1994 Northridge Earthquake
Widespread failure ofwelded flange - boltedweb moment connections
Page 2 of 51
EngDoc.ir
Damage Observations:Steel MomentConnections
Backup Bar
Beam Flange
Column FlangeStiffener
Weld Access Hole
Pre-NorthridgeWelded Flange – Bolted Web Moment Connection
Page 3 of 51
EngDoc.ir
Page 4 of 51
EngDoc.ir
Page 5 of 51
EngDoc.ir
Page 6 of 51
EngDoc.ir
Page 7 of 51
EngDoc.ir
Page 8 of 51
EngDoc.ir
Page 9 of 51
EngDoc.ir
Page 10 of 51
EngDoc.ir
Page 11 of 51
EngDoc.ir
Page 12 of 51
EngDoc.ir
StressConcentrations:
• Weld accesshole
• Shear in flange
• Inadequateflexuralparticipation ofweb connection
Page 13 of 51
EngDoc.ir
Page 14 of 51
EngDoc.ir
Page 15 of 51
EngDoc.ir
Improved Weld AccessHole
See Figure 11-1 in the 2005AISC Seismic Provisions fordimensions and finishrequirements
Page 16 of 51
EngDoc.ir
Page 17 of 51
EngDoc.ir
Page 18 of 51
EngDoc.ir
Page 19 of 51
EngDoc.ir
38
ANSI/ASIC 358-10
Page 20 of 51
EngDoc.ir
39
Refers to
Relies on
ANSI/AISC 358 Prequalified Connectionsfor Special and Intermediate Steel Moment
Frames for Seismic Applications
SOME SPECIFICS
Page 21 of 51
EngDoc.ir
• Reduced Beam Section Connection• Bolted Unstiffened and Stiffened Extended End-
Plate Moment Connections• Welded Unreinforced Flange – Welded Web
• Bolted Flange Plate• Kaiser Bolted Bracket
• ConXtech Moment Connection
The Double Tee Stub is currently being balloted.
Connections PrequalifiedIncluding Supplement No. 1
42
Reduced Beam Section (RBS) Connection
Page 22 of 51
EngDoc.ir
43
End Plate Moment Connections
Unstiffened Stiffened Stiffened4-Bolt: 4E 4-Bolt: 4ES 8-Bolt: 8ES
44
Bolted Flange Plate Connection
Page 23 of 51
EngDoc.ir
45
Welded Unreinforced Flange – Welded WebConnection
• Provisions apply only to the prequalifiedconnections.
• Beam and Column cross-section limitationsbased on specific test matrices
• Rolled and Built-up Members permitted• Specific welding requirements for built-up
members
Prequalified Unique Requirements
Page 24 of 51
EngDoc.ir
47
Specific Prequalified Connections
Reduced BeamSection (RBS)
Reduced Beam Section (RBS)
RBS Concept:
• Trim Beam FlangesNear Connection
• Reduce Moment atConnection
• Force Plastic HingeAway from Connection
Page 25 of 51
EngDoc.ir
49
Reduced Beam Section (RBS)
50
Connection was Prequalified at UT - Austin
Page 26 of 51
EngDoc.ir
51
Whitewashed Connection Prior to Testing
52
Whitewashed Connection Prior to Testing
Page 27 of 51
EngDoc.ir
53
Connection at 0.02 radian.
54
Connection at 0.02 radian.
Page 28 of 51
EngDoc.ir
55
Connection at 0.03 radian.
56
Connection at 0.04 radian.
Page 29 of 51
EngDoc.ir
57
Conformance Results
58
Reduced Beam Section (RBS)
Prequalification Requirements for RBS in SMF
• Beam depth: Up to W36
• Beam weight: Up to 300 lb/ft
• Column depth: Up to W36 for wide-flangeUp to 24-inches for box columns
• Beam connected to column flange(connections to column web not prequalified)
• RBS shape: Circular
• RBS dimensions: Per specified design procedure
Page 30 of 51
EngDoc.ir
59
Beam flange welds: - CJP groove welds- Treat welds as Demand Critical- Remove bottom flange backing andprovide reinforcing fillet weld
- Leave top flange backing in-place; filletweld backing to column flange
- Remove weld tabs at top and bottom flanges
Beam web to column connection:- Use fully welded web connection (CJP weldbetween beam web and column flange)
See ANSI/AISC 358 for additional requirements (continuity plates,beam lateral bracing, RBS cut finish, etc.)
Reduced Beam Section (RBS)
Prequalification Requirements for RBS in SMF
60
Reduced Section Geometry
fb0.75
61
Protected Zone
No Shear Studs.No welded, bolted, screwed or shot-in attachments for
perimeter edge angles,exterior facades, partitions,duct work,piping or other construction.
Decking arc-spot welds are permitted.
Reduced Beam Section (RBS)
62
Lateral Brace Violates Protected Zone
Page 32 of 51
EngDoc.ir
63
Lateral Brace Violates Protected Zone
64
End-Plate Moment Connections
Unstiffened Stiffened Stiffened4-Bolt: 4E 4-Bolt: 4ES 8-Bolt: 8ES
Specific Prequalified Connections
Page 33 of 51
EngDoc.ir
65
End-Plate Concept:
• No Field Welding• Simple Erection• Connection is Stronger than
Beam
• Special welding requirements• Concrete slab requirements
End-Plate Moment Connections
Connections were prequalified at Virginia Tech
66
End-Plate Moment Connections
Page 34 of 51
EngDoc.ir
67
For High Seismicand Wind
Applications
AISC Design Guide 4
68
Weld access hole not permitted because ofruptures that occurred during testing.
Rupture
End-Plate Welding
Page 35 of 51
EngDoc.ir
Weld access hole not permitted because ofruptures that occurred during testing.
Rupture
End-Plate Welding
70
Recommended welding procedure:
• No weld access holes• Surface Preparation:
– All surfaces ground clean– Flanges beveled 45º full depth
• Minimum root opening
45°
45°
Typical Beam
End-Plate Welding
Page 36 of 51
EngDoc.ir
71
Recommended welding procedure:Welding Sequence:1. Fillet welds on both sides of web
installed.2. Fillet welds on inside of flanges
installed.3. Flange groove weld root backgouged
and flange groove welds installed.Note: Welds over webs are not CJP. Backgouge
Backgouge
1
2
3
3
End-Plate Welding
72
• Effective end-plate width in calculations– Beam flange width + 1 in.
• Bolt gage < beam flange width• Bolt spacing and pitch
– Provide adequate tightening clearances• Finger shims
– Used to correct beam length variations
Detailing Requirements
Page 37 of 51
EngDoc.ir
73
• Length of Stiffener
Lst = hst / tan 30º
30°±
1"±
Lst
1"±
hst
4ES and 8ES Stiffener Detailing
74
8-Bolt Stiffened Moment End-Plate, 8ES
Page 38 of 51
EngDoc.ir
75
8-Bolt Stiffened Moment End-Plate, 8ES
76
Prequalification Requirements:
• Beam depth: Min. and max. in Table 6.1
• Beam weight: No limit
• Column depth: Up to W36
• Beam connected to column flange(connections to column web not prequalified)
• Bolts: A325 or A490
• Finger Shims: Permitted
End-Plate Moment Connections
Page 39 of 51
EngDoc.ir
77
Rig
id L
ink
Lateral SupportTyp.
CompositeSlab
Pin Support
Rig
id L
ink
W24x68 W24x68
Test Column
ReactionFrame
ActuatorTest Frame
W14
x257
Connection Test with Concrete Slab
78
Test 1 with Concrete Slab
Page 40 of 51
EngDoc.ir
79
Test 1 with Concrete Slab
80
Premature Bolt Rupture
Test 1 with Concrete Slab
Page 41 of 51
EngDoc.ir
81
W27x84 (A992)NORTH
W27x84 (A992)SOUTH
W14x311 (A
36)
11'-0" 11'-0"
7'-0"
10'-0" 10'-0"
7'-0"
7'-2
"6'-11
"
PAPPLIED
LATERAL SUPPORT
W14X22FILLER BEAM
PIN SUPPORT
PIN
SU
PP
OR
T
PIN
SU
PP
OR
T
1 1/4" END PLATE (A36)W/ 1 1/8"Ø A325 BOLTS
5" COMPOSITE SLAB(3" COVER ON 2"COMPOSITE METAL DECK)
10'-0" 10'-0"
3'-0
"3'-0
"
1'-11 1/4"3'-4 1/2" 4'-8 1/4"
NO STUDSHINGE ZONE
EN
D O
FS
TIF
FE
NE
R
1'-11 1/4"4'-8 1/4" 3'-4 1/2"
NO STUDSHINGE ZONE
EN
D O
FS
TIF
FE
NE
R1/2" MIN. GAPFORMED W/ NEOPRENEFILLED W/ FOAM INSUL.
5" COMPOSITE SLAB(3" COVER ON 2 COMPOSITE METAL DECK)
REINFORCED W/ 4x4-W2.9xW2.9 WWF
3/4"Ø X 4" SHEAR STUDS@ 1'-0" MAX.
DOUBLER PLATE(FAR SIDE)
Test 2 with Concrete Slab
82
Test 2 with Concrete Slab
Page 42 of 51
EngDoc.ir
83
-250
-200
-150
-100
-50
0
50
100
150
200
250
-0.05 -0.04 -0.03 -0.02 -0.01 0.00 0.01 0.02 0.03 0.04 0.05
Total Rotation (rad.)
Col
umn
Tip
Load
(kip
s)
-250
-200
-150
-100
-50
0
50
100
150
200
250
-0.06 -0.04 -0.02 0.00 0.02 0.04 0.06
Beam Rotation (rad.)
Col
umn
Tip
Load
(kip
s)
Column Tip Load Column Tip Loadvs . vs.
Total Rotation Beam Rotation
Test 2 with Concrete Slab
84
Requirement for All Prequalified BoltedConnections
Compressible expansion joint material, atleast 1 in. thick, shall be installed to isolatethe column/connection from the concrete
slab.
Page 43 of 51
EngDoc.ir
85
Bolted FlangePlate (BFP)
Specific Prequalified Connections
86
Bolted Flange Plate (BFP)
BFP Concept:
•Shop Welded/Field Bolted•A325 or A490 bolts
•Top and bottom flangeplates must be identical
•Hinge at end of flangeplates
Page 44 of 51
EngDoc.ir
87
Prequalified atU. of California
at San Diego
Bolted Flange Plate (BFP)
88
Bolted Flange Plate (BFP)
Page 45 of 51
EngDoc.ir
89
Bolted Flange Plate (BFP)
90
Bolted Flange Plate (BFP)
Page 46 of 51
EngDoc.ir
91
Bolted Flange Plate (BFP)
92
Bolted Flange Plate (BFP)
Page 47 of 51
EngDoc.ir
93
Bolted Flange Plate (BFP)
94
Bolted Flange Plate (BFP)
Page 48 of 51
EngDoc.ir
95
FractureLocation Close-up of Fracture
Location
Bolted Flange Plate (BFP)
96
Welded UnreinforcedFlange - Welded Web
(WUF–W)
Specific Prequalified Connections
Page 49 of 51
EngDoc.ir
97
WUF-W Concept:
• Full beam strength• Shop welded single plate
with bolts for erection• Field welded beam flange
to column flange• Field welded single plate to
beam web• Similar to pre-Northridge
Welded Unreinforced Flange- Welded Web(WUF-W)
connection
98
Welded Unreinforced Flange- Welded Web(WUF-W)
Erection Bolts
Page 50 of 51
EngDoc.ir
[email protected]@kiau.ac.irLink d. Alireza rezaeian
با تشکر از توجه حضار گرامی
Page 51 of 51