Webinars DL Protection System Device 40 Device 78 06302010

Embed Size (px)

Citation preview

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    1/56

    Power Plant and Transmission SystemPower Plant and Transmission SystemProtect on Coor nat onProtect on Coor nat on

    LossLoss--of of--Field (40) and OutField (40) and Out--of of--Step Protection (78)Step Protection (78)

    NERC Protection Coordination Webinar Series

    June 30, 2010

    Dr. Murty V.V.S. Yalla

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    2/56

    DisclaimerDisclaimer2

    The information from this webcast is provided forn orma ona purposes on y. n en y s a erence o e

    examples contained within this presentation does notconstitute compliance with the NERC Compliance Monitoringand Enforcement Pro ram "CMEP" re uirements NERCReliability Standards, or any other NERC rules. While theinformation included in this material may provide some of the

    methodology that NERC may use to assess compliance with,

    should not be treated as a substitute for the ReliabilityStandard or viewed as additional Reliability Standardrequirements. In all cases, the entity should rely on the

    anguage con a ne n e e a y an ar se , an noon the language contained in this presentation, to determinecompliance with the NERC Reliability Standards.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    3/56

    3

     Agenda Agenda

    Technical Reference Document Overview

    Objectives

    Descri tion of Protection Functions

    Stability Fundamentals and Examples

     Conditions that Would Cause Operation of TheseFunctions

    Detailed Coordination Information• Function 40 – Loss-of-Field (a.k.a. Loss-of-Excitation)

    •   – - -

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    4/56

    4

     Agenda Agenda

     

    • Settings that Protect the Generator 

    • r ca ear ng me

    • Worst Case Survivable Condition• Sufficient Studies

    Question and Answer 

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    5/56

    5

    Technical Reference Document OverviewTechnical Reference Document Overview

     – 

    Recommendation TR-22

    • ’

    The Need for this Technical Reference-

    •  August 14, 2003 Blackout

    • Subsequent Events

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    6/56

    6

    Technical Reference Document OverviewTechnical Reference Document Overview

     

    Benefits of Coordination:

    • To the Generator Owner 

    • To the Transmission Owner 

    • To the Planning Coordinator 

     

    Delivery to the Customer 

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    7/56

    7

    ObjectiveObjective

     

    generator protection for Loss-of-Field andOut-of-Step.

    Facilitate improved coordination between

    ower lant and transmission s stem

    protection for these specific protection

    functions.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    8/56

    8

    ScopeScope

     

    System.

     

    applicable to all generators, but concentrates on

    s nchronous enerators connected at 100-kV

    and above.

     to distribution systems are outside the scope of

    this document.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    9/56

    9

    The Need for LossThe Need for Loss--of of--FieldField

    ProtectionProtection – – Function 40Function 40

    “The source of excitation for a generator may be

    completely or partially removed through such incidentsas accidental tripping of a field breaker, field open circuit,field short circuit flashover of the sli rin s , volta eregulation system failure, or the loss of supply to theexcitation system. Whatever the cause, a loss ofexcitation ma resent serious o eratin conditions forboth the generator and the system.

    When a generator loses its excitation, it overspeeds and

    opera es as an n uc on genera or. con nues osupply some power to the system and receives itsexcitation from the system in the form of vars.”

    IEEE C37.102-2006 – Guide for ACGenerator Protection, Section 4.5.1

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    10/56

    10

    The Need for LossThe Need for Loss--of of--FieldField

    ProtectionProtection – – Function 40Function 40

     

    •  Accidental tripping of a field breaker.

    • e open c rcu or e s or c rcu as over o e

    slip rings).

      ,

    supply to the excitation system.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    11/56

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    12/56

    12

    The Need for LossThe Need for Loss--of of--FieldField

    ProtectionProtection – – Function 40Function 40

     

    •  A loss of field condition causes devastating impact on

    the ower s stem due to loss of reactive ower

    support from the generator.

    • Creates a substantial reactive power drain from thesystem.

    • On large generators this condition can contribute to or

    trigger a wide area system voltage collapse

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    13/56

    13

    The Need for LossThe Need for Loss--of of--SynchronismSynchronism

    ProtectionProtection – – Function 78Function 78

    “The protection normally applied in the generator zone, such as differential, - , .,

    synchronism. The loss-of-field relay may provide some degree of protectionbut cannot be relied on to detect generator loss of synchronism under allsystem conditions. Therefore, if during a loss of synchronism the electricalcenter is located in the re ion from the hi h-volta e terminals of the GSUtransformer down into the generator, separate out-of-step relaying shouldbe provided to protect the machine. This is generally required for largermachines that are connected to EHV systems.

    On lar e machines the swin travels throu h either the enerator or the main transformer. This protection may also be required even if the electricalcenter is out in the system and the system relaying is slow or cannot detecta loss of synchronism. Transmission line pilot-wire relaying, current-differential relaying, or phase comparison relaying will not detect a loss of

    sync ron sm. or genera ors connec e o ower vo age sys ems,overcurrent relaying may not be sensitive enough to operate on loss ofsynchronism.”

    IEEE C37.102-2006 – Guide for ACGenerator Protection, Section 4.5.3.1

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    14/56

    14

    The Need for LossThe Need for Loss--of of--SynchronismSynchronism

    ProtectionProtection – – Function 78Function 78

    During an out-of-step or pole slip condition the voltagemagn u e e ween e genera or an e sys em

    reaches two per unit (at 180 degrees) which can result inhigh currents that cause mechanical forces in the

    torques.

    It is possible for the resulting torques to be of sufficientmagn u e so a ey cause ser ous amage o eshaft and to the turbine blades.

    It can cause excessive overheatin and shortin at the

    ends of the stator core.

    It can also cause damaging transient forces in the.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    15/56

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    16/56

    16

    Stability FundamentalsStability Fundamentals

    Power System Stability - “If the oscillatory response of a power

    damped and the system settles in a finite time to a new steadyoperating condition we say the system is stable. If the system is notstable, it is considered unstable.”

    Stability is a property of an electrical power system which has two ormore synchronous machines. A system is stable for a specific set of

    conditions if all synchronous machines remain in step with each

    for another.

    Transient Stability

      –Minus Electrical Torque

    Ta = Tm - Te Newton Meters

    qua rea r er on

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    17/56

    Equal Area Method toEqual Area Method to

    Determine StabilitDetermine Stabilit

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    18/56

    18

    Stability Study ExamplesStability Study Examples

    This group of protective functions (Function 40 and 78) needs

    to be validated against transient stability studies to insure that

    Sample apparent impedance swings are

    presented in this figure for a dual lens

    - -

    r pp ng oes no occur or s a e mpe ance sw ngs.

      .

    the time interval between markers is 100 ms

    (6 cycles) such that the faster swings have

    greater distance between markers. The

    three traces represent marginally stable and

    unstable swings for fault clearing at and just

    beyond the critical clearing time, and a trace

    for the worst credible contingency

    representing the fastest unstable swing

       Marginally Stable Swing

       Marginally Unstable Swing

       Worst Case (Fastest) Unstable

    Swing

    Notes: Time between markers (◄)

    is 100 ms

    Scale is apparent impedance

    in secondary ohms

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    19/56

    19

    System Events that Could Cause UndesiredSystem Events that Could Cause Undesired

    Operation of These Protection FunctionsOperation of These Protection Functions

     

    Loss of Critical Lines

    Loss of Critical Units

    Events such as Au ust 14 2003 Blackout

    System Islanding Conditions

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    20/56

    20

    General Data Exchange RequirementsGeneral Data Exchange Requirements – –

    Generator Owner Data and InformationGenerator Owner Data and Information

    The following general information must be exchanged in addition to,

    • Relay scheme descriptions

    • Generator off nominal frequency operating limits

    • CT and VT/CCVT configurations

    • Main transformer connection configuration

    • Main transformer tap position(s) and impedance (positive and zerosequence) and neutral grounding impedances

    • High voltage transmission line impedances (positive and zerosequence) and mutual coupled impedances (zero sequence)

    •   u u uinclude direct and quadrature axis, negative and zero sequenceimpedances and their associated time constants)

    • Documentation showing the function of all protective elements listeda ove

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    21/56

    21

    General Data Exchange RequirementsGeneral Data Exchange Requirements – –

    Transmission or Distribution Owner Data and InformationTransmission or Distribution Owner Data and Information

    The following general information must be exchanged in addition to,

    • Relay scheme descriptions

    • Regional Reliability Organization’s off-nominal frequency plan

    • CT and VT/CCVT configurations

    •  Any transformer connection configuration with transformer tap

    position(s) and impedance (positive and zero sequence) and neutral

    • High voltage transmission line impedances (positive and zerosequence) and mutual coupled impedances (zero sequence)

    • Documentation showin the function of all rotective elements

    • Results of fault study or short circuit model

    • Results of stability study

    -

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    22/56

    22

    Detailed Coordination InformationDetailed Coordination Information

    for Functions 40 and 78for Functions 40 and 78

     

    under seven headings, as appropriate, for eachfunction in the document.

    The following slides present a section-by-section

    summar for Functions 40 and 78.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    23/56

    23

    Document FormatDocument Format – – Seven SubSeven Sub--SectionsSections

    for Each Protection Functionfor Each Protection Function Purpose

    Coordination of Generator and Transmission S stem

    • Faults

    • Loadability

    • Other Conditions, where a licable

    Considerations and Issues

    Coordination Procedure

    •  

    • Setting Considerations

    Examples

    •  

    • Improper Coordination

    Summary of Detailed Data Required for Coordination of the ProtectionFunction

    Table of Data and Information that must be Exchanged

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    24/56

    24

    LossLoss--of of--FieldField – – Function 40Function 40

    Purpose

    • Detect and prevent unsafe and damaging operation of thegenerator during loss-o -excitation events.

    Loss of Field protection

    characteristic on the R-X diagram

    Figure 3.5.1 — (1) Locus of Swing Impedance during Light and Heavy Loads for Loss-of-Field, and

    (2) Relationship between Minimum Excitation Limiter (MEL) or Under Excitation Limiter (UEL)

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    25/56

    25

    Coordination of Generator andCoordination of Generator andTransmission SystemTransmission System – – Function 40Function 40

    Faults

    • Step 1 — The Transmission Owner provides the Planning Coordinator with the

    generator bus.

    • Step 2 — The Planning Coordinator determines the stability impedance trajectoryfor the above conditions.

    •   —Owner.

    The Generator Owner utilizes these plots to demonstrate that these impedance

    trajectories coordinate with the time delay setting of the loss-of-field (LOF) relay toprevent misoperations by having adequate time delay.

    •  A system stability study may be required to evaluate the generator and systemresponse to power system faults.

    The response of the LOF relays under these conditions must be studied to see if theyrespond to power swing conditions as a result of system faults.

    The Transmission Owner, Generator Owner, and Planning Coordinator must shareinformation on these studies and LOF relay settings to prevent inadvertent tripping ofgenerators for external fault conditions not related to a loss-of-field condition.

    If there is an out-of-step protection installed it should be coordinated with the LOFrotection.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    26/56

    26

    Coordination of Generator andCoordination of Generator andTransmission SystemTransmission System – – Function 40Function 40

    Loadability

    • Step 1 — The Generator Owners confirms that the LOF relay setting coordinateswith the generator reactive capability and the excitation system capability toensure that the LOF relay does not restrict operation of the generating unit.

    • Step 2 — A light load system study is completed in which the generator is takingin vars.

     A sufficient number of o eratin conditions and s stem contin encies are evaluated toidentify the worst case operating condition for coordination with the LOF relay setting.

    The output of this study is provided to the Generator Owner to evaluate whether theworst case operating load condition(s) lies outside the LOF characteristic.

    • Step 3 — For any case where the operating load point lies within a properly setc arac er s c a mu ua y agree upon so u on mus e app e , .e., s un

    reactor, turning off capacitor banks in the area, etc).

    Where the solution requires real-time action by an operator the solution is incorporatedinto a system operating procedure.

    •   , ,Coordinators is necessary to prevent loadability considerations from restrictingsystem operations.

    This is typically not a problem when the generator is supplying VARs because the LOFcharacteristics are set to operate in third and fourth quadrant.

    However, when the generator is taking in VARs due to light load and line chargingconditions, or failure of a transmission capacitor bank to open due to control failure,

    loss-of-field relays can misoperate if the apparent impedance enters the relaycharacteristic in the fourth quadrant.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    27/56

    27

    Considerations and IssuesConsiderations and Issues – – Function 40Function 40

    The LOF relay settings must be provided to the Planning

    Coordinator can determine if any stable swings encroach longenough in the LOF relay trip zone to cause an inadvertent trip.

     that power system modifications do not result in stable swingsentering the trip zone(s) of the LOF relay causing an inadvertent trip.

    If permanent modifications to the power system cause the stablesw ng mpe ance tra ectory to enter t e c aracter st c, t en t ePlanning Coordinator must notify the Generator Owner that newLOF relay settings are required.

    impedance trajectory so that the new LOF settings willaccommodate stable swings with adequate time delay. The newsettings must be provided to the Planning Coordinator from the

    .

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    28/56

    28

    Coordination Considerations – – Function 40Function 40

     

    controls are such that the loss-of-field relay mustnot operate before the UEL limit (with a margin)

    is reached.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    29/56

    29

    ExampleExample -- Proper CoordinationProper Coordination

     – – Function 40Function 40 Typical Loss-of-Field Relay Setting Calculation for two zone offset mho characteristic

    (calculations are in transmission system primary ohms).

    Ste -1 — Calculate the Base im edance = 17.56 Ω/ er unit 

    Step-2 — Convert X’d and Xd in per unit to Ohms:

    • 3.61 Ω

    • 20.88 Ω

    Step-3 — Element settings:

    • Offset = (50%) (X’d) = (0.5) (3.61) = 1.8 Ω

    • Z1 = 1 pu = 17.6 Ω

    • Z2 = = 20.88 Ω

    Step-4 — Plot various characteristics as shown in figure 3.5.1

    Step-5 — set the time delays for zone 1 and zone 2 elements.

    • Typical time delay settings are:

    • Zone : . sec

    • Zone 2: 0.5 sec

    System stability studies should be conducted to see if the above time delays are sufficient toprevent inadvertent tripping during stable power swings.

    Figure 3.5.3 illustrates some of these types of swing characteristics that need to be studied.

    Step-6 — Set the undervoltage supervision (if appropriate):

    • V = 85% of = 0.85 x 120V =102 V

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    30/56

    30

    ExampleExample -- Proper CoordinationProper Coordination

     – – Function 40Function 40

    System stability studies should be conducted to ensure the time delay settings

    are sufficient to prevent inadvertent tripping during stable power swings.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    31/56

    31

    Summary of Protection FunctionsSummary of Protection Functions

    Re uired for CoordinationRe uired for Coordination – – Function 40Function 40

    Table 

    Excerpt 

    — Function 

    40 

    Protection 

    Coordination 

    Considerations

    Generator Protection Function  Transmission System Protection 

    System Concerns unc ons

    40  – Loss of  Field (LOF)  Settings used for planning and system 

    studies

      Preventing encroachment on reactive capability curve

      See details from sections 4.5.1 and A.2.1 of  C37.102‐2006

      It is imperative that the LOF function does not operate for stable 

    power swings  – The impedance trajectory of  most units with a 

    lagging power factor (reactive power into the power system) for 

    stable swin s will ass into and back out of the first and second 

    quadrants

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    32/56

    32

    Protection Function Data and InformationProtection Function Data and Information

    Exchan e Re uired for CoordinationExchan e Re uired for Coordination – – Function 40Function 40

    Table 

    Excerpt 

    — Function 

    40 

    Data 

    to 

    be 

    Exchanged 

    Between 

    Entities

     

    Relay settings: loss of  field characteristics, 

    including time delays, at the generator terminals

    Generator reactive capability

    The worst case clearing time for each of  the 

    power system elements connected to the 

    transmission bus at which the generator is 

    connected

    Impedance trajectory from system stability 

    studies for the strongest and weakest available 

    system

    Feedback on problems found in coordination and 

    stability studies

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    33/56

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    34/56

    34

    Loss of SynchronismLoss of Synchronism – – Function 78Function 78

    Fi ures 3.13.1A and 3.13.1B illustrate a sim le

    representation of two (2) systems Es (power system)

    and Eg (a generator) connected through a GSU

    .

    • Figure 3.13.1C shows typical power swing loci which are

    dependent on the ratio of Eg / Es.

    • When Eg is less than Es, which may occur when the generator is

    underexcited, the power swing loci will appear electrically

    “closer” to the enerator than the ower s stem.

    • Due to the variability of the apparent impedance trajectory it is

    desirable to base out-of-step protection settings on transient

    .

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    35/56

    35

    Coordination of Generator andCoordination of Generator and

    Transmission S stemTransmission S stem – – Function 78Function 78

    • There are no coordination issues for system faults forthis function althou h the a arent im edance

    swings for which out-of-step protection must be

    coordinated often occur as the result of system faults.

    Loadability

    • There are no coordination issues related to loadability

    for this function.

    C d f G dC d f G d

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    36/56

    36

    Coordination of Generator andCoordination of Generator and

    Transmission S stemTransmission S stem – – Function 78Function 78 Other Operating Conditions

    •  A generator may pole-slip (out-of-step or loss-of-synchronism), or fallou o sync ron sm w e power sys em or a num er o reasons.The primary causes are:

    Prolonged clearance of a low-impedance fault on the power system.

      .

    Partial or complete loss of excitation.

    • To properly apply this protection function, stability studies must be

    performed. These studies: Require extensive coordination.

    Usually are conducted by the Transmission Planner or Planning Coordinator.

    Should evaluate a wide variety of system contingency conditions.

    • Out-of-step protection Should not be applied unless stability studies indicate that it is needed.

    Should be applied in accordance with the results of those studies.

    Must be reviewed as system conditions change.

    C di ti f G t dC di ti f G t d

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    37/56

    37

    Coordination of Generator andCoordination of Generator andTransmission S stemTransmission S stem – – Function 78Function 78

    Other Operating Conditions (continued)

    • Studies must be used to verify that the out-of-step protection:

    Provides dependable tripping for unstable swings.

    Provides secure operation for stable swings.

    •  

    The marginal condition representing the unstable swing that is closest to astable condition.

    The fastest swin t icall resultin from the most severe s stem condition.

    • Typically the out-of-step settings are developed by:

    Calculating initial settings for blinders, time delay, etc. using a graphicalapproach.

    Refining the settings as necessary based on transient stability simulations.

    • This process requires an exchange of information between theTransmission Owner(s), the Generator Owners(s) and the TransmissionPlanner and/or Planning Coordinator.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    38/56

    38

    Coordination ProcedureCoordination Procedure

    1. Model the overall system and carry outtransient stability runs for representativeoperating conditions. The modeling of the

    XXgenera ors s ou nc u e e vo age regu a or,generator governor and power system stabilizer

    (PSS) if in service.2. Determine values of generator transient

     A B

    D

    XmaxSG1SYSTEM

     A B

    D

    XmaxSG1SYSTEM

      ,(XTG) and system impedance under maximumgeneration (XmaxSG1).

    3. Set the Mho unit to limit the reach to 1.5 timesthe transformer impedance in the system

    P

    M

    R

    1.5 X TG

    TRANSTGX

    O

    P

    M

    R

    1.5 X TG

    TRANSTGX

    O

    direction. In the generator direction the reach istypically set at twice generator transientreactance. Therefore the diameter of the MHOcharacteristic is2 X’d + 1.5 XTG.

    Swing Locus

    ELEMENTMHO

    d

     A B

    2X d́

    GENdX´

    Swing Locus

    ELEMENTMHO

    d

     A B

    2X d́

    GENdX´

    4. Determine by means of the transient stabilityruns, the critical angle δ between the generatorand the system by means of the transientstability simulations. This is the angle

    C

    ELEMENTSBLINDER

    ELEMENT

    PICK-UP

    ELEMENT

    PICK-UPC

    ELEMENTSBLINDER

    ELEMENT

    PICK-UP

    ELEMENT

    PICK-UP

     the critical clearing time.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    39/56

    39

    Coordination Procedure (cont.)Coordination Procedure (cont.)

    5. Determine the blinder distance d, which iscalculated with the following expression:

    XX

     A B

    XmaxSG1SYSTEM

     A B

    XmaxSG1SYSTEM

    .  to travel from the position corresponding to thecritical angle δ to that corresponding to 180°.This time is obtained from the rotor angle vs.

    time curve which is generated by the transientstabilit stud for the most severe transmission

    P

    M

    R

    . TG

    TRANSTGX

    O

    P

    M

    R

    . TG

    TRANSTGX

    O

     fault, when the system experiences the firstslip.

    7. The time delay of the 78 function should be setequal to the value obtained from the transient

    Swing Locus

    ELEMENTMHO

    d

     A B

    2X d́

    GENdX´

    Swing Locus

    ELEMENTMHO

    d

     A B

    2X d́

    GENdX´

    s a y s u y n s ep . s va ue s equa o

    half the time for the apparent impedance totravel between the two blinders and providesadequate margin to permit tripping for fasterswings, while providing security against

    C

    ELEMENTSBLINDER

    ELEMENT

    PICK-UP

    ELEMENT

    PICK-UP C

    ELEMENTSBLINDER

    ELEMENT

    PICK-UP

    ELEMENT

    PICK-UP

    opera on or au con ons.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    40/56

    40

    Determination of Timer SettingDetermination of Timer Setting

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    41/56

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    42/56

    42

    Determination of Timer SettingDetermination of Timer Setting

     

    Rotor Angle Generator G_1Angle (degree)

    200

    220240

    260

    Case1 (tc=90 ms), with controls

    Case2 (tc=180 ms), with controls

    =

    120

    140

    160

    180

      ,

    Case1 (tc=90 ms), without controls

    Case2 (tc=180 ms), without controls

    Case3 (tc=190 ms), without controls

    40

    60

    80

    100

    -40

    -20

    0

    20

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

     

    Figure G-4

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    43/56

    43

    Determination of Timer SettingDetermination of Timer Setting

    Several plots from the transient stability runs can be obtained for a myriad. - -

    information is the Rotor Angle vs. Time and R + j X vs. time.

    From the respective plots it can be observed that:

    • In Case 1 with a clearin time of 90 milliseconds the s stem remains insynchronism.

    • In Case 2, G1 and the system are still in synchronism with a clearing time of 180milliseconds.

    •   , .above it is evident that the critical time to clear the fault is equal to 180 ms afterfault inception.

    The rotor angles for the three cases are shown in Figure G-4, from which it°  .

    swing locus to travel from the critical angle to 180° is approximately 250milliseconds.

    Therefore the time delay setting should be set to 250 milliseconds.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    44/56

    44

    Determination of Timer SettingDetermination of Timer Setting

    R vs. X diagrams for the three cases show the impedance trajectoryseen by the relay during the disturbances. When there is an

    oscillation in the generator which is stable, the swing locus does notcross the impedance line.

    When generator goes out-of-step, the transient swing crosses thesystem impedance line each time a slip is completed and the relayshould trip the generator.

    gure - s ows t e vs. agram or cases , , an .

    • In the first two cases it is clear that the load point does not cross thesystem impedance line.

    • For case 3, the load point crosses the system impedance line indicatingthat the synchronism is lost and therefore out-of-step tripping must beallowed.

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    45/56

    45

    Determination of Timer SettingDetermination of Timer Setting

     

    4.0

    -2.0

    0.0

    .

    -10.0 -8.0 -6.0 -4.0 -2.0 0.0 2.0 4.0 6.0 8.0 10.0

    -6.0

    -4.0

       X   (   O   h  m   )

    -

    -10.0

    -8.0

    -16.0

    -14.0

    .

    R (Ohm)

    G1, tc=90 ms G1, tc=180 ms G1, tc=190 ms Impedance Line

    Figure G-6

    ExampleExample -- Proper CoordinationProper Coordination

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    46/56

    46

    ExampleExample Proper CoordinationProper Coordination – – Function 78Function 78

    ExampleExample -- Proper CoordinationProper Coordination

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    47/56

    47

    ExampleExample Proper CoordinationProper Coordination – – Function 78Function 78

    Check List

    •  calculation should be on the generator voltage base.

    • The GSU transformer reactance (Xt) used in the settingcalculation should be on the enerator volta e base.

    • The reverse reach should be greater than GSU transformerreactance (Xt).

    •  system should be used to set the blinders (as determined by atransient stability study).

    •  A power system stability study should be performed for the relayme e ay se ng.

    [1] Note: Pursuant to C37.102, with regard to setting of the blinder, theang e s e angu ar separa on e ween e genera or an esystem, at which the relay determines instability. If a stability studyis not available, this angle is typically set at 120º.

    ExampleExample -- Proper CoordinationProper Coordination

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    48/56

    48

    ExampleExample Proper CoordinationProper Coordination – – Function 78Function 78

     Assumptions:

    2.26-/phase, 50% of 2.26-

    /phase = 1.13-

    /phase, 145-kV Reverse Reach – = 2.26 -

    Forward Reach – = 2 x 3.61 =7.22-/phase

    Diameter of Mho Element – D =9.48-

    Center of Mho Element – C =(D/2)- = (9.48/2) – 2.26 = 2.48==> - . ,

    Blinders – d1 & d2 = {(X’d + Xt)/2}tan {90˚-(140˚/2)} = {(3.61 +2.3)/2}tan{90˚-(140˚/2)} = 2.955

    ˚ = -

    NOTE: Settings should bevalidated and refined as

    necessary based on transient.   .

    Summary of Protection FunctionsSummary of Protection Functions

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    49/56

    49

    Summary of Protection FunctionsSummary of Protection FunctionsRequired for CoordinationRequired for Coordination – – Function 78Function 78

    Table 

    Excerpt 

    — Function 

    78 

    Protection 

    Coordination 

    Considerations

    Generator Protection Function Transmission S stem Protection Functions S stem Concerns 

      System studies

     are

     required

    78 — Out‐of ‐Step

      nc u ng coor na on o  oc ng an  

    tripping)

    78 (if  applicable)

      Settings should be used for planning and system studies either 

    through explicit modeling of  the function, or through monitoring 

    impedance swings at the relay location in the stability program and 

    applying engineering  judgment

    Protection Function Data and InformationProtection Function Data and Information

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    50/56

    50

    Protection Function Data and InformationProtection Function Data and InformationExchange Required for CoordinationExchange Required for Coordination – – Function 78Function 78

    Table 

    Excerpt 

    — Function 

    78 

    Data 

    to 

    be 

    Exchanged 

    Between 

    Entities

    Generator Owner Transmission Owner Planning Coordinator

    Determine if  there is a need for generator 

    out‐of ‐step protection

    Relay settings, time delays and 

    characteristics for out‐of ‐step tripping and 

    blocking

    Provide relay settings, time delays and 

    characteristics for the out‐of ‐step tripping and 

    blocking if  used

    Determine if  there is a need for 

    transmission line out‐of ‐step 

    tripping/blocking related to the generator

    Feedback on coordination problems found 

    in stability studies.

    Wh t i Impo t nt to Coo din tionWh t i Impo t nt to Coo din tion

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    51/56

    51

    What is Important to CoordinationWhat is Important to Coordination

     

    Critical Clearing Time

    Worst Case Survivable Condition

    Sufficient Studies

    Settings that Protect the GeneratorSettings that Protect the Generator

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    52/56

    52

    Settings that Protect the GeneratorSettings that Protect the Generator

    described in the IEEE Guide for AC GeneratorProtection (C37.102) for both Function 40 and

    78 based on machine and system reactance.

    The time to tri are ad usted based on thespecific generator and application.

     

    presentation, but again, specific settings need tobe determined b the entities.

    Critical Clearing TimeCritical Clearing Time

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    53/56

    53

    Critical Clearing TimeCritical Clearing Time

     

    return to a stable system following a systemdisturbance.

    If fault clearing exceeds the unit critical clearing

    time then the machine will lose s nchronismwith the system and is required to trip.

    Worst Case Survivable ConditionWorst Case Survivable Condition

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    54/56

    54

    Worst Case Survivable ConditionWorst Case Survivable Condition

    The protection must be set to avoid unnecessary tripping for worstcase survivable conditions:

    • Operation of transmission equipment within continuous and emergencythermal and voltage limits

    • Recovery from a stressed system voltage condition for an extremesystem event – i.e. 0.85 pu voltage at the system high side of thegenerator step-up transformer 

    •   w w

    • Transient frequency and voltage conditions for which UFLS and UVLSprograms are designed to permit system recovery

    When coordination cannot be achieved without compromisingprotection of the generator, the generator protection setting must beaccounted for in system studies.

    Sufficient StudiesSufficient Studies

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    55/56

    55

    Sufficient StudiesSufficient Studies

    The Plannin Coordinator must stud a number of

    operating conditions sufficient to bound the worst case.

     Assess sensitivity of generator and system response to:

    • System load level

    • Generator loading (both active and reactive power)• Commitment and dispatch of other generators

    • System operating states (N-0, N-1, . . .)

    The most limiting operating condition may vary amongprotective functions or even for different settings for a

    .

  • 8/20/2019 Webinars DL Protection System Device 40 Device 78 06302010

    56/56

    56

    uestion & Answer

    Contact:

    Phil Tatro, System Analysisand Reliability Initiatives

    [email protected]

    . .