Transcript
Page 1: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Practical Troubleshooting & Problem Solving of Ethernet Networks:

RS-232 Fundamentals

Page 2: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

DTE vs DCE

• DTE– Data Terminal Equipment– Transmits on Pin 2 for 25-pin connector

• DCE– Data Communications Equipment– Transmits on Pin 3 for 25-pin connector

Page 3: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

RS-232 Connections (DB25)

Page 4: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

EIA-232

• Electrical Signal levels– Logic 0 =+3 to+25V = Control ON– Logic 1 = -3 to -25V = Control OFF

• Mechanical Interface– DB-25, DB-9 connectors

• Circuit Functionality

Page 5: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Voltage Levels for EIA-232

Data Line Driver

Control Line Driver

0 (Space)

1 (On)

1 (Mark)

0 (Off)

Data Lines

Driver Receiver

Control Lines

Data Receiver

Control Receiver

+25 V

+25 V

+25 V

+25 V

-25 V

-25 V

-25 V

-25 V

+5 V

+5 V

+3 V

+3 V

-5 V

-5 V

-3 V

-3 V

0 V

0 V

0 V

0 V

ON

OFF

0

1

Page 6: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Pin AssignmentsPin Number

(DTE)DB9 Connector IBM Assignment

DB25 ConnectorEIA-232 Pin Assignment

1 Received Line Signal Shield

2 Received Data Transmitted Data

3 Transmitted Data Received Data

4 DTE Ready Request to Send

5 Signal Common/Ground Clear to Send

6 DCE Ready DCE Ready

7 Request to Send Signal Common/Ground

8 Clear to Send Received Line Signal

9 Ring Indicator + Voltage (Testing)

20 - DTE Ready

22 - Ring Indicator

Page 7: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Limitations• Point-to-Point

• Distance Limitation = 2500pf (50ft @ 50pf/ft)

• 20kbps

• -3 to -25V and +3 to +25 V

• Note Table 2.1 Page 30 !

Page 8: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Typical Approach

• Check basic Parameters

• Identify which is DTE and DCE

• Clarify handshaking compatibility– either Hardware– or Software

• Check actual protocol– use protocol analyzer

Page 9: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Test Equipment

• Multimeter

• LED

• Breakout Box

• PC Based Protocol Analyzer

• Dedicated Protocol Analyzer

Page 10: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Breakout Box

LEDs usually Bi-Color

Red commonly Positive Green commonly Negative

DIPSwitches

Common

Page 11: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

RS-232 Breakout Box

Page 12: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Protocol Analyzer Connections

Protocol Analyzer

Page 13: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Typical RS-232 Problems

• Mechanical Problems– Keep wires short– Stranded wire instead of solid wire– Only one wire soldered per pin– Bare wire should not be visible– Back shell must secure wire

Page 14: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Typical RS-232 Problems

• Setup Problems– Software setup compatible

• 8N1or 7E1 or 7O1

– Baud rate correct– Code correct - Binary/Hex or ASCII– Software set up for handshaking

• Hardware or Software control

Page 15: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

Typical RS-232 Problems

• Noise Problems

– Ground Induced Noise

– Induced Noise on TX or RX lines

– Induced noise on Control Lines

Page 16: Practical Fieldbus, DeviceNet & Ethernet for Indusrty

Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare

DO YOU WANT TO KNOW MORE?

If you are interested in further training or information, please visit:

http://idc-online.com/slideshare