  • I-E96-610AAPPENDIX A - NTCL01 TERMINATION UNIT CONFIGURATION

    INTRODUCTION

    The INNIS01 Network Interface Slave Module (NIS) can use theNTCL01 Communication Termination Unit (TCL) for termina-tion. Jumpers on the TCL unit select the type of cable used toconnect the NIS module to an INFI-NET system. Refer to theNTCL01 instruction for complete information. Figure A-1shows the location of jumpers and connectors. Figures A-2 andA-3 show the coaxial and twinaxial cable connections. TableA-1 lists the jumper settings used on TCL unit circuit boardrevision levels D and E. Table A-2 lists the jumper settingsused on TCL unit circuit board revision levels F or higher.

    Figure A-1. NTCL01 Connector and JumperLocations (Revision F or Greater)

    NTCL01 TB2 TB1J1

    J2

    J4

    J3

    J10 J6J9

    F1

    P1

    E2

    COMM

    E1

    +24 V

    J5J8 J7

    LOOP 2 LOOP 1

    1 1IN+ IN+

    2 2IN IN

    7 7SHLD SHLD

    6 6OUT OUT

    5 5OUT+ OUT+

    4 4NC NC

    3 3SHLD SHLD

    8 8PSS2 PSS1

    3

    12

    3

    12

    3

    12

    3

    12

    3

    12

    3

    12

    CHASSIS GROUND T00205AINTRODUCTION A - 1

  • NTCL01 TERMINATION UNIT CONFIGURATION

    TP85180D

    NKCL01NKCL11

    T00384A

    NKPL01NKPL02

    IN FROMLOOPFigure A-2. NTCL01 Coaxial Cable Connections to INNIS01 Modules

    Figure A-3. NTCL01 Twinaxial Cable Connections to INNIS01 Modules

    NKTL01-3

    NTCL01

    8 7 6 5 4 3 2 1

    8 7 6 5 4 3 2 1TB1

    TB2

    LOOP2

    LOOP1

    P1

    NTCL01

    8 7 6 5 4 3 2 1

    8 7 6 5 4 3 2 1TB1

    TB2

    LOOP2

    LOOP1

    P1

    NTCL01

    8 7 6 5 4 3 2 1

    8 7 6 5 4 3 2 1TB1

    TB2

    LOOP2

    LOOP1J2

    J2

    J2

    J1

    J1

    J1

    E2

    E1

    P1

    COM

    +24 V

    E2

    E1

    COM

    +24 V

    E2

    E1

    COM

    +24 V

    IN FROM LOOP

    NKTL01-3

    TO OTHER NODES

    J3J4

    J3J4

    J3J4

    P3

    P1

    P2

    INNIS01

    P3

    P1

    P2

    INNIS01

    NKLS01NKLS11

    NKLS01NKLS11

    NKTT01NKTT11

    P3

    P1

    P2

    NTCL01

    8 7 6 5 4 3 2 1

    8 7 6 5 4 3 2 1TB1

    TB2

    LOOP2

    LOOP1

    NTCL01

    8 7 6 5 4 3 2 1

    8 7 6 5 4 3 2 1TB1

    TB2

    LOOP2

    LOOP1

    IN

    IN

    SH

    SHP1

    P1

    INNIS01

    COME2

    E1 +24V

    COME2

    E1 +24V

    P3

    P1

    P2

    INNIS01

    OUT TOOTHER NODES

    J3J4

    J3J4

    J2

    J2

    J1

    J1

    NKLS01NKLS11

    NKLS01NKLS11INTRODUCTIONA - 2 I-E96-610A

  • NTCL01 TERMINATION UNIT CONFIGURATION

    I-E96-610ATable A-1. NTCL01 Jumper Settings for Revision D and E

    Jumper Number Twinaxial Cable Jumper SettingsCoaxial Cable Jumper

    SettingsJ5 - J12 2 - 3 2 - 3

    J13 - J18 1 - 2 2 - 3

    Table A-2. NTCL01 Jumper Settings for Revision F or Greater

    Jumper Number Twinaxial Cable Jumper SettingsCoaxial Cable Jumper

    SettingsJ5 - J10 1 - 2 2 - 3INTRODUCTION A - 3

  • Document SummaryAPPENDIX A - NTCL01 TERMINATION UNIT CONFIGURATIONINTRODUCTIONFiguresA-1. NTCL01 Connector and Jumper Locations (Revision F or Greater)A-2. NTCL01 Coaxial Cable Connections to INNIS01 ModulesA-3. NTCL01 Twinaxial Cable Connections to INNIS01 Modules

    TablesA-1. NTCL01 Jumper Settings for Revision D and EA-2. NTCL01 Jumper Settings for Revision F or Greater