ZA-1x-xxxx INSTRUCTION FOR USE AUTOMATIC STANDBY UNIT Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only. ENGLISH OEZ s.r.o., edivská 339, 561 51 Letohrad, Czech Republic, www.oez.com Š 991149c

ZA-1x-xxxx - OEZ

Embed Size (px)

Citation preview

Page 1: ZA-1x-xxxx - OEZ

ZA-1x-xxxx

INSTRUCTION FOR USE

AUTOMATIC STANDBY UNIT

Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

ENGLISH

OEZ s.r.o., edivská 339, 561 51 Letohrad, Czech Republic, www.oez.comŠ 991149c

Page 2: ZA-1x-xxxx - OEZ

DESCRIPTION

COMPOSITION OF TYPE DESIGNATION

OF SUPPLY

INSTALLATION

DIMENSIONS

SPECIFICATIONS

WIRING DIAGRAM

FUNCTION, SETTING

TIME DIAGRAMS

ERROR MESSAGE

PUTTING INTO OPERATION

TROUBLESHOOTING

3

4

5

5

7

8

9

10

10

11

13

14

15

17

20

Design ZA-11-xxxx

Built-in design ZA-x1-xxxx-B1

Built-in design with sheet-steel cover ZA-x1-xxxx-N1

Connecting for BC160... ZA-1x-7xxx

BL1000..., BL1600... ZA-1x-8xxx

Arion WL ZA-1x-6xxx

PARTS

Design ZA-10-xxxx

Connecting for BD250..., BH630... ZA-1x-7xxx

Connecting for

Connecting for

6

12

21

21

NECESSARY EQUIPMENT OF CIRCUIT BREAKERS/SWITCH-DISCONNECTORS CONTROLLED BY THE AUTOMATIC STANDBY UNI

TECHNICAL SUPPORT 23

- 2 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

CONTENTS

991149c

Page 3: ZA-1x-xxxx - OEZ

- 3 -

Design in switchboard IP65

Application

Function

The automatic standby unit (hereinafter referred to as ZA) is used to provide power supply without any long-term blackouts in various sectors of services, industry, etc.

The automatic standby unit ensures automatic and, above all, safe control of switching of two power supplies to twoloads so that the electric power is supplied without long failures.The automatic standby unit is designed for collaboration with circuit breakers/switch-disconnectors Modeion and ArionWL, which ensure power switching. For detailed information on circuit breaker/switch-disconnector fitting see page 10.The power supplies can be switched over by a failure of one or more phases, undervoltage or overvoltage of the powersupplies. The automatic standby unit enables the control (switching on/off) of the backup power supply (generator).

Control and settingBasic functions of the automatic standby unit are selected by a rotary switch on the front panel, and additionalsettings (modes and reaction times) are setby means of control panel.

display informing the operator about immediate state of circuit breakers, power supplies and actuallyperformed action.

ouch display for setting the parameters for automatic control of the standby mode. Example: reactiontimes (for detailed information see Table of Specifications on page 10), automatic standby mode (seefunctions and setting on page 15 - 16) or security password, which protects the automatic standby unitagainstunauthorized resetting.

otary switch for setting of 4 basic functions of the automatic standby unit(for detailed description see"functions and setting" on page 15 and 16).

he user can use undervoltage relays (only for design ZA-xx-xx1x) to set the values of undervoltage orovervoltage (independently of each other) to be evaluated by theautomatic standby unit as a power supplyfailure with taking an appropriate action.

here is a screw terminal block for connection of individual conductors, which connect the automatic unitwith circuit breakers/switch-disconnectors.

DescriptionOn the front panel there is

In the automatic standby unit

:

:

a) A

b) T

c) R

a) T

b) T

c) Every automatic standby unit includes terminals for connection of the STOPbutton (terminals 30 and 31).

d) Every automatic standby unit includes terminals for connection of the inspection button (terminals 40 and41). The inspection button serves for possible checks on instruments. If no mechanical interlocking isinstalled, it is necessary to beware of a parallel run. The inspection button will disable the control unitoperation and will supply power to the under-voltage releases, see the wiring diagram. If the sheet-steelcover is used, the inspection button is already included and is connected.

Two basic designsAutomatic standby unit is delivered:a) IP65.

b)I .

In metallic switchboard design

n built-in design in the switchboard door

The arrangement of circuit breakers/switch-disconnectorsand their connection to the automatic standby unitThe arrangement of circuit breakers (a distance between them) isnot limited in any way. If mechanical interlocking is used to increasesafety in manual control, the distance between the circuitbreakers/switch-disconnectors is given by the used mechanicalinterlocking.

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

DESCRIPTION

Touch display

Functions switchSwitchboard IP65

Advantages:The display of the automatic standby unit informsthe operator of the immediate state of circuitbreakers, power supplies and actually performedaction.

The automatic standby unit is protected againstunauthorized resetting by the password.

Safety

Power supply

The circuit breakers/switch-disconnectors are electrically interlocked by means of the automatic standbyunit so that in no case both the power supplies can be switched on simultaneously. To increase safety inmanual control it is possible to complete the circuit breakers/switch-disconnectors by mechanicalinterlocking.

The automatic standby unit must be supplied either from controlled power supplies (or from a momentarilyactive one) or from an independent external power supply such as UPS or AKU. The function of theautomatic standby unit depends in some cases on the power supply Metod (see time diagrams on page 17 -19).

The built-in design on the switchboard door

3

Basic block diagram

991149c

Page 4: ZA-1x-xxxx - OEZ

- 4 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

COMPOSITION OF TYPE DESIGNATION

01

01

678

012

01

6

MODI ZA - X X - X X X X - Y Special design codeB1 plastic transparent coverG1 signal for the generator (make-and-break contact)N1 sheet-steel cover, including the inspection button

for control of two power supplies with longitudinal coupling

monitoring of only loss of voltage

metallic switchboard design

control of combination of ARION WLControlled combinations of circuit breakers

built-in design on the switchboard door

with longitudinal coupling

control of combination of Modeion BL

Design

signal contacts of mode switch + signalling of circuit breaker switched ON+ signal for the generátor + failure state

own from active power supply (optional backup power supply AC/DC 24Vpower supply of the backup power supply AC/DC 110-230V

control of combination of Modeion BC, BD, BH

Signalling

Network monitoring circuit

power supply of the backup power supply DC 24VPower supply of the automatic standby unit

Mechanical arrangement

undervoltage relays with setting, monitoring of phase sequence

Customised design:B1G1

N1

-- - .

.b . - , 32 and 33 -

.

-

The circuit breaker is fitted with a plastic transparent cover.Signal for the generator start make-and-break contactThe automatic standby unit is fitted with a relay with a make-and-break contact Terminals 32, 33, 34 are conducted to the terminallock Terminals 32 and 34 make contact break

contact In the case of use of the G1design, theH4 signalling is notconnected.Sheet-steel cover with an inspection button. Possibility of sealingOf the terminal block for connection of the control circuits.

Design in switchboard IP65

We recommend consulting all designs with the manufacturer before placing an order.

By agreement with the manufacturer, it is possible to complete theautomatic standby unit e.g. by the following functions:

ignalling of further states and functionsonitoring of undervoltage on the loadonitoring of other external influences etc.

- S .- M .- M

991149c

Page 5: ZA-1x-xxxx - OEZ

- 5 -

INSTALLATION

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

PARTS OF SUPPLYAutomatic standby unit ZA-10-xxxx

Automatic standby unit ZA-11-xxxx

-- C- A- S

-- C- A- S 6

Instruction for useertificate of product quality and completenessutomatic standby unitcrew M8x8 4 pcs

Instruction for useertificate of product quality and completenessutomatic standby unitcrew M x8 4 pcs

Automatic standby unit ZA-10-xxxxThe switchboard of the automatic standby unit is adapted for the installation on the wall or integration in a distribution panel. t is necessary to use M8 screws to fasten it.The automatic standby unit must be mounted in such place that valid standards and operating conditions stated by the manufacturer, see the chapter Parameters, are observed.

I

I :nstallation procedure1) F2) I3) P 5 6

asten the switchboard on the wall by means of the attached screws M8.nterconnect the automatic standby unit with the circuit breakers, see Wiring diagram.erform setting and put the automatic standby unit into operation, see the chapter Functions and setting page 1 , 1 .

Automatic standby unit ZA-11-xxxxThe automatic standby unit is adapted for the mounting on the switchboard door. It is necessary to use M6 screws to fasten it. Theautomatic standby unit must be mounted in such place that valid standards and operating conditions stated by the manufacturer, see thechapter Parameters, are observed.

Installation procedure1) C2)3) F4) I5) I6) P 5 6

ut openings for the automatic standby unit display and function switch in the switchboard door.Fasten the display in the prepared switchboard door.

asten the base plate of the automatic standby unit and the function switch.nterconnect the display with the automatic standby unit base plate.nterconnect the automatic standby unit with the circuit breakers, see chap. Wiring diagram.erform setting and put the automatic standby unit into operation, see the chapter Functions and setting page 1 , 1 .

:

991149c

Page 6: ZA-1x-xxxx - OEZ

- 6 -

Design ZA-x0-xxx

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

DIMENSIONS

151

181 500

Drilling diagram for wall

43532,5 32,5

500

991149c

Page 7: ZA-1x-xxxx - OEZ

- 7 -

Design ZA-x1-xxxx

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

DIMENSIONS

30

Opening for functions switchOpening for display

458

43511,5 11,5

5010/45°

10,4

Protective spacease plateB

129

78,8

43,577,4

8

991149c

Page 8: ZA-1x-xxxx - OEZ

- 8 -

Built-in design with ZA-x1-xxxx-B1 plastic cover

458

370

458

43511,5 11,5

5010/45°

10,4

102

94

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

DIMENSIONS

Drilling diagram for mounting plastic cover

991149c

Page 9: ZA-1x-xxxx - OEZ

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

DIMENSIONSBuilt-in design with ZA-x1-xxxx-N1 sheet-steel cover

458179,5

11468

- 9 - 991149c

Page 10: ZA-1x-xxxx - OEZ

- 10 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

SPECIFIKATIONS

Standards

POWER SUPPLY

External (outlets 26,27) from independent pow er supplyAC Ue

DC Ue

Input pow er AC/DC 100 VA / 100 WOv erv oltage category I2)

Internal 3) from activ e pow er supplyRated frequency fn 50/60 Hz

ZA-0x -xx x x IP65/IP20ZA-x 1-x x x x by design sw itchboard/IP20

standardsradio emission ZA-00-x x x x or ZA-10-x x x x

ZA-01-x x x x or ZA-11-x x x x class Adisturbing v oltages ZA-00-x x x x or ZA-10-x x x x class B

ZA-01-x x x x or ZA-11-x x x xConnecting cross-sectionRange of ambient temperature 0 ÷ 50 °C

Local LCD(outlets 12-15)

(outlets 22-25)

Connecting cross-section S

Min. time betw een circuit breaker sw itching (standby time) 3 s (according to circuit breaker design)T1 0 ÷ 999 s, by 1 sT2 0 ÷ 999 s, by 1 sT3 0 ÷ 999 s, by 1 sTA 0,5 s

(the signalling only functions if the automatic standby unit is supplied)

0,5 ÷ 1 mm2 (recommended section min. 0,75 mm2)

Electromagnetic compatibility

class B

OPERATOR

Rated operating v oltage24 V1) for ZA-1x -x 0(1)x x , or 110 ÷ 230 V for ZA-0x -x 2x x

class B

Degree of protection internal/ex ternal

Weight

person w ith relev ant electrotechnical qualification

ZA-11-x x x x nebo ZA-11-x x x x 11 kg

24 V1) for ZA-1x -x 0(1)x x , or 110 ÷ 230 V for ZA-0x -x 2x x

ZA-10-x x x x 500 x 500 x 181 mmZA-11-x x x x see page 7ZA-10-x x x x nebo ZA-10-x x x x 21 kg

m

Controlled time of loss of v oltage 4)

Min. time betw een circuit breaker sw itching 4)

UNDERVOLTAGE RELAYS

Dimensions Wx Hx D

AC Ie / Ue

Controlled time of v oltage renew al

Underv oltage settingOv erv oltage setting 80 ÷ 130 % Un

TIME SETTING

Time from loss of v oltage to circuit breaker action 5)

70 ÷ 120 % Un

Remote10 A/230 V (AC-3) (potential-less contacts)

EN 60947-6-1; EN 60204-1; EN 60068-2-1; EN 60086-2-2; EN 60068-3-3Ik" = max . 10 kA, Ik" = >10 kA - necessary protection by fuses 6 ÷ 16 A w ithcharacteristic gG

EN 60947-1, EN 55011

DC Ie / Ue

0,5 ÷ 1 mm2 (recommended section min. 0,75 mm2)0,1 A/24 V (against terminal –)

OPERATION SIGNALLING

Ik”- short-circuit current in the circuit of power suppliesDepending on design, see page 4.From the power supply which is connected to the load; in failure of both power supplies the automatic standby unit is without voltage until voltage is renewed on one ofthe power supplies.In case of permanent supplying of the automatic standby unit.In case that the automatic standby unit is not supplied.With regard to classification of the device in the overvoltage category I (sensitive electronic devices) according to SN EN 60664-1 it is recommended to protect theautomatic standby unit MODI against overvoltage in accordance with EN 62305.For selection of an appropriate overvoltage protection it is possible to refer to theOvervoltage protections application manual, which can be freely downloaded at www.oez.cz.

Note:

2)

4)

5)

5)

1)

Circuit breaker type BC160 BD250… BH630… BL1000S BL1600S ARION WL

Accessories

Underv oltage release SP-BC-X024 SP-BHD-X024 SP-BHD-X024 SP-BL-X024 SP-BL-X024 -Aux iliary sw itch PS-BC-0010-Au PS-BHD-1100-Au PS-BHD-1100-Au PS-BL-2200-Au PS-BL-2200-Au -Alarm sw itch NS-BC-0010-Au PS-BHD-1000-Au PS-BHD-1000-Au - - -Relativ e sw itch - - - PS-BL-2200-Au PS-BL-2200-Au -Motor driv e MP-BC-X230-B MP-BD-X230 MP-BH-X230 MP-BL-X230 MP-BL-X230 -

ARION WL - - - - - ….-….-4AJ2-Z+C22+K07+x x x 1)

1) xxx - mechanical interlocking according to circuit breaker S55 - fixed designR55 - withdrawable design with frameR56 - for plug-in frameR57 - withdrawable circuit breakerNote: C

FF

ircuit breakers can be fitted by the mechanical interlocking.or detailed information on circuit breakers/switch-disconnectors BC160, BD250, BH630, BL1000 and BL1600 see the catalogue Moulded case circuit breakers.or detailed information on circuit breakers/switch-disconnectors Arion WL see the catalogue Air circuit breakers Arion WL.

NECESSARY EQUIPMENT OF CIRCUIT BREAKERS/SWITCH-DISCONNECTORS CONTROLLED BY THE AUTOMATIC STANDBY UNIT

2)

2) for switch-disconnectors it is not necessaryto install a signal switch

991149c

Page 11: ZA-1x-xxxx - OEZ

- 11 -

XT0

18

N-

H6

ZA

3.PS-BC-0010-Au

1.NS-BC-0010-AuL2

Z1

L1 PEL3 N

1.1

6

4

1

BC

1.BC160...

L2L3

T1

PEL1 N

3.BC160...

2

MP-BC-X230-B

4

SP-BC-X024

7

2

85

4

6

3

201203207 206

SP-BC-X024

D1D2

2

3.4

SB1

1L3

1

PEN

F

1L21L1

SA30 31 12 1413 15 1716

H1

L+ N-

H2

N-

H3

N- N-

H5H4

N-

1.2

5

3

L1

Z2

NL2 L3 PE

MP-BC-X230-B

205208204202

BC1

3.1

2

MP-BC-X230-B

4 1

2 4 1

SP-BC-X024107

108

102105

104

106

101

2L12L22L3

PE

L+

26 27

Uz

-

N- -

Uv

22 23

+ +

2524

++

H7 H8 H10H9

2.BC160...103

N

F

BC

L1

T2

NL2 L3 PE

40 41

SA2

Connectingí for Bc160...

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

WIRING DIAGRAM

T - transformerG - generatorF - fuses 6-16A with characteristic gG

ZA - automatic standby unit

1.BC160 - circu t breaker of power supply 1

2.BC160 - circu t breaker of power supply 2

Z - load

- phase sequenc must be observed- phase sequenc must be observed

XT0 - connecting terminal blockSA - functio switchH1-6 - function signalling of automatic standby unitH7 - circuit breaker 1 switched ON signalH8 - circuit breaker 2 switched ON signal

H10 - error signal26(L+), 27(N-) - external supplying from independent power supplySB1 - stop button

SP-BC-X024 - undervoltage r lease3.PS-BC-0010-Au - auxiliary swi1.NS-BC-0010-Au - alarm switchMP-BC-X230-B - motor drive

SP-BC-X024 - undervoltage r lease3.PS-BC-0010-Au - auxiliary swi1.NS-BC-0010-Au - alarm switchMP-BC-X230-B - motor drive

ee

e

e

n

tch

tch

- 10 A/AC 230 V (AC-3)- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )

- 0,1 A/DC 24 V (against terminal / - / minus )- AC/DC 24 V for ZA-xx-x0xx and ZA-xx-x1xx, or AC/DC 110 V, AC 230 V / DC 220 V for ZA-xx-x2xx

H9 - circuit breaker 3 switched ON signal (coupling)

(only design ZA-xx-xxxx-A3)

SP-BC-X024 - undervoltage r lease3.PS-BC-0010-Au - auxiliary swi1.NS-BC-0010-Au - alarm switchMP-BC-X230-B - motor drive

: during the use of the switch-disconnector it is not necessary to use the signal switch. In the case that the signal switch is not installed, it is necessary to interconnect terminalsfor connection of the switch(1st source - terminals 1 and 2; 2nd source - terminals 101 and 102).

- 0,1 A/DC 24 V (against terminal / - / minus )

i

i

3.BC160 - circu t breaker of the coupling

Note

ie

tch

Setting of the modeof the motor drive control 0

1 2

N

991149c

Page 12: ZA-1x-xxxx - OEZ

- 12 -

12

34

56

1.31.4

3.33.4

A1A2

L1L2L3

N PE

L1 L2 L3

L1 L2 L3

4 15641 5 2 6

N PE N PE

XT0

2

N PEL1 L2 L3

2 6 4 5 1

258

49

7

6

3

1

107

106

109104108105102

101

103

205208209204202201203207 206

1L11L21L3N

PE

2L12L22L3

NPE

26 27

N-L+

-

-

22 23 24 2512

L+

13 14 15 16 17 18

H7 H8 H9 H10

Uz

N- N- N- N- N- N-

H1 H2 H3 H4 H5 H6

Uv

+ + + +

ZABH

SP-BHD-X024BH

SP-BHD-X024

1.BH630... 2.BH630...

T1

MP-BH-X230-BMP-BH-X230-B

Z2

F F

1.BD250...

BD

MP-BD-X230-B

2.BD250...

BD

MP-BD-X230-B

T2

Z1

SP-BHD-X024

3.PS-BHD-1000-Au

1.PS-BHD-1000-Au

BD,BH

MP-BD-X230-BMP-BH-X230-B

3.BD250...3.BH630...

SA

SB1

SA2

40 41

Connecting for BD250... and BH630...

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

WIRING DIAGRAM

T - transformerG - generatorF - fuses 6-16A with characteristic gG

ZA - automatic standby unit

1.BD250…(1.BH630…) - circu t breaker of power supply 1

2.BD250…(2.BH630…) - circu t breaker of power supply 2

Z - load

- phase sequenc must be observed- phase sequenc must be observed

XT0 - connecting terminal blockSA - functio switchH1-6 - function signalling of automatic standby unitH7 - circuit breaker 1 switched ON signalH8 -H9 -H10 - error signal26(L+), 27(N-) - external supplying from independent power supplySB1 - stop button

SP-BHD-X024 - undervoltage r lease3.PS-BHD-1000-Au - auxiliary swi1.PS-BHD-1000-Au - alarm switchMP-BD-X230 (MP-BH-X230) - motor drive

SP-BHD-X024 - undervoltage r lease3.PS-BHD-1000-Au - auxiliary swi1.PS-BHD-1000-Au - alarm switchMP-BD-X230 (MP-BH-X230) - motor drive

ee

e

e

n

tch

tch

- 10 A/AC 230 V (AC-3)- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- AC/DC 24 V for ZA-xx-x0xx and ZA-xx-x1xx, or AC/DC 110 V, AC 230 V / DC 220 V for ZA-xx-x2xx

circuit breaker 2 switched ON signalcircuit breaker 3 switched ON signa (coupling)l

(only design ZA-xx-xxxx-A3)

SP-BHD-X024 - undervoltage r lease3.PS-BHD-1000-Au - auxiliary swi1.PS-BHD-1000-Au - alarm switchMP-BD-X230 (MP-BH-X230) - motor drive

: during the use of the switch-disconnector it is not necessary to use the signal switch. In the case that the signal switch is not installed, it is necessary to interconnect terminalsfor connection of the switch(1st source - terminals 1 and 2; 2nd source - terminals 101 and 102).

i

i

3.BD250…(3.BH630…) - circu t breaker of the coupling

Note

ie

tch

991149c

Page 13: ZA-1x-xxxx - OEZ

- 13 -

12

34

56

1.131.14

3.133.14

A1A2

3.213.22

L1L2L3

N PE

L1 L2 L3

L1 L2 L3

4 141 2

N PE N PE

XT0

2

N PEL1 L2 L3

2 4 1

258

4

7

6

3

1

107

106

104

108105

102

101

103

205208204202201 203207 206

1L11L21L3NPE

2L12L22L3

NPE

26 27

N-L+

-

-

22 23 24 2512

L+

13 14 15 16 17 18

H7 H8 H9 H10

Uz

N- N- N- N- N- N-

H1 H2 H3 H4 H5 H6

Uv

+ + + +

910

9 10

9

10

30 31

ZABL

SP-BL-X024

BL

SP-BL-X024

1.BL1600... 2.BL1000...

T1

Z2

F F

1.BL1000...

MP-BL-X230

2.BL1600...

MP-BL-X230

T2

Z1

SP-BL-X024

1.PS-BL-2200-Au

3.PS-BL-2200-Au

BL

MP-BL-X230

3.BL1000...3.BL1600...

SA1

SB1

SA2

4140

Connecting for BL

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

WIRING DIAGRAM

T - transformerG - generatorF - fuses 6-16A with characteristic gG

ZA - automatic standby unit

1.BL...- circu t breaker of power supply 1

2.BL...- circu t breaker of power supply 2

Z - load

- phase sequenc must be observed- phase sequenc must be observed

XT0 - connecting terminal blockSA - functio switchH1

SP-BL-X024 - undervoltage r lease3.PS-BL-2200-Au -1.PS-BL-2200-Au -MP-BL-X230 - motor drive

SP-BL-X024 - undervoltage r lease

MP-BL-X230 - motor drive

ee

e

e

n-6 - function signalling of automatic standby unit

H7 - circuit breaker 1 switched ON signalH8 - circuit breaker 2 switched ON signalH9 - circuit breaker 3 switched ON signa (coupling)lH10 - error signal26(L+), 27(N-) - external supplying from independent power supplySB1 - stop button (only design ZA-xx-xxxx-A3)

relative switchauxiliary swi

3.PS-BL-2200-Au - relative switch1.PS-BL-2200-Au - auxiliary swi

SP-BL-X024 - undervoltage r lease3.PS-BL-2200-Au - relative switch1.PS-BL-2200-Au - auxiliary swiMP-BL-X230 - motor drive

: during the use of the switch-disconnector it is not necessary to use the signal switch. In the case that the signal switch is not installed, it is necessary to interconnect terminalsfor connection of the switch(1st source - terminals 1 and 2; 2nd source - terminals 101 and 102).

- 10 A/AC 230 V (AC-3)- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- AC/DC 24 V for ZA-xx-x0xx and ZA-xx-x1xx, or AC/DC 110 V, AC 230 V / DC 220 V for ZA-xx-x2xx

i

i

tch

tch

tch

3.BL...- circu t breaker of the coupling

Note

ie

991149c

Page 14: ZA-1x-xxxx - OEZ

- 14 -

12

34

56

L1L2L3

N PE

L1 L2 L3

L1 L2 L3

N PE N PE

XT0

N PEL1 L2 L3

107106

104108

105

102

101

103

205 208 204 202 201203207 206

1L11L21L3NPE

2L12L22L3

NPE

26 27

N-L+

-

-

22 23 24 2512

L+

13 14 15 16 17 18

H7 H8 H9 H10

Uz

N- N- N- N- N- N-

H1 H2 H3 H4 H5 H6

Uv

+ + + +

210

X5.2X5.1

X6.7X6.8

X5.11X5.12

X6.3

X7.12X6.5

X6.6

X6.4X7.13

110

76

48

5

2

1

3

10

X5.2X5.1

X6.7X6.8

X5.11X5.12

X6.3

X7.12X6.5

X6.6

X6.4X7.13

30 31

ZA

T1

Z2

F F

1.Arion 2.Arion

T2

Z1

3.Arion

SA1

SB1

SA2

40 41

Connecting for Arion WL

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

WIRING DIAGRAM

T - transformerG - generatorF - fuses 6-16A with characteristic gG

ZA - automatic standby unit

1. Arion - circu t breaker of power supply 1

2. Arion - circu t breaker of power supply 2

Z - load

- phase sequenc must be observed- phase sequenc must be observed

XT0 - connecting terminal blockSA - functio switchH1-

26(L+), 27(N-) - external supplying from independent power supplySB1 - stop button

X5,6,7 - connector for connection of accessories (see the documentation of circuit breaker Arion)

ee

n6 - function signalling of automatic standby unit

H7 - circuit breaker 1 switched ON signalH8 - circuit breaker 2 switched ON signalH9 - circuit breaker 3 switched ON signa (coupling)lH10 - error signal

(only design ZA-xx-xxxx-A3)

X5,6,7 - connector for connection of accessories (see the documentation of circuit breaker Arion)

X5,6,7 - connector for connection of accessories (see the documentation of circuit breaker Arion)

Note: if the switch-disconnector is used, it is not necessary to use the signal switch “switched off by release”. In the case that the switch is not installed, it is necessary to interconnectterminalsfor connection of the switch (1st source - terminals 1 and 2; 2nd source - terminals 101 and 102).

- 10 A/AC 230 V (AC-3)- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- 0,1 A/DC 24 V (against terminal / - / minus )- AC/DC 24 V for ZA-xx-x0xx and ZA-xx-x1xx, or AC/DC 110 V, AC 230 V / DC 220 V for ZA-xx-x2xx

i

i

2. Arion - circu t breaker of the couplingi

991149c

Page 15: ZA-1x-xxxx - OEZ

Function:1) ) (switch positio 3, signalling H3)

.

Pc P

n

Possi le setting:bA A)b) riority of 1 power supply) riority of2 power supply

st

nd

AUTOMATIC OPERATION, AUTOMATIC STANDBYT

utomatic standby

f

he automatic standby unit can work in three modes, which are selected by means of control push-buttons on the display

urthermore, it is possible to set min. time of switching between power supplies (T ), time for detection of voltage (T ) and power supply failure (T ).2 3 1

- 15 -

3

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

FUNCTION, SETTINGFunction: de ermines automatic or manual operation

Mo e: de ermines priority of power supplies in automatic operation

t

t

(It is set by the rotary swit h)

(It is set by the control pu h-buttons of the automatic standby unit)

c

sd

Function switch:Position Function description

0 ( )Circuit breakers off, system reset reset of error messages1 ( )Circuit breaker 1 permanently on at mains failure the standby will not take place2 Circuit breaker 2 permanently on (at mains failure the standby will not take place)3 -Circuit breaker 1 and 3 permanently on coupling

(at mains failure the standby will not take place)

4 Circuit breaker 2 and 3 permanently on - coupling(at mains failure the standby will not take place)

5 Circuit breaker 1 and 2 permanently on (at mains failure the standby will not take place)6 Automatic operation, the circuit breakers are controled by the automatic standby unit

Mode:

a)

b )

c)

STANDBYFOR BOTH POWER SUPPLIES

STANDBYFOR 1 POWER SUPPLY

STANDBYFOR 2 POWER SUPPLY

Both loads can be supplied permanently from any power supply. In case of loss of voltage of the power supply theload is supplied from the load, the load is disconnected from the power supply and connected (via coupling closing)to 2 power supply. After voltage renewal of the original power supply the coupling opens, and the load isconnected to the original power supply.

The load 1 can be supplied from the power supply 1 or the power supply 2, the load 2 can only be supplied fromthe power supply 2. In case of loss of voltage of the power supply 1, the load 1 is disconnected from the powersupply 1, and connected to the power supply 2 (via coupling closing).After voltage renewal of the power supply 1the coupling opens and the load 1 is connected to the original power supply. In loss of voltage of power supply 2the load 2 will remain without voltage for the time of the loss of voltage of power supply 2, no standby will takeplace.

The load 2 can be supplied from the power supply 2 or the power supply 1, the load 1 can only be supplied fromthe power supply 1. In case of loss of voltage of the power supply 2, the load 2 is disconnected from the powersupply 2, and connected to the power supply 1 (via coupling closing). After voltage renewal of the power supply 2the coupling opens and the load 2 is connected to the original power supply. In loss of voltage of power supply 1 theload 1 will remain without voltage for the time of the loss of voltage of power supply 1,no standby will take place.

nd

ST

ND

2)MANUALOPERATION - both 1 power supply and 2 power supply areOFF

3)MANUALOPERATION - operation only with 1 power supply

MANUALOPERATION operation only with 2 power supply

MANUALOPERATION operation only with 1 power supply with closed coupling

MANUALOPERATION operation with both power supplies

st nd

st

nd

st

(switchposition0)

(switch position 1, signalling H1)The load 1 is permanently supplied from 1 power supply. In case of lossof voltage, the power supply is disconnected from the load automatically.The power supply willremain disconnectedeven after voltage renewal. The power supply can only be connected manually (by turning the switch gradually from position 1 to position 0

switch position 2 signalling

switch position signalling

switch position signallingThe load 1 is permanently supplied from 1 power supply,The load 2 is permanently supplied from 2 power supply. Incase of loss of voltage, the power supplies aredisconnected from the loads automatically.The power supplies will remain disconnected even after voltage renewal. The power supplies can only be connectedManually (by turning the switch gradually from position 5 toposition 0

in position 0 it is necessary to wait at least2 s before further handling the switch

st

1

st nd

The load 2 is permanently supplied from 2 power supply. In case of loss of voltage, the power supply is disconnected from the load automatically. The power supply willremain disconnected even after voltage renewalThe power supply can only be connected manually (by turning the switch gradually from position 2 to position 0

nd

Both loads are permanently supplied from 1st power supply. In case of loss of voltage, the power supply is disconnected from the load automatically. The power supply willremain disconnected evenafter voltagerenewal. Thepower supply can only beconnected manually (by turning the switch gradually from position 3 to position 0

switch position signallingBoth loads are permanently supplied from 2nd power supply. In case of loss of voltage, thepower supply is disconnected from the load automatically. The power supplywill remain disconnected even after voltage renewal.The power supply can only be connected manually (by turning the switch gradually from position 4 to position 0

MANUALOPERATION operation only with 2 power supply with closed couplingnd

)

1)

1)

).

).

- 1

( , H2)

( 3, H3)

( 5, H5)

- 5

4

5

7

) -

) -

) -

1) ).- 2

1)

1)

).

).

- 3

( 4, H4)

- 4

6) -

991149c

Page 16: ZA-1x-xxxx - OEZ

Setting of parametersAll parameters are blocked by password. After entering the password, all parameter options areaccessible until the parameter setup mode is terminated. The parameter setup menu is accessed bypressing the F1 key on the control panel. After it, it is necessary to enter the password again. Thepassword consists of 4 digits. These are set on the keyboard that appears when clicking in thepassword box. The password must be confirmed by “Enter”. After it, press the key F1 Parameters todisplay the Parameter Setup menu.

- 16 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

FUNCTION, SETTING

Setting of undervoltage relays nly design ZA-xx-xx1x(o )The automatic standby unit monitors the level of voltage of power supplies, power failures and phase sequence by means of undervoltage relays. On these relays it ispossible to set the overvoltage / undervoltage level, to which the automatic standby unit shall react within the range + 30 %/ -20 %; in case ofensuring permanent powersupply of the system from 2 or standby power supply, it is possible to set the tolerance of the monitored voltage at +/- 30 %. Delay of making of the undervoltage relaycontact is set by the manufacturer and cannotbe changed.

nd

Undervoltage settingof 2 power supplynd

Undervoltage settingof 1 power supplyst

Overvoltage settingof 1 power supplyst

Overvoltage settingof 2 power supplynd

Undervoltage relays

Setting the contrast of display ZAAfter booting (time limit to automatic booting the main screen by default 3 seconds if I do not, thecontrast can be set up when restarting ZA) select Control Panel —› OP —› Contrast —› UP neboDOWN

The password is the serial number of the automatic standby unit!

Function mode of automatic standby unit ZAThe required mode is set by pressing the relevant push-button in the Parameter menu(Main/backup, Equivalent, Backup/main). Current mode is displayed on the display.

Time setting of automatic standby unit ZA3 times are set in the parameter menu:T1 - The time, for which an error must sustain on the power supply to be considered a failure.T2 - The time, for which the load must be without voltage, i.e. the time of switching over between

the circuit breakers.T3 - The time, in which the power supply must be renewed to be considered good.

Termination of parameter settingUse the keys F2-4 for return to the main screen.

Control panel - setting of parameters

Control panel - main screen

Connection to the ZA control unit

Earthing

Supply connection from ZA

991149c

Page 17: ZA-1x-xxxx - OEZ

Funcion: Mode:Power supply of the automatic standby unit:

automatic standby Standby for both power supplies (1 power supply is a transformer, 2 power supply is a transformer)from active power supply

st nd

- 17 -

1.AZ 2.AZ 5.AZ3.AZ 4.AZ

UT2

QT2

Q3

UZ1

UZ2

UnA

QT1

UT1

T1 T2 T3 T1 T2 TAT1

T3

T3

T2

T2T1

T2

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

TIME DIAGRAMSTime diagram 1

U voltage of 1 transformerQ circuit breaker of 1 transformerU voltage of 2 transformerQ circuit breaker of 2 transformerQ switch-disconnector of the longitudinal couplingU voltage on the load 1U voltage on the load 2U power supply of the automatic standby unitT controlled time of loss of voltageT min. time between circuit breaker switchingT controlled time of voltage renewalT time from loss of voltage to circuit breaker action in

case that the automatic standby unit is not supplied

T1

T1

T2

T2

3

Z1

Z2

nA

1

2

3

A

st

st

nd

nd

note: imest T , T , T are adjustable1 2 3

FUNCTION DESCRIPTIONInitial stateVoltage exists on both1 power supply and 2 power supply.The load 1 is supplied from 1 power supply and the load 2 is supplied from 2 power supply.

In case of loss of U for a time longer than T1, Q is switched off automatically and if U exists for at leastT , Q (coupling) is switched onautomatically afterT .

After renewal of U for min.T , Q (coupling) is disconnected and Q is switched on automatically after T . In case of loss of U for a timeshorter thanT1, the automatic standby unit does not react to such loss of voltage.

In case of loss of U for a time longer thanT ,Q is switched offautomatically and and if U exists for at least T , Q (coupling) is switchedon automatically afterT .

In case of loss of U and absence of U ,Q and Q (coupling) are switched off automatically afterT .After renewal of U for min.T , Qand Q (coupling) are switched on automatically.The condition for switching Q on is expiration of time T .

In case of loss of U for a time longer than T1, Q and Q (coupling) are disconnected automatically. Even if the voltage U is presentLonger than T , the Q and Q (coupling) is switched on only after T .

st nd st nd

T1 T1 T2 3 3

2

T1 3 3 T1 2 T2

T2 1 T2 T1 3 3

2

T1 T2 T1 3 A T2 3 t2

3 T2 2

T2 T2 3 T1

3 T1 3 2

:

a a (3.AZ)

4 a a (4.AZ)

1 utomatic st ndby :

2 utomatic st ndby :

st

nd

th

a a (1.AZ)

a a (2.AZ)

5 automatic standby (5.AZ):

3 utomatic st ndby :

utomatic st ndby :

rd

th

991149c

Page 18: ZA-1x-xxxx - OEZ

- 18 -

1.AZ 2.AZ 4.AZ 5.AZ3.AZ

UT2

QT2

Q3

UZ1

UZ2

UnA

QT1

UT1

T1 T2 T1 TAT1

T3

T3

T2

T2T1

T3 T2

Function: Mode:Power supply of the automatic standby unit:

automatic standby standby for power supply No. 1 (1 power supply is a transformer, 2 power supply is a transformer)from active power supply

st nd

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

TIME DIAGRAMSTime diagram 2

U voltage of 1 transformerQ circuit breaker of 1 transformerU voltage of 2 transformerQ circuit breaker of 2 transformerQ switch-disconnector of the longitudinal couplingU voltage on the load 1U voltage on the load 2U power supply of the automatic standby unitT controlled time of loss of voltageT min. time between circuit breaker switchingT controlled time of voltage renewalT time from loss of voltage to circuit breaker action in

case that the automatic standby unit is not supplied

T1

T1

T2

T2

3

Z1

Z2

nA

1

2

3

A

st

st

nd

nd

note: imest T , T , T are adjustable1 2 3

FUNCTION DESCRIPTIONI :nitial state

1 utomatic st ndby :

2 utomatic st ndby :

3 utomatic st ndby :

utomatic st ndby :

st

nd

rd

th

th

a a (1.AZ)

a a (2.AZ)

a a (3.AZ)

4 a a (4.AZ)

5 automatic standby (5.AZ):

Voltage exists on both 1 power supply and 2 power supply. The load 1 is supplied from 1 power supply and the load 2 is supplied from 2 power supply.

Incase of loss of U for a time longer than T , Q is switched off automatically and if U exists for at least T , Q (coupling) is switched on

After renewal of U for min.T , Q (coupling) is disconnected and Q is switched on automatically after T . In case of loss of U for a timeshorter thanT , the automatic standby unit does not react to such loss of voltage.

In case of loss of U for a time longer thanT ,Q is switched offautomatically.Even if U is presentat least for T , Q (coupling) will notswitch on.

In case of loss of U and absence of U ,Q is switched offautomatically afterT .After renewal of U for min.T , Q and Q (coupling)are switched on automatically .The condition for switching Q on is expiration of time T .

In case of loss of U for a time longer than T , Q and Q (coupling) are disconnected automatically. Even if the voltage U is presentLonger than T , the Q and Q (coupling) is switched on only after T .

st nd st nd

3

T1 1 T1 T2 3 3

T1 3 T1 2 T2

1

T2 1 T2 T1 3 3

T1 T2 T1 A T2 3 T2 3

T2 2

T2 1 T2 3 T1

3 T1 3 2

automatically after T .2

991149c

Page 19: ZA-1x-xxxx - OEZ

- 19 -

Function standby for power supply No. 2: Mode:Power supply of the automatic standby unit:

automatic standby (1 power supply is a transformer, 2 power supply is a transformer)from active power supply

st nd

AUTOMATIC STANDBY UNIT MOD IZA for the circuit breakers Modeion and Arion WL

TIME DIAGRAMSTime diagram 3

U voltage of 1 transformerQ circuit breaker of 1 transformerU voltage of 2 transformerQ circuit breaker of 2 transformerQ switch-disconnector of the longitudinal couplingU voltage on the load 1U voltage on the load 2U power supply of the automatic standby unitT controlled time of loss of voltageT min. time between circuit breaker switchingT controlled time of voltage renewalT time from loss of voltage to circuit breaker action in

case that the automatic standby unit is not supplied

T1

T1

T2

T2

3

Z1

Z2

nA

1

2

3

A

st

st

nd

nd

note: imest T , T , T are adjustable1 2 3

FUNCTION DESCRIPTIONInitial stateVoltage exists on both 1 power supply and 2 power supply.The load 1 is supplied from 1st power supply and the load 2 is supplied from 2 power supply

After renewal of U for min. T , Q (coupling) is disconnected and Q is switched on automatically after T In case of lossofU for a timeshorter than T , the automatic standby unit does not react tosuch lossof voltage.

In case of loss of U for a time longer than T , Q is switched off automatically. Even if U is present at least for T , Q (coupling)will not switch on.

In case of loss of U and absence of U ,Q is switched offautomatically afterT .After renewal of UT1 for min.T , Q and Q (coupling)are switched on automatically.The condition for switching Q and Q (coupling) on is expiration of time T .

In case of renewal of U and loss of voltage of U in T , Q and Q (coupling) are disconnected automatically after T . IfT expires beforeT , Q and Q (coupling) are switched offafterT .Q is switched on automatically after T .

st nd nd

T2 3 3 T1 2 T1

1

T1 1 T2 T2 3 3

T2 T1 T2 A 3 T1 3

T2 3 2

T2 T1 3 T1 3 1 3

1 T1 3 3 T2 2

:

a a (1.AZ)

a a (2.AZ)

a a (3.AZ) P d v n d d n d a v . I když je p ítomno dobu ,nedojdez (spojky)

5 automatic standby (5.AZ):

1 utomatic st ndby :

2 utomatic st ndby :

3 utomatic st ndby : okud ojde k ýpadku U a obu elší ež T , ojde k utomatickému ypnutíQ U min.po T kapnutíQ .

st

nd

rd

th

T 1 2 T 31 T 2

3

4 a a (4.AZ)th utomatic st ndby :

991149c

Page 20: ZA-1x-xxxx - OEZ

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

ERROR MESSAGES

- 20 -

It is not possible to sw itch on the circuit breaker 1 Circuit breaker 1 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)It is not possible to sw itch on the circuit breaker 2 Circuit breaker 2 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)It is not possible to sw itch on the circuit breaker 3 Circuit breaker 3 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)It is not possible to sw itch off the circuit breaker 1 Circuit breaker 1 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)It is not possible to sw itch off the circuit breaker 2 Circuit breaker 2 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)It is not possible to sw itch off the circuit breaker 3 Circuit breaker 3 w as not sw itched on in time Tz (set in the automatic standby unit program; not selectable)

Circuit breaker 1 sw itched off by releaseThe release of the circuit breaker 1 tripped (for BC160, BD250, BH630, Arion). If the circuit breaker is ofw ithdraw able design, the message may be caused by w ithdraw al of the circuit breaker.

Circuit breaker 2 sw itched off by releaseThe release of the circuit breaker 2 tripped (for BC160, BD250, BH630, Arion). If the circuit breaker is ofw ithdraw able design, the message may be caused by w ithdraw al of the circuit breaker.

Circuit breaker 3 sw itched off by release The release of the circuit breaker 3 tripped (for BC160, BD250, BH630, Arion)Error of circuit breaker 1 The release of the circuit breaker 1 tripped or other fault of the circuit breaker (for BL1000, BL1600)Error of circuit breaker 2 The release of the circuit breaker 2 tripped or other fault of the circuit breaker (for BL1000, BL1600)Error of circuit breaker 3 The release of the circuit breaker 3 tripped or other fault of the circuit breaker (for BL1000, BL1600)Crcuit breaker 1 sw itched off spontaneously Circuit breaker 1 sw itched off w ithout the automatic standby unit command; this is not tripping from a releaseCircuit breaker 2 sw itched off spontaneously Circuit breaker 2 sw itched off w ithout the automatic standby unit command; this is not tripping from a releaseCircuit breaker 3 sw itched off spontaneously Circuit breaker 3 sw itched off w ithout the automatic standby unit command; this is not tripping from a releaseError of sw itch change during outage In failure of pow er supply of the automatic standby unit, the position of the function sw itch w as changedPow er supply 1 w as bey ond tolerance Pow er supply 1 w as out of tolerance or had a failurePow er supply 1 w as bey ond tolerance Pow er supply 2 w as out of tolerance or had a failure

Circuit breakers off Automatic standby unit is sw itched offCircuit breaker 1 on Load 1 is supplied from pow er supply 1Circuit breaker 2 on Load 2 is supplied from pow er supply 2Circuit breakers 1 and 3 on Both loads are supplied from pow er supply 1Circuit breakers 2 and 3 on Both loads are supplied from pow er supply 2Circuit breakers 1 and 2 on The load 1 is supplied from the pow er supply 1 and the load 2 is supplied from the pow er supply 2.

Position 0 - sw itched off Circuit breakers off, sy stem reset (nulov ání chy bov ý ch hlášení )Position 1 - permanently 1 Circuit breaker 1 permanently on (at mains failure the standby w ill not take place)Position 2 - permanently 2 Circuit breaker 2 permanently on (at mains failure the standby w ill not take place)Position 3 - permanently 1 and 3 Circuit breakers 1 and 3 permanently on - coupling (at mains failure the standby w ill not take place)Position 4 - permanently 2 and 3 Circuit breakers 2 and 3 permanently on - coupling (at mains failure the standby w ill not take place)Position 5 - permanently 1 and 2 Circuit breakers 1 and 2 permanently on (at mains failure the standby w ill not take place)Position 6 - automat Automatic operation, the circuit breakers are controled by the sy stem MODI

Pow er supply 1 main - pow er supply 2 backup Main/backup mode, see Automatic standby functionEquiv alent pow er supplies Equiv alent pow er supplies mode, see Automatic standby functionPow er supply 1 backup - pow er supply 2 main Main/backup mode, see Automatic standby function

Both pow er supplies bey ond tolerance Both pow er supplies are out of the set tolerance or had a loss of v oltagePow er supply 1 OK / Pow er supply 2 not ready Pow er supply 1 is w ithin tolerance and pow er supply 2 has loss of v oltage or is not w ithin tolerancePow er supply 1 not ready / Pow er supply 2 OK Pow er supply 2 is w ithin tolerance and pow er supply 1 has loss of v oltage or is not w ithin tolerancePow er supply 1 w as out Pow er supply 1 w as out of the set tolerance or had a loss of v oltagePow er supply 2 w as out Pow er supply 2 w as out of the set tolerance or had a loss of v oltageBoth pow er supplies OK Both pow er supplies are w ithin the v oltage tolerance

MODE

POWER SUPPLIES

ERRORS

CIRCUIT BREAKERS

SWITCH

991149c

Page 21: ZA-1x-xxxx - OEZ

- 21 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

PUTTING INTO INTO OPERATION, TROUBLESHOOTING

1)P :UTTING INTO INTO OPERATION- Switch the „SA“ function switch to position „0“.- In case that the automatic standby unit is in the version with measurement of undervoltage / overvoltage and phase sequence (ZA-xx-xx1x), set the upper greentrimmer on the measuring relays „KA1, KA2“ to basic value of +10 % , and the lower green trimmer to 10 %.

- Switch on the both monitored power supplies; measure the voltage on the terminals „1L1-2L3“ of the terminal block „XT0“; in case that the power supply outputsare led in four-conductor (3 phases + PEN), it is necessary to interconnect the terminals „N“ and „PE“ on the terminal block „Xt0“.

- After application of voltage from the power supplies to the „XT0“ terminal board, the text "The circuit breakers off", "Both power supplies OK" appears on thedisplay.

- Check the parameter setting by means of the display of the control unit.

Mode - set to „main/backup“T1 - The time, for which an error must sustain on the power supply to be considered a failure - set to 0 s.T2 - The time, for which the load must be without voltage, i.e. the time of switching over between the circuit breakers - set to 0 s.T3 - The time, in which the power supply must be renewed to be considered good - set to 0 s.

- Switch the „SA“ switch, hereinafter only „SA“ to position „1“ - permanently circuit breaker 1.- The automatic standby unit must switch on the circuit breaker of 1 power supply and display the message " "- Switch the „SA“ switch to position „0“ off; the switched on circuit breaker must switch off; in this position it is necessary to be at least 2 s so that the control unit

will not reset.

- Switch the „SA“ switch to position „2“ - permanently circuit breaker 2.- The automatic standby unit must switch on the circuit breaker of 2 power supply and display the message “ ”.- Switch the „SA“ switch to position „0“ off; the switched on circuit breaker must switch off; in this position it is necessary to be at least 2 s so that the control unit

will not reset.- Gradually test in the same way the switch positions „1-5”, the automatic standby unit must in individual positions switch the circuit breakers as stated in the

chapter Functions and setting.

- Switch the „SA“ switch to position „6“ - automatic operation.- The automatic standby unit must switch on the circuit breakers of the both power supplies and display the message " " and "

".

- Switch off 1 power supply (it can be simulated by the switching off the circuit breaker FA1 on the panel of the automatic standby unit); the circuit breaker of 1power supply Q must switch off* and the circuit breaker of the coupling Q must switch on*.

- On the display there must be the message " " and " ".- Switch on 1 power supply (in case of simulation, switch on the circuit breaker FA1 on the panel of the automatic standby unit), the circuit breaker of the couplingQ must switch off* and after it the circuit breaker of 1 power supply Q must switch on*.

- On the display there must be the message " " and " ”.

- Switch off 2 power supply (it can be simulated by the switching off the circuit breaker FA2 on the panel of the automatic standby unit); the circuit breaker of 2power supply Q must switch off* and the circuit breaker of the coupling Q must switch on.

- On the display there must be the message " " and " ".- Switch on 2 power supply (in case of simulation, switch on the circuit breaker FA2 on the panel of the automatic standby unit), the circuit breaker of thecoupling Q must switch off* and after it the circuit breaker of 2 power supply Q must switch on*.

- On the display there must be the message " " and " ".- Switch the „SA“ switch to position „0“ off; the switched on circuit breakers must switch off; in this position it is necessary to be at least 2 s so that the control unitwill not reset.

* Time for power supply switching over i.e. the time from the moment of loss of voltage of the active power supply to the moment of switching on the standby is the sum ofreaction times of the control unit, charging of circuit breaker and times present in the automatic standby unit menu.

SET BY THE MANUFACTURER:

2) FUNCTION TESTING

st

nd

st s

T1

st

st

nd nd

nd

nd

Circuit breaker 1 on .

Circuit breaker 2 on

Circuit breakers 1 and 2 on Bothpower supplies OK

Circuit breakers 2 and 3 on Power supply 1 not ready, Power supply 2 OK

Circuit breakers 1 and 2 on Both power supplies OK

Circuit breakers 1 and 3 on Power supply 1 OK, Power supply 2 not ready

Circuit breakers 1 and 2 on Both power supplies OK

3

3 T1

T2 3

3 T2

991149c

Page 22: ZA-1x-xxxx - OEZ

- 22 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

991149c

Page 23: ZA-1x-xxxx - OEZ

- 23 -

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

991149c

Page 24: ZA-1x-xxxx - OEZ

AUTOMATIC STANDBY UNIT MODI ZA for the circuit breakers Modeion and Arion WL

TECHNICAL SUPPORT