Page 1: Masters of Engineering

Masters of Engineering

Small Signal Stability

Aaron CowanElectrical Engineering

Power

Page 2: Masters of Engineering

Small Signal Stability• Exciter

– Field current– Terminal voltage

• Power System Stabilizer– Enhance stability– Rotor angle

• Equal Area Criterion (Fig 13.5, Kundur)– Aa < Ad

– Aa > Ad

Page 3: Masters of Engineering

SMIB Example

delta _wr

delta _deltadelta _Tedelta _Psi_fd

v_s

v_1

delta _E_t

V_refw_0/s

Voltage Transducer

1

T_R.s+1

1

2*Hs+K_D

PSS

delta_wrv _s

K_6

K_5

K_4

K_2

K_1

1s

Field Circuit

K_3

T_3.s+1Exciter

K_AV_ref

delta _Tm

Problem details in section 12.3 of Power System Stability and Control, Kundur

Page 4: Masters of Engineering

Results

Matlabωd = 1.21Hzξ = 0.1447KS = 1.1062KD = 15.6306

Kundurωd = 1.05Hzξ = 0.15KS = 0.829KD = 14.08

State Matrix and eigenvalues agree

[0 −0.109 −0.123 0 0 0

376.99 0 0 0 0 00 −0.193 −0.4229 −27.317 0 27.3170 −7.312 20.839 −50 0 00 −1.037 −1.173 0 −0.714 00 −4.840 −5.477 0 26.969 −30.303

][Δ𝜔𝑟Δ𝛿Δ𝜓 𝑓𝑑Δ𝜈 1Δ𝜈 2Δ𝜈𝑠

]A =

Page 5: Masters of Engineering

Power World Transient Stability

slack

Bus1

72 MW 27 Mvar

Bus 4

Bus 5

125 MW 50 Mvar

Bus 2

163 MW 7 Mvar

Bus 7 Bus 8 Bus 9 Bus 3

85 MW -11 Mvar

100 MW 35 Mvar

Bus 6

90 MW 30 Mvar

1.026 pu1.025 pu

0.996 pu

1.016 pu1.032 pu 1.025 pu

1.013 pu

1.026 pu

1.040 pu

WECC equivalent in Power World

Page 6: Masters of Engineering

Exciter Models

Page 7: Masters of Engineering

Exciter Models

Page 8: Masters of Engineering

Exciter Models

Page 9: Masters of Engineering

PSS Model

Page 10: Masters of Engineering

IEEE 421.2

Page 11: Masters of Engineering

SMIB – Power World

• Equivalent SMIB• State Matrix• Eigenvalues{

Page 12: Masters of Engineering

Power World Transient Stability

slack

Bus1

72 MW 27 Mvar

Bus 4

Bus 5

125 MW 50 Mvar

Bus 2

163 MW 7 Mvar

Bus 7 Bus 8 Bus 9 Bus 3

85 MW -11 Mvar

100 MW 35 Mvar

Bus 6

90 MW 30 Mvar

1.026 pu1.025 pu

0.996 pu

1.016 pu1.032 pu 1.025 pu

1.013 pu

1.026 pu

1.040 pu

WECC equivalent in Power World

Page 13: Masters of Engineering

Stability Simulation• Default values used

– Did change TR to 0.02 in all cases• SEXS_GE and STAB1 ↔ Fig 17.5,

Kundur• Set all generator stability models

equal– Innumerable permutations

Page 14: Masters of Engineering

Stability Simulation• Fault on line 7-5

– Both breakers open– Cleared in 0.07 sec

• Three cases for each Exciter– Each generator

• Three cases for each Exciter+PSS– Each generator

Page 15: Masters of Engineering

Generator 1

Page 16: Masters of Engineering

Generator 1: ESAC1A

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

2520151050-5-10-15-20-25-30-35-40

220

200

180

160

140

120

100

80

60

40

20

0

-20

-40

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

20151050-5-10-15-20-25-30-35-40

240

220

200

180

160

140

120

100

80

60

40

20

0

-20

𝑀𝑊 0=71.6 𝛿0=3.5° 𝑀𝑊 𝑐𝑙𝑒𝑎𝑟=70.6 𝛿𝑐𝑙𝑒𝑎𝑟=−5.3 °

Page 17: Masters of Engineering

Generator 2

Page 18: Masters of Engineering

Generator 2: ESDC1A

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

100959085807570656055

2102001901801701601501401301201101009080706050403020100

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

100959085807570656055

220210200190180170160150140130120110100

9080706050403020100

𝑀𝑊 0=163 𝛿0=61.1° 𝑀𝑊 𝑐𝑙𝑒𝑎𝑟=163 𝛿𝑐𝑙𝑒𝑎𝑟=70.7 °

Page 19: Masters of Engineering

Generator 3

Page 20: Masters of Engineering

Generator 3: SEXS_GE

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

6059585756555453525150494847

100

95

90

85

80

75

70

65

60

55

50

45

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

5958575655545352515049

95

90

85

80

75

70

65

60

55

50

45

𝑀𝑊 0=85 𝛿0=54.1 ° 𝑀𝑊 𝑐𝑙𝑒𝑎𝑟=85 𝛿𝑐𝑙𝑒𝑎𝑟=51.9 °

Page 21: Masters of Engineering

Summary• Power World Transient Stability

– Block Diagrams– SMIB Eigenvalues

• ESDC1A without PSS• SEXS_GE with PSS• PSS stability enhancement

Page 22: Masters of Engineering

Small Signal Stability

Questions?

Page 23: Masters of Engineering

Generator 1: ESDC1A

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

151050-5-10-15-20-25-30-35-40-45

1701601501401301201101009080706050403020100

-10-20-30

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

151050-5-10-15-20-25-30-35-40-45

200

180

160

140

120

100

80

60

40

20

0

-20

Page 24: Masters of Engineering

Generator 1: SEXS_GE

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

20151050-5-10-15-20-25-30

180

160

140

120

100

80

60

40

20

0

-20

MW vs. Rotor Angle Generator 1

MW Terminal_Gen '1' '1'gfedcb

1614121086420-2-4-6-8-10-12-14-16-18-20-22-24-26-28-30

1701601501401301201101009080706050403020100

-10-20

Page 25: Masters of Engineering

Generator 2: ESAC1A

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

989694929088868482807876747270686664626058565452504846

2102001901801701601501401301201101009080706050403020100

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

95908580757065605550

2202102001901801701601501401301201101009080706050403020100

Page 26: Masters of Engineering

Generator 2: SEXS_GE

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

908886848280787674727068666462605856545250

2202102001901801701601501401301201101009080706050403020100

MW vs. Rotor Angle Generator 2

MW Terminal_Gen '2' '1'gfedcb

90888684828078767472706866646260585654

2001901801701601501401301201101009080706050403020100

Page 27: Masters of Engineering

Generator 3: ESDC1A

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

64636261605958575655545352515049

100

95

90

85

80

75

70

65

60

55

50

45

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

646362616059585756555453525150494847

105

100

95

90

85

80

75

70

65

60

55

50

45

Page 28: Masters of Engineering

Generator 3: ESAC1A

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

6160595857565554535251504948474645

100

95

90

85

80

75

70

65

60

55

50

45

MW vs. Rotor Angle Generator 3

MW Terminal_Gen '3' '1'gfedcb

61605958575655545352515049484746

105

100

95

90

85

80

75

70

65

60

55

50

45


Recommended