Design Standards - Preferred Equipment Lists i
Document Authorisation
Author: Principal Engineer Infrastructure Standards Development
Signed:
Date:
Checked by: Manager Technical Advisory and Standards Signed:
Date:
Approved by: General Manager Asset Management Signed:
Date:
Document Revision Control
Version Description of Revision Person Making Issue Date Approval
1 Initial draft for ACTEW review Denis Baker 11Mar14
2 Revision to accommodate internal review and for workshop with internal stakeholders
Denis Baker 28Apr14
3
Updated, reformatted, and incorporate Sewerage Network and changed to Icon Water.
As amended following review workshop input
Denis Baker, Scott Domars, Mark Hendy, Andrew Brick, Anthony Mayer, Megan Cursley
30Jun15
© Icon Water Ltd. This publication is copyright and contains information that is the property of Icon Water Ltd. It may be reproduced for the purposes of use while engaged on Icon Water commissioned projects.
Disclaimer
This document has been prepared for Icon Water Ltd and is used for its purposes. No warranty is given as to its suitability for any other purpose.
Table of Contents
Purpose ...............................................................................................................................................................................................1
Part A - Water Network Hydraulic Products PEL .............................................................................................................................2
1. Pressure Pipelines - Ductile Iron Pipe ...........................................................................................................................................2
2. Pressure Pipelines - Ductile Iron Fittings .......................................................................................................................................4
3. Pressure Pipelines - PVC Pipes .................................................................................................................................................. 10
4. Pressure Pipelines - Polyethylene Pipe and Fittings .................................................................................................................... 11
5. Valves and Installations - Gate Valves ........................................................................................................................................ 12
6. Valves and Installations - Air Valves ............................................................................................................................................ 13
7. Valves and Installations - Butterfly Valves ................................................................................................................................... 13
8. Valves and Installations - Check Valves ...................................................................................................................................... 14
9. Valves and Installations – Fire Hydrants .................................................................................................................................. 14
10. Valves and Installations - Property Service Connections ......................................................................................................... 15
11. Water Network Maintenance Fittings ........................................................................................................................................ 17
Part B - Sewerage Network Hydraulic Products PEL .................................................................................................................... 19
12. Sewerage Network Pipelines - PVC Pipe and Fittings.............................................................................................................. 19
13. Sewerage Network Pipelines - Vitrified Clay Pipe and Fittings ................................................................................................. 23
14. Sewerage Network Pipelines - Polypropylene Pipe and Fittings .............................................................................................. 24
15. Sewerage Network Pipelines - Ductile Iron Pipe and Fittings ................................................................................................... 25
16. Sewerage Network Pipelines - Glass Reinforced Plastic Pipe and Fittings .............................................................................. 26
17. Sewerage Network Pipelines - Sewer Access Pit Components ............................................................................................... 28
Design Standards - Preferred Equipment Lists iii
Part C – Water and Sewerage Networks - Telemetry Electrical and Instrumentation Products PEL ........................................ 29
18. Water and Sewerage Networks - Telemetry Products .............................................................................................................. 30
19. PLC Equipment ........................................................................................................................................................................ 31
20. Water and Sewerage Networks - Electrical Products ............................................................................................................... 36
21. Water and Sewerage Networks - Instrumentation Products ..................................................................................................... 43
22. Water and Sewerage Networks - Telemetry Electrical and Instrumentation PEL Addendum for Simple Sites ......................... 47
Part D - Water and Sewerage Networks - Mechanical Equipment PEL ........................................................................................ 59
23. Water Network - Pump Sets and Materials Handling ............................................................................................................... 59
24. Sewerage Network - Pump Sets and Materials Handling ......................................................................................................... 59
25. Sewerage Network - Foul Air Fans and Odour Scrubbers........................................................................................................ 59
26. Water and Sewerage Networks - Cranes Ventilation Fans and Generators ............................................................................. 59
Part E – Water and Sewerage Networks – Work at Height PEL .................................................................................................... 60
27. Fall Protection Equipment ........................................................................................................................................................ 60
Design Standards - Preferred Equipment Lists 1
Purpose
The purpose of these Preferred Equipment Lists (PELs) is to identify products that have been accepted by Icon Water for use in the Water and Sewerage Networks and to outline any limitations on their use. These PELs are divided in parts that reflect different engineering disciplines that Icon Water has categorised products into. These PELs form part of the Icon Water Design Standards required by the Water and Sewerage Network (Design and Maintenance) Code made under the Utilities (Technical Regulation) Act 2014 which requires Icon Water Ltd to develop, maintain and implement design standards for the Water Network and the Sewerage Network. The Icon Water PELs form part of the design standards and must be read in conjunction with all of the documents that make up the Icon Water Design Standards for the Water Network and the Sewerage Network including Standard Specifications and Standard Drawings. Additional products may be accepted for use after an assessment of the product’s suitability for use in accordance with the Icon Water Design Standards Products and Materials Acceptance Application Guide. In the absence of specific, proposed products and materials for specific projects being in the PELs, these additional products and materials shall be subject to the acceptance by the Manager Water Assets Planning for the Water Network and the Manager Sewerage Assets Planning for the Sewerage Network. Such acceptances for a specific project will not be considered as a precedent for other projects or for general acceptance by Icon Water.
Design Standards - Preferred Equipment Lists 2
Part A - Water Network Hydraulic Products PEL
1. Pressure Pipelines - Ductile Iron Pipe
WSA PS–200 Ductile Iron Pipe for Water Supply and Sewerage AS 2280 – Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA Appraisal Icon Water Approval
CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010
Nominal
Size Product
Pressure Rating
Limitations on use
DN100 – DN750
Ductile Iron Pressure Pipe Product Codes C302.10, C302.15, C302.2, C302.30, C302.37, C302.45, C302.50, C302.60, C302.75
PN16 DN200 and DN250 not approved for use in the
Water Network
Polyethylene sleeving required for pipes when installed in the ground.
No direct tapping for service connections is permitted.
C301.10 SC, C301.15 SC, C301.22 SC, C301.30 SC, C301.37, C301.45, C301.50, C301.60, C301.75
PN35
Design Standards - Preferred Equipment Lists 3
Supplier Brand Name WSAA Appraisal Icon Water Approval
Pentair TYTONXCEL PA 10/16.2 Issue 2 18/05/2011 PC162
DN100 – DN750
Ductile Iron Pressure Pipe Product Codes D100XCEL35CSC, D150XCEL35CSC, D225XCEL35CSC, D300XCEL35CSC, D375XCEL35CSC, D450XCEL35CSC, D500XCEL35CSC, D600XCEL35CSC, D675XCEL35CSC
PN35
DN200 and DN250 not approved for use in the Water Network
Polyethylene sleeving required for pipes when installed in the ground.
No direct tapping for service connections is permitted.
Design Standards - Preferred Equipment Lists 4
2. Pressure Pipelines - Ductile Iron Fittings
WSA PS–201 Ductile Iron Fittings for Water Supply and Sewerage AS 2280 – Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010
Nominal Size Product Pressure Rating Limitations on use
DN80-DN750 SO-SO Bends 90°, 45°, 22.5°, 11.25° PN35
DN80-DN750 FL-FL Bends 90°, 45°, 22.5°, 11.25° PN16
DN80-DN750 SP-SP Bends 90°, 45°, 22.5°, 11.25° PN16
DN80-DN600 Hydrant, Washout, Duckfoot and Pedestal Bends
PN16
DN100-DN750 SO-SO-SO Tee PN35
DN100-DN750 SO-SO-FL Tee PN16
DN100-DN600 SO-SP-FL Hydrant Tee PN16
DN450-DN750 FL-FL-FL Tee PN16
DN100-DN750 Scour Tee PN16
DN80-DN750 FL-SO Connector PN16
Design Standards - Preferred Equipment Lists 5
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010
Nominal Size Product Pressure Rating Limitations on use
DN80-DN750 FL-SP Connector PN16
DN80-DN750 SO-SO Connector PN16
DN100-DN150 Pretap Connector PN16
DN80-DN100 Hydrant Riser PN16
DN100-DN750 SO-SO Taper PN16
DN100-DN750 SO-FL Taper PN16
DN100-DN750 FL-FL Taper PN16
DN80-DN750 End Cap PN16
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
Pentair Auslite PA 10/16.2 Issue 2 18/05/2011 Bill Bencke 04/12/2006
Nominal Size Product Pressure Rating Limitations on use
DN100-150 SO-SO Bend 90°, 45°, 22.5°, 11.25° PN16
DN100-150 SO-SO-FL Tee PN16
DN100-150 SO-SO-SO Tee PN16
DN100-150 20mm READYTAP FC 4 Tap PN16
Design Standards - Preferred Equipment Lists 6
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
Pentair Auslite PA 10/16.2 Issue 2 18/05/2011 Bill Bencke 04/12/2006
Nominal Size Product Pressure Rating Limitations on use
DN100-150 FL-SO Connector PN16
DN100-150 FL-SP Connector PN16
DN80-DN100 Hydrant Riser PN16
DN100 FL-FL Bend 90° PN16
DN100 SO-FLWash/ Bend 90° PN16
DN80-DN100 SUREFLOW Spring Hydrant PN16
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
Pentair Tyton PA 10/16.2 Issue 2 18/05/2011 PC162
Nominal Size Product Pressure Rating Limitations on use
DN100-DN750 SO-SO Bend 90°, 45°, 22.5°, 11.25° PN16, PN35
DN80-DN750 FL-FL Bend 90°, 45°, 22.5°, 11.25° PN16, PN35
DN100-DN150 FL-SO Washout Bends PN16, PN35
DN100-DN600 FL-FL Duckfoot Bends PN16, PN35
DN225-DN750 SO-SO-SO Tee PN16, PN35
Design Standards - Preferred Equipment Lists 7
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
Pentair Tyton PA 10/16.2 Issue 2 18/05/2011 PC162
Nominal Size Product Pressure Rating Limitations on use
DN225-DN750 SO-SO-FL Tee PN16, PN35
DN100-DN750 SP-SP-FL Tee PN16, PN35
DN100-DN750 FL-FL-FL Tee PN16, PN35
DN100-DN750 SO-SP-FL Hydrant and Air Valve Tee PN16, PN35
DN100-DN750 SO-SO-FL Scour Tee PN16, PN35
DN100-DN750 SO-SO, FL-SO, FL-SP Connector PN16, PN35
DN150-DN750 SO-SO, SO-FL Taper PN16, PN35
DN100-DN750 FL-FL Taper PN16, PN35
DN100-DN150 FL-FL Connector PN16, PN35
DN100-DN750 Integrally Cast Thrust Connector PN35
DN80-DN750 Puddle Flange PN16
DN100-DN150 Blank Flange PN16, PN35
DN100-DN750 End Cap PN16, PN35
Design Standards - Preferred Equipment Lists 8
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
VINIDEX Superlink PA10/09.2 27/05/2011
Nominal Size Product Pressure Rating Limitations on use
DN100-DN375 SO-SO Bends 90°, 45°, 22.5°, 11.25° PN35
DN100-DN375 FL-SO Connector PN35
DN100-DN375 FL-SP Connector PN35
DN100-DN375 SO-SO Connector PN35
DN100-DN150 READYTAP Connector PN35
DN100-DN375 End Cap PN35
DN80-DN100 Hydrant Riser PN35
DN150-DN375 SO-SO Taper PN35
DN100-DN375 SO-SO Connector PN35
DN100-DN375 FL-SO Connector PN35
DN100-DN375 Air Valve and Hydrant Tee PN35
DN100-DN375 Scour Tee PN35
DN100-DN375 SO-SO-SO Tee PN35
DN100-DN375 SO-SO-FL Tee PN35
DN100-DN375 SP-SP-FLTee PN35
DN100-DN375 SO-SO-SO Tee PN35
Design Standards - Preferred Equipment Lists 9
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
VINIDEX Superlink PA10/09.2 27/05/2011
Nominal Size Product Pressure Rating Limitations on use
DN100-DN375 FL-FL Bend PN35
DN100-DN150 Eccentric FL-FL Taper PN35
DN100-DN375 Concentric FL-FL Taper PN35
DN100-DN375 FL-FL-FL Tee PN35
DN100-DN375 SP-SP-FL Tee PN35
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
VINIDEX Superlink II PA06/11 02/2011 Bill Bencke 25/06/2007
Nominal Size Product Pressure Rating Limitations on use
DN100-DN150
SO-SO Bends 90°, 45°, 22.5°, 11.25°
Product Codes 77584 - 77591
PN16
DN100-DN150
SO-SO-FL Tee
Product Codes 77592 - 77596
PN16
DN100-DN150
SO-SO-SO Tee
Product Codes 77597 - 77599
PN16
Design Standards - Preferred Equipment Lists 10
3. Pressure Pipelines - PVC Pipes
WSA PS–209 Polyvinylchloride Modified (PVC-M) Pressure Pipe for Water Supply and Sewerage WSA PS–210 Polyvinylchloride Oriented (PVC-O) Pressure Pipe for Water Supply and Sewerage AS 4441 - Oriented PVC (PVC-O) pipes for pressure applications AS 4765 - Modified PVC (PVC-M) pipes for pressure applications Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA
Appraisal Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
IPLEX PIPELINES
BLUE RHINO PA 10/08 16/02/2011
DN100 – DN375
PVC-M Pressure Pipe
PN16 Series 2
DN200 and DN250 not accepted for use in the Water Network
No direct tapping for service connections is permitted.
IPLEX PIPELINES
APOLLO BLUE
PC137
DN100 – DN300
PVC-O Pressure Pipe
PN16 Series 2
DN200 and DN250 not accepted for use in the Water Network
No direct tapping for service connections is permitted.
Pentair
TUF-FLO
Bill Bencke 16/06/2004
DN100 – DN375
PVC-M Pressure Pipe
PN16 Series 2
DN200 and DN250 not approved for use in the Water Network
No direct tapping for service connections is permitted.
VINIDEX SUPERMAIN Bill Bencke 29/11/2000
DN100-DN375
PVC-O Pressure Pipe
PN16 Series 2
DN200 and DN250 not approved for use in the Water Network
No direct tapping for service connections is permitted.
Design Standards - Preferred Equipment Lists 11
4. Pressure Pipelines - Polyethylene Pipe and Fittings
WSA PS–207 Polyethylene (PE) Pipes for Pressure Applications - Water Supply and Sewerage WSA PS–208 Polyethylene (PE) Moulded Pressure Fittings for Pressure Applications - Water Supply and Sewerage AS 4130 - Polyethylene pipes for pressure applications Icon Water Standard Drawing Numbers -
Polyethylene Pipe
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size Product Pressure
Rating Limitations on use
VINIDEX
DN16-DN63 PE Pressure Pipe PN16
Design Standards - Preferred Equipment Lists 12
5. Valves and Installations - Gate Valves
WSA PS–260 Gate Valves, Resilient Seated for Pressure Applications – Water Supply and Sewerage WSA PS–261 Gate Valves, Metal Seated for Pressure Applications – Water Supply and Sewerage AS 2638.1 – Gate valves for waterworks purposes – metal seated AS 2638.2 – Gate valves for waterworks purposes – resilient seated Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA
Appraisal Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
AVK AVK 17/10/2000 Bill Bencke
DN100 – DN375
Series 57/40 Resilient Seated Gate Valve
PN16
Pentair
AUSLITE 23/09/2007 Bill Bencke
DN100 – DN150
Resilient Seated Gate Valve PN16
TYCO PC162 DN80 – DN600
Resilient Seated Gate Valve Figure 500
PN16
TYCO PC162 DN80 – DN150
Rising Spindle Gate Valve Figure 500R
PN16
TYCO PC162 DN80 – DN100
Metal Seated Gate Valve Figure 400
PN16
Scour valve only
VINIDEX SUPERLINK II 25/06/2007 Bill Bencke
DN100 – DN150
Resilient Seated Gate Valve
PN16
Hygrade Water
Hawle-A PA 06/07
Andreas Marquardt Expiry 24July2015
DN80-DN150
Resilient Seated Gate Valve – flanged. Compliant with AS 2638.2, AS/NZS 4020, AS 4087, AS 4158
PN16 DN200 not approved for use in the Water Network
Hygrade Water
Hawle E2 Resilient Seated Sluice Valve
PA 04/03
Andreas Marquardt Expiry 24July2015
DN100, DN150
Resilient Seated Gate Valve – flanged. Compliant with AS 2638.2, AS/NZS 4020, AS 4087, AS 4158
PN16 DN200 and DN250 not approved for use in the Water Network
Design Standards - Preferred Equipment Lists 13
6. Valves and Installations - Air Valves
WSA PS–265 Air Valves for Pressure Applications - Water Supply AS 4956 – Air valves for water supply Icon Water Standard Drawing Numbers -
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
VENT-O-MAT
VENT-O-MAT
DN80 – DN150
Series RBX Air Valve with test port, valve and valve cap
PN16
Higher pressure rating required for specific application requirements. For PN16 flange compatible with AS 4087 Table B5
7. Valves and Installations - Butterfly Valves
WSA PS–263 Butterfly Valves for Pressure Applications - Water Supply AS 4795 - Butterfly Valves for Water Supply
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair KEYSTONE DN500-DN1050
Double Flanged – Figure 631 Butterfly Valve
PN16
Design Standards - Preferred Equipment Lists 14
8. Valves and Installations - Check Valves
WSA PS–264 Non-Return (Reflux) Valves for Pressure Applications - Water Supply AS 4794 - Non-return valves – Swing check and tilting disc Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA
Appraisal Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair SUPERCHECK PC162 DN100-DN150
Resilient Seated Swing Check Valve
PN16
9. Valves and Installations – Fire Hydrants
WSA PS–267 Hydrant (Spring) for Pressure Applications - Water Supply AS 3952 - Water supply – Spring hydrant valve for waterworks purpose Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA
Appraisal Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair
SUREFLOW PC162 DN80 Spring Hydrant PN16
Design Standards - Preferred Equipment Lists 15
10. Valves and Installations - Property Service Connections
WSA PS–214 Copper (Cu) Property Service Pipes for Pressure Applications - Water Supply WSA PS–310 Tapping Bands – Mechanical for Water Supply WSA PS–313 Clamps – Offtake for Under Pressure Connections AS 1432 - Copper tubes for plumbing, gas fittings and drainage applications AS 2280 - Ductile Iron Pipe and Fittings AS 2638.2 - Gate valves for waterworks purposes – resilient seated AS 3688 - Press fit connector fittings for copper tube Icon Water Standard Drawing Numbers -
Stainless Steel Clamp Offtakes
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure Rating
Limitations on use
Pentair WANG
PC162
DN150-DN300
Single part, 316 stainless steel clamp with BSP threaded offtake (20, 25, 32, 40, 50)
PN16
Clamps shall have at least two studs. Clamp shall not be rotated after it is assembled around the pipe.
PC162
DN100-DN450
Two part, 316 stainless steel clamp with BSP threaded offtake (20, 25, 32, 40, 50)
PN16
80 and above offtake must be flanged. The clamp shall not be rotated after it is assembled around the pipe.
PC162 DN100-DN450
Two part flanged offtake clamp (Flange to AS 4087 Table B5, sizes 80 to 300)
PN16
The clamp shall not be rotated after it is assembled around the pipe.
Design Standards - Preferred Equipment Lists 16
Property Service Water Meters
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure Rating
Limitations on use
Elster Elster PC44W/12 Expiry July 2018
DN20 to DN150
Water Meters (20, 25, 32, 40, 50, 80, 100, 150)
PN16
Property Service Fittings
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure Rating
Limitations on use
Tradelink Plumbing Supplies
Viega Thomas Tyrell 8July13
DN20-DN50
Copper alloy press fit fittings complying with AS 3688 section 10.1 (b)
Use only on hard drawn copper tube complying with AS 1432 Type B.
Property Service Pipe
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure Rating
Limitations on use
Accepted Plumbing Supply Outlets
Bill Bencke 03/03/2009
DN20-DN80
Copper Tube
AS 1432 Type B,
hard drawn
Property Service connections only
Design Standards - Preferred Equipment Lists 17
11. Water Network Maintenance Fittings
WSA PS-201 Ductile Iron Fittings for Water Supply and Sewerage WSA PS-311 Mechanical Couplings – Unrestrained AS 2280 - Ductile iron pipes and fittings AS 4181 - Stainless steel clamps for waterworks purposes Icon Water Standard Drawing Numbers –
Mechanical Couplings
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
CREVET AVK PC192
DN100-DN300
Supa Series 601 Gibault
PN16
Not to be used on new works
Pentair
VARI GIB PC192 DN80-DN600
Gibault PN16 Not to be used on new works
EZI GIB DN100-DN200
Gibault PN16 Not to be used on new works
Hygrade Water
Hawle-Synoflex
PA 06/07
Andreas Marquardt Expiry 20June2016
DN80-DN300
Socket Socket connector Socket Flange connector (AS 4087 Figure B5 flanges)
PN16
Not to be used on new works Coatings and elastomers certified to AS/NZS 4020.
Design Standards - Preferred Equipment Lists 18
Stainless Steel Repair Clamps
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair WANG PC192
DN80-DN225
Single piece, 316 passivated stainless steel repair clamp, minimum 2 studs
PN16
Different DN80 clamp for galvanised and DICL pipe. The clamp must not be rotated after it is assembled around the pipe
Stainless Steel Tapping Clamps
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair WANG PC192
DN100-DN300
Two piece, 316 passivated stainless steel, BSP threaded offtake clamp with minimum 2 studs clamp
PN16
The clamp must not be rotated after it is assembled around the pipe
DN100-DN450
Two part 316 passivated stainless steel, offtake flanged compatible with AS 4087 Table B7, clamp with minimum 4 studs clamp
PN16
The clamp must not be rotated after it is assembled around the pipe
Design Standards - Preferred Equipment Lists 19
Part B - Sewerage Network Hydraulic Products PEL
12. Sewerage Network Pipelines - PVC Pipe and Fittings
PVC not to be used in or within 1 km downstream of industrial areas or hospitals.
WSA PS-230 PVC-U Non pressure pipe and fittings WSA PS-236 Variable bend, post formed PVC-U non pressure fittings AS 1260 PVC-U pipes and fittings for drain, waste and vent applications Icon Water Standard Drawing Numbers -
PVC Pipe
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Pressure
Rating Limitations on use
IPLEX
DN100 – DN225
Plain Wall PVC Pipe (SCJ) SN8
DN300 - DN375
Plain Wall PVC Pipe (RRJ) SN8
Pentair
DN100 – DN225
Plain Wall PVC Pipe (SCJ) SN8
DN100 - DN375
Plain Wall PVC Pipe (RRJ) SN8
VINIDEX
DN100 – DN225
Plain Wall PVC Pipe (SCJ) SN8
DN300 - DN375
Plain Wall PVC Pipe (RRJ) SN8
Design Standards - Preferred Equipment Lists 20
Fittings for PVC Pipe
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
IPLEX
Nominal Size Product Pressure Rating Limitations on use
DN100-DN150 Plain Bends F&F (SWJ) 88°, 45°, 30°, 15°, 5° SN8
DN150-DN375 Fabricated Bends F&F (SWJ) 88°, 45°, 30°, 15°, 5° SN8
DN100-DN150 Plain Bends F&F (SWJ) 88°, 42°, 30°, 22° 15°,11°, 5° SN8
DN150-DN225 Fabricated Bends M&F (SWJ) 88°, 60°, 45° SN8
DN100 – DN150 Plain Junction F&F (SWJ) 88°, 45° SN8
DN225 – DN375 Fabricated Junction F&F (SWJ) 88°, 45° SN8
DN100 –DN225 Plain Coupling (SWJ) SN8
DN300 – DN375 Fabricated Coupling (SWJ) SN8
DN100-DN150 Access Coupling (SWJ) SN8
DN100-DN375 Bend F&F (RRJ) 88°, 45° SN8
DN100-DN375 Bend M&F (RRJ) 88°, 45°, 30°, 15°, SN8
DN100-DN375 Junction F&F (RRJ) 88°, 45° SN8
DN150-DN300 Bend M&F (RRJ) 88°, 45° SN8
Design Standards - Preferred Equipment Lists 21
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
VINIDEX
Nominal Size Product Pressure Rating Limitations on use
DN100 Bend F&F (SCJ) 5° SN8
DN100-DN150 Bend F&F (SCJ) 15° SN8
DN100 Bend F&F (SCJ) 30° SN8
DN100-DN225 Bend F&F (SCJ) 45° SN8
DN100 Bend F&F (SCJ) 60° SN8
DN100-DN150 Bend F&F (SCJ) 88° SN8
DN225 Bend F&F (SCJ) 90° SN8
DN100 Bend M&F (SCJ) 5° SN8
DN100-DN150 Bend M&F (SCJ) 15° SN8
DN100 Bend M&F (SCJ) 30° SN8
DN100-DN150 Bend M&F (SCJ) 43° SN8
DN100 Bend M&F (SCJ) 60° SN8
DN100-DN150 Bend M&F (SCJ) 88° SN8
DN100-DN300 45° Plain Junctions F&F (SCJ) SN8
DN100-DN150 45° Plain Junctions M&F (SCJ) SN8
DN100-DN225 88° Plain Junctions F&F (SCJ) SN8
Design Standards - Preferred Equipment Lists 22
Supplier Brand Name WSAA Appraisal Icon Water Acceptance
VINIDEX
Nominal Size Product Pressure Rating Limitations on use
DN100 88° Plain Junctions M&F (SCJ) SN8
DN225-DN300 Straight Couplings F&F (SCJ) SN8
DN100-DN150 Access Couplings (SCJ) SN8
DN100-DN300 Slip Coupling (SCJ) SN8
DN100 – DN150 Sewer Bend F&F (RRJ) 90°, 88°, 45° SN8
DN100 – DN150 Sewer Bend M&F (RRJ) 90°, 60°, 45° SN8
DN100 – DN300 45° Sewer Junctions (RRJ) F&F SN8
DN150 90° Sewer Junctions (RRJ) F&F SN8
DN150 – DN300 45° Sewer Junctions (RRJ) M&F SN8
DN150 90° Sewer Junctions (RRJ) M&F SN8
DN100 –DN300 Sewer Slip Couplings (RRJ) SN8
DN100 Sewer Straight Couplings (RRJ) SN8
DN100-DN300 Sewer Manhole Couplings (RRJ) SN8
Design Standards - Preferred Equipment Lists 23
13. Sewerage Network Pipelines - Vitrified Clay Pipe and Fittings
WSA PS–231 Vitrified Clay (VC) Pipe and Fittings AS 1741 Vitrified clay pipes and fittings with flexible joints - Sewer quality Icon Water Standard Drawing Numbers - Vitrified Clay Pipe
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pipe Class
Limitations on use
LEAP AUSTRALASIA
HEPWORTH SUPERSLEVE
DN100 – DN300
Socketless Vitrified Clay Pipe
4
Fittings for Vitrified Clay Pipe
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pipe Class
Limitations on use
LEAP AUSTRALASIA
HEPWORTH
DN100 – DN300
Bend 90°, 45°, 30°, 15° 4
DN100 – DN300
Jointing Coupling 4
DN100 – DN300
Jointing ‘O’ Ring 4
DN100-DN300
Curved Square Junction 4
DN100-DN300
Oblique Junction 4
DN100-DN300
Square Junction 4
DN100-DN150
Plug 4
DN100-DN225
Taper 4
Design Standards - Preferred Equipment Lists 24
14. Sewerage Network Pipelines - Polypropylene Pipe and Fittings
Polypropylene not to be used in or within 1 km downstream of industrial areas or hospitals.
WSA PS-242 Polypropylene (Ribbed Construction) Non-Pressure Pipe and Fittings AS/NZS 5065 Polyethylene and polypropylene pipes and fittings for drainage and sewerage applications Icon Water Standard Drawing Numbers -
Polypropylene Pipe
Supplier Brand Name
WSAA Appraisal
Icon Water acceptance Nominal Size Product Stiffness Rating
Limitations on use
VINIDEX SewerPRO Approval- Peter Szlapinski 10/09/2008 DN150 –
DN600 Polypropylene Pipe
SN8 6 metre lengths only.
Fittings for Polypropylene Pipe
Supplier Brand Name WSAA Appraisal Icon Water acceptance
VINIDEX SewerPRO Approval- Peter Szlapinski 10/09/2008
Nominal Size Product Stiffness Rating Limitations on use
DN150 – DN600 Coupling SN8
DN150 – DN600 Slip Coupling SN8
DN150 – DN375 Adaptor Coupling SN8
DN150 – DN600 45° Junction SN8
DN150 – DN600 88° Junction SN8
DN150 – DN600 Tee SN8
DN150 – DN600 Inspection Tee SN8
DN150 Bend M-F SN8
DN150 – DN600 45° Bend F-F SN8
DN150 – DN600 90° Bend F-F SN8
DN150 – DN600 Push On Cap SN8
DN300 – DN600 Shorts SN8
Design Standards - Preferred Equipment Lists 25
15. Sewerage Network Pipelines - Ductile Iron Pipe and Fittings
WSA PS-200 Ductile Iron Pipe for Water Supply and Sewerage AS 2280 Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair TYTONXTREME DN100 – DN600
Ductile iron pressure pipe with calcium aluminate
cement lining PN20
Ductile Iron Pipe Fittings
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pressure
Rating Limitations on use
Pentair Tyton Joint
DN100-DN600
SO-SO Bends 90°, 45°, 22.5°, 11.25° End Cap SO-SO Taper SO-SO-SO Tee SO-SO-FL Tee SP-SP-FL Tee FL-FL Bend FL-FL-FL Tee SP-SP-FL Tee
PN35 All fittings shall be bonded polymeric coated
Design Standards - Preferred Equipment Lists 26
16. Sewerage Network Pipelines - Glass Reinforced Plastic Pipe and Fittings
GRP not to be used in or within 1 km downstream of industrial areas or hospitals.
WSA PS–205S Filament Wound Glass Reinforced Plastics (FW-GRP) Pipes and Fittings for Pressure and Non-Pressure Applications - Sewerage AS 3571.1 Plastics piping systems - Glass reinforced thermoplastics (GRP) systems based on unsaturated polyester (UP) resin Part 1: Pressure and non-pressure drainage and sewerage Icon Water Standard Drawing Numbers - GRP Pipe
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pipe
Rating Limitations on use
GLOBAL PIPE
HOBAS SEWERLINE
DN300 – DN675
Centrifugally Cast GRP Non-Pressure Pipe
SN10000
IPLEX
FLOWTITE GRP
DN375 – DN675
Filament Wound GRP Non-Pressure Pipe
SN10000
GRP Pipe Fittings
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pipe
Rating Limitations on use
GLOBAL PIPE
HOBAS SEWERLINE
DN300 – DN675
Coupling
DN375 – DN675
Access Chamber Connector
DN300 – DN375
Saddle Tee Junction
DN300 – DN375
45° Slope Junction
DN300 – DN600
Tees
DN300 – DN675
Bends
Design Standards - Preferred Equipment Lists 27
GRP Pipe Fittings
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Pipe
Rating Limitations on use
IPLEX
FLOWTITE GRP
DN375 – DN675
Coupling
DN375 – DN675
Access Chamber Connector
DN300 – DN375
Saddle Tee Junction
DN300 – DN375
45° Slope Junction
DN300 – DN600
Tees
DN300 – DN675
Bends
Design Standards - Preferred Equipment Lists 28
17. Sewerage Network Pipelines - Sewer Access Pit Components
WSA PS-290 Access Covers for Water Supply and Sewerage to AS 3996 WSA PS-323 Maintenance Holes – Precast Concrete AS 3996 Access Covers and Grates AS 4198 Precast Concrete Access Chambers for Sewerage Applications
Icon Water Standard Drawing Numbers -
Access Covers and Frames
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Relevant
Documents Limitations on use
GATIC GATIC
DN900 Circular Solid Top Ductile Iron Access Cover and Frame Class B and D
Class B non-trafficable areas Class D trafficable areas
915x915
Square Concrete Infill Ductile Iron Access Cover and Frame Class D
Class D trafficable areas
Precast Access Chamber Components.
Supplier Brand Name WSAA
Appraisal Icon Water acceptance
Nominal Size
Product Relevant
Documents Limitations on use
PREMIER PRECAST
PC58 DN1015 Chamber Height 350, 525, 700, 1050 mm
Not to be used if vehicle access unavailable for Section 27 Vehicle Hitch Mount Sleeve Model 8514461.
Design Standards - Preferred Equipment Lists 29
Part C – Water and Sewerage Networks - Telemetry Electrical and Instrumentation Products PEL
Icon Water may choose to free issue telemetry, electrical and/or instrumentation equipment to a contractor. Whether the equipment is issued to a contractor or is supplied by a contractor, the following shall apply:
1. In many of the telemetry, electrical and/or instrumentation equipment categories, Icon Water has established formal Period Contracts for the supply and delivery of equipment within that broad category. While Icon Water has nominated specific preferred units or items within that category, the conditions of the Period Contracts allow access to other equipment ranges or families within that broad category, i.e. special, innovative or non standard solutions may be more appropriate.
2. The following preferred telemetry, electrical and/or instrumentation equipment listings shall include all associated accessories and ancillary devices applicable to the primary equipment within that category whether individually listed or not.
3. Where Icon Water is to free issue nominated equipment and devices this will be specified in the project specification. Accordingly, design consultants and contractors are required to provide to Icon Water, within an appropriate timeframe considering equipment lead times; a comprehensive Bill of Materials (BOM) of all telemetry, electrical and/or instrumentation equipment required to be free issued. The BOM shall include ALL accessories and ancillary items necessary to complete the required works independent of how small or minor. If an item is not identified in the BOM it will not be ordered for free issue. Responsibility for delays resulting from the omission of items from the BOM shall rest solely with the design consultant or contractor or originator of the BOM.
4. Sections 18 to 21 inclusive of this PEL apply to the Complex Sites in the Water Network. Section 22 is an addendum that applies to the Simple Sites in the Water Network. The definition of Complex Sites and Simple Sites is given in the Icon Water Standard Specification - O&M Manuals. Where section 22 conflicts with sections 18 to 21, then section 22 takes precedence at Simple Sites.
Design Standards - Preferred Equipment Lists 30
18. Water and Sewerage Networks - Telemetry Products
Telemetry Application and Software
SCADA System Software: SCADA System Paging Module: Operating System - SCADA Server: Operating System - Data/Report Server: Operating System - SCADA Workstation: Reporting Software:
Citect For Windows, Version TBA upon request Citect Alarm Paging Module, Version TBA upon request TBA upon request TBA upon request TBA upon request TBA upon request
Telemetry Hardware Configurations
Main I/O Servers Reporting/Data Server Operator Workstations
To Be Advised upon request – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}
Networking Hardware
Ethernet Hub: Ethernet Router: Ethernet Switch:
Firewall Device:
To Be Advised upon request To Be Advised upon request To Be Advised upon request
FortiGate (Model To Be Advised upon request)
Radio Hardware
DDRN:
Schneider Electric – Trio ER45e – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}
Microwave:
To be Advised – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}
Design Standards - Preferred Equipment Lists 31
19. PLC Equipment
The preferred supplier for PLC Control System equipment for Complex Sites in the Water Network is Rockwell Automation Australia. The following equipment and networking protocols are the preferred equipment and configurations for PLC Control Systems at Complex Sites in the Water Network.
Application/Item Manufacturer Preferred Family/Model Additional Information
Zone PLC/Main Functional Area PLC’s Rockwell Automation ControlLogix
PLC – SCADA System Network - EtherNet
PLC – SCADA System ethernet Network switch:
Moxa Technologies EDS-508A-MM-SC If port count exceeded, then use Moxa EDS-619 switch with relevant CM-600 interface modules
Ethernet Media Converter Moxa Technologies IMC-101-M-SC 10/100BaseTX to 100BaseFX converter, multi mode.
PLC – SCADA Network Rockwell Automation EtherNet/IP
PLC – PLC – Zone PLC Network: Rockwell Automation ControlNet (under review, may change to EtherNet)
Dual Redundant Fibre Optic
PLC – Field Distributed I/O Network: Rockwell Automation ControlNet
PLC – MCC Distributed I/O Network (and miscellaneous drives and field equipment)
Rockwell Automation DeviceNet Utilising KwikLink Flat Media Cabling System
MCC Distributed I/O Hardware: Rockwell Automation DeviceNet Starter Auxiliary Flex I/O Combo modules to be used if DeviceNet Starter Auxiliary not appropriate
Field Distributed I/O Hardware: Rockwell Automation Flex I/O
Design Standards - Preferred Equipment Lists 32
Specific PLC Applications
The following equipment items are the preferred equipment items in their specific application:
Zone PLC/Main Functional Area PLCs
Application/Item Manufacturer Make/Model Additional Information
ControlLogix Chassis/Rack
Rockwell Automation
1756-Axx where xx refers to no. of slots.
Rack size appropriate to application plus spare capacity, refer this Std.
ControlLogix 24VDC Power Supply Rockwell Automation
1756-PB72
ControlLogix 1756 Controller / Processor Rockwell Automation
1756-L7x - where x is the code number that relates to memory capacity.
Unless otherwise specified the processor shall be the 1756-L73 (8MB)
Panel Mount Battery Module Rockwell Automation
1756-BATM
Redundant Media ControlNet Bridge Rockwell Automation
1756-CNBR Dual Redundant Fibre Optic Cable network
Single Media ControlNet Bridge Rockwell Automation
1756-CN2
DeviceNet Bridge Rockwell Automation
1756-DNB
Modbus Protocol Converter Prosoft 1756-MCM
EtherNet Bridge Rockwell Automation
1756-EN2TR
Fibre Optic Modem Rockwell Automation
1786-RPA + 1786-RPFM Not rack/chassis mounted – generally mounted within Fibre Optic Termination Cubicle or equivalent.
Design Standards - Preferred Equipment Lists 33
MCC Distributed I/O
Application/Item Manufacturer Make/Model Additional Information
DeviceNet Starter Auxiliary modules (4x DI / 2 x DO)
Rockwell Automation
100-DNY42R Preferred configuration
FlexIO 10x DI / 6x DO Combo Module Rockwell Automation
1794-IB10XOB6 Non-preferred configuration - only applicable when multiple starter auxiliaries are not practical. This has been used within MCC main incomer cell. For terminal base details, refer FDIO components.
DeviceNet Kwiklink Network Cabling - Trunk
Rockwell Automation
DeviceNet Class 1 Flat Cable 1485-CP1E
For field DN networks, e.g. actuators, use of thick round trunk cable in combination with junction boxes is preferred. Pt. No. 1485C-P1Axx
Network Cabling – Drop cables Rockwell Automation
1485K-P1F5-C (1m drop cable)
1485K-P6F5-C (6m drop cable)
Network Connections Rockwell Automation
1485P-P1E4-R5 (IP67 Micro Module & Base)
1485A-T1E4 (IP67 Terminator & Base)
1485P-P1H4-T4 (Open Style module & Base)
Lower IP rating is acceptable within MCC or other panels with min IP54 rating. At Stromlo, 1485P-P1H4-R5 was installed.
Open style module used only for DeviceNet network power supply connections.
Design Standards - Preferred Equipment Lists 34
Field Distributed I/O (FDIO cubicles)
Application/Item Manufacturer Make/Model Additional Information
Flex I/O ControlNet Communications Adapter Rockwell Automation 1794-ACN15 + plus tap
Flex I/O EtherNet Communications Adapter Rockwell Automation 1794-AENTR
Flex I/O DeviceNet Communications Adapter Rockwell Automation 1794-ADN
Flex I/O 3-wire Terminal Base Unit Rockwell Automation 1794-TB3
Flex I/O Fused Terminal Base Unit Rockwell Automation 1794-TBNF Used with 1794-OW8 output module
Flex I/O Temperature Terminal Base Unit Rockwell Automation 1794-TB3T Used with Thermocouple inputs.
Flex I/O 16pt sink Digital Input Module Rockwell Automation 1794-IB16 Preferred for Digital Inputs
Flex I/O Fused Relay Sink/Source Digital Output Module
Rockwell Automation 1794-OW8 Preferred for Digital Outputs.
Flex I/O 16pt Digital Output (with current limiting)
Rockwell Automation 1794-OB16P Not preferred.
Flex I/O 24VDC 4pt Isolated Analog Input Module
Rockwell Automation 1794-IF4I
Flex I/O 24VDC 4 pt Isolated Analog Output Module
Rockwell Automation 1794-OF4I
Flex I/O 24VDC 2pt in/2pt out Analog Combo Module
Rockwell Automation 1794-IF2XOF21 Applicable when only one output required
Flex I/O 24VDC 8pt RTD Input Module Rockwell Automation 1794-IT8
ControlNet to Devicenet Rockwell Automation 1788-CN2DN
EtherNet to DeviceNet Rockwell Automation 1788-EN2DN
ControlNet to Modbus Prosoft MVI-94-MCM
Design Standards - Preferred Equipment Lists 35
Field Distributed I/O (FDIO cubicles)
Application/Item Manufacturer Make/Model Additional Information
Entek XM-120 Vibration Module Rockwell Automation - Entek
1440-VST02-01RA
Entek XM-940 Terminal Base to suit Vibration Module
Rockwell Automation - Entek
1440-TB-A
ControlNet Taps Rockwell Automation 1786-TPYS (Y Tap)
1786-TPYR (Y Tap with right angle end)
1786-TPR (T Tap)
1786-XT (Coax terminator)
TPYS used for connection to 1756-CNB/R modules.
TPYR used for connection to ACN15.
TPR used where coax surge suppression needs to be fitted.
Field Operator Interface Panels
Application/Item Manufacturer Preferred Item Additional Information
Panelview Plus 12" Colour TouchScreen with EtherNet Interface
Rockwell Automation
2711PRDB12C (currently under review – may go to industrial PC)
PanelPC VersaView 17” TFT, Touch Screen, Win7, HMI
Rockwell Automation
6181P-17A2SW71AC Embedded ethernet port (currently under review – may go to industrial PC)
Design Standards - Preferred Equipment Lists 36
20. Water and Sewerage Networks - Electrical Products
Application/Item Manufacturer Preferred Make/Model Additional Information
Motor Control Centres B&R Enclosures Signature SE series, demountable cells (i.e. use of bus plugs), min. cell size - 2. Form 3B minimum.
Unless otherwise accepted by Manager Water Assets Planning.
Refer also MCC Standard drawings and LMW 8.02 S012.
Intelligent Motor Protection Relays (MPR) E3+ range
Rockwell Automation
E3 PLUS: 193-EC2nn range for motor size range up to and including 33 kW model. 193-EC5nn range (provides voltage and power monitoring functions) for motors above 33 kW where ‘nn’ refers to specific size or rating.
Model and firmware revision to be accepted by Managers Water and Sewerage Assets Planning.
MV/HV MPR Schneider Areva T&D Micom P241*********** (typical P241111A2M0320C)
LV Switchgear (not including LV Distribution Centres and MCBs):
Schneider Up to 250 amps:
MCCB: Compact NSX system 100/160/250H featuring TM_D and MA trip units.
NS80H magnetic only motor protection Circuit Breakers up to 37 kW may be approved for use by Managers Water & Sewerage Assets Planning based on specific application.
TeSys GV2P or L for smaller motor circuit protection – use to be approved by Managers Water & Sewerage Assets Planning based on specific application.
Above 250 amps:
Compact NSX system 400/630H featuring MicroLogic trip unit (model to be accepted by Managers Water and Sewerage Assets Planning for each specific application)
Masterpact NT and NW range featuring
Motor Circuit Breakers – use NS80H for small motors.
Design Standards - Preferred Equipment Lists 37
Application/Item Manufacturer Preferred Make/Model Additional Information
MicroLogic trip unit. Model of circuit breaker and trip unit to be accepted by Managers Water and Sewerage Assets Planning for each specific application.
Load Break Switches / Isolators – Interpact INS range.
LV Motor Starter & control Equipment:
Schneider Contactors (<150 Amps): LC1-D range
Contactors (>150 Amps): LC1-F range
Bi-metallic TOL: LRD range
Thermistor Relay: LT3SA00MW
Phase Failure Relays: RM17TE004 or RM35TF30
Miniature control relays: RXM4AB2** range
Contactors generally with 240 V 50 Hz coils. Surge suppression modules to be provided if supplied from UPS.
Contactors to be fitted with LA4Dxx relay interface modules where possible.
Any 24 VDC coil relays to be provided with diode protection.
LV Electronic Soft Starters: Rockwell Automation Bulletin 150
SMC-Flex series
Generally 24 VDC control supply required for Soft starters (cooling fan supply may be a separate 240 VAC supply).
Accessories to the match specific application including but not limited to EtherNet or DeviceNet communications adapter, local HMI, transient protection modules.
LV VVVF Drives: Danfoss
FC302 for up to 160% starting torque Or
FC202 for up to 110% starting torque.
Accessories to match the specific application and Icon Water requirements including but not limited to DeviceNet or EtherNet communications c/w DC standby capability, Harmonic and Sine filters, and extended I/O functionality
Range and model as appropriate to the specific application.
LV Distribution Centres & MCBs
Schneider MB,MD Series Enclosures Multi 9 MCBs shall be used for Auxiliary items supplied from MCC compartments,
Design Standards - Preferred Equipment Lists 38
Application/Item Manufacturer Preferred Make/Model Additional Information
MSC or MBB Series Chassis *
Acti 9 iC60H, NG125H MCBs. Acti 9 iC60 RCBO 10 kA or Vigi to suit iC60 type AC for 3ph+N RCD.
however, cascade/current limiting protection of the unit is required with the main isolator or circuit breaker
* For Essential power and UPS Distribution Board applications use of MGB Isobar chassis is required unless otherwise specifically accepted for each application by Managers Water and Sewerage Asset Planning.
Field Enclosures and Start/Stop Stations
Rockwell Automation LCS enclosures:
800F-nP (Poly Carbonate) for indoor applications unless there is risk of mechanical damage in which case refer to outdoor requirements.
800F-nM (cast metal) or 800F Stainless Steel where exposed to UV or where increased mechanical protection is required
Where ‘n’ in the part number is number of holes.
Where chemical compatibility is an issue then enclosure material to be appropriate to the application
Minor Control Equipment Rockwell Automation Pushbuttons - 800FP-F range.
Latch or E-Stop - 800FP-MT44 or MP44
Pilot lights - 800FP-Px (C/w separate LED cluster type bulb e.g. 800E-N157R)
Selector switches: 800FP-S range
Volt/Current Selector switch and actuator: 194L-E12 range + 194L-HC range
Icon Water may specify exceptions to the standard requirements dependant on project application.
Design Standards - Preferred Equipment Lists 39
Application/Item Manufacturer Preferred Make/Model Additional Information
Voltmeter, Ammeters, CTs, and Current Transducer
Rockwell Automation
Powermonitor 1000 or 5000 series.
Typical models include;
- Bulletin 1408-TR2A-ENT
- Bulletin 1426-M6E-A or 1426-M6E-DNT-A
The type and specific model of Powermonitor 1000 or 5000 including data communications interface and other options and accessories to be submitted for acceptance by Managers Water and Sewerage Assets Planning for each specific application.
Or
Crompton
Or
Voltmeter: 244 Series
Ammeter/MDI: 244 Series
CTs: MA5H class 1.
Current Transducers: 252 series with 4-20 mA output
The use of voltmeters, ammeters and current transducers will typically only be accepted for basic and low power applications.
Lightning/Surge Protection Erico
Primary POE, Main Switchboards, MCCs: TDS1100-2SR-277 per phase or model to suit application.
FCPs / L+P switchboard AC: TDS350-TT-277 for 3-phase or TDS150-1SR-277 for 1 phase or model to suit application
DC Dist: DSD140-2BR-24/48
BNC Coaxial: CSP-1BNC-90
Universal Transient Barrier: UTB-30
UTP-30 used for protection of DeviceNet, as well as PLC 24 VDC I/O wiring (where required).
UTB-30 required for all analogue inputs and outputs where instrumentation is located external to the building that the wiring originates from.
Use of UTB-30S instead of UTB30 requires accepted by Managers Water and Sewerage Assets Planning.
Terminals
Schneider NSYTRV Range (Colour Grey for std terminals)
Power & Control: NSYTRV range – min size 6mm width i.e. NSYTRV42
Instrumentation: NSYTRV42ST
Fuse Terminals: NSYTRV42SF5
Earth Terminals: NSYTRVxxPE range
For the Instrumentation terminals, accepted alternatives are:
- Phoenix UK5-MTK-P/P
- Weidmuller WTR 4 STB, Pt. No. 7910210000
Design Standards - Preferred Equipment Lists 40
Application/Item Manufacturer Preferred Make/Model Additional Information
Uninterruptible Power Supplies (UPS)
Eaton 9155 and 9130 ranges. Specific model to be selected based upon application requirements and each application accepted by Managers Water and Sewerage Assets Planning.
Refer also LMW 8.02 S019. UPS arrangement including batteries, mechanical by-pass unit, battery charger, cabinet design, refer existing Complex Sites UPS installations and standard drawings.
DC Power Supplies - battery backed
Eaton APR24-3G / ES Rectifiers
SC200 Controller Batteries – 6TJ9 Monoblocs
DC Power Supplies - DC/DC and AC/DC non battery backed
Powerbox
DC/DC Converter 5A or 7A: PB1H24-24M or -24R
AC/DC power supplies: PBB20C 24 series.
DC/DC converter used to supply DeviceNet, 1794 - Flex I/O analogue input and output modules and communications modules such as 1794-ACN15s and AENT. Use of Rockwell Automation Bulletin 1606-XL** only where specifically accepted by Managers Water and Sewerage Assets Planning.
Cable and Wire markers
Grafoplast and Brady Cable Markers: Grafoplast SI2K series – yellow backgound, black text minimum of 5 mm high font (Do Not Condense text), UV stabilised sleeves and cable ties.
Wire number sleeves: Grafoplast sleeves
Wire number markers: Black text, white background. Min. font size 6 (point size 10, approx. 2.5mm high). Grafoplast medium sized number markers, correct sized sleeves OR Brady insert labels.
Enclosures and Junction Boxes – General Purpose - process area
B&R Enclosures Connector TE series - 316 Stainless Steel.
Each variation from the preferred makes and model to be accepted by Managers Water and Sewerage Assets Planning. All J/boxes, enclosures to be supplied with
Design Standards - Preferred Equipment Lists 41
Application/Item Manufacturer Preferred Make/Model Additional Information
Universal NI series – 316 Stainless Steel.
mounting pan/panel. Use of insulating material where practical is preferred. NI series to be supplied with NI020/S lock. A junction box for an equipment item may be combined with the LCS for that same equipment item only where specifically accepted by Managers Water Assets Planning.
Power outlets - process/outdoor/workshop areas
Clipsal 56 series outlets, and matching plugs as appropriate to application
Note requirement for round earth pin for EP outlets.
Chemical compatibility with materials of construction to be confirmed for chemical storage/batching/dosing areas
Valve Electric Actuators:
- Modulating control
- Isolation – open/close, ¼ turn, etc.
Rotork or Limitorque
Rotork
Rotork, series as appropriate and approved but generally IQ series. Specific model appropriate to application.
Limitorque MX series.
Rotork - model as appropriate to application and accepted by Manages Water and Sewerage Assets Planning.
Required make and model of actuator shall be specified for each individual project and accepted by Managers Water and Sewerage Assets Planning.
Use of discrete monitoring and controls for actuator or use of communication network, e.g. EtherNet or DeviceNet for control and monitoring to be accepted by Managers Water and Sewerage Assets Planning for each the specific project.
Solenoid Valve / actuators Burkett or ASCO Model as appropriate to application. Unless otherwise accepted supply voltages will be 240 VAC or 24 VDC (generally 240 VAC will be used for non critical applications).
Flexible Conduit
(requirements for indoors and outdoors process/plant equipment areas).
Flexicon
Flexicon LTP - Black sheath c/w metal fittings either nickel plated brass or stainless steel as specified Flexicon LPC – Black PVC for outdoors applications or as otherwise specified. Orange
Standard process area flex conduit: Flexible sheathed metal conduit for use as specified, or where required for screening/earthing, or for protection Heavy duty flexible plastic conduit used
Design Standards - Preferred Equipment Lists 42
Application/Item Manufacturer Preferred Make/Model Additional Information
AdapterFlex
sheath for indoors applications. Complete with metal fittings either nickel plated brass or stainless steel as specified. Flexicon - other types as suited to specific applications and each application accepted by Managers Water and Sewerage Assets Planning. AdapterFlex SPL – Black sheath Complete with metal fittings either nickel plated brass or stainless steel as specified
instead of flexible metal conduit where corrosion is an issue and where specifically accepted by Managers Water and Sewerage Assets Planning. Nylon fittings not accepted.
Flexible sheathed metal conduit for use as listed above.
Fluorescent Luminaires Pierlite For Indoor applications;
1. Process areas – model PWPxyzQS c/w polycarbonate diffuser
2. For Non Process areas such as MCC rooms, control rooms & office areas – specification of fittings as accepted by Manager Water Assets Planning
For outdoor applications;
1. General - Vandalux VCxyzQS
‘xyz’ denotes manufacturer’s number code indicating number of and wattage of lamps.
For applications exposed to UV, FRP/GRP and similar materials are not acceptable.
Emergency Lighting TBA upon request Design and makes/models of emergency and exit lighting to be accepted by Manager Water Assets Planning.
Normal practice for emergency lighting in process areas is the use of spot light fittings (e.g. Bardic or Legrand - SLSMT 210). Spot light fittings are to be supplied from Essential Power type socket outlets to allow ease of isolation or removal for maintenance
Fluorescent type emergency lighting fittings are not accepted.
Flood Light / Area lighting / Roadway lighting
TBA upon request Design and makes/models of these lighting types to be submitted for each application for acceptance by Managers Water and Sewerage Assets Planning.
For applications exposed to UV FRP/GRP and similar materials are not accepted.
Design Standards - Preferred Equipment Lists 43
21. Water and Sewerage Networks - Instrumentation Products
Application/Item Manufacturer Preferred Family/Model Additional Information
Electromagnetic Flowmeter – full bore type
ABB
Siemens
WaterMaster, Model specification as appropriate to the application
MAG 5000 / 6000 transmitter, MAG 5100 W Flow tube
Remote Transmitter featuring 240 VAC power supply required unless otherwise accepted by Managers Water and Sewerage Assets.
Specific model details to be selected based upon individual application requirements.
Electromagnetic Flowmeter – Insertion type for low accuracy applications.
Generally prohibited.
May only be accepted for a specific application by Managers Water and Sewerage Assets in which case suitable make and model shall be selected.
Flowmeter Variable Area –Rotameters.
Kytola Model 2851R-5CA-A -H Scale 0.05 to 0.5 Litres/minute of Water complete with hand knob and 2851 Constant Flow Regulator.
Model LH-8SA-HR Scale 0.2 to 2.6 Litre/min of water , ¼” BSP Female 316 stainless steel, rear connections, with hand knob
The models listed are generally used for Water Quality instrumentation sample lines. Other models to cater for greater flows to be accepted Managers Water and Sewerage Assets for each application.
Pressure Transmitters ABB
Endress + Hauser
266HSHMSBB1E8L5B2S2N4 (0-600 kPa)
Or 266HSHPSBB1E8L5B2S2N4 (0-2400 kPa)
Or 266DSHFSSA2B1V1E8L5B2S2N4 (Diff Press 0 -40 kPa)
Models TBC
Fitted with Integral transient and surge protection module. Other transmitters depending on the application from the ABB range may be aaccepted by Managers Water and Sewerage Assets Planning. Endress + Hauser models equivalent to ABB may be proposed
Design Standards - Preferred Equipment Lists 44
Application/Item Manufacturer Preferred Family/Model Additional Information
Suspended hydrostatic Endress + Hauser WaterPilot, Pt. No. FMX2165-****, model as appropriate to the application
Ultra Sonic liquid/solid level meters.
Siemens
or
Endress + Hauser equiv.
SITRANS Probe LU and Multi Ranger
Models TBC
Other models depending on the application from the Siemens range may be accepted by Managers Water and Sewerage Assets.
Endress + Hauser equivalent models may be proposed
RADAR – liquid or solid level, guided and unguided,
Siemens
Endress + Hauser
Models TBC
Models TBC
Models to be proposed depending on the application for acceptance by Managers Water and Sewerage Assets Planning.
Ultra Sonic Sludge Blanket monitoring meters.
TBA TBA Makes and models to be proposed for each application for acceptance by Managers Water and Sewerage Assets Planning.
Vibrating liquid/solid level switches
Endress + Hauser FTM30 – FTM32 -*4D***, model appropriate to the application.
Process turbidity analysers Hach
WTW
HACH Lasertrac for Ultra low turbidity applications
Visoturb IQ SensorNet for submersion applications in channels or tanks i.e. not WQ panel pipe insertion type applications.
For other applications makes and models to be proposed for acceptance by Managers Water and Sewerage Assets Planning.
Process pH analysers Endress + Hauser Transmitter: CPM253/-MR0105 or CM442-AA-M2-A4-F2-6-0-A-AA (24VDC supply model which is std, use of 240 VAC model is subject to approval)
Electrode: CPS-11D7BA21
Flow chamber (where required): CPA250-A00
Electrode cable: CYK10-A**1
Electrode model variant listed is for standard applications. For non standard applications different model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning.
Design Standards - Preferred Equipment Lists 45
Application/Item Manufacturer Preferred Family/Model Additional Information
Process ORP analysers Endress + Hauser Transmitter: Same family as pH Model variants appropriate to the application
Process Conductivity analysers
Endress + Hauser Transmitter: refer pH Transmitters for detail.
Electrode model dependant on application to be proposed for acceptance for each application by Managers Water and Sewerage Assets Planning.
Process Dissolved Oxygen analysers
WTW - IQ SensorNet Sensor: TriOxmatic 700IQ
Network Display terminal: MIQ/T2020
Network J-box: MIQ/JB
Digital network controller: DIQ/S182 or 2020XT featuring Modbus output.
Additional IQ SensorNet devices and/or model variants for non standard applications, to be proposed for acceptance by Managers Water and Sewerage Assets Planning.
Process Chlorine analysers USF / Wallace & Tiernan Micro2000, model variant as appropriate to the application .
Process Chlorine Gas Detectors
Draeger Polytron 7000 CL2
Process Gas Detectors Draeger For H2S, Combustible gas, Oxygen. Polytron
Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.
No Flow (clean liquid) switches - used to detect loss of sample flow for analytical instrumentation.
IFM-Efector TBA Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.
Proximity Switches IFM-Efector IF5397, 2 wire , 24 VDC PNP or other to suit application.
Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.
Loop powered LCD process indicator, 4 - 20 mA.
TBA TBA Specific make and model to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application. Considerations to include: suitable IP rating, DIN size – use standardized sizes, backlighting requirements, engineering units required to be displayed or factory marked on the indicator.
Pressure Switches United Electric J400 ranges Specific make and model to be proposed for
Design Standards - Preferred Equipment Lists 46
Application/Item Manufacturer Preferred Family/Model Additional Information
IFM-Efector TBC acceptance by Managers Water and Sewerage Assets Planning for each application.
Temperature Switches United Electric
IFM-Effector
F300 ranges
TBC
Specific make and model to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.
Vibration Accelerometer Rockwell Automation - Entek
General purpose Accelerometer model 9000A, Pt. No. EK-43781L
For use with Rockwell Automation - Entek XM series Vibration Modules.
Temperature Transmitter ABB PT100 – TH02 Or other make and models depending on application to be proposed for acceptance by Managers Water and Sewerage Assets Planning
I/P Converter ABB TEIP11 18311 182110100 Or other make and models depending on application to be proposed for acceptance by Managers Water and Sewerage Assets Planning
General instrumentation signal convertors and isolators including R/I convertors
Weidmuller Mann Series Process Instruments For example ITX Plus range. Range and specific model to be selected to suit specific application.
Design Standards - Preferred Equipment Lists 47
22. Water and Sewerage Networks - Telemetry Electrical and Instrumentation PEL Addendum for Simple Sites
The items of preferred telemetry, electrical and instrumentation equipment additional to the Complex Sites for the Simple Sites are as detailed below. Where this section 22 differs with sections 18 to 21, then this section 22 takes precedence at Simple Sites.
Application/Item Manufacturer Preferred Family/Model Additional Information
DC Power Supply – Battery Charger
RF Industries SME240-12-10 Use power contact to signal power failure.
Battery required for non-UPS backed sites. Battery to be sized to suit load.
DC/DC Single Output Converter 12 VDC to 24 VDC
Powerbox PBIH-1224M
(Bracket: F-P100-1)
Converter to provide 24 VDC power to PLC from 12 VDC supply.
DC Power Supply -240 VAC to 24 VDC at 4.5 amps
Powerbox PBB2OC-24M
(Bracket: FD-A)
For use with larger sites where a dedicated 24 VDC 4.5 amp power supply unit is required.
DC Power Supply -240 VAC to 24 VDC at 6.5 amps
Powerbox PBB2OC-24R
(Bracket: FD-A)
For use with larger sites where a dedicated 24 VDC 6.5 amp power supply unit is required.
RTU Rockwell Automation
ML1400
1766-L32BXB 24 VDC supply. Special purpose IO points.
RTU - AI module Rockwell Automation 1762-IF4 4 way analogue input module 4-20 mA
RTU - AO module Rockwell Automation 1762-OF4 4 way analogue output module 4-20 mA
RTU - DI module Rockwell Automation 1762-IQ16 16 way digital input module
RTU - DO module Rockwell Automation 1762-OW16 16 way digital output module
Signal Converters Weidmuller
(Mann Industries)
ITX Plus series Loop powered, multi input, 4-20 mA output.
Design Standards - Preferred Equipment Lists 48
Application/Item Manufacturer Preferred Make/Model Additional Information
Valve Actuators Rotork IQ3 series Additional modules required: Modbus RTU communications.
Status signals required:
Open limit, close limit, MR, actuator alarm, Over torque trip.
Controls needed:
Open, Close.
Submersible Pump Seal Fail Relay
ITT Flygt Minicas II (24Vac/dc) This device is usually ordered with its respective pump, so the exact make and model are subject to final pump choice and is required to be proposed for acceptance by Managers Water and Sewerage Assets Planning.
Float switch (non mercury type)
ITT Flygt ENM-10 Replaces ENH-10.
Required to come with 20 m integral cable.
Pressure Switch United Electric 400 Series, Type J400
Model to suit application
Adjustable set point ranges. Site specific selection of equipment range is required.
½ “ NPTF connection.
Ranges: 300 inches water column vacuum to 250 inches water column vacuum (-746.7 to 622.3 mbar)
Pressure: 30 inches Hg vacuum to 6000 psi
(-1.0 to 413.7 bar)
Differential Pressure: 1 inches water column differential to 200 psi differential
(2.5 mbar to 13.8 bar)
Differential Pressure Switch United Electric 400 Series, Type J400K Adjustable set point ranges. Site specific selection of equipment range is required.
½ “ NPTF connection.
Differential Pressure: 3 to 100 psi differential
(0.2 to 6.9 bar differential)
Design Standards - Preferred Equipment Lists 49
Application/Item Manufacturer Preferred Make/Model Additional Information
Temperature Switch United Electric 400 Series, Type B400
Model to suit application
Adjustable set point ranges. Site specific selection of equipment range is required.
Stainless steel immersion stem.
Temperature ranges: -180 to 650 °F
(-117.8 to 343.3°C)
Submersible Pump Thermistor Relay
Schneider LT3-SM00ED (24 Vac)
UPS Powerware PW9130
AS400MS relay card “Management
Card Contact &
RS232 / Serial” for expansion options. Part number 3400390200.
Notes:
1. Cable #1838795 from Element14 (formerly Farnell Electronics) required.
2. Do not use AS400BD relay card.
Use Powerware Maintenance Bypass Switch MBS2000SW1 up to 2200 VA or MBS3000SW1 up to 3000 VA.
Simple Sites that include revenue metering to have 24 hours UPS backup for MagMaster meter power supply.
Other Simple Sites to have 4 hours UPS backup.
UPS to be double conversion type.
Additional option relay card must be included to provide:
UPS On Battery, Low Battery, UPS Operational and UPS bypassed as a minimum.
DC battery backed power supply
Powerware APS3 family.
Includes SC200 module, 6 output relays, expansion IO cards, inverters, regulators and DC/DC converters.
Design Standards - Preferred Equipment Lists 50
Application/Item Manufacturer Preferred Make/Model Additional Information
VSD
Danfoss FC202 for up to 110% starting torque
Door mounted HMI.
Ethernet/IP communications to PLC.
External 24 VDC supply option.
ATEX card for hazardous locations.
Safe stop option.
Harmonics, dV/dT and/or Sine filters subject to analysis.
Sine filters must be used with unscreened cables or submersible pumps.
VSD options matrix TBA upon request.
VSD
Danfoss FC302 for up to 160% starting torque
Door mounted HMI.
Ethernet/IP communications to PLC.
External 24 VDC supply option.
ATEX card for hazardous locations.
Safe stop option.
Harmonics, dV/dT and/or Sine filters subject to analysis.
Sine filters must be used with unscreened cables or submersible pumps.
VSD options matrix TBA upon request.
VSD Sine filters Danfoss To match associated VSD size 1. May be required where the pump has integral unscreened flex power cables.
2. May be required when the pump motor has inadequate class insulation to be suitable for use with VSD.
VSD Harmonic filters Danfoss To match associated VSD size May be required subject to location and Electricity Networks direction.
Design Standards - Preferred Equipment Lists 51
Application/Item Manufacturer Preferred Make/Model Additional Information
Motor Softstarter Rockwell Automation SMC - Flex Soft starter may be required by Electricity Networks Service and Installation Rules.
Ethernet/IP option.
Door mounted HMI.
Motor CTs as required.
“Pump Control” option.
Ethernet hub - unmanaged Moxa EDS-208 8 port copper only.
Plastic body.
Media converter (copper to fibre)
Moxa IMC-21-S-SC Single mode fibre.
Managed Ethernet Switch Moxa EDS-508A-MM-SC
Ethernet hub – managed with fibre connections
Moxa EDS-619 CM-600-4TX & CM-600-4SSC option cards to suit.
Singe mode fibre.
FOBOT - Fibre Termination Module – DIN rail mounted
MOLEX Part number to be determined – new product just released.
SC connectors.
12 port, DIN rail mounted.
(FO cable and equipment must be installed by MOLEX certified installer to achieve 25 year warranty)
FOBOT - Fibre Termination Module – DIN rail mounted (To be used until Molex have acceptable a commercial offering)
AFC FDE-12SC1-P
SPLCASS-MS-HD-6/12
Loaded on DIN rail enclosure with 12F SC for patching.
Splice Cassette Mini Stack HD combs with clear lid.
Fibre Optic Cable MOLEX Subject to application.
(AFOLH012OS1 has been used for Telemetry)
Refer BSD fibre optic standards – latest version MUST be used.
(FO cable and equipment must be installed by MOLEX certified installer to achieve 25 year warranty
Design Standards - Preferred Equipment Lists 52
Application/Item Manufacturer Preferred Make/Model Additional Information
Modbus Gateway Moxa MB3170 Where the previous model MB3180 has been used, an Element14 cable #1216699 is required.
Panelview (HMI) – small Rockwell Automation 2711C-T6T
(C600 colour TFT, touch screen)
Ethernet/IP comms support to PLC
Panelview (HMI) - large Rockwell Automation 2711PRDB12C (PVPlus 1250 – cirkey – tch display)
Ethernet/IP communications support to PLC. This display requires the 2711PRP8D to be installed.
Minor Control Equipment Rockwell Automation Pushbuttons 800FP-F range, Latch Mushroom head (red) 800FP-MT4.
LEDs: 800FP-P range.
22 mm Series.
Lamps to be “push to test” for lamp test function.
Lamp colours:
Red: running/open.
Green: stopped/closed.
Amber: fault.
White: available.
Phase Failure Relay Schneider RM35TF30 Provides: asymmetry, phase failure, phase sequence, under and over voltage.
Voltage Monitor Relay – single phase
Schneider RM17UAS15 Provides: under and over voltage measurement.
Circuit breakers – small systems (including reservoirs, gauge stations, valve farms, vent fans)
Schneider GV2 with rotary head (and lock off capability)
Suitable for 3 phase motors.
Circuit breakers – small systems (including reservoirs, gauge stations, valve farms, vent fans)
Schneider C60H with MGN26380 lock off option
Suitable for single phase self contained loads including dosing pumps, small fans.
Pump “no water” sensor
(to be used with electrodes and module mounted in pump.)
Hawk Measurement Systems
Gladiator Admittance Switch – Smart Probe
AS2100BS212TN
05XPO5
To be used with Pleuger Pumps that are fitted with suitable threaded spigot in the pump shroud.
Design Standards - Preferred Equipment Lists 53
Application/Item Manufacturer Preferred Make/Model Additional Information
Liquid Level Relay
(to be used with electrodes mounted in pump, module elsewhere.)
Carlo Gavazzi CLD2ET1C230 (240 VAC for use with existing sites where 24 VDC controls are not available)
CLD2ET1CM24 (24Vdc for use in all new sites & site upgrades)
To be used for “no water” detection in Pleuger Pumps that are fitted with factory installed probes in the shroud.
240 VAC unit for maintenance replacement use only.
Water Flowmeters ABB WaterMaster
To have the following:
24 VDC power supply
Modbus RTU communications option installed.
3 off output contacts
Field mounted flow element.
Factory potted cable at the flow element.
Specify cable length to suit the project.
Switchboard mounted flow transmitter.
NATA certified, 5 point calibration (0%, 25%, 50%, 75%, 100%).
Earth rings must always be installed.
Reservoir Level (head pressure)
ABB 266HSHMSBB1E8L5B2S2N4
(replaces ABB 264HSPABB1B2-E5, C/W AR0328 INTERNAL SURGE PROTECTION)
0-600 kPa range.
Loop powered.
4-20 mA
Water main pressure ABB 266HSHPSBB1E8L5B2S2N4
(replaces ABB 264HSPSBB1-E5-B2, C/W AR0328 INTERNAL SURGE PROTECTION)
0-2400 kPa range.
Loop powered.
4-20 mA
Design Standards - Preferred Equipment Lists 54
Application/Item Manufacturer Preferred Make/Model Additional Information
Differential pressure ABB 266DSHFSSA2B1V1E8L5B2S2N4
(replaces ABB 264DSFSSA1B1-V1-E5-B2,C/W AR0328 INTERNAL SURGE PROTECTION)
0-40 kPa range.
Loop powered.
4-20 mA
Pressure Instrument
Manifold
2 valve manifold for isolation and venting
ABB (Oliver) G12FMS/PP Suitable for PEL gauge pressure or absolute pressure switches with 1/2" NPTF connection.
316 SS
Pressure Instrument
Manifold
3 valve manifold for isolation and equalisation
ABB (Oliver) Y34S Suitable for PEL differential pressure switches with 1/2" NPTF 316 SS
Pressure Instrument Manifold
5 valve manifold for isolation, venting and equalisation
ABB (Oliver) Y53S/PP Suitable for PEL differential pressure switches with 1/2" NPTF
316 SS
Intrinsically Safe Barrier – digital input
Pepperl & Fuchs KFD2-SR2-Ex2.W Dual channel model.
Subject to entity concept calculations.
Equivalent make and model can be proposed for acceptance by Managers Water and Sewerage Assets Planning.
Intrinsically Safe Barrier – analogue input
Pepperl & Fuchs KFD2-STC4-Ex1.20
(dual output)
KFD2-STC4-Ex1
(single output)
Current sourcing output, single channel.
Must submit equivalent for acceptance by Manager Water Assets Planning.
Subject to entity concept calculations.
Design Standards - Preferred Equipment Lists 55
Application/Item Manufacturer Preferred Make/Model Additional Information
Flow switch IFM Efector SI6600
EVM003 (10 m cable)
As used in emergency showers.
PNP output.
Small sensor offset from body - use tee to install. Notes:
1. Mounting adapter may be required to adapt Aseptoflex process connection to pipe size.
2. SI2100 now obsolete.
Interposing Relay 24 VDC coil (single pole change over contact)
Finder 385124VACDC
(relay includes integral base)
Use bridging link 93.20 (for ganging).
For use with RTU FET outputs.
Interposing Relay 240 VAC coil (single pole change over contact)
Finder 3851240VACLCS
Use bridging link 93.20 (for ganging).
Notes:
1. Relay includes integral base
2. For use with new RTU’s for existing site upgrades only where control voltage is 240 VDC.
Interposing Relay 24 VDC coil (double pole change over contact)
Finder 56329007424VDC For use with seal fail and overload reset connections.
Relay base to suit Finder 563290074 series relays.
Finder 96.72
Lightning/Surge Protection
(Primary POE)
Erico
TDS1100-2SR-277 per phase or model to suit application.
Typically required after Main Switch. Health contacts to be monitored (any single failure to signal group failure). Supply CB position to be monitored.
Lightning/Surge Protection
(FCPs / L+P switchboard)
Erico
TDS350-TT-277 for 3-phase or TDS150-1SR-277 for 1 phase or model to suit application
Typically required after DB Section Main Switch (where required). Health contacts to be monitored (any single failure to signal group failure). Supply CB position to be monitored.
Design Standards - Preferred Equipment Lists 56
Application/Item Manufacturer Preferred Make/Model Additional Information
Lightning/Surge Protection
(DC Distribution)
Erico
DSD140-2BR-24/48
Lightning/Surge Protection
(BNC Coaxial)
Erico
CSP-BNC-90
Lightning/Surge Protection
(Universal Transient Barrier)
Erico
UTB-30SP UTP-30 used for protection of I/O wiring (where required).
UTB-30 required for all analogue inputs and outputs where instrumentation is located external to the building that the wiring originates from.
UTB-30 required for digital inputs and outputs where field device is installed external to the building that the wiring originates from.
Use of UTB-30S instead of UTB30 requires acceptance of Manager Water Assets Planning.
Lightning/Surge Protection
(RS232)
Erico
DEPRS23299D
(DB9M and DB9F connections)
For use up to 15 VDC signal levels.
To be used with all RS232 communications between RTUs and field devices where device is inserted into DB9 cables.
Lightning/Surge Protection (RS485/RS232)
Erico UTB15SPG
(screw terminals)
For use with up to 15 VDC balanced pair signal lines. To be used where field devices terminate in flying leads.
Lightning/Surge Protection
(RS422, RS485)
Erico
DEPRS42299D 9 VDC balanced signal.
Lightning/Surge Protection
(Ethernet)
Erico
LANRJ45POE RJ45, 100BaseT, Cat 5 Protector. In line connector. Din rail mounting.
Power Connectors (up to 63 amps)
Marechal Socket Outlet: 61 64 013 972
Inlet: 61 68 013 972
Socket Outlet Sleeve: 61 6A 027
Inlet Handle: 61 6A 253 40P
Large loads - including pumps and generators
Design Standards - Preferred Equipment Lists 57
Application/Item Manufacturer Preferred Make/Model Additional Information
Signal connectors Marechal Socket Outlet: 01 M4 081
Inlet: 01 M8 081
Socket Outlet Sleeve: 01 NA 027
Inlet Handle: 01 NA 253 32P
Small loads - including flow switches, no water probes, water jacket PT100’s
Ultrasonic Level Switch Siemens Pointek ULS200 (Milltronics) 2 internal programmable relays.
24 VDC powered.
Ultrasonic Level Instrument Siemens SITRANS (Proble LU) HART 7ML5221
4-20 mA output.
Wall Temperature Sensor Siemens SYMARO QAA2017 4-20 mA output.
0-50 degrees (default – can be jumper changed).
Smoke detector Firetronics FID-L 12/24 VDC external power, ionisation smoke detector, latching LED indicator.
Vertical float switch PDL (Schneider) FS5 (float switch assembly) 20 amp contact, 2.7 m line, weight, stops and float.
Ethernet isolation module Phoenix Contact 2313931 FL ISOLATOR 100-RJ/RJ
2 x RJ45 connectors to allow insertion in line.
Motion Sensor Clipsal Infrascan 750WPR Include external switch to override motion operation.
Fluorescent Luminaires Pierlite Indoors - PWP236
Outdoors – PWP236 fitted with anti vandal mechanisms
For indoor use - maintained fittings required as per Building Code of Australia ratio.
Power Monitor Schneider PM710GM NOTE soon to be discontinued.
240 Vac supply, class 1 measurement, with Modbus-485 communications.
Power Monitor Schneider PM5320 24 Vdc supply, class 0.5 measurement. With Modbus TCP communications.
Power monitor Carlo Gavazzi EM2172DAV53XOSX (EM21 energy meter 5A RS485)
Use with CT’s XXX/5. Quantity = 3 Use with 282CT1 CT Test/disconnect terminals. Quantity = 3.
Design Standards - Preferred Equipment Lists 58
Application/Item Manufacturer Preferred Make/Model Additional Information
To be used in site retrofits (not switchboard replacements)
Design Standards - Preferred Equipment Lists 59
Part D - Water and Sewerage Networks - Mechanical Equipment PEL
The mechanical items of preferred equipment for the Water and Sewerage Networks that are yet to be identified will be updated in the PELs as product acceptances are made by Icon Water. In the absence of PELs for required mechanical products and materials, mechanical products and materials proposed for specific Icon Water projects shall be subject to the acceptance of the Manager Water Assets Planning for the specific Water Network projects and the Manager Sewerage Assets Planning for the specific Sewerage Network projects.
23. Water Network - Pump Sets and Materials Handling
24. Sewerage Network - Pump Sets and Materials Handling
25. Sewerage Network - Foul Air Fans and Odour Scrubbers
26. Water and Sewerage Networks - Cranes Ventilation Fans and Generators
Design Standards - Preferred Equipment Lists 60
Part E – Water and Sewerage Networks – Work at Height PEL
27. Fall Protection Equipment
AS/NZS 1891.1 – Industrial fall arrest systems and devices – Harness and ancillary equipment Icon Water Standard Drawing Numbers -
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Load
Rating Limitations on use
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Upper Offset Mast, Model 8518006AU stainless steel
15 kN
Mast offset reach 762 to 1080 mm
Anchor point height 927 to 1384 mm
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Lower Mast stainless steel, Model 8518002
832 mm mast extension for use only with Advanced System Davit
Combined maximum of two mast extensions
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Lower Mast stainless steel, Model 8518003
1143 mm mast extension for use only with Advanced System Davit
Combined maximum of two mast extensions
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Advanced Three Piece Expandable Base, Model 8518008AU
15 kN
Maximum offset 1080 mm
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Adjustable Barrel Mount Sleeve, Model 8512285
For varying wall thicknesses
Maximum wall thickness 609 mm
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Advanced Vehicle Hitch Sleeve, Model 8514461
Maximum offset 1219 mm offset mast
Design Standards - Preferred Equipment Lists 61
AS/NZS 1891.1 – Industrial fall arrest systems and devices – Harness and ancillary equipment Icon Water Standard Drawing Numbers -
Supplier Brand Name
WSAA Appraisal
Icon Water Acceptance
Nominal Size
Product Load
Rating Limitations on use
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Core mount stainless steel sleeve, Model 8510110
Designed for cored concrete
101.6 mm cored hole
Complete with PVC liner and sleeve cap
Not to be used for new concrete works
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Flush floor mount stainless steel sleeve, Model 8512828
To be used for new concrete work
Designed for cast in place concrete
Complete with PVC liner and sleeve cap
Capital Safety
DBI SALA Project CX10747 Expiry 12Mar16
Not applicable
Emergency Retrieval Sealed Self Retracting Lifeline with stainless steel cable, Model 3400102
4 kN
For raising and lowering personnel
Fall arresting force of 4 kN