0.5 to 125A: Multi 9 circuit breakerssymetrical rail mounting
C60
O - OFF
MERLIN GERIN
NC100HC100A415Va
27265
10kA IEC 947.2
O - OFF
1 3
2 4
multi 9
MERLIN GERIN
multi 9C60NC63400Va6000
24208
O - OFFO - OFF
10kA IEC 947.2
1 3
2 4
MERLIN GERIN
multi 9DPN vigiC40 I∆n 0,300A230Va
20912
BS EN 61009
O - OFF
test mensueltest monthly
N 2
N 1
a4500
6 kA IEC 947.2
DPN Vigi
NC100
6 to 32A 1 to 40A 6 to 40A 10 to 40A 0.5 to 63A 10 to 100A 125A
DPNa DPN N DPN N Vigi V40H C60a C60N C60H C60L NC100H NC100L NC100LS NC100LH NC125Hnumber of poles 1 + N 1 + N 1 + N 1 + N 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1 2-3-4 1-2-3-4 1-2-3-4 1-2-3-4 1-2-3-4 3-4
electrical characteristicsrated current (A) In 30°C 32 40 40 40 40 63 63
40°C 25 32.40 50.63 100 63 63 63 125rated insulation voltage (V) Ui 440 440 440 440 440 440 440 440 440 440 440 440 440 440 415impulse withstand voltage (kV) Uimp 4 4 4 4 6 6 6 6 6 6 6 6 6 6 6rated operational voltage (V) Ue AC 50.60Hz 230 230 230 240 440 440 440 440 440 440 440 440 440 440 415fast closing ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
disconnection with positive contact indication ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
AC breaking capacity (kA rms)IEC 947.2 (EN 60.947.2) Icu 130V 10 20 30 50 50 50
240V 10 5 10 10 20 15 30 25 50 20 40 15 30 20 50 70 80 20400V 10 25 36 50415V 3 5 3 10 4 15 6 25 5 20 4 15 10 25 36 40 10440V 3 6 10 20 15 10 6 20 30 30
Ics (% of Icu) 100% 100% 100% 75% 75% 50% 50% 50% 50% 75% 75% 75% 75% 75%IEC 898 Icn 230V 4.5 6 6
Ics 4.5 6 6DC breaking capacity (kA)IEC 947.2 (EN 60.947.2) Icu 60V 15 15 10 15 20 25 25 25 20 (1p)
125V 10 (2p) 20 (2p) 25 (2p) 30 (2p) 30 (2p) 30 (2p) 30 (2p)125V 20 (3p) 30 (3p) 40 (3p) 50 (3p) 50 (3p) 50 (3p) 40 (3p)250V 25 (4p) 40 (4p) 50 (4p) 60 (4p) 60 (4p) 60 (4p) 20 (4p) 25 (1p) 36 (1p) 50 (1p)
Ics (% of Icu) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
trip units (non adjustable)curve type B (lm = 3.2 to 4.8ln) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
C (lm = 7 to 10ln) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
D (lm = 10 to 14ln) ■ ■ ■ ■
K (lm = 10 to 14In) ■ ■
Z (lm = 2.4 to 3.2) ■ ■
MA (lm = 12ln) ■ ≤ 40A ■ ≤ 63Apersonnel protectionadd-on rcd's (Vigi module) integrated integrated ■ ■ ■ ■ ■ ■ ■ ■ ■
30-300mA 30mAelectrical auxiliariesauxiliary and alarm switches (OF-SD) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
shunt trip (MX) ; undervoltage release (MN) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
installationplug in base ■ ■ ≤ 63Aterminal shieds ■ ■
padlocking device ■ ■ ■ ■ ■ ■ ■
rotary handle ■ ■ ■
dimensions (mm) W 18 18 36 36 18/P 27/PH 78 78 78 81 81 81D 70 70 70 70 70 70
4 Merlin Gerin Merlin Gerin 5
15 to 600A: Compactdisconnector mouled case circuit breakerslow breaking capacity range: E
ImIr
DE 225225A/48C90
105%Ir
alarm
ImIr
OFF
MERLIN GERINcompact
NS225 EUi 550V. Uimp 6kV.
220/240380/415440500660/690250
853635308
50
cat A
IEC947-2UTE VDE BS CEI UNE NEMA
Ue(V)
Icu(kA)
Ics=50% Icu
225Apushto
trip
pushto
trip
225E
P93083
Compact NS225E
15 to 100A 125 to 225A 250 to 400A 500 to 600A
C100E NS225E NS400E NS600Enumber of poles 3 3 3 3
electrical characteristicsrated current (A) In 40°C 100 225 400 600rated insulation voltage (V) Ui 500 500 500 500rated impulse withstand voltage (kV) Uimp 6 6 6 6rated operational voltage (V) Ue AC 50/60Hz 500 500 500 500
DCcharacteristics according to IEC 947.2rated ultimate breaking capacity Icu AC 50/60Hz 220/240V 30 30 30 30(kA rms) 380V 18 18 25 25
415V 10 15 25 25440V 8 15 18 18500V 7.5 15 15660/690V
rated service breaking performance Ics (% of Icu) 50% 50% 50% 50%utilisation category A A A Apollution degree III III III IIIfront face insulation class II ■ ■ ■ ■
rated admissible short time Icw (kA rms)withstand current duration (s)performances according NEMArated breaking capacity AB1 (O-CO) (kA) 240V 30 30 30 30
480V 8 15 18 18600V
trip unitsthermal magnetic ■ ■ ■ ■
solid state
protectionfor distribution standard networks ■ ■ ■ ■
generator fed networkslong distance networksdirect current networks
for motor startersfor people ELCB's Vigicompact
Vigirex residual current relays ■ ■ ■ ■
indications and measurementauxiliary and alarm switches (OF-SD-SDE) ■ ■ ■ ■
local and/or distance control and monitoring (Dialpact) ■ ■ ■ ■
data transmission (Dialpact) ■ ■ ■ ■
voltage presence indicatorcurrent transformer moduleammeter moduleinsulation monitoring module
control accessoriesshunt trip (MX) ; undervoltage release (MN) ■ ■ ■ ■
direct or extended rotary handlesmotor mechanism for remote control
installationversion fixed ■ ■ ■ ■
plug-in on a basedraw-out on chassis
accessories terminal shields ■ ■ ■ ■
padlocking and locking device ■ ■ ■ ■
dimensions of 2-3 pole fixed version (mm) W 105 105 140 140H 128 161 255 255D 95 86 110 110
weight (kg) 3 pole fixed version 1.3 1.8 6 6
modelsvisible break circuit breaker Visucompactswitch - disconnectorautomatic / manual source changeover
6 Merlin Gerin Merlin Gerin 7
16 to 3200A: Compactdisconnector mouled case circuit breakersstandard range: N
0
push to trip
OFF compactMERLIN GERIN
CM2500HE
3-pole
600V 50/60Hz
2500A max.
IEC-VDE-BS
molded caseswitch
ON
OFF
TRIP
ST 306ST
test
longtime
shorttime
groundfault
trip indicator (push to reset)
tr
84 81
1.5
2
3
4 5
6
8
10xIr
Im
.63
.7
.8
.85 .9
.95
.98
1xIn
IrSTR 22 SE90
105%Ir
alarm
ImIr
I n = 2 5 0 A
OFF
MERLIN GERINcompact
NS250 NUi 750V. Uimp 8kV.
220/240380/415440500660/690250
853635308
50
cat A
IEC947-2UTE VDE BS CEI UNE NEMA
Ue(V)
Icu(kA)
Ics=100% Icu
160/250Apushto
trip
pushto
trip
250N
P93083
PUSH TO TRIP
MERLIN GERINcom pact
C 1001 HUi 750V. Uimp 8kV.
Ue(V)
220/240
380/415
440
500/525
660/690
100
70
65
40
35
IEC 947-2UTE VDE BS CEI
UNE NEMA
Icu(kA)
cat B
Ics = 100% IcuIcw 8kA / 0,25s.
OFF
60 70 80 90 105 %Ir
STR 55UE
TFR
Io
xIn
T tr tmth
Ir ImIhI
test
fault
t
i
connected
disconnected
16 to 100A 16 to 160A 16 to 250A 160 to 400A 250 to 630A 320 to 800A 400 to 1000A 500 to 1250A 625 to 1250A 800 to 1600A 1000 to 2000A 1250 to 2500A 1600 to 3200A
NS100N NS160N NS250N NS400N NS630N C801N C1001N C1251N CM1250N CM1600N CM2000N CM2500N CM3200Nnumber of poles 2 - 3 - 4 2 - 3 - 4 2 - 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3
electrical characteristicsrated current (A) In 40°C 100 160 250 400 630 800 1000 1250 1250 1600 2000 2500 3200rated insulation voltage (V) Ui 750 750 750 750 750 750 750 750 750 750 750 750 750rated impulse withstand voltage (kV) Uimp 8 8 8 8 8 8 8 8 8 8 8 8 8rated operational voltage (V) Ue AC 50/60Hz 690 690 690 690 690 690 690 690 690 690 690 690 690characteristics according to IEC 947.2rated ultimate breaking capacity Icu AC 50/60Hz 220/240V 85 85 85 85 85 85 85 85 85 85 85 85 85(kA rms) 380/415V 25 36 36 45 45 50 50 50 70 70 70 70 70
440V 25 35 35 42 42 42 42 42 65 65 65 65 65500V 18 30 30 30 30 40 40 40 50 50 50 50 50
for DC consult general catalogue 660/690V 8 8 8 10 10 25 25 25 50 50 50 50 50rated service breaking performance Ics (% of Icu) 100% 100% 100% 100% 100% 50% 50% 50% 50% 50% 50% 50% 50%utilisation category A A A A A B B B B B B B Bpollution degree III III III III III III III III III III III III IIIfront face insulation class II ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
rated admissible short time Icw (kA rms) 12 15 15 32 32 32 32 32withstand current duration (s) 1 1 1 1 1 1 1 1performances according NEMArated breaking capacity AB1 (O-CO) (kA) 240V 85 85 85 85 85 85 85 85 85 85 85 85 85
480V 25 35 35 42 42 42 42 42 65 65 65 65 65600V 10 20 20 20 20 30 30 30 50 50 50 50 50
trip unitsthermal magnetic ■ ■ ■
solid state ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
protectionfor distribution standard networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
generator fed networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
long distance networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
direct current networks ■ ■ ■ ■ ■ ■
for motor starters ■ ■ ■ ■ ■ ■ ■ ■
for people ELCB's Vigicompact ■ ■ ■ ■ ■
Vigirex residual current relays ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
indications and measurementauxiliary and alarm switches (OF-SD-SDE) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
local and/or distance control and monitoring (Dialpact) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
data transmission (Dialpact) ■ ■ ■ ■ ■ ■ ■ ■
voltage presence indicator ■ ■ ■ ■ ■
current transformer module ■ ■ ■ ■ ■
ammeter module ■ ■ ■ ■ ■
insulation monitoring module ■ ■ ■ ■ ■
control accessoriesshunt trip (MX) ; undervoltage release (MN) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
direct or extended rotary handles ■ ■ ■ ■ ■ ■ ■ ■
motor mechanism for remote control ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
installationversion fixed ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
plug-in on a base ■ ■ ■ ■ ■
draw-out on chassis ■ ■ ■ ■ ■ ■ ■ ■
accessories terminal shields ■ ■ ■ ■ ■ ■ ■ ■
padlocking and locking device ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
dimensions of 2-3 pole fixed version (mm) W 105 105 105 140 140 210 210 210 418 418 418 418 418H 161 161 161 255 255 374 374 374 430 430 430 430 550D 86 86 86 110 110 172 172 172 337 337 337 337 337
weight (kg) 3 pole fixed version 1.6 1.6 1.9 6.0 6.0 13 13 13 41 41 46 63 83
modelsvisible break circuit breaker Visucompact ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
switch - disconnector ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
automatic / manual source changeover ■ ■ ■ ■ ■ ■ ■ ■
Compact NS250N
Compact C801N with universal chassis
Compact CM1250N
8 Merlin Gerin Merlin Gerin 9
1.5 to 3200A: Compactdisconnector mouled case circuit breakershigh breaking capacity range: H
1.5
2
3
4 5
6
8
10xIr
Im
.63
.7
.8
.85 .9
.95
.98
1xIn
IrSTR 22 SE90
105%Ir
alarm
ImIr
I n = 2 5 0 A
OFF
MERLIN GERINcompact
NS250 NUi 750V. Uimp 8kV.
220/240380/415440500660/690250
853635308
50
cat A
IEC947-2UTE VDE BS CEI UNE NEMA
Ue(V)
Icu(kA)
Ics=100% Icu
160/250Apushto
trip
pushto
trip
250N
P93083
1.5 to 80A 16 to 100A 16 to 160A 16 to 250A 160 to 400A 250 to 630A 320 to 800A 400 to 1000A 500 to 1250A 625 to 1250A 800 to 1600A 1000 to 2000A 1250 to 2500A 1600 to 3200A
NS80HMA NS100H NS160H NS250H NS400H NS630H C801H C1001H C1251H CM1250H CM1600H CM2000H CM2500H CM3200Hnumber of poles 3 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3
electrical characteristicsrated current (A) In 40°C 80 100 160 250 400 630 800 1000 1250 1250 1600 2000 2500 3200rated insulation voltage (V) Ui 750 750 750 750 750 750 750 750 750 750 750 750 750 750rated impulse withstand voltage (kV)Uimp 8 8 8 8 8 8 8 8 8 8 8 8 8 8rated operational voltage (V) Ue AC 50/60Hz 690 690 690 690 690 690 690 690 690 690 690 690 690 690characteristics according to IEC 947.2rated ultimate breaking Icu AC 50/60Hz 220/240V 100 100 100 100 100 100 100 100 100 125 125 125 125 125capacity (kA rms) 380/415V 70 70 70 70 70 70 70 70 70 85 85 85 85 85
440V 65 65 65 65 65 65 65 65 65 85 85 85 85 85500V 25 50 50 50 50 50 50 50 50 50 50 50 50 50
for DC consult general catalogue 660/690V 6 10 10 10 20 20 40 40 40 50 50 50 50 50rated service breaking perform. Ics (% of Icu) 100% 100% 100% 100% 100% 100% 50% 50% 50% 50% 50% 50% 50% 50%utilisation category A A A A A A B B B B B B B Bpollution degree III III III III III III III III III III III III III IIIfront face insulation class II ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
rated admissible short time Icw (kA rms) 12 15 15 32 32 32 32 32withstand current duration (s) 1 1 1 1 1 1 1 1performances according NEMArated breaking capacity AB1 (O-CO) (kA) 240V 100 100 100 100 100 100 100 100 100 125 125 125 125 125
480V 65 65 65 65 65 65 65 65 65 85 85 85 85 85
600V 10 35 35 35 35 35 42 42 42 50 50 50 50 50
trip unitsthermal magnetic ■ ■ ■
solid state ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
protectionfor distribution standard networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
generator fed networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
long distance networks ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
direct current networks ■ ■ ■ ■ ■
for motor starters ■ ■ ■ ■ ■ ■ ■ ■ ■
for people ELCB's Vigicompact ■ ■ ■ ■ ■
Vigirex residual current relays ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
indications and measurementauxiliary and alarm switches (OF-SD-SDE) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
local and/or distance control and monitoring (Dialpact) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
data transmission (Dialpact) ■ ■ ■ ■ ■ ■ ■ ■ ■
voltage presence indicator ■ ■ ■ ■ ■
current transformer module ■ ■ ■ ■ ■
ammeter module ■ ■ ■ ■ ■
insulation monitoring module ■ ■ ■ ■ ■
control accessoriesshunt trip (MX) ; undervoltage release (MN) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
direct or extended rotary handles ■ ■ ■ ■ ■ ■ ■ ■ ■
motor mechanism for remote control ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
installationversion fixed ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
plug-in on a base ■ ■ ■ ■ ■
draw-out on chassis ■ ■ ■ ■ ■ ■ ■ ■
accessories terminal shields ■ ■ ■ ■ ■ ■ ■ ■ ■
padlocking and locking device ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
dimensions of 2-3 pole fixed version (mm) W 90 105 105 105 140 140 210 210 210 418 418 418 418 418H 120 161 161 161 255 255 374 374 374 430 430 430 430 550D 80 86 86 86 110 110 172 172 172 337 337 337 337 337
weight (kg) 3 pole fixed version 1.0 1.6 1.6 1.9 6.0 6.0 13 13 13 41 41 46 63 83
modelsvisible break circuit breaker Visucompactswitch - disconnectorautomatic / manual source changeover ■ ■ ■ ■ ■ ■ ■ ■
Compact NS250H
60 70 80 90 105 %Ir
STR 55UE
TFR
Io
xIn
T tr tmth
Ir ImIhI
test
fault
t
i
I
0
MERLIN GERINcompact
C 1001 HUi 750V. Uimp 8kV.
Ue(V)
220/240
380/415
440
500/525
660/690
100
70
65
40
35
IEC 947-2UTE VDE BS CEI
UNE NEMA
Icu(kA)
cat B
Ics = 100% IcuIcw 8kA / 0,25s.
Compact C801H with motor mechanism
0
push to trip
OFF compactMERLIN GERIN
CM2500HE
3-pole
600V 50/60Hz
2500A max.
IEC-VDE-BS
molded case
switch
ON
OFF
TRIP
ST 306ST
test
longtime
shorttime
groundfault
trip indicator (push to reset)
tr
84 81
Compact CM1250H
10 Merlin Gerin Merlin Gerin 11
16 to 1000A: Compactdisconnector mouled case circuit breakerscurrent limiting range: L
1.5
2
3
4 5
6
8
10xIr
Im
.63
.7
.8
.85 .9
.95
.98
1xIn
IrSTR 22 SE90
105%Ir
alarm
ImIr
I n = 2 5 0 A
OFF
MERLIN GERINcompact
NS250 NUi 750V. Uimp 8kV.
220/240380/415440500660/690250
853635308
50
cat A
IEC947-2UTE VDE BS CEI UNE NEMA
Ue(V)
Icu(kA)
Ics=100% Icu
160/250Apushto
trip
pushto
trip
250N
P93083
16 to 100A 16 to 160A 16 to 250A 160 to 400A 250 to 630A 320 to 800A 400 to 1000A
NS100L NS160L NS250L NS400L NS630L C801L C1001Lnumber of poles 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4 3 - 4
electrical characteristicsrated current (A) In 40°C 100 160 250 400 630 800 1000rated insulation voltage (V) Ui 750 750 750 750 750 750 750rated impulse withstand voltage (kV) Uimp 8 8 8 8 8 8 8rated operational voltage (V) Ue AC 50/60Hz 690 690 690 690 690 690 690characteristics according to IEC 947.2rated ultimate breaking capacity Icu AC 50/60Hz 220/240V 150 150 150 150 150 150 150(kA rms) 380/415V 150 150 150 150 150 150 150
440V 130 130 130 130 130 100 100500V 100 100 70 100 50 100 100
for DC consult general catalogue 660/690V 75 75 20 75 35 60 60rated service breaking performance Ics (% of Icu) 100% 100% 100% 100% 100% 50% 50%utilisation category A A A A A A Apollution degree III III III III III III IIIfront face insulation class II ■ ■ ■ ■ ■ ■ ■
rated admissible short time Icw (kA rms) 6.4 8withstand current duration (s) 1 1performances according NEMArated breaking capacity AB1 (O-CO) (kA) 240V 200 200 200 200 200 150 150
480V 130 130 130 130 130 100 100600V 50 50 50 50 50 65 65
trip unitsthermal magnetic ■ ■ ■
solid state ■ ■ ■ ■ ■ ■ ■
protectionfor distribution standard networks ■ ■ ■ ■ ■ ■ ■
generator fed networks ■ ■ ■ ■ ■ ■ ■
long distance networks ■ ■ ■ ■ ■ ■ ■
direct current networks ■ ■ ■ ■ ■ ■ ■
for motor starters ■ ■ ■ ■ ■ ■ ■
for people ELCB's Vigicompact ■ ■ ■ ■ ■
Vigirex residual current relays ■ ■ ■ ■ ■ ■ ■
indications and measurementauxiliary and alarm switches (OF-SD-SDE) ■ ■ ■ ■ ■ ■ ■
local and/or distance control and monitoring (Dialpact) ■ ■ ■ ■ ■ ■ ■
data transmission (Dialpact) ■ ■ ■ ■ ■ ■ ■
voltage presence indicator ■ ■ ■ ■ ■
current transformer module ■ ■ ■ ■ ■
ammeter module ■ ■ ■ ■ ■
insulation monitoring module ■ ■ ■ ■ ■
control accessoriesshunt trip (MX) ; undervoltage release (MN) ■ ■ ■ ■ ■ ■ ■
direct or extended rotary handles ■ ■ ■ ■ ■ ■ ■
motor mechanism for remote control ■ ■ ■ ■ ■ ■ ■
installationversion fixed ■ ■ ■ ■ ■ ■ ■
plug-in on a base ■ ■ ■ ■ ■
draw-out on chassis ■ ■ ■ ■ ■ ■ ■
accessories terminal shields ■ ■ ■ ■ ■ ■ ■
padlocking and locking device ■ ■ ■ ■ ■ ■ ■
dimensions of 2-3 pole fixed version (mm) W 105 105 105 140 140 210 210H 161 161 161 255 255 374 374D 86 86 86 110 110 262 262
weight (kg) 3 pole fixed version 1.6 1.6 1.9 6.0 6.0 25 25
modelsvisible break circuit breaker Visucompactswitch - disconnectorautomatic / manual source changeover ■ ■ ■ ■ ■ ■ ■
Compact NS250L
STR 53 UE
test
MERLIN GERINcompact
NS400 LUi 750V. Uimp 8kV.
Ue(V)
220/240
380/415
440
500/525
660/690
100
70
65
40
35
IEC 947-2UTE VDE BS CEIUNE NEMA
Icu(kA)
cat B
Ics = 100% IcuIcw 6kA / 0,25s
In = 400A
pushto
trip
pushto
trip400
tr
tm
ImIr I
%Ir >Ir >Im >Ih
Io
x In.5
.6.7
.8 .91
1
Ir
x Io
.8.85
.88.9 .93
.95
1
.98
Im
x Ir1.5
2
34 5
6
10
8
Il
x In1.5
2
34 6
8
11
10
Ih
x In.2
.3
.4.5 .6
.7
10
.8
tr
(s) @ 6 Ir
1
2
48 16
16
th(s)
I2t1
2
34 4
3
1
2
on off
tm(s)
I2t0
1
23 3
2
0
1
on off
A
Compact NS400L
PUSH TO TRIP
MERLIN GERINcompact
C 1001 HUi 750V. Uimp 8kV.
Ue(V)
220/240
380/415
440
500/525
660/690
100
70
65
40
35
IEC 947-2UTE VDE BS CEI
UNE NEMA
Icu(kA)
cat B
Ics = 100% IcuIcw 8kA / 0,25s.
OFF
60 70 80 90 105 %Ir
STR 55UE
TFR
Io
xIn
T tr tmth
Ir ImIhI
test
fault
t
i
Compact C801L
12 Merlin Gerin Merlin Gerin 13
800 to 6300A: Masterpactdisconnector air circuit breaker
M08 M20 M32 M50M10 M25 M40 M63M12M16
number of poles 3 - 4 3 - 4 3 - 4 3 - 4
electrical characteristicsrated current (A) In 40°C 800-1000-1250-1600 2000-2500 3200-4000 5000-63004th pole rating (A) 800-1000-1250-1600 2000-2500 3200-4000 2500-3200rated insulation voltage (V) Ui 1000rated impulse withstand voltage (kV) Uimp 8breaking time (ms) total maxi. 25 to 30 (with no intentional delay)closing time (ms) <80rated operational voltage (V) Ue AC 50/60Hz 690utilisation category Bpollution degree IVfront face insulation class II ■
endurance with maintenance mechanical 20000 15000 15000 (10000 for M40) 10000CO cycle without maintenance mechanical 10000 10000 10000 (5000 for M40) 5000
electrical (440V) 10000 8000 3000 2000characteristics according to IEC 947-2 (1) N1 H1 H2 N1 H1 H2 H1 H2 H1 H2rated ultimate breaking capacity Icu 220/415V 40 65 100 55 75 100 75 100 100 150(kA rms) AC 50/60Hz 440V 40 65 100 55 75 100 75 100 100 150
500/690V 40 65 85 55 75 85 75 85 85 85rated service breaking performances Ics (% of Icu) 100 100 100 100 100 100 100 100 100 80
rated short-circuit making capacity Icm 220/415V 84 143 220 121 165 220 165 220 220 330(kA peak) 50/60Hz 440V 84 143 220 121 165 220 165 220 220 330
500/690V 84 143 187 121 165 187 165 187 187 187rated admissible short time Icw 0.5s 40 65 65 55 75 75 75 75 100 100withstand current (kA rms) 1s 30 50 50 55 75 75 75 75 100 100performances according NEMArated breaking capacity (O-CO) (kA) 480V 40 65 100 55 75 100 75 100 100 150
600V 40 65 85 55 75 85 75 85 100 100
trip unitssolid state ■
protectionsensor ratings (A) 200 to 1600 200 to 2500 600 to 4000 2000 to 6300
control unit protection type (2) instantaneous STR18 M ■
distribution STR28 D ■
selective STR38 S ■
universal STR58 U/68 U ■
unprotected circuit breaker / type NI HI HF NI HI HF HI HF HI HFrated short-circuit making capacity (kA peak) 220/690V 84 105 143 84 105 165 105 165 187 220rated breaking capacity for DC (Icu=Ics=Icw) HI type only 50kA 125V DC maximum, consult us for other specific version
indications, measurement and monitoringammeter STR28/38/58/68 ■
energy STR68 ■
maintenance indicator STR68 ■
data transmission STR68 ■
load monitoring STR58/68 ■
alarm indicator STR18/28/38/58/68 ■
segregated fault indicator STR38/58/68 ■
communication (Dialpact) STR58 ■
control accessoriesshunt trip ; closing release ; undervoltage release ■
motor mechanism for remote control ■
installationversion (front or rear fixed ■ ■ ■ ■ (M50)vertical or horizontal connections) draw-out ■
accessories automatic safety shutters ■
padlocking and locking devices ■
dimensions W x H x D (mm) 3 pole draw-out version 435 x 439 x 367 M50 : 815 x 484 x 367M63 : 1045 x 484 x 367
weight (kg) 3 pole draw-out version 65 (M16: 69) 82 M32 : 130 / M40 : 152 M50 : 215 / M63 : 245
push to reset
II1 I2 I3
90%
50%
20%
STR 58 UE
0.63Io Ir
0.8
0.5 1
xIn
90
105%Ir
.88.9 .92
.95
.981.8
.85
xIo
Im tm
3
4 56
8101.5
2
xIo
.3
.4 .3
.1.1
.2
on I2t off
.2
0
Ir fault
tr
Im fault
tm
I
faultIh
th
t
i
test
+ S –
– T +
T
F
Ih th
400
500 600800
1000
1200250
320
A
.3
.4 .4
.2.1
.2
on I2t off
.3
.1
I
off2
xIn
Ir :
Im :
th :
I
IG LI
GL
LG
LIG
off
reset V
tr60
120 240
480
1530
at 1,5Ir
4
6
8 12
17
22
Ic1 Ic2
.86
.9 .93.95
.98
1.8
.85
.7
.8 .85
.95
.5.6
xIr
.9
1
R
xIr
test
Opush OFF
MERLIN GERIN
M32 H1masterpact
IEC 947-2
00000
connected
test
disconnected
O OFF discharged
Ipush ON
Ui
Ue
Icu
Ics
Icw
1000V
380/440V
100kA
100kA
75kA 1s
50/60Hz
480/690V
85kA
85kA
Masterpact M08
14 Merlin Gerin Merlin Gerin 15
.4.2.1
MERLIN GERINinterpact
INS80Ui 500VUimp 6kV
Ith 80A@ 60°CUe(V) Ie(A)
AC23A
IEC 947.3UTE VDE BS CEI UNE
500 80AC22A
AC23ADC23A
806363
440500250
OFFO
ONI
Interpact INS80
Interpact IN switch-disconnectors IN250 IN400 IN630 IN1000 IN1600 IN2500number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
electrical characteristics as per IEC 947-3conventional thermal current (A) Ith 60°C 250 400 630 1000 1600 2500rated insulation voltage (V) Ui AC 50/60Hz 690 690 690 690 690 690rated impulse withstand voltage (kV) Uimp 8 8 8 8 8 8rated operational voltage (V) Ue AC 50/60Hz 690 690 690 690 690 690
DC 250 250 250 250 250 250rated operational current (A) Ie AC 50/60Hz AC 22 A AC 23 A AC 22 A AC 23 A AC 22 A AC 23 A AC 21 A AC 22 A AC 21 A AC 22 A AC 21 A AC 22 A
220/240V 250 250 400 400 630 630 1000 1000 1600 1600 2500 2500380/415V 250 250 400 400 630 500 1000 1000 (2) 1600 1600 (2) 2500 2500440/480 (1) -500V 250 250 400 400 630 500 1000 800 1600 1200 2500660/690V 250 125 400 250 500 320 1000 1600 2500
DC DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 21 A DC 22 A250V (1P) 250 250 400 400 630 630 1000 1000 1600 1600 1600
making capacity Icm (kA peak) switch-disconnector alone 30 40 50 75 75 105with upstream protection 330 330 330 176 105 105
short-time withstand current Icw (kA rms) 1s 8500 12000 25000 35000 35000 500003s 4900 6900 14400 20000 20000 2850020s 1900 2680 5590 7800 7800 11000
suitability for isolation ■ ■ ■ ■ ■ ■
endurance (category A) (CO cycles) mechanical 10000 10000 10000 3000 3000 3000electrical AC AC22A 690V 1000 1000 1000 500 500 500
AC23A 500V 1000 1000 1000electrical DC DC23A 250V 1000 1000 1000 500 500 500 (DC21A)
positive contact indication yes yes yes yes yes yesdegree of pollution III III III III III III
installationdimensions of 3 poles fixed FC (mm) W 230 280 280 340 340 340
H 170 230 230 300 300 440D 99.5 118 118 118 118 200
weight (kg) 3 poles, fixed, FC 2.7 4.3 4.8 12 15 35
(1) Suitable for 480 V NEMA.(2) IN1000 and IN1600: 630A in AC23A.
interpactMERLIN GERIN
IN630
IEC-VDE-BS-UTE
Ui 660 Vlth 630AAC 22 630AAC 23 500A380/415V500 V
I
0 OFF
Interpact IN630
40 to 2500A: Interpactswitch-disconnector
Interpact INS switch-disconnectors INS40 INS63 INS80 INS100 INS125 INS160number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
electrical characteristics as defined by IEC 947-3 and EN 60947-3conventional thermal current (A) Ith at 60°C 40 63 80 100 125 160rated insulation voltage (V) Ui AC 50/60Hz 690 690 690 750 750 750rated impulse-withstand voltage (kV) Uimp 8 8 8 8 8 8rated operational voltage (V) Ue AC 50/60Hz 500 500 500 690 690 690
DC 250 250 250 250 250 250rated operational current (A) Ie AC 50/60Hz AC 22 A AC 23 A AC 22 A AC 23 A AC 22 A AC 23 A AC 22 A AC 23 A AC 22 A AC 23 A AC 22 A AC 23 A
220/240-380/415-440/480V (1) 40 40 63 63 80 80 100 100 125 125 160 160500V 40 32 63 40 80 63 100 100 125 125 160 160660/690V 100 63 125 80 160 100
DC (4P in series) DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A DC 22 A DC 23 A250V 40 40 63 63 80 80 100 100 125 125 160 160
short-circuit Icm (kA peak) switch-disconnector alone 15 15 15 20 20 20making capacity with upstream protection 75 75 75 154 154 154short-time withstand current Icw (A rms) 1s 3000 3000 3000 5500 5500 5500
3s 1730 1730 1730 3175 3175 317520s 670 670 670 1230 1230 1230
suitability for isolation ■ ■ ■ ■ ■ ■
endurance (category A) (CO cycles) mechanical 20000 20000 20000 15000 15000 15000electrical AC AC22A 500V 3000 3000 3000 2000 2000 2000
AC22A 690V 2000 2000 2000electrical AC AC23A 440V 3000 3000 3000 2000 2000 2000
AC23A 500V 2000 (32A) 2000 (40A) 2000 (63A) 2000 2000 2000AC23A 690V 1500 (63A) 1500 (80A) 1500 (100A)
electrical DC DC23A 250V 1500 1500 1500 1500 1500 1500positive contact indication yes yes yes yes yes yesdegree of pollution III III III III III III
installationoverall dimensions of 3 poles (mm) W 90 90 90 135 135 135
H 81 81 81 100 100 100D 62.5 62.5 62.5 62.5 62.5 62.5
approximate weight (kg) 3 poles 0.5 0.5 0.5 0.8 0.8 0.8