Evaluating Collection Spaces

I M A G E P E R M A N E N C E I N S T I T U T E | A U G U S T 1 5 , 2 0 1 9 T R A I N I N G S U S T A I N A B L E E N V I R O N M E N T A L M A N A G E M E N T T E A M S F O R C U LT U R A L I N S T I T U T I O N S

Page 2: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 2

Today’s Webinar

▶ Funding provided by the National Endowment for the Humanities Education and Training grant

▶ Series I: Environmental Management

▶ Series II: Environmental Data Analysis

▶ January 23, 2020

Page 3: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 3

IPI is an academic research center in the College of Art and

Design at the Rochester Institute of Technology (RIT) dedicated to

supporting the preservation of cultural heritage collections in

libraries, archives, and museums around the world.

Page 4: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 4

Your Presenters

Kelly M. Krish

Preventive

Conservation

Specialist

[email protected]

Christopher Cameron

Sustainable

Preservation

Specialist

[email protected]

Page 5: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 5

Questions Feedback

Page 6: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 6

Environmental Management: Phases

▶ Set-up

▶ Understand the problem

▶ Why is the environment important?

▶ Assemble documentation

▶ Build team

▶ Define objective

▶ Deploy instrumentation

Page 7: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 7

Assemble Documentation

Page 8: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 8

Levels of Control

Policies/Procedures

Location/Site

Building

Room

Storage Housing

Object

Page 9: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 9

Building and Room Envelopes

▶ Heat loads and sources of moisture:▶ Solar load

▶ Transmission through exterior

▶ Infiltration from surrounding spaces

▶ Openings (windows, doors, holes, structural design)

▶ Construction materials

▶ Presence of insulation, vapor barriers

▶ Within space (lights and electronics, people)

Page 10: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 10

Types of Collection Spaces

▶ Exhibition

▶ Storage areas

▶ Cold storage

Page 11: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 11

Understanding Mechanical

System

Page 12: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 12

HVAC Systems

Forced Air System

Air Handling Unit

Boiler

Air Conditioner

Page 13: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 13

Inside a unit

Cooling Coil Heating Coil

Page 14: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 14

Downstream Equipment

Humidifiers Reheats

Page 15: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 15

Supply Vents or

Diffusers

Page 16: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 16

Return Vents or

Grilles

Page 17: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 17

Best tool for determining air flow

Page 18: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 18

Supply and Return Issues

Page 19: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 19

Thermostats

Page 20: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 20

There should be free airflow to all thermostats

Page 21: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 21

Heating

Radiators

Page 22: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 22

Helpful Tools

Non-contact Digital Laser Infrared Thermometer

Temperature Gun

Page 23: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 23

Helpful Tools

IR Camera

Page 24: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 24

Helpful Tools: Zone Maps

Page 25: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 25

Zoning issues

▶ Multiple units that serve one space

▶ One air handling unit serving both occupied spaces and

collection spaces is not recommended

▶ Directors office, restrooms, galleries, server rooms, etc.. tied with

collection spaces

▶ Staff offices in collection spaces

Page 26: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 26

Human Comfort Control Issues

Human comfort requires different conditions than collections

Human comfort, according to ASHRAE: ▶ 68-75°F in the winter

▶ 75-80°F in the summer

Collections need cooler conditions

Page 27: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 27

Define Objective

Data Analysis

Page 28: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 28

An optimal storage environment is one that achieves the best possible preservation of collections with the least possible consumption of energy, and is sustainable over time.

Page 29: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 29

Extremes

▶ What: highs and lows of temperature and relative humidity

beyond what is usually experienced in the space

▶ Where: unconditioned spaces, lack of environmental

controls, areas with additional loads, change in operation

Page 30: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 30

Extremes

▶ How to Identify:

▶ Reports from staff

▶ Temp gun

▶ IR camera

▶ Environmental data

Page 31: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 31

Extremes▶ Consequences: Accelerated chemical deterioration,

increased risk of other forms of damage; operational costs

▶ Mitigation: Depends on cause▶ Secure building and room envelope

▶ Reduce moisture loads (landscaping, outside air)

▶ Reduce heating and cooling loads▶ Use shades, etc.

▶ Remove occupancy

▶ Reduce lighting

▶ Relocate/ buffer sensitive materials

Page 32: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 32

Harmful Microclimates

▶ What: The climate of a very small or

restricted area that differs from the

climate of the surrounding area

▶ Where: By supply diffusers, within

compact shelving, against exterior

walls/windows, inside containers, etc.

▶ Any place where differences exist

Page 33: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 33

Harmful Microclimates

▶ How to Identify:

▶ Reports from staff

▶ Temp gun

▶ IR camera

▶ Environmental data

▶ Anemometer

▶ Moisture meter

Page 34: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 34

Harmful Microclimates

▶ Consequences: Mold outbreaks can

occur, increased risk of other forms of

damage; operational costs

▶ Mitigation: Depends on cause▶ Arrange boxes and storage furniture to

promote air mixing▶ Identify and eliminate sources of

dampness▶ Relocate/ buffer sensitive materials

Page 35: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 35

Sustainability ▶ Depends on:

▶ Local Climate

▶ Building Envelope

▶ Mechanical System

▶ Collection Needs

▶ Institution’s Goals

▶ Achievable with:

▶ Knowledge of Collections

▶ Team Approach

▶ Reliable Data

▶ Experimentation

Page 36: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 36

Outdoor vs. Desired Conditions

Temperature Dew Point

High temperatures High moisture

Page 37: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 37

Influence of Building Envelope

Temperature Dew Point

Page 38: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 38

Influence of Mechanical System

Temperature Dew Point

Cooling

Heating

Dehumidification

Humidification

Page 39: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 39

Effects of Heating LoadsTemperature

Page 40: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 40

Build Team

Evaluate Options

Page 41: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 41

Risk Management: Teamwork

Team members:

▶ Those who create the environment (Facilities staff)

▶ Those responsible for preservation of collections (Collections staff)

▶ Those who work in and around collections (Curatorial, Interpretation)

▶ Those responsible for administration and finances (Administration, Finance)

▶ Those who direct the sustainability mission and goals (Sustainability officers)

Page 42: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 42

Risk Management: Control

▶ Policies/Procedures

▶ Location/Site

▶ Building

▶ Room

▶ Storage Unit

▶ Object

▶ Avoid

▶ Block

▶ Reduce

▶ Detect

▶ Respond

Levels of Control Methods of Control

Page 43: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 43

Risk Management: Control

▶ Building

▶ Respond

Levels of Control Methods of Control

▶ Room

▶ Storage Unit

▶ Object

▶ Detect

▶ Reduce

▶ Block

Page 44: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 44

Risk Management: Options

Factors to consider:

▶ Timeframe

▶ Cost

▶ Impact

▶ Sequence/relationship with other options

▶ Goals/priorities preservation plan

Page 45: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 45

Institute Actions

Page 46: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 46

DO:

▶ Assemble Documentation

▶ Collections

▶ Building Envelope

▶ Mechanical System and Downstream Equipment

▶ Build team

▶ Define objective

▶ Deploy instrumentation

▶ Begin data collection, analysis

Page 47: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 47

DO NOT:

▶ Institute certain actions without awareness of the consequences

▶ Open windows

▶ Install window A/C unit

▶ Arbitrarily lower temperatures

▶ More outside air/economizer

▶ 2012 Energy Conservation Code recommends an economizer to be capable of supplying 100% outside air

▶ 5°F temperature dead band

▶ Can lead to significant change in RH

Page 48: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 48

Advocacy

With effective team management, you can:

▶ Define realistic, sustainable preservation and operational goals

▶ Reduce operational inefficiencies

▶ Reduce the number of human comfort calls

▶ Improve communication and understanding between collection and facility staff

Page 49: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 49

Advocacy: Collections

Experiences Metrics

Page 50: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 50

Advocacy: Institution

▶ Mission

▶ Research

▶ Outreach

▶ Professionalism

Page 51: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 51

Advocacy: Financial

▶ Preventive vs. Interventive

▶ Sustainability

▶ Prioritization

Page 52: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 52

Other Challenges

▶ Dedicated funding

▶ Phased approach

▶ Grants

▶ Equipment loans

▶ Staff time

▶ Shared responsibilities

▶ Less time spent on repeated issues

▶ Other

Page 53: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 53

Conclusions ▶ Documentation

▶ Building

▶ Mechanical system and equipment

▶ Layout

▶ Defining Objective, Data Analysis

▶ Extremes and microclimates

▶ Capabilities of climate, envelope, system

▶ Evaluate Options

▶ Levels and methods of control

▶ Institute Actions

Page 54: Evaluating Collection Spaces...One air handling unit serving both occupied spaces and collection spaces is not recommended Directors office, restrooms, galleries, server rooms, etc

| 54

Thank you!