Wiring & Protection

Embed Size (px)

Citation preview

  • 7/30/2019 Wiring & Protection

    1/204 home power 147 february & march 2012

    Chapter 2 of the National Electrical CodeWiring and

    Protectionis lengthy and important, covering a number of

    topics. PV installers must appropriately apply those sections

    that pertain to PV systems.

    Conductor IdentificationChapter 2 starts with Article 200, Use and Identification ofGrounded Conductors. Many in the PV industry refer to

    the DC conductors from the PV modules as positive and

    negative, but that nomenclature is of less importance in

    modern systems.

    In the majority of PV systems installed today, the inverters

    use an isolation transformer. For PV systems using these

    inverters, the NEC requires bonding one of the current-

    carrying conductors on the PV side of the inverter to

    ground. Typically, this is accomplished across the ground-

    fault protection device located in the inverterbonding the

    negative conductor to ground creates a negatively groundedsystem. Some PV systems require bonding the positive

    conductor to ground. (Note that nearly all PV modules can

    be positively grounded.) To top off that variability, there are

    now ungrounded inverters, in which neither PV conductor

    is bonded to ground. These systems are covered in Section

    690.35, Ungrounded Photovoltaic Power Systems.

    Given the different wiring configurations, its most

    accurate to refer to the conductors in terms of grounded

    current-carrying; ungrounded current-carrying; and

    grounding conductors rather than negative, positive,

    and ground conductors. This terminology also helps clarify

    how each of these conductors should be identified, which

    brings us back to Article 200, which sets the requirements for

    identifying the grounded current-carrying conductors for all

    electrical systems, including PV systems.

    Section 200.6 details those identification methods.

    Subsection 200.6(A) deals with identifying conductors

    that are 6 AWG and smaller. In residential grid-tied PV

    systems, it is likely that all the conductors used will fall into

    this size category. Section 200.6(A) lists eight appropriate

    identification methods, one of which is specific to PV systems

    (discussed later). The first three methods and the PV-specific

    requirement are the most commonly used. The grounded

    current-carrying conductors can either be white, gray, or

    marked with three continuous white stripes on top of any

    color insulation other than green, which is reserved solely for

    grounding conductors.

    Given those requirements, for most PV systems the

    negative is the grounded conductor and should follow one

    of those identification methods. If the positive conductor is

    the grounded conductor, it will follow those rules. And forungrounded systems, neither conductor is marked that way.

    Now that you have identified the grounded current-

    carrying conductor(s), you can identify and mark the

    ungrounded current-carrying conductor(s). These can be any

    color other than those listed in 200.6not white, gray, or

    with three continuous white stripes; nor green or green with

    yellow stripes. In the case of negative-grounded PV systems, I

    recommend that the ungrounded color be red. This will meet

    Code and helps identify the positive polarity of the conductor.

    Regardless of the chosen color-coding, I also recommend

    using marking tape at the termination to identify the polarity

    of all of the conductors.It is important to cover the marking allowance specific

    to PV systems200.6(A)(6) allows the installer to mark

    small PV source circuit with distinctive white markings at all

    terminations. This is an exception to the general rule for small

    conductors, so you may need to bring this to an inspectors

    attention. The exposed USE-2 or PV cable can be black and

    marked at the terminations made inside junction or combiner

    boxes. Just remember that once you transition to an interior

    wire such as THWN-2, that conductor type is outside the

    scope of this allowance and must meet one of the other

    requirements listed.

    For conductors 4 AWG and larger, 200.6(B) outlines the

    rules you are required to follow. The first three methods are

    identical as the requirement for small conductors. The fourth

    method allows for distinctive white or gray markings that

    encircle the conductor at the termination point.

    Overcurrent ProtectionArticle 240, Overcurrent Protection, sets the rules on how to

    properly select, locate, and enclose overcurrent protection

    devices (OCPDs) to protect conductors from overload, short-

    circuit, and ground-fault conditions. Section 240.4 contains

    some critical information on the required methods to

    properly protect conductors. Conductors must be protected

    against overcurrent in accordance with the conductors

    codecornerrenewable energy and the national electrical code

    Wiring & Protectionby Ryan Mayfield

  • 7/30/2019 Wiring & Protection

    2/210www.homepower.com

    ampacity values (as listed in Section 310.15), unless otherwise

    required or allowed within 240.4(A) through (G). In general,

    a conductor needs overcurrent protection at a value less than

    or equal to the conductors ability to carry current.

    A general rule is often followed up with specific cases

    and/or exceptions. In 240.4(B), an allowance is made forovercurrent devices rated at 800 A or less. When specific

    conditions are met, a conductor can be protected by an

    overcurrent device with an ampere rating greater than the

    conductor. The next higher standard-rated device can be used

    to protect the conductor if the conductors ampacity doesnt

    correspond to a standard OCPD ampere rating, the next

    standard OCPD doesnt exceed 800 A, and the conductors

    being protected are not part of a branch circuit supplying

    multiple receptacles. For PV systems, once you adjust a

    conductors ampacity for conditions of use and continuous

    duty, that conductor can be placed on an overcurrent device

    with a rating greater than the conductor. For example, letssay you are using a 10 AWG conductor to connect a string of

    modules to an inverter. After applying correction factors if

    that 10 AWG conductor has an ampacity value of 21 A, you

    can use a 25 A OCPD.

    Section 240.4(D) lists special requirements for small

    conductors, namely the limitations of OCPD ampere ratings

    based on the conductor size. So, unless specifically allowed in

    240.4(E) or (G), the OCPD protecting small copper conductors

    cannot exceed:

    15 A for 14 AWG Copper

    20 A for 12 AWG Copper 30 A for 10 AWG Copper

    When sizing conductors, you may have a scenario where

    one of the above listed conductors must be protected by an

    OCPD with a smaller rating than the conductors ampacity.

    The 240.4(D) section simply defines the maximum OCPD

    rating, even if the conductors ampacity exceeds the OCPD

    rating. For example, after correction factors are applied, a 10

    AWG conductor may have an ampacity value of 35 A. The

    Code requires that this conductor is protected by an OCPD

    with a maximum ampere rating of 30 A.

    Article 240.6(A) lists standard OCPD ratings, the values

    referenced when determining the proper OCPD for protecting

    conductors. The standard values start at 15 A and go up to 6,000

    A. Per 690.9(C), for OCPDs protecting PV source circuits, the

    standard ratings are 1 A to 15 A in 1 A increments. After that,

    the standard values listed in 240.6 are applicable. Practical

    examples of this selection process, as well as conductor sizing

    will be covered in an upcoming Code Corner.

    Section 240.24 covers the location and accessibility

    requirements for OCPDs. Generally, all OCPDs must be

    readily accessible and the center of the grip on the OCPDs

    operating handle may not exceed 6 feet 7 inches above

    the working platform when in its highest position. Two

    allowances to this rule may apply to a PV installation. One

    is that OCPDs may be accessed by portable means, such as

    ladders, if the OCPDs are mounted adjacent to the equipment

    they are protecting. The other is not an exception listed in 240

    but rather an allowance in 690. In 690.9(C), the Code allows

    the OCPDs protecting PV source circuits to be accessible,

    but doesnt require that they be readily accessible (per NECdefinition of readily accessibleagain we see that it is

    acceptable to access particular OCPDs via a ladder and so

    forth).

    Section 240.24 specifies that OCPDs be located where

    they are not exposed to potential physical damage. This may

    require protecting the OCPDs with barriers (for example,

    bollards may be used to prevent potential damage to OCPDs

    by vehicular traffic). Section 240.24(D) prohibits locating

    OCPDs in the vicinity of easily ignitable material, such as

    in clothes closets. And finally, OCPDs are not allowed in

    bathrooms [240.24(E)] or over steps [240.24(F)].

    Part III of Article 240, which covers enclosures forOCPDs, affects many PV installations, and Section 240.32 is

    of particular importance. If the OCPDs are located outside,

    youll need to verify that the enclosure used to house the

    OCPD complies with 312.2, as referenced in 240.32. This is to

    prevent moisture from entering and accumulating within the

    enclosure. Article 312.2 has requirements for raceways and

    cables entering the enclosure, stating that if an enclosure is

    being entered above uninsulated live parts, the fittings used

    to enter the box must be listed for wet locations. Thankfully,

    PV installers have multiple options for enclosures listed for

    various applications. For enclosures that will be mounted

    on an outdoor vertical surface, you can use NEMA 3R-ratedenclosures. Some manufacturers of NEMA 3R enclosures

    have listed their products for installation on a tilted surface;

    this should be verified on a per-model basis. Typically, for

    enclosures mounted in a non-vertical orientation, a NEMA

    4 enclosure should be used (see NEC table 110.28 for more

    information on enclosure types).

    Setting up Your InstallationThese two Code articles, 200 and 240, set the foundation for PV

    installations. Be sure to read through to the end of Article 240,

    as it covers the various types of OCPDs. As with nearly all of

    the Code, I suggest you read and re-read these articles. Youd

    be surprised how often something new jumps out at you and

    changes your thinking.