Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
Checked by
WP6 Deliverable
Demonstration and validation report for tools and field testing
This project has received funding from the European Union’s Seventh
development and demonstration under grant agreement No
SUPSI – AIT
30/10/2015 – Final Version
Checked by Caroline Tjengdrawira – 3E
WP6 Deliverable 6.3
Demonstration and validation report for tools and field testing
G. Corbellini (SUPSI)
Jan Slamberger (AIT)
This project has received funding from the European Union’s Seventh Framework Programme for research, technological
ation under grant agreement No 308991.
6.3
Demonstration and validation report for tools and field testing
Programme for research, technological
Page 2 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
DEMONSTRATION AND VALIDATION REPORT
FOR TOOLS FOR FIELD TESTING Demonstration and Validation of Overall Tools – D6.3
CONTENTS
SUMMARY. ......................................................................................................... 3
1 DESCRIPTION OF TEST SITES ........................................................................ 4
1.1 TISO 10KW .......................................................................................... 4
1.2 CPT .................................................................................................... 5
1.3 AIT ..................................................................................................... 6
1.3.1 PART 1 ................................................................................................. 6
1.3.2 PART 2 ................................................................................................. 7
1.3.3 PART 3 ................................................................................................. 7
2 BEST PRACTICE FOR ON-SITE TESTING ............................................................. 8
2.1 PV MODULE STRINGS ................................................................................ 8
2.1.1 INSTRUMENTATION ................................................................................... 8
2.1.2 PROCEDURE ........................................................................................... 8
2.2 INVERTER ............................................................................................ 14
2.2.1 INSTRUMENTATION ................................................................................. 14
2.2.2 PROCEDURES ........................................................................................ 15
2.2.3 SAFETY ............................................................................................... 17
3 MEASUREMENT RESULTS ........................................................................... 18
3.1 TISO 10KW ........................................................................................ 18
3.1.1 SUMMARY ............................................................................................ 18
3.1.2 STRINGS ............................................................................................. 21
3.2 CPT .................................................................................................. 23
3.2.1 INVERTER ............................................................................................ 23
3.2.2 STRINGS ............................................................................................. 28
3.3 AIT ................................................................................................... 30
3.3.1 SUMMARY ............................................................................................ 30
3.3.2 INVERTERS ........................................................................................... 30
3.3.3 STRINGS ............................................................................................. 38
4 CONCLUSIONS....................................................................................... 46
Page 3 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 SUMMARY.
To validate the tool for on-site testing of PV plant, SUPSI and AIT have chosen to the
test them on 3 PV plants with different characteristics, all equipped with crystalline
silicon modules as required by the Performance Plus project.
The purpose of the tool is to provide innovative testing procedures and techniques to
accurately analyze the PV performance, detect issues and, on this base, permit the
operators to react any issue in underperformance in timeline manner, resolving the
problems where possible.
The 3 test sites are introduced in chapter 1, with all technical information and historical
main data. In chapter 2 we summarize the useful results regarding the operational
aspects of on-site measurement, summarizing best practices and lessons learnt from the
two research institutes experiences combined with the measurements performed during
this project.
In chapter 3 we present the electrical measures and the results of the processing using
the developed tool, these are split between the system level (inverter and strings) and
the strings level.
The knowledge base of the tool is described in deliverables D5.1, D5.2, D5.3 and D5.4 of
the Performance Plus project, while recommended procedures and tool description are
presented into the deliverable D5.5. Further possible developments of the tool are
depicted in the deliverable D7.2 where an integrated device for fault detection is
described together with its own implementation in the market and possible stakeholders.
Page 4 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 1 DESCRIPTION OF TEST SITES
The 3 test sites chosen represent different modules technologies (mono or poly
crystalline silicon), ages (from one to thirty years old), and inverter sizes (from 1.5 to 15
kW).
1.1 TISO 10KW
The first site chosen for the validation of the tool developed is a very old plant,
considered the first one connected to the grid in Europe, built in 1982; the plant is
located in Lugano (Switzerland) in the campus Trevano, where the PV group of SUPSI is
based.
The main characteristics of the PV plant are summarized in the following table.
LOCATION
Latitude 46.00 N Longitude 8.57 E Mounting Fixed
Tilt 30° Azimuth 8° E Installation 1982
PV MODULES
Number of modules 288 Manufacturer Arco Solar
Nominal Power 37W Number of cells 35
VOC 20.3V ISC 2.5A VMPP 16.1V IMPP 2.3A
α 0.1% β -0.41% γ -0.48%
Technology mono-Si
INVERTER
Number of inverters 6 Model SMA Sunnyboy
Number of strings 4 Modules per string 12
The modules of the TISO 10kW plant show many defects. Using the initial performance
as a reference for the comparison against the actual performance, we expect to see that
every module degradation modes is strongly present. For this reason, this analysis is not
so interesting.
Instead, we compared the measure performances in 2014 and 2015. This approach will
allow us to study which degradation modes are still active in the most recent years of
the plant operation and if there are any new optical or electrical losses affecting the
strings.
We do not expect to see Potential Induced Degradation (PID) failure mode because the
voltage on the module strings is limited to 250V, commonly considered too low to
generate Potential Induced Degradation.
Page 5 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 1.2 CPT
On the rooftop of a school in Lugano, we measured a PV plant of 24kWp DC that was
suspected of under-performance (in particular for one inverter). In the plant there are 96
PV modules connected to two inverters; one inverter is connected to the east-facing
modules, and the other to the west-facing modules.
These inverters can switch the output from one to two and three phases depending on
the power output; this feature improves significantly the efficiency, in particular at low
irradiance. This has to be considered when analyzing the efficiency curves of the
inverters.
LOCATION
Latitude 46.03 Longitude 8.96 Mounting Fixed
Tilt 6° Azimuth East-West Installation 2014
PV MODULES
Number of modules 96 Manufacturer Trina Solar
Nominal Power 260W Number of cells 60
VOC 38.2V ISC 9A VMPP 30.6V IMPP 8.5A
α 0.05%/°C β -0.32%/°C γ -0.41%/°C
Technology Poly-Si
INVERTER
Number of inverters 2 Model Fronius
Number of strings 4 Modules per string 12
Page 6 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 1.3 AIT
AIT has chosen the building integrated photovoltaic plant (BIPV) for the test case. This
plant was built in the year 2008 as a part of shading system for offices building. Due to
installation into façade, there is a high risk of soiling and shading. The advantage of this
installation is the reflection of irradiance of office windows. This reflection increases the
total irradiance on the PV array plane for up to 30%. The BIPV plant is built from three
different technologies from modules. These are mono-Si, poly-Si and poly-Si with back
contacts technology. The technical data from PV plant are presented in the followed
subsections.
FIGURE 1: BIPV TEST CASE AT AIT
1.3.1 PART 1
LOCATION
Latitude 48.27 N Longitude 16.43 E Mounting BIPV
Tilt 30° Azimuth 5° W Installation 2008
PV MODULES
Number of modules 40 Manufacturer Solarwatt
Nominal Power 130W Number of cells 55
VOC 33,7 ISC 5,28 VMPP 27,4 IMPP 4,81
α +0,03 %/K β -0,37 %/K γ -0,50 %/K
Technology mono-Si
INVERTER
Number of inverters 1 Model Sunways NT6000
Number of strings 2 Modules per string 20
Page 7 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 1.3.2 PART 2
LOCATION
Latitude 48.27 N Longitude 16.43 E Mounting BIPV
Tilt 30° Azimuth 5° W Installation 2008
PV MODULES
Number of modules 40 Manufacturer Solarwatt
Nominal Power 124W Number of cells 55
VOC 33,5 ISC 4,87 VMPP 27,3 IMPP 4,55
α +0,05 %/K β -0,31 %/K γ -0,41 %/K
Technology Poly-Si
INVERTER
Number of inverters 1 Model Sunways NT6000
Number of strings 2 Modules per string 20
1.3.3 PART 3
LOCATION
Latitude 48.27 N Longitude 16.43 E Mounting BIPV
Tilt 30° Azimuth 5° W Installation 2008
PV MODULES
Number of modules 40 Manufacturer Solarwatt
Nominal Power 121W Number of cells 55
VOC 32,8 ISC 5,34 VMPP 25,3 IMPP 4,79
α +0,05 %/K β -0,31 %/K γ -0,41 %/K
Technology Poly-Si
back-contact
INVERTER
Number of inverters 2 Model SMA SB3300
Number of strings 4 Modules per string 10
Page 8 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
2 BEST PRACTICE FOR ON-SITE TESTING
2.1 PV MODULE STRINGS
2.1.1 INSTRUMENTATION
I-V tracer
The main device for these studies is an I-V tracer to accurately measure the I-V
characteristics of the module string under study. The I-V tracer has a synchronized
measurement for module temperature and irradiation on the plane of the array.
The irradiation can be measured with a pyranometer or a reference cell. While a
pyranometer is more accurate in measuring the global irradiation on the plane of the
array, we suggest using a reference cell of the same technology (poly-crystalline or
mono-crystalline silicon) of the installed modules to avoid the spectral mismatch
between the sensors and the modules as much as possible.
The ISC is strongly dependent on irradiation (and almost not dependent on temperature)
so if the measured ISC deviates significantly from the expectation, it is recommended to
double check the calibration of the irradiation sensor. On the other hand the VOC is
strongly dependent on temperature (and typically have a very limited degradation
respect to original value as explained in D5.4) and therefore it is important to first verify
the accuracy temperature sensor (TBOM) before measuring the VOC.
Thermal camera
When a module string measurement is performed, it is very important to measure the
temperature at the back of the module properly as the temperature information will be
used to correct the module measured electrical parameters to the Standard Test
Condition (STC). In particular, we want to avoid the situation where the temperature
sensor (PT100, PT1000 or thermocouple) is installed in a non-representative location on
the module, for e.g. behind a cell that is affected by an hot spot, to avoid erratic
temperature reading which could falsely affect the STC correction calculations. In
addition, it is important to check the uniformity of the module temperature with a
thermal camera.
Dark I-V on-site
For the dark I-V measurement we prepared a new device using a traditional power
feeder and an I-V tracer developed internally in SUPSI, the MPTT3000, that can reach
very high accuracy on current and voltage measurements. With this setup we have been
able to measure the dark I-V characteristic of strings of modules and then use them in
the software for degradation modes analysis.
2.1.2 PROCEDURE
As explained in D5.5 and in the manual of the D5.6, SUPSI has built a synthetic
procedure to perform on field testing at module string level.
Page 9 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 This procedure, depicted in Figure
performed on single modules or
parameters, most of them available from modules datasheet
FIGURE 2: PROCEDURE FOR STRI
As the flowchart illustrate, the string analysis is done by based on the behavior of the
parameters obtained from the I
In case of low measured short circuit current
irradiation transformed into electricity
1. Uniform soiling happens typically where small particles
affected modules (where “uniform” means both at module and at cell level
this case, we usually
effective irradiation)
cells and the modules are not limiting each other.
2. Uniform shading is very similar to uniform soiling
particulates coverage. T
irradiation yield.
3. Optical factors that limit the current in the cells: glass corrosion, degradation of
anti-reflective coating, and/or discoloration of the encapsulant. These factors
could be determined by performing visual inspection.
In both uniform soiling and uniform shading,
sensor is measuring the proper value
a reference cell made with same technology of the modules (mono
silicon). It is also important to
respect to the modules (position, no shading from surrounding objects, tilt, location etc.)
When the short circuit current is not affected, the next parameter to che
circuit voltage behavior. Most publications report a low or no degradation
This procedure, depicted in Figure 2, is useful for a qualitative analysis of the I
performed on single modules or strings and has an advantage of needi
parameters, most of them available from modules datasheet.
: PROCEDURE FOR STRING ANALYSIS
As the flowchart illustrate, the string analysis is done by based on the behavior of the
parameters obtained from the I-V tracer.
short circuit current, we can search for the reason of lower
irradiation transformed into electricity:
Uniform soiling happens typically where small particles uniformly
where “uniform” means both at module and at cell level
usually see a lower-than-expected ISC (that is only dependent on
) but no step in the I-V curve is observed, meaning that
modules are not limiting each other.
Uniform shading is very similar to uniform soiling but with the absence of
particulates coverage. The end effect is however the same, a
Optical factors that limit the current in the cells: glass corrosion, degradation of
reflective coating, and/or discoloration of the encapsulant. These factors
could be determined by performing visual inspection.
iform soiling and uniform shading, we have to be sure that our irradiation
sensor is measuring the proper value. It is therefore important to verify the value using
a reference cell made with same technology of the modules (mono-
It is also important to check that the sensor has been installed correctly with
(position, no shading from surrounding objects, tilt, location etc.)
When the short circuit current is not affected, the next parameter to che
Most publications report a low or no degradation
, is useful for a qualitative analysis of the I-V curves
needing only simple
As the flowchart illustrate, the string analysis is done by based on the behavior of the
we can search for the reason of lower
uniformly cover the
where “uniform” means both at module and at cell level). In
(that is only dependent on
, meaning that the
but with the absence of
however the same, a reduction in the
Optical factors that limit the current in the cells: glass corrosion, degradation of
reflective coating, and/or discoloration of the encapsulant. These factors
we have to be sure that our irradiation
. It is therefore important to verify the value using
or poly-crystalline
that the sensor has been installed correctly with
(position, no shading from surrounding objects, tilt, location etc.).
When the short circuit current is not affected, the next parameter to check is the open
Most publications report a low or no degradation (<10%) of the
Page 10 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 open circuit voltage VOC. When low VOC is observed, the first step is to check that the
module temperature is measured in a proper way. Best practice recommends collecting
the module temperature data at different points of a module (in the center or near the
frame). Unfortunately the cell temperature has big uncertainty and thus the
measurement needs to be performed very accurately. Best practice recommends placing
the sensors on the rear of the module to avoid the glass mass affecting the temperature
readout. The overall temperature uniformity should also be checked using a
thermographic camera. The effect of cables is usually seen as a “voltage drop” not
related to VOC; in open circuit there is no current and thus the energy losses in cables
are zero. Once we are sure that the voltage drop is not due to wrong module
temperature, the voltage drop could be explained only in two ways:
4. One or more sub-modules are bypassed, meaning that a failure has caused that
some bypass diodes to be shorted. If an entire module is shorted, the difference
between the expected and the actual VOC is a multiple of module VOC; this can be
detected by measuring module by module or using the shading method. In the
shading method, one module is shaded one at a time to understand which ones
cause losses; in this case we have to repeat the I-V measurement several times
to identify the problematic module.
5. If the VOC is accompanied by drop in fill factor, some modules could be affected by
Potential Induced Degradation. This phenomenon affect modules at the end of
string that are at higher voltages and can be partially recovered applying reverse
voltage; new devices are already available in the market to solve this problem.
When we measure a low fill factor, with a smooth curve and normal ISC and VOC, it means
that we have low shunt resistance or high series resistance (or both).
6. A typical signature of degradation is in series resistance. The RS of a PV module is
the sum of the single ohmic resistances in the different parts of the electrical
circuit in the PV module: cell solder bonds, emitter and base regions, cell
metallization, cell-interconnect bus-bars, and resistances in junction-box
terminations. An increasing value of RS could be attributed to various failures
inside modules, as depicted in D5.2 and in Figure 3.
FIGURE 3: SOURCES FOR THE SERIES RESISTANCE IN A PV MODULE
7. The shunt resistance RSH represents any parallel high-conductivity paths (shunts)
through the solar cell or on the cell edges as shown in Figure 4. Degradation in
RSH (decreasing) is due to crystal damage and impurities in and near the p-n
junction, and gives rise to the shunt current. These shunt paths divert currents
away from the intended load and their effects are detrimental to the module
performance especially at low irradiance level.
Page 11 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 4: SOURCES OF THE SHUNT RESISTANCE IN A PV MODULE
A more detailed analysis of the performance at string level can be performed with the
tool developed in the deliverable D5.6 of this project. With this tool the measured I-V
curve on-site are processed in order to take into account the losses on the cables and
the statistical variation of the parameters of the modules. It is also possible to simulate
the expected degradation of the modules after a defined period.
The comparison between the measured (and corrected to standard condition) and the
expected I-V curves can lead to insights on the actual degradation mode affecting the
string. The first table in Table 1 summarizes the ranking of the expected impacts of each
degradation modes on the I-V curve parameters, for example, the PID strongly reduces
the fill factor while there is not a significant effect on the short circuit current.
The second table includes value from dark measurement (without irradiation) that can
be performed by covering the modules properly or during night time; these measures
can be easily implemented in climates where it is not easy to find sunny condition
(irradiation higher than 600 W/m2) for long periods.
For detail explanation of how all the rankings are derived, please refer to the deliverable
D5.5 of the Performance Plus project.
TABLE 1: SUMMARY OF DEGRADTION EFFECTS ON I-V CURVES
Deg. modes FF FF low light ISC VOC ∆RS
OPTICAL ? ? - - ?
ELECTRICAL -- - - 0 ++
CELL - - - - ++
PID -- --- 0 - 0
Deg. modes ������ VD_MAX VP J0
OPTICAL 0 0 0 0
ELECTRICAL -- + + 0
CELL - + - +++
PID -- -- - ++++
Page 12 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 2.1.2.1 CORRECTION OF I-V MEASUREMENT TO STC CONDITION
As explained in the deliverable D5.5, a new method has been
developed to obtain a single I-V curve from different
measurement on site. The goal is to obtain a more accurate
result avoiding the noise in the measurements and the
uncertainties coming from unstable measurement and estimation
of temperature coefficients.
The procedure is explained in details in D5.5 and considers an
averaging of each I-V curve based on its deviation from STC
(25°C and 1000 W/m2).
Moreover the tool offers the possibility to choose between five procedures for STC
correction, as documented in D5.5.
FIGURE 6: EXAMPLE OF CORRECTION TO STANDARD CONDITION, A NEW METHOD IS IMPLEMENTED
TO OBTAIN A SINGLE I-V CURVE FROM MORE MEASUREMENT IN DIFFERENT CONDITION
Figure 5:
selection of
method for STC
correction
Page 13 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 2.1.2.2 SIMULATION OF CABLES VOLTAGE DROP AND DEGRADATION
An optional mini tool has been incorporated in the overall
performance assessment tool to allow for the simulation of the
degradation of performance and the effect of the voltage drop
due to cables and energy dissipation for the Joule effect.
Typically the voltage drop could be neglected but in some cases,
especially for new installations with string inverters, this could
be relevant.
The left chart in Figure 8 shows the result of the simulation of
the degradation modes affecting the TISO plant including the
voltage drop due to cables. Here we can see that the voltage
drop due to cables is no longer significant for plants which have
been operational for 30 years while the degradation effect is
clearly dominant. In the picture at right we point out an
example we faced in a multi MW installation on an industrial
rooftop with inverters installed in the building quite far from the
PV modules.
FIGURE 8: LEFT: EXAMPLE OF DEGRADATION SIMULATION FOR A TISO STRING OF 12 MODULES
AFTER 30 YEARS OF OPERATION, THE EFFECT OF THE VOLTAGE DROP DUE TO CABLES IS
NEGLIGIBLE WHILE THE SHAPE OF THE CURVE IS – RIGHT: THE EFFECT OF 200M OF CABLES OF
SECTION 8MM2
Figure 7: settings
for the simulation
of the degradation
Page 14 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 2.2 INVERTER
2.2.1 INSTRUMENTATION
The main device for analyzing
efficiency of the PV systems. This instrument measures voltage and current on
side, and voltage, current and cos
power, the AC power and the
FIGURE 9: MODEL OF THE SYSTE
where:
• ��� is an efficiency factor
• �� is the DC current
• ��� is the VC voltage
• �� is the AC current
• ��� is the AC voltage
• ������ is the power factor
The performance ratio of PV system could be calculated with synchronous measurements
of the inverter, the irradiance on the PV plane and
FIGURE 10: MODEL OF THE SYSTE
����� �
where:
• ����� is the performance ratio of
analyzing PV systems and inverters is the instrument for testing
PV systems. This instrument measures voltage and current on
and voltage, current and cos� on the AC-side. From the measured data the DC
the inverter efficiency are calculated.
: MODEL OF THE SYSTEM – INVERTER ON-SITE TESTING
������ � ����� · ������ · �������������� · ������
efficiency factor of the inverter
is the power factor
The performance ratio of PV system could be calculated with synchronous measurements
irradiance on the PV plane and the PV module temperature.
: MODEL OF THE SYSTEM – SYSTEM ON-SITE TESTING
� ∑ �� ��� · ��� ��� · �������������� ∑ �! · "#$%�&�
"'() · *1 , - · ./01���� 2 /34�56�����
performance ratio of the system
PV systems and inverters is the instrument for testing the
PV systems. This instrument measures voltage and current on the DC-
measured data the DC
The performance ratio of PV system could be calculated with synchronous measurements
module temperature.
Page 15 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 • 7 is the sample number
• 8 is the number of samples
• �� is the nominal power*
• - is the temperature coefficient for power at Maximum Power Point
• /01� is the temperature of the cell of the PV-module
• /34� is the temperature at STC = 25°C
• 934� is the global irradiation at STC = 1000 W/m2
• 9:1� is the global irradiation on the plane of the array
*The nominal power from the module name plates can be used. In this case the
guaranteed values could be verified.
2.2.2 PROCEDURES
Whenever the monitoring system is showing significant energy losses with respect to
expected energy yield, the string analysis should be perform to possibly identify the root
causes. If the string analysis leads to no particular results, the operator should perform
an investigation at the inverter level.
Similar to the modules and strings analysis procedure developed by SUPSI for the DC
side, AIT (Austrian Institute of Technology) has developed a procedure for
troubleshooting at inverter level. The procedure is summarized in Figure 11.
First, the visual inspection of inverter has to be done to identify the mechanical and
degradation failures of inverter. Additionally the installation has to be checked if they are
following the guidelines in the manual of the inverter manufacturer. Installation and
operation according the manual are the basis for well performing inverters.
If no deviations are found, the procedure will be followed with the check of inverter error
log files. If defined errors are found, the failure indicator has to be followed; otherwise
the procedure has to be followed with VDC und IDC measurement to check short term
stability of the Maximum Power Point Tracker (MPPT). This check requires stable ambient
conditions. The possible failures of instability are failure of DC-Controller or Cin defect
(switching ripple).
If the MPPT is stable, the level V/I measurement has to be done next; the check will be
performed on string level. A single string of modules will be connected to the inverter
and the measured power will be stored, after a few second the same single string will be
measured with I-V curve tracer; these two measurements have to be performed during
stable ambient conditions. The possible failures are multiple maxima, algorithm runaway
and the failure of PV-modules.
If no incorrectness of the MPPT are found, the procedure has to be followed with VAC, IAC,
cos ϕ measurement to check grid disturbances. The possible causes of failure are failure
of AC-Controller, failure of output filter or low grid quality.
If no grid disturbances are found, the procedure has to be followed with PAC and PDC
comparison to show conversion efficiency. The possible causes of low conversion
efficiency are stable and variable energy losses.
Page 16 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 If the conversion efficiency is normal, the communication check has to be done to check
the correctness of provided status by the inverter. The possible causes of this failure are
failure on the physical connections and the failures on interfaces.
If no failure is found, the change of set points (P/Q, V/Q, Pmax) has to be done (if
applicable). After that, the communication check has to be repeated.
If there still no failure was found, the laboratory characterization has to be done to
precisely identify the failure causes.
FIGURE 11: INVERTER CHECK PROCEDURE
Page 17 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 2.2.3 SAFETY
The on-site inverter and system testing is performed on PV systems under operation.
The PV arrays have up to 1000V voltage and some 10A current in the case of parallel
coupling. The main risk is the risk of electric shock. Before any connection is made, the
PV array and inverter must be switched off. The place where the measurement is taken
has to be dry and without dust. The measurement cables have to be insulated and
certified for high voltage. The second risk is a risk of height. Special safety protection
and procedure are required to avoid incidents such as falling from height.
Page 18 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 3 MEASUREMENT RESULTS
3.1 TISO 10KW
For the TISO installation, the main test goal is to evaluate the progression of the
degradation in recent years. From previous tests it is quite clear that every degradation
mode (except for PID) has been occurring for several years causing the strong under-
performance (>20% respect to PMPP) we see today. Overall the system is performing well
albeit the plant has been operational for 33 years; these could be attributed to the fact
that the modules were hand-made and use thicker silicon solar cells (400 µm).
3.1.1 SUMMARY
The test measurements were carried out in the summer of 2014 and the summer of
2015. Several repetitions were conducted to achieve a condition close enough to STC in
order to reduce the uncertainties coming from the temperature coefficients and the low
irradiance efficiency (quite difficult in this case where the modules present high series
resistances and many shunt patterns for current leakage).
TABLE 2: TOTAL PLANT POWER REFERRED TO STC CONDITION IN DIFFERENT PERIODS
1982 2014 2015 Power corrected to STC [W] 10241 8056 7726 Degradation rate reference 79% 75%
In Figure 12 we present a summary of the degradation of performances between the
2014 and 2015 measurements. As it can be seen from the graph, performance
degradation in average of 4% is observed over the period of 12 months.
Page 19 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 12: DEGRADATION OF PERFORMANCE AT STRING LEVEL BETWEEN 2014 AND 2015, MOST
STRINGS SHOW VALUES ABOUT 4%
Recalling the deliverables D5.2 and D5.5, we categorized the degradation modes into
four categories:
• Optical
• Electrical
• Cells cracking
• Potential Induced Degradation (PID)
The following figures present the observations from the visual inspection of the PV
modules. From Figure 13 and 15 it is clear that the modules are suffering from optical
losses; this phenomenon seems to be stable from some years. With the on-site testing
we confirmed this intuition and understood that additional losses of the last year should
be addressed to electrical losses in particular to new shunt paths inside the module or
increasing of series resistance due to hot spots (Figure 14) or other electrical defects.
-2%
0%
2%
4%
6%
8%
10%
12%
14%
Power degradation @STC [W]
Page 20 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 13: VISUAL APPEARANCE OF SOME MODULES OF THE TISO PLANT, MOST OF THEM ARE
SUFFERING FROM YELLOWING CAUSING CLEAR OPTICAL LOSSES
FIGURE 14: IMAGES FROM THE THERMAL CAMERA SHOWING HOT SPOTS CORRESPONDING TO THE
JUNCTION BOXES ON THE BACKSIDE OF THE MODULES
Other important defects are shown in Figure 15, in particular regarding the defects
associated with the degradation of the bus bars and the cell degradation subsequent to
strong hot spots (in summer we measured temperature of about 105°C).
Page 21 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 15: BURNT CELLS, AND BUS BARS DEFECTS ARE SHOWN FROM THE TISO PLANT
3.1.2 STRINGS
We present one very representative case of the results of the I-V measurements of
strings and the application of the developed software (D5.6) presented in D5.5.
The other strings measured showed a very similar behaviour in the extracted parameters
to the string analyzed in detail here.
The result of the first string analysis is reported in Figure 16; in this case we used all the
features of the tool, including cables voltage drop, expected degradation, light and dark
I-V measurement.
Page 22 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 16: ANAYSIS OF THE REPRESENTATIVE STRING
FIGURE 17: SUMMARY OF DEVIATIONS BETWEEN REFERENCE AND MEASURED VALUES
TABLE 3: REFERENCE TABLE FOR LIGHT I-V DEVIATION
Deg.
modes FF FF low light ISC VOC ∆RS
OPTICAL ? ? - - ?
ELECTRICAL -- - - 0 ++
CELL - - - - ++
PID -- --- 0 - 0
Page 23 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 TABLE 4: REFERENCE TABLE FOR DARK I-V DEVIATION
Deg. modes ������ VD_MAX VP J0
OPTICAL 0 0 0 0
ELECTRICAL -- + + 0
CELL - + - +++
PID -- -- - ++++
In the Figure 16 and Tables 3-4 we summarized the results of the deviation analysis
between the measured and the reference I-V curves between 2014 and 2015.
Comparing the last row of the Figure 17 and the rows of the Table 3 and 4, it is pretty
clear that the main degradation mode affecting the string is the electrical one.
To understand which degradation mode is addressable we recommend comparing the
reference table (Table 3) with the output of the tool (Table 4) and check which line has
more similar rankings (plus and minus). In addition, combining the light and dark I-V
measurements we have more chances to figure out the main degradation mode affecting
the string.
We have also found that magnitudes of the variations of the parameters are high,
implying that the electrical degradation is severe. In this case, both the light and dark I-
V measurements agree on the root cause.
The measurement on other strings, not reported here, confirmed that electrical
degradation is the main one causing the strong degradation occurring in the plant (from
79% to 75% in only one year).
3.2 CPT
For this test plant, we started by measuring the whole system, then focused on one
inverter, and then on the strings connected to this inverter to detect which could be the
root cause of the energy losses.
3.2.1 INVERTER
To evaluate the performance of the plant as a whole we start our measurements from
the inverters, and then focused on strings when we understood that the problem was at
that level.
We repeated these measures in different occasions and then summarized the results in
the figures below. The repeated measurements were carried out under different ambient
conditions and consequently different behaviours of the PV plant due to thermal,
irradiation or soiling effects were observed.
3.2.1.1 INVERTER 1
In the Figure 18-21 we present the results of the tool for the inverter analysis. In this
case, the results do not indicate significant under-performance on the plant, considering
the Performance Ratio (Figure 19) falls regularly between 85% and 90% and the
conversion efficiency rarely falls below 95% (Figure 18).
Page 24 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 In the Figure 21 the DC losses is about 8%, indicating that the DC part of the plant is
not affected by significant under-performance. This value, on the long term, is in
agreement with values calculated with PVSyst or similar software.
FIGURE 18: ANALYIS OF THE INVERTER 1
FIGURE 19: ANALYIS OF THE INVERTER 1
Page 25 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 20: ANALYIS OF THE INVERTER 1
FIGURE 21: SANKEY DIAGRAM OF INVERTER 1
3.2.1.2 INVERTER 2
On the second inverter we repeated the same measurements to evaluate the overall
performances. From Figure 22 we see that the conversion efficiency is almost always
above 95% as claimed in the inverter datasheet.
In Figure 23 we see that in several occasions the PR is very low, in particular in sunny
conditions. From Figure 24 the efficiency is always good and does not depend on the
voltages so we considered the DC part (strings of modules) as the main possible cause
of under-performances.
Page 26 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 22: ANALYIS OF THE INVERTER 2
FIGURE 23: ANALYIS OF THE INVERTER 2
Page 27 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 24: ANALYIS OF THE INVERTER 2
FIGURE 25: SANKEY DIAGRAM FOR INVERTER 2
Page 28 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 3.2.2 STRINGS
3.2.2.1 TESTING OF SOILING EFFECT
From Figure 26 we understand that there was a significant under performance in one
inverter (array PV losses 16% are clearly too much, and the PR was sometimes very low)
and therefore we put our focus on the strings connected to this inverter.
We tested all the strings connected to this inverter and selected one to show here as an
example for the use of the tool.
FIGURE 26: STRING SUSPECTED OF CAUSING UNDER PERFORMANCE
TABLE 5: REFERENCE AND RESULTING TABLES FOR THE STRING
Comparing the reference table (Table 5, left) and the tables with measured values (Table
5, right) the most reasonable degradation mode indicated is the optical one, meaning
there could be something that reduces the irradiation available at the cell of the PV
Deg. modes FF FF low light ISC VOC
OPTICAL +- +- - -
ELECTRICAL -- - - 0
CELL - - - -
PID -- --- 0 -
Page 29 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 modules with respect to the reference cell used to measure the irradiation on the plane
of modules.
A visual inspection carried out on the string found a high level of soiling, we then
repeated the measurement and the results are shown Figure 27.
FIGURE 27: THE SAME STRING AFTER CLEANING IT
After cleaning the modules we repeated the measurements and the results are also
shown in Figure 27; in this case the differences between the reference parameters and
the calculated ones after the cleaning are negligible (all of them are lower than 1%), i.e.
within the uncertainty threshold of the measurement equipment. We therefore concluded
that the whole electrical losses are attributable to the soiling effect on the modules,
confirming the assumption from the tool.
Page 30 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 3.3 AIT
As mentioned in section 1.3, AIT has chosen a building integrated photovoltaic plant
(BIPV) for the test case. This plant was built in the year 2008 as a part of shading
system for offices building. Due to installation into façade, there is a high risk of soiling
and shading. The advantage of this installation is the reflection of irradiance of office
windows. This reflection increases the total irradiance on the PV array plane for up to
30%. The BIPV plant is built from three different module technologies. These are mono-
Si, poly-Si and poly-Si with back contacts technology.
3.3.1 SUMMARY
On the monitoring the under-performance of the PV system has been found. First, the
test of the system and inverter has been made (subsection 3.3.2). The analyses of this
test (see Figures 28-43) show that the main losses are on the PV array side (up to 22%);
meanwhile, the inverter efficiencies are in the range of the datasheets values.
Second, the measurements of PV module strings have been done. Significant steps in
the I-V curve are observed in all cases (see Figures 44-51), indicating, according to the
procedure summarized in the Figure 2, that a mismatch of module parameters within the
same string is present and influencing the electrical output. The main reasons for those
mismatches could be partly shading, non-homogenous soiling or cracks/burns of the
cells.
After analyses the large deviations of the shunt resistance RSH in all PV strings have been
found (see Tables 6-9). The shunt resistance RSH is defined as the derivation of the
voltage (slope of the IV curve) near the short-circuit current point. In the case where the
I-V curve is not smooth, the calculation of RSH is not accurate and should not been taken
into account.
The test with IR-camera should be made to define exact reason of the losses of this
power plant. Unfortunately, the PV modules from this power plant are integrated into
façade and therefore difficult to make reliable IR-tests.
3.3.2 INVERTERS
During the testing of the inverter and the system performance, the DC current, the DC
voltage, the AC current, the AC voltage, cos �, ambient temperature, module
temperature and irradiance on the PV plane have been measured. The tool for
system/inverter analysis has calculated the theoretical DC power, actual DC power and
actual AC power from the captured data. Figure 28 presents the inverter efficiency from
the inverter in the part 1 of the installation.
The mean efficiency is 96.6%; this is in the range of the datasheet value (maximum
efficiency 97%, Euro efficiency 96.5%). Figure 29 presents the Performance Ratio from
the inverter in part 1. The mean value is 69.4%; this is lower than expected. Normally
the value of the Performance Ratio is expected to be above 80%. Figure 30 presents the
ratio between the AC voltage and the DC power at the inverter; additionally the values of
the inverter efficiency at measurement points are presented by colour. The inverter
efficiency is higher at lower power and higher voltage. Figure31 presents the Sankey
diagram for the power losses. As in can be seen, the main losses are PV array losses
Page 31 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 (22.1%), the second losses are degradation losses (estimated 5.6%), the third losses
are inverter losses (2.5%), and the last losses are cable and contact losses (0.5%). The
analysis from part two and three show the similar issues (see Figures 32-43).
Regarding to the results of the inverter/system analysis (the main losses are on PV array
side), the PV module string analysis have to be done to define reasons of higher PV array
losses (see subsection 3.3.3).
FIGURE 28: PART 1 INVERTER 1: CONVERSION EFFICIENCY
FIGURE 29: PART 1 INVERTER 1: PERFORMACE RATIO
Page 32 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 30: PART 1 INVERTER 1: INVERTER EFFICIENCY
FIGURE 31: PART 1 INVERTER 1: LOSSES
Page 33 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 32: PART 2 INVERTER 1: CONVERSION EFFICIENCY
FIGURE 33: PART 2 INVERTER 1: PERFORMACE RATIO
Page 34 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 34: PART 2 INVERTER 1: INVERTER EFFICIENCY
FIGURE 35: PART 2 INVERTER 1: LOSSES
Page 35 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 36: PART 3 INVERTER 1: CONVERSION EFFICIENCY
FIGURE 37: PART 3 INVERTER 1: PERFORMACE RATIO
Page 36 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 38: PART 3 INVERTER 1: INVERTER EFFICIENCY
FIGURE 39: PART 3 INVERTER 1: LOSSES
Page 37 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 40: PART 3 INVERTER 2: CONVERSION EFFICIENCY
FIGURE 41: PART 3 INVERTER 2: PERFORMACE RATIO
Page 38 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 42: PART 3 INVERTER 2: INVERTER EFFICIENCY
FIGURE 43: PART 3 INVERTER 2: LOSSES
3.3.3 STRINGS
Eight strings of the AIT plants have been tested using the tool for the degradation modes
detection. The modules have been in operation for seven years; this was taken into
account when evaluating the parameters.
In all cases the strings show significant steps in the I-V curve, indicating, according to
the procedure summarized in the Figure 2, that a mismatch of modules parameters
inside the same string is present and influencing the electrical output.
Page 39 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 3.3.3.1 PART 1
The results from the first part of the installation are shown in Figures 44-45 and then
summarized in Table 6-7.
Analyzing the parameters extracted by the tool from the light I-V measurements, it
seems reasonable to assume that a combination of electrical and cell cracking
degradation occurs. The very low fill factor can lead often to electrical problems in the
module. PID mode should be excluded because it would not affect the photocurrent and
also, the module structure is glass/glass so PID, if present, is active only near the edges
of the module.
FIGURE 44: PART 1 INVERTER 1 STRING 1: PV STRING ANALYSIS
Page 40 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 45: PART 1 INVERTER 1 STRING 2: PV STRING ANALYSIS
TABLE 6: PART 1: COMPARISON BETWEEN DATASHEET AND MEASURED DATA
Datasheet Light @ STC Δ [%] Light @ STC Δ [%]
IPH 5.28 4.64 -12.20 4.70 -11.02
I0 6.86 5.95 -13.17 3.83 -44.21
n 1.17 1.30 11.10 1.14 -2.87
RSH 1.01 663.06 65264.61 511.71 50345.05
RS 10.74 10.26 -4.48 9.29 -13.55
ISC 5.28 4.57 -13.40 4.61 -12.71
VOC 674.00 656.55 -2.59 662.96 -1.64
FF 0.74 0.65 -11.93 0.65 -12.31
String 1
Part 1
Inverter 1
String 2
Page 41 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 TABLE 7: SUMMARY OF PARAMETERS AND REFERENCE TABLE
3.3.3.2 PART 2
The same analysis has been applied on the part 2 of the installation. The results are very
similar, so we can also attribute the performance issue to the electrical and cell levels.
The results of the testing are summarized in Figures 46-47 and Table 8.
FIGURE 46: PART 2 INVERTER 1 STRING 1: PV STRING ANALYSIS
Deg. modes FF FF low light ISC VOC
OPTICAL +- +- - -
ELECTRICAL -- - - 0
CELL - - - -
PID -- --- 0 -
Page 42 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 47: PART 2 INVERTER 1 STRING 2: PV STRING ANALYSIS
TABLE 8: PART 2: COMPARISON BETWEEN DATASHEET AND MEASURED DATA
Datasheet Light @ STC Δ [%] Light @ STC Δ [%]
IPH 4.87 4.98 2.28 4.98 2.21
I0 4.48 7.54 68.09 7.50 67.15
n 1.16 1.16 0.03 1.17 1.26
RSH 1.71 563.06 32763.96 538.03 31303.02
RS 11.50 12.12 5.37 13.41 16.59
ISC 4.87 4.90 0.61 4.89 0.48
VOC 670.00 648.66 -3.19 654.59 -2.30
FF 0.79 0.65 -18.39 0.64 -18.60
String 2String 1
Part 2
Inverter 1
Page 43 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 3.3.3.3 PART 3
The same analysis has been applied the part 3 of the installation. The results are very
similar, so we can also attribute the performance issue to the electrical and cell levels.
The results of the testing are summarized in Figures 48-51 and Table 9.
FIGURE 48: PART 3 INVERTER 1 STRING 1: PV STRING ANALYSIS
Page 44 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 49: PART 3 INVERTER 1 STRING 2: PV STRING ANALYSIS
FIGURE 50: PART 3 INVERTER 2 STRING 1: PV STRING ANALYSIS
Page 45 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015
FIGURE 51: PART 3 INVERTER 2 STRING 2: PV STRING ANALYSIS
TABLE 9: PART 3: COMPARISON BETWEEN DATASHEET AND MEASURED DATA
Datasheet Light @ STC Δ [%] Light @ STC Δ [%] Light @ STC Δ [%] Light @ STC Δ [%]
IPH 5.34 5.14 -3.79 5.08 -4.93 5.21 -2.50 5.10 -4.44
I0 2.24 1.41 -37.32 6.87 206.49 7.64 240.61 1.01 -55.10
n 1.20 1.16 -3.41 1.12 -7.20 1.14 -5.28 1.15 -4.25
RSH 4.98 333.77 6597.42 372.50 7374.50 292.97 5778.66 325.81 6437.64
RS 7.59 6.71 -11.55 6.84 -9.85 7.78 2.57 7.14 -5.86
ISC 5.34 5.03 -5.76 4.98 -6.73 5.09 -4.73 5.02 -5.99
VOC 328.00 320.18 -2.38 318.92 -2.77 322.03 -1.82 321.64 -1.94
FF 0.69 0.63 -9.19 0.64 -7.80 0.62 -10.10 0.63 -8.89
String 2String 1String 2String 1
Inverter 1 Inverter 2
Part 3
Page 46 of 46
Dem
onstr
ation a
nd V
alidation R
eport
for
Tools
for
Fie
ld T
esting -
30/1
0/2
015 4 CONCLUSIONS
The overall objective the Work Package (WP) 5 of the Performance Plus was to define
new procedures and software for field testing that can improve the quality of
measurements and the resulting information to operate and optimize the energy output
(and so the LCOE) of PV plants. Moreover the tools aim to simplify the job of PV plant
operators by improving the quality of on-site measurement and thus reducing the
associated uncertainties.
The tools and procedure developed and reported in the deliverables D5.5 and D5.6 of the
Work Package 5 have been applied to three real PV installations, all equipped with silicon
crystalline modules and small size inverters. This report presented the results of these
demonstration works.
In the first test case, the tools have been applied to a very old PV installation (>30year
old) in Lugano (Switzerland) to understand which module degradations are still affecting
the plant performance in the recent years. From this test case, we have attributed that
the recent losses are due to electrical issues in the modules while the optical
phenomenon (such as the yellowing) has stabilized. These results have been obtained by
combining light and dark I-V measurements.
In the second test case, the tools were tested on a rooftop installation, also in Lugano
(Switzerland). By testing both the DC and AC parts of the installation we found that the
inverter showed regular performances. Analysis showed the main root cause of the
losses is the soiling on the PV modules.
In the third test case, the tools were applied on a BIPV installation at Vienna (Austria).
The analysis indicates the issues to be at electrical and cells level.
By testing the new procedures and software for field testing we developed in WP5, we
have demonstrated that it has been possible to analyze PV installations of different ages
and types and investigate the root causes that cause the under-performance and energy
losses of the studied PV plants. These tools offer promising results for further
development into a fixed device which can be physically installed in PV installation as
explained in the deliverable D7.2 of the Performance Plus.