65
Design Standards Water Network and Sewerage Network Preferred Equipment Lists ABN 86 069 381 960

Water and Sewerage Networks PEL

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Design Standards

Water Network and Sewerage Network

Preferred Equipment Lists

ABN 86 069 381 960

Design Standards - Preferred Equipment Lists i

Document Authorisation

Author: Principal Engineer Infrastructure Standards Development

Signed:

Date:

Checked by: Manager Technical Advisory and Standards Signed:

Date:

Approved by: General Manager Asset Management Signed:

Date:

Document Revision Control

Version Description of Revision Person Making Issue Date Approval

1 Initial draft for ACTEW review Denis Baker 11Mar14

2 Revision to accommodate internal review and for workshop with internal stakeholders

Denis Baker 28Apr14

3

Updated, reformatted, and incorporate Sewerage Network and changed to Icon Water.

As amended following review workshop input

Denis Baker, Scott Domars, Mark Hendy, Andrew Brick, Anthony Mayer, Megan Cursley

30Jun15

© Icon Water Ltd. This publication is copyright and contains information that is the property of Icon Water Ltd. It may be reproduced for the purposes of use while engaged on Icon Water commissioned projects.

Disclaimer

This document has been prepared for Icon Water Ltd and is used for its purposes. No warranty is given as to its suitability for any other purpose.

Table of Contents

Purpose ...............................................................................................................................................................................................1

Part A - Water Network Hydraulic Products PEL .............................................................................................................................2

1. Pressure Pipelines - Ductile Iron Pipe ...........................................................................................................................................2

2. Pressure Pipelines - Ductile Iron Fittings .......................................................................................................................................4

3. Pressure Pipelines - PVC Pipes .................................................................................................................................................. 10

4. Pressure Pipelines - Polyethylene Pipe and Fittings .................................................................................................................... 11

5. Valves and Installations - Gate Valves ........................................................................................................................................ 12

6. Valves and Installations - Air Valves ............................................................................................................................................ 13

7. Valves and Installations - Butterfly Valves ................................................................................................................................... 13

8. Valves and Installations - Check Valves ...................................................................................................................................... 14

9. Valves and Installations – Fire Hydrants .................................................................................................................................. 14

10. Valves and Installations - Property Service Connections ......................................................................................................... 15

11. Water Network Maintenance Fittings ........................................................................................................................................ 17

Part B - Sewerage Network Hydraulic Products PEL .................................................................................................................... 19

12. Sewerage Network Pipelines - PVC Pipe and Fittings.............................................................................................................. 19

13. Sewerage Network Pipelines - Vitrified Clay Pipe and Fittings ................................................................................................. 23

14. Sewerage Network Pipelines - Polypropylene Pipe and Fittings .............................................................................................. 24

15. Sewerage Network Pipelines - Ductile Iron Pipe and Fittings ................................................................................................... 25

16. Sewerage Network Pipelines - Glass Reinforced Plastic Pipe and Fittings .............................................................................. 26

17. Sewerage Network Pipelines - Sewer Access Pit Components ............................................................................................... 28

Design Standards - Preferred Equipment Lists iii

Part C – Water and Sewerage Networks - Telemetry Electrical and Instrumentation Products PEL ........................................ 29

18. Water and Sewerage Networks - Telemetry Products .............................................................................................................. 30

19. PLC Equipment ........................................................................................................................................................................ 31

20. Water and Sewerage Networks - Electrical Products ............................................................................................................... 36

21. Water and Sewerage Networks - Instrumentation Products ..................................................................................................... 43

22. Water and Sewerage Networks - Telemetry Electrical and Instrumentation PEL Addendum for Simple Sites ......................... 47

Part D - Water and Sewerage Networks - Mechanical Equipment PEL ........................................................................................ 59

23. Water Network - Pump Sets and Materials Handling ............................................................................................................... 59

24. Sewerage Network - Pump Sets and Materials Handling ......................................................................................................... 59

25. Sewerage Network - Foul Air Fans and Odour Scrubbers........................................................................................................ 59

26. Water and Sewerage Networks - Cranes Ventilation Fans and Generators ............................................................................. 59

Part E – Water and Sewerage Networks – Work at Height PEL .................................................................................................... 60

27. Fall Protection Equipment ........................................................................................................................................................ 60

Design Standards - Preferred Equipment Lists 1

Purpose

The purpose of these Preferred Equipment Lists (PELs) is to identify products that have been accepted by Icon Water for use in the Water and Sewerage Networks and to outline any limitations on their use. These PELs are divided in parts that reflect different engineering disciplines that Icon Water has categorised products into. These PELs form part of the Icon Water Design Standards required by the Water and Sewerage Network (Design and Maintenance) Code made under the Utilities (Technical Regulation) Act 2014 which requires Icon Water Ltd to develop, maintain and implement design standards for the Water Network and the Sewerage Network. The Icon Water PELs form part of the design standards and must be read in conjunction with all of the documents that make up the Icon Water Design Standards for the Water Network and the Sewerage Network including Standard Specifications and Standard Drawings. Additional products may be accepted for use after an assessment of the product’s suitability for use in accordance with the Icon Water Design Standards Products and Materials Acceptance Application Guide. In the absence of specific, proposed products and materials for specific projects being in the PELs, these additional products and materials shall be subject to the acceptance by the Manager Water Assets Planning for the Water Network and the Manager Sewerage Assets Planning for the Sewerage Network. Such acceptances for a specific project will not be considered as a precedent for other projects or for general acceptance by Icon Water.

Design Standards - Preferred Equipment Lists 2

Part A - Water Network Hydraulic Products PEL

1. Pressure Pipelines - Ductile Iron Pipe

WSA PS–200 Ductile Iron Pipe for Water Supply and Sewerage AS 2280 – Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA Appraisal Icon Water Approval

CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010

Nominal

Size Product

Pressure Rating

Limitations on use

DN100 – DN750

Ductile Iron Pressure Pipe Product Codes C302.10, C302.15, C302.2, C302.30, C302.37, C302.45, C302.50, C302.60, C302.75

PN16 DN200 and DN250 not approved for use in the

Water Network

Polyethylene sleeving required for pipes when installed in the ground.

No direct tapping for service connections is permitted.

C301.10 SC, C301.15 SC, C301.22 SC, C301.30 SC, C301.37, C301.45, C301.50, C301.60, C301.75

PN35

Design Standards - Preferred Equipment Lists 3

Supplier Brand Name WSAA Appraisal Icon Water Approval

Pentair TYTONXCEL PA 10/16.2 Issue 2 18/05/2011 PC162

DN100 – DN750

Ductile Iron Pressure Pipe Product Codes D100XCEL35CSC, D150XCEL35CSC, D225XCEL35CSC, D300XCEL35CSC, D375XCEL35CSC, D450XCEL35CSC, D500XCEL35CSC, D600XCEL35CSC, D675XCEL35CSC

PN35

DN200 and DN250 not approved for use in the Water Network

Polyethylene sleeving required for pipes when installed in the ground.

No direct tapping for service connections is permitted.

Design Standards - Preferred Equipment Lists 4

2. Pressure Pipelines - Ductile Iron Fittings

WSA PS–201 Ductile Iron Fittings for Water Supply and Sewerage AS 2280 – Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010

Nominal Size Product Pressure Rating Limitations on use

DN80-DN750 SO-SO Bends 90°, 45°, 22.5°, 11.25° PN35

DN80-DN750 FL-FL Bends 90°, 45°, 22.5°, 11.25° PN16

DN80-DN750 SP-SP Bends 90°, 45°, 22.5°, 11.25° PN16

DN80-DN600 Hydrant, Washout, Duckfoot and Pedestal Bends

PN16

DN100-DN750 SO-SO-SO Tee PN35

DN100-DN750 SO-SO-FL Tee PN16

DN100-DN600 SO-SP-FL Hydrant Tee PN16

DN450-DN750 FL-FL-FL Tee PN16

DN100-DN750 Scour Tee PN16

DN80-DN750 FL-SO Connector PN16

Design Standards - Preferred Equipment Lists 5

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

CREVET IRONTITE PA 10/08 16/02/2011 Bill Bencke 18/01/2010

Nominal Size Product Pressure Rating Limitations on use

DN80-DN750 FL-SP Connector PN16

DN80-DN750 SO-SO Connector PN16

DN100-DN150 Pretap Connector PN16

DN80-DN100 Hydrant Riser PN16

DN100-DN750 SO-SO Taper PN16

DN100-DN750 SO-FL Taper PN16

DN100-DN750 FL-FL Taper PN16

DN80-DN750 End Cap PN16

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

Pentair Auslite PA 10/16.2 Issue 2 18/05/2011 Bill Bencke 04/12/2006

Nominal Size Product Pressure Rating Limitations on use

DN100-150 SO-SO Bend 90°, 45°, 22.5°, 11.25° PN16

DN100-150 SO-SO-FL Tee PN16

DN100-150 SO-SO-SO Tee PN16

DN100-150 20mm READYTAP FC 4 Tap PN16

Design Standards - Preferred Equipment Lists 6

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

Pentair Auslite PA 10/16.2 Issue 2 18/05/2011 Bill Bencke 04/12/2006

Nominal Size Product Pressure Rating Limitations on use

DN100-150 FL-SO Connector PN16

DN100-150 FL-SP Connector PN16

DN80-DN100 Hydrant Riser PN16

DN100 FL-FL Bend 90° PN16

DN100 SO-FLWash/ Bend 90° PN16

DN80-DN100 SUREFLOW Spring Hydrant PN16

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

Pentair Tyton PA 10/16.2 Issue 2 18/05/2011 PC162

Nominal Size Product Pressure Rating Limitations on use

DN100-DN750 SO-SO Bend 90°, 45°, 22.5°, 11.25° PN16, PN35

DN80-DN750 FL-FL Bend 90°, 45°, 22.5°, 11.25° PN16, PN35

DN100-DN150 FL-SO Washout Bends PN16, PN35

DN100-DN600 FL-FL Duckfoot Bends PN16, PN35

DN225-DN750 SO-SO-SO Tee PN16, PN35

Design Standards - Preferred Equipment Lists 7

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

Pentair Tyton PA 10/16.2 Issue 2 18/05/2011 PC162

Nominal Size Product Pressure Rating Limitations on use

DN225-DN750 SO-SO-FL Tee PN16, PN35

DN100-DN750 SP-SP-FL Tee PN16, PN35

DN100-DN750 FL-FL-FL Tee PN16, PN35

DN100-DN750 SO-SP-FL Hydrant and Air Valve Tee PN16, PN35

DN100-DN750 SO-SO-FL Scour Tee PN16, PN35

DN100-DN750 SO-SO, FL-SO, FL-SP Connector PN16, PN35

DN150-DN750 SO-SO, SO-FL Taper PN16, PN35

DN100-DN750 FL-FL Taper PN16, PN35

DN100-DN150 FL-FL Connector PN16, PN35

DN100-DN750 Integrally Cast Thrust Connector PN35

DN80-DN750 Puddle Flange PN16

DN100-DN150 Blank Flange PN16, PN35

DN100-DN750 End Cap PN16, PN35

Design Standards - Preferred Equipment Lists 8

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

VINIDEX Superlink PA10/09.2 27/05/2011

Nominal Size Product Pressure Rating Limitations on use

DN100-DN375 SO-SO Bends 90°, 45°, 22.5°, 11.25° PN35

DN100-DN375 FL-SO Connector PN35

DN100-DN375 FL-SP Connector PN35

DN100-DN375 SO-SO Connector PN35

DN100-DN150 READYTAP Connector PN35

DN100-DN375 End Cap PN35

DN80-DN100 Hydrant Riser PN35

DN150-DN375 SO-SO Taper PN35

DN100-DN375 SO-SO Connector PN35

DN100-DN375 FL-SO Connector PN35

DN100-DN375 Air Valve and Hydrant Tee PN35

DN100-DN375 Scour Tee PN35

DN100-DN375 SO-SO-SO Tee PN35

DN100-DN375 SO-SO-FL Tee PN35

DN100-DN375 SP-SP-FLTee PN35

DN100-DN375 SO-SO-SO Tee PN35

Design Standards - Preferred Equipment Lists 9

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

VINIDEX Superlink PA10/09.2 27/05/2011

Nominal Size Product Pressure Rating Limitations on use

DN100-DN375 FL-FL Bend PN35

DN100-DN150 Eccentric FL-FL Taper PN35

DN100-DN375 Concentric FL-FL Taper PN35

DN100-DN375 FL-FL-FL Tee PN35

DN100-DN375 SP-SP-FL Tee PN35

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

VINIDEX Superlink II PA06/11 02/2011 Bill Bencke 25/06/2007

Nominal Size Product Pressure Rating Limitations on use

DN100-DN150

SO-SO Bends 90°, 45°, 22.5°, 11.25°

Product Codes 77584 - 77591

PN16

DN100-DN150

SO-SO-FL Tee

Product Codes 77592 - 77596

PN16

DN100-DN150

SO-SO-SO Tee

Product Codes 77597 - 77599

PN16

Design Standards - Preferred Equipment Lists 10

3. Pressure Pipelines - PVC Pipes

WSA PS–209 Polyvinylchloride Modified (PVC-M) Pressure Pipe for Water Supply and Sewerage WSA PS–210 Polyvinylchloride Oriented (PVC-O) Pressure Pipe for Water Supply and Sewerage AS 4441 - Oriented PVC (PVC-O) pipes for pressure applications AS 4765 - Modified PVC (PVC-M) pipes for pressure applications Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA

Appraisal Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

IPLEX PIPELINES

BLUE RHINO PA 10/08 16/02/2011

DN100 – DN375

PVC-M Pressure Pipe

PN16 Series 2

DN200 and DN250 not accepted for use in the Water Network

No direct tapping for service connections is permitted.

IPLEX PIPELINES

APOLLO BLUE

PC137

DN100 – DN300

PVC-O Pressure Pipe

PN16 Series 2

DN200 and DN250 not accepted for use in the Water Network

No direct tapping for service connections is permitted.

Pentair

TUF-FLO

Bill Bencke 16/06/2004

DN100 – DN375

PVC-M Pressure Pipe

PN16 Series 2

DN200 and DN250 not approved for use in the Water Network

No direct tapping for service connections is permitted.

VINIDEX SUPERMAIN Bill Bencke 29/11/2000

DN100-DN375

PVC-O Pressure Pipe

PN16 Series 2

DN200 and DN250 not approved for use in the Water Network

No direct tapping for service connections is permitted.

Design Standards - Preferred Equipment Lists 11

4. Pressure Pipelines - Polyethylene Pipe and Fittings

WSA PS–207 Polyethylene (PE) Pipes for Pressure Applications - Water Supply and Sewerage WSA PS–208 Polyethylene (PE) Moulded Pressure Fittings for Pressure Applications - Water Supply and Sewerage AS 4130 - Polyethylene pipes for pressure applications Icon Water Standard Drawing Numbers -

Polyethylene Pipe

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size Product Pressure

Rating Limitations on use

VINIDEX

DN16-DN63 PE Pressure Pipe PN16

Design Standards - Preferred Equipment Lists 12

5. Valves and Installations - Gate Valves

WSA PS–260 Gate Valves, Resilient Seated for Pressure Applications – Water Supply and Sewerage WSA PS–261 Gate Valves, Metal Seated for Pressure Applications – Water Supply and Sewerage AS 2638.1 – Gate valves for waterworks purposes – metal seated AS 2638.2 – Gate valves for waterworks purposes – resilient seated Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA

Appraisal Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

AVK AVK 17/10/2000 Bill Bencke

DN100 – DN375

Series 57/40 Resilient Seated Gate Valve

PN16

Pentair

AUSLITE 23/09/2007 Bill Bencke

DN100 – DN150

Resilient Seated Gate Valve PN16

TYCO PC162 DN80 – DN600

Resilient Seated Gate Valve Figure 500

PN16

TYCO PC162 DN80 – DN150

Rising Spindle Gate Valve Figure 500R

PN16

TYCO PC162 DN80 – DN100

Metal Seated Gate Valve Figure 400

PN16

Scour valve only

VINIDEX SUPERLINK II 25/06/2007 Bill Bencke

DN100 – DN150

Resilient Seated Gate Valve

PN16

Hygrade Water

Hawle-A PA 06/07

Andreas Marquardt Expiry 24July2015

DN80-DN150

Resilient Seated Gate Valve – flanged. Compliant with AS 2638.2, AS/NZS 4020, AS 4087, AS 4158

PN16 DN200 not approved for use in the Water Network

Hygrade Water

Hawle E2 Resilient Seated Sluice Valve

PA 04/03

Andreas Marquardt Expiry 24July2015

DN100, DN150

Resilient Seated Gate Valve – flanged. Compliant with AS 2638.2, AS/NZS 4020, AS 4087, AS 4158

PN16 DN200 and DN250 not approved for use in the Water Network

Design Standards - Preferred Equipment Lists 13

6. Valves and Installations - Air Valves

WSA PS–265 Air Valves for Pressure Applications - Water Supply AS 4956 – Air valves for water supply Icon Water Standard Drawing Numbers -

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

VENT-O-MAT

VENT-O-MAT

DN80 – DN150

Series RBX Air Valve with test port, valve and valve cap

PN16

Higher pressure rating required for specific application requirements. For PN16 flange compatible with AS 4087 Table B5

7. Valves and Installations - Butterfly Valves

WSA PS–263 Butterfly Valves for Pressure Applications - Water Supply AS 4795 - Butterfly Valves for Water Supply

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair KEYSTONE DN500-DN1050

Double Flanged – Figure 631 Butterfly Valve

PN16

Design Standards - Preferred Equipment Lists 14

8. Valves and Installations - Check Valves

WSA PS–264 Non-Return (Reflux) Valves for Pressure Applications - Water Supply AS 4794 - Non-return valves – Swing check and tilting disc Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA

Appraisal Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair SUPERCHECK PC162 DN100-DN150

Resilient Seated Swing Check Valve

PN16

9. Valves and Installations – Fire Hydrants

WSA PS–267 Hydrant (Spring) for Pressure Applications - Water Supply AS 3952 - Water supply – Spring hydrant valve for waterworks purpose Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA

Appraisal Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair

SUREFLOW PC162 DN80 Spring Hydrant PN16

Design Standards - Preferred Equipment Lists 15

10. Valves and Installations - Property Service Connections

WSA PS–214 Copper (Cu) Property Service Pipes for Pressure Applications - Water Supply WSA PS–310 Tapping Bands – Mechanical for Water Supply WSA PS–313 Clamps – Offtake for Under Pressure Connections AS 1432 - Copper tubes for plumbing, gas fittings and drainage applications AS 2280 - Ductile Iron Pipe and Fittings AS 2638.2 - Gate valves for waterworks purposes – resilient seated AS 3688 - Press fit connector fittings for copper tube Icon Water Standard Drawing Numbers -

Stainless Steel Clamp Offtakes

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure Rating

Limitations on use

Pentair WANG

PC162

DN150-DN300

Single part, 316 stainless steel clamp with BSP threaded offtake (20, 25, 32, 40, 50)

PN16

Clamps shall have at least two studs. Clamp shall not be rotated after it is assembled around the pipe.

PC162

DN100-DN450

Two part, 316 stainless steel clamp with BSP threaded offtake (20, 25, 32, 40, 50)

PN16

80 and above offtake must be flanged. The clamp shall not be rotated after it is assembled around the pipe.

PC162 DN100-DN450

Two part flanged offtake clamp (Flange to AS 4087 Table B5, sizes 80 to 300)

PN16

The clamp shall not be rotated after it is assembled around the pipe.

Design Standards - Preferred Equipment Lists 16

Property Service Water Meters

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure Rating

Limitations on use

Elster Elster PC44W/12 Expiry July 2018

DN20 to DN150

Water Meters (20, 25, 32, 40, 50, 80, 100, 150)

PN16

Property Service Fittings

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure Rating

Limitations on use

Tradelink Plumbing Supplies

Viega Thomas Tyrell 8July13

DN20-DN50

Copper alloy press fit fittings complying with AS 3688 section 10.1 (b)

Use only on hard drawn copper tube complying with AS 1432 Type B.

Property Service Pipe

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure Rating

Limitations on use

Accepted Plumbing Supply Outlets

Bill Bencke 03/03/2009

DN20-DN80

Copper Tube

AS 1432 Type B,

hard drawn

Property Service connections only

Design Standards - Preferred Equipment Lists 17

11. Water Network Maintenance Fittings

WSA PS-201 Ductile Iron Fittings for Water Supply and Sewerage WSA PS-311 Mechanical Couplings – Unrestrained AS 2280 - Ductile iron pipes and fittings AS 4181 - Stainless steel clamps for waterworks purposes Icon Water Standard Drawing Numbers –

Mechanical Couplings

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

CREVET AVK PC192

DN100-DN300

Supa Series 601 Gibault

PN16

Not to be used on new works

Pentair

VARI GIB PC192 DN80-DN600

Gibault PN16 Not to be used on new works

EZI GIB DN100-DN200

Gibault PN16 Not to be used on new works

Hygrade Water

Hawle-Synoflex

PA 06/07

Andreas Marquardt Expiry 20June2016

DN80-DN300

Socket Socket connector Socket Flange connector (AS 4087 Figure B5 flanges)

PN16

Not to be used on new works Coatings and elastomers certified to AS/NZS 4020.

Design Standards - Preferred Equipment Lists 18

Stainless Steel Repair Clamps

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair WANG PC192

DN80-DN225

Single piece, 316 passivated stainless steel repair clamp, minimum 2 studs

PN16

Different DN80 clamp for galvanised and DICL pipe. The clamp must not be rotated after it is assembled around the pipe

Stainless Steel Tapping Clamps

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair WANG PC192

DN100-DN300

Two piece, 316 passivated stainless steel, BSP threaded offtake clamp with minimum 2 studs clamp

PN16

The clamp must not be rotated after it is assembled around the pipe

DN100-DN450

Two part 316 passivated stainless steel, offtake flanged compatible with AS 4087 Table B7, clamp with minimum 4 studs clamp

PN16

The clamp must not be rotated after it is assembled around the pipe

Design Standards - Preferred Equipment Lists 19

Part B - Sewerage Network Hydraulic Products PEL

12. Sewerage Network Pipelines - PVC Pipe and Fittings

PVC not to be used in or within 1 km downstream of industrial areas or hospitals.

WSA PS-230 PVC-U Non pressure pipe and fittings WSA PS-236 Variable bend, post formed PVC-U non pressure fittings AS 1260 PVC-U pipes and fittings for drain, waste and vent applications Icon Water Standard Drawing Numbers -

PVC Pipe

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Pressure

Rating Limitations on use

IPLEX

DN100 – DN225

Plain Wall PVC Pipe (SCJ) SN8

DN300 - DN375

Plain Wall PVC Pipe (RRJ) SN8

Pentair

DN100 – DN225

Plain Wall PVC Pipe (SCJ) SN8

DN100 - DN375

Plain Wall PVC Pipe (RRJ) SN8

VINIDEX

DN100 – DN225

Plain Wall PVC Pipe (SCJ) SN8

DN300 - DN375

Plain Wall PVC Pipe (RRJ) SN8

Design Standards - Preferred Equipment Lists 20

Fittings for PVC Pipe

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

IPLEX

Nominal Size Product Pressure Rating Limitations on use

DN100-DN150 Plain Bends F&F (SWJ) 88°, 45°, 30°, 15°, 5° SN8

DN150-DN375 Fabricated Bends F&F (SWJ) 88°, 45°, 30°, 15°, 5° SN8

DN100-DN150 Plain Bends F&F (SWJ) 88°, 42°, 30°, 22° 15°,11°, 5° SN8

DN150-DN225 Fabricated Bends M&F (SWJ) 88°, 60°, 45° SN8

DN100 – DN150 Plain Junction F&F (SWJ) 88°, 45° SN8

DN225 – DN375 Fabricated Junction F&F (SWJ) 88°, 45° SN8

DN100 –DN225 Plain Coupling (SWJ) SN8

DN300 – DN375 Fabricated Coupling (SWJ) SN8

DN100-DN150 Access Coupling (SWJ) SN8

DN100-DN375 Bend F&F (RRJ) 88°, 45° SN8

DN100-DN375 Bend M&F (RRJ) 88°, 45°, 30°, 15°, SN8

DN100-DN375 Junction F&F (RRJ) 88°, 45° SN8

DN150-DN300 Bend M&F (RRJ) 88°, 45° SN8

Design Standards - Preferred Equipment Lists 21

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

VINIDEX

Nominal Size Product Pressure Rating Limitations on use

DN100 Bend F&F (SCJ) 5° SN8

DN100-DN150 Bend F&F (SCJ) 15° SN8

DN100 Bend F&F (SCJ) 30° SN8

DN100-DN225 Bend F&F (SCJ) 45° SN8

DN100 Bend F&F (SCJ) 60° SN8

DN100-DN150 Bend F&F (SCJ) 88° SN8

DN225 Bend F&F (SCJ) 90° SN8

DN100 Bend M&F (SCJ) 5° SN8

DN100-DN150 Bend M&F (SCJ) 15° SN8

DN100 Bend M&F (SCJ) 30° SN8

DN100-DN150 Bend M&F (SCJ) 43° SN8

DN100 Bend M&F (SCJ) 60° SN8

DN100-DN150 Bend M&F (SCJ) 88° SN8

DN100-DN300 45° Plain Junctions F&F (SCJ) SN8

DN100-DN150 45° Plain Junctions M&F (SCJ) SN8

DN100-DN225 88° Plain Junctions F&F (SCJ) SN8

Design Standards - Preferred Equipment Lists 22

Supplier Brand Name WSAA Appraisal Icon Water Acceptance

VINIDEX

Nominal Size Product Pressure Rating Limitations on use

DN100 88° Plain Junctions M&F (SCJ) SN8

DN225-DN300 Straight Couplings F&F (SCJ) SN8

DN100-DN150 Access Couplings (SCJ) SN8

DN100-DN300 Slip Coupling (SCJ) SN8

DN100 – DN150 Sewer Bend F&F (RRJ) 90°, 88°, 45° SN8

DN100 – DN150 Sewer Bend M&F (RRJ) 90°, 60°, 45° SN8

DN100 – DN300 45° Sewer Junctions (RRJ) F&F SN8

DN150 90° Sewer Junctions (RRJ) F&F SN8

DN150 – DN300 45° Sewer Junctions (RRJ) M&F SN8

DN150 90° Sewer Junctions (RRJ) M&F SN8

DN100 –DN300 Sewer Slip Couplings (RRJ) SN8

DN100 Sewer Straight Couplings (RRJ) SN8

DN100-DN300 Sewer Manhole Couplings (RRJ) SN8

Design Standards - Preferred Equipment Lists 23

13. Sewerage Network Pipelines - Vitrified Clay Pipe and Fittings

WSA PS–231 Vitrified Clay (VC) Pipe and Fittings AS 1741 Vitrified clay pipes and fittings with flexible joints - Sewer quality Icon Water Standard Drawing Numbers - Vitrified Clay Pipe

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pipe Class

Limitations on use

LEAP AUSTRALASIA

HEPWORTH SUPERSLEVE

DN100 – DN300

Socketless Vitrified Clay Pipe

4

Fittings for Vitrified Clay Pipe

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pipe Class

Limitations on use

LEAP AUSTRALASIA

HEPWORTH

DN100 – DN300

Bend 90°, 45°, 30°, 15° 4

DN100 – DN300

Jointing Coupling 4

DN100 – DN300

Jointing ‘O’ Ring 4

DN100-DN300

Curved Square Junction 4

DN100-DN300

Oblique Junction 4

DN100-DN300

Square Junction 4

DN100-DN150

Plug 4

DN100-DN225

Taper 4

Design Standards - Preferred Equipment Lists 24

14. Sewerage Network Pipelines - Polypropylene Pipe and Fittings

Polypropylene not to be used in or within 1 km downstream of industrial areas or hospitals.

WSA PS-242 Polypropylene (Ribbed Construction) Non-Pressure Pipe and Fittings AS/NZS 5065 Polyethylene and polypropylene pipes and fittings for drainage and sewerage applications Icon Water Standard Drawing Numbers -

Polypropylene Pipe

Supplier Brand Name

WSAA Appraisal

Icon Water acceptance Nominal Size Product Stiffness Rating

Limitations on use

VINIDEX SewerPRO Approval- Peter Szlapinski 10/09/2008 DN150 –

DN600 Polypropylene Pipe

SN8 6 metre lengths only.

Fittings for Polypropylene Pipe

Supplier Brand Name WSAA Appraisal Icon Water acceptance

VINIDEX SewerPRO Approval- Peter Szlapinski 10/09/2008

Nominal Size Product Stiffness Rating Limitations on use

DN150 – DN600 Coupling SN8

DN150 – DN600 Slip Coupling SN8

DN150 – DN375 Adaptor Coupling SN8

DN150 – DN600 45° Junction SN8

DN150 – DN600 88° Junction SN8

DN150 – DN600 Tee SN8

DN150 – DN600 Inspection Tee SN8

DN150 Bend M-F SN8

DN150 – DN600 45° Bend F-F SN8

DN150 – DN600 90° Bend F-F SN8

DN150 – DN600 Push On Cap SN8

DN300 – DN600 Shorts SN8

Design Standards - Preferred Equipment Lists 25

15. Sewerage Network Pipelines - Ductile Iron Pipe and Fittings

WSA PS-200 Ductile Iron Pipe for Water Supply and Sewerage AS 2280 Ductile iron pipes and fittings Icon Water Standard Drawing Numbers -

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair TYTONXTREME DN100 – DN600

Ductile iron pressure pipe with calcium aluminate

cement lining PN20

Ductile Iron Pipe Fittings

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pressure

Rating Limitations on use

Pentair Tyton Joint

DN100-DN600

SO-SO Bends 90°, 45°, 22.5°, 11.25° End Cap SO-SO Taper SO-SO-SO Tee SO-SO-FL Tee SP-SP-FL Tee FL-FL Bend FL-FL-FL Tee SP-SP-FL Tee

PN35 All fittings shall be bonded polymeric coated

Design Standards - Preferred Equipment Lists 26

16. Sewerage Network Pipelines - Glass Reinforced Plastic Pipe and Fittings

GRP not to be used in or within 1 km downstream of industrial areas or hospitals.

WSA PS–205S Filament Wound Glass Reinforced Plastics (FW-GRP) Pipes and Fittings for Pressure and Non-Pressure Applications - Sewerage AS 3571.1 Plastics piping systems - Glass reinforced thermoplastics (GRP) systems based on unsaturated polyester (UP) resin Part 1: Pressure and non-pressure drainage and sewerage Icon Water Standard Drawing Numbers - GRP Pipe

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pipe

Rating Limitations on use

GLOBAL PIPE

HOBAS SEWERLINE

DN300 – DN675

Centrifugally Cast GRP Non-Pressure Pipe

SN10000

IPLEX

FLOWTITE GRP

DN375 – DN675

Filament Wound GRP Non-Pressure Pipe

SN10000

GRP Pipe Fittings

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pipe

Rating Limitations on use

GLOBAL PIPE

HOBAS SEWERLINE

DN300 – DN675

Coupling

DN375 – DN675

Access Chamber Connector

DN300 – DN375

Saddle Tee Junction

DN300 – DN375

45° Slope Junction

DN300 – DN600

Tees

DN300 – DN675

Bends

Design Standards - Preferred Equipment Lists 27

GRP Pipe Fittings

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Pipe

Rating Limitations on use

IPLEX

FLOWTITE GRP

DN375 – DN675

Coupling

DN375 – DN675

Access Chamber Connector

DN300 – DN375

Saddle Tee Junction

DN300 – DN375

45° Slope Junction

DN300 – DN600

Tees

DN300 – DN675

Bends

Design Standards - Preferred Equipment Lists 28

17. Sewerage Network Pipelines - Sewer Access Pit Components

WSA PS-290 Access Covers for Water Supply and Sewerage to AS 3996 WSA PS-323 Maintenance Holes – Precast Concrete AS 3996 Access Covers and Grates AS 4198 Precast Concrete Access Chambers for Sewerage Applications

Icon Water Standard Drawing Numbers -

Access Covers and Frames

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Relevant

Documents Limitations on use

GATIC GATIC

DN900 Circular Solid Top Ductile Iron Access Cover and Frame Class B and D

Class B non-trafficable areas Class D trafficable areas

915x915

Square Concrete Infill Ductile Iron Access Cover and Frame Class D

Class D trafficable areas

Precast Access Chamber Components.

Supplier Brand Name WSAA

Appraisal Icon Water acceptance

Nominal Size

Product Relevant

Documents Limitations on use

PREMIER PRECAST

PC58 DN1015 Chamber Height 350, 525, 700, 1050 mm

Not to be used if vehicle access unavailable for Section 27 Vehicle Hitch Mount Sleeve Model 8514461.

Design Standards - Preferred Equipment Lists 29

Part C – Water and Sewerage Networks - Telemetry Electrical and Instrumentation Products PEL

Icon Water may choose to free issue telemetry, electrical and/or instrumentation equipment to a contractor. Whether the equipment is issued to a contractor or is supplied by a contractor, the following shall apply:

1. In many of the telemetry, electrical and/or instrumentation equipment categories, Icon Water has established formal Period Contracts for the supply and delivery of equipment within that broad category. While Icon Water has nominated specific preferred units or items within that category, the conditions of the Period Contracts allow access to other equipment ranges or families within that broad category, i.e. special, innovative or non standard solutions may be more appropriate.

2. The following preferred telemetry, electrical and/or instrumentation equipment listings shall include all associated accessories and ancillary devices applicable to the primary equipment within that category whether individually listed or not.

3. Where Icon Water is to free issue nominated equipment and devices this will be specified in the project specification. Accordingly, design consultants and contractors are required to provide to Icon Water, within an appropriate timeframe considering equipment lead times; a comprehensive Bill of Materials (BOM) of all telemetry, electrical and/or instrumentation equipment required to be free issued. The BOM shall include ALL accessories and ancillary items necessary to complete the required works independent of how small or minor. If an item is not identified in the BOM it will not be ordered for free issue. Responsibility for delays resulting from the omission of items from the BOM shall rest solely with the design consultant or contractor or originator of the BOM.

4. Sections 18 to 21 inclusive of this PEL apply to the Complex Sites in the Water Network. Section 22 is an addendum that applies to the Simple Sites in the Water Network. The definition of Complex Sites and Simple Sites is given in the Icon Water Standard Specification - O&M Manuals. Where section 22 conflicts with sections 18 to 21, then section 22 takes precedence at Simple Sites.

Design Standards - Preferred Equipment Lists 30

18. Water and Sewerage Networks - Telemetry Products

Telemetry Application and Software

SCADA System Software: SCADA System Paging Module: Operating System - SCADA Server: Operating System - Data/Report Server: Operating System - SCADA Workstation: Reporting Software:

Citect For Windows, Version TBA upon request Citect Alarm Paging Module, Version TBA upon request TBA upon request TBA upon request TBA upon request TBA upon request

Telemetry Hardware Configurations

Main I/O Servers Reporting/Data Server Operator Workstations

To Be Advised upon request – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}

Networking Hardware

Ethernet Hub: Ethernet Router: Ethernet Switch:

Firewall Device:

To Be Advised upon request To Be Advised upon request To Be Advised upon request

FortiGate (Model To Be Advised upon request)

Radio Hardware

DDRN:

Schneider Electric – Trio ER45e – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}

Microwave:

To be Advised – {generally this hardware will be supplied/ordered through ActewAGL Business Systems}

Design Standards - Preferred Equipment Lists 31

19. PLC Equipment

The preferred supplier for PLC Control System equipment for Complex Sites in the Water Network is Rockwell Automation Australia. The following equipment and networking protocols are the preferred equipment and configurations for PLC Control Systems at Complex Sites in the Water Network.

Application/Item Manufacturer Preferred Family/Model Additional Information

Zone PLC/Main Functional Area PLC’s Rockwell Automation ControlLogix

PLC – SCADA System Network - EtherNet

PLC – SCADA System ethernet Network switch:

Moxa Technologies EDS-508A-MM-SC If port count exceeded, then use Moxa EDS-619 switch with relevant CM-600 interface modules

Ethernet Media Converter Moxa Technologies IMC-101-M-SC 10/100BaseTX to 100BaseFX converter, multi mode.

PLC – SCADA Network Rockwell Automation EtherNet/IP

PLC – PLC – Zone PLC Network: Rockwell Automation ControlNet (under review, may change to EtherNet)

Dual Redundant Fibre Optic

PLC – Field Distributed I/O Network: Rockwell Automation ControlNet

PLC – MCC Distributed I/O Network (and miscellaneous drives and field equipment)

Rockwell Automation DeviceNet Utilising KwikLink Flat Media Cabling System

MCC Distributed I/O Hardware: Rockwell Automation DeviceNet Starter Auxiliary Flex I/O Combo modules to be used if DeviceNet Starter Auxiliary not appropriate

Field Distributed I/O Hardware: Rockwell Automation Flex I/O

Design Standards - Preferred Equipment Lists 32

Specific PLC Applications

The following equipment items are the preferred equipment items in their specific application:

Zone PLC/Main Functional Area PLCs

Application/Item Manufacturer Make/Model Additional Information

ControlLogix Chassis/Rack

Rockwell Automation

1756-Axx where xx refers to no. of slots.

Rack size appropriate to application plus spare capacity, refer this Std.

ControlLogix 24VDC Power Supply Rockwell Automation

1756-PB72

ControlLogix 1756 Controller / Processor Rockwell Automation

1756-L7x - where x is the code number that relates to memory capacity.

Unless otherwise specified the processor shall be the 1756-L73 (8MB)

Panel Mount Battery Module Rockwell Automation

1756-BATM

Redundant Media ControlNet Bridge Rockwell Automation

1756-CNBR Dual Redundant Fibre Optic Cable network

Single Media ControlNet Bridge Rockwell Automation

1756-CN2

DeviceNet Bridge Rockwell Automation

1756-DNB

Modbus Protocol Converter Prosoft 1756-MCM

EtherNet Bridge Rockwell Automation

1756-EN2TR

Fibre Optic Modem Rockwell Automation

1786-RPA + 1786-RPFM Not rack/chassis mounted – generally mounted within Fibre Optic Termination Cubicle or equivalent.

Design Standards - Preferred Equipment Lists 33

MCC Distributed I/O

Application/Item Manufacturer Make/Model Additional Information

DeviceNet Starter Auxiliary modules (4x DI / 2 x DO)

Rockwell Automation

100-DNY42R Preferred configuration

FlexIO 10x DI / 6x DO Combo Module Rockwell Automation

1794-IB10XOB6 Non-preferred configuration - only applicable when multiple starter auxiliaries are not practical. This has been used within MCC main incomer cell. For terminal base details, refer FDIO components.

DeviceNet Kwiklink Network Cabling - Trunk

Rockwell Automation

DeviceNet Class 1 Flat Cable 1485-CP1E

For field DN networks, e.g. actuators, use of thick round trunk cable in combination with junction boxes is preferred. Pt. No. 1485C-P1Axx

Network Cabling – Drop cables Rockwell Automation

1485K-P1F5-C (1m drop cable)

1485K-P6F5-C (6m drop cable)

Network Connections Rockwell Automation

1485P-P1E4-R5 (IP67 Micro Module & Base)

1485A-T1E4 (IP67 Terminator & Base)

1485P-P1H4-T4 (Open Style module & Base)

Lower IP rating is acceptable within MCC or other panels with min IP54 rating. At Stromlo, 1485P-P1H4-R5 was installed.

Open style module used only for DeviceNet network power supply connections.

Design Standards - Preferred Equipment Lists 34

Field Distributed I/O (FDIO cubicles)

Application/Item Manufacturer Make/Model Additional Information

Flex I/O ControlNet Communications Adapter Rockwell Automation 1794-ACN15 + plus tap

Flex I/O EtherNet Communications Adapter Rockwell Automation 1794-AENTR

Flex I/O DeviceNet Communications Adapter Rockwell Automation 1794-ADN

Flex I/O 3-wire Terminal Base Unit Rockwell Automation 1794-TB3

Flex I/O Fused Terminal Base Unit Rockwell Automation 1794-TBNF Used with 1794-OW8 output module

Flex I/O Temperature Terminal Base Unit Rockwell Automation 1794-TB3T Used with Thermocouple inputs.

Flex I/O 16pt sink Digital Input Module Rockwell Automation 1794-IB16 Preferred for Digital Inputs

Flex I/O Fused Relay Sink/Source Digital Output Module

Rockwell Automation 1794-OW8 Preferred for Digital Outputs.

Flex I/O 16pt Digital Output (with current limiting)

Rockwell Automation 1794-OB16P Not preferred.

Flex I/O 24VDC 4pt Isolated Analog Input Module

Rockwell Automation 1794-IF4I

Flex I/O 24VDC 4 pt Isolated Analog Output Module

Rockwell Automation 1794-OF4I

Flex I/O 24VDC 2pt in/2pt out Analog Combo Module

Rockwell Automation 1794-IF2XOF21 Applicable when only one output required

Flex I/O 24VDC 8pt RTD Input Module Rockwell Automation 1794-IT8

ControlNet to Devicenet Rockwell Automation 1788-CN2DN

EtherNet to DeviceNet Rockwell Automation 1788-EN2DN

ControlNet to Modbus Prosoft MVI-94-MCM

Design Standards - Preferred Equipment Lists 35

Field Distributed I/O (FDIO cubicles)

Application/Item Manufacturer Make/Model Additional Information

Entek XM-120 Vibration Module Rockwell Automation - Entek

1440-VST02-01RA

Entek XM-940 Terminal Base to suit Vibration Module

Rockwell Automation - Entek

1440-TB-A

ControlNet Taps Rockwell Automation 1786-TPYS (Y Tap)

1786-TPYR (Y Tap with right angle end)

1786-TPR (T Tap)

1786-XT (Coax terminator)

TPYS used for connection to 1756-CNB/R modules.

TPYR used for connection to ACN15.

TPR used where coax surge suppression needs to be fitted.

Field Operator Interface Panels

Application/Item Manufacturer Preferred Item Additional Information

Panelview Plus 12" Colour TouchScreen with EtherNet Interface

Rockwell Automation

2711PRDB12C (currently under review – may go to industrial PC)

PanelPC VersaView 17” TFT, Touch Screen, Win7, HMI

Rockwell Automation

6181P-17A2SW71AC Embedded ethernet port (currently under review – may go to industrial PC)

Design Standards - Preferred Equipment Lists 36

20. Water and Sewerage Networks - Electrical Products

Application/Item Manufacturer Preferred Make/Model Additional Information

Motor Control Centres B&R Enclosures Signature SE series, demountable cells (i.e. use of bus plugs), min. cell size - 2. Form 3B minimum.

Unless otherwise accepted by Manager Water Assets Planning.

Refer also MCC Standard drawings and LMW 8.02 S012.

Intelligent Motor Protection Relays (MPR) E3+ range

Rockwell Automation

E3 PLUS: 193-EC2nn range for motor size range up to and including 33 kW model. 193-EC5nn range (provides voltage and power monitoring functions) for motors above 33 kW where ‘nn’ refers to specific size or rating.

Model and firmware revision to be accepted by Managers Water and Sewerage Assets Planning.

MV/HV MPR Schneider Areva T&D Micom P241*********** (typical P241111A2M0320C)

LV Switchgear (not including LV Distribution Centres and MCBs):

Schneider Up to 250 amps:

MCCB: Compact NSX system 100/160/250H featuring TM_D and MA trip units.

NS80H magnetic only motor protection Circuit Breakers up to 37 kW may be approved for use by Managers Water & Sewerage Assets Planning based on specific application.

TeSys GV2P or L for smaller motor circuit protection – use to be approved by Managers Water & Sewerage Assets Planning based on specific application.

Above 250 amps:

Compact NSX system 400/630H featuring MicroLogic trip unit (model to be accepted by Managers Water and Sewerage Assets Planning for each specific application)

Masterpact NT and NW range featuring

Motor Circuit Breakers – use NS80H for small motors.

Design Standards - Preferred Equipment Lists 37

Application/Item Manufacturer Preferred Make/Model Additional Information

MicroLogic trip unit. Model of circuit breaker and trip unit to be accepted by Managers Water and Sewerage Assets Planning for each specific application.

Load Break Switches / Isolators – Interpact INS range.

LV Motor Starter & control Equipment:

Schneider Contactors (<150 Amps): LC1-D range

Contactors (>150 Amps): LC1-F range

Bi-metallic TOL: LRD range

Thermistor Relay: LT3SA00MW

Phase Failure Relays: RM17TE004 or RM35TF30

Miniature control relays: RXM4AB2** range

Contactors generally with 240 V 50 Hz coils. Surge suppression modules to be provided if supplied from UPS.

Contactors to be fitted with LA4Dxx relay interface modules where possible.

Any 24 VDC coil relays to be provided with diode protection.

LV Electronic Soft Starters: Rockwell Automation Bulletin 150

SMC-Flex series

Generally 24 VDC control supply required for Soft starters (cooling fan supply may be a separate 240 VAC supply).

Accessories to the match specific application including but not limited to EtherNet or DeviceNet communications adapter, local HMI, transient protection modules.

LV VVVF Drives: Danfoss

FC302 for up to 160% starting torque Or

FC202 for up to 110% starting torque.

Accessories to match the specific application and Icon Water requirements including but not limited to DeviceNet or EtherNet communications c/w DC standby capability, Harmonic and Sine filters, and extended I/O functionality

Range and model as appropriate to the specific application.

LV Distribution Centres & MCBs

Schneider MB,MD Series Enclosures Multi 9 MCBs shall be used for Auxiliary items supplied from MCC compartments,

Design Standards - Preferred Equipment Lists 38

Application/Item Manufacturer Preferred Make/Model Additional Information

MSC or MBB Series Chassis *

Acti 9 iC60H, NG125H MCBs. Acti 9 iC60 RCBO 10 kA or Vigi to suit iC60 type AC for 3ph+N RCD.

however, cascade/current limiting protection of the unit is required with the main isolator or circuit breaker

* For Essential power and UPS Distribution Board applications use of MGB Isobar chassis is required unless otherwise specifically accepted for each application by Managers Water and Sewerage Asset Planning.

Field Enclosures and Start/Stop Stations

Rockwell Automation LCS enclosures:

800F-nP (Poly Carbonate) for indoor applications unless there is risk of mechanical damage in which case refer to outdoor requirements.

800F-nM (cast metal) or 800F Stainless Steel where exposed to UV or where increased mechanical protection is required

Where ‘n’ in the part number is number of holes.

Where chemical compatibility is an issue then enclosure material to be appropriate to the application

Minor Control Equipment Rockwell Automation Pushbuttons - 800FP-F range.

Latch or E-Stop - 800FP-MT44 or MP44

Pilot lights - 800FP-Px (C/w separate LED cluster type bulb e.g. 800E-N157R)

Selector switches: 800FP-S range

Volt/Current Selector switch and actuator: 194L-E12 range + 194L-HC range

Icon Water may specify exceptions to the standard requirements dependant on project application.

Design Standards - Preferred Equipment Lists 39

Application/Item Manufacturer Preferred Make/Model Additional Information

Voltmeter, Ammeters, CTs, and Current Transducer

Rockwell Automation

Powermonitor 1000 or 5000 series.

Typical models include;

- Bulletin 1408-TR2A-ENT

- Bulletin 1426-M6E-A or 1426-M6E-DNT-A

The type and specific model of Powermonitor 1000 or 5000 including data communications interface and other options and accessories to be submitted for acceptance by Managers Water and Sewerage Assets Planning for each specific application.

Or

Crompton

Or

Voltmeter: 244 Series

Ammeter/MDI: 244 Series

CTs: MA5H class 1.

Current Transducers: 252 series with 4-20 mA output

The use of voltmeters, ammeters and current transducers will typically only be accepted for basic and low power applications.

Lightning/Surge Protection Erico

Primary POE, Main Switchboards, MCCs: TDS1100-2SR-277 per phase or model to suit application.

FCPs / L+P switchboard AC: TDS350-TT-277 for 3-phase or TDS150-1SR-277 for 1 phase or model to suit application

DC Dist: DSD140-2BR-24/48

BNC Coaxial: CSP-1BNC-90

Universal Transient Barrier: UTB-30

UTP-30 used for protection of DeviceNet, as well as PLC 24 VDC I/O wiring (where required).

UTB-30 required for all analogue inputs and outputs where instrumentation is located external to the building that the wiring originates from.

Use of UTB-30S instead of UTB30 requires accepted by Managers Water and Sewerage Assets Planning.

Terminals

Schneider NSYTRV Range (Colour Grey for std terminals)

Power & Control: NSYTRV range – min size 6mm width i.e. NSYTRV42

Instrumentation: NSYTRV42ST

Fuse Terminals: NSYTRV42SF5

Earth Terminals: NSYTRVxxPE range

For the Instrumentation terminals, accepted alternatives are:

- Phoenix UK5-MTK-P/P

- Weidmuller WTR 4 STB, Pt. No. 7910210000

Design Standards - Preferred Equipment Lists 40

Application/Item Manufacturer Preferred Make/Model Additional Information

Uninterruptible Power Supplies (UPS)

Eaton 9155 and 9130 ranges. Specific model to be selected based upon application requirements and each application accepted by Managers Water and Sewerage Assets Planning.

Refer also LMW 8.02 S019. UPS arrangement including batteries, mechanical by-pass unit, battery charger, cabinet design, refer existing Complex Sites UPS installations and standard drawings.

DC Power Supplies - battery backed

Eaton APR24-3G / ES Rectifiers

SC200 Controller Batteries – 6TJ9 Monoblocs

DC Power Supplies - DC/DC and AC/DC non battery backed

Powerbox

DC/DC Converter 5A or 7A: PB1H24-24M or -24R

AC/DC power supplies: PBB20C 24 series.

DC/DC converter used to supply DeviceNet, 1794 - Flex I/O analogue input and output modules and communications modules such as 1794-ACN15s and AENT. Use of Rockwell Automation Bulletin 1606-XL** only where specifically accepted by Managers Water and Sewerage Assets Planning.

Cable and Wire markers

Grafoplast and Brady Cable Markers: Grafoplast SI2K series – yellow backgound, black text minimum of 5 mm high font (Do Not Condense text), UV stabilised sleeves and cable ties.

Wire number sleeves: Grafoplast sleeves

Wire number markers: Black text, white background. Min. font size 6 (point size 10, approx. 2.5mm high). Grafoplast medium sized number markers, correct sized sleeves OR Brady insert labels.

Enclosures and Junction Boxes – General Purpose - process area

B&R Enclosures Connector TE series - 316 Stainless Steel.

Each variation from the preferred makes and model to be accepted by Managers Water and Sewerage Assets Planning. All J/boxes, enclosures to be supplied with

Design Standards - Preferred Equipment Lists 41

Application/Item Manufacturer Preferred Make/Model Additional Information

Universal NI series – 316 Stainless Steel.

mounting pan/panel. Use of insulating material where practical is preferred. NI series to be supplied with NI020/S lock. A junction box for an equipment item may be combined with the LCS for that same equipment item only where specifically accepted by Managers Water Assets Planning.

Power outlets - process/outdoor/workshop areas

Clipsal 56 series outlets, and matching plugs as appropriate to application

Note requirement for round earth pin for EP outlets.

Chemical compatibility with materials of construction to be confirmed for chemical storage/batching/dosing areas

Valve Electric Actuators:

- Modulating control

- Isolation – open/close, ¼ turn, etc.

Rotork or Limitorque

Rotork

Rotork, series as appropriate and approved but generally IQ series. Specific model appropriate to application.

Limitorque MX series.

Rotork - model as appropriate to application and accepted by Manages Water and Sewerage Assets Planning.

Required make and model of actuator shall be specified for each individual project and accepted by Managers Water and Sewerage Assets Planning.

Use of discrete monitoring and controls for actuator or use of communication network, e.g. EtherNet or DeviceNet for control and monitoring to be accepted by Managers Water and Sewerage Assets Planning for each the specific project.

Solenoid Valve / actuators Burkett or ASCO Model as appropriate to application. Unless otherwise accepted supply voltages will be 240 VAC or 24 VDC (generally 240 VAC will be used for non critical applications).

Flexible Conduit

(requirements for indoors and outdoors process/plant equipment areas).

Flexicon

Flexicon LTP - Black sheath c/w metal fittings either nickel plated brass or stainless steel as specified Flexicon LPC – Black PVC for outdoors applications or as otherwise specified. Orange

Standard process area flex conduit: Flexible sheathed metal conduit for use as specified, or where required for screening/earthing, or for protection Heavy duty flexible plastic conduit used

Design Standards - Preferred Equipment Lists 42

Application/Item Manufacturer Preferred Make/Model Additional Information

AdapterFlex

sheath for indoors applications. Complete with metal fittings either nickel plated brass or stainless steel as specified. Flexicon - other types as suited to specific applications and each application accepted by Managers Water and Sewerage Assets Planning. AdapterFlex SPL – Black sheath Complete with metal fittings either nickel plated brass or stainless steel as specified

instead of flexible metal conduit where corrosion is an issue and where specifically accepted by Managers Water and Sewerage Assets Planning. Nylon fittings not accepted.

Flexible sheathed metal conduit for use as listed above.

Fluorescent Luminaires Pierlite For Indoor applications;

1. Process areas – model PWPxyzQS c/w polycarbonate diffuser

2. For Non Process areas such as MCC rooms, control rooms & office areas – specification of fittings as accepted by Manager Water Assets Planning

For outdoor applications;

1. General - Vandalux VCxyzQS

‘xyz’ denotes manufacturer’s number code indicating number of and wattage of lamps.

For applications exposed to UV, FRP/GRP and similar materials are not acceptable.

Emergency Lighting TBA upon request Design and makes/models of emergency and exit lighting to be accepted by Manager Water Assets Planning.

Normal practice for emergency lighting in process areas is the use of spot light fittings (e.g. Bardic or Legrand - SLSMT 210). Spot light fittings are to be supplied from Essential Power type socket outlets to allow ease of isolation or removal for maintenance

Fluorescent type emergency lighting fittings are not accepted.

Flood Light / Area lighting / Roadway lighting

TBA upon request Design and makes/models of these lighting types to be submitted for each application for acceptance by Managers Water and Sewerage Assets Planning.

For applications exposed to UV FRP/GRP and similar materials are not accepted.

Design Standards - Preferred Equipment Lists 43

21. Water and Sewerage Networks - Instrumentation Products

Application/Item Manufacturer Preferred Family/Model Additional Information

Electromagnetic Flowmeter – full bore type

ABB

Siemens

WaterMaster, Model specification as appropriate to the application

MAG 5000 / 6000 transmitter, MAG 5100 W Flow tube

Remote Transmitter featuring 240 VAC power supply required unless otherwise accepted by Managers Water and Sewerage Assets.

Specific model details to be selected based upon individual application requirements.

Electromagnetic Flowmeter – Insertion type for low accuracy applications.

Generally prohibited.

May only be accepted for a specific application by Managers Water and Sewerage Assets in which case suitable make and model shall be selected.

Flowmeter Variable Area –Rotameters.

Kytola Model 2851R-5CA-A -H Scale 0.05 to 0.5 Litres/minute of Water complete with hand knob and 2851 Constant Flow Regulator.

Model LH-8SA-HR Scale 0.2 to 2.6 Litre/min of water , ¼” BSP Female 316 stainless steel, rear connections, with hand knob

The models listed are generally used for Water Quality instrumentation sample lines. Other models to cater for greater flows to be accepted Managers Water and Sewerage Assets for each application.

Pressure Transmitters ABB

Endress + Hauser

266HSHMSBB1E8L5B2S2N4 (0-600 kPa)

Or 266HSHPSBB1E8L5B2S2N4 (0-2400 kPa)

Or 266DSHFSSA2B1V1E8L5B2S2N4 (Diff Press 0 -40 kPa)

Models TBC

Fitted with Integral transient and surge protection module. Other transmitters depending on the application from the ABB range may be aaccepted by Managers Water and Sewerage Assets Planning. Endress + Hauser models equivalent to ABB may be proposed

Design Standards - Preferred Equipment Lists 44

Application/Item Manufacturer Preferred Family/Model Additional Information

Suspended hydrostatic Endress + Hauser WaterPilot, Pt. No. FMX2165-****, model as appropriate to the application

Ultra Sonic liquid/solid level meters.

Siemens

or

Endress + Hauser equiv.

SITRANS Probe LU and Multi Ranger

Models TBC

Other models depending on the application from the Siemens range may be accepted by Managers Water and Sewerage Assets.

Endress + Hauser equivalent models may be proposed

RADAR – liquid or solid level, guided and unguided,

Siemens

Endress + Hauser

Models TBC

Models TBC

Models to be proposed depending on the application for acceptance by Managers Water and Sewerage Assets Planning.

Ultra Sonic Sludge Blanket monitoring meters.

TBA TBA Makes and models to be proposed for each application for acceptance by Managers Water and Sewerage Assets Planning.

Vibrating liquid/solid level switches

Endress + Hauser FTM30 – FTM32 -*4D***, model appropriate to the application.

Process turbidity analysers Hach

WTW

HACH Lasertrac for Ultra low turbidity applications

Visoturb IQ SensorNet for submersion applications in channels or tanks i.e. not WQ panel pipe insertion type applications.

For other applications makes and models to be proposed for acceptance by Managers Water and Sewerage Assets Planning.

Process pH analysers Endress + Hauser Transmitter: CPM253/-MR0105 or CM442-AA-M2-A4-F2-6-0-A-AA (24VDC supply model which is std, use of 240 VAC model is subject to approval)

Electrode: CPS-11D7BA21

Flow chamber (where required): CPA250-A00

Electrode cable: CYK10-A**1

Electrode model variant listed is for standard applications. For non standard applications different model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning.

Design Standards - Preferred Equipment Lists 45

Application/Item Manufacturer Preferred Family/Model Additional Information

Process ORP analysers Endress + Hauser Transmitter: Same family as pH Model variants appropriate to the application

Process Conductivity analysers

Endress + Hauser Transmitter: refer pH Transmitters for detail.

Electrode model dependant on application to be proposed for acceptance for each application by Managers Water and Sewerage Assets Planning.

Process Dissolved Oxygen analysers

WTW - IQ SensorNet Sensor: TriOxmatic 700IQ

Network Display terminal: MIQ/T2020

Network J-box: MIQ/JB

Digital network controller: DIQ/S182 or 2020XT featuring Modbus output.

Additional IQ SensorNet devices and/or model variants for non standard applications, to be proposed for acceptance by Managers Water and Sewerage Assets Planning.

Process Chlorine analysers USF / Wallace & Tiernan Micro2000, model variant as appropriate to the application .

Process Chlorine Gas Detectors

Draeger Polytron 7000 CL2

Process Gas Detectors Draeger For H2S, Combustible gas, Oxygen. Polytron

Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.

No Flow (clean liquid) switches - used to detect loss of sample flow for analytical instrumentation.

IFM-Efector TBA Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.

Proximity Switches IFM-Efector IF5397, 2 wire , 24 VDC PNP or other to suit application.

Specific model variants to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.

Loop powered LCD process indicator, 4 - 20 mA.

TBA TBA Specific make and model to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application. Considerations to include: suitable IP rating, DIN size – use standardized sizes, backlighting requirements, engineering units required to be displayed or factory marked on the indicator.

Pressure Switches United Electric J400 ranges Specific make and model to be proposed for

Design Standards - Preferred Equipment Lists 46

Application/Item Manufacturer Preferred Family/Model Additional Information

IFM-Efector TBC acceptance by Managers Water and Sewerage Assets Planning for each application.

Temperature Switches United Electric

IFM-Effector

F300 ranges

TBC

Specific make and model to be proposed for acceptance by Managers Water and Sewerage Assets Planning for each application.

Vibration Accelerometer Rockwell Automation - Entek

General purpose Accelerometer model 9000A, Pt. No. EK-43781L

For use with Rockwell Automation - Entek XM series Vibration Modules.

Temperature Transmitter ABB PT100 – TH02 Or other make and models depending on application to be proposed for acceptance by Managers Water and Sewerage Assets Planning

I/P Converter ABB TEIP11 18311 182110100 Or other make and models depending on application to be proposed for acceptance by Managers Water and Sewerage Assets Planning

General instrumentation signal convertors and isolators including R/I convertors

Weidmuller Mann Series Process Instruments For example ITX Plus range. Range and specific model to be selected to suit specific application.

Design Standards - Preferred Equipment Lists 47

22. Water and Sewerage Networks - Telemetry Electrical and Instrumentation PEL Addendum for Simple Sites

The items of preferred telemetry, electrical and instrumentation equipment additional to the Complex Sites for the Simple Sites are as detailed below. Where this section 22 differs with sections 18 to 21, then this section 22 takes precedence at Simple Sites.

Application/Item Manufacturer Preferred Family/Model Additional Information

DC Power Supply – Battery Charger

RF Industries SME240-12-10 Use power contact to signal power failure.

Battery required for non-UPS backed sites. Battery to be sized to suit load.

DC/DC Single Output Converter 12 VDC to 24 VDC

Powerbox PBIH-1224M

(Bracket: F-P100-1)

Converter to provide 24 VDC power to PLC from 12 VDC supply.

DC Power Supply -240 VAC to 24 VDC at 4.5 amps

Powerbox PBB2OC-24M

(Bracket: FD-A)

For use with larger sites where a dedicated 24 VDC 4.5 amp power supply unit is required.

DC Power Supply -240 VAC to 24 VDC at 6.5 amps

Powerbox PBB2OC-24R

(Bracket: FD-A)

For use with larger sites where a dedicated 24 VDC 6.5 amp power supply unit is required.

RTU Rockwell Automation

ML1400

1766-L32BXB 24 VDC supply. Special purpose IO points.

RTU - AI module Rockwell Automation 1762-IF4 4 way analogue input module 4-20 mA

RTU - AO module Rockwell Automation 1762-OF4 4 way analogue output module 4-20 mA

RTU - DI module Rockwell Automation 1762-IQ16 16 way digital input module

RTU - DO module Rockwell Automation 1762-OW16 16 way digital output module

Signal Converters Weidmuller

(Mann Industries)

ITX Plus series Loop powered, multi input, 4-20 mA output.

Design Standards - Preferred Equipment Lists 48

Application/Item Manufacturer Preferred Make/Model Additional Information

Valve Actuators Rotork IQ3 series Additional modules required: Modbus RTU communications.

Status signals required:

Open limit, close limit, MR, actuator alarm, Over torque trip.

Controls needed:

Open, Close.

Submersible Pump Seal Fail Relay

ITT Flygt Minicas II (24Vac/dc) This device is usually ordered with its respective pump, so the exact make and model are subject to final pump choice and is required to be proposed for acceptance by Managers Water and Sewerage Assets Planning.

Float switch (non mercury type)

ITT Flygt ENM-10 Replaces ENH-10.

Required to come with 20 m integral cable.

Pressure Switch United Electric 400 Series, Type J400

Model to suit application

Adjustable set point ranges. Site specific selection of equipment range is required.

½ “ NPTF connection.

Ranges: 300 inches water column vacuum to 250 inches water column vacuum (-746.7 to 622.3 mbar)

Pressure: 30 inches Hg vacuum to 6000 psi

(-1.0 to 413.7 bar)

Differential Pressure: 1 inches water column differential to 200 psi differential

(2.5 mbar to 13.8 bar)

Differential Pressure Switch United Electric 400 Series, Type J400K Adjustable set point ranges. Site specific selection of equipment range is required.

½ “ NPTF connection.

Differential Pressure: 3 to 100 psi differential

(0.2 to 6.9 bar differential)

Design Standards - Preferred Equipment Lists 49

Application/Item Manufacturer Preferred Make/Model Additional Information

Temperature Switch United Electric 400 Series, Type B400

Model to suit application

Adjustable set point ranges. Site specific selection of equipment range is required.

Stainless steel immersion stem.

Temperature ranges: -180 to 650 °F

(-117.8 to 343.3°C)

Submersible Pump Thermistor Relay

Schneider LT3-SM00ED (24 Vac)

UPS Powerware PW9130

AS400MS relay card “Management

Card Contact &

RS232 / Serial” for expansion options. Part number 3400390200.

Notes:

1. Cable #1838795 from Element14 (formerly Farnell Electronics) required.

2. Do not use AS400BD relay card.

Use Powerware Maintenance Bypass Switch MBS2000SW1 up to 2200 VA or MBS3000SW1 up to 3000 VA.

Simple Sites that include revenue metering to have 24 hours UPS backup for MagMaster meter power supply.

Other Simple Sites to have 4 hours UPS backup.

UPS to be double conversion type.

Additional option relay card must be included to provide:

UPS On Battery, Low Battery, UPS Operational and UPS bypassed as a minimum.

DC battery backed power supply

Powerware APS3 family.

Includes SC200 module, 6 output relays, expansion IO cards, inverters, regulators and DC/DC converters.

Design Standards - Preferred Equipment Lists 50

Application/Item Manufacturer Preferred Make/Model Additional Information

VSD

Danfoss FC202 for up to 110% starting torque

Door mounted HMI.

Ethernet/IP communications to PLC.

External 24 VDC supply option.

ATEX card for hazardous locations.

Safe stop option.

Harmonics, dV/dT and/or Sine filters subject to analysis.

Sine filters must be used with unscreened cables or submersible pumps.

VSD options matrix TBA upon request.

VSD

Danfoss FC302 for up to 160% starting torque

Door mounted HMI.

Ethernet/IP communications to PLC.

External 24 VDC supply option.

ATEX card for hazardous locations.

Safe stop option.

Harmonics, dV/dT and/or Sine filters subject to analysis.

Sine filters must be used with unscreened cables or submersible pumps.

VSD options matrix TBA upon request.

VSD Sine filters Danfoss To match associated VSD size 1. May be required where the pump has integral unscreened flex power cables.

2. May be required when the pump motor has inadequate class insulation to be suitable for use with VSD.

VSD Harmonic filters Danfoss To match associated VSD size May be required subject to location and Electricity Networks direction.

Design Standards - Preferred Equipment Lists 51

Application/Item Manufacturer Preferred Make/Model Additional Information

Motor Softstarter Rockwell Automation SMC - Flex Soft starter may be required by Electricity Networks Service and Installation Rules.

Ethernet/IP option.

Door mounted HMI.

Motor CTs as required.

“Pump Control” option.

Ethernet hub - unmanaged Moxa EDS-208 8 port copper only.

Plastic body.

Media converter (copper to fibre)

Moxa IMC-21-S-SC Single mode fibre.

Managed Ethernet Switch Moxa EDS-508A-MM-SC

Ethernet hub – managed with fibre connections

Moxa EDS-619 CM-600-4TX & CM-600-4SSC option cards to suit.

Singe mode fibre.

FOBOT - Fibre Termination Module – DIN rail mounted

MOLEX Part number to be determined – new product just released.

SC connectors.

12 port, DIN rail mounted.

(FO cable and equipment must be installed by MOLEX certified installer to achieve 25 year warranty)

FOBOT - Fibre Termination Module – DIN rail mounted (To be used until Molex have acceptable a commercial offering)

AFC FDE-12SC1-P

SPLCASS-MS-HD-6/12

Loaded on DIN rail enclosure with 12F SC for patching.

Splice Cassette Mini Stack HD combs with clear lid.

Fibre Optic Cable MOLEX Subject to application.

(AFOLH012OS1 has been used for Telemetry)

Refer BSD fibre optic standards – latest version MUST be used.

(FO cable and equipment must be installed by MOLEX certified installer to achieve 25 year warranty

Design Standards - Preferred Equipment Lists 52

Application/Item Manufacturer Preferred Make/Model Additional Information

Modbus Gateway Moxa MB3170 Where the previous model MB3180 has been used, an Element14 cable #1216699 is required.

Panelview (HMI) – small Rockwell Automation 2711C-T6T

(C600 colour TFT, touch screen)

Ethernet/IP comms support to PLC

Panelview (HMI) - large Rockwell Automation 2711PRDB12C (PVPlus 1250 – cirkey – tch display)

Ethernet/IP communications support to PLC. This display requires the 2711PRP8D to be installed.

Minor Control Equipment Rockwell Automation Pushbuttons 800FP-F range, Latch Mushroom head (red) 800FP-MT4.

LEDs: 800FP-P range.

22 mm Series.

Lamps to be “push to test” for lamp test function.

Lamp colours:

Red: running/open.

Green: stopped/closed.

Amber: fault.

White: available.

Phase Failure Relay Schneider RM35TF30 Provides: asymmetry, phase failure, phase sequence, under and over voltage.

Voltage Monitor Relay – single phase

Schneider RM17UAS15 Provides: under and over voltage measurement.

Circuit breakers – small systems (including reservoirs, gauge stations, valve farms, vent fans)

Schneider GV2 with rotary head (and lock off capability)

Suitable for 3 phase motors.

Circuit breakers – small systems (including reservoirs, gauge stations, valve farms, vent fans)

Schneider C60H with MGN26380 lock off option

Suitable for single phase self contained loads including dosing pumps, small fans.

Pump “no water” sensor

(to be used with electrodes and module mounted in pump.)

Hawk Measurement Systems

Gladiator Admittance Switch – Smart Probe

AS2100BS212TN

05XPO5

To be used with Pleuger Pumps that are fitted with suitable threaded spigot in the pump shroud.

Design Standards - Preferred Equipment Lists 53

Application/Item Manufacturer Preferred Make/Model Additional Information

Liquid Level Relay

(to be used with electrodes mounted in pump, module elsewhere.)

Carlo Gavazzi CLD2ET1C230 (240 VAC for use with existing sites where 24 VDC controls are not available)

CLD2ET1CM24 (24Vdc for use in all new sites & site upgrades)

To be used for “no water” detection in Pleuger Pumps that are fitted with factory installed probes in the shroud.

240 VAC unit for maintenance replacement use only.

Water Flowmeters ABB WaterMaster

To have the following:

24 VDC power supply

Modbus RTU communications option installed.

3 off output contacts

Field mounted flow element.

Factory potted cable at the flow element.

Specify cable length to suit the project.

Switchboard mounted flow transmitter.

NATA certified, 5 point calibration (0%, 25%, 50%, 75%, 100%).

Earth rings must always be installed.

Reservoir Level (head pressure)

ABB 266HSHMSBB1E8L5B2S2N4

(replaces ABB 264HSPABB1B2-E5, C/W AR0328 INTERNAL SURGE PROTECTION)

0-600 kPa range.

Loop powered.

4-20 mA

Water main pressure ABB 266HSHPSBB1E8L5B2S2N4

(replaces ABB 264HSPSBB1-E5-B2, C/W AR0328 INTERNAL SURGE PROTECTION)

0-2400 kPa range.

Loop powered.

4-20 mA

Design Standards - Preferred Equipment Lists 54

Application/Item Manufacturer Preferred Make/Model Additional Information

Differential pressure ABB 266DSHFSSA2B1V1E8L5B2S2N4

(replaces ABB 264DSFSSA1B1-V1-E5-B2,C/W AR0328 INTERNAL SURGE PROTECTION)

0-40 kPa range.

Loop powered.

4-20 mA

Pressure Instrument

Manifold

2 valve manifold for isolation and venting

ABB (Oliver) G12FMS/PP Suitable for PEL gauge pressure or absolute pressure switches with 1/2" NPTF connection.

316 SS

Pressure Instrument

Manifold

3 valve manifold for isolation and equalisation

ABB (Oliver) Y34S Suitable for PEL differential pressure switches with 1/2" NPTF 316 SS

Pressure Instrument Manifold

5 valve manifold for isolation, venting and equalisation

ABB (Oliver) Y53S/PP Suitable for PEL differential pressure switches with 1/2" NPTF

316 SS

Intrinsically Safe Barrier – digital input

Pepperl & Fuchs KFD2-SR2-Ex2.W Dual channel model.

Subject to entity concept calculations.

Equivalent make and model can be proposed for acceptance by Managers Water and Sewerage Assets Planning.

Intrinsically Safe Barrier – analogue input

Pepperl & Fuchs KFD2-STC4-Ex1.20

(dual output)

KFD2-STC4-Ex1

(single output)

Current sourcing output, single channel.

Must submit equivalent for acceptance by Manager Water Assets Planning.

Subject to entity concept calculations.

Design Standards - Preferred Equipment Lists 55

Application/Item Manufacturer Preferred Make/Model Additional Information

Flow switch IFM Efector SI6600

EVM003 (10 m cable)

As used in emergency showers.

PNP output.

Small sensor offset from body - use tee to install. Notes:

1. Mounting adapter may be required to adapt Aseptoflex process connection to pipe size.

2. SI2100 now obsolete.

Interposing Relay 24 VDC coil (single pole change over contact)

Finder 385124VACDC

(relay includes integral base)

Use bridging link 93.20 (for ganging).

For use with RTU FET outputs.

Interposing Relay 240 VAC coil (single pole change over contact)

Finder 3851240VACLCS

Use bridging link 93.20 (for ganging).

Notes:

1. Relay includes integral base

2. For use with new RTU’s for existing site upgrades only where control voltage is 240 VDC.

Interposing Relay 24 VDC coil (double pole change over contact)

Finder 56329007424VDC For use with seal fail and overload reset connections.

Relay base to suit Finder 563290074 series relays.

Finder 96.72

Lightning/Surge Protection

(Primary POE)

Erico

TDS1100-2SR-277 per phase or model to suit application.

Typically required after Main Switch. Health contacts to be monitored (any single failure to signal group failure). Supply CB position to be monitored.

Lightning/Surge Protection

(FCPs / L+P switchboard)

Erico

TDS350-TT-277 for 3-phase or TDS150-1SR-277 for 1 phase or model to suit application

Typically required after DB Section Main Switch (where required). Health contacts to be monitored (any single failure to signal group failure). Supply CB position to be monitored.

Design Standards - Preferred Equipment Lists 56

Application/Item Manufacturer Preferred Make/Model Additional Information

Lightning/Surge Protection

(DC Distribution)

Erico

DSD140-2BR-24/48

Lightning/Surge Protection

(BNC Coaxial)

Erico

CSP-BNC-90

Lightning/Surge Protection

(Universal Transient Barrier)

Erico

UTB-30SP UTP-30 used for protection of I/O wiring (where required).

UTB-30 required for all analogue inputs and outputs where instrumentation is located external to the building that the wiring originates from.

UTB-30 required for digital inputs and outputs where field device is installed external to the building that the wiring originates from.

Use of UTB-30S instead of UTB30 requires acceptance of Manager Water Assets Planning.

Lightning/Surge Protection

(RS232)

Erico

DEPRS23299D

(DB9M and DB9F connections)

For use up to 15 VDC signal levels.

To be used with all RS232 communications between RTUs and field devices where device is inserted into DB9 cables.

Lightning/Surge Protection (RS485/RS232)

Erico UTB15SPG

(screw terminals)

For use with up to 15 VDC balanced pair signal lines. To be used where field devices terminate in flying leads.

Lightning/Surge Protection

(RS422, RS485)

Erico

DEPRS42299D 9 VDC balanced signal.

Lightning/Surge Protection

(Ethernet)

Erico

LANRJ45POE RJ45, 100BaseT, Cat 5 Protector. In line connector. Din rail mounting.

Power Connectors (up to 63 amps)

Marechal Socket Outlet: 61 64 013 972

Inlet: 61 68 013 972

Socket Outlet Sleeve: 61 6A 027

Inlet Handle: 61 6A 253 40P

Large loads - including pumps and generators

Design Standards - Preferred Equipment Lists 57

Application/Item Manufacturer Preferred Make/Model Additional Information

Signal connectors Marechal Socket Outlet: 01 M4 081

Inlet: 01 M8 081

Socket Outlet Sleeve: 01 NA 027

Inlet Handle: 01 NA 253 32P

Small loads - including flow switches, no water probes, water jacket PT100’s

Ultrasonic Level Switch Siemens Pointek ULS200 (Milltronics) 2 internal programmable relays.

24 VDC powered.

Ultrasonic Level Instrument Siemens SITRANS (Proble LU) HART 7ML5221

4-20 mA output.

Wall Temperature Sensor Siemens SYMARO QAA2017 4-20 mA output.

0-50 degrees (default – can be jumper changed).

Smoke detector Firetronics FID-L 12/24 VDC external power, ionisation smoke detector, latching LED indicator.

Vertical float switch PDL (Schneider) FS5 (float switch assembly) 20 amp contact, 2.7 m line, weight, stops and float.

Ethernet isolation module Phoenix Contact 2313931 FL ISOLATOR 100-RJ/RJ

2 x RJ45 connectors to allow insertion in line.

Motion Sensor Clipsal Infrascan 750WPR Include external switch to override motion operation.

Fluorescent Luminaires Pierlite Indoors - PWP236

Outdoors – PWP236 fitted with anti vandal mechanisms

For indoor use - maintained fittings required as per Building Code of Australia ratio.

Power Monitor Schneider PM710GM NOTE soon to be discontinued.

240 Vac supply, class 1 measurement, with Modbus-485 communications.

Power Monitor Schneider PM5320 24 Vdc supply, class 0.5 measurement. With Modbus TCP communications.

Power monitor Carlo Gavazzi EM2172DAV53XOSX (EM21 energy meter 5A RS485)

Use with CT’s XXX/5. Quantity = 3 Use with 282CT1 CT Test/disconnect terminals. Quantity = 3.

Design Standards - Preferred Equipment Lists 58

Application/Item Manufacturer Preferred Make/Model Additional Information

To be used in site retrofits (not switchboard replacements)

Design Standards - Preferred Equipment Lists 59

Part D - Water and Sewerage Networks - Mechanical Equipment PEL

The mechanical items of preferred equipment for the Water and Sewerage Networks that are yet to be identified will be updated in the PELs as product acceptances are made by Icon Water. In the absence of PELs for required mechanical products and materials, mechanical products and materials proposed for specific Icon Water projects shall be subject to the acceptance of the Manager Water Assets Planning for the specific Water Network projects and the Manager Sewerage Assets Planning for the specific Sewerage Network projects.

23. Water Network - Pump Sets and Materials Handling

24. Sewerage Network - Pump Sets and Materials Handling

25. Sewerage Network - Foul Air Fans and Odour Scrubbers

26. Water and Sewerage Networks - Cranes Ventilation Fans and Generators

Design Standards - Preferred Equipment Lists 60

Part E – Water and Sewerage Networks – Work at Height PEL

27. Fall Protection Equipment

AS/NZS 1891.1 – Industrial fall arrest systems and devices – Harness and ancillary equipment Icon Water Standard Drawing Numbers -

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Load

Rating Limitations on use

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Upper Offset Mast, Model 8518006AU stainless steel

15 kN

Mast offset reach 762 to 1080 mm

Anchor point height 927 to 1384 mm

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Lower Mast stainless steel, Model 8518002

832 mm mast extension for use only with Advanced System Davit

Combined maximum of two mast extensions

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Lower Mast stainless steel, Model 8518003

1143 mm mast extension for use only with Advanced System Davit

Combined maximum of two mast extensions

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Advanced Three Piece Expandable Base, Model 8518008AU

15 kN

Maximum offset 1080 mm

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Adjustable Barrel Mount Sleeve, Model 8512285

For varying wall thicknesses

Maximum wall thickness 609 mm

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Advanced Vehicle Hitch Sleeve, Model 8514461

Maximum offset 1219 mm offset mast

Design Standards - Preferred Equipment Lists 61

AS/NZS 1891.1 – Industrial fall arrest systems and devices – Harness and ancillary equipment Icon Water Standard Drawing Numbers -

Supplier Brand Name

WSAA Appraisal

Icon Water Acceptance

Nominal Size

Product Load

Rating Limitations on use

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Core mount stainless steel sleeve, Model 8510110

Designed for cored concrete

101.6 mm cored hole

Complete with PVC liner and sleeve cap

Not to be used for new concrete works

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Flush floor mount stainless steel sleeve, Model 8512828

To be used for new concrete work

Designed for cast in place concrete

Complete with PVC liner and sleeve cap

Capital Safety

DBI SALA Project CX10747 Expiry 12Mar16

Not applicable

Emergency Retrieval Sealed Self Retracting Lifeline with stainless steel cable, Model 3400102

4 kN

For raising and lowering personnel