8/10/2019 Electrical WIP Test Form
1/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE / TIME
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
TEST CARRIED OUT BY (Sub-contractor) : TEST WITNESSED BY :
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
Note : Note:Refer to Room Performance Sheets
DECLARATION :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No 002 (May 20
Installed Correctly, (YES/NO
FORM NO. : F-QM-EET-0
ATTENUATORS TEST FORM
YES NO YES
Attenuator
ReferenceManufacturer Type Non-Shedding Type, (YES/NO) Size
NO
YES NO YES NO
YES NO
YES NO YES
YES NO YES
NO
YES NO
NO
YES NO YES NO
YES NO
YES NO YES
YES NO YES
NO
YES NO
NO
YES NO YES NO
YES NO
YES NO YES
YES NO YES
NO
YES NO
NO
YES NO YES NO
YES NO
YES NO YES
YES NO YES
NO
YES NO
NO
YES NO YES NO
YES NO
YES NO YES
YES NO YES
NO
YES NO
NO
YES NO YES NO
YES NO YES
YES NO YES
YES NO YES
NO
NO
YES
NO
YES NO YES NO
(Name/Signature) (Date) (Client Representative)(MDCBP - MEFPS Field QC Engineer)
NOYES NO
(Sub-Contractor PIC / QAQC) (Client Representative)
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
MDCBP - MEFPS Field QC Engineer
8/10/2019 Electrical WIP Test Form
2/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE / TIME :
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
TEST CARRIED OUT BY : TEST WITNSSED & RESULTS ACCEPTED BY :
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
Location
Design
Lighting
Level
Distance
Measured
from floor
Average Lighting Level in LUX
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
Tested
No of Locations Average Emergency Lighting
LevelBy Date
FORM NO. : F-QM-EET-002
ILLUMINATION LEVEL TEST
FORM
Data recorded above has been reviewed and found to besatisfactory.
_____________________________ ______________________
(Client Representative)
(Client Representative)(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
(Sub-Contractor/Approved Testing Agency) (MDCBP MEPFS Field QC Engr.)
8/10/2019 Electrical WIP Test Form
3/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location :
Schematic :
1. Cell Details
a. Manufacturer g. Type
b. Connection h. Material
c. Signal Output* i. Serial No.
d. Temperature Sensing, MA/MV* j. Range, Me. Correct tag no.attached, YES/NO* k. Calibration Certificate No.
f. Removable for calibration, YES/NO* l. Correction Factor
2. Transmitter Details
a. Manufacturer k. Type
b. Item of plant controlled l. Serial No.
c. Range, M m. Alarm relays
d. Electrical Supply, V n. Sensor type
e. Tag Label attached YES/NO * o. No. of Outputs:
f. Temp Compensation AUTO/MANUAL *INDICATING/RECORDING *
g. Type and form of Output 1 MA/MV * INDICATED/RECORDED *
h. Type and form of Output 2 MA/MV * INDICATED/RECORDED *
i. Combined Unit calibrated to SOP/Method Statement reference.
j. Results available in RAW DATA/SITE SYSTEM *
Calibrated by:
Test Instrument :
Serial No. :
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
(Sub-Contractor PIC / QAQC)
COMMENTS :
DECLARATION :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
__________________________________________________
FORM NO. : F-QM-EET-003
CONDUCTIVITY CELL ANDTRANSMITTER TEST FORM
______________________________
(Name/Signature) (Date)
(Client Representative)
Data recorded above has been reviewed and found to besatisfactory. _____________________________ ______________________________________(Client Representative) (Date)
(MDCBP - MEFPS Field QC Engineer)
8/10/2019 Electrical WIP Test Form
4/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED :TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
Distribution Board Reference No.: Type:
Legend : A = Between Ends Of P (N) (C.P.C.) at Distribution Board
B = Test Lead
C = Closed Ends At Distribution Board & Mid Point Ring
A B C A C A B C A B
A B C A C
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
DISTRIBUTION : MDCBP Document Controller
Revision No. 002 (May 2014)
C
Circuit
No.
Resistance Phase (W) Verification Resistance Neutral (W) Verification
B
FORM NO. : F-QM-EET-004
CONTINUITY OF RING METAL
CIRCUIT CONDUCTORS TEST
FORM
Circuit
No.
Resistance C.P.C. (W) Verification Tested
B By Date
(Client Representative)(MDCBP - MEFPS Field QC Engr.)(Sub-Contractor PIC / QAQC)
Subcon
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
8/10/2019 Electrical WIP Test Form
5/28
PROJECT :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
1. Distribution Board Reference No:
2. Type:
3. Test Results:
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
FORM NO. : F-QM-EET-005
CONTINUITY OF PROTECTIVE
CONDUCTOR TEST FORM
( ) By Date
CONTROL NO. :
R1 + R2 R1 + R2 Zs
( ) ( )
Circuit No.
Design
Test VerifyTested
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ______________________
(Client Representative)
(Client Representative)(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
8/10/2019 Electrical WIP Test Form
6/28
PROJECT :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location :
Schematic :
I. Motor Control Centres
1. Manufacturer: 4. Heater Size (W) :
2. Type: 5. Main Fuse Size (A) :
3. Serial No:. 6. Control Fuse Size (A) :
II. Incomer Details
1. Fed From: 6. Ampere Rating:
2. Voltage Rating: 7. Frame:
3. Fault Rating: 8. Thermal:
4. Type No: 9. Cable Size:
5. Earth Connection Type:
III. Control Bus Section
IV. Instrument Details
Voltmeter Range: Ammeter Range:
Protection Detail Incl. CT Ratio: CT Ratio:
V. Check List (
if satisfactory )
Holding Bolts Busbar Chamber Busbar Joints
Insulators in Place Locking Mechanism Mechanical Check OK
Labels To Drawing Detail Shutters Operate Heater Operation OK
VI. Test Data
S-E T-ES-T T-R
* Phase Rotation Correct : Yes No
Earthloop (Zs), W :
Main Fuse Size, A :
Control Fuse Size, W:
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
FORM NO. : F-QM-EET-006
MOTOR CONTROL
CENTERS TEST FORM
(Sub-Contractor PIC / QAQC)
/ /
Insulation Resistance (M W )
CONTROL NO. :
R-E
Transformer KVAVolts Ratio Primary/Secondary
Fuse Size Primary/Secondary
No. 1 / /
No. 2
Data recorded above has been reviewed and found to
be satisfactory._____________________________ ______________________
(Client Representative)
R-S
(Client Representative)(MDCBP - MEFPS Field QC Engineer)
8/10/2019 Electrical WIP Test Form
7/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location :
Schematic :
POWER TRANSFORMERS - CAST RESIN
Manufacturer: Rating: App. Std:
Equipment No: Voltage Ratio: Impedence: Cooling Forced? Yes/No:
Serial No: Amps HV: Set points C: Yes No
Type: LV: Enclosure Type: (Normal Tapping)
Weight: Temp Class: Vector Group: Frequency:
Temperature Monitoring: Alarm Set Point C Trip Set Point C
Cable HT Reference: Cable LV Reference:
SUPPLIERS/MANUFACTURER'S TEST DATA
Phase Phase
Check List ( if satisfactory) :
R-S S-T T-R
mW
mW
Sign : Date :
Enclosure Interlocked with HV Tap Change Operation Phase Marking Bonding
Temperature Monitored Tap Change Lock-in - Pos Transformer Label
Sign : Date :
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
(Sub-Contractor PIC / QAQC)
The following were tested and found to be satisfactory:
Noise level at full load(dBA) : * Temperature trip: Yes No
Fans On (C) : * Temperature alarm: Yes No
Fans Off (C) : * Cooling fans : Yes No N/A
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
FORM NO. : F-QM-EET-007
POWER TRANSFORMERS -
CAST RESIN TEST FORM
(PLANT INSPECTION)
Impedance Voltage - MeasuredTest Report Reference No.(Available in raw data/site
system *)
Position
(Normal)Uk(%) Ur(%) Ux(%) J(
oC) Ur(%) Uk(%) J(
oC)
Partial Discharge Phase
No-Load
Losses(w)
Current
(%)
Short Circuit Losses
(W)Voltage
(%)
Inception Voltage (...x Urated)
PD at 1,5 Usystem, 30 sec (pC)
Rated PD at 1,1 Usystem, 3 min (pC)
Measured Extinction Voltage (...x Urated)
L.V. Test Time (sec) Test Time (sec)
Induced Voltage Test Applied Voltage Test
Resistance of winding at ______________C L.V. Winding (Volt) H.V.-L.V./Core (KV)
Excited by (Hz) L.V.-Core (KV)
H.V. Position Frequency L.V. -Screen (KV)
Data recorded above has been reviewed and found to
be satisfactory.
_____________________________ ______________________
(Client Representative)
(Client Representative)(MDCBP - MEFPS Field QC Engineer)
8/10/2019 Electrical WIP Test Form
8/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location :
Schematic :
Motor Drive Circuits :
MCC Item Ref. No: Drive Serving:
Type Of Starter: Star-Delta/Autotransformer/DOL/Soft/VSD/Other (specify)
Motor Details :
Manufacturer: FLC:
Model: Voltage: KW:
Serial No: Frequency: RPM:
Enclosure: Frame Size: IP Rating:
For Certified Equipment Only :
Approving Body : Certificate No : Class :
Cable Details :
Motor Cable No: Type:
Cores: Size / Length:
* Cable No: Insulation Resistance. (Incl. Motor) Checked? Yes No
Check List :
* Direction Of rotation (Whilst Looking At Non Drive End): Clockwise Anticlockwise
* Checked Labelling @ MCC: Yes NoTerminations Check Earthing Details
Motor State Method and Earth Wire:
Control Interfaces Earth Fault Loop Impedance (Zs):
Indication * If serving a variable speed drive, separate certificate has been completed:
Emergency Stop Yes No N/A
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
Test Data :
* Local Alarms Indication OK: Yes No * Emergency Stop Operation OK: Yes No
Running Current (Amps) : * General Indication OK: Yes No
Test carried out by: Test witnessed and results acccepted by :
COMMENTS :
NOTE : * Delete as applicable.
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 2014)
(Client Representative)
____________________________________________________________ _________________________________________________________________
(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
FORM NO. : F-QM-EET-008
MOTOR DRIVE CIRCUITSTEST FORM
(Sub-Contractor / Approved Testing Agency) (MDCBP MEPFS Field QC Engr.)
Data recorded above has been reviewed and found to besatisfactory.
_____________________________ ______________________
(Client Representative)
8/10/2019 Electrical WIP Test Form
9/28
PROJECT : REPORT NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No.:
System No.
1. Room Design Conditions : %RHo
C
2. External Design Conditions :
a. summer %RHo
C
b. winter %RHo
C
3. Room Loads :
a. Solar load, kW d. Equipment load e. Total Room load f. Occupancy load
b. Fabric load, kW - latent - latent - latent
c. Corrective load, kW - Sensible - Sensible - Sensible
Entrance
1) Heater positions to be agreed with Glaxo prior to testing, and shown on plan thus +
2) Chart recorder positions to be agreed with Glaxo prior to testing, units to be installed 1m above FFL,
Show positions on plan thus o.
4. Test Format
The test should last for a minimum of 48 hours to an agreed method statement including:
a. No load conditions
b. Progressive increase to simulated peak summer load conditions (i.e. part load).c. 8 hour period at simulated peak summer load conditions.
d. Period at reduced conditions (i.e.part load).
e. Period at no load conditions.
f. Period at no load conditions.
5. Test Instrument : Serial No.:
Note: Lights to be left on during testing
Test carried out by : Subcontractor Test witnessed and results accepted by : MDCBP Field QC Engineer
COMMENTS :
NOTE : * Delete as applicable.
DECLARATION :
Date :
DISTRIBUTION : Subcon MDCBP Document Controller
Revision No. 002 (May 201
FORM NO. : F-QM-EET-0
LOAD TEST FORM
Data recorded above has been reviewed and found to
be satisfactory._____________________________ ______________________
(Client Representative)
PQ
The result should be bound into Raw Data, with each chart marked to show; location and room reference, start and completion time and
date, Protocol No., equipment type and serial numbers and latent and sensible loads applied.
______________________ ________________ ______________________Subcontractor PIC / QAQC (Date) (Name/Signature) (Date)
_________________
8/10/2019 Electrical WIP Test Form
10/28
PROJECT : CONTROL NO.
LOCATION:
DATE PREPARED : DATE/TIME TESTING:
Functional Description :
Location :
Schematic :
PROTECTION RELAYS :
Manufacturer: Unit Type:Model No: Systems Voltage: Frequency:
Serial No: Settings Range: Ass. Switchboard/Mcc Ref:
R S T Neutral
INSTALLATION INSPECTED AND DETAILS RECORDED BY :
(MDCBP-MEFPS Field QC Engineer)
INSTALLATION COMPLIES WITH THE DESIGN :
Date :
SECONDARY INJECTION TESTS :
2 5 10
100
R 100
100
S 100
100
T 100
25 or 50
25 or 50
TEST CARRIED OUT BY : TEST WITNESSED AND RESULTS ACCEPTED BY :
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION : MDCBP Document Controller
Revision No. 002 (May 2014)
FORM NO. : F-QM-EET-0010
PROTECTION RELAYS
TEST FORM
current transformer
details
serial numbersratio manufacturer accuracy
(Subcontractor)
___________________________(MDCBP-MEFPS Supervisor)
Time Multiplier
SettingRelay
Phase
Element
1
0.5
1
0.5
Relay Setting
%
Pick-Up
Current
Operating Time @ Time Setting
Earth/Ground
1
0.5
Instantaneous O/C Relay Relay Setting
Over-Current
1
0.5
Tripping Current
R Phase
S Phase
T Phase
Subcon
________________________________________ __________________________________________
(Sub-Contractor / Approved Testing Agency) (MDCBP-MEPFS Field QC Engineer)
___________________________Data recorded above has been reviewed and found to
be satisfactory. (Client Representative)
8/10/2019 Electrical WIP Test Form
11/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : DATE/TIME TESTING:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
1. Data
Manufacturer: Type: Serial No.
Switchboard Ref: Rating: Voltage:
No. Poles: Frequency:
V.T. Ratio: / V Rated Breaking Capacity: kA for secs.
Description Of Open/Close/Trip Mechanisms & Operations:
2. Check List (
if satisfactory )
General Labelling General Operation
Status Indication Intertripping
Ammeter Key Interlocks
Voltmeter Shuttering
Kwhr Meter Protective Relay (See Below)
Other Instruments: Pad Locking Facilities
3. Current Transformers 4. Protective Relays Tests
R S T
5. Protective Devices
R S T N
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
Subcontractor PIC / QAQC
COMMENTS :
Note : * Delete as applicable
DECLARATION :
DISTRIBUTION :
Revision No. 002 (May 2014)
Type Of Relay :Instantaneous.
OvercurrentEarth Fault
FunctionRatio Note : For Detailed Results See Separate forms
Titled "Protection Relays". (IOTC/E/011, Item Ref.
No. _______________ ) This is confirmation only.
N E/L
FORM NO. : F-QM-EET-011
CIRCUIT BREAKER TEST
FORM
NoConnected ()
E/F
Primary Injection YES/NO* YES/NO*
Setting
Range
Secondary Injection YES/NO* YES/NO*
Function Manufacturer Type
(Client Representative)(MDCBP - MEFPS Field QC Engineer)
Subcon MDCBP Document Controller
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
8/10/2019 Electrical WIP Test Form
12/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
Manufacturer : Type:
Supplied From: Size Of Supply Cable :
Back-Up Fuse Rating
Test Results Verification:
a. Circuit Description List Provided* Yes No
b. Blanks Fitted On Outgoing Ways* Yes No
c. Adequate Warning & Identification Labelling Fitted* Yes No
kA
IR Polarity Zs RCD
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
Note : * Delete as applicable
DECLARATION :
DISTRIBUTION :
Revision No. 002 (May 2014)
Circuit No.Protective Device Load Current (A) Cable Size (mm
2) Earth Cable Size
(mm2)Size (A) Type
FORM NO. : F-QM-EET-012
DISTRIBUTION BOARD
TEST FORM
Verification Of Tests Carried Out () Inspected
Circuit No. Ring Continuity CPC Conti-nuity By Date
(Client Representative)
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
Subcon MDCBP Document Controller
8/10/2019 Electrical WIP Test Form
13/28
PROJECT : CONTROL NO:
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
Distribution Board Reference No :
Type :
P/N R/STN S/RTN T/RSN N/RST
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
(Sub-Contractor PIC / QAQC)
COMMENTS :
DECLARATION :
Date :
DISTRIBUTION :
Revision No. 002 (May 2014)
Between Poles
By Date
FORM NO. : F-QM-EET-013
INSULATION RESISTANCE
TEST FORM
Circuit No.No. of
Points
Insulation ResistanceTested
R+S+T+N To Earth
(MDCBP - MEFPS Field QC Engineer)
Subcon MDCBP Document Controller
(Client Representative)
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ______________________
(Client Representative)
8/10/2019 Electrical WIP Test Form
14/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED : TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
Cable Details
From To
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
DISTRIBUTION :
Revision No. 002 (May 2014)
Cable No.Circuit Cores Size
(mm2
)
Grade
Used SpareType (see Key
Below)
Conductor,
Cu/Al Volts
FORM NO. : F-QM-EET-014
CABLES AND CONDUCTORS
TEST FORM
Cable No.Insulation Resistance Test (M) Tested
Core-Core To Earth By Date
Key to Cable Type
1 = PVC/PVC 4 = XLPE/SWA/PVC 7 = XLPE/AWA/LSF 10 = * *
2 = PVC/SWA/PVC 5 = XLPE/AWA/PVC 8 = MICC 11 = * *
(Client Representative)(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
3 = PVC/AWA/PVC 6 = XLPE/SWA/LSF 9 = * *
Subcon MDCBP Document Controller
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
8/10/2019 Electrical WIP Test Form
15/28
PROJECT : CONTROL NO. :
LOCATION :
DATE/TIME PREPARED: TESTING DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
1. Distribution Board Reference No.: Type:
2. Earth Loop Impedance (Ze) at Distribution Board, W :
3. Type of Earthing System : TN-C/TN-S/TN-c-S/IT/TT*
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
Test Zs
(W)
Tested
By
Circuit
No.
Design
Zs ()Test Zs ()
TestedCircuit No.
Design Zs
(W)Date By Date
FORM NO. : F-QM-EET-015
EARTH FAULT LOOP
IMPEDANCE TEST FORM
(Client Representative)(MDCBP - MEFPS Field QC Engineer)( Sub-Contractor / QAQC )
8/10/2019 Electrical WIP Test Form
16/28
Date :
DISTRIBUTION :
Revision No. 002 (May 2014)
Subcon MDCBP Document Controller
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ______________________
(Client Representative)
8/10/2019 Electrical WIP Test Form
17/28
PROJECT : REPORT NO. :
LOCATION :
INSPECTION DATE/TIME:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
1. VARIABLE SPEED DRIVE
a. Manufacturer :
b. Type: g. Frequency, Hz:c. Serial No.: h.Continuous Rated Output Power, kVA :
d. Drive Ref:: i. Mains Supply - Voltage:
e. MCC Ref: j. Continuous Rated Output Current,A :
f. Method of Operation : PWM/VVC/Other (Please Specify) :
2. CHECK LIST ( if satisfactory or N/A if not applicable) :
a. Overall Operation YES NO N/A
b. Security Measure YES NO N/A
c. Labelling YES NO N/A
d. EMC Compatability YES NO N/A
e. Terminations YES NO N/A
3. SETTINGS :
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
DECLARATION :
DISTRIBUTION :
S
Po
DATE PREPARED:
Range
PI Feedback Scaling
PI Band Width
Set
Point Description Range
Motor Voltage
Analogue Reference PI Prop. Amplification SW. Freq. Range
Reset After Trip Rated Motor Current
Motor Current No Load Monitoring (a) SW. Freq. Range
Description
Output Frequency PI Integrate Time
Jogging Frequency Lower Frequency Limit, (Hz)
Description
FORM NO. : F-QM-EET
VARIABLE SPEED DRIVE
TEST FORM
RangeSet
Point
U/F Characteristic Thermal Motor Protection
Start/Stop Mode PI Feedback Type
Res. Bypass 2
Relay Function Current Limit (a) Res. Bypass 3
Rated Motor Output (kW) Switching Frequency
Local/Remote Operation Ramp-Down Time Res. Bypass 4
Res. Bypass 1
Local Reference (Hz) Read-Out Factor Ramp-Up Time
Digital Input Function
Analogue Output Upper Frequency Limit, (Hz) Rated Motor Voltage (v)
(Client Representative)(MDCBP - MEFPS Field QC Engineer)(Sub-Contractor PIC / QAQC)
Data recorded above has been reviewed and found to be satisfactory. ___________________________ _________________________
(Client Representative) (Date)
Subcon MDCBP Document Controller
8/10/2019 Electrical WIP Test Form
18/28
PROJECT : CONTROL NO. :
LOCATION :
DATE / TIME PREPARED: DATE / TIME TESTING:
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
THERMOSTAT
a. Manufacturer :
b. Type :c. Serial No. :
d. Range, (oC) :
e. Constant rating,A :
f. Length, mm :
g. Voltage,AC/DC *:
h. Body material :
i. Spring Design :
j. Positioned correctly, YES/NO * :
k. Item of plant being controlled :
l. Tag label attached, YES/NO * :
m. Calibrated to Sop/Method Statement * reference Results in Raw Data/Site System *
Calibrated by: Signature : Date :
Functional test satisfactory, YES/NO * :
Set point :
Test Instrument :
Serial No :
TEST CARRIED OUT BY (Subcontractor) : TEST WITNESSED & RESULTS ACCEPTED BY : MDCBP-Field QC Engr.
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
Note : * Delete as applicable
DECLARATION :
DISTRIBUTION :
Revision No. 002 (May 2014)
______________________ ________________ ______________________ _________________(Name/Signature) (Date) (Name/Signature) (Date)
FORM NO. : F-QM-EET-017
THERMOSTAT TEST FORM
Subcon MDCBP Document Controller
(Sub-Contractor PIC / QAQC) (Client Representative)(MDCBP - MEFPS Field QC Engineer)
Data recorded above has been reviewed and found to be
satisfactory._____________________________ ___________________________
(Client Representative) (Date)
8/10/2019 Electrical WIP Test Form
19/28
PROJECT : CONTROL NO. :
LOCATION :
DATE PREPARED: DATE / TIME TESTING :
Functional Description :
Location Drawing No. :
Schematic Drawing No. :
PRESSURE SWITCH
a. Manufacturer :
b. Type :
c. Differential :
d. Action DA/RA* :
e. Electrical Supply V,AC/DC * :
f. Location to Design, YES/NO * :
g. Tag label attached YES/NO * :
h. Results in Raw Data/Site System * :
i. Calibrated to Sop/Method Statement * : Reference :
Functional test satisfactory YES/NO * :
Set Point :
Test Instrument :
Serial No :
TEST CARRIED OUT BY: Subcontractor TEST WITNESSED & RESULTS ACCEPTED BY : MDCBP-Field Engr.
INSTALLATION INSPECTED AND DETAILS RECORDED BY : INSTALLATION COMPLIES W/ DESIGN :
COMMENTS :
Note : * Delete as applicable
DECLARATION :
DISTRIBUTION :
Revision No. 002 (May 2014)
(Date)
Data recorded above has been reviewed and found to be
satisfactory.(Client Representative)
_____________________________ ___________________________
_______________________(MDCBP - MEFPS Field QC Engineer)
PRESSURE SWITCH TEST
FORM
FORM NO. : F-QM-EET-018
______________________ ________________ ______________________
Subcon MDCBP Document Controller
_________________
(Client Representative)
(Name/Signature) (Date) (Name/Signature) (Date)
(Sub-Contractor PIC / QAQC)
8/10/2019 Electrical WIP Test Form
20/28
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
No. of
RunsLength,
m
No. of
RunsLength,
m
PREPARED BY: INSPECTED BY: APPROVED BY:
FROM TO
ITEM
NO.
LINE MANDRELLING TEST PIPES
REMARK
Primary
Ductline
FORM NO. : F-QM
MANDRELLING
TEST
PROJECT :
LOCATION :
Secondary
DuctlineMaterial Diameter, mm
8/10/2019 Electrical WIP Test Form
21/28
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
I. Type of Test: II. Equipment/Instrument Used:
Continuity Brand :
Resistance Serial No. :
Other/s Range :
III. Location / Item of Test :
IV. Continuity Test :
CIRCUIT
NO.L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1-G L2-G L3-G N-G
WIRE
SIZE
PREPARED BY: INSPECTED BY: APPROVED BY:
DESCRIPTION REM
FORM NO. : F
CONTINUITY
ELECTRICAL
TESTING
PROJECT :
LOCATION :
8/10/2019 Electrical WIP Test Form
22/28
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
INITIAL FINAL INITIAL FINAL INIT IAL FINAL
PREPARED BY: INSPECTED BY: APPROVED BY:
(MDCBP Supervisor / Superintendent)
DISTRIBUTION :
FORM NO. : F-QM-
ELECTRICAL
GROUNDING
TESTING
PROJECT :
LOCATION :
(MDCBP Field QC Engineer)
PT.1 PT.2 PT.3
(Subcon PIC/ QAQC)
Subcon MDCBP Document Controller
REMARKWIRE SIZE
Revision No. : 002 (M
ITEM
NO.LOAD DESCRIPTION QTY.
EARTH RESISTANCE READINGS(MEGA-OHMS)
8/10/2019 Electrical WIP Test Form
23/28
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1-G L2-G L3-G N-G
PREPARED BY: INSPECTED BY: APPROVED BY:
(MDCBP Supervisor / Superintendent)
DISTRIBUTION :
(Subcon PIC / QAQC) (MDCBP Field QC Engineer)
Revision No. : 002 (M
Subcon MDCBP Document Controller
CIRCUIT
BREAKERREM
CIRCUIT
NO.DESCRIPTION
FORM NO. : F-QM-E
ELECTRICAL
FUNCTIONAL
TESTING
PROJECT :
LOCATION :
VOLTAGE READINGS WIRE
SIZE
8/10/2019 Electrical WIP Test Form
24/28
Structural Sanitary/Plumbing Date Cond
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others _____________
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
A. Insulation Resistance Test
30sec. Test Instrument Used :
1min. Name/Type :
10min. Model/Serial No. :
Limit (Rdg>) Manufacturer :
Remarks Calibration Date :
B. Winding Resistance Test
Test Instrument Used :
1min. Name/Type :
10min. Model/Serial No. :
Limit (Rdg>) Manufacturer :
Remarks: Resistance value of each winding should not be far from each (small variance only) Calibration Date :
C. Turns Ration Test
Test Instrument Used :
Name/Type :
Model/Serial No. :
Manufacturer :
Calibration Date :
D. Excitation Current Test
Test Instrument Used :
Name/Type :
Model/Serial No. :
Manufacturer :
Calibration Date :
E. Diaelectric Breakdown Voltage Test of Insulating Oil
1 2 3 4 5
Remarks:
1. The limits for the winding resistance test are 5% difference with the other windings or compare with the manufacturer's test values.
2. The insulation resistance readings are corrected to 20 degrees Celsius with a multiplier of 1.98
3. The insulation resistance readings for the secondary windings should reached the equipment maximum range at a given test voltage.
4. Test results must be within the limits.
PREPARED BY: INSPECTED BY: APPROVED BY:
REMARKSLimits > 24KV
TYPE TRIALS AVERAGE inkV
WINDING
TERMINALSTAP
TEST
VOLTAGE
EXCITATION CURRENT
(Ma)REMARKS LIMITS +
X(0)-X(1) X(0)-X(2) X(0)-X(3)
WINDING
TERMINALSTAP
EXPECTED
RATIO
AS FOUND
RATIO
PERCENT DIFFERENCE
(%)
REMARKS
LIMITS +
Test Voltage: Test Voltage: Test Voltage:
TAP POSITION VOLTAGE
Primary Winding (Mohm)
VOLTAGE
Secondary Winding
(Milliohm)H(1)-(2) H(2)-(3) H(3)H(1)
TIMEPri-Ground (megaohms)
Pri-Secondary
(megaohms)
FO
TRANSFORMER TEST
PROJECT :
LOCATION :
Sec-Ground (megaohms)
8/10/2019 Electrical WIP Test Form
25/28
LOCATION :
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
5. Emergency to Normal Time (sec.)
PREPARED BY: INSPECTED BY:
(MDCBP Supervisor / Superintendent)
DISTRIBUTION : Subcon MDCBP Document Control
Revision No. : 002 (May 20
APPROVED BY:
(SubCon PIC / QAQC) (MDCBP Field QC Engineer)
REMARKS
1. Power Transfer
2. Load Sharing
3. Syncronization
4. Normal to Emergency Time (sec.)
6. Cool Down Time (sec.)
FORM NO. : F-QM-EET-0
AUTOMATIC
TRANSFER
SWITCH (ATS)
TESTING
PROJECT :
DATA AUTOMATIC MANUAL PASSED FAILED
8/10/2019 Electrical WIP Test Form
26/28
FORM NO. : F-QM-EET-025
Structural Sanitary/Plumbin Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
1 2 3 4 5 6 7 8
1. Power Factor %
2. Time(sec)
3. Circuit Breaker Rating
4. Ampere Trip
5. Kvar rating
6. Kvar rating/bank
7. Capacitor Brand
8. Feeder Type
9. Feeder Size
10. Feed Size(G)
11. No. of steps
12. Voltage reading
L1
L2
L3
L1-G
L2:G
L3-G
13. Ampere reading:
L1
L2
L3
14. Frequency:
15. Fed From:
PREPARED BY: INSPECTED BY: APPROVED BY:
DISTRIBUTION : MDCBP Document Controller
REMARKS
Revision No. : 002 (May 2014)
Subcon
CAPACITOR TEST
PROJECT :
LOCATION :
DATA NO. OF STEPS
8/10/2019 Electrical WIP Test Form
27/28
Structural Elec'l/Auxiliaries Sanitary/Plumbing FIR
Architectural Mechanical FDAS/BAS Oth
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
SMOKE HEAT BELLANNUNCIATO
R
MANUAL
PULL
STATION
FLOW
SWITCH
SUPE
Y SW
PREPARED BY: INSPECTED BY: APPROVED BY :
DISTRIBUTION :
TOTAL
LOCATIONSERIAL
NUMBER
DEVICE TYPE
ITEM
NO.NAME TAG
(Subcon PIC / QAQC) (MDCBP Field QC Engineer) (MDCBP Supervisor / Superintendent)
MDCBP Document Controller Subcon
FIRE ALARM TESTING
PROJECT :
LOCATION :
8/10/2019 Electrical WIP Test Form
28/28
Structural Sanitary/Plumbing Date Conducted : Control No. :
Architectural FDAS/BAS
Elec'l/Auxiliaries FIRE PRO
Mechanical Others
Site Location : Brand :
Equipment No. : Model/Serial No. :
Type/ Rating : Asset No. :
INITIAL FINAL
PREPARED BY: INSPECTED BY: APPROVED BY:
(MDCBP Supervisor / Superintendent)
DISTRIBUTION :
Revision No. : 002 (May 2014)
(Subcon PIC / QAQC) (MDCBP Field QC Engineer)
LOCATION
DECIBEL (db) FUNCTIONALTEST
REMARKS
DESIGNACTUAL
PASSED
Subcon MDCBP Document Controller
FORM NO. : F-QM-EET-027
BACKGROUND
MUSIC/PUBLIC
ADDRESS SYSTEM
TESTING
PROJECT :
LOCATION :
ITEM
NO.EQUIPMENT / DEVICE