DESCRIPTION The nVent RAYCHEM ECW-GF-DP is a remote display panel only for the RAYCHEM ECW-GF electronic controller. The ECW-GF-DP allows remote monitoring of the heating cable system operation. The display has LED indicators which signal communication loss to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be located up to 328 feet (100 m) from the ECW-GF controller. The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Refer to the ECW-GF installation instructions (H58339) for further details. For technical support, call nVent at (800) 545-6258. TOOLS REQUIRED • Large slotted screwdriver • Needle nose pliers • Small slotted screwdriver • Wire strippers ADDITIONAL MATERIALS REQUIRED • Duplex junction box • 1/2 inch conduit • Communication cable: 8 conductor 22 AWG shielded Alpha Cat. No. 1298C or equivalent This unit should be installed, opened, and repaired by qualified personnel only. To avoid shock hazard, do not open the front cover with power connected to the controller or any controlled equipment. Always open any circuit breakers and remove power from any high voltage electrical circuits installed in close proximity to or sharing an enclosure with the ECW-GF-DP prior to removing the enclosure cover plate. Read all instructions carefully before installation. Save this Installation and Operation Instruction for future reference. WARNING: KIT CONTENTS Item Qty Description A 1 Display panel with mounting screws B 1 Single duplex outlet cover plate with mounting screws A B APPROVALS Nonhazardous Locations ECW-GF-DP Remote Display Pane Installation and Operation Instructions

WARNING...to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: WARNING...to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be

DESCRIPTIONThe nVent RAYCHEM ECW-GF-DP is a remote display panel only for the RAYCHEM ECW-GF electronic controller. The ECW-GF-DP allows remote monitoring of the heating cable system operation. The display has LED indicators which signal communication loss to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be located up to 328 feet (100 m) from the ECW-GF controller.The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Refer to the ECW-GF installation instructions (H58339) for further details.For technical support, call nVent at (800) 545-6258.

TOOLS REQUIRED• Large slotted screwdriver • Needle nose pliers• Small slotted screwdriver • Wire strippers

ADDITIONAL MATERIALS REQUIRED• Duplex junction box• 1/2 inch conduit• Communication cable: 8 conductor 22 AWG shielded

Alpha Cat. No. 1298C or equivalent

This unit should be installed, opened, and repaired by qualified personnel only.To avoid shock hazard, do not open the front cover with power connected to the controller or any controlled equipment. Always open any circuit breakers and remove power from any high voltage electrical circuits installed in close proximity to or sharing an enclosure with the ECW-GF-DP prior to removing the enclosure cover plate. Read all instructions carefully before installation. Save this Installation and Operation Instruction for future reference.

WARNING:

KIT CONTENTS

Item Qty DescriptionA 1 Display panel with mounting screwsB 1 Single duplex outlet cover plate with

mounting screwsA

B

APPROVALSNonhazardous Locations

ECW-GF-DPRemote Display Pane Installation and Operation Instructions

nVent Thermal

nVent.com

Page 2: WARNING...to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be

2 | nVent.com

Ambient thermister

Conduit

Heating cable

ECW-GF

Power

Wall

ECW-GF-DP

nVent

nVent.com

le

328 ft (100 m) max.

1

+12V

@10

0ma

2

RX+

3

RX–

4

Gnd

5

TX+

6

TX–

7

Gnd

81J6J1

2345678

RedBlackWhiteGreenOrangeBlueBrownYellow

RedBlackWhiteGreen

OrangeBlue

BrownYellow

NC

+12V @100ma

123

T1T2SH

J5

Remote Display

TX+TX–GndRX+RX–GndNC

ECW-GF

Terminate cable shield at ECW-GF controller end only

Shield

1

2

The ECW-GF-DP remote display panel is only compatible with the ECW-GF controller.

• Install the ECW-GF-DP in an indoor dry location in a standard duplex junction box, up to 328 ft (100 m) from the ECW-GF.

• Route the communication cable through the 1/2-in entry.

• Communication cable type: 8 conductor 22 AWG shielded (Alpha 1298C or equivalent)

• Connect the cable to the controller and display in the following order:

SYSTEM ILLUSTRATION

Page 3: WARNING...to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be

nVent.com | 3

.25 in

1 Red2 Black3 White4 Green5 Orange6 Blue7 Brown8 Yellow

7 8

Remote Display Panel

1 R

ed

J5

J6

ShieldT2T1

2 B

lack

3 W

hite

4 G

reen

5 O

rang

e6

Blu

e7

Bro

wn

8 Y

ello

w

ECW-GF

Power

Ground-Fault Reset

Ground-Fault Test

ECW-GF-DP

Blinking = Communication error

Blinking = Ground-fault trip

or circuitry failure

Blinking = Ground-fault test pass

Blinking alternately red and amber

= Other alarm; check ECW-GF

3 4

5 6

• Prepare communication cable by stripping 1/4 in of insulation from each wire.

• Install wires according to Steps 4 and 5.

• Connect the communication cable to the ECW-GF-DP.

• Install plastic cover over ECW-GF-DP Remote Display Panel.

• Connect the communication cable to the ECW-GF controller.

• Terminate cable shield in the SH position on the J5 (Thermistor) terminal block.

• Stow wires and install ECW-GF-DP in duplex junction box.

• Secure with screws supplied.

• Multiple heating cable circuits may be monitored by mounting the ECW-GF-DP in multiplex boxes.

Page 4: WARNING...to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be

nVent.com

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

Raychem-IM-H58410-ECWGFDP-EN-1805 PN P000001089

North America Tel +1.800.545.6258Fax: [email protected]

Europe, Middle East, AfricaTel +32.16.213.511Fax [email protected]

Asia PacificTel +86.21.2412.1688Fax [email protected]

Latin AmericaTel +1.713.868.4800Fax [email protected]

Green LED

Red LED

Amber LED

Reset

Test

Normal Operation The Green LED shows that the display is connected to the ECW-GF controller and the controller is powered.

Communication ErrorIf the Green LED is blinking verify that the wiring to the display and controller are correct.

Ground-Fault ErrorIf the Red LED is blinking, the system has a ground-fault error. Check the ECW-GF controller for the error code on the display. Press the Reset button once the ground-fault error has been corrected.Ground-Fault Test To test the ground-fault circuitry, press and hold the Test button, if the circuit passes, the Amber LED will blink rapidly.

System AlarmIf the Red and Amber LEDs are blinking alternately, the heating cable system is in alarm. (Temperature sensor failure or high/low temperature alarm.) Check the ECW-GF controller for the displayed error.

OPERATING INSTRUCTIONS