Date, Venue, etc..( Arial, Font size 18 )AMI experience of Tata Power
…Message Box ( Arial, Font size 18 Bold)
Introduction
• Tata Power is engaged in Supply of Electricity across Mumbai Licensed area.
• The total spread of licensed area is 485 sq. km. and houses a population of approximately 1.45 crores
• Customer base in the Mumbai licensed area is around three lakh.
• Tata Power has recently installed an Automatic Meter Reading system for high value customers in Industrial & commercial segment.
…Message Box ( Arial, Font size 18 Bold)
Objective of AMR system
• To fully automate the process of meter reading and billing without any human intervention.
• Faster detection of metering abnormalities, theft and network faults.
• Monitoring and profiling energy consumption of consumers.
• Provide load profile data to key customers on Tata Power Customer Portal.
• Facilitate accurate Load forecasting.
• Facilitate Demand Response Initiatives.
…Message Box ( Arial, Font size 18 Bold)
Secured GPRS cloud
HT/ LT customers Communication technology
Internet Internet
MDASSAP Billing server
Web server
Information to customer through internet
AMR system architecture
SAP PI
MDMMiddlew
are
AMR Data Centre
…Message Box ( Arial, Font size 18 Bold)
MDAS
Meter Data Acquisition System (MDAS) :
• A common Meter Data Acquisition System is deployed to read all makes of meters.
• MDA system acquires meter raw data stored in the Modem memory.
• Raw files received from different types of meters are processed through the respective API utility tools and converted into XML file.
• Also, health status of all the installed modems, communication logs and events are captured in MDAS.
…Message Box ( Arial, Font size 18 Bold)
MDMS Meter Data Management System (MDMS) :
• MDM is the central repository for meter data and maintains interval data, event logs , register data & outage history for all the connected meters.
• The MDM system has a facility to upload meter data read through
CMRI. This facility is used to manage the data of meters not covered under AMR.
• MDM validates meter data as per predefined validation rules to ensure that only correct data is sent for billing.
• The MDM system provides many useful MIS reports
…Message Box ( Arial, Font size 18 Bold)
MDMS
The MDM system has following functional elements
- Data collection, aggregation and analysis
- Validation, Editing & Estimation - Report generation and status reporting
- Event list
- Customer Care
Itron Enterprise Edition Platform
MeterData Management
CustomerCare
Curtailment Manager
Revenue Protection Suite
Multiple Data Collection Systems
Handheld AMR Solutions
C&I Meter and Collection Systems AMI
Utility Operational and Back-office Systems
…Message Box ( Arial, Font size 18 Bold)
Middleware
Middleware :
• The SAP PI middleware is used for integrating MDAS, MDM and SAP billing system for seamless exchange of data.
• The SAP PI system maps the meter CDF file with MDM system.
• New meter creation or deletion is done in SAP system which is communicated to the MDM through the middleware.
…Message Box ( Arial, Font size 18 Bold)
Communication -Last mile connectivity & related issues
• Selection of communication technology < Speed < Reliability < Data Security < Cost ( Capex + Opex ) GPRS was selected as the best option on the above parameters for high
value commercial and industrial consumers.
• Meter protocols Intelligent Modems are deployed which collect meter data using API API are provided by Meter suppliers as per MIOS. Modems collect data from meter at 30 minute interval & stores the same in
its memory. The data is pushed every midnight to MDAS.
…Message Box ( Arial, Font size 18 Bold)
Last mile connectivity and related issues in AMR
• Integration with Billing system
< Billing data is collected in MDM.
< MDM does data validation
< SAP-PI Middleware is used for pushing data from MDM to SAP
• Sharing meter data with customers
< Customer logs on to TPC Customer Web Portal through internet.
< Customer portal pulls meter data from MDMS
…Message Box ( Arial, Font size 18 Bold)
Tata Power Customer Care Portal
…Message Box ( Arial, Font size 18 Bold)
Consumption in Graphical format
…Message Box ( Arial, Font size 18 Bold)
Consumption in Graphical format
…Message Box ( Arial, Font size 18 Bold)
Consumption in Histogram format
…Message Box ( Arial, Font size 18 Bold)
Last mile connectivity in AMR
• The capital & operational cost per meter is relatively high for GPRS. Hence, GPRS is not viable for low end consumers. It is necessary to explore
technological option suitable for deployment of AMR for low end consumers. • In many Residential / Commercial complexes, large number of meters are installed in
close vicinity and form a cluster.
• RS-485 Modbus seems attractive and viable option for covering cluster meters under AMR.TPC has installed one pilot based on RS-485 technology and the performance is under observation.
• Physical looping of meter communication ports is cumbersome and tamper prone. RF Mesh seems to be an option. TPC is planning to set up a pilot based on RF Mesh technology for cluster metering installations.
• For Residential consumers, PLC may be a viable option. TPC is planning to set up a pilot project to explore this option.
…Message Box ( Arial, Font size 18 Bold)
Future Road Map
First Steps towards Smart Grid
…Message Box ( Arial, Font size 18 Bold)
Pilot project on RS-485
• Around 40 number three phase WC meters installed in a commercial
complex are covered under pilot.
• All meters are L & T make with inbuilt RS-485 port
• The RS-485 terminals of all meters are connected in a daisy chain and are
looped to a data concentrator.
• The data concentrator collects meter data once every fifteen minutes and
stores the same in its memory.
• The data concentrator has inbuilt GPRS Modem which pushes meter data
to Head end system at scheduled interval( Once a day)
…Message Box ( Arial, Font size 18 Bold)
Rishab Chambers
…Message Box ( Arial, Font size 18 Bold)
RS 485 Looping
…Message Box ( Arial, Font size 18 Bold)
DCU Installation
…Message Box ( Arial, Font size 18 Bold)
System Configuration for RS-485 cluster
DCU DCU DCU
201 2
…
21 40
…
581 600
…
…
1 2 30
22 582
DCU
…
LT Commercial consumers
RS485 RS485 RS485
Internet Internet
MDAS
SAP Billing server
Web server
SAP PI
MDMMiddlew
are
…Message Box ( Arial, Font size 18 Bold)
Pilot with RF Mesh technology
• A pilot project based on RF Mesh technology is planned to be set up covering about 200 meters.
• The meter data will be collected in a data concentrator using RF .
• The DCU will push the data to Head end system using GPRS.
• The proposed system architecture is as below
22
…Message Box ( Arial, Font size 18 Bold)
System Configuration for RF Mesh Technology
DCU
…
Internet Internet
MDAS
SAP Billing server
Web server
SAP PI
MDMMiddlew
are
…Message Box ( Arial, Font size 18 Bold)
Pilot with PLC technology
• A pilot project based on PLC technology is planned to be set up covering about 100 meters in residential segment.
• The meter data will be collected in a data concentrator using power line as a communication media.
• The DCU will push the data to Head end system using GPRS.
• The proposed system architecture is as below
…Message Box ( Arial, Font size 18 Bold)
System Configuration for PLCC Technology
DCU
…
Internet Internet
MDAS
SAP Billing server
Web server
SAP PI
MDMMiddlew
are
0.4KV 3-4W POWER LINE
DISTRIBUTION TRANSFORMER
DCU WITH INBUILT GPRS MODEM
COMMUNICATION MEDIUM GPRS NETWORK 11KV / 0.4KV
1- LT Domestic Consumer
3- / 1- Cluster Meter
POWER LINE COMMUNICATION
DISTRIBUTION TRANSFORMER
…Message Box ( Arial, Font size 18 Bold)
Interface Meter Monitoring System
TPCD
AMR Servers
@ CARNAC Polling servers
Web- BasedClient s on TPC WAN
Master Servers @ LDC, Trombay
BEST &REL
TPCCORPORAT
E WAN
TPCCORPORAT
E WAN
JDBC connectivity
Database &Application Servers
TPC Automation WAN
* BEST / REL
New Fire Wall
1 2 3
WEB SERVER
TPC existing Fire Wall
GLOBALINTERNET
GLOBALINTERNET
SLDC
TPCG
TPCD TPCG
RS 485 to Ethernet converter
ABT meters at Substation
SAP server
…Message Box ( Arial, Font size 18 Bold)
Pilot on Smart Metering solution
It is proposed to install one pilot towards implementation of Smart Grid initiatives. This would include smart metering & Home area network .
Smart metering will include< Remote disconnection /reconnection < Load control / Device control Home Area Network (HAN) with energy gateway < Demand Response Signaling. < Provision of Customer Energy Usage Information to In-Home Displays. < Control Activation/Deactivation of HAN Appliances. < Real time pricing signals
…Message Box ( Arial, Font size 18 Bold)
Thanks for patient hearing.
…Message Box ( Arial, Font size 18 Bold)
Pilot Project Objectives
• To evaluate the potential value of remote equipment control, thermostats, and other energy conservation features
• To evaluate electricity meters with a load limiting/disconnect switch
• To evaluate customer interest & experience in Home Area Display Units
…Message Box ( Arial, Font size 18 Bold)
Pilot project architecture
…Message Box ( Arial, Font size 18 Bold)
Targeted Customer Benefits
• Convenience- customer has access to their own data - accurate timely meter reads without intrusion in their property
• Consumption and Demand Response Control- interval data for time of use rates- smart thermostats- load limiting disconnect switch
• Reliability- reduced outage times- proactive load and voltage data
…Message Box ( Arial, Font size 18 Bold)
Targeted Customer Benefits
• Power Quality- accurate timely load and voltage information for Network planning
• Utility/Customer Business Savings- meter reading cost
- asset management- outage management- theft reduction- other operational savings
…Message Box ( Arial, Font size 18 Bold)
What’s Next?
The opportunities are endless…
• Allow customers to have fun with High tech products the way they were meant to be ....
• Control almost anything:• Lighting• Security Systems• Thermostats• Remote controlled devices
The "smart" meter can be utilized to:• Read the meter both locally and remotely
(on demand)• As a sensor• Remote limitation of the throughput
through the meter to control demand• Interconnection to premise-based
networks and devices, remote control of meters within home
• Remote provisioning of services (e.g. Security)
How Smart metering is different from Traditional metering
Traditional/ AMR meter
Manual/Automated reading
Utility database
Smart meter
Interface
Home controls
Gateway AMI Infrastructure
Smart homes