Water Pipe Design Lecture2.pdf

Embed Size (px)

Citation preview

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    1/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    Chilled Water system

    Introduction

    For large installations the Condenser, Evaporator, Compressor and

    Expansion device can be purchased as a package unit, known as a

    Chiller . The usual package consists of electrically driven

    compressor(s) mounted on top of two shell and tube heat exchangers,one for the evaporator and the other for the condenser.

    The cooling coil(s) are piped up to the chiller in the conventionalmanner as shown below.

    In some countries the Cooling tower is the preferred method of

    removing heat from the system.

    Cooling towers that are open to atmosphere are not often used since

    the water may become contaminated.

    A closed cycle cooling tower or evaporative cooler can be used to

    reduce contamination risk.

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    2/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    2

    Chiller Schematic Diagram with Air Cooled Condenser

    Cooling Coil(s)

    Condenser

    Evaporator

    Compressor

    Heat Rejection

    Heat Input

    Expansion

    valve

    1

    23

    4

    Refrigerant Gas

    Refrigerant Liquid

    + Vapour

    -

    Pump

    Control

    Valve

    Chilled

    Water

    flow

    Chilled

    Water

    return

    Fans

    Chiller

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    3/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    3

    Cooling Coil(s)

    Condenser

    Evaporator

    Compressor

    Heat Rejection

    Heat Input

    Expansion

    valve

    1

    23

    4

    Refrigerant Gas

    Refrigerant Liquid

    + Vapour

    -

    Pump

    Control

    Valve

    Chilled

    Water

    flow

    Chilled

    Water

    return

    Chiller

    Cooling Tower

    Condenser Water

    Chiller Schematic Diagram with Cooling Tower

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    4/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    4

    Alternative arrangements are shown for smaller installations where the

    condenser may be mounted on the roof or external wall of a building and

    cooled by outside air.

    The evaporator may be installed directly into the ductwork or air handling unit

    (AHU) for smaller installations.

    This is known as a Direct Expansion (or DX) coil.

    A typical Direct Expansion (or DX) system is shown below.

    This avoids using condenser water and chilled water in the system and

    installing the accompanying plant.

    Direct Expansion Cooling Coil

    also known as DX coil in Air

    Handling Unit (AHU)

    Condenser

    Compresso

    Heat Rejection

    Heat Input

    Expansion

    valve

    1

    23

    4

    Refrigerant

    Gas

    Refrigerant Liquid +

    Vapour

    -

    Refrigerant

    Flow

    Refrigerant

    Return

    FansAir Cooled

    Condenserincorporating

    Compressor(s)

    Direct Expansion (DX) System

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    5/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    5

    Chilled-water System

    In larger buildings and particularly in multi-story buildings, the split-system

    approach begins to run into problems.

    Either running the pipe between the condenser and the air handler exceedsdistance limitations (runs that are too long start to cause lubrication difficultiesin the compressor), or the amount of duct work and the length of ducts becomes

    unmanageable.At this point, it is time to think about a chilled-water system.

    In a chilled-water system, the entire air conditioner is situated on the roof orbehind the building.

    It cools water to between 4.0oC and 8.0

    oC.

    This chilled water is then piped throughout the building and connected to the

    cooling coils in air handlers as needed.There is no practical limit to the length of a chilled-water pipe if it is well-insulated.

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    6/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    6

    Chilled Water Temperatures

    Typically chilled water flow and return temperatures to cooling coils is generallybetween 7

    oC and 12

    oC, depending upon the dew point to be maintained.

    When this water is pumped through the evaporator section of the chiller this water

    temperature will be lowered by about 4oC to 6oC.In order that the necessary heat transfer may take place, the refrigerant must be atsome temperature below that of the leaving water but, at the same time, it must

    generally be slightly above freezing point.

    In a typical case, the following water temperatures may be used:

    Apparatus dew point 12CCooling coil outlet 10C

    Cooling coil inlet 6C

    Water at evaporator outlet 5.5C

    The refrigerant in the evaporator would in this case be maintained at about 1C

    giving a differential for4.5C for heat transfer.As will be appreciated, this small temperature potential means that the coolingsurface of a simple tubular type would need to be very extensive: a variety of

    devices has been developed to augment the transfer rate.

    Ethylene/glycol solutions may be used in cooling coils in order to allow lower airtemperatures to be obtained.

    The temperatures of the fluid circulating may be -7C from the evaporator and -3Creturning to it, or lower as required.

    In instances where cooling for an air-conditioning system is provided from arefrigeration machine by direct expansion, the refrigerant is piped directly tocooling coils in the air stream which thus become the evaporator.

    The surface temperature of the coils is a function of the leaving air temperaturerequired, the form of the coil surface and the velocity of the air flow.Refrigerant temperatures much below freezing point are inadmissible owing to the

    risk of build-up ofice on the coil surface when dehumidification is taking place.An apparatus dew point of3C is normally considered as the practical minimum for

    such coils if frosting is to be avoided.

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    7/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    7

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    8/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    8

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    9/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    9

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    10/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    1

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    11/20

    Pipe Design Lecture No.(2) By Badran M. Salem

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    12/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    2

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    13/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    3

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    14/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    4

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    15/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    5

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    16/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    6

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    17/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    7

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    18/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    8

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    19/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    9

  • 7/29/2019 Water Pipe Design Lecture2.pdf

    20/20

    Pipe Design Lecture No.(2) By Badran M. Salem

    21