66
WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED BATCH SYSTEM FOR SMALL QUANTITY GENERATORS by PANEENDRA S. TIRUPATHI, B.Tech. A THESIS IN CHEMICAL ENGINEERING Submitted to the Graduate Faculty of Texas Tech University in Partial Fulfillment of the Requirements for the Degree of MASTER OF SCIENCE IN CHEMICAL ENGINEERING Approved Accepted May, 1994

WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED BATCH

SYSTEM FOR SMALL QUANTITY GENERATORS

by

PANEENDRA S. TIRUPATHI, B.Tech.

A THESIS

IN

CHEMICAL ENGINEERING

Submitted to the Graduate Faculty of Texas Tech University in

Partial Fulfillment of the Requirements for

the Degree of

MASTER OF SCIENCE

IN

CHEMICAL ENGINEERING

Approved

Accepted

May, 1994

Page 2: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

~o~ gr:zqCJj/J

~t2 1~ 11 ~) lf ACKNOWLEDGMENTS ~/l-~ rjj1/9~

' ) )-:J. 77 I am deeply indebted to my research advisor, Dr. Richard

Tock for his valuable guidance, patience, constant

encouragement and financial support during the course of

this research. I also express a sincere appreciation to Dr.

R. Russell Rhinehart, my other committee member, for his

suggestions and criticisms throughout this work.

I would like thank Mr. Randy Nix and Mr. Richard

Whitehead of the Environmental Health and Safety Department

of Texas Tech University for their timely help and support

in conducting the experiments.

I wish to dedicate this work to my parents. I also wish

to express my gratitude to my brothers and sisters, back

home in India for their unflagging support and

encouragement.

.. 11

Page 3: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

TABLE OF CONTENTS

ACKNOWLEDGMENTS • • • • • • • • • • • • • •

LIST OF FIGURES • • • • • • • • • • • • • • • •

CHAPTER

1. INTRODUCTION • • • • • • • • • • • • • • •

2. LITERATURE SURVEY • • • • • • • • • • • • •

3. FUNDAMENTALSOFpH • • • • • • • • •

3. I Definition of pH . • • • • • • • • • •

3.2 Rangeability and Sensitivity • • • • • • • •

3. 3 Titration Curves • • • • • • • • • •

3 0 3 0 1 The strong acid and strong base neutralization •

3. 3. 2 The weak acid and strong base neutralization •

3.3 .3 The strong acid and weak base neutralization. •

3. 3. 4 The weak acid and weak base neutralization •

3.4 Buffering • • • • • • • • • • • •

3. 5 pH control Difficulty . • • • • • • • •

3. 5. 1 Titration curve generation •

3. 5. 2 Titration curve sensitivity •

• •

• •

4. EXPE~NTALSETUPPROCEDURE. •

4 .I Apparatus • • • • • • • • •

• •

• •

• •

• •

4. 1. 1 In-line Electrode • • • • • • • • •

4.1.2 pH Controller •

4. 1. 3 Metering Pumps

• • • • • •

• • • • •

• • •

• • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

• • • •

4.1.4 Mixers • • • • • • • • • • • • • •

4.2 pH Sensing and Transmission • • • • • • • • • • •

... w

.. 11

v

1

3

70

7

10

I1

1I

13

16

16

21

22

22

23

25

25

25

27

27

28

29

Page 4: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

4. 3 Experimental Setup • • • • • • • • • • • • • • 29

4. 3. 1 Preparing reagent solutions. • • • • • • • • • • 31

4.3.2 pH sensor calibration • • • • • • • • • • • • 33

4.3.3 Pump calibration • • • • • • • • • • • • • 34

4. 4 Experimental Procedure • • • • • • • • • • • • • 34

5. RESULTS AND DISCUSSIONS • • • • • • • • • • • 36

5.1 Strong Acid versus Strong Base • • • • • • • • • • • 36

5.2 Strong Acid versus Weak Base • • • • • • • • • • • 40

5.3 Weak Acid versus Strong Base • • • • • • • • • • • 40

5.4 Weak Acid versus Weak Base • • • • • • • • • • • 45

6. CONCLUSIONS AND FUTURE RESEARCH • • • • • • • • 49

BffiLIOGRAPHY • • • • • • • • • • • • • • • • 50

APPENDICES

A. ECONOMIC JUSTIFICATION . • • • • • • • • • • 52

B. OPERATING MANUAL • • • • • • • • • • • • • 54

C. HAZARDOUS OPERABILITY STUDY. • • • • • • • • • 58

0

IV

Page 5: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

LIST OF FIGURES

3 . 1 : Typical titration curve for strong acid and strong base system (McMillan 1984) • •

3.2: Typical titration curve for weak acid and strong base system (McMillan 1984) • •

3. 3 : Typical titration curve for strong acid and weak base system (McMillan 1984) • •

3.4: Typical titration curve for weak acid and weak base system (McMillan 1984) •

3.5: MultipleS-shaped curve • • • •

4.1: In-line electrode • • • • • • •

4. 2: Schematic of experimental setup • • •

• •

• •

• •

• •

• •

• •

• •

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

5. 1 : Results of neutralization of hydrochloric acid with sodium hydroxide

5.2: Results of neutralization of sodium hydroxide with hydrochloric acid

5. 3: Results of neutralization of hydrochloric acid with sodium carbonate

5. 4: Results of neutralization of sodium carbonate with hydrochloric acid

5. 5: Results of neutralization of acetic acid with sodium hydroxide • •

5. 6: Results of neutralization of sodium hydroxide with acetic acid •

5. 7: Results of neutralization of acetic acid with sodium carbonate •

5. 8: Results of neutralization of sodium carbonate with acetic acid •

v

12

14

17

18

20

26

30

38

39

41

42

43

44

46

47

Page 6: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTER 1

INTRODUCTION

Many wastewater streams are hazardous simply because they contain weak or strong

acids, bases, and/or their partially neutralized salts. Such wastewaters must be neutralized

before being discharged into the environment. The level of pH for any aqueous solution is

conventionally measured with a pH meter, and the wastewater is neutralized by the

addition of a strong inexpensive acid or a caustic base.

The Environmental Health & Safety (EH&S) Department of Texas Tech University is

responsible for collection of all chemical wastes produced on campus. Included in these

wastes are both acidic and basic wastewaters. The most typical acid wastes produced are

acetic acid, hydrochloric acid, and sulfuric acid. The composition of this wastewater can

vary considerably, but consists of small volumes ofliquids from various teaching and

research laboratories. Increased environmental regulations to encourage waste reduction

coupled with the rising cost for hazardous chemical disposal have encouraged the EH&S

Department to consider neutralization of wastewaters. Neutralization eliminates the

hazardous corrosive characteristics and allows the neutralized solution to be discharged to

the city sewer system.

Industrially pH control and/or adjustment have included a wide range of applications.

These include boiler water treatment, chemical and biological reactions, municipal

wastewater treatment, acid pickling and etching, cooling tower water treatment,

electrohydrolysis and coagulation/precipitation. However, the application of

neutralization to relatively small quantities of wastewater can be difficult because of the

unknown and non-stationary fluid composition, which must be brought to a pH = 7. 0.

At Texas Tech University, the wastewater is collected manually across campus from

the various teaching and research laboratories, and as noted is of a wide variety and

1

Page 7: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

composition. Hence, the university's initial procedure for neutralization of such

wastewater was carried out manually by experienced technicians. Manual processes are

labor intensive requiring the generation of a sample titration curve followed by the actual

neutralization of the bulk wastewater. This study, however, reports on the findings of a

semi-automatic approach to the neutralization process designed to reduced labor

requirements.

There were two main objectives of this project. The first was to initiate a study of

cost-benefit ratio of an automated wastewater neutralization unit versus the old manual

procedure. The second objective was the assembly of a prototype, semi-automated

wastewater treatment unit. The prototype experimental setup was then assembled at the

Texas Tech University, hazardous waste treatment storage and disposal (TSD) facility.

This thesis describes the research and development process which created the pH

adjustment procedure. Hence, Chapter 2 discusses background information, such as the

definition of pH, rangeability and sensitivity, concept of titration curves, the various

possible titration curves, buffering, and the difficulty of pH control. Chapter 3 presents

some prior work, current practices, and a summary of the theoretical and the practical

work reported in the literature in this field. The experimental setup, a description of the

apparatus including the in-line electrode, pH controller, metering pumps, mixers and the

basic concepts of pH sensing and transmission are discussed in Chapter 4 along with a

detailed experimental procedure. Chapter 5 presents the results obtained with the system

together with a discussion. The conclusions and suggestions for the further developments

are embodied in Chapter 6.

2

Page 8: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTER2

LITERATURE SURVEY

Strong concentrations of acids and bases have a severe effect on aquatic life, and

these same solutions are hazardous to both human health and the environment. As a

consequence, pH adjustment/control has been an important unit operation in waste

treatment for many years. There has been a significant amount of research done on pH

controVadjustment and reported in the published literature. Even so, the solution for the

problems of a small quantity generator (SQG) of these wastes have not yet been

adequately addressed. In our case an attempt was made with different types of acidic or

caustic wastes based on our understanding with the basic principles of neutralization.

McMillan (1984) described the neutralization of various possible cases in some detail.

He discussed the neutralization of strong acid with strong base and weak base and

neutralization of weak acid with strong base and weak base in detail along with the typical

titration curves. These details were given in the following chapter, "Fundamentals of pH".

The pH chemistry was also discussed with clarity. The temperature effects on pH and the

effects which result when the solution to be neutralized is exposed to the air were

discussed. Wastewater exposed to the air can absorb enough carbon dioxide to lower the

pH. This is a particular problem for nearly pure water and caustic samples. The pH of the

pure water at 25 OC can change from a pH of7 to a pH of5.7 by exposure to air.

McMillan shows how the mixing equipment size, type and kind of agitation required can

be assessed by the titration curve.

F.G.Shinsky (1973) also describes the batch neutralization process. He describes the

advantages of batch neutralization as having the ability to retain an effiuent until its quality

meets specifications. According to Shinsky, economic incentives lean toward the batch

process whenever the plant production units are operated batch wise. Overshoot

3

Page 9: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

problems and the remedy at neutral point are discussed in detail. Thus buffers can be used

to avoid the overshoot problem at the neutral point for neutralizing the strong acid with

strong base or vice versa. When the total flow rates or the hazard waste production are

reduced, then the batch process is an ideal option to consider since reservoirs used for

confinement are manageable.

The pH control/adjustment and basic components required for pH control were also

discussed by Ross (1989). The five basic components of pH control system were listed as

(1) Monitoring, controlling and record instrumentation,

(2) pH electrodes and holders,

(3) Effiuent holding tanks,

( 4) Chemical pumps and reagent storage tanks, and

( 5) Mixers I agitators.

According to Ross many of the problems encountered in a pH neutralization system

are centered around the pH electrode. Incorrect choice of electrodes, holders and

placement of electrodes are sources of common problems. He described the most

common problems experienced with pH electrode as

( 1) Oily and solid coatings requiring frequent removal for cleaning.

(2) pH bulb breakage or premature failure due to abrasives or solid materials in the

solution.

The pH error based on temperature is expressed as 0. 03 pH I pH unit I 1 0°C. For

example, between 1 S and 3 SOC with a working pH range between 6 and 8, the error

would only be ±0.03 pH.

The accuracy of the equipment used in the neutralization of wastewater is quite

important. Kalis (1990) in his article," How Accurate Is Your On-Line pH Analyzer?"

discussed the calibration techniques, maintenance, and temperature effects on pH probes

in detail with the clear pictures showing calibration errors. He described two calibration

4

Page 10: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

techniques, the first being the grab sample method (process calibration), and the second

being the two point calibration (buffer calibration). He reported that using the grab

sample method, a 0. 02 pH accuracy is very difficult to achieve. A small sample from the

process is taken, and the pH is found by using a standard pH meter. Then the on-line

analyzer is adjusted to reflect the reference measurement from the lab. The advantage of

this process is that the sensor life is extended because the sensor need not be removed

from the process line. The disadvantage is the measuring error of the lab analyzer is added

to the process analyzer.

The two point calibration involves using the buffer solutions with pH 7, pH 4, and pH

10. The pH sensor is calibrated for a pH of 7 and then the slope control is adjusted with

buffer solutions with a pH 4 and pH 10. The temperature effects were not considered

because of the negligible effect of temperature over the range of 6 pH and 8 pH. He

found out the two point calibration is better and the instrument will be corrected for

sensitivity and offset voltage.

Horwitz (1993) described how pH control can be deceiving, strange, mystical, and

unpredictable. He suggested a four-step strategy for successful control. The four steps

being:

1. Equalize the flow to the control system. Equalizing of the flow is allowing the

solution to reside in the tank where reagent is added to the wastewater for some time for

better control of the system. The ability to equalize both flow and concentration variables

depends on the magnitude of the stream and the amount of time required to get proper

equalization. As flow streams get larger and equalization time increases, the size of the

necessary tankage may become excessive.

2. Providing good mixing of the solution for better control of the system.

3. Use a minimum of two stages. The number of the stages depends on the nature of

the range of pH variation and the steepness of the titration curve(s). Agitation is needed

5

Page 11: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

for the first stage but is not necessary for the second stage. Third stage can also be used

when attenuation is necessary.

4. Characterize the controller with the titration curve.

6

Page 12: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTER3

FUNDAMENTALS OF pH

Neutralization processes and pH adjustments, involve the combined fundamentals of

thermodynamics, chemical reaction equilibria, reaction kinetics and solution chemistry.

Before attempting to study pH control or adjustment process as, it is important to

understand the basic principles of pH and neutralization. This chapter outlines the

fundamentals of pH, its applications and limitations, the concept of strong and weak

reagents, the neutralization characteristics of the different types of reagents and the

analysis and sensitivity of titration curves.

3. 1 The Definition of pH

The process variable pH is the negative logarithm ofbase 10 ofthe hydrogen ion

activity. The small p indicates that the mathematical relationship between the ion and the

variable as a power function; the H designates the ion as hydrogen (McMillan 1984).

Hydrogen ions exist in all streams that contain water, and can be visualized as a single,

positive-charged hydrogen nucleus, or proton (IP"). It is generally accepted that, in water

streams, this hydrogen ion is actually thought to be bound to a water molecule in the form

of a hydronium ion (H30+).

The mathematical definition of pH is:

pH= -log 10 (a H+) (3.1)

Where aH+ is the activity of hydrogen ions expressed in normality (g io~t). Activity

is related to concentration by the following equation.

a= yC (3.2)

Where activity, a, and concentration, C, are in the same units and y is the activity

coefficient. At high dilutions, the activity coefficient approaches unity, which gives the

7

Page 13: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

familiar definition of pH. Since wastewater solutions are very dilute, the usage of

concentrations instead of activities should not make any significant difference.

pH= -log 10 (CH) (3.3)

where (CH) represents the concentration of hydrogen ions in the solution in g-ions

/liter. The measurement of pH gives the dissociation of acid or base molecules into ions.

pH is thus, a measure of the acidity or alkalinity of an aqueous electrolyte solution.

For non unity activity coefficients, the activity coefficient is calculated in the following

way. The activity coefficient of an ion is closely related to the ionic strength of a solution.

The ionic strength (Jl), which is a measure of the total concentration of ions in a solution,

is defined as 1

J.1 = -:rc· z~ 2 I I (3.4)

where Ci is the concentration of the ith ion and Zi is the charge on the ith ion. The

exact relationship between y and J.1 is given by the extended Debye-Huckel equation

(Harris 1987) as: -0.51z2JP

logy = r.: a-vJ.J

1 + ( 305 )

(3.5)

where a is the effective hydrated radius ofthe ion in picometer (10-12 m). This

equation works well for J.1S 0.1 M. The activity coefficients of different ions as a function

of solution ionic strength is listed in a tabular form on page 91 of Quantitative Chemical

Analysis (Harris 1987). From that table, a values for H+ and OH- ions are 900 picometers

and 350 picometers, respectively.

The positive values of pH correspond to hydrogen ion concentrations less than unity

and negative values of pH correspond to concentrations greater than unity. Pure water

has a pH of 7 at 24 °C, 0.1 N hydrochloric acid has a pH of 1.0 at 25 OC and 0.1 N

sodium hydroxide has a pH of 13.0 at 25 OC (CRC Handbook). However, the pH meter

8

Page 14: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

scales have a maximum range of only 0 to 14 pH. There are two reasons for this. First,

the set points of feed back pH loops are all well within the 0 to 14 range, since biological

processes and equipment cannot tolerate concentrations outside of this range. Secondly,

even though some feed forward pH measurements could fall outside this range, the pH

electrode's accuracy rapidly deteriorates at the extremities of this range. The hydrogen ion

concentration decreases by a factor of 10 for each unit increase in pH. The product of

hydrogen ion and hydroxyl ion concentration is a constant for water at a given

temperature. The hydroxyl ion consists of a hydrogen bound to a oxygen ion with a net

negative charge of unity. Thus, the charge of the hydroxyl ion is equal in magnitude and

opposite in sign to the hydrogen ion. The 7 pH point is termed as neutral point. For

water at 25 °C the product of hydrogen ion concentration and hydroxyl ion concentration ,

is a constant and the product ofthem is equal to 10·14.

A dissociation constant is used to define the relationship between the activities of the

components. For example consider the dissociation reactions in water:

HCI <=> H+ + Cl­

NaOH <=> Na+ + OH- .

(3.6)

(3.7)

The dissociation constant for acid {K3 ) for equation 3. 6 is given by

K = [W][C/-] (3.8) a [HC/]

A weak acid is one that is only partially dissociated in water. This means that Ka is

small for a weak acid. The dissociation constant for base <Kt, ) for equation 3. 7 is given

by [OJr][Na+]

K., = [NaOH] . (3.9)

The K values provide a measure of the strength of the acid or base. The dissociation

constant "K" typically falls numerically in the same range as the hydrogen ion

9

Page 15: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

concentration, so that it is convenient to express it as a negative logarithm like pH; where

the small p designates the power function.

pK = -logK. (3.IO)

For example, for water the dissociation constant is given as Kw and it is given as '

H20 <=> H+ + OH- (3.II)

Kw = [H+] [OH·]

log Kw = log [H+] +log [OH·]

-log Kw= pH+ pOH = I4.00 at 25 OC.

The dissociation constants vary with temperature, and, hence, the pH of the solution

varies with temperature. The error caused by operating between 40 and 80 Of over a

range from pH 6 to 8 without temperature compensation is only ±0.03 pH units (Shinsky

1973). Even in the case of high or low pH, the temperature effect on the pH is small, and

can be neglected because the error at the neutralization point is negligible.

3. 2 Rangeability and Sensitivity

The pH scale corresponds to a hydrogen ion concentration ranging from I oO to I o-14

g-moles per liter. Measuring electrodes can respond to changes as small as O.OOI pH, so

instruments can track hydrogen ion concentration changes as small as Sxi0-10 moles per

liter at 7 pH. No other measurement has such tremendous sensitivity (McMillan I984).

The implications of such great rangeability and sensitivity is illustrated by Hoyle

( 1972). The reagent flow should essentially be proportional to the difference between the

hydrogen ion concentration of the process fluid and the set point. Neutralization from a

pH of 6 to a pH of 7 requires only one unit of reagent, and to neutralize from pH I to pH

7 requires 1 00,000 units of reagent. This is because of the logarithmic relation between

pH and hydrogen ion concentration. The flow control device should have enough

rangeability to bring the pH of solution to 7 by delivering the required amount of reagent.

IO

Page 16: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

3. 3 Titration Curves

The titration curve is the primary unit of information required for pH control.

Simply, this curve expresses the pH versus the ratio of reagent to influent ratio

relationship, and, thereby, allows us to determine how much reagent is required to

neutralize an influent solution. It is also called the "characteristic curve" or the

"equalization curve." The titration curve is the single most important piece of information

for the design, operation and troubleshooting of pH control systems.

3. 3 . 1 The strong acid and strong base neutralization

The strong acid and strong base curves as shown in Fig. 3 .1 (McMillan 1984) is

distinguished by its vertical slope throughout most of the pH scale range. Titration curves

rarely consist of straight lines; and the enlargement of a straight line usually will reveal

another curve. A titration curve without a clearly defined abscissa is worthless, because

the shape will change with the abscissa range. The neutral point occurs at a pH equal to

one half of the pKw (dissociation constant of water which is given as 10 -14 g-moleslliter),

so that its location depends on solution temperature. K w is a weak function of

temperature of the form 1 o-f(T), where ftT) at 25° C is the familiar 14. K w varies from

14.94 at 2730 K to 13.02 at 333° K (McMillan 1984). Since, the dissociation constants

vary with temperature, the pH of the solution varies with temperature. The neutral point

on the titration curve is the point at which pH of the solution is 7. The equivalence point

on the titration curve is the point at which the quantity of base added is the exact amount

necessary for stoichiometric reaction with the acid or vice versa.

In the neutralization of any strong acid with strong base, there are three regions of the

titration curve of concern. They are:

11

Page 17: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

1~

t3

12

11

10

9

8

7 -

6

5

~

3

2

· 1

0

0 0 .2 0.~ 0.6 0.8 1.0 1.2 1.~ 1.6

Ratio of Reagent to Influent Flow

Figure 3.1 Typical titration curve for strong acid and strong base system (McMillan 1984)

12

1.8 2 .0

Page 18: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

I . Before reaching the equivalence point. In this region the solution concentration

is high in hydrogen ion concentration. The pH is calculated by using the hydrogen ion

concentration at any point of time before the equivalence point is reached.

2. At the equivalence point. At the equivalence point the amount of base added is

the exact amount necessary for stoichiometric reaction with the acid. Enough OH- ions

had been added to react with all the H+ ions in the solution. The pH at the equivalence

point in the neutralization of any strong acid (or base) with strong base (or acid) will be 7

at 25 °C. The equivalence point coincides with the neutral point for a strong acid and

strong base system. The slope of the titration curve is steepest at the equivalence point for

a strong acid strong base neutralization. The strong acid and strong base system appears

to be symmetrical about the equivalence point.

3. After the equivalence point. After the equivalence point more base is added.

Hence the solution is rich in OH- ions. The pOH of the solution is determined analytically

by calculating the OH- concentration. The pH can be calculated from pOH by the relation

pH+pOH=l4.

3. 3. 2 The weak acid and strong base neutralization

The weak acid and strong base system in Fig. 3.2 (McMillan 1984) is distinguished by

its steep slope in the upper pH scale range. The center of this steep slope is the

equivalence point location, and it is dependent upon the dissociation constant of the weak

acid. When compared to the strong acid and strong base titration, the curve in this case

starts at much higher pH, increases more rapidly at first, then flattens out before it

becomes vertical. The vertical part of the curve is only about half as long as in the case of

strong acid and strong base neutralization.

13

Page 19: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

... 13

12

11

·o I 9 I s~

I 7 .!.

I pH i

6..L

sl ~

3

2

1

0

0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6

Ratio of Reagent to Influent Flow

Figw-e 3.2 Typical titration curve for weak acid and strong base system (McMillan 1984)

14

1.8 2.<

Page 20: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

case starts at much higher pH, increases more rapidly at first, then flattens out before it

becomes vertical. The vertical part of the curve is only about half as long as in the case of

strong acid and strong base neutralization.

Before any base is added, the solution contains just HA in water. HA is weak acid

and the pH of the solution is determined by the equilibrium.

From the equation 3.6, it is given that [H+][A-]

Ka = [HA] .

From equation 3.11, it is given that

Kw = [H+] [OH·].

(3.12)

(3.13)

(3.14)

From equations 3.13 and 3.14, the pH ofthe solution is determined by calculating the

hydrogen ion concentration. The hydrogen ion is considered to be dissociated both from

the weak acid as well as water. Before the equivalence point the neutralization reaction is

given as follows.

(3.15)

Before the equivalence point, there is a mixture of both HA and A- , which is a buffer.

Hence to calculate the pH in this region, the Henderson-Hasselbalch equation is used.

This equation is given as

pH= pK8 +log ( [A·] I [HA] ). (3.16)

Based on this equation when pH equals the pKa, the negative acid ion activity is equal

to the acid molecule activity, and, hence, the dissociation is at the midpoint.

At the equivalence point, the quantity of the base added is exa~ly enough to consume

HA. At the equivalence point HA is converted to A-, a weak base. To calculate pH at

this point the equation is written for the weak base with water.

(3.17)

15

Page 21: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

The concentration of A- is no longer the initial concentration of HA, because it has

been diluted with the base. The concentrations ofHA and OH-are equal. Hence, since

the pOH can be calculated, pH can also be calculated. The equivalence point pH will

always be above 7 for the neutralization of strong base and weak acid, since the acid is

converted to its conjugate base at the equivalence point.

3. 3. 3 The strong acid and weak base neutralization

The strong acid and weak base system as shown in Fig. 3. 3 (McMillan 1984) is

distinguished by its steep slope in the lower pH scale range. The center of this steep slope

is in the lower pH scale range, and is the equivalence point. It is always below pH 7, and

it is dependent upon the dissociation constant of the weak base. The procedure to find the

pH at any point in the neutralization process and the equivalence point can be calculated

by using the procedure described in section 3.3.2.

3. 3. 4 The weak acid and weak base neutralization

The weak acid and weak base system in Fig. 3. 4 (McMillan 1984) is distinguished by

the lack of a steep slope throughout the range. The titration curve slope is greatest at the

equivalence point, but it is still relatively small compared to the previous systems. The

equivalence point ordinate depends upon both the acid and base dissociation constant.

Considering the stoichiometry for the neutralization of weak acid and weak base

K = Ka 1 K- -

- Ka(for BH+) -

16

(3.18)

Kb (3.19) Kw

Page 22: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

14

13

12

11

10

9

8 t

flH I

7 --

6

5

• 3

2

1

0 -0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6

Ratio of Reageot to tn1tuent F"""'·

Figure 3.3 Typical titration cwve for strong acid and weak base system (McMillan 1984)

17

1.8 2.1

Page 23: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

t.C

13

12

11

10

9

e -I

oH

: t 5 I ~

3

2

1

0

0 02 0.~ 0.6 0.8 1.0 1.2 1.4 1.6

Ratio of Reagent to Influent Flow

Figure 3.4 Typical titration curve for weak acid and weak base system (McMillan 1984)

18

1.5 2 .0

Page 24: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Combining the equations 3.18 and 3.19 it can be written as

HA+B<::>BH++A- K = KaKb. Kw

(3.20)

For weak acids and weak bases, K of the above reaction can be large or small. There

are three cases of concern.

Case 1: K is large ( K>>1).

If K is large the reaction goes to completion. When the reactants are mixed, they will

proceed to make products until one of the reactants is consumed. This case can be treated

as if one reactant is a strong acid or a strong base.

Case 2: K is not large.

In this case the reaction does not goes to completion because the value ofK is not

large. A substantial quantity of unreacted starting material will be in equilibrium with

products.

Case 3: Equimolar mixture ofHA and B, regardless of the size ofK.

An equimolar mixture of weak acid and weak base behaves as the intermediate form

of a polyprotic acid. The pH ofthe equimolar mixture should be very nearly midway

between pK3 for HA and pK3 for BH+.

A common misconception is that a titration curve consists of a single S-shaped curve.

In Fig. 3.5 (McMillan 1984), a weak acid with pKa dissociation at 2.5 and 5.5 pH is

titrated with a weak base with pKb dissociation constants at 8.5 and 11.5 pH. It is noted

that three S-shaped titration curves are formed with an equivalence point at the point of

steepest slope for each S. The dissociation constants have to be more than 2 pH units

apart to create multiple S-shaped curves. When ever an acid (base) is neutralized with a

base( acid), when exact amount of base (acid) necessary for stiochiometric reaction is

added the acid (base) is said to be neutralized and that particular point on titration curve is

19

Page 25: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

14

13

12

11

10

9 pKa=6.5

6

pH 7

6

s

4

3

2

1

0

0 02 0.4 0.6 0.8 1.0 1.2 1 .... 1.6 1.8 2.0

Ratio of Reagent to Influent Aow

Figure 3.5 MultipleS-shaped curves (McMillan 1984)

20

Page 26: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

called as equivalence point. Hence, in a mixture of acids, the acids are neutralized one by

one depending upon the value of their dissociation constants, the higher the dissociation

constant the earlier it gets neutralized. Hence, there forms multiple S-shaped curves and

multiple equivalence points. The curves are symmetrical because the concentrations and

the distances between the dissociation constants are equal. Normally pH titration curves

are not symmetrical.

3.4 Buffering

Buffering is defined as the capacity of a solution to resist changes in pH. Examples of

buffer solutions include mixtures of acetic acid and sodium acetate, ammonium nitrate and

ammonia, and the sodium salts of dihydrogen phosphate and mono hydrogen phosphate.

Any weak reagent discussed above buffers by holding a reserve of undissociated reagent.

The buffer consists of an acid and its conjugate base. To buffer effectively, there must be

a source of unionized agent available and a source of companion ions. For example, acetic

acid, though a weak acid, has very little buffering capacity above pH 6 where it is almost

completely ionized. However, at low pH values it has great capacity to absorb hydroxyl

ions. Similarly, a mixture of weak acid and its strong-base salt or a weak base and its

strong-acid salt will show a great capacity to resist pH changes by absorbing ions.

Commercial buffer solutions are usually prepared using the combinations.

For example, consider an acetic acid and sodium acetate buffer.

We have

CH3COOH --+- CH3COO- + H+

NaOH --+- Na+ + OH-.

(3.17)

(3.18)

From equation 3.17, the dissociation constant of acid can be written as

[C H3COO-][Ir]

Ka= [CH3COOH]

21

Page 27: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

The dissociation constant of acetic acid is given as

Ka = 1.75 x Io-s.

The extent of the dissociation of acetic acid is very small when , ~ompared to the

original acid concentration because the concentration of acetic acid is much larger than Ka and because the acetate ion furnished by the sodium acetate represses the dissociation of

acetic acid. So ifO.l N concentration of acetic acid and sodium acetate is used the pH of

the solution would be 4.76. The pH of this buffer changes by 0.1 pH if 10 ml of sodium

hydroxide ofO.l N is added.

3. 5 pH Control Difficulty

Generation of the titration curve either analytically or experimentally, and the

sensitivity of titration curve are the two most important difficulties associated with pH

control. Samples exposed to the air can absorb enough carbon dioxide to lower the pH.

This is a problem peculiar to nearly pure water and caustic samples. The pH of absolutely

pure water at 25° C can change from a pH of 7 to a pH of 5 simply by exposure to air.

The errors at the high and low ends of the pH scale depend upon the type of pH

measurement electrode used. This is particularly a problem for pH measurement above I 0

pH when the sample or reagent contains the sodium ion or other strong alkali ions. If the

titration curve changes with time, separate samples should be gathered over a

representative period and individually titrated. The samples should not be combined for

titration.

3. 5. 1 Titration curve generation

The analytical titration curves considered thus far involved only single, monoprotic

acids or bases. If a mixture of strong and weak, monoprotic and multiprotic reagents is

involved, then generation of an analytical titration curve becomes a difficult task though

22

Page 28: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

not impossible. One way to circumvent this problem is to generate the titration curve

experimentally in a laboratory sample. Once the titration curve is known, analytically or

experimentally, the titrant flow can be calculated and used for pH control. One of the

most important applications of pH control is continuous, large scale eftluent wastewater

neutralization. In this particular study, however, application of pH control was desired for

small quantities of wastes in a batch process. The acidic or caustic wastes generally

generated by the academic practices contain a wide variety of acids or caustics from

different sources. If the identification, concentration, and the equilibrium constant for all

the species in wastewater were known then the titration curve could be, in principle,

analytically determined. Determination of analytical titration curve is practically

impossible in the case of highly variant wastewater pH control. Experimental procedures

appear to be the best solution for the generation of titration curves for mixtures of

corrosive wastewater.

The titration curve generation method involves taking a small process sample in a

beaker and adding aliquots of a fixed concentration of the reagent to change pH. The

values are recorded as a curve of pH versus the amount of reagent added. The level of

reagent addition is reduced near the equivalence point in order to have a clear titration

curve which correctly gives the details of titration.

3 . 5. 2 Titration curve sensitivity

The relationship between pH and all possible combinations of strong and weak acids

and bases are explained in the above sections. The typical pH electrode can respond to

changes as small as 0. 001 pH, which means pH measurement can track changes of Sx 1 o-

10 at 7 pH. No other commonly used measurement is known to have this level extreme

sensitivity (McMillan 1984 ). The reagent demand varies in response to the titration curve

for each situation. Hence the titration curve will give an idea how much of reagent is

23

Page 29: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

needed. In a particular case at pH= 6, the amount of reagent needed relative to the

amount of reagent needed at pH = 7, is just one unit, whereas the reagent needed from pH

= 2 to pH= 7 requires 10,000 units (Hoyle, 1972).

24

Page 30: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTER4

EXPERIMENTAL SETUP AND PROCEDURE

A semi-automated batch process was selected to neutralize the wastewater produced

by the research and teaching laboratories at Texas Tech University. This was based on the

understanding that the wastes are typically of various composition and concentration. The

batch processing approach offers several advantages. The most important advantage is

the ability to retain the treated solution until its quality meets the required specifications

for release. When treating extremely corrosive wastes, this safe guard is mandatory.

Also, with the batch system, a single mixing vessel can be used to add the reagent needed

to neutralize the wastewater over a period of time. Batch treatment can also be used to

collect and treat small quantities of wastes that neutralize each other. This latter approach

represents a control method with obvious cost savings.

For small quantity generators (SQGs), neutralization of wastewater does not always

represent a viable option because of limitations in manpower or expertise. The simplicity

of the proposed system and its favorable economics should encourage SQGs to consider a

semi-automated batch system for neutralization. A brief description of various

components used with the experimental setup is given below. This will be followed by an

explanation of experimental procedure.

4.1 Apparatus

4. I. I In-line Electrode

The electrode used was a Signet's in-line (model2710) electrode. The electrode is

depicted in Fig. 4.1 (Signet's manual for pH sensor). The electrode is a double junction

electrode, which significantly reduces the migration of poisoning ions to the reference

25

Page 31: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

~Oaring .. ~ (SensOr/Housing)

@~~ . ....__. @SeN«--~~---~

Figure 4.1 In-line Electrode

26

Page 32: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

electrode, and thereby results in an increased electrode life. A silver/silver chloride

electrode in this pH sensor permits its use over a wide temperature range.

This electrode with its unique flat surface design is ideal for application in

wastewaters, such as those produced with lime slurries, pulp and paper, electroplating,

and other installations where coating, abrasion, breakage, or reference junction fouling

problems exist. The sensor must be installed with the electrode pointing downward to

insure adequate electrolyte flow. Therefore, for optimum performance, it was installed

vertically in the experimental setup. Where physical constraints exist, it can be installed at

a maximum 450 angle and still be functional.

4 .1. 2 pH controller

For pH measurement process control application, Signet's pH controller (Model

9030) was used. The modular "plug-in" input/output option cards allow the pH controller

to be customized to the needs of the user. All the functions are accessed and controlled

from the front panel, so there are no mechanical potentiometers which require adjustment.

The two line LCD features a 4.5 digital main display line plus an eight character,

alphanumeric line which is used to prompt the user through all calibration and output

control parameters. It can be operated between 32° to 1300 F. Display accuracy is plus

or minus 0. 02 of the pH scale. The gain is defined as the ratio of the change in the output

to the change in the input. The pH controller used is an on-off controller. The Lo relay

setpoint was set at 6. 5 and Hi relay setpoint was set at 7.5. So the pH controller switches

on the device connected to it as soon as the pH falls below 6.5 or above 7.5.

4.1.3 Metering pump

A metering pump (LMI b711-915) was installed which could be energized by the

signal from the pH controller. This pump responds to any dry switch closure. An

27

Page 33: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

adjustable electronic pressure control is another unique, standard feature on this pump.

Both the pump and the connecting tubing which was used are resistant to both acidic and

basic solutions. The pump has a capacity range of0.19 to 38.4 gaVday with a maximum

insertion pressure of 1Mpa.

In operation, the pump transfers the acidic or basic reagent when it is energized by

the pH controller. With this experimental design, the pH controller energizes the pump

when relay 1 ( LO relay setpoint) or relay 2 (HI relay setpoint) are on. Thus the pump is

automatically switches to the on mode whenever the pH falls below 6.5 or rises above

7.5; 6.5 and 7.5 being LO relay and Ill relay of pH controller. The flow rate that was

used in the lab scale experiments is 27 gals per day.

4 .1. 4 Mixers

In neutralizing the wastewater solution either in continuous streams or batch systems,

the wastewater needs to be well mixed with the reagent, so as to enable the neutralization

reactions to take place. The mixer assures good mixing of the wastewater solution with

reagent. In our system assembled in the treatment storage and disposal facility (TSD) of

Texas Tech University, a gear pump for recirculation was used to enhance the mixing of

the solution. The gear pump was connected to the bottom of the stainless steel holding

tank with thick walled PVC piping. The unthrottled flow rate of the gear pump was

measured at 125 gal/hr. An in-line pH sensor was placed in the discharge pipe from the

gear pump. The sensor reads the pH of the solution and relays the information to the pH

controller. The controller activates the metering pump which transfers the reagent needed

from the reagent tank to the holding tank in the neutralization process.

28

Page 34: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

4.2 pH Sensins and Transmission

A pH measuring and control device consists of a sensing part and a transmission part.

The pH probe, or sensing elements used in our system, was an in-line pH sensor which

was mounted vertically in the pipe line as explained earlier.

The transmission was accomplished with a pH transmitter. In this instance the small

m V current developed by the sensing glass electrode and reference electrode is converted

into pH units for recording. The pH sensor also sends the signal to the controller through

a cable.

4.3 Experimental Setup

Fig. 4.2 depicts the experimental setup that was assembled for a batch process, semi­

automated wastewater neutralization system. A holding tank with capacity of 3 5 gal was

used for the neutralization process of corrosive wastewater at the treatment storage and

disposal facility (TSD). A recirculating pump was connected to the bottom of holding

tank as shown in Fig. 4.2. The discharge line from the pump extends into the holding

tank, and has an in-line pH sensor. All the piping consists of thick walled poly vinyl

chloride (PVC) pipe.

The sensor cable was connected to the input terminal of the pH controller. The

controller was fitted with an output card, which was connected to the metering pump

switching circuit. Basically, the output card in the pH controller activates the metering

pump according to preset conditions. The pH controller is an on-off controller. These

preset conditions were selected as pH 6.5 for the LO relay setpoint and a 7.5 pH as them

relay setpoint. In this case, the control of the on-off switch of the reagent metering pump

is controlled by the pH reading. Two separate containers were used to store the

inexpensive acid and caustic reagents. The suction tube end of the metering pump is

immersed in the acid or caustic reagent according to the requirement to neutralize the

29

Page 35: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

~----------------------, I I I . I

Metering Pump

P2

Base T2B

Holding Tank Tl

V2

Pump Pl

pH Controller C 1

T I I

pH Sensor Sl

Figure 4.2 Schematic of Experimental Setup.

30

VI

Yorain

Page 36: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

corrosive wastewater solution. The stroke of the metering pump, and, hence the flow rate

of the metering pump, can be adjusted with a knob on the front panel of the reagent pump.

The flow rate of the metering pump was set at 27 gals per day. The discharge end of the

tubing from the reagent pump is arranged in such a way that the flow of the reagent is

directed into the holding tank. If necessary a timer can be used to keep track of elapsed

time for the process, and, thereby provide a plot or curve of pH versus time.

4.3.1 Preparing reagent solutions

Acidic or basic reagents were used as to neutralize the wastewater. The acid reagent

used for neutralizing basic wastewater was hydrochloric acid (strong acid), and the basic

reagent used for neutralizing acidic wastewater was sodium hydroxide(strong base).

These solutions were prepared in the concentration range 0.01 N to 0.03 N, which is an

approximate concentration range for many wastewater neutralizing reagents. However,

the results can be extrapolated to higher or lower concentrations. The reagents are

prepared with deionized water.

The various calculations that are needed in preparing the solutions are described as

follows. Most of the commercially available acids or bases are in the form of their highly

concentrated solutions. The solutions are available in glass bottles with labels containing

relevant information, such as density, specific gravity, normality, and weight percent. To

prepare a required dilute solution it is necessary to know the relationship between

normality and the weight percent. This relationship is given as

(4.1)

Where

N Required normality of the dilute solution,

31

Page 37: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Pc : Density of the concentrated solution in gm/ml,

V c Volume of the concentrated solution in ml,

X Weight fraction of the component,

E : Equivalent weight of the component in gm/gm equivalents,

V : Estimated volume of the dilute solution in liters.

For example, it is necessary to calculate the volume of30% by weight of sodium

hydroxide solution needed to prepare 30 liters ofO.Ol N sodium hydroxide solution. By

using the above equation

Vc = 0.01 X 40 X 30 = 30_2?ml. 1.3215 X 0.30

Equation 4.1, therefore, is useful for conversion of normality to weight percent or

vice versa. However, if the normality of the concentrated solution is known, then the

following formula can be utilized to calculate the volume needed based on the

concentration requirements for the dilute solution.

(4.2)

Where

N8 : Normality of the dilute solution,

Nb : Normality of the concentrated solution,

V a Volume of the dilute solution in ml,

V b Volume of the concentrated solution in mi.

The volume of the concentrated hydrochloric acid solution of 5 N required to prepare

50 liters ofO.Ol N dilute solution is

- 0.01 X 50000- IOOml Vb- - · 5

32

Page 38: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Some of reagents are available in the form of pellets and powders which are actually

cheaper than the concentrated solutions. In this case it becomes necessary to calculate the

weight of reagent required to prepare a dilute solution. The basic definition of normality

is given by

Where

N= W ExV

N : Normality of the dilute solution,

W : Weight of the sample in gm,

V : Volume of the dilute solution in liters,

(4.3)

E : Equivalent weight of the component in gm/gm equivalents.

For example, the quantity of sodium hydroxide pellets or powder required to make

0. 0 1 N 50 liter solution is

w 0.01 X 50 X 40= 20gms.

It is important to note that the number of replaceable hydrogen ions before

neutralization are two in case of phosphoric acid even though it is a triprotic acid. In case

of phosphoric acid solution preparation, the equivalent weight is taken as half of molecular

weight even though in general equivalent weight is one-third of molecular weight.

4.3.2 pH sensor calibration

The pH sensor should be calibrated from time to time to assure accurate results. The

pH sensor is typically calibrated with the help of the buffer solutions. Buffers of pH 7. 0

and pH 4. 0 were utilized to calibrate the pH sensor for the acidic solutions, whereas

buffers of pH 7. 0 and pH 10.0 are used to calibrate the pH sensor for the basic solutions.

It was observed that the pH calibration procedure can still have an error up to ± 0. 5 units

33

Page 39: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

from the true value. This error arises from various factors like the age of the probe,

temperature changes, and electronic drift, etc.

4.3.3 Metering pump calibration

The metering pump needs to be calibrated from time to time. The calibration process

for the pump is as follows. The pump should be primed. The pressure control knob is

turned fully clockwise. Place the valve in a graduated container with a volume of 1000

mi. The pump is then switched on. Using a timer tum the pump on for a measured

amount of time. Then calculate the pump output theoretically (maximum output X the %

stroke) and compare the results with the volume displaced in the graduate. If there is any

deviation adjust stroke estimating required correction and the above procedure is

repeated.

4. 4 Experimental Procedure

The experimental procedure will be explained with the help of Fig. 4.2 on page 28.

The wastewater that requires neutralization is emptied into the holding tank. For strong

acidic or basic wastes, the maximum volume of wastewater that could be neutralized is

slightly less than half the capacity of the holding tank. The initial pH of the wastewater

should be measured either with a simple pH meter or by switching off the reagent pump

and noting the reading displayed on the pH controller. Once the pH of wastewater

solution is known, the suction end of the metering pump is placed in the corresponding

reagent required to neutralize the wastewater in the holding tank.

Enhanced mixing of the wastewater is assured with the recirculating pump which can

recirculate at a flow rate of 125 gal/hr. This pump has a capacity to empty the tank 3.59

times an hour. The recirculating pump is switched on after opening the valve to allow the

flow of wastewater into the holding tank. The pH controller was calibrated when it was

34

Page 40: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

used for the first time, and, for good performance, it should be calibrated from time to

time with buffer solutions of pH 7. 0 and pH 4. 0 for acidic solutions and pH 7. 0 and pH

10.0 for basic solutions. The pH controller is then switched on. The metering pump is

switched on after making sure that the suction end and discharge end of the metering

pump are in the appropriate containers.

Once the pH electrode relays the pH of the wastewater solution to the pH controller,

the pH controller activates the metering pump if the pH of the wastewater falls outside the

pH range of relay set points. The pH controller thus operates the metering pump and

transfers the reagent required to neutralize the wastewater in small quantities. Relay set

points are set points that represent the pH at which each relay is energized. In LO relay

operation (lower limit), the relay is energized when the pH drops below the setpoint and is

de-energized when the pH rises above the setpoint. In Ill relay operation (upper limit),

the relay is energized when the pH rises above the setpoint and is de-energized when the

pH falls below the setpoint.

A timer was used to keep track of elapsed time and pH of the wastewater solution

was recorded. Normally process reagent was continuously added in small quantities by

the metering pump until the pH was brought into limits. The pH readings were observed

at the beginning of the experiment on the pH controller for a while to make sure that pH

value of the wastewater solution is rising or falling as per the case to make sure that the

pump suction end of the tubing is in the right reservoir. The pH controller then

automatically de-energizes the metering pump once the pH of the solution is within LO or

In relay setpoints, and the process is stopped. A plot of pH versus time can be made to

see the exact results of the neutralization process. These curves typically look like a

titration curve with experimental constraints. After treatment and final pH check by the

operator, the wastewater is ready to be transferred to the drain and the city sewer system.

35

Page 41: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTERS

RESULTS AND DISCUSSION

In Chapter 4, the design and development of the batch system neutralization

procedure was discussed in detail. This chapter presents the actual performance results

obtained with the non-linear controller for a variety of waste acids and bases. The test

runs were carried out on the bench scale setup described in Chapter 4. The samples

selected were typical wastes from research and teaching laboratories. Some of the

wastewater was supplied by the EH&S Department of Texas Tech University. The

experiments were run for all possible scenarios that might arise during the process of

neutralization of typical wastewaters.

The reagents were selected on the basis of cost effectiveness. They are hydrochloric

acid of concentration O.OIN as acidic reagent and sodium hydroxide of concentration

O.OIN as basic reagent. Reagents like sodium carbonate of0.01N and acetic acid O.OIN

were also tested for cases which required neutralizing strong acid with weak base and

strong base with weak acid. These weak reagents were also used to see the results of

weak acid weak base neutralization. Section 5.1 describes how the system works for

hydrochloric acid and sodium hydroxide. Section 5.2 deals with the working procedure

for a strong acid and weak base, i.e., hydrochloric acid and sodium carbonate. Similarly,

Sections 5.3 and 5.4 describes the procedure and the results obtained for a weak acid

against a strong base and a weak base.

5.1 The Strong Acid versus Strong Base

There were two types of experiments performed in this instance: neutralization of a

typical strong acid with a strong basic reagent and the neutralization of a strong base with

a strong acidic reagent.

36

Page 42: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

In the fist case hydrochloric acid, a typical acidic waste produced across campus, was

emptied into the holding tank. The recirculating pump was switched on to recirculate the

waste acid. As soon as the controller receives a signal from the probe it displays the pH of

the wastewater solution. When the wastewater pH falls below pH 6.5, the metering pump

is activated and starts transferring the strong basic reagent. The strong basic reagent is

added incrementally until the solution in the tank attains a pH of6.5. As soon as the pH

of the solution reaches 6.5 the pump automatically shuts off flow of the basic reagent.

The last few drops of reagent, after good mixing by recirculating pump, will make the

solution pH, approximately 7.0. The final pH level is the reason for setting up the LO

relay setpoint at 6. 5 and m relay setpoint at 7. 5.

Figure 5.1 shows the results obtained when sodium hydroxide of concentration 0.01N

was used to neutralize hydrochloric acid. The results are in the form of a curve pH versus

time in minutes. The results obtained by the semi-automated batch system for wastewater

treatment demonstrate that the wastewater pH was brought well within the limits specified

by EPA prior to discharge into a publicly owned water treatment (POW).

The above procedure was repeated for the neutralization of strong base, i.e., sodium

hydroxide, with hydrochloric acid. The results are shown in Figure 5 .2. The results show

that the pH of the solution was brought well within limits of EPA. The experimental

constraints being the time lag in the reading received on the pH controller display board

and the actual pH of the solution. The final pH of the wastewater solution was 7.1 0.

The strong acid versus strong base titration curve has a tremendous gain· at the

neutral point. This characteristic makes the neutralization of such wastes highly

challenging. But with the semi-automated batch system the problem is not

insurmountable, because the amount of wastewater to be neutralized is large when

compared with the reagent flow rate. In this way the problem of sudden rise in. pH at the

37

Page 43: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

14

12 2 0 +-------~----~~----~-------+------~------+-------~----~~----~

0 0.

5 1

1.5

2 2.

5 3

3.5

4 4.

5

Tim

e in

min

Fig

ure

5.

I R

esul

ts o

fNeu

tral

izat

iono

fHyd

roch

lori

c A

cid

wit

h S

odiu

m H

ydro

xide

Page 44: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

w

\0

13

11 9

:g_

7 5 3 1

0 2

Neu

tral

Lin

e

4 6

8 10

12

14

16

18

20

22

24

26

28

30

32

Tim

e in

min

Figu

re 5

.2

Res

ults

of N

eutr

aliz

atio

n o

f Sod

ium

Hyd

roxi

de w

ith H

ydro

chlo

ric

Aci

d

Page 45: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

neutral point can be managed, and it is possible to keep the wastewater solution pH well

within the EPA mandated limits.

5.2 Strong Acid versus Weak Base

This case was also tested for both possibilities, one neutralizing strong acid with weak

base and the other neutralizing the weak base with strong acid. The strong acid and weak

base typically obtained from the research and academic laboratories were hydrochloric

acid and sodium carbonate.

Figures 5.3 and 5.4 represents the results obtained for both cases of neutralization.

The results shown in Figure 5. 3 demonstrate that the pH of the hydrochloric acid solution

was brought well within limits ofEPA and the pH of the final solution was 6.6. The

results show that the time taken to neutralize hydrochloric acid by sodium carbonate is

approximately 38 minutes whereas in the other case only 4.5 minutes are required. Figure

5.4 demonstrate that the pH of the final basic solution was 7. Neutralization requires

more time to neutralize the strong acid with weak base. However, for our system, time is

not an important constraint. The technician can leave the system on and then come back

at a convenient time and to drain the wastewater when neutralization is completed.

5.3 Weak Acid versus Strong Base

This case was also tested for both possibilities, one neutralizing weak acid with strong

base and the other neutralizing the strong base with weak acid. The weak acid and strong

base selected were acetic acid and sodium hydroxide. The same experimental procedure

as discussed in section 4.4 was repeated for both the cases, and the results are plotted in

Figures 5. 5 and 5. 6. Figure 5.5 shows the results of the acetic acid neutralization with

sodium hydroxide. Figure 5. 6 shows the results of the sodium hydroxide neutralization

with acetic acid.

40

Page 46: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

13

11 9

=a 7

~ -

5 3 1

0 2

4 6

8

Neu

tral

Lin

e

~

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

Tim

e in

min

Figu

re 5

.3

Res

ults

ofN

eutr

aliz

atio

n o

f Hyd

roch

lori

c A

cid

with

Sod

ium

Car

bona

te

Page 47: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

13

-

11

-

9 -

:I:

0..

7

~

I 5 ~

/ N

-~

Neu

tral L

ine

I 3

-

I 1

I I

I I

I I

I I

0 0.

5 1

1.5

2 2.

5 3

3.5

4 4.

5

Tim

e in

min

Figu

re 5

.4

Res

ults

ofN

eutr

aliz

atio

n o

f Sod

ium

Car

bona

te w

ith H

ydro

chlo

ric A

cid

Page 48: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

13

11

I N

eutra

l Lin

e '

9

::X:: 0..

7

I ~

w

5 3 1

0 2

4 6

8 10

12

14

16

18

20

22

24

26

Tim

e in

min

Figu

re 5

.5

Res

ults

of N

eutra

lizat

ion

of A

cetic

Aci

d w

ith S

odiu

m H

ydro

xide

Page 49: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

13

+

11

-

9

:t

0..

7

1

~

I 5 +

~

I 3

-

1

0

-7

Neu

tral

Lin

e

i I I

1 2

I 3

Tim

e in

min

I 4

Fig

ure

5.6

Res

ults

of

Neu

tral

izat

ion

of

Sod

ium

Hyd

roxi

de w

ith A

cetic

Aci

d

l I

5 6

Page 50: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

5.4 Weak Acid versus Weak Base

This case also tested for both possibilities, one neutralizing weak acid with weak base

and the other neutralizing the weak base with weak acid. Acetic acid and sodium

carbonate are considered for this experiment. The curves in Figures 5. 7 and 5. 8 show the

results obtained for both cases. The time taken for neutralizing the acetic acid was

approximately 24 minutes whereas the time taken for neutralizing the sodium carbonate

required approximately 6 minutes. The curves looks like the portions of typical titration

curve of weak acid versus weak base.

The main difficulties observed with this kind of experimental setup are as follows.

The pH reading that is displayed on the display board of pH controller is different from the

actual solution pH in the tank. The reagent is pumped to and mixed in the tank almost

instantaneously. It takes few seconds for the solution in the tank to reach the sensor. It

was observed that there was a probable error of approximately± 0.5 pH to ±0.1 pH

depending upon the kind of waste that is being treated. There are also some variations

caused by contamination of the solution by absorption of carbon dioxide from air, and

imperfect mixing. These source of variation can hypothetically effect the pH of the

solution to some extent.

The dissociation constants vary with temperature, and, hence the pH of the solution

varies with temperature, as a consequence the pH of the solution will also vary with

temperature. The dissociation constant is a weak function of temperature. The error

caused by operating between 40 and 800 F over the range from pH 6 to 8 without a

temperature compensation is only ±0. 03 pH units. This is hardly a significant error

because the LO relay setpoint and m relay setpoint are well within the range from 6 to 8

pH units. The error in this experiment will be smaller because the pH sensor that was used

has a temperature compensator. The pH sensor can be operated efficiently in the range of

45

Page 51: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

~

0'\

:X::

0.

14

12

10

Neu

tral

Lin

e

8 6 4 2 0 +-----+-----+-----+-----+-----r-----r-----~--~----~----~-----+----~

0 2

4 6

8 10

12

Tim

e in

min

14

16

18

Fig

ure

5.7

Res

ults

ofN

eutr

aliz

atio

n o

f Ace

tic a

cid

with

Sod

ium

Car

bona

te

20

22

24

Page 52: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

13

11 9

::t:

0.

7

I "'

~

I /

'-l

5 t

Neu

tral L

ine

I 3 1

0 0.

2 0.

4 0.

6 0.

8 1

1.2

1.4

1.6

Tim

e in

min

Figu

re 5

.8

Res

ults

of N

eutra

lizat

ion

of S

odiu

m C

arbo

nate

with

Ace

tic A

cid

Page 53: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

32 to 185° F. Hence temperature does not affect the pH readings significantly in these

wastewater neutralization studies, because the experimental setup is in a temperature

controlled room.

Overall, this semi-automated batch system for the neutralization of wastewater

produced by Texas Tech University worked well for acidic and basic solutions tested.

Economically and time-wise, this system solves many ofthe problems of hazard waste

neutralization for acidic and basic wastewater. The system is simple to operate and

maintain. The results obtained demonstrate for SQG's the effectiveness of this system to

economically neutralize wastewater . A simplified economic analysis of the system was

made and compared with the cost incurred by conventional third party disposal methods in

order to estimate the cost-benefit ratio. It is observed that semi-automated batch process

could save the expenditure of wastewater neutralization of Texas Tech University by

$18,000 over a five-year period oftime.

48

Page 54: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

CHAPTER6

CONCLUSIONS AND RECOMMENDATIONS

Semi-automated batch process techniques were applied to the controVadjustment of

pH processes. This technique was successfully demonstrated on a bench scale with an in­

line pH controller. The model was tested for several kinds and concentrations of mineral

and organic acids and caustic wastes. The system successfully neutralized the mineral or

organic acids and caustic wastes using inexpensive and easily available reagents.

The system was setup in the TSD facility for EH&S Department's use. After it was

tested, the system is ready to function at the designed level. However, the system could

be made more sophisticated by incorporating some small changes. These changes could

not be implemented at this point of time because of financial constraints. Another pH

sensor and controller along with a metering pump would eliminate the problem of

changing reagent tanks as per the requirement. This second in-line controller should be

able control another metering pump, which is connected to dedicated acid or caustic

reagent. This addition would solve the problem of changing the suction end tube of

metering pump from acid to base reagent whenever there was a change in the type of

wastewater being treated. The electrodes still need to be checked from time to time. A

spare set of electrodes should be available to replace a faulty electrode.

Environmental regulations change from time to time. With inevitable change, future

requirements may mean that a computer will be needed between the controller and

metering pump along with AID or D/ A converter. This will provide the technician with

the ability to inventory all the wastes that are being neutralized, and to store other details

such as the final pH and quantity of the of the solution left in the holding tank.

49

Page 55: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

BffiLIOGRAPHY

"Programmable controllers cut industrial wastewater treatment costs," Pollution Engineering, V 21, pp. 84, May 1991.

"The automated wastewater plant," Chemical Engineering, V 100, pp. 147, January 1993.

Armour, M.A. :Hazardous laboratory chemicals. Disposal guide, CRC Press, Boca Raton, FL, 1991.

Freeman, H.M. : Standard handbook of hazardous waste treatment and disposal, Mc­Graw Hill Company, New York, 1989.

Goldman, Jr. J.C. and P.T. Bowen: "Exploring wastewater treatment: A treasure chest oftechnologies," Pollution Engineering, V 24, pp. 56-62, September 1992.

Gray, D.M. and J. Marshall :"How to choose a pH measurement system," Pollution Engineering, V 24, pp. 45-47, November 1992.

Gustafsson, T.K. and K.V. Wallaer: "Myths about pH and pH control," AICHE Journal, V 32(2), pp.335-337, 1986

Gustafsson, T .K.: "Calculation of the pH value of mixture of solutions - An Illustration of the use of chemical reaction invariants," Chemical Engineering Science, V 37(9), pp.1419-1421, 1982.

Harris, D.C.: Quantitative chemical analysis (2nd ed.), W.H.Freeman and Company, New York, 1987.

Horwitz, B.A.: " pHrustrations of a process engineer," Chemical Engineering Progress, V 89, pp. 123-125, March 1993.

Hoyle, D. C.: "The effect of process design on pH and pion control." Proceedings of 18th ISA-AID Symposium, San Francisco, CA, 1972.

Jacobs, O.L.R., W.A. Bardan and C. G. Proudfoot: "Computer-aided design of systems for regulating pH." Chemical Engineer, pp.19-21, March 1984.

Kalis, G.: "How accurate is your pH analyzer?" Intech, V 37, pp. 5~58, June 1990.

Kalis, G. and N.Nichols: "Combine monitoring techniques to advance pH control," Power, V 135, pp. 64-65, September 1991.

50

Page 56: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Kaufinan, J. A. : Waste disposal in academic institutions, Lewis Publishers, Inc, Chelsa, MI, 1990.

Kendrick, A.: "Tight pH control key to waste treatment process," Process Industries Canada, V 68, November 1984.

LMI B711-915, Metering pump Instruction manual, Liquid Metronics Division, Acton, MA, 1993.

Mahuli, S.K., R.R. Rhinehart and J.B. Riggs: "pH control using a statistical technique for continuous on-line model adaptation," Computers & Chemical Engineering, V !1, pp. 309-317, April 1993.

Mahuli, S.K.: "Non-linear model-based control of pH," Master's thesis, Texas Tech University, August 1991.

McMillan, G.K.: "pH control: A magical mystery tour," Intech, Volume 31, pp. 69-76, September 1984.

McMillan, G.K.: pH control, Instrument Society of America, 1984.

Peters, D. G., J.M. Hayes, G.M. Hieftje: A brief introduction to modem chemical analysis (Saunders Golden Sunburst Series), W.B. Saunders Company, 1976.

Piovoso, M.J. and J .M. Williams : " Self-tuning pH control: A difficult problem, An effective Solution," Intech, V 32, pp 45-49, May 1985.

Powers, P. W. : How to dispose of toxic substances and industrial wastes, Noyes Data Corporation, Park Ridge, NJ, 1976.

Rittenhouse, R. C.: " Wastewater management rises top priority," Power Engineering, V 96, pp.21-26, October 1992.

Ross, M.: "pH control from practical point ofview," Metal Finishing, V ll pp. 47-48, November 1989.

Shinskey, F.G.: pH and pion control in process and waste streams, Wiley-Interscience, New York, 1973.

Signet 2712, pH Sensor Instruction manual, George Fischer Signet Inc, Tustin, CA, 1992.

Signet 9030 lntelek Pro, pH Controller Instruction manual, George Fishcer Signet Inc, Tustin, CA, 1992.

Vetrovec, F.: "Controlling pH automatically," Instruments & Control Systems, V 59, pp. 59-60, January 1986.

51

Page 57: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

APPENDIX A

ECONOMIC JUSTIFICATION

An economic analysis was made to estimate the cost-

benefit ratio for a semi-automated batch system desiqned to

neutralize the wastewater produced by teachinq and research

laboratories of Texas Tech University. The EH&S Department

currently expends $20 per kiloqram for disposal of corrosiv~

wastewater. The University produces approximately 200

kiloqrams of hazardous wastewater. Approximately $20,000

has been spent for third party disposal over the last five

years.

The total cost incurred for the development of the

semi-automated batch system for neutralization is as

follows.

Meterinq Pump

pH Controller

pH Sensor

Total

• •

• •

• •

• •

$ 662.00

$ 635.00

$ 285.00

$1582.00

This total plus additional reaqent costs and

miscellaneous expenses could run to only $2000 over five

years. The listed equipment has a workinq life in excess of

five years. Hence, at present generation rates, the use of

neutralization for hazardous waste reduction by the semi-

52

Page 58: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

automated batch process would save the University $

18,000.00 over a five year period.

Hence, this or a similar semi-automated batch process

can be adopted by any small quantity generator as a means of

disposal for the corrosive wastewater in compliance with EPA

regulations. This approach is currently more cost effective

(10/1) than third party disposal.

53

Page 59: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

APPENDIX B

OPERATING MANUAL

Nomenclature

V1, V2 Manual operated valves

C1 pH controller

P1 Recirculatory pump

P2 Metering Pump

S1 pH sensor

T1 Holding Tank

T2A Acid Reagent Tank

T2B Base Reagent Tank

The schematic is shown in Fig. 4.2 in page 30.

Initial Conditions

1. V1 is closed.

2. V2 is open.

3. P1 turned off.

4. P2 turned off.

5. All the power switches turned off.

operating Procedure for Acidic Wastewater Solution

1. Transfer the wastewater solution into the holding

tank(T1). The maximum quantity of wastewater solution at

one time should not exceed 17 gals(60 1).

2. Make sure V2 is open.

54

Page 60: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

3. Place the suction end of metering pump from the water

tank to the basic reagent tank(T2B).

4. Turn on the recirculatory pump(P1).

5. Turn on the power supply to the pH controller(C1) and

metering pump(P2).

6. Adjust the knob for desired stroke (%80 optimum).

7. Monitor the pH on the pH sensor(S1), making sure the

pH of the wastewater is rising.

8. When the metering pump(P2) stops transferring the

reagent, check the pH of the wastewater solution on the pH

controller display board (it should be between 6.5 and 7.5

pH).

9. Check the pH of the wastewater solution with the hand

pH meter for a second confirmation.

Initial Conditions

1. V1 is closed.

2. V2 is open.

3. P1 turned off.

4. P2 turned off.

5. All the power switches turned off.

Operating Procedure for Basic Wastewater Solution

1. Transfer the wastewater solution into the holding

tank(T1). The maximum quantity of wastewater solution at

one time should not exceed 17 gals(60 1).

2. Make sure the valve V2 is open.

55

Page 61: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

3. Place the suction end of metering pump from the water

tank to the acidic reagent tank(T2A).

4. Turn on the recirculatory pump(Pl).

5. Turn on the power supply to the pH controller(Cl) and

metering pump(P2).

6. Adjust the knob for desired stroke (tao optimum).

7. Monitor the pH on the pH sensor (Sl) and making sure

the pH of the wastewater is dropping.

8. When the metering pump(P2) stops transferring the

reagent, check the pH of the wastewater solution on the pH

controller display board (it should be between 6.5 and 7.5

pH).

9. Check the pH of the wastewater solution with the hand

pH meter for a second confirmation.

Shut Down Procedure

1. Turn-off the power supply to pH controller(Cl).

2. Turn-off the power supply to the metering pump(P2).

3. Close valve V2.

4. Open valve Vl.

5. After neutralized solution is drained out, turn-off

the recirculatory pump (Pl).

6. Close valve Vl.

1. Place the suction end of the metering pump(P2) in

water tank.

56

Page 62: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Emergency Shut oown Procedure

1. Turn-off the power supply metering pump.

2. Turn-off the power supplies.

Safety Requirement

1. Wear safety goggles, gloves and lab apron when

preparing reagent solution as well as when running the batch

system.

2. When emergency happens, turn-off the metering pump

first and then turn-off all the power supplies.

3. All chemicals must be labeled.

4. Floor must be kept dry and clean. Any spill should

be cleaned up immediately.

5. Flammable and highly corrosive materials are not to

be neutralized in this batch system.

6. Final pH check before draining out the wastewater to

confirm the wastewater pH is well within limits of EPA.

7. Do not open V1(drain valve) at any time except when

the wastewater is neutralized and ready to drain out.

Chemical used

1. 0.01-0.03 N Sodium hydroxide as basic reagent.

2. 0.01-0.03 N Hydrochloric acid as acidic reagent.

3. 0.01-0.03 N Acetic acid as weak acidic reagent.

4. 0.01-0.03 N Sodium carbonate as weak basic reagent.

57

Page 63: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

APPENDIX C

HAZARDOUS OPERABILITY STUDY

58

Page 64: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Tab

le C

. I H

azar

dous

Ope

rabi

lity

Stud

y

Item

Li

ne o

r E

q-P

roce

ss

Dev

iati

on

Poss

ible

Cau

ses

Poss

ible

con

sequ

e-A

ctio

n re

quire

d

uipm

ent

para

met

er

nces

1 H

oldi

ng ta

nk

Leve

l M

ore

I. M

ore

addi

tion

of re

agen

t I.

Spill

s in

to th

e sp

ill t

ank

1. St

op th

e m

eter

ing

pum

p

2. N

eutr

aliz

atio

n of

conc

en-

2. D

ilute

the

was

tew

ater

bef

ore

trat

ed w

aste

wat

er

neut

raliz

atio

n

3. p

H s

enso

r bro

ken

3. C

heck

/repl

ace

the

sens

or

4. p

H c

ontr

olle

r bro

ken

4. C

hedc

/repl

ace

pH c

ontr

olle

r

Les

s 1.

VI

open

I.

Env

ironm

enta

lly h

azar

dous

1.

Clo

se v

alve

VI

2. P

ossi

ble

leak

in p

ipin

g 2.

Lea

ks in

to th

e sp

ill ta

nk

2. R

epla

ce p

ipin

g

3. P

ossi

ble

leak

in p

ump

3. R

epla

ce p

ump

Con

cent

ra-

As

wel

l as

I. pH

sen

sor b

roke

n I.

No

good

mix

ing

I. C

heck

/repl

ace

the

sens

or

"" tio

n 2.

pH

con

trol

ler b

roke

n 2.

Pre

ssur

e ris

e in

pip

ing

2. C

heck

/repl

ace

the

cont

rolle

r \0

3.

V2

is c

lose

d 3.

Ope

n va

lve

V2

pH

Hig

her

l. F

ast a

dditi

on o

f rea

gent

I.

May

cro

ss s

etpo

int

1. R

educ

e th

e %

stro

ke o

f m

eter

ing

pum

p

Low

er

l. S

low

add

ition

of r

eage

nt

l. C

onsu

mes

tim

e l.

Inc

reas

e th

e %

stro

ke o

f

2. R

ecirc

ulat

ory

pum

p is

off

m

eter

ing

pum

p 2.

Mak

e su

re th

e pu

mp

is o

n

2 V

alve

VI

Flow

N

o 1.

Val

ve V

I is

clo

sed

I. Pr

essu

re in

crea

se in

the

I. O

pen

valv

e V

I

2. P

ump

is b

roke

n pi

ping

2.

Rep

lacd

fix

pum

p

3. P

ump

is c

logg

ed

2. C

once

ntra

tion

rise

in ta

nk

3. C

lean

pum

p

4. P

ipe

is c

logg

ed

3. N

o dr

ain

faci

lity

4. C

lean

pip

e

S. V

alve

is c

logg

ed

4. N

o go

od m

ixin

g S.

Cle

an v

alve

VI

Page 65: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

Tab

le C

. I H

azar

dous

Ope

rabi

lity

Stu

dy

3 V

alve

V2

Flow

N

o 1.

Val

ve V

2 is

clo

sed

I. Pr

essu

re i

ncre

ase

in t

he

1. O

pen

valv

e V

2

2. P

ump

is b

roke

n pt

pmg

2. R

epla

ce/f

ix p

ump

3. P

ump

is c

logg

ed

2. C

once

ntra

tion

rise

in ta

nk

3. C

lean

pum

p

4. P

ipe

is c

logg

ed

3. N

o dr

ain

faci

lity

4. C

lean

pip

e

S. V

alve

is c

logg

ed

4. N

o go

od m

ixin

g S.

Cle

an v

alve

V2

4 R

ecir

cula

tory

Fl

ow

No

1. P

ipe

is c

logg

ed

I. C

once

ntra

tion

rise

in ta

nk

I. C

lean

/rep

lace

pip

e

pum

p 2.

Pum

p br

oken

2.

Rep

lace

pum

p

3. P

ump

turn

ed o

ff

3. M

ake

sure

pum

p tu

rned

on

4. N

o w

aste

wat

er in

tank

4.

Tra

nsfe

r w

aste

wat

er in

to

hold

ing

tank

/ turn~ff th

e pu

mp

0\

S M

eter

ing

Flow

N

o I.

pH

of w

aste

wat

er is

I.

Pres

sure

ris

e 1.

Dra

in th

e ne

utra

lized

was

te

0 pu

mp

betw

een

6.5

and

7.S

2. p

H m

ay n

ot r

each

set

poin

t 2.

Cle

an/r

epla

ce p

ipin

g

2. P

ipe

is c

logg

ed

3. R

efill

the

reag

ent

3. N

o re

agen

t avi

alab

le

4. R

epla

ce th

e co

ntro

ller

4. p

H c

ontr

olle

r is

bro

ken

Mor

e I.

% s

trok

e is

hig

h 1.

Fas

t pH

cha

nge

1. R

educ

e th

e %

str

oke

Less

1.

% s

trok

e is

low

1.

Slo

w p

H c

hang

e 1.

Inc

reas

e th

e %

str

oke

6 pH

sen

sor/

pH

Fa

ster

1.

Fas

t add

ition

of r

eage

nt

1. M

ay c

ross

set

poin

t 1.

Red

uce

%st

roke

Con

trol

ler

2. H

igh

% s

trok

e 2.

Neu

tral

ize

in b

ulk

3. L

ess

quan

tity

of w

aste

-w

ater

com

pare

d to

the

flow

ra

te o

f rea

gent

Page 66: WASTEWATER NEUTRALIZATION USING A SEMI-AUTOMATED …

0\ -

pH s

enso

r I

Con

trol

ler

pH

Slow

er

Tab

le C

. I H

azar

dous

Ope

rabi

lity

Stu

dy

I. Sl

ow a

dditi

on o

f rea

gent

2.

Low

% s

trok

e 3.

Con

cent

rate

d w

aste

wat

er

in h

oldi

ng ta

nk

I. S

low

neu

tral

izat

ion

2. M

ay o

verf

low

the

tank

I.

Inc

reas

e th

e %

stro

ke

2. D

ilute

the

was

tew

ater

be

fore

neu

tral

izat

ion