Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Project Name
Engineer
Contractor
SCHEDULE ATTACHED
Item # Tag ID
Probe Length Adj. Side Length Internal Insula on
BASE MODEL
GTC116‐P
GTM116‐P
GTL116‐P
GTD116‐P
Other ______________
PROBES & SENSOR NODES
P+ Density (see density table, next
page)
Custom Probes: ___
Nodes/Probe: ___
Custom meets or exceeds P+ density
AVERAGING
Airflow: Independent, arithme c aver‐
age
Temperature: Independent, field se‐
lectable, velocity weighted (default) or
arithme c average
LISTINGS
UL 873
BTL (GTC116 and GTM116)
CE (European shipments only)
Other __________________________
INDIVIDUAL SENSING NODES
HOUSING Glass‐filled polypropylene (std.)
Solid Kynar (/SS op on)
THERMISTORS Self‐heated sensor: Herme cally‐sealed bead‐in‐glass
thermistor probe
Temperature sensor: Herme cally‐sealed bead‐in‐glass
thermistor probe
INTERNAL WIRING Kynar coated copper
AIRFLOW MEASUREMENT Accuracy: ±2% of reading
Calibrated range: 0 to 5,000 fpm
Calibra on points: 16
NIST‐traceable calibra on
TEMPERATURE
MEASUREMENT
Accuracy: ±0.15⁰F
Calibrated range: ‐20 to 160⁰F
Calibra on points: 3
NIST‐traceable calibra on
PROBE ENVIRONMENTAL LIMITS
TEMPERATURE
Probe ‐20 to 160⁰F
Transmi er ‐20 to 120⁰F
Probe 0 to 100%
Transmi er 5 to 95%
HUMIDITY (non‐condensing)
Refer to a ached SCHEDULE for table details if bu on is checked in any of the tables
Advantage 3
High-performance Airflow Measurement with Temperature & Alarm Capability SUBMITTAL DATA
®
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
GTx116-P+ GOLD SERIES
I‐P Units
RECTANGULAR PROBE POSITIONING IN DUCT
# of
Probes a b
1 ½ X NA
2 ¼ X ½ X
3 ⅙ X ⅓ X
4 ⅛ X ¼ X
ROUND PROBE POSITIONING IN DUCT
# of
Probes a
1 NA
2 90⁰
3 60⁰
4 45⁰
b = distance from probe 1 to 2, 2 to 3 and 3 to 4
a = angle from probe 1 to 2, 2 to 3 and 3 to 4
Note: # probes=2 shown for illustra on
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
P+ SENSOR DENSITY TABLE (# Probes/# Sensor nodes per probe)
Probe Length (inches)
6
8
10
12
14
16
18
20
22
24
30
36
42
48
54
60
66
72
84
96
108
120
Round 1/1 1/1 1/1 1/2 2/2 2/2 2/2 2/4 2/4 2/4 2/4 2/4 2/6 2/8 2/8 2/8 2/8 4/4 4/4 4/4 4/4 4/4
Flat Oval All flat ovals are custom. Contact EBTRON or your representative for information on flat ovals.
Square/R
ectangle A
djacen
t Side Len
gth (in
ches)
6 1/1 1/1 1/1 1/1 1/2 1/2 1/2 1/2 1/2 1/2 1/4 1/4 1/4 1/4 1/6 1/6 1/6 1/6 1/6 1/6 1/8 1/8
8 1/1 1/1 1/1 1/2 1/2 1/2 1/2 1/4 1/4 1/4 1/4 1/4 1/6 1/6 1/6 1/6 1/6 1/6 1/8 1/8 1/8 1/8
10 1/1 1/1 1/1 1/2 1/2 1/3 1/4 1/4 1/4 1/4 1/6 1/6 1/6 1/6 1/6 1/8 1/8 1/8 1/8 1/8 1/8 2/6
12 1/1 1/1 1/1 1/2 1/3 1/3 1/4 1/4 1/4 1/4 1/6 1/6 1/6 1/6 1/8 1/8 1/8 1/8 1/8 1/8 2/6 2/6
14 2/1 2/1 2/1 2/2 2/2 2/2 2/2 2/2 2/3 2/3 1/6 1/6 1/8 1/8 1/8 1/8 1/8 1/8 2/6 2/6 2/6 2/6
16 2/1 2/1 3/1 2/2 2/2 2/2 2/2 2/3 2/3 2/3 1/6 1/6 1/8 1/8 1/8 1/8 1/8 1/8 2/6 2/6 2/6 2/7
18 2/1 2/1 3/1 2/2 2/2 2/2 2/3 2/3 2/3 2/3 1/6 1/8 1/8 1/8 1/8 1/8 2/6 2/6 2/6 2/6 2/7 2/8
20 2/1 3/1 3/1 2/2 2/2 2/3 2/3 2/3 2/3 2/3 2/4 1/8 1/8 1/8 1/8 2/6 2/6 2/6 2/6 2/7 2/8 2/8
22 2/1 3/1 3/1 2/2 3/2 2/3 2/3 2/3 2/3 2/3 2/4 1/8 1/8 1/8 2/6 2/6 2/6 2/6 2/7 2/8 2/8 2/8
24 2/1 4/1 4/1 2/2 3/2 2/3 2/3 2/3 2/3 2/3 2/4 2/4 1/8 1/8 2/6 2/6 2/6 2/6 2/7 2/8 2/8 2/8
30 4/1 4/1 4/1 3/2 3/2 3/2 3/2 2/4 2/4 2/4 2/4 2/4 2/6 2/6 2/6 2/7 2/7 2/8 2/8 2/8 2/8 2/8
36 4/1 4/1 4/1 3/2 3/2 3/2 4/2 4/2 4/2 2/4 2/4 2/6 2/6 2/6 2/7 2/8 2/8 2/8 2/8 2/8 2/8 2/8
42 4/1 4/1 4/1 3/2 4/2 4/2 4/2 4/2 4/2 4/2 2/6 2/6 2/7 2/7 2/8 2/8 2/8 2/8 2/8 2/8 2/8 2/8
48 4/1 4/1 4/1 3/2 4/2 4/2 4/2 4/2 4/2 4/2 3/4 2/6 2/7 2/8 2/8 2/8 2/8 2/8 2/8 2/8 2/8 2/8
54 4/1 4/1 4/1 4/2 4/2 4/2 4/2 4/2 3/4 3/4 3/4 2/7 2/8 2/8 2/8 2/8 2/8 4/4 2/8 2/8 2/8 2/8
60 4/1 4/1 4/1 4/2 4/2 4/2 4/2 3/4 3/4 3/4 4/4 4/4 2/8 2/8 2/8 4/4 4/4 4/4 4/4 2/8 2/8 2/8
66 4/1 4/1 4/1 4/2 4/2 4/2 3/4 3/4 3/4 3/4 4/4 4/4 4/4 2/8 2/8 4/4 4/4 4/4 4/4 4/4 2/8 2/8
72 4/1 4/1 4/1 4/2 4/2 4/2 3/4 3/4 3/4 3/4 4/4 4/4 4/4 2/8 4/4 4/4 4/4 4/4 4/4 4/4 4/4 2/8
84 4/1 4/1 4/1 4/2 4/3 4/3 3/4 3/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
96 4/1 4/1 4/1 4/2 4/3 4/3 3/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
108 4/1 4/1 4/1 4/2 4/3 4/3 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
120 4/1 4/1 4/1 4/2 4/3 4/3 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Probe 1
Probe(s) 2 to 4
Inside edge of duct
(including insulation)
a
b
Probe Length
Probe(s) 2 to 4
a⁰
IMPORTANT NOTES REGARDING SENSOR DENSITY
1. Items in RED do not meet guide spec sensor density due to manufacturing limita ons.
2. Items in GREEN meet sensor density requirements but do not match guide spec aspect ra o requirements for the number of probes.
3. UNDERLINED items cannot be manufactured as internal mount due to manufacturing limita ons.
PROBE MOUNTING STYLE
INTERNAL ‐ 304 stainless steel brackets
INSERTION ‐ 304 stainless steel brackets
STAND‐OFF ‐ 304 stainless steel brackets
Probes < 18 in. are ¼ in. undersized and do not have a terminal stud
Overall tube length is 2 in. > ordered probe length
PROBE TUBE MATERIAL
Stand‐
ard
Gold anodized 6063 alumi‐
num (1.1” dia.)
/SS
op on
316 stainless steel (1.125”
dia.)
10 . (std.) 30 .
15 . 40 .
20 . 50 . (max.)
25 . Custom ____ .
CABLE LENGTH
CABLE TYPE
FEP Plenum Rated (std.)
Other __________________________
CONNECTOR PLUG DIMENSIONS
TRANSMITTER
GTC116 Two isolated analog output signals (field selectable/scalable 0‐
5/0‐10 VDC or 4‐20mA) plus one isolated RS‐485 network con‐
nec on (field selectable BACnet MS/TP or Modbus RTU)
GTM116 Two isolated analog output signals (field selectable/scalable 0‐
5/0‐10 VDC or 4‐20mA) plus one isolated Ethernet network
connec on (simultaneously supported BACnet Ethernet, BAC‐
net IP, Modbus TCP or TCP/IP)
GTL116 One isolated Lonworks Free Topology network connec on
GTD116 One USB connec on for thumb drive data‐logging of sensor
airflow and temperature over specified me intervals
EB‐Link (/EL opt.) Interface for handheld EB‐Link Reader (provided separately)
TRANSMITTER CONNECTOR PLATE
# OF PROBES 1 2 3 4
MAX. SENS/PROBE 8
TYPE A B
RECEPTACLES 2 4
4
CONNECTORS & INTERCONNECTS
Gold plated plug/receptacle pins
Gold plated PCB edge card fingers
Gold plated PCB interconnects
ENIG plated printed circuit boards 24 VAC TRANSFORMER SELECTION
2 4 6 8 10 12 14 16
13 VA 14 VA 15 VA 16 VA 17 VA 18 VA 19 VA 20 VA
TOTAL SENSORS
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
GTx116-P+_Subm
ittalData_r2a
MAIN CIRCUIT BOARD CONNECTIONS
①
②
③
❹
❺ ANALOG OUTPUT
CONNECTIONS
GTC116‐P
GTM116‐P
+ Common
Airflow ① ③
Temperature
or Alarm ② ③
Models
24 VAC POWER CONNECTIONS
ALL
L2 (gnd.) L1 (hot)
24 VAC ❹ ❺
Models
OUTPUT CARD
NETWORK CONNECTIONS
GTL116‐P
Net + Net ‐
Lon Free Top. ① ②
Models
OUTPUT CARD CONNECTIONS
NETWORK CONNECTIONS
GTC116‐P
Net + Net ‐
RS‐485 ① ②
Models
Net
Com
③
NETWORK CONNECTIONS
Models GTM116‐P
Ethernet ① RJ‐45 (10/100)
①
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com