Xgb-modbus Rtu Sample

Embed Size (px)

Citation preview

XGB-INV IG5A (RS-485 Modbus RTU)

Sample programReception ( D100, 1word )

The communication between IG5A and built-in XGB Cnet through ch2 (RS-485). XGB Sample Program

Transmission ( M000, M001 2 words )

IG5A Setting : DRV=3(RS-485), FRQ=7(RS-485), I59=0(Modbus RTU), I60=1(station no.), I61=4(19,200bps), I65=0(Parity:None, Stop Bit:1)Eg) XGB (D1000 or M000 1 Word data) -> address no. 5 of iG5A inverter (Frequency reference ) XGB (M001 1 Word data) -> address no. 6 of iG5A inverter (Run command )

1/ 2

XGB-INV IG5A (RS-485 Modbus RTU)XG-PD Parameter setting Please set Channel 2 of Active mode to Use P2P settings in using XG-PD of XG5000.

Sample program

You have to set P2P Channel to Modbus RTU client.

P2P Block setting

2/ 2