203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
227
5004-M-78 FLAME SAFEGUARD REPLACEMENT CHASSISProductOverview
The5004-M-78 Flame Safeguard Replacement Chassis consists of the electronics of the 5004-M-85 flamesafeguard controller, designed tomount into anexistingQ7800A1005,Q7800B1003,orCB780(833-2725)wiringsubbase. It is a direct replacement for most RM7800E, RM7800L, and CB780 flame safeguard controllers.
• Existing scanners can be reused or replaced withPreferredUV,IR,orUVself-checkingscanners.
Onemodelnumber(5004-M-78)replacesanexisting:
• Controlchassis• Displaymodule• Purgetimer• Flameamplifier
As with the 5004-M-85, the flame amplifier inputs areuniversal. Purge timing, PTFI timing, and other controlfunctionsaredeterminedbyDIPswitchselection.
*QA5004-216RemoteDisplay(Optional)
Description Catalog Number5004-M-78 Boiler FSG Controller
FSGControllerw/ IntegralDisplay.UniversalUV, IR,UVSelf-Check, andFlameRod Input.DIPswitch selectablepurge,PTFI time,RS-485ModbusCommunications.FitsQ7800A1005,Q7800B1003,andCB780wiringsubbases.QA5004-216remotedisplay.
5004-M-78
OrderingInformation
5004-M-78 Chassis terminal designations
Rear view showing connector pins
22 NOT USED
21 15 SEC MTFI
20 FUEL POC
19 HF SWITCH
18 LF SWITCH
17 EXT. RESET
F
10
9
8
7
6
SCANNER (H)
IGNITIONXFMR
MAIN VALVES
PILOT
RUNNINGINTERLOCKS
START LIMITS
5
4
3
N
G
FD FANMOTOR
120 VAC L1
ALARM
120 VACNEUTRAL
SCANNER (L)
16
15
14
13
12
NOT USED
MODULATE
LOW FIRE
COMMON
HIGH FIRE
Quanta-Flame 5004-M-78 Flame Safeguard