, Inspections & Certification The Netherlands
Arnhem, 7 June 2011
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE
APPARATUS A three-phase SF6 generator circuit-breaker, three-pole operated
DESIGNATION HVX-63 SERIAL No. 1HC210024022 and 1HC210024023
Rated maximum voltage 24 kV, rms (1) Rated continuous current 6300 / 8000 A, rms Rated short-circuit current 63 kA, rms Rated power frequency 50/60 Hz
MANUFACTURER ABB Switzerland Ltd., Zürich, Switzerland
TESTED FOR ABB Switzerland Ltd., Zürich, Switzerland
TESTED BY KEMA HIGH-POWER LABORATORY Utrechtseweg 310 - 6812 AR Arnhem - The Netherlands
DATE(S) OF TESTS 9 December 2010
The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Certificate, has been subjected to the series of proving tests in accordance with
IEEE C37.013a (2007) subclause 6.2.3.1 (Test duties 1, 2, 3, 4-A and 4-B). The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard and to justify the ratings assigned by the manufacturer as listed on page 5.
Ve
rsio
n: 1
F1
-1-2
TDT 2235-10
(1) See note (1) on page 5.
This Certificate applies only to the apparatus tested. The responsibility for conformity of any apparatus having the same designations with that tested rests with the Manufacturer. This Certificate consists of 104 sheets in total. This Certificate falls under the scope of the accreditation certificate L 020 of the Dutch Council for Accreditation. See information sheet (page 2). © Copyright: Only integral reproduction of this Certificate is permitted without written permission from KEMA. Electronic copies in e.g. PDF-format or scanned version of this Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
KEMA Nederland B.V.
S.A.M. Verhoeven Director Testing, Inspections & Certification The Netherlands
Arnhem, 7 June 2011
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE
APPARATUS A three-phase SF6 generator circuit-breaker, three-pole operated
DESIGNATION HVX-63 SERIAL No. 1HC210024022 and 1HC210024023
Rated maximum voltage 24 kV, rms (1) Rated continuous current 6300 / 8000 A, rms Rated short-circuit current 63 kA, rms Rated power frequency 50/60 Hz
MANUFACTURER ABB Switzerland Ltd., Zürich, Switzerland
TESTED FOR ABB Switzerland Ltd., Zürich, Switzerland
TESTED BY KEMA HIGH-POWER LABORATORY Utrechtseweg 310 - 6812 AR Arnhem - The Netherlands
DATE(S) OF TESTS 9 December 2010
The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Certificate, has been subjected to the series of proving tests in accordance with
IEEE C37.013a (2007) subclause 6.2.3.1 (Test duties 1, 2, 3, 4-A and 4-B). The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard and to justify the ratings assigned by the manufacturer as listed on page 5.
Ve
rsio
n: 1
ABB | HVS-63S Generator circuit-breaker 7
HVS-63S system type circuit breaker ratings
Rated maximum voltage kV 24
Rated frequency Hz 50 / 60
Rated continuous current 50 Hz / 60 Hz A rms up to 7150 / up to 6900
Rated insulation level
Rated power frequency withstand voltage breaker / line disconnector kV rms 60 / 70
Rated lightning impulse withstand voltage breaker / line disconnector kV peak 125 / 145
Rated peak withstand current kA peak 190
Rated short-time withstand current kA, 3s 63
Rated interrupting time ms 49
Mechanical endurance life CO 10000
Additional safety featuresBy using an advanced Geneva mechanism and key locks system, the design of the disconnector drives ensures full flexibility in implementation of the interlocking needs of the power plant. Special care in the encapsulation of the pole frame assures protection from unintentional access to moving parts between operating mechanism and switching components for the highest safety of operators & maintenance engineers. The breaking chamber technology from HVR-63 with very fast opening time assures the clearance of potential harmful faults in tens of miliseconds for higher protection of power plant assets.
Type-tested according to latest standardsHVS-63S is type-tested according to the latest standards for GCB, including switching with full-phase opposition fault current (180° out-of-phase).Moreover, it is type-tested to interrupt current exhibiting delayed current zeros up to 130 percent degree of asymmetry, which are typical for turbo generators. The above capabilities exceed the mandatory requirements of the latest GCB standard and IEEE C37.013.
Equipment Options1 Generator circuit-breaker2 Line disconnector switch3 Earthing switch4 Starting switch for SFC connection5 Manual short-circuiting connection6 Surge capacitor7 Current transformers8 Voltage transformers9 Surge arrester
Contact us
Note
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts – is forbidden without prior written consent of ABB.
Copyright© 2016 ABB
All rights reserved