Power Imbalance Estimation in Distribution Networks with Renewable Energy
Resources
Vladimir Terzija, Deyu Cai and Mustafa Kayikci*
The University of Manchester*TNEI
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Content
• Introduction• Physical nature of frequency instability• Algorithm for power imbalance estimation• Test results• Low Frequency Demand Control Scheme• Conclusion
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Renewable energy policy has a target to reduce CO2 emission in order to protect our environment and to prevent global warming
At present, in the UK the conventional coal-fired power stations are replaced with nuclear power and renewable energy sources (wind farms, small hydro power generators…)
Target 2020: 32% electricity from wind and small hydro turbines
Introduction
Figure: Future configuration of power generations in the UK.
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Since a large percentage of renewable energy sources will be connected to distribution networks, future distribution networks will be consisting of conventional consumers and distributed generators, such as small synchronous generators, wind farms and photovoltaic generators.
How to prevent blackouts in an isolated distribution network with such a diverse generation mix?
Figure: A typical distribution network with mixed energy sources.
Introduction
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
1. Voltage Stability.2. Transient Stability. 3. Frequency Stability (usually asssociated with active power P
balance between generation and consumption).
Consumption
Generation
?External
networks outage
Stability Issues in Distribution Networks
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
ieimit
i
n
i2 pppdtdf
fH
Δ=−=
iHnf
if
mip
eip
ipΔ
is the inertia constant of a generator in s, is the rated frequency in Hz,
is the actual generator frequency in Hz,
is the mechanical turbine power in p.u.,
is the electrical power in p.u., is the power imbalance between generation and consumption in p.u.
Estimation of the Magnitude of Disturbance (EMD)(the basic concept)
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Two approaches:
1. Multiple point measurement, based on synchronized Measurement Technology (PMUs, Data Concentrators, Comms.)
2. Single point measurement in a selected point in the network
GPS
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
GPS
DataConcentrator
Application
PMU
PMU
PMU
Multiple Points Measurement
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
dtdf
fH
dtdf
fH
pp ec
n
eciN
1i n
iN
1iitotal
22==Δ=Δ ∑∑
==
∑=
=N
1iiec HH
∑∑==
=N
1ii
N
1iiiec HfHf
Multi-generator system:
is the inertia constant of the system equivalent inertia centre
is the frequency of the system equivalent inertia centre
dtdfHHH
fdf
fHp meas
z
1iDFWF
y
1iFSWF
x
1iSG
n
meas
n
ectotal )(2
dt2
iii⋅++=⋅=Δ ∑∑∑ ∑
===
The EMD in Distribution Networks (EMDN) can be simplified as follows:
measf is the frequency measured at a certain pointin the distribution network
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Test Systems
Figure: System structure for all three testing cases
Two test cases are considered
In both test cases, two synchronous generators were fixed at buses 3 and 4.
At bus 2, a Fixed Speed Wind Farm, or a DIFIG based Wind Farm are connected.
In order to compare the simulations results, the same disturbance (the outage of the external grid at bus 1, supplying 2 MW (0.2 p.u.)), was simulated at 0.5 s.
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Results
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5-0.35
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
ΔP
(p.u
)
Time(s)
Plot of Estimated Disturbance, ΔP
ΔP (Estimated using single frequency)
ΔP (Sum of ΔPi, using local freqquencies)
0 1 2 3 4 5-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
ΔP (p
.u)
Time(s)
Plot of Estimated Disturbance, ΔP
ΔP (Sum of ΔPi, using local freqquencies)ΔP (Estimated Hec and using single frequency)
dtdf
fHpp i
N
1i n
iN
1iitotal
2∑∑==
=Δ=ΔEstimated by EMDN
Case 1 Case 2
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Load Shedding Based on EMDN
0 1 2 3 4 549
49.2
49.4
49.6
49.8
50
50.2
50.4
Freq
uenc
y(H
z)
Time(s)
Frequency Responses during disturbances
freqency NLSfrequency 1LSfrequency 2LS
0 1 2 3 4 548
48.5
49
49.5
50
50.5
Freq
uenc
y(H
z)
Time(s)
Frequency Responses during disturbances
frequency NLSfrequency 1LSfrequency 2LS
Two adaptive Low Frequency Demand Control schemes (Load Shedding) plans based on the EMDN are implemented:
1) single staged LS with set frequency 49.6 Hz, and
2) two staged LS with set frequency 49.6 Hz and 49.4 Hz
Case 1 Case 2
No Load shedding
2 staged Load shedding
1 staged Load shedding
1 estp p=
/ 2i estp p=
Prague, 8-11 June 2009
Prof
Vla
dim
ir Te
rzija
, The
Uni
vers
ity o
f Man
ches
ter
Conclusions1) The magnitude of the disturbance can be effectively estimated by
using the EMD algorithm
2) The scheme might be coordinated with the information about the spinning reserve in the system, Demand Side Management and primary response of generators