41 - 81 HYDRONIC
®
VULCAN AIR TO WATER HEAT PUMP FOR OUTDOOR INSTALLATION
WBAN 41 - 81 (R-407C)
Size Heating
[kW]
41 15,3
61 19,8
81 26,7
CERTIFIED QUALITY SYSTEM UNI EN ISO 9001:2008
Operation only in heating Operation up to -18°C Reduced energy consumption Water production from 60°C to -10°C external air
According to the EN 14511-1:2008
RE
PL
AC
E:
BT
05
I01
6G
B-0
5
BT
05I0
16
GB
-07
The heating of the future respects the environment. The VULCAN heat pump series represent an important stage in the development of this type of unit. They feature the most up-to-date advances in technology, standing out for: EFFICIENCY thanks to its special construction, the WBAN series ensures high energy efficiency also in extreme working conditions; SELF-ADAPTING the evolved electronics implemented adapt the operating parameters of the chiller to the load conditions of the system it is installed in, optimising consumption, noise and the working life of the components; EASE OF INSTALLATION each unit is supplied as standard with a complete hydronic assembly and is completely tested in the factory; installation is consequently quick and easy.
*Due to its high efficiency, "Vulcan'" may be eligible for heat pump subsidies in Your Country. Please contact Your tax office or utility.
HYDRONIC 41 - 81
PERFECT FOR RESIDENTIAL
Eurovent energy efficiency classificaton class A in heating mode PERFECT FOR HEATING AND UNDERFLOOR HEATING
Thanks to its characteristics the unit can be used both in traditional systems with TERMINAL UNITS and in systems with EMBEDDED UNDERFLOOR PIPING with higher efficiency than traditional units.
TOP NOISELESSNESS
FOR A SUPERIOR COMFORT
WATER FILTER (external installation) SUPPLIED AS STANDARD
Steel mesh mechanical filter positioned at the exchanger inlet. Suitable for filtering water and trapping the impurities present in the water circuit.
STANDARD-SUPPLIED USER KEYPAD
Electric - refrigerating - water alarm signals
Check comfort-economic-test control
SUMMER-WINTER-OFF signals
SUMMER-WINTER-OFF control
A special measure in the refrige-rating circuit prevents ice from forming in the base of the air exchanger.
The remote keyboard allows unit start and stop, Summer/Winter setting, 2 selections of ambient temperature, one of "COMFORT" temperature where the set point is visualized only on board, an other of "ECO" temperature that decreases in winter mode and increases in summer mode the set point and the hidric /cooling/electric circuit alarm signal. The connection is done with a shielded cable 3 x 0.34mm2 max 100m which is connected with the unit. Thanks to its pleasant aspect it can be installed in ambient.
Noise is one of the most critical factors of this type of unit. The application of special regulation logic enables to adapt the fan operating speed to the system load and to the external air temperature. In this way you can optimize the energy efficiency and guarantee the lowest possible noise level, especially during evening and night hours, when the air temperature is lower and sensitivity to noise is greater.
BT
05
I01
6G
B-0
7
2
EUROVENT ENERGY EFFICIENCY CLASSES WATER: 30/35°C AIR 7°C D.B. / 6°C W.B.
41 - 81 HYDRONIC
CONFIGURATION CODE ( 1 ) ( 2 ) ( 3 ) ( 4 ) ( 5 ) ( 6 )
WBAN 41 400TN CCS - HYGU - -
4 1 4 0 0 T N C C S (Standard) - (Standard) HY G U (Standard) - (Standard) - (Standard)
6 1 2 3 0 M C C C A EH2 4 6 - 3 W V SF ST R 4 N
8 1 C C C A 1
C C C C
(1) VOLTAGE Supply voltage 400/3/50+N(400TN) 400TN = 400/3/50+N (sizes 61-81) Supply voltage 230/1/50(230M) only size 41
(2) CONDENSING COIL Standard condenser coil(CCS) standard Copper / aluminium condenser coil with acrylic lining(CCCA) Copper / aluminium condenser coil with Fin Guard treatment (Silver)(CCCA1) Copper /copper condenser coil(CCCC)
(3) AUXILIARY ELECTRIC HEATING ELEMENTS Integration heating elements: not required(-) standard modular integration electric heater 2-4 and 6kW(EH246)
(4) HYDRONIC GROUP UTILITY SIDE hydronic group utility side(HYGU) standard Hydronic group utility side: not required(-)
(5) 3-WAY VALVE Three-way valve: not required(-) standard three-way valve(3WV) for sanitary hot water
(6) SOFT STARTER Disposal for inrush current reduction: not required(-) standard disposal for inrush current reduction, for unit 400/3/50+N(SFSTR4N) disposal for inrush current reduction, for unit 400/3/50+N In sizes 41 230/1/50, the soft starter is included standard.
STANDARD UNIT SPECIFICATIONS
COMPRESSOR Hermetic orbiting scroll compressor complete with motor over-temperature and over-current devices and protection against excessive gas discharge temperature. Fitted on rubber antivibration mounts and complete with oil charge. A oil heater is automatically switched on at the compressor shut-down to prevent oil dilution by the refrigerant. STRUCTURE Structure made from "aluzink" plate, providing excellent mechanical charac-teristics and extensive corrosion strength PANELLING External panels in prepainted aluminium especially indicated in outdoor installation due to its superior resistance to corrosion avoiding periodic painting. Side panels are easily removable and allow complete access to unit components. Internal sound proof lining reduces sound pressure lev-els. INTERNAL EXCHANGER Direct expansion heat exchanger, braze-welded AISI 316 stainless steel plates with large exchange surface and complete with external heat and anti-condensate insulation. The exchanger comes complete with: - antifreeze heater to protect the water side exchanger, preventing the formation of frost if the water temperature falls below a set value. EXTERNAL EXCHANGER Heat exchange coil with aluminium fins and copper tubes in staggered rows. The coils are complete with integral subcooling circuit which assures the correct refrigerant feeding of the expansion valve. Available in different options as per optional list. The unit is fitted as standard with coil protection grills. FAN Propeller fans with aluminium pressure die-cast blades, directly driven by single-phase external rotor electric motor complying with VDE 0530/12.84, complete with thermal protection, IP 54 class according to DIN 40 050 norm. The impellers are housed in aerodynamically shaped nozzles to increase the efficiency and minimize the sound level, and protected by fan guards. REFRIGERANT CIRCUIT The circuit is complete with: - filter dryer - expansion device - high pressure switch - low pressure switch - liquid receiver - 4-way reverse cycle valve - Ice Protection System: system to prevent ice on the bottom of air coil TRAY Thermoformed ABS condensate collection tray fitted with drain pipe. ELECTRICAL PANEL The Power Section includes: - compressor and fan fuses only on unit 230/1/50
- compressor circuit breaker only on unit 400/3/50 - compressor control contactor - main door lock isolator switch - In sizes 41 230/1/50, the soft starter is included standard. The control section includes: - microprocessor control - variable fan speed control for operation at low ambient temperatures - automatic defrost control - set point compensation with outside temperature probe - set point compensation with 4-20 mA signal - high refrigerant gas pressure pre-alarm function that in many cases pre-vents the unit from being shut-down - compressor overload protection and timer - relay for remote cumulative fault signal - Management of electrical heating elements - double temperature management - Domestic water valve control - Electronic for Elfo Control system (optional) REMOTE KEYPAD FOR USER remotable control keypad, including: - SLEEP button for optimised night-time operation - ON/OFF and alarm reset buttons - signal led electric circuit alarm - signal led refrigerant circuit alarm - hydraulic circuit alarm signal led The remote keypad connection for user to the unit is set using a 3 x 0.34 mm2 screened cable. Maximum distance 100m. HYDRAULIC CIRCUIT - stainless steel mesh mechanical filter. - Centrifugal pump - diaphragm expansion vessel - water side safety valve - Water fill assembly with pressure gauge - drain valve - differential pressure switch, water side ACCESSORIES SYSTEM ACCESSORIES - 100 litres hydraulic breaker - hose kit for connection to chiller/heat pump. With connections of 1" - hose kit for connection to chiller/heat pump. With connections of 1 1/4" - Radiant panels management kit with 1" connections - Kit for management of radiant panels with connections of 1 1/4" - 500 litres domestic hot water kit - Boiler control kit - Electronic wall-mounting room thermostat ACCESSORIES SEPARATELY PROVIDED: - Rubber antivibration mounts - Domestic hot water kit control - serial communication module to supervisor (MODBUS) - phase monitor - Local control portable keypad with cable 1,5 metres
BT
05
I01
6G
B-0
7
3
HYDRONIC 41 - 81
GENERAL TECHNICAL SPECIFICATIONS
Size 41 61 81
HEATING
Heat output (39/45°C - 7 °C D.B. / 6°C W.B.) 1 kW 15,3 19,8 26,7
Compressor power input (39/45°C - 7 °C D.B. / 6°C W.B.) 1 kW 4,07 5,32 7,23
Total power input 2 kW 4,39 5,64 7,87
COP (39/45°C - 7 °C D.B. / 6°C W.B.) 1 3,49 3,51 3,39
COP (EN 14511:2004; 30/35°C - 7 °C D.B. / 6°C W.B.) 3 3,9 4,08 3,9
COP (EN 14511:2004; 30/35°C - 7 °C D.B. / 6°C W.B.) high efficiency 4 4,1 4,14 4,1
COMPRESSOR
Type of compressors SCROLL SCROLL SCROLL
No. of Compressors Nr 1 1 1
Std Capacity control steps Nr 1 1 1
Oil charge (C1) l 1,4 1,7 4
Refrigerant charge (C1) kg 4 4,2 5,5
Refrigerant circuits Nr 1 1 1
INTERNAL EXCHANGER
Type of internal exchanger 4 PHE PHE PHE
No. of internal exchangers Nr 1 1 1
Water flow rate (Internal Exchanger) 1 l/s 0,63 0,79 1,06
Useful pump discharge head 1 kPa 43 60 100
Water content l 2 2,2 2,7
EXTERNAL SECTION FANS
Type of fans 5 AX AX AX
Number of fans Nr 2 2 4
Standard air flow l/s 1780 1780 2500
Installed unit power kW 0,16 0,16 0,16
CONNECTIONS
Water fittings 1"GAS F 1"GAS F 1"GAS F
HYDRAULIC CIRCUIT
Max water side pressure kPa 550 550 550
Safety valve calibration kPa 600 600 600
EXPANSION VESSEL
Expansion vessel capacity l 5 5 5
Maximum water side pressure kPa 600 600 600
Nitrogen buffer pressure kPa 150 150 150
No. of expansion vessels Nr 1 1 1
POWER SUPPLY
Standard power supply V 230/1/50 400/3/50+N 400/3/50+N
NOISE LEVELS
Sound pressure level (1 m) dB(A) 58 60 64
DIMENSIONS
Length mm 1120 1120 1526
Depth mm 524 524 557
Height mm 1176 1176 1224
Packing volume m3 0,9 0,9 1,4
STANDARD UNIT WEIGHTS
Shipping weight kg 153 160 270
Operating weight kg 150 157 266
Shown datas are referred to units working in perfect installation and exchangers' cleaning conditions. (1) data referred to the following conditions : outlet water internal exchanger 45°C outdoor air temperature 7°C DB - 6°C WB DT=difference between inlet/outlet water temperature=6°C
(2) Total input is obtained from compressor input + fan input (3) The indicated COP values were calculated in compliance with the provisions of standard EN 14511-1:2008. (4) PHE = plates (5) AX = axial-flow fan
BT
05
I01
6G
B-0
7
4
41 - 81 HYDRONIC
15
20
25
30
35
40
45
50
55
60
65
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
Ta (°C)
Tw
(°C
)
( 1 )
TW [°C] = HEAT EXCHANGER OUTLET WATER TEMPERATURE TA = OUTSIDE AIR TEMPERATURE (°C) (1) THE SHADED AREA SHOWS OPERATION WITH AIR FLOW RATE IN MODULATION
OPERATING LIMITS (HEATING) EXTERNAL EXCHANGER
Max air temperature inlet (WB) 1 °C 40 40 40
Min air inlet temperature (W.B.) 2 °C -18 -17 -17
INTERNAL EXCHANGER
Min. water outlet temperature 3 °C 20 20 20
Max water outlet temperature 4 °C 60 60 60
Water thermal head (min / max) °C 3 / 8 3 / 8 3 / 8
VOLTAGE: 230/1/50
ELECTRICAL DATA
Size 41
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Pump A 1,2
F.L.A. - Total A 30.5
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Pump kW 0,3
F.L.I. - Total kW 6.2
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value A 45
power supply 230/1/50 Hz +/-6% voltage unbalance: max 2 % The pump is included in the total values calculation The units are compliant with the provisions of European standards CEI EN 60204 and CEI EN 60335. In case of abnormal conditions, the device does not limit the current, providing the torque necessary at the compressor starting..
VOLTAGE: 400/3/50+N
ELECTRICAL DATA
Size 41 61 81
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Pump A 1,2 2,1 3,2
F.L.A. - Total A 10,5 15,8 22,9
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Pump kW 0,3 0,4 0,7
F.L.I. - Total kW 5,3 7,5 11,1
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value A 66,5 104,4 104,8
power supply 400/3/50 (+ NEUTRAL) +/- 6% Maximum Phase Unbalance: 2% The pump is included in the total values calculation The units are compliant with the provisions of European standards CEI EN 60204 and CEI EN 60335. for non standard voltage please contact Clivet technical office
BT
05
I01
6G
B-0
7
5
ATTENTION: IN CASE OF PREDOMINANT WINDS, WINDBREAK BARRIERS ARE NECESSARY. Shown datas are referred to units working in perfect installation and exchangers' cleaning conditions.
(1) water to internal exchanger 44/50°C summer operation, with fan speed control device (2) water to internal exchanger 49/55°C (3) outdoor air temperature 7°C DB - 6°C WB (4) Outdoor air temperature: -10°C D.B./ -10.5 °C W.B.
HYDRONIC 41 - 81
10
20
30
40
50
60
70
80
90
100
110
120
130
140
0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3
DP
(k
Pa
)
Q (l/s)
41
61
81
Q (l/s)
Dp
(kP
a)
PUMP PERFORMANCE
CURVE OF DISCHARGE HEAD WITH HYDRONIC ASSEMBLY DP[KPA]=USEFUL DISCHARGE HEAD Q[L/S]= WATER-FLOW RATE THE HEADS ARE INTENDED AS AVAILABLE AT THE UNIT CONNEC-TIONS
FOULING CORRECTION FACTOR
INTERNAL EXCHANGER
m² °C/W F1 FK1
0.44 x 10^(-4) 1,00 1,00
0.88 x 10^(-4) 0,97 0,99
1.76 x 10^(-4) 0,94 0,98
EXCHANGER PRESSURE DROPS
CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS
5% 10% 15% 20% 25% 30% 35% 40% % ethylene glycol by weight
Freezing temperature °C -2,0 -3,9 -6,5 -8,9 -11,8 -15,6 -19,0 -23,4
Safety temperature °C 3,0 1,0 -1,0 -4,0 -6,0 -10,0 -14,0 -19,0
Cooling Capacity Factor Nr 0,995 0,990 0,985 0,981 0,977 0,974 0,971 0,968
Compressor input Factor Nr 0,997 0,993 0,990 0,988 0,986 0,984 0,982 0,981
Internal exchanger Glycol solution flow Factor Nr 1,003 1,010 1,020 1,033 1,050 1,072 1,095 1,124
Pressure drop Factor Nr 1,029 1,060 1,090 1,118 1,149 1,182 1,211 1,243
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
BT
05
I01
6G
B-0
7
6
F1 = Heat power correction factor FK1 = Compressor power input correction factor
10
20
30
40
50
60
70
80
90
0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3
DP
(k
Pa
)
Q (l/s)
41
61
81
Q (l/s)
Dp
(kP
a)
DP = PRESSURE DROP Q = WATER FLOW
SIZE 41 61 81
Minimal flow [l/s] 0,48 0,64 0,83
Maximum flow [l/s] 0,73 0,92 1,21
41 - 81 HYDRONIC
HEATING PERFORMANCE
Size
41
61
81
Ta (°C)
DB/WB
-15 / -15,4
-10 / -10,5
-7 / -8
-5 / -5,4
2 / 1,1
7 / 6
10 / 8,2
-15 / -15,4
-10 / -10,5
-7 / -8
-5 / -5,4
2 / 1,1
7 / 6
10 / 8,2
-15 / -15,4
-10 / -10,5
-7 / -8
-5 / -5,4
2 / 1,1
7 / 6
10 / 8,2
INTERNAL EXCHANGER WATER OUTLET TEMPERATURE (°C)
35 40 45 50 55 60
kWt kWe kWt kWe kWt kWe kWt kWe kWt kWe kWt kWe
8,93 2,88 8,91 3,05 8,95 3,31 9,08 3,68 9,28 4,16
10,2 3,00 10,2 3,19 10,2 3,48 10,3 3,87 10,5 4,37 10,7 4,96
10,9 3,06 10,9 3,26 10,9 3,57 11,0 3,97 11,1 4,47 11,3 5,07
11,6 3,12 11,6 3,34 11,7 3,66 11,8 4,07 11,9 4,58
13,6 3,29 13,6 3,54 13,7 3,89 13,8 4,33 13,8 4,86
15,3 3,42 15,3 3,70 15,3 4,07 15,4 4,53 15,5 5,08
16,0 3,49 16,1 3,78 16,1 4,16 16,2 4,62
11,6 3,66 11,9 3,92 12,2 4,27 12,4 4,72 12,7 5,26
13,2 3,78 13,4 4,10 13,6 4,48 13,8 4,94 14,0 5,46 14,3 6,05
14,1 3,86 14,2 4,20 14,4 4,60 14,6 5,06 14,8 5,57 15,1 6,15
15,1 3,94 15,1 4,31 15,3 4,72 15,4 5,19 15,6 5,70 15,9 6,26
17,8 4,20 17,8 4,61 17,8 5,06 17,8 5,54 17,9 6,05 18,0 6,60
20,2 4,44 20,1 4,87 20,0 5,33 19,9 5,82 19,8 6,35
21,4 4,56 21,2 4,99 21,1 5,46 20,9 5,96
15,1 5,69 15,0 5,14 15,0 5,02 15,2 5,32 15,6 6,06
16,9 4,90 16,9 5,21 17,1 5,68 17,4 6,31 17,8 7,11 18,4 8,06
18,0 4,68 18,1 5,30 18,3 5,98 18,6 6,74 19,0 7,56 19,6 8,45
19,2 4,58 19,4 5,43 19,6 6,27 19,9 7,12 20,4 7,97 20,9 8,83
23,0 4,94 23,2 5,92 23,4 6,88 23,7 7,82 24,0 8,74
26,3 5,76 26,5 6,45 26,7 7,23 26,9 8,11 27,1 9,07
28,0 6,29 28,1 6,73 28,3 7,36 28,4 8,17
Ta = external exchanger air intake temperature kWt = Heating capacity (kW) kWe = Compressor power input in kW Performances in function of the inlet/outlet water temperature differential = 5°C Data listed in the tables are based on plate exchangers without fouling and clean coils. For different situation it is necessary to use adeguate correction factors.
INTEGRATED HEATING CAPACITIES
Air temperature external exchanger inlet °C (D.B. / W.B.) -5 / -5.4 OTHERS 5 / 3.9 0 / -0.6
Heating capacity multiplication coefficient 0,89 1 0,94 0.88
To obtain the integrated heating capacities (the real heating capacity considering the defrost cycles too), multiply the kWt value in the heating performance tables by the following coefficient.
BT
05
I01
6G
B-0
7
7
SOUND LEVELS
Siz
e
Sound Power Level (dB) Sound pressure
level
Sound power level
Octave band (Hz)
63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)
41 54 62 67 69 70 66 58 45 58 73
61 55 63 69 71 72 68 59 47 60 75
81 60 68 73 75 76 72 64 51 64 79
Measures according to ISO 3744 regulations, with respect to the EUROVENT 8/1 certification. The sound pressure is measured at 1 m from the external surface of the unit in open field conditions. data referred to the following conditions : unit at full load outlet water internal exchanger 45°C External air temperature : 7°C D.B./6.0°C W.B.
HYDRONIC 41 - 81
ACCESSORIES
BT
05
I01
6G
B-0
7
8
Each accessory is marked by a configuration code, e.g. CMMBX. If the last letter is X, it means that the accessory is provided sepa-rately. If the code does not contain the letter X, the accessory is installed at the factory.
The table summarizes the values of COP calculated in accordance with the law EN14511-1:2008
10
20
30
40
50
60
70
80
90
100
0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3
DP
(k
Pa
)
Q (l/s)
41 61
81
41 61 81
4,10 - -
4,14 4,14 4,10
WBAN (R-407C)
COP 400/3/50 EN14511 :2004
COP 230/1/50 EN14511 :2004
Q [L/S] = WATER FLOW RATE DP [KPA] = USEFUL STATIC PRESSURE
0,04
0,05
0,06
0,07
0,08
0,09
0,10
0,11
0,12
0,13
0,14
0,15
0,16
0,17
0,18
0,19
0,20
0,21
0,22
0,23
0,24
0,25
0,26
0,27
0,28
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9
Pcir
c [kW
]
Q [l/s]
81
61
41
PCIRC [KPA] = ELECTRIC POWER ABSORBED Q [L/S] = WATER FLOW RATE
* Due to its high efficiency, "Vulcan'" may be eligible for heat pump subsidies in Your Country. Please contact Your tax office or utility.
EN 14511-1.2008
EN 14511-1.2008
(HEOH) - HIGH EFFICIENCY ONLY IN HEATING
Option for energy optimization of the units, including the circulating pump use in direct current.
This option is available only with the full optional version.
AVAILABLE HEAD TO THE SYSTEM [KPA]
SYSTEM CIRCULATOR ABSORPTION CURVE
41 - 81 HYDRONIC
(CCCA) copper / aluminium condenser coils with acrylic lining
The copper/aluminium evaporator coils with acrylic lining can be used in the room where the ambient air contains a concentration of salt and other not very aggres-sive agents.
Configuration Detail
(CCCA1) copper / aluminium condenser coils with Fin Guard (Silver) treatment
The Fin Guard Silver, for finned exchanger, is a polyurethane vernish waterproof (for waterworks, see and discharge water). It is also resistant to oil products and other different solvents. It hasn't any effects on the air side pressure drops.
Configuration Detail
(CCCC) copper / copper condenser coils
The copper/copper condensing coil allows a better resistence to the natural agent like salt and sulphureous vapours.
Configuration Detail
(EH246) modular integration electric heater 2-4 and 6kW
HEATING ELEMENT WATER-SIDE PRESSURE DROP
On request the unit can be provided with integration heating elements. Different powers can be selected based on needs. The electrical heating elements are immersed in a small 1-litre tank equipped with a safety thermostat The heating elements are activated by means of an on/off button as a main or additional component based on a temperature threshold, based on parameters defined at first start up.
1.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
17.0
19.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2
Q (l/s)
DP
(k
Pa)
Q = WATER FLOW DP = PRESSURE DROP
THE PRESSURE DROPS SHOWN IN THE GRAPH ARE TO BE SUBTRACTED, WITH PARITY OF FLOW RATE, FROM THE USEFUL STATIC PRESSURE. IF THE RESULT IS LESS THAN THE PRESSURE DROPS OF THE SYSTEM, IT IS ADVISABLE TO INSTALL AN EXTERNAL PUMP THAT ENSURES THE NECESSARY STATIC PRESSURE.
Configuration Detail
BT
05
I01
6G
B-0
7
9
HYDRONIC 41 - 81
(3WV) three-way valve
Built-in 3-way valve for domestic hot water
The unit is provided with a 3-way on/off valve to divert the flow of water to a hot water storage tank. Activation of the 3-way valve takes place by means of closure of a dry contact on the electrical board of the unit. As soon as this function is enabled, the set point of the unit is placed at the value established by the appropriate parameter in the electronic control.
(1) UNIT ELECTRIC PANEL (2) EXPANSION VESSEL (3) WATER SIDE SAFETY VALVE (4) PUMP (5) THREE-WAY VALVE (6) TERMINAL UNITS (7) UNDERFLOOR HEATING (8) WATERWORKS WATER INLET (9) SANITARY WATER
Pressure drop three-way valve
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
0,5 0,7 0,9 1,1 1,3 1,5 1,7 1,9 2,1 2,3 2,5 2,7 2,9 3,1
Q (l/s)
Dp
(kP
a)
PRESSURE DROP THREE-WAY VALVE Q = WATER FLOW DP = PRESSURE DROP
THE PRESSURE DROPS SHOWN IN THE GRAPH ARE TO BE SUBTRACTED, WITH PARITY OF FLOW RATE, FROM THE USEFUL STATIC PRESSURE. IF THE RESULT IS LESS THAN THE PRESSURE DROPS OF THE SYSTEM, IT IS ADVISABLE TO INSTALL AN EXTERNAL PUMP THAT ENSURES THE NECESSARY STATIC PRESSURE.
Configuration Detail
(-) unit without hydronic assembly
The unit can be requested without circulating pump, expansion vessel, safety valve water side and filling assembly.
Configuration Detail
(PMX) phase monitor
The phase monitor allows to check the right presence of electric supply phases for 400/3/50 units.
separately supplied accessories
BT
05
I01
6G
B-0
7
10
41 - 81 HYDRONIC
(SFSTR4N) Disposal for inrush current reduction
Disposal for inrush current reduction, for unit 400/3/50+N
Starting up a motor directly can overload the electricity network, with start-up currents up to 8 times the nominal current. Thanks to the breakaway current reduction device, start-up takes place gradually, with the start-up current being limited during this period of time. The start-up current can therefore be reduced to 3.5 - 4 times the nominal current, meaning that the power systems and protection devices can be sized with lower parameters. In sizes 41 230/1/50, the soft starter is included standard.
Configuration Detail
(PBLC1X) Service handset for local control with 1.5-metre cable
The service keyboard is necessary for the unit programming and setting. These operations must be done by qualified personnel without compromising the
operation of the whole unit. The service keyboard is supplied with a connection cable of 1,5 m lenght .
separately supplied accessories
(CMMBX) Serial communication module to supervisor (MODBUS)
The serial communication module to supervisor (MODBUS) is connected with the principal module through a comb connection (see lay-out on electrical panel). In this way the remote assistance and supervision are available through standard MODBUS protocol. It is possible to connect to a single supervisor system up to 127 units. The connection to PC must be obtained through a converter RS485/232; the serial port RS232 admits as maximum a 10 m length. The serial communication module to supervisor (MODBUS) is necessary when the unit is connected to ELFOCONTROL.
separately supplied accessories
(AMRX) Rubber antivibration mounts
The rubber antivibration mounts reduce the vibrations of compressor during its operation and they are installed at the base toe.
separately supplied accessories
BT
05
I01
6G
B-0
7
11
HYDRONIC 41 - 81
SYSTEM ACCESSORIES
(KTFL1X) Hose kit for connection to chiller/heat pump. With connections of 1"
The kit is composed of: Two hoses, length 300 and diameter 1”, required for connection of the machine to the system. This kit can be used for heat pumps from 4 to 18kW
separately supplied accessories
(KTFL2X) Hose kit for connection to chiller/heat pump. With connections of 1 1/4"
The kit is composed of: Two hoses, length 300 and diameter 1 ¼”, required for connection of the machine to the system. This kit can be used for heat pumps from 19 to 30kW
separately supplied accessories
(KBQRE5X) 500 litres domestic hot water kit
The kit is composed of: Storage tank in Fe360b and internal vitrification treatment in accordance with DIN 4753.3, exter-nal insulation in stiff polyurethane and exchange coil xx m2, maximum operating pressure 6 bar Electrical heating element 4 kW for possible integration and anti-legionellosis cycle for boiler of 500 litres. Electronic module for the management of the production of domestic hot water: DHW temperature setting, setting of time period for production of domestic hot water with priority based on a minimum temperature, management of anti-legionellosis cycle, control for three-way valve, management of the electrical heating element. The electronic module dialogues with the heat pump through the serial communication cable. Three-way deviator valve 1 1/4” and non-return valve 1 1/4” to be installed in the system Serial connection cable twisted and shielded for networks RS485 AGW22/24 with a length of 15 metres. - Serial communication card CMMBX to be connected in the heat pump Dimensions of boiler of 500 litres: 760 x 1690mm If this accessory is requested, the unit cannot be provided with the three-way valve installed on board. This is because it is to be installed on the system, near the hot water heater.
separately supplied accessories
(KITERAX) Room thermostat
Wall-mounted weekly electronic timer thermostat with summer, winter night adjustment. Range of adjustment +2°C/+35°C. Dimensions 123X88X23.
separately supplied accessories
BT
05
I01
6G
B-0
7
12
41 - 81 HYDRONIC
(KVMSP1X)Radiant panels management kit with 1" connections (KVMSP2X)Kit for management of radiant panels with connections of 1 1/4"
(KVMSP1X)The kit is made up of: 1” Mixer valve with three-point modulating actuator. Power box and modulating valve connection Temperature probe to be installed on the outlet of the radiator panels (l=20metres) Thermostat of maximum temperature 55°C Control for circulation pump to the radiator panel This kit may be used with 4 - 18kW heat pumps (KVMSP2X)The kit is made up of: 1 1/4” Mixer valve with three-point modulating actuator. Power box and modulating valve connection Temperature probe to be installed on the outlet of the radiator panels (l=20metres) Thermostat of maximum temperature 55°C Control for circulation pump to the radiator panel This kit may be used with 19 - 30kW heat pumps
separately supplied accessories
(KVICX) Boiler control kit
The kit is composed of: -Pair of two way motorized valves for boiler cut-off -Pair of two way motorized valves for heat pump cut-off Valve control electrical junction box
separately supplied accessories
(KSAX) 100 litres hydraulic breaker
Storage tank Fe360b and anti-corrosion treatment with organic enamelling, external insulation with polyurethane and polyethylene mat, thickness 50 mm maximum of operation 6 bar. Diameter 500 Height 900 8 connections
separately supplied accessories
(CACSX) Domestic hot water kit control
The module makes it possible to control the temperature of a domestic hot water tank, not provided by Clivet. The adjustment module comes with 2 temperature probes, 1 safety thermostat, power circuit and heating element control with protections against short circuits (the heating element is not provided by Clivet) and the installation box. As opposed to the control of domestic hot water performed directly by the machine electronics, the kit makes it possible to set re-fill time periods and anti-legionella cycles, and to manage a re-circulation pump on the storage tank.
The storage tank must be suitably sized based on the combination with the selected heat pump.
separately supplied accessories
BT
05
I01
6G
B-0
7
13
HYDRONIC 41 - 81
PLUMBING DIAGRAM
FAN COIL / RADIATORS
HEAT PUMP
SANITARY WATER
PLUMBING DIAGRAM
Heat pump + radiators + radiant panels + domestic hot water
FAN COIL / RADIATORS
HEAT PUMP
RADIANT PANELS
SANITARY WATER
PLUMBING DIAGRAM
BOILER FAN COIL / RADIATORS
HEAT PUMP
RADIANT PANELS
SANITARY WATER
Heat pump + radiators + radiant panels + domestic hot water + boiler
Heat pump + radiators + domestic hot water
BT
05
I01
6G
B-0
7
14
41 - 81 HYDRONIC
DIMENSIONAL DRAWING
1
2
3
4
5
7
8
14
9
10
12
13
12
1120
476
1137
6
1
55
15
7
5
3
524
117
6
"G"
W3
M N
O
W1
W4
W2
(15)
500
(15)
15
0
6 10
10
7
98
2
35
7
P
100685
8011 11
Size 41 61 (1) COMPRESSOR (2) ELECTRICAL PANEL (3) INTERNAL EXCHANGER (4) EXTERNAL EXCHANGER (5) FAN (6) PUMP (7) EXPANSION VESSEL (8) WATER OUTLET 1" GAS (9) WATER INLET 1" GAS (10) ECONOMISER EXCHANGER (11) CONDENSATE DISCHARGE (12) AUXILIARY ELECTRIC HEATERS (OPTIONAL) (13) 3-WAY VALVE WATER LINE (OPTIONAL) (14) SANITARY WATER OUTLET 1"F GAS (OPTIONAL) (15) CLEARANCE ACCESS RECOMMENDED (G) BARYCENTRE
M mm 466 457
N mm 671 680
O mm 224 226
P mm 252 250
Length mm 1120 1120
Depth mm 524 524
Height mm 1176 1176
W1 kg 42 45
W2 kg 29 30
W3 kg 47 50
W4 kg 33 33
Operating weight kg 150 157
Shipping weight kg 153 160
BT
05
I01
6G
B-0
7
15
HYDRONIC 41 - 81
DIMENSIONAL DRAWING
"G"
W3
W1
W4
W2
1526
508
1
2
3
4
5
6
7
914
8
10
1212
13
117
124
60
2
1
6 10
3
M NO
P
5 5
(15)
500
(15
)
15
0
12
245
1543
5572
42
177
11 11 80
1061065
Size 81 (1) COMPRESSOR (2) ELECTRICAL PANEL (3) INTERNAL EXCHANGER (4) EXTERNAL EXCHANGER (5) FAN (6) PUMP (7) EXPANSION VESSEL (8) WATER OUTLET 1" GAS (9) WATER INLET 1" GAS (10) ECONOMISER EXCHANGER (11) CONDENSATE DISCHARGE (12) AUXILIARY ELECTRIC HEATERS (OPTIONAL) (13) 3-WAY VALVE WATER LINE (OPTIONAL) (14) SANITARY WATER OUTLET 1"F GAS (OPTIONAL) (15) CLEARANCE ACCESS RECOMMENDED (G) BARYCENTRE
M mm 526
N mm 1017
O mm 266
P mm 242
Length mm 1526
Depth mm 557
Height mm 1224
W1 kg 92
W2 kg 48
W3 kg 83
W4 kg 43
Operating weight kg 266
Shipping weight kg 270
16
BT
05
I01
6G
B-0
7
41 - 81 HYDRONIC
BT
05
I01
6G
B-0
7
17
HYDRONIC 41 - 81
18
BT
05
I01
6G
B-0
7
41 - 81 HYDRONIC
BT
05
I01
6G
B-0
7
19
HYDRONIC 41 - 81
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited. © Copyright - CLIVET S.p.A. - Feltre (BL) - Italy
CLIVET SPA
Feltre (BL) ITALY
Tel. + 39 0439 3131
Fax + 39 0439 313300
CLIVET UK LTD
Fareham (Hampshire) U.K.
Tel. + 44 (0) 1489 572238
Fax + 44 (0) 1489 573033
CLIVET SAS
Verrierès le Buisson - FRANCE
Tel. + 33 (0)1 69 20 25 75
Fax + 33 (0)1 69 20 60 76
CLIVET ESPAÑA S.A.
Madrid - SPAIN
Tel. + 34 91 6658280
Fax + 34 91 6657806
CLIVET GmbH
Norderstedt - GERMANY
Tel. +49 (0) 40 32 59 57-0
Fax +49 (0) 40 32 59 57-194
CLIVET NEDERLAND B.V.
Amersfoort - Netherlands
Tel. + 31 (0) 33 7503420
Fax + 31 (0) 33 7503424
CLIVET RUSSIA
Moscow - RUSSIA
Tel. +74956462009
Fax +74956462009
CLIVET MIDEAST FZC
Dubai - UAE
Tel. +97 14 3518501
Fax +97 14 3518502
CLIVET TF AIR SYSTEMS (P) LTD.
Malur - INDIA
Tel. +91 8151 232683/5
Fax +91-8151-232684