29
You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits… Training Course Introduction to SmartScan

Embed Size (px)

Citation preview

Page 1: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Training Course

Introduction to SmartScan

Page 2: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25

SmartScan 25 is a four‑wire, low‑voltage device, and is available with a customized graphic LCD display. SmartScan has two major components:

The main control unit The sensor (connected via a

cable).

SolidScan

Page 3: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Electronic

What do we get ?

5 independent SPDT relays AC/DC Power supply Communication:

4–20mA, RS - 232 / 485 Advanced calculations:

Volume Kg Totalization

SmartScan 25

Page 4: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25 can be used in the following applications:

Solid applications Long range liquid

applications Aggregates Dust

SmartScan 25Applications

Page 5: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25Models

SmartScan 25 Standard(L,O,S)

SmartScan 25 Long Range(L,O,S)

Liquid0.6m - 25m

1.96ft – 82.02ft

0.6m – 40m

1.96ft – 131.23ft

Open Channel0.6m - 25m

1.96ft – 82.02ft

0.6m – 40m

1.96ft – 131.23ft

Solid0.6m - 20m

1.96ft – 65.61ft

0.6m – 30 m

1.96ft – 98 ft

Page 6: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25

SmartScan 25 has a range of up to 40 m (131.23 ft)

An accuracy of 0.25% within that range

Resolution of 1 mm (0.03")

Accuracy & Resolution

MonoScan 0.25%

5m 40m30m25m20m15m12m8.5m

SmartScan 50 0.1% - 0.25% SmartScan 25 0.25%

Page 7: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25

Low energy transducer

After transmission, the transducer will detect severalechoes from the target.

The statistical calculation will be based on these echoes,giving a more accurate average.

25KHz sensor

Page 8: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

25 kHz Sensor’s recommendations (all ranges)

E-CTFE Coated Aluminum Designed for complex

environments with problematic echo, such as non-conductive vapors or liquids

Good performance in problematic applications

High resistance in acid and alcoholic environments

Available housing material PP/PVDF

SmartScan 25

Page 9: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

All CE sensors are supplied with either pre cut cable or with flexible cable.

EX sensors supplied with fixed length. Pre cut cables are offered at various length,

as indicated in the User’s manual and price list.

Flexible length supplied with 5 m/16.4ft loose-end cable and can be adjusted according the table in the next page.

Sensor cable specifications: 4 wires, 0.75 mm² overall shielded, compatible to HELUKABEL P.N.16028 (www.helukabel.de).

SmartScan 25 and 50Sensor cable recommendations

Page 10: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25 and 50

Can be changed to a range of

5m/16.4ft to 50m/164ft

50m/164ft to 100m/328ft

100m/328ft to 150m/492ft

150m/492ft to 200m/656ft

Flexible cables for 25 KHz and 50KHz sensors

Can be changed to a range of

5m/16.4ft to 100m/328ft

100m/328ft to 200m/656ft

50 KHz sensor cable25 KHz sensor cable

Note: All sensors are supplied with a 5 m’ loose-end cable when ordering flexible cables.

Page 11: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

25 KHz IS Sensors (all ranges)

Hazardous area Installation: Max. cable length

between unit and barriers: Up to 25m (82ft)

Max. cable length between sensor and barriers: Up to 75m (246ft)

SmartScan 25

Page 12: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25Fixed cables length for 25 KHz EX sensors

25 KHz EX sensor cable

Fixed cable length

25m/82ft

50m/164ft

75m/246ft

100m/328ft

Page 13: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

High added value – supplied with 4–20mA, 5 independent SPDT relays, RS - 232 or RS – 485, Modbus

Embedded software configuration for advanced calculations – Volume, Kg, Totalization

Accurate average calculations of uneven surfaces

Light equipment – simple to install and easy to handle

Ranges of up to 40m (131.23ft)

SmartScan 25Benefits

Page 14: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 50

SmartScan 50 is a four‑wire, high‑voltage device, and is available with a customized graphic LCD display. SmartScan has two major components: The main control unit The sensor (connected

via a cable).

SolidScan

Page 15: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 50

What can we get ?

5 independent SPDT relays AC/DC Power supply Communication:

4–20mA, RS - 232 / 485 Advanced calculations:

Volume Kg Totalization (for open channels) Sum (for roll applications)

Electronic

Page 16: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 50 can be used in the following applications:

Open Channel/Flow Liquid applications where

the filling/emptying is rapid

Solid applications where very precise measurement is required

Diameter, to measure roll thickness

SmartScan 50Applications

Page 17: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 50Models

SmartScan 50 L

for Liquid

SmartScan 50 S

for Solid

SmartScan 50 D

for Diameter

SmartScan 50 O

for Open Channel

0.4m - 12m

1.31ft - 39.37ft

0.4m - 8.5m

1.31ft – 27.88ft

0.5m - 3m

1.64ft –9.84ft

0.4m - 12m

1.31ft - 39.37ft

Accuracy0.2%

Accuracy0.25%

Accuracy0.1%

Accuracy0.2%

Page 18: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 50

SmartScan 50 has a range of up to 12 m (39.37 ft)

An accuracy of up to 0.25% within that range

Resolution of 1 mm (0.03")

Accuracy & Resolution

MonoScan 0.25%

5m 40m30m25m20m15m12m8.5m

SmartScan 50 0.1% - 0.25% SmartScan 25 0.25%

Page 19: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

High energy transducerAfter transmission the transducer will detect the strongest echo from target.

50 KHz sensor is mostly suitable for flat surfaces or aggregates, where the achieved result will be more accurate.

SmartScan 5050KHz sensor

Page 20: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Glass reinforced epoxy

Used in complex and difficult applications such as narrow pipes, steps, or any other place with many obstructions or interferences

For high resolution results For accurate reading in non-

linear surfaces For liquids and solids

applications.

50 kHz Sensor’s recommendations

SmartScan 50

Page 21: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

High added value – supplied with 4–20mA, 5 independent SPDT relays, RS - 232 or RS – 485

Embedded software configuration for advanced calculations-

Volume, Kg, Totalization and sum.

Preprogrammed default settings

Rapid response with high accuracy

Available with glands or conduit adaptors

SmartScan 50

Benefits

Page 22: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Certificates

SmartScan50 is compliant with the following industry standards: CE – EMC FM – 3810 (unclassified) NI: Class I, II, III, Division 2 Group A, B, C, D, E, F and G

For use in zone 2 without barrier

SmartScan50 Control Unit

Page 23: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Certificates

50KHz sensor ATEX: EEx mb II T4

For use in zone 1 without barrier (gas & dust) FM: DIP, Class I, II, III, Division 2 Group A, B, C, D, E, F

and G NI: Class I, II, III, Division 2 Group A, B, C, D, E, F, G

SmartScan50 Sensor

Page 24: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Certificates

SmartScan 25 is compliant with the following industry standards: CE – EMC FM – 3810 (unclassified) NI: Class I, II, III, Division 2 Group A, B, C, D, E, F and G

For use in Div 2 without a barrier

SmartScan 25 & SmartLite

Page 25: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Certificates

Intrinsically safe ATEX - EEx ia IIC T4.

For use in Zone 0, 1, 2 with a barrier FM: Class I, II, III Division 1 Group A, B, C, D, E,

F and G ATEX - EEx mb II T4

For use in Zone 1 without a barrier Non Incendive and DIP

FM: Class I , II, III Division 2 Group A, B, C, D, E, F and G

Sensor 25Khz

Page 26: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25 and 50

When SmartScan is reopened, ensure that you replace the O-ring, in order that the unit will remain sealed. The O-ring is suitable for one use only.

In order to ensure that the unit remains sealed, make sure to use round cables for (glands fitting) with a minimum of 6-7 mm diameter.

Important Notes

Page 27: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

SmartScan 25 and 50

The sensor should always be mounted above it’s dead zone. If the device enter its blocking distance it will not measure correctly.

If possible, the sensor should be centered or at least 0.5m from sidewalls.

Important Notes

Page 28: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

The sensor should be placed as far as possible from filling or other noisy inlets.

The sensor should preferably be installed when the tank is empty or at least at the minimum application level.

The sensor should be mount as perpendicular as possible

SmartScan 25 and 50Important Notes

Page 29: You Can Measure the Benefits… Training Course Introduction to SmartScan

You Can Measure the Benefits…

Sensor TypePipe LengthPipe internal

Diameter

25 KHz0.5 - 1m (1.64-

3.28ft)3-6 inch

50 KHz0.5 - 1m (1.64-

3.28ft)3-6 inch

Notes:• When using a guided pipe the sensor should be mount at the center of the pipe and the pipe should

be parallel to tank’s wall. •It is strongly recommended to use Scan Distance when installing through a guided pipe.

• For any pipe material’s beside plastic please consult factory prior installation.

SmartScan 25 & 50Sensor Installation Via Pipe