Upload
phammien
View
222
Download
0
Embed Size (px)
Citation preview
1
TANK VOLUME INDICATORWL2000 WATER TANKS
WL2600 CLASS A FOAM CONCENTRATE TANKSWL2700 CLASS B FOAM CONCENTRATE TANKS
WL2000 Rev0404
2
CONTENTS
Table of Contents
CONTENTS ............................................................................................................... 2List of Figures ........................................................................................................ 3
INTRODUCTION ...................................................................................................... 4Overview ................................................................................................................ 4Features.................................................................................................................. 4Specifications......................................................................................................... 5
GENERAL DESCRIPTION....................................................................................... 6Components .......................................................................................................... 6
INSTALLATION ........................................................................................................ 8Install Display Module ........................................................................................... 8Install Cab Miniature Display ................................................................................. 8Install Pressure Sensor ......................................................................................... 10Install Pressure/Vacuum Foam Tank Vent ........................................................... 12Install Remote Light Driver .................................................................................. 14Install Buzzer ........................................................................................................ 14
OPERATION............................................................................................................ 15Options ................................................................................................................ 15
CALIBRATION........................................................................................................ 16Overview .............................................................................................................. 16Non-Linear Calibration ......................................................................................... 17Linear Calibration ................................................................................................. 18Fine Calibration .................................................................................................... 19
DIAGNOSTICS ....................................................................................................... 20WIRING ................................................................................................................... 22
Master Display ..................................................................................................... 22Remote and Cab Miniature Displays ................................................................... 23Remote Light Driver ............................................................................................ 24Typical System Configuration ............................................................................. 25
CLEAN/INSPECT PRESSURE/VACUUM FOAM TANK VENT......................... 26PARTS LIST ............................................................................................................ 27
WL2000 Rev0404
3
List of FiguresFigure 1. Display Module Mounting Dimensions ....................................................... 9Figure 2. Cab Miniature Display Mounting Dimensions ............................................ 9Figure 3. Pressure Sensor ........................................................................................ 11Figure 4. Pressure/Vacuum Foam Tank Vent ........................................................... 13Figure 5. Remote Light Driver ................................................................................. 14Figure 6. Diagnostics ............................................................................................... 20Figure 7. Master Display Wiring .............................................................................. 22Figure 8. Remote and Cab Miniature Display Wiring .............................................. 23Figure 9. Remote Light Driver Wiring ...................................................................... 24Figure 10. Typical System Configuration ................................................................ 25Figure 11. Clean and Inspect Pressure/Vacuum Foam Tank Vent ........................... 26Figure 12. Parts List ................................................................................................. 27
WL2000 Rev0404
4
INTRODUCTIONOverview
The FRC TANKVISION volume indicator shows the actual volume of liquid ina tank. The liquid in the tank exerts a pressure that is measured by a sensor. As theamount of liquid changes, the pressure it exerts on the sensor changes proportionally.The pressure change is used to calculate the exact volume of liquid in the tank. TheTANKVISION can be calibration to accurately display the volume in tanks of allshapes and sizes.
The display module is able to communicate with other display modules over theFRC datalink. This allows for one master display module to control multiple displays.The module also provides an output for cab miniature displays, remote light drivers,and a low level warning buzzer.
The TANKVISION indicator is a unique design made up of an extended wideview lens with nine super bright LEDs mounted behind it. This allows the display to bevisible and clearly read from all line-of-sight angles for a full 180 degrees.
The pressure/vacuum foam tank vent is supplied for use on foam concentratestorage tanks. These tanks should remain closed to the atmosphere. The FRC ventenables the tank to compensate for changes in pressure or vacuum due to thermalexpansion, filling, or when withdrawing foam concentrate from the tank.
The remote light driver provides the option to have four 60 watt remote lightscontrolled by the TANKVISION to show full, 3/4, 1/2, and 1/4 tank.
FeaturesSelf-Calibrating for Any Shape or Size Tank
Visual Warnings At 1/4 and Almost Empty Tank Conditions
Unlimited Remote Displays
Pressure/Vacuum Foam Tank Vent for Sealed Foam Tanks
Color Coded for Water, Class A, or Class B Foam
Self-Diagnostic Capabilities
Cab Miniature Display (Optional)
Remote Light Driver (Optional)
Low Level Warning Buzzer (Optional)
Tank Thin Wall Adapter Kit (Optional)
WL2000 Rev0404
5
Specifications
Display Module
Supply Voltage: 9 - 30 VDC
Supply Current: 0.25 Amp Maximum
Dimensions: 4.4 x 3.0 Inches
Housing: Waterproof Cast Aluminum
Indicators: 9 Super Bright LEDs
Viewing Angle: 180°
Pressure Sensor
Housing: Stainless Steel
Sensor: Ceramic Diaphragm
Pressure Range: 0 - 5 PSI (Maximum Tank Height - 10 Feet)
Excitation Voltage: 5 VDC
Pressure/Vacuum Foam Tank Vent
Material: PVC and Aluminum with Delrin Valves
Relief Pressure: ±0.01 PSI
Maximum Flow Rate: Compensates 100% for Concentrate Flow Rates
Below 60 GPM
Cab Miniature Display
Supply Voltage: 9 - 30 VDC
Supply Current: 0.15 Amp Maximum
Dimensions: 2.25 x 1.0 Inches
Remote Light Driver
Supply Voltage: 9 - 30 VDC
Supply Current: 0.1 Amp Maximum
Switch: Solid State
Switching Voltage: 9 - 30 VDC
Switching Current: 20 AMPS Maximum @ 12 VDC
10 AMPS Maximum @ 24 VDC
WL2000 Rev0404
6
GENERAL DESCRIPTIONComponents
The TANKVISION volume indicator consists of the following components:
Display Module
Pressure Sensor
Pressure/Vacuum Relief Valve (Foam Tanks)
Cab Miniature Display (Optional)
Remote Light Driver (Optional)
Buzzer (Optional)
Cables
Display Module
The tank volume display module is waterproof and has dimensions of 4.4 incheshigh by 3 inches wide. An output signal from a pressure sensor mounted on the tank isinput to the master display module. It is processed and the volume of liquid in the tankis shown on the 9 LED display. Outputs from the master display module provide tankvolume information to other displays and remote devices.
Pressure Sensor
The pressure sensor is mounted on a side of the tank near the bottom. It providesan signal that is proportional to the volume of liquid in the tank to the input of themaster display module. The electrical connector is waterproof and molded into thepressure sensor housing.
The pressure sensor FRC part number WL-PT1 is used on tanks between 1 and10 feet in vertical height. For tanks taller than 10 feet contact FRC for options.
Pressure/Vacuum Foam Tank Vent
The pressure/vacuum foam tank vent is supplied for use on sealed foam tanks.The vent will compensate for changes in tank pressure due to thermal expansion orwhen withdrawing foam concentrate from the tank. Internal passageways provide apath for air to move between the tank and a center cavity in the vent. These passagewaysare self-draining and designed to prevent splashing foam from entering the center cavityand clogging the pressure and vacuum valves. The pressure and vacuum valves areeasily accessed and disassembled for periodic cleaning or inspections. (Refer toMaintenance section.)
Note: The vent can compensate for a maximum foam concentrate flow rateof 60 GPM. If the flow rate of foam concentrate from the tank will exceed60 GPM, two (2) vents will be required.
WL2000 Rev0404
7
Cab Miniature Display (Optional)
The cab miniature display has dimensions of 2.25 inches high by 1 inches wide. Itprovides the option of mounting a remote display in the cab that uses a minimum ofpanel space. An output signal from the master display module is input to the cabminiature display and the volume of liquid in the tank is shown on the 5-LED display.
Remote Light Driver (Optional)
The remote light driver is waterproof and has dimensions of 4 inches high by 2.75inches wide by 1 inch deep. An output signal from the master display module is inputto the remote light driver. This provides the option to power four (4) 60 watt remotelights that show the volume of liquid in the tank. The lights will show full, 3/4, 1/2, and1/4 tank levels.
Buzzer (Optional)
The buzzer will provide an audio alarm when the tank volume drops to 25%. It willbuzz 9 times. The buzzer resets when the tank volume goes above 25%.
WL2000 Rev0404
8
INSTALLATIONThe TANKVISION display modules are interchangeable. The master display
module is connected to the pressure sensor and is the only module that needs to becalibrated.
Note: The calibration procedure needs to be performed every time a masterdisplay module is installed.
Install Display Module Note: It is recommended to mount the display at eye level.
1. Measure and mark mounting location for display module panel cutout andmounting screw holes. Make sure there is clearance behind the panel for thedisplay and cables before cutting holes. Refer to Figure 1 for layout anddimensions.
2. Cut out a 4 by 2 1/8-inch hole and drill four (4) holes (clearance or tapped) for6-32 mounting screws.
3. Place display module in position and secure with four (4) screws.
4. Connect the display module cables and wires. (Refer to Wiring section.)
Install Cab Miniature DisplayNote: The cab miniature display is not weatherproof or designed to be
mounted in wet areas.
1. Measure and mark mounting location for cab miniature display mounting hole.Make sure there is clearance behind the panel before drilling hole. Refer toFigure 2 for layout and dimensions.
2. Drill a clearance hole for 3/8" threads.
3. Place cab miniature display in position and secure with nut.
4. Connect the cab miniature display wires. (Refer to Wiring section.)
WL2000 Rev0404
9
Panel Cutout
Figure 1. Display Module Mounting Dimensions
5/8"1 1/2"
1 3/16"
1 9/16"
Drill a clearance holefor 3/8" threads.
2 3/4"
3/4"
Figure 2. Cab Miniature Display Mounting Dimensions
WL2000 Rev0404
10
Install Pressure SensorThe pressure sensor is mounted on one of the tank sides approximately 2 inches
from the bottom. If the tank has a vertical height greater than 10 feet contact FRC, adifferent sensor may be required.
Pressure sensors are interchangeable. It is recommended that the calibrationprocedure be performed if the pressure sensor is changed.
Note: When mounting the pressure sensor on a tank with thin walls, less than3/8", it is recommended that the tank wall be reinforced at the sensormounting location.
Pressure Sensor Installation
1. Measure and mark mounting location for sensor. (Mounting hole should beapproximately 2" from bottom of tank.) Make sure there is clearance for sensorand cable before drilling hole. Refer to Figure 3 for dimensions.
2. Drill and tap a 1/4 NPT hole.
3. Apply sealant around base and threads of pressure sensor.
4. Screw transducer into hole.
4. Connect sensor cable. (Refer to Wiring section.)
Thin Wall Adapter Installation
The thin wall adapter kit includes the adapter, two 10-24 x 5/8" screws, 5 minuteepoxy, and a mixing stick.
1. Measure and mark mounting location for adapter. Make sure there is clearancefor adapter, sensor, and cable before drilling hole. Refer to Figure 3 fordimensions.
2. Drill and tap a 1/2 NPS (National Pipe Straight Thread) hole.
3. Screw the adapter into the hole.
4. Use the adapter as a template and drill and tap two 10-24 holes for two screws.
5. Back adapter out of hole and apply 5 minute epoxy to back of flange, onthreads, and in two 10-32 through holes.
6. Screw adapter into hole and secure with two screws.
7. Allow the epoxy time to set.
8. Apply sealant around base and threads of pressure sensor and screw intoadapter.
9. Connect transducer cable. (Refer to Wiring section.)
WL2000 Rev0404
11
SupplyVoltage5 VDC
OutputSignal
Ground
Typical PressureSensor Location
TypicalTank
1.7"
1.86"
Pressure Sensor
Mount the sensorapproximately 2" from
the bottom of tank.Apply sealent
around base andthreads.
1/2 NPS
Thin Wall Adapter
2"
Pressure Sensor withThin Wall Adapter
Figure 3. Pressure Sensor
Apply epoxy aroundflange, threads, and
screws.
Apply sealentaround base and
threads.
WL2000 Rev0404
12
Install Pressure/Vacuum Foam Tank VentA pressure/vacuum foam tank vent is supplied for use on sealed foam tanks. The
recommended location to mount the vent is in the cover of the foam tank fill tower. Ifthere is no fill tower, mount the vent at the highest point of the tank top so that it is notimmersed in foam. For installations where clearance above the fill tower is limited, a90° mounted vent is available.
Note: The vent can compensate for a maximum foam concentrate flow rateof 60 GPM. If the flow rate of foam concentrate from the tank will exceed60 GPM, two (2) vents will be required.
Install Top Mounted Tank Vent
The top mounted tank vent is mounted in a vertical position through a 1 1/8-inchhole on the lid of the fill tower and is secured by a hand tightened nut.
Note: The tank vent must be in a vertical position and can not be immersedin foam.
1. Measure and mark mounting location for vent. Make sure there is clearance forthe valve before drilling hole. Refer to Figure 4 for dimensions.
2. Drill 1 1/8-inch diameter hole.
3. Insert vent into the hole with the gasket in place.
4. Screw on nut and hand tighten.
Install 90° Mounted Tank Vent
The 90° mounted tank vent is mounted on a vertical side of the fill tower. It mustbe located as close to the top of the fill tower as possible. The vent is held in place withwith two (2) 1/4-20 x 3-inch bolts, washers, and locknuts.
Note: The tank vent must be in a vertical position and can not be immersedin foam.
1. Measure and mark mounting location for vent. Make sure there is clearance forthe valve before drilling holes. Refer to Figure 4 for dimensions.
2. Drill 3/4-inch diameter hole and two through holes for 1/4-20 bolts.
3. Apply sealant to mounting surfaces and bolt holes.
4. Secure vent in place with two bolts, washers, and locknuts.
WL2000 Rev0404
13
Top Mounted Tank Vent
Gasket (Between MountingSurface and Tank Vent)
Nut (1 1/8" - 12 TPI)
Maximum MountingSurface Thickness
1 3/4"
12345678123456781234567812345678123456781234567812345678
2 1/2"
5/8"
90° Mounted Tank Vent
1/4" Dia.(Thru holes for two1/4-20 x 3" bolts.)
3/4" Dia.
2 5/8"
Figure 4. Pressure/Vacuum Foam Tank Vent
Note: The tank vent must be mountedin a vertical position. The vent can notbe immersed in foam. (If there is no fill
tower, mount the vent at the highestpoint of the tank top so that it is not
immersed in foam.)
2 5/8"
3 7/8"
1 1/2"
Top Mounted Tank Vent1 1/8" Diameter Hole
90° Mounted Tank Vent3/4" Diameter Hole with
Two 1/4" Bolt Holes
Foam TankFill Tower
90° MountedTank Vent
Top MountedTank Vent
TypicalFoam Tank
WL2000 Rev0404
14
Install Remote Light DriverThe remote light driver is water proof to allow for flexibility in the mounting location.
1. Measure and mark mounting location for light driver. Make sure there is clearancefor driver and cable before drilling holes. Refer to Figure 5 for dimensions.
2. Drill and tap two 10-32 holes.
3. Secure remote light driver with two screws.
4. Connect cable and wires. (Refer to Wiring section.)
Install BuzzerInstall the buzzer close to the TankVision so the audible warning is easily associated
with the TankVision. A cutout hole of 1-1/4" is required. ( Refer to the wiring section.)
Figure 5. Remote Light Driver
2 3/4"
1 3/8"
3 1/2"4"
WL2000 Rev0404
15
OPERATIONNo operator input is required for the TANKVISION to be operational. When
power is on the tank volume gauge will be operating. The signal from the pressuresensor is processed and the tank volume shows on the display.
Note: Calibrating the TANKVISION display to the tank is required beforeoperations. (Refer to Calibration section.)
Master Display Module
All 9 LEDs will be on when the tank is full.
Each LED will go off starting at the top as the tank volume decreases.
The bottom 2 LEDs will flash when the tank volume is less than 25%.
All 9 LEDs will rapidly down-chase when the tank is almost empty.
Options
Remote Display Module
The remote display will repeat exactly what is shown on the master display.
Cab Miniature Display
All 5 LEDs will be on when the tank is full.
The LEDs will show full, 3/4, 1/2, 1/4, and empty tank.
Remote Light Driver
Note: If there is no signal on pin 2 (input from a display module) the lightswill remain off. (Refer to Wiring section.)
When power is applied the remote light driver will run a lamp test function. Thelamp test will start at the 1/4 light and cycle each remote light on and off. At thecompletion of the lamp test the remote light driver turns on the lights to show the tankvolume.
All 4 lights will be on when the tank is full.
The lights will show full, 3/4, 1/2, and 1/4 tank.
The 1/4 light will blink when the tank volume is less than 25%.
Buzzer
The buzzer will sound when the the tank volume drops to 25%.
WL2000 Rev0404
16
CALIBRATIONThe TANKVISION has unique calibration programs that enable it to be used on
tanks of all shapes and sizes.
Note: The standard pressure sensor is limited to a maximum tank height often feet.
Overview
Magnet Sensor
The calibration programs are accessed by activating the CAL. magnet sensor thatis located at the bottom on the front of the display module. The sensor is activated byplacing the north pole of a small magnet in close proximity of the sensor. (The sensorwill not respond to the south pole of the magnet.) The magnet is then moved about 1-inch away, this will produce an electronic signal that is similar to a button being released.If the LEDs in the display do not change try moving the magnet further away from thesensor.
In these procedures the term ‘swipe’ will mean to move the magnet up to and thenaway from the magnetic sensor.
Non-Linear Calibration
The first program is a non-linear calibration procedure that can be used for anyshape or size tank. This procedure must to be used for irregular shape tanks (e.g.: T-shape, oval, elliptical, tank with through hole, etc.). The program compares the pressurein the tank, as the tank fills at a steady rate, to time. This provides accurate volumedisplays.
Linear Calibration
The second program is a linear calibration procedure that can only be used whenthe tank volume is proportional to the height. This would include square or rectangularshape tanks with no irregularities. It is quick way of calibrating a tank but not asaccurate as the non-linear procedure. The program compares a full tank to an emptytank, takes the difference and divides it into eight equal volume displays.
Fine Calibration
This program is for use to fine tune the tank volume display after a non-linear orlinear calibration procedure has been completed. It would only be needed in caseswhere one type of liquid is used for calibration when a different liquid would normallybe in the tank. For example this would allow the basic calibration of a foam tank to bedone using water and then the calibration would be fine tuned when the tank is filledwith foam.
WL2000 Rev0404
17
Non-Linear CalibrationThis non-linear calibration procedure can be used for any shape or size tank. The
calibration process requires that the tank be empty at the start of the procedure andthen filled at a steady rate of flow.
The term ‘swipe’ will mean to move the magnet up to and then away from theCAL. sensor at the bottom of the display.
To exit the calibration mode swipe the magnet eight times. The top eight displayLEDs go on, the calibration program terminates, no program data is changed.
1. Empty the tank.
2. Apply power to the display module.
3. Swipe the magnet three times to enter the calibration mode.
Result: Top three display LEDs flash on and off.
Note: Once the calibration process is activated the flow rate of liquid into thetank must remain constant for the procedure to be accurate.
4. Fill the tank at a steady rate of flow.
5. When the tank is full stop the flow. (There is no problem if the tank overflows.)
Note: The program will only act on three swipes to set the calibration intomemory, or eight swipes to terminate the calibration program. If a wrongentry is made, wait six seconds and it will clear.
6. Swipe the magnet three times to set the calibration into memory.
Result: Top three display LEDs go on.
7. After six seconds the calibration process will terminate and all the LEDs willgo on to show that the tank is full.
WL2000 Rev0404
18
Linear CalibrationThis linear calibration procedure can only be used for square or rectangular shape
tanks with no irregularities. The calibration process requires that the tank be full at thestart of the procedure.
The term ‘swipe’ will mean to move the magnet up to and then away from theCAL. sensor at the bottom of the display.
To exit the calibration mode swipe the magnet eight times. The top eight displayLEDs go on, the calibration program terminates, no program data is changed.
1. Fill the tank.
2. Apply power to the display module.
Note: Once the calibration program is activated there is a six second timeout. Do not wait more than six seconds to move from step 3 to step 4.
3. Swipe the magnet four times to enter the calibration mode.
Result: Top four display LEDs flash on and off.
4. After three seconds swipe the magnet four times to set the calibration intomemory.
Result: Top four display LEDs go on.
5. After six seconds the calibration process will terminate and all the LEDs willgo on to show that the tank is full.
WL2000 Rev0404
19
Fine CalibrationThis fine calibration procedure is used to fine tune the tank volume display after a
non-linear or linear calibration has been completed. The calibration process requiresthat the tank be full at the start of the procedure and the display shows 75% or more.
The term ‘swipe’ will mean to move the magnet up to and then away from theCAL. sensor at the bottom of the display.
To exit the calibration mode swipe the magnet eight times. The top eight displayLEDs go on, the calibration program terminates, no program data is changed.
1. Fill the tank.
2. Apply power to the display module.
Note: Once the calibration program is activated there is a six second timeout. Do not wait more than six seconds to move from step 3 to step 4.
3. Swipe the magnet five times to enter the calibration mode.
Result: Top five display LEDs flash on and off.
4. After three seconds swipe the magnet five times to set the calibration intomemory.
Result: Top five display LEDs go on.
5. After six seconds the calibration process will terminate and all the LEDs willgo on to show that the tank is full.
WL2000 Rev0404
20
DIAGNOSTICSThere are diagnostic codes built into the TANKVISION. These diagnostic codes
will help in the troubleshooting process.If there is no input on pin 2 of the remote light driver, the remote lights will remain
off.
Top and Bottom LEDsAlternately Flash.
CabMiniatureDisplayMaster or
RemoteDisplay
Pressure Sensor notdetected at master
display
Sensorr cable not connectedBroken wire / bad connector onsensor cableDefective sensor
Datalink not detected atremote display
Datalink cable not connectedBroken wire / bad connector ondatalink cable
Problem Probable CauseDisplay
1/4 and 3/4 LEDsAlternately Flash.
Cab MiniatureDisplay
Data not detected at cabminiature display
Broken wire / bad connector todisplay input
3/8 and 5/8 LEDsAlternately Flash.
Master orRemoteDisplay
Illegal calibrationprocedure
Restart procedure
Figure 6. Diagnostics
WL2000 Rev0404
21
This page intentionally left blank.
WL2000 Rev0404
22
WIRINGMaster Display
1
4 5
8
Master DisplayConnector
Pin Description 1 Power 9-30 VDC 2 Ground 3 Sensor 5 VDC 4 Sensor Signal 5 Buzzer Ground (150mA) 6 Display Signal Out 7 Datalink (+) 8 Datalink (–)
Note: When the display is used inthe Auto TankVision system pin 5 isthe output to the Auto TankVisionswitch panel.
Pressure Sensor Connector
SupplyVoltage5 VDC
OutputSignal
Ground
Standard HarnessMaster Display
Module
Deutsch PlugDTM06-8S
Master DisplayModule
Pressure Sensor
Figure 7. Master Display Wiring
WL2000 Rev0404
23
Remote and Cab Miniature Displays
Remote DisplayModule
Standard HarnessRemote Display
Module
Deutsch PlugDTM06-8S
Remote DisplayConnector
Pin Description 1 Power 9-30 VDC 2 Ground 3 N/A 4 N/A 5 Buzzer Ground (150mA) 6 Display Signal Out 7 Datalink (+) 8 Datalink (–)
Note: A white wire with a Deutsch pin on oneend (to plug into the standard harnessconnector) and a butt connector on the other(to connect to customer provided wire) isprovided with the Cab Miniature Display.
1234512345
White Wire
123456123456123456123456123456123456
123412341234123412341234
1234123412341234123412341234
ButtConnectors
Cab MiniatureDisplay
Cab Miniature DisplayWiring
Wire Description Red Power 9-30 VDC Black Ground White Display Signal
Figure 8. Remote and Cab Miniature Display Wiring
WL2000 Rev0404
24
Remote Light DriverNotes:Connect a wire from the master or a remote display module pin 6 to the remote
light driver pin 2 (this is the input signal to the remote driver).Connect power to pin 3 (this is power for the remote driver) and to pin 8 (this is
power for the remote lights). It is recommended that pin 3 and pin 8 be tied together.The maximum current at pin 8 is 20 AMPS @ 12VDC (10 AMPS @ 24 VDC).
1
4 5
8
Light Driver ConnectorPin Signal Description 1 Ground 2 Signal Input 3 Power 9 to 30 VDC 4 1/4 Tank Output 5 1/2 Tank Output 6 3/4 Tank Output 7 Full Tank Output 8 Light Power 9 to 30 VDC
Remote LightDriver
Light Power(12 VDC 20 A)(24 VDC 10 A)
Use 16 AWG Wire
GND
Full Tank
9 - 30 VDC Power
Typical RemoteLight Stack
Ground
Input FromDisplay Module Pin 6
1/2 Tank
3/4 Tank
1/4 Tank
Figure 9. Remote Light Driver Wiring
WL2000 Rev0404
25
Typical System Configuration
Note: If pins are needed for theconnectors order FRC part WLP-01(Socket Contact 0462-201-16141).
FRC DatalinkMasterDisplay
PressureSensor
Power
RemoteDisplay
CabMiniatureDisplay
WarningBuzzer
12 VDC
Power
RemoteLightDriver
ToRemoteLights
Power
123123123
121212
12121212
Power
Note: An unlimited number of remotedisplays can be connected. Any remotedisplay can become a master unit bydisconnecting the sensor from the masterand connecting it to the remote.
To OtherMiniatureDisplays Daisey Chain
To OtherRemoteDisplays
Figure 10. Typical System Configuration
WL2000 Rev0404
26
CLEAN/INSPECT PRESSURE/VACUUM FOAM TANKVENT
The pressure/vacuum foam tank valve is supplied for use on sealed foam tanks.There are internal passageways that provide a path for air to move between the
tank and a center cavity in the vent. These passageways are self-draining and designedto prevent splashing foam from entering the center cavity and clogging the pressureand vacuum valves.
The pressure and vacuum valves are easily accessed and disassembled for periodiccleaning or inspections. Unscrew the cap from the main body and lift the valves out ofthe center cavity. Clean all parts with warm water.
Note: The internal pressure and vacuum valves are different sizes. Make sureto reassemble these valves correctly.
Figure 11. Clean and Inspect Pressure/Vacuum Foam Tank Vent
Pressure Valve
Vucuum Valve
Note: It is extreamlyimportant that the
pressure and vucuumvalves are assembled
correctly.
Pressure Valve
Center CavityVacuum Valve
Tank Vent
Tank Top
Vent toAtmosphere
Cap
Main Body
Nipple
Cutaway Diagram
WL2000 Rev0404
27
PARTS LISTIndex FRC Part No. Description
WL2000 TankVision Kit
WL2600 TankVision Kit Class A Foam
WL2700 TankVision Kit Class B Foam
1 WL2200D . TankVision Display
2 WLC-XX . Master Display Cable
XX = Cable Length (In Feet)
3 WL-PT1 . Pressure Sensor
WL-2100S Remote Kit
WL2200D . TankVision Display
4 WLC-2XXS . Remote Display Cable
XX = Cable Length (In Feet)
5 WL2500 Cab Miniature Display
WL2800A Cab Miniature Display Class A Foam
WL2800B Cab Miniature Display Class B Foam
6 WL2900 Remote Light Driver
7 WL-400 Pressure/Vacuum Tank Vent Top Mounted
8 WL-400H Pressure/Vacuum Tank Vent 90° Mounted9 WL-20A Thin Wall Adapter
1 2 3 4
5
8
9
67
1234512345123451234512345
Figure 12. Parts List