4
Project Name Engineer Contractor SCHEDULE ATTACHED Item # Tag ID Probe Length Adj. Side Length Internal InsulaƟon BASE MODEL GTC116P GTM116P GTL116P GTD116P Other ______________ PROBES & SENSOR NODES P+ Density (see density table, next page) Custom Probes: ___ Nodes/Probe: ___ Custom meets or exceeds P+ density AVERAGING Airow: Independent, arithmeƟc average Temperature: Independent, eld selectable, velocity weighted (default) or arithmeƟc average LISTINGS UL 873 BTL (GTC116 and GTM116) CE (European shipments only) Other __________________________ INDIVIDUAL SENSING NODES HOUSING Glasslled polypropylene (std.) Solid Kynar (/SS opƟon) THERMISTORS Selfheated sensor: HermeƟcallysealed beadinglass thermistor probe Temperature sensor: HermeƟcallysealed beadinglass thermistor probe INTERNAL WIRING Kynar coated copper AIRFLOW MEASUREMENT Accuracy: ±2% of reading Calibrated range: 0 to 5,000 fpm CalibraƟon points: 16 NISTtraceable calibraƟon TEMPERATURE MEASUREMENT Accuracy: ±0.15F Calibrated range: 20 to 160F CalibraƟon points: 3 NISTtraceable calibraƟon PROBE ENVIRONMENTAL LIMITS TEMPERATURE Probe 20 to 160F TransmiƩer 20 to 120F Probe 0 to 100% TransmiƩer 5 to 95% HUMIDITY (noncondensing) Refer to aƩached SCHEDULE for table details if buƩon is checked in any of the tables Advantage 3 High-performance Airflow Measurement with Temperature & Alarm Capability SUBMITTAL DATA ® EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com GTx116-P+ GOLD SERIES IP Units

with Temperature & Alarm Capability SUBMITTAL DATA · 2019-11-08 · RECTANGULAR PROBE POSITIONING IN DUCT # of Probes a b 1 ½ X NA 2 ¼ X ½ X 3 ⅙ X ⅓ X 4 ⅛ X ¼ X ROUND PROBE

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: with Temperature & Alarm Capability SUBMITTAL DATA · 2019-11-08 · RECTANGULAR PROBE POSITIONING IN DUCT # of Probes a b 1 ½ X NA 2 ¼ X ½ X 3 ⅙ X ⅓ X 4 ⅛ X ¼ X ROUND PROBE

Project Name 

Engineer 

Contractor 

SCHEDULE ATTACHED 

Item #   Tag ID 

Probe Length  Adj. Side Length  Internal Insula on 

BASE MODEL 

GTC116‐P  

GTM116‐P 

GTL116‐P 

GTD116‐P 

Other ______________ 

PROBES & SENSOR NODES 

P+ Density (see density table, next 

page) 

Custom  Probes: ___ 

  Nodes/Probe: ___ 

Custom meets or exceeds P+ density 

AVERAGING 

Airflow: Independent, arithme c aver‐

age 

Temperature: Independent, field se‐

lectable, velocity weighted (default) or 

arithme c average 

LISTINGS 

UL 873 

BTL (GTC116 and GTM116) 

CE (European shipments only) 

Other __________________________ 

INDIVIDUAL SENSING NODES 

HOUSING   Glass‐filled polypropylene (std.) 

Solid Kynar (/SS op on) 

THERMISTORS  Self‐heated sensor: Herme cally‐sealed bead‐in‐glass 

thermistor probe 

Temperature sensor: Herme cally‐sealed bead‐in‐glass 

thermistor probe 

INTERNAL WIRING  Kynar coated copper 

AIRFLOW MEASUREMENT  Accuracy: ±2% of reading 

Calibrated range: 0 to 5,000 fpm 

Calibra on points: 16 

NIST‐traceable calibra on 

TEMPERATURE 

MEASUREMENT 

Accuracy: ±0.15⁰F 

Calibrated range: ‐20 to 160⁰F 

Calibra on points: 3 

NIST‐traceable calibra on 

PROBE ENVIRONMENTAL LIMITS 

TEMPERATURE  

Probe  ‐20  to 160⁰F 

Transmi er  ‐20  to 120⁰F 

Probe  0 to 100% 

Transmi er  5 to 95% 

HUMIDITY (non‐condensing) 

Refer to a ached SCHEDULE for table details if  bu on is checked in any of the tables 

Advantage 3

High-performance Airflow Measurement with Temperature & Alarm Capability SUBMITTAL DATA

®

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

GTx116-P+ GOLD SERIES 

I‐P Units 

Page 2: with Temperature & Alarm Capability SUBMITTAL DATA · 2019-11-08 · RECTANGULAR PROBE POSITIONING IN DUCT # of Probes a b 1 ½ X NA 2 ¼ X ½ X 3 ⅙ X ⅓ X 4 ⅛ X ¼ X ROUND PROBE

RECTANGULAR PROBE POSITIONING IN DUCT 

 

# of 

Probes a  b 

1  ½ X  NA 

2  ¼ X  ½ X 

3  ⅙ X  ⅓ X 

4  ⅛ X  ¼ X 

ROUND PROBE POSITIONING IN DUCT 

 # of 

Probes a 

1  NA 

2  90⁰ 

3  60⁰ 

4  45⁰ 

b = distance from probe 1 to 2, 2 to 3 and 3 to 4 

a = angle from probe 1 to 2, 2 to 3 and 3 to 4 

Note: # probes=2 shown for illustra on

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

P+ SENSOR DENSITY TABLE (# Probes/# Sensor nodes per probe) 

  

Probe Length (inches) 

 

 

 

10 

 

12 

 

14 

 

16 

 

18 

 

20 

 

22 

 

24 

 

30 

 

36 

 

42 

 

48 

 

54 

 

60 

 

66 

 

72 

 

84 

 

96 

 

108 

 

120 

Round    1/1  1/1  1/1  1/2  2/2  2/2  2/2  2/4  2/4  2/4  2/4  2/4  2/6  2/8  2/8  2/8  2/8  4/4  4/4  4/4  4/4  4/4 

Flat Oval   All flat ovals are custom.  Contact EBTRON or your representative for information on flat ovals. 

Square/R

ectangle  A

djacen

t Side Len

gth (in

ches)  

6  1/1  1/1  1/1  1/1  1/2  1/2  1/2  1/2  1/2  1/2  1/4  1/4  1/4  1/4  1/6  1/6  1/6  1/6  1/6  1/6  1/8  1/8 

8  1/1  1/1  1/1  1/2  1/2  1/2  1/2  1/4  1/4  1/4  1/4  1/4  1/6  1/6  1/6  1/6  1/6  1/6  1/8  1/8  1/8  1/8 

10  1/1  1/1  1/1  1/2  1/2  1/3  1/4  1/4  1/4  1/4  1/6  1/6  1/6  1/6  1/6  1/8  1/8  1/8  1/8  1/8  1/8  2/6 

12  1/1  1/1  1/1  1/2  1/3  1/3  1/4  1/4  1/4  1/4  1/6  1/6  1/6  1/6  1/8  1/8  1/8  1/8  1/8  1/8  2/6  2/6 

14  2/1  2/1  2/1  2/2  2/2  2/2  2/2  2/2  2/3  2/3  1/6  1/6  1/8  1/8  1/8  1/8  1/8  1/8  2/6  2/6  2/6  2/6 

16  2/1  2/1  3/1  2/2  2/2  2/2  2/2  2/3  2/3  2/3  1/6  1/6  1/8  1/8  1/8  1/8  1/8  1/8  2/6  2/6  2/6  2/7 

18  2/1  2/1  3/1  2/2  2/2  2/2  2/3  2/3  2/3  2/3  1/6  1/8  1/8  1/8  1/8  1/8  2/6  2/6  2/6  2/6  2/7  2/8 

20  2/1  3/1  3/1  2/2  2/2  2/3  2/3  2/3  2/3  2/3  2/4  1/8  1/8  1/8  1/8  2/6  2/6  2/6  2/6  2/7  2/8  2/8 

22  2/1  3/1  3/1  2/2  3/2  2/3  2/3  2/3  2/3  2/3  2/4  1/8  1/8  1/8  2/6  2/6  2/6  2/6  2/7  2/8  2/8  2/8 

24  2/1  4/1  4/1  2/2  3/2  2/3  2/3  2/3  2/3  2/3  2/4  2/4  1/8  1/8  2/6  2/6  2/6  2/6  2/7  2/8  2/8  2/8 

30  4/1  4/1  4/1  3/2  3/2  3/2  3/2  2/4  2/4  2/4  2/4  2/4  2/6  2/6  2/6  2/7  2/7  2/8  2/8  2/8  2/8  2/8 

36  4/1  4/1  4/1  3/2  3/2  3/2  4/2  4/2  4/2  2/4  2/4  2/6  2/6  2/6  2/7  2/8  2/8  2/8  2/8  2/8  2/8  2/8 

42  4/1  4/1  4/1  3/2  4/2  4/2  4/2  4/2  4/2  4/2  2/6  2/6  2/7  2/7  2/8  2/8  2/8  2/8  2/8  2/8  2/8  2/8 

48  4/1  4/1  4/1  3/2  4/2  4/2  4/2  4/2  4/2  4/2  3/4  2/6  2/7  2/8  2/8  2/8  2/8  2/8  2/8  2/8  2/8  2/8 

54  4/1  4/1  4/1  4/2  4/2  4/2  4/2  4/2  3/4  3/4  3/4  2/7  2/8  2/8  2/8  2/8  2/8  4/4  2/8  2/8  2/8  2/8 

60  4/1  4/1  4/1  4/2  4/2  4/2  4/2  3/4  3/4  3/4  4/4  4/4  2/8  2/8  2/8  4/4  4/4  4/4  4/4  2/8  2/8  2/8 

66  4/1  4/1  4/1  4/2  4/2  4/2  3/4  3/4  3/4  3/4  4/4  4/4  4/4  2/8  2/8  4/4  4/4  4/4  4/4  4/4  2/8  2/8 

72  4/1  4/1  4/1  4/2  4/2  4/2  3/4  3/4  3/4  3/4  4/4  4/4  4/4  2/8  4/4  4/4  4/4  4/4  4/4  4/4  4/4  2/8 

84  4/1  4/1  4/1  4/2  4/3  4/3  3/4  3/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4 

96  4/1  4/1  4/1  4/2  4/3  4/3  3/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4 

108  4/1  4/1  4/1  4/2  4/3  4/3  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4 

120  4/1  4/1  4/1  4/2  4/3  4/3  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4  4/4 

Probe 1

Probe(s) 2 to 4

Inside edge of duct

(including insulation)

a

b

Probe Length

Probe(s) 2 to 4

a⁰ 

IMPORTANT NOTES REGARDING SENSOR DENSITY 

1.  Items in RED do not meet guide spec sensor density due to manufacturing limita ons. 

2.  Items in GREEN meet sensor density requirements but do not match guide spec aspect ra o requirements for the number of probes. 

3.  UNDERLINED items cannot be manufactured as internal mount due to manufacturing limita ons. 

Page 3: with Temperature & Alarm Capability SUBMITTAL DATA · 2019-11-08 · RECTANGULAR PROBE POSITIONING IN DUCT # of Probes a b 1 ½ X NA 2 ¼ X ½ X 3 ⅙ X ⅓ X 4 ⅛ X ¼ X ROUND PROBE

PROBE MOUNTING STYLE 

INTERNAL ‐ 304 stainless steel brackets  

INSERTION ‐ 304 stainless steel brackets 

STAND‐OFF ‐ 304 stainless steel brackets 

Probes < 18 in. are ¼ in. undersized and do not have a terminal stud 

Overall tube length is 2 in. > ordered probe length 

PROBE TUBE MATERIAL 

Stand‐

ard 

Gold anodized 6063 alumi‐

num (1.1” dia.) 

/SS 

op on 

316 stainless steel (1.125” 

dia.) 

10  . (std.)  30  . 

15  .  40  . 

20  .  50  . (max.) 

25  .  Custom ____  . 

CABLE LENGTH 

CABLE TYPE 

FEP Plenum Rated (std.) 

Other __________________________ 

CONNECTOR PLUG DIMENSIONS 

 

TRANSMITTER 

GTC116   Two isolated analog output signals (field selectable/scalable 0‐

5/0‐10 VDC or 4‐20mA) plus one isolated RS‐485 network con‐

nec on (field selectable BACnet MS/TP or Modbus RTU) 

GTM116  Two isolated analog output signals (field selectable/scalable 0‐

5/0‐10 VDC or 4‐20mA) plus one isolated Ethernet network 

connec on (simultaneously supported BACnet Ethernet, BAC‐

net IP, Modbus TCP or TCP/IP) 

GTL116  One isolated Lonworks Free Topology network connec on 

GTD116  One USB connec on for thumb drive data‐logging of sensor 

airflow and temperature over specified  me intervals 

EB‐Link (/EL opt.)  Interface for handheld EB‐Link Reader (provided separately) 

TRANSMITTER CONNECTOR PLATE 

# OF PROBES  1  2  3  4 

MAX. SENS/PROBE  8 

TYPE  A  B 

RECEPTACLES  2  4 

CONNECTORS & INTERCONNECTS 

Gold plated plug/receptacle pins 

Gold plated PCB edge card fingers 

Gold plated PCB interconnects 

ENIG plated printed circuit boards 24 VAC TRANSFORMER SELECTION  

2  4  6  8  10  12  14  16 

13 VA  14 VA  15 VA  16 VA  17 VA  18 VA  19 VA  20 VA 

TOTAL SENSORS 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com

Page 4: with Temperature & Alarm Capability SUBMITTAL DATA · 2019-11-08 · RECTANGULAR PROBE POSITIONING IN DUCT # of Probes a b 1 ½ X NA 2 ¼ X ½ X 3 ⅙ X ⅓ X 4 ⅛ X ¼ X ROUND PROBE

GTx116-P+_Subm

ittalData_r2a

MAIN CIRCUIT BOARD CONNECTIONS 

 ①

❹ 

❺ ANALOG OUTPUT  

CONNECTIONS 

GTC116‐P 

GTM116‐P 

+  Common 

Airflow  ①  ③ 

Temperature 

or Alarm  ②  ③ 

Models  

 

24 VAC POWER CONNECTIONS 

ALL 

L2 (gnd.)  L1 (hot) 

24 VAC  ❹  ❺ 

Models 

 

OUTPUT CARD 

NETWORK CONNECTIONS 

GTL116‐P 

Net +  Net ‐ 

Lon Free Top.  ①  ② 

Models 

 

OUTPUT CARD CONNECTIONS 

 

 

NETWORK CONNECTIONS 

GTC116‐P 

Net +  Net ‐ 

RS‐485  ①  ② 

Models 

Net 

Com 

③ 

 

NETWORK CONNECTIONS 

Models   GTM116‐P 

Ethernet  ① RJ‐45 (10/100) 

① 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com