www.powmatic.co.uk +44 (0) 1460 53535 [email protected] Doc Ref: M02 Issue 5.4 May 2018 Industrial & Commercial Heating Systems VPC Gas Cabinet Heater Range User, Installation & Servicing Manual

VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

Embed Size (px)

Citation preview

Page 1: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

w w w . p o w m a t i c . c o . u k+ 4 4 ( 0 ) 1 4 6 0 5 3 5 3 5

i n f o @ p o w r m a t i c . c o . u k

Doc Ref: M02 Issue 5.4 May 2018

Industrial & Commercial Heating Systems

VPC Gas Cabinet Heater Range

User, Installation& Servicing Manual

Page 2: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 2 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Installer Date:________________Signed: _____________________________________Installer

Commissioned Date:________________Signed:_______________________Commissioning Engineer

Important: This certificate must be kept with the appliance

Failure to provide a copy of the commissioning sheet invalidates the heater warranty

----------------------------------------------------Powrmatic Ltd, Hort Bridge, Ilminster, Somerset, TA19 9PS

Tel: 01460 53535 Fax: 01460 52341 Web: www.powrmatic.co.uk e-mail: [email protected]

Certificate of GuaranteeDear CustomerThis is to certify that this heater is guaranteed for two years parts and one year labour from the date of original commissioning. The heater must be commissioned within 4 weeks of installation.

To make a claimIn the first instance you must contact your appliance supplier, or installer and provide:-1. The appliance type and serial number.2. The original commissioning documentation. As much detail as possible on the fault.3. Your supplier, or installer, will then contact Powrmatic to make a guarantee claim on your behalf.

Conditions of Guarantee1. The heater must have been installed by a competent recognised installer, and in accordance with the manufacturer’s instructions, building regulations and local regulations.2. The heater has been professionally commissioned, within 4 weeks of installation, and a copy of the commissioning sheet returned to Powrmatic.3. The heater has been maintained on a yearly basis by a competent servicing company.4. The heater has been used in accordance with the manufacturer’s instructions. 5. The correct specification fuel has been used.6. No unauthorised repairs of modifications have been made. Powrmatic ‘General Conditions of Sales’ have been observed.7. Except for the obligation of Powrmatic Ltd to perform warranty repairs during the guarantee period Powrmatic will not be liable in respect of any claim for direct or indirect consequential losses, including loss of profits or increased cost arising from loss of use of the heater, or any event arising there from.

ExclusionsConsumables such as gaskets, ignition electrodes, flame rectification electrodes, drive belts, fusible links, control batteries are all excluded from guarantee.

Page 3: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 3 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Dear Customer - thank you for choosing Powrmatic.

We appreciate you buying one of our high quality products and know that you have made the best choice. By choosing Powrmatic, you are investing in UK manufacturing & its workforce. We pride ourselves by manufacturing products that provide clean, comfortable and safe working environments worldwide together with the personal & professional service and back-up you deserve. If you have any questions or concerns regarding this product, please contact our Technical Support Team by calling 01460 53535.

Title Section Contents Page

User Instructions 4

Pre Installation 1.1 Introduction 5 Duties 6 Dimensions 7 Accessories 8 1.2 Technical data 9 1.3 General Requirements 11 1.4 Ventilation Air Requirements 13 Installation 2.1 Fitting the unit 14 2.2 Flue/Combustion Air Duct System 16 2.3 General Identification of Electrical Items 18 2.4 Electrical Cable Installation 19 2.5 Wiring Diagrams 20 2.6 Commissioning and Testing 26 2.7 Servicing 30

Additional Documents 3.1 Fault Finding Flow Chart 33 3.2 Short List of Parts 34 3.3 Gas Conversion 36

Appendices Information required for ecodesign (ErP) Directive 2009/125 38

Users, Installation and Servicing Instructions

CONTENTS

Page 4: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 4 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

D) Description of Operation

Important: The heater must NOT be controlled by switching ON and OFF the main electrical supply to it.1) Standard Units

The ignition sequence commences each time the external controls e.g. Time clock, room thermostat etc. call for heat. The internal exhaust fan will run and, when sufficient combustion airflow is proved by the air pressure switch, the ignition spark will be generated, the main gas valve opens and the burners light. The heater fan will automatically start approximately 2 minutes after the burners light. When the external controls are satisfied the burners will be turned off and approximately 2 - 3 minutes later the heater fan will be automatically stopped. If the burners fail to light the control box will make another four attempts at ignition.

2) High / Lo & Modulating Units

When the burners are alight, the heat output will be controlled either to high fire or low fire or, in the case of modulating units, to any point between high and low fire; depending on the requirements of the space being heated and the controls system.

3) Summer / Winter Modes

Certain types of external controls will provide for two modes of operation i.e.Summer: The heater fan alone will run at the dictate of the external controls to provide air movement.Winter: The heater will operate normally.

4) Fan and Limit Control

The fan and limit controls are mounted towards the top of the air heater inner bulkhead and are accessed via the front door.i) Main Air Fan MAN / AutoWhen the white button is pushed in the fan will run continuously i.e. not controlled by any external controls e.g. Time clock. When the white button is pulled out the fan will start and stop automatically in conjunction with the burner. ii) Limit ThermostatThis operates if high temperatures within the heater are detected, the burners are turned off and a red indicator light inside the heater is illuminated. The fault condition must be identified and rectified and the thermostat manually reset.When the unit has cooled push the reset switch on the front of the heater to reset the limit thermostat interlock relay, the red indicator light will go out and the unit is operational again.

If the heater has not been left operational proceed as follows.

A) Checks before lighting the Air Heater

The following preliminary checks should be made before lighting the heater(s)

a) Ensure that the ELECTRICAL supply to the heater is switched OFF.b) Check that all warm air delivery outlets are open.c) Check that the thermostat is set at MAX.d) Check that the clock control is set to an ON period.e) Check that any other controls are calling for heat.

B) Lighting the Air Heater

1. Switch on the electrical supply at the isolator

2. If the Limit indicator light comes on press the limit interlock reset switch inside the heater.

3. The startup sequence will commence. After a short delay the burners will light.

4. If the burners fail to light the control box will automatically restart the ignition sequence. If after 5 attempts at ignition the burners have still failed to light the control box will go to lockout and the amber lockout light inside the heater (or on the low level remote reset, MC200 or Powrtrol RR if fitted) will be illuminated. To restart the ignition sequence depress the reset button on the low level reset for about 1-2 seconds.

WARNING: If it is not possible to light the heater after several attempts, contact the installer or local service company.

C) To Shut Down the Air Heater

1) For Short Periods:

Turn the room thermostat to the OFF, or set to it’s lowest setting.

2) For Long Periods:

Complete step 1 above. Wait for 5 minutes and then turn OFF the electrical supply at the isolator.

User Instructions

Page 5: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 5 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Note: The limit thermostat(s) can only be reset once the unit has cooled down.Unless the cause of the fault condition is readily obvious, for example a power cut whilst

the heater was operating, a service engineer should be contacted.

E) Maintenance

To maintain efficient, reliable and safe operation of the heater it must serviced by a qualified person at least annually and preferably at the end of the heating season.

IMPORTANTFree access must be maintained to and around the heater for servicing purposes and the air supply to the heater must not be restricted

in any way. Combustible materials must not be stored adjacent to the heater.

If at any time a gas leak is suspected, turn OFF the gas supply at the meter and contact the local gas undertaking immediately.

All Powrmatic heaters use gas and electricity to power them, they may also contain moving parts such as pulleys and belts. It would be hazardous to tamper with or attempt to

service unless you are a competent person in the field of Gas and Electrical work.

If you have any safety questions reference the servicing and installation of any of our heaters please do not hesitate to contact our head office for expert advice. Your safety is paramount to us.

Gas Safety (Installation & Use) (Amendment) Regulations

It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the current issue of the

above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with. * An approved class of person listed on the gas safe register.

The VPC range are highly efficient gas fired, fanned circulation floor standing air heaters that cover heat outputs of 30kW to 130kW. The units have a single closed flue system that can be either vertical or horizontal and feature a single burner assembly which as standard is ON/OFF but can also be supplied in High/Low or Modulating formats. High/Low or Modulating formats give a turn down facility of approximately 2:1. The heaters are certified for use on Natural Gas, Group H - G20, and Propane - G31 only.Appliance Categories are Cat II2H3P (GB, IE).

The heaters intended primarily for heating commercial or industrial premises. They must not be used where the atmosphere inside the premises could be contaminated e.g. Dust, oil mist etc. or in areas classified as hazardous as defined in BS 5345: Part 2. They are not suitable for siting externally.

VPC heaters feature a closed combustion circuit and have an internal exhaust fan, mounted downstream of the heat exchanger, to evacuate the products of combustion and draw in air for combustion. The air heater must be connected to a flue system that is approved by Powrmatic Ltd.

They may be used where the atmosphere inside the premises could be contaminated e.g. Dust, oil mist etc. but the heaters are not airtight and therefore may not be used in areas classified as hazardous as defined in BS 5345: Part 2 or areas subjected to significant negative pressures due to extract systems.

VPC heaters have a centrifugal fan assembly fitted at the base of the heater to circulate the air being heated past the formed tube heat exchanger.

Heaters are fitted as standard with inshot burners, a fully automatic control for ignition, flame sensing, gas supply control and safety functions, an internal exhaust fan, main air fan and fan/limit thermostat.

Options include High/Low or Modulating burner controls, inlet duct connection, outlet duct connection, 90° outlet bend and a full range of modular duct components.

IMPORTANTService and Maintenance Engineers shall ensure that replacement items are fitted, adjusted and set in accordance with the

data and detail set out in these instructions. If in doubt consult Powrmatic Technical Department.

Gas Safety (Installation & Use) Regulations 1998It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the current issue of the

above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.* An approved class of person listed on the gas safe register.

1.1 Introduction

Page 6: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 6 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Model 30 52 80 110 130

Output kW 30 52 80 110 130

Input (nett CV) kW 32.6 56.5 87.0 119.5 141.3

Volume m3/s 0.87 1.59 2.34 2.96 3.63

Airflow

Heads m 3 3 4 4 4

Throw m 12.0 22.0 21.0 26.0 27.0

Fan Static

Standard Pa 150 200 225 150 200

Uprated (Refer to Powrmatic)

Electrics

SupplyStandard V/ph/Hz 230/1/50

Optional V/ph/Hz n/a 400/3/50

StdFan

Motor kW 0.55 1.1 1.4 1 x 1.5 1 x 2.2

Start amp 6.5 8.3 19 28 40

Run amp 4.2 4.2 9.5 9.3 10.7

Fuel

Connection BSP/Rc ¾”

Minimum Inlet Pressure

Nat Gas mbar 17.5

LPG mbar 37.0

ConsumptionNat Gas m3/h 3.45 5.98 9.19 12.64 14.94

LPG m3/h 1.33 2.31 3.55 4.89 5.78

OverallDims

UF UprightFreeblow

Height mm 2272 2713 2804 2715 2998

Width mm 750 750 750 750 750

Depth mm 1108 1108 1412 1767 1767

InstallClearance

UF UprightFreeblow

Front mm 1000

Blank mm 150

Louvred mm 500

Read mm 500

Flue

Diameter mm Ø 100 130

Max Length

Flue Only m 12

Room Sealed m 6

Combustion Air Spigot mm Ø 100 130

Noise Levels dB(A) 60 68 76 72 74

Nett Weight kg 178 248 305 362 410

Notes -

• Fuel consumption and output figures based upon nett calorific values as follows -Natural gas (G20) nett CV 34.02 MJ/m³ -Propane (G31) nett CV 88.00 MJ/m³• Heaters have efficiency levels which meet with the minimum heater efficiency requirements of UK Part L Building Regulations• Air handling data is assessed at room ambient conditions• Throw figures provide the distance to the point where the terminal velocity degrades to 0.25 m/s• Overall vertical heater height include heads or extended heads where appropriate• Standard height heads can be specified where site height is restricted• Blank and louvred lower side panels are interchangeable• Noise levels are applicable to standard UF models and are measured 5m from appliance and in free field conditions• Motor kW, run and start amps apply to standard electrical supply as stated. For optional data contact sales office• Connection of combustion air duct is not required for ‘flue only’ applications• It is the responsibility of the installing contractor to ensure that ductwork is correctly sized and balanced when installing ducted units

VPC UF / VPC UD

Duties

Page 7: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 7 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Model A B C D E F G H J J1 K L MHead Plan

30 1108 750 1676 100 265 1378 142 237 255 596 207 657 650 2

52 1108 750 2132 100 265 1832 142 237 286 581 256 657 650 2

80 1412 750 2132 130 265 1756 220 237 340 672 308 960 650 3

110 1767 750 2043 130 265 1667 220 237 340 672 308 1315 650 4

130 1767 750 2209 130 265 1835 220 237 400 788 358 1315 650 3

G

H

50

G

HØ D

GAS ENTRY

COMBUSTION AIR INLET

EXHAUST AIR OUTLET

ALTERNATIVE FLUE& COMBUSTION AIR

POSITIONS

J 1 J J

J 1

K

BAB

C

M

E

L

L

M

M

F

Dimensions

Page 8: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 8 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

650750

760660 760

660

136SIDE REAR

NL

136185

SIDE REAR

760660

NL

185

760660

650750

660

650L

660

50

50

SIDE REAR

Side/Rear Inlet Spigot Side/Rear Filters

Model 30 52 80 110 130

L 657 960 1315

N 757 1060 1415

Side/Rear Dampers

Head Plan 2 Head Plan 3Head Plan 1

Notes -• All dimensions are outside dimensions• Vertical units shown.• Standard filter specification is 10ppi• Higher specification filters available on request - contact our sales team for more information• Standard dampers are manual operation - motorised options available

Head Plans

Accessories

Page 9: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 9 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

High Fire Low Fire

Injectors Burner Pressure

Gas Rate

Nominal CO2

Nett Flue Temp

Burner Pressure

Gas Rate

Nominal CO2

Nett Flue Temp

MODEL No. Size (mm) Marked mbar m³/h % °C mbar m³/h % °C

VPC30 6 1.94 194 13.8 3.45 8.6 171 4.6 1.90 3.7 125

VPC52 12 1.94 194 10.4 5.98 8.2 172 3.0 3.22 3.1 117

VPC80 12 2.54 254 8.1 9.19 8.0 146 2.1 4.44 2.7 91

VPC110 10 3.00 300 10.2 12.64 9.0 180 3.2 6.50 3.2 114

VPC130 12 3.00 300 10.0 14.94 7.2 180 3.6 8.26 3.4 113

Injector Sizes & Burner Pressures - Natural Gas - Group H - G20 Net CV (Hi = 34.02MJ/m³). Minimum Inlet Pressure = 17.5mbar

High Fire Low Fire

Injectors Burner Pressure

Gas Rate

Nominal CO2

Nett Flue Temp

Burner Pressure

Gas Rate

Nominal CO2

Nett Flue Temp

MODEL No. Size (mm) Marked mbar m³/h % °C mbar m³/h % °C

VPC30 6 1.36 136 21.7 1.33 11.0 170 7.0 0.74 4.6 125

VPC52 12 1.25 125 27.0 2.31 8.9 170 8.0 1.24 4.0 118

VPC80 12 1.55 155 24.1 3.55 9.4 151 6.0 1.72 3.4 99

VPC110 10 1.94 194 26.5 4.89 10.4 192 7.0 2.51 4.0 121

VPC130 12 1.94 194 25.0 5.78 9.0 181 7.9 3.19 3.6 114

Injector Sizes & Burner Pressures - Propane G31 Net CV (Hi = 88.00MJ/m³).Minimum Inlet Pressure = 37mbar

MODELElectrical

SupplyMotor

kWNominal

Motor R.P.M.Max Fan Amps (A)

Start Amps (A)

Run Amps (A)

Fuse Rating (A)

VPC30 230V 1N 0.55 940 4.3 6.5 4.4 7

VPC52 230V 1N 1.1 940 4.2 8.3 4.5 7

VPC80 230V 1N 1.4 940 10.0 19.0 9.4 15

VPC110 230V 1N 1.5 1500 6.7 28.0 9.3 15

VPC130 230V 1N 2.2 1500 9.4 40.0 10.7 15

VPC110 400V 3N 1.5 1500 3.5 17.5 3.4 5

VPC130 400V 3N 2.2 1500 4.8 25.1 4.5 7

High Fire Low FireAir Volume

Maximum Duct

ResistanceFan

MotorNoise Level WeightInput

(Nett) Output Input (Nett) Output

MODEL kW kW m³/s m³/h Pa kW dB(A) kg

VPC30 32.6 30 18.0 15.7 0.8664 3119 150 0.55 68 178

VPC52 56.5 52 30.4 26.1 1.5884 5718 200 1.10 68 248

VPC80 87.0 80 42.0 36.8 2.3372 8414 225 1.40 76 305

VPC110 119.5 110 61.5 53.3 2.9568 10645 150 1.50 72 362

VPC130 141.3 130 78.1 69.0 3.6288 13064 200 2.20 74 410

Electrical Loadings - 1Pha

Heater Specifications

1.2 Technical Data

Page 10: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 10 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Motor (a) Motor Pulley (b) Motor Pulley TaperLock (c) Centrifugal Fan (d)

kW Pha RPM Pt no. Size Pt no. Size Pt no. type Size Pt no.

VPC30 0.55 1 940 n/a n/a n/a n/a n/a 1 321 x 321 1402CFAN280/T/15

VPC52 1.1 1 940 n/a n/a n/a n/a n/a 1 321 x 321 1402CFAN210/T/15

VPC80 1.4 1 940 n/a n/a n/a n/a n/a 1 381 x 381 1402CFAN580/T/15

VPC110 1.5 1 1500 140001908 95x1SPA 142000602 1210-24 142003350 2 321 x 321 1402CFAN240/T/2DECK

VPC130 2.2 1 1500 140001998 100x1SPA 142000601 1610-28 142161028 2 321 x 321 1402CFAN240/T/2DECK

VPC110 1.5 3 1500 140001915 95x1SPA 142000602 1210-24 142003350 2 321 x 321 1402CFAN240/T/2DECK

VPC130 2.2 3 1500 140002000 100x1SPA 142000601 1610-28 142161028 2 321 x 321 1402CFAN240/T/2DECK

Drive Data - Standard Motor

Fan Pulley (e) Fan Pulley TaperLock (f) Belt(s) (g) Contactor/Relay Overload

Size Pt no. Size Pt no. Size Pt no. Type Pt no. Type Pt no.

n/a n/a n/a n/a n/a n/a 5.5kW AC3 143000601 7-11A 143000801 VPC30

n/a n/a n/a n/a n/a n/a 5.5kW AC3 143000601 7-11A 143000801 VPC52

n/a n/a n/a n/a n/a n/a 7.5kW AC3 143000600 7-11A 143000801 VPC80

170x1SPA 142001689 1610-25 142003370 A990/38 142109801 7.5kW AC3 143000600 7-11A 143000801 VPC110

180x1SPA 142001675 1610-25 142003370 A1050/40 142110507 7.5kW AC3 143000600 12-18A 142000800 VPC130

160x1SPA 142001619 1610-25 142003370 A990/38 142109801 7.5kW AC3 143000600 7-11A 143000801 VPC110

180x1SPA 142001675 1610-25 142003370 A1050/40 142110507 7.5kW AC3 143000600 5-8A 142000802 VPC130

a

b

c

d

e

fg

Fan type 2Fan type 1

Page 11: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 11 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

1.3.1. Related Documents

All VPC heaters comply with the following European Directives:

Energy Related Product Directive: 2009/125/EC*Gas Appliance Directive: 2009/142/ECElectromagnetic Compatibility Directive: 2004/108/ECLow Voltage Directive: 2006/95/ECMachinery Directive: 2006/42/EC

Air heater(s) must be installed in accordance with BS6230 and BS5440 plus any relevant requirements of local and national building codes. * where appropriate

1.3.2 Location

The location chosen for the air heater must permit:- the provision of a satisfactory flue system and an adequate air supply.- adequate space for servicing and air circulation around the air heater.

The heater(s) must not be installed in conditions for which it is not specifically designed e.g. where the atmosphere is corrosive or salty. Standard units are not suitable for outdoor location.

Where the location of the air heater is such that it might suffer external mechanical damage e.g. from overhead cranes, fork lift trucks, it must be suitably protected.

VPC units are designed to operate within an ambient temperature range of -10 to 25°C.

1.3.3 Electrical Supply

Wiring external to the air heater must be installed in accordance with the I.E.E. Regulations for Electrical Installations and any local regulations which apply.All standard heaters are supplied by 230V - 1ph, 50Hz. The method of connection to the main electricity supply must:-

- facilitate the complete electrical isolation of the unit(s)- be in a readily accessible position adjacent to the unit(s)- serve only the unit(s)- have a contact separation of at least 3mm in all poles. See the accompanying wiring diagram for the heater electrical connections

1.3.4 Gas Supply

1.3.4.1 Service Pipes

The local gas undertaking should be consulted at the installation planning stage in order to establish the availability of an adequate supply of gas. An existing service pipe must not be used without prior consultation with the local gas undertaking. The inlet gas pressure under running conditions must not be less than 17.5mb.

1.3.4.2 Meters

An existing meter should be checked, preferably by the gas undertaking, to ensure that the meter is adequate to deal with the total rate of gas supply required by all connected equipment.

1.3.4.3. Installation Pipes

Installation pipes should be fitted in accordance with IGE/UP/2. Pipe work from the meter to the air heater must be of adequate size. Do not use pipes of a smaller size than the inlet gas connection of the heater. The complete installation must be tested for soundness as described in the above Code.

1.3.4.4. Boosted Supplies

Where it is necessary to employ a gas pressure booster the controls must include a low pressure cut off switch at the booster inlet. The local gas undertaking must be consulted before a gas pressure booster is fitted.

1.3.5 Flue System

VPC units must be used with a closed flue system and have an internal exhaust fan, mounted downstream of the heat exchanger, to both assist the evacuation of the products of combustion and to draw in air for combustion.

The flue must terminate in a freely exposed position and be sited to prevent the products of combustion entering any opening in a building in such concentration as to be prejudicial to health or a nuisance.

1.3.6 Air Distribution System

VPC units used in buildings having a low heat loss i.e. where single units are required to cover a large floor area, and in buildings with high roof or ceiling heights Calecon thermal economiser units should be fitted to ensure even

1.3 General Requirements

Page 12: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 12 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

heat distribution and minimise stratification.

Care should be taken to avoid impeding the air throw with racking, partitions, plant or machinery etc.

Care must be taken to ensure that return-air intakes are kept clear of sources of smells and fumes, and where there is any possibility of pollution of the air by dust, shavings etc., precautions must be taken to prevent contamination.If necessary suitable barrier rails should be provided to prevent any combustible material being placed within 900mm of the warm air outlets.

Page 13: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 13 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Type B flued installations. Where VPC heaters are installed within the heated space (ie not in a plant room or an enclosure) and having a building design air change rate of greater than 0.5/h, additional provision for ventilation is not required.

If the building design air change rate is less than 0.5/h, additional provision for natural or mechanical ventilation is required. These being:Natural Ventilation:Grilles having a free area of at least 2cm² per kW of rated heat input shall be provided at low level i.e. below the level of the heater flue connection.Mechanical Ventilation:Must ensure that the space air change rate is at least 0.5/h, must be of the ‘input’ type and interlocked to ensure the heaters cannot work if the input system is not working.

Type B flued installations. Where VPC heaters are installed in a plant room or an enclosure (ie not within the heated space) having combustion air drawn directly from the room and connected to a flue that evacuates the products of combustion directly from the room additional provision for natural or mechanical ventilation is required. These being:Natural Ventilation:There must be permanent air vents communicating directly with the outside air, at high level and at low level.

Plant RoomsLow level (inlet) 4cm²/kw of total rated net heat inputHigh level (outlet) 2cm²/kw of total rated net heat inputEnclosuresLow level (inlet) 10cm²/kw of total rated net heat inputHigh level (outlet) 5cm²/kw of total rated net heat inputMechanical Ventilation:The minimum flow rate of ventilation shall be 4.14m³/h per kilowatt of total rated heat input.

Type C flued installations. Where VPC heaters are Installed within the heated space (ie not in a plant room or an enclosure) having combustion air ducted to the appliance and combustion products ducted to the outside air, NO additional provision for the supply of either combustion air or for combustion products dilution or additional provision for the supply of air is necessary.

Type C flued installations.Where VPC heaters are Installed in a plant room or an enclosure (ie not within the heated space) having combustion air ducted to the appliance and combustion products ducted to the outside, air vents shall be provided and be permanently open.To room or internal spaceLow level (inlet) 10cm²/kw of total rated net heat inputHigh level (outlet) 10cm²/kw of total rated net heat inputDirect to outside airLow level (inlet) 5cm²/kw of total rated net heat inputHigh level (outlet) 5cm²/kw of total rated net heat input.

Type B22 Installation (these refer to section 2.2 of these instructions)Air vents shall be permanently open.In all cases figures are per heater installed.For multi heater installations the appropriate values for each heater must be added together

Type C12 or C32 Installation (these refer to section 2.2 of these instructions)Air vents shall be permanently open.Figures are for heaters in plant rooms or enclosures ONLYIn all cases figures are per heater installed. For multi heater installations the appropriate values for each heater must be added together.

VPCInputkW

In the heated space

In a plant room, ventilation to

outside

In an enclosure, ventilation to

outside

In the heated space

Ventilation is to a room or internal

space

Ventilation is to a outside air

Low level grille. Free area cm²

Low level grille. Free area cm²

High level grille. Free area cm²

Low level grille. Free area cm²

High level grille. Free area cm²

Free area grille cm²

Low level grille. Free area cm²

High level grille. Free area cm²

Low level grille. Free area cm²

High level grille. Free area cm²

30 32.6 65.2 130.0 65.2 326.0 163.0 n/a 326.0 326.0 163.0 163.0

52 56.5 113.0 226.0 113.0 565.0 283.0 n/a 565.0 565.0 283.0 283.0

80 87.0 174.0 348.0 174.0 870.0 435.0 n/a 870.0 870.0 435.0 435.0

110 119.5 239.0 478.0 239.0 1195.0 598.0 n/a 1195.0 1195.0 598.0 598.0

130 141.3 283.0 565.0 283.0 1413.0 707.0 n/a 1413.0 1413.0 707.0 707.0

1.4 Ventilation Air Requirements

Page 14: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 14 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Model 30 52 80 110 130

A Front mm 1000 1000 1000 1000 1000

B Rear mm 500

C Above mm 1000

D Side (Blank panel)* mm 150

E Side (Louvred)* mm 500

To the front of the heater to nearest wall 1.0mTo the rear of the heater to nearest wall 0.5mTo the side having louvred lower panels* 0.5mTo the side having blank lower panels (see below)* 0.15mAbove the heater 1.0m

* Side panels are interchangeable to ease with installation against walls etc. Therefore D can = 1.0m if E = 0.15m OR E can = 0.15m if D = 1.0m

AE* B

Minimum Clearance Distance

D*

C

2.1 Fitting the Unit

Page 15: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 15 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.

The air heater must be installed in accordance with the rules in force and the relevant requirements of any fire regulations or insurance company's requirements appertaining to the area in which the heater is located, particularly where special risks are involved such as areas where petrol vehicles are housed, where cellulose spraying is carried out, in wood working departments etc.

2.1.4 Minimum Clearances

The minimum clearances for installation and servicing shown opposite must be observed.

Any combustible material adjacent to the air heater and the flue system must be so placed or shielded as to ensure that its temperature does not exceed 65 °C.

IMPORTANT:1. Heaters shall not be installed in:-a) Those parts of spaces within buildings that have been classified as hazardous areas as defined in BS 5345 : Part 2. b) Where there is a foreseeable risk of flammable particles or gases or corrosion inducing gases or vapours being drawn into either the heated air stream or the air for combustion.c) In areas subjected to significant negative pressures due to extract systems.

2.1.2 Fitting the Unit

If necessary consideration should be given to mounting the heater on resilient pads, or equivalent, to minimise transfer of noise and vibration to the structure of the building.

Floor mounted heaters must be installed on a level noncombustible surface.

Heaters mounted at high level must be supported on a purpose designed platform or framework that is suspended from vertical drop rods, chains or straps or mounted on specifically designed cantilever brackets from a non-combustible wall. The method of installation support must be capable of adequately supporting the weight of the unit (See section 1.2) and any ancillary equipment. Before installing the heater the existing structure must be inspected to ensure it is suitable. All supports should be protected against the effects of rust or corrosion.

Any combustible material adjacent to the air heater and the flue system must be so placed or shielded as to ensure that its temperature does not exceed 65 °C.

If the method of mounting allows for any movement of the heater it is essential that all gas, duct, and electrical connections to the heater are made with flexible connections to maintain continuity of connection.

2.1.3 Gas Connection

To facilitate servicing a servicing valve and downstream union must be fitted at the inlet to the air heater. The gas supply to the air heater must be completed in solid pipe work and be adequately supported. Heaters suspended by drop rods, straps or chains must have a flexible connection as the final link between the gas supply pipe work and the heater. Sufficient slack must be left in the connection to take account of normal movement of the heater.

WARNING: When completing the final gas connection to the heater do not place undue strain on the gas pipe work of the heater.

2.1.4 Air Distribution System General

VPC heaters, if required, can be used with duct work either to more precisely define the point of air delivery, and /or provide ducted return air or ducted fresh air inlet. The system should be checked to ensure that the installation work has been carried out in accordance with the design requirements. Particular attention should be given to the correct arrangement of delivery ducts and registers, return air ducts and grills and general adequacy of return air paths. Ensure that the total duct system resistance does not exceed the available air pressure of the equipment supplied refer to section 1.2. If the duct system resistance is less than the available air pressure of the equipment supplied additional resistance must be introduced e.g. by adjustment of duct outlet nozzles and balancing of the duct system. Conversely if the duct system resistance is greater than the available air pressure of the heater supplied the system resistance must be reduced.

2.1.4 Room Thermostat Siting

The room thermostat should be fitted at a point which will be generally representative of the heated area as far as temperature is concerned. Draughty areas, areas subjected to direct heat e.g. from the sun, and areas where the air movement is relatively stagnant e.g. in recesses, should be avoided. The thermostat should be mounted approximately 1.5m from the floor.

Any room thermostat, frost thermostat, time clock etc. must be suitable for switching 230V, 5A and must be of the 'snap action' type to minimise contact bounce.

For electrical connections of external controls see section 2.5 or the accompanying wiring diagram.

Page 16: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 16 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

The minimum distance between surfaces of the flue pipe and any surfaces made from combustible materials is 300mm. If it is necessary for the flue pipe to pass through a structure made from combustible materials a metal sleeve must be used so that the minimum clearance of 300mm is maintained.

The flue and combustion air ducts supplied with the heater are capable of withstanding their own weight over the allowable flue lengths. Wall bands and bracing brackets, or equivalent, must be used to provide lateral stability and should be used at centres not exceeding 2.5 metres.

All models are supplied as standard with a top flue outlet and the flue outlet and combustion air sockets temporarily fitted.

2.2.1 Conversion to Side Flue Outlet

1. Remove the two blanking plates from the flue /combustion air openings at the side of the unit.

2. Disconnect the flexible pipe from the exhaust spigot.

3. Remove the four screws securing the exhaust spigot and reposition the spigot to the side of the heater using the top position. Refit the flexible pipe

4. Remove the four screws securing the combustion air spigot and reposition spigot to the side of the heater.

5. Refit the blanking plates to cover the holes in the top of the heater.

2.2.1.2 Internal Combustion Air

1. If ducted combustion air is not required (see Section 1.4) fit the mesh inlet plate (supplied loose) behind the unused combustion air inlet hole.

2.2.2. General Requirements

See Figures 1a to 2b for the different types of flue installation. In all cases the flue outlet socket must be connected via the provided flue system to outside air. The maximum permitted length of flue system is 6m, or 12m if the flue outlet only is used. If an offset is required two sets of 45° bends should be used each set being equivalent to 0.5m of flue length. 90° bends may be used but each set will be equivalent to 1.0m of flue length.

The minimum flue length (end of flue terminal to side or top of heater) shall not be less than 1.3m.

All outer joints must be finished with the provided locking bands. A smear of silicon grease to the inside of sockets will assist in fitting components together. All flue and combustion air ducts must be supported independently of the air heater. The flue or flue/combustion air terminal must not be installed so as to be less than:

- 300mm below an opening e.g. window, air brick etc. - 200mm below eaves or gutter.- 300mm from an internal or external corner. - 1200mm from a surface facing the terminal. - 1500mm vertically from another terminal on the same wall. - 300mm horizontally from another terminal on the same wall.- 2000mm from ground level.

2.2.3. Installation of Flue System

Note: A terminal guard, as supplied by Powrmatic Ltd, must be fitted to horizontal flue terminals.

2.2.3.1. Vertical System - Top Outlet

1. Locate the position of the flue terminal cut a hole in the roof to suit.

2. Fit the flashing and the flue terminal so that the lower edge of the outer case is over the top of the flashing.

Weather with silicon sealant or equivalent. Fit a condensate drain length into the flue socket on the heater and an equivalent straight length onto the combustion air socket.

3. Fit the twin to concentric adaptor to the terminal section and then extend down to the heater using straight lengths.

Fit adjustable lengths as the final connection pieces, to facilitate flue disconnection for servicing.

Extend the adjustable lengths to make the final connection but do not exceed the maximum extended length so as to maintain joint integrity.

Extend the drainage off take of the condensate drainage length to a suitable gully or drain.

4. Ensure that internal silicon sealing rings are in place and that all tubes are pushed fully home.

Secure concentric lengths with the locking bands provided.

2.2 Flue/Combustion Air Duct System

Page 17: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 17 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Fig 1a Exhaust only system - verticalType C32 installation

6m maximum

Terminal

Lengths Adjustablelengths

Single to twinadaptor

Flashing

Flue socketCombustion air socket

Condensate drainlength

2.2.3.2. Horizontal System - Side Outlet

1. Locate the position of the flue terminal, allowing for a slight gradient running down from the heater to the terminal of 2° - 3° and cut a hole in the building wall to suit.

2. Fit the flue terminal, securing via the wall plate and weather with silicon sealant or similar.

3. Fit the twin to concentric adaptor to the terminal section and extend the flue and combustion air ducts to the heater using straight lengths. Fit an adjustable length prior to the unit, to facilitate flue disconnection for servicing. Extend the adjustable lengths to make the final connection to the appropriate heater inlet/outlet spigots.

4. Ensure that internal silicon sealing rings are in place and that all tubes are pushed fully home. Secure concentric lengths with the locking bands provided.

Notes for all systems.i) Final overall length of adjustable disconnection piece must be between 360 - 415mm.ii) 45° offsets may be used if required. Each set is

equivalent to 0.5m of flue length.iii) Where VPC heaters are used in clean environments it is permissible to take the combustion air directly from the heated space. The supplied mesh intake plate, must be fitted to the combustion air inlet on the rear of the heater.

Fig 1b Exhaust only system - horizontalType C12 installation

Terminal

Lengths

Adjustable length

Single to twinadaptorFlue socket

Combustionair duct

6m maximum

Combustionair socket

2.2.3.3. Internal Combustion Air System

1. Complete the run of flue sections from the terminal spigot to the flue outlet socket of the heater generally as described in 2.2.3.1. and 2.2.3.2., ensuring that the internal silicon sealing rings are in place.

2. It is recommended that both air inlets are utilized and that both are fitted with the mesh inlet plates supplied.

Fig 2a Individual system - verticalType B22 installation

12m maximum

Terminal

Lengths

Adjustablelength

Flashing

Fluesocket

OPTION 1Combustion air entry(fitted with inlet grille) Condensate drain

length

OPTION 2Combustion air entry(fitted with inlet grille)

Page 18: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 18 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Fig 2b Individual system - horizontalType B22 installation

TerminalLengthsAdjustablelengthFlue

outlet

OPTION 2Combustion air entry(fitted with inlet grille)

12m maximum

2.2.4. Condense Length

VPC gas fired heaters (with on/off burner)A VPC heater fitted with an on/off burner, an approved flue

terminal & vertical flue run that’s predominantly internal, will typically not require an inline condense drain as flue gas temperatures are higher than the dew point, which is approximately 60°C.

VPC gas fired heater (with high/low & modulating burners)A VPC heater fitted with high/low or modulating burner may require an inline condense flue drain if vertically flued, due to the lower flue gas temperatures experienced when the heater is operating at low firing rates.

Exceptions may occur if the installation requires significant length of the flue which may cause chilling, or if heater may be exposed to high winds and heavy rain, which may ingress the flue. We would always recommend fitting the inline condense drain even if the drain point is capped, should the drain be required in the future. Any clarification can be achieved by consulting with Powrmatic’s Technical Department.

FAN / LIMIT THERMOSTAT

EXHAUST FAN

PRESSURE SWITCH

GAS VALVE

MANUAL OVERRIDE SWITCH

BURNER RESET

HIGH LIMIT RESET

CONTACTOR

OVERLOAD

MC200 CAB

2.3 General Identification of Electrical Items

Page 19: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 19 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Electrical Connections

Warning: THIS APPLIANCE MUST BE EARTHED.

Warning: Lockout reset is by a switched Neutral to the controls in the heater.

The electrical supply must be run to a point adjacent to the heater and be suitably terminated to provide an isolation point that will prevent remote activation of the unit during servicing.

Reference must be made to the table below to ascertain the electrical loading of the unit(s) being installed so that cables of adequate cross-sectional area are used for the electrical installation.

The length of the conductors between the cord anchorage and the terminals must be such that the current carrying conductors become taut before the earth conductor if the cable or cord slips out of the cord anchorage.

All external controls must be of an approved type. Initial Wiring InstalationKeyA = 2 core and earthB = MC200 On/Off = 6 core and earth MC200 Hi/Lo = 7 core and earth MC200 Mod = 8 core and earthC= Screened 2 core (MC200 models only)** (screen must be grounded only at the MC200, See instructions supplied with controller for wiring sizing, Max. 100m)

All units are fully prewired and only require final connections for the incoming mains supply and completion of the control circuit (230V).

The wiring terminals are located behind the front panel which has to be removed.

The mains supply ( single or three phase) connections are via a Hylec terminal block.

Control Circuitry connections are via a 30A numbered terminal strip. They are:

terminal 1 Heat onterminal 2 Fan onlyterminal 3* 0-10V (modulating) OR 230V High Fireterminal 4* 0V (modulating negative)terminal 5 Lockout indicationterminal 6 Burner reset* Used where required

Model Phase RunningAmps (A)

30 1 4.452 1 4.580 1 9.4110 1 9.3130 1 10.7110 3 3.4130 3 4.5

2.4 Electrical Cable Installation

Page 20: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 20 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 30-80 On/Off Gas Cabinet 1Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N1 1

CO

MP

ON

EN

T L

IST

Po

wrm

ati

c p

art

#

A. B

rah

ma

Co

ntr

ol

DM

N32

B. H

on

ey

we

ll F

an

/Lim

it T

he

rmo

sta

t

C

. L

imit

In

dic

ato

r / R

es

et

Bu

tto

nD

. A

ir P

res

su

re S

wit

ch

E

. M

ain

Gas

Va

lve

F.

Ex

ha

ust

/ C

om

bu

sti

on

Fa

n

G.

Ma

in f

an

H. H

yle

c T

erm

inal

Blo

ck

3 W

ay

I. N

Vx

Ve

r 2

Wir

ing

Lo

om

J

. Ig

nit

ion

Ele

ctr

od

eK

. R

ec

tifi

ca

tio

n P

rob

e

L.

Fu

se

Ho

lder

3.1

5A

M.

Hig

h L

imit

In

terf

ac

e B

oa

rd

N. In

tern

al

Lo

ck

ou

t R

es

et

Bu

tto

nO

. Jo

x R

ela

yP

. E

ng

inee

rs O

ve

rrid

e S

wit

ch

Q.

MC

20

0 F

ue

l S

av

er

R. P

ow

rtro

l R

em

ote

Re

set

S.

Kte

c C

on

tac

tor

T.

Ote

c O

ve

rlo

ad

U. J

ox

Re

lay

14

50

30

844

14

30

00

306

14

30

70

274

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

14

31

00

603

14

76

00

101

M

od

el sp

ec

ific

14

24

23

003

14

30

00

526

14

24

03

600

/21

430

70

274

14

30

00

816

14

31

00

663

MC

200

BL

PO

WR

TR

OL

/RR

Mo

del sp

ec

ific

Mo

del sp

ec

ific

143

000816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

NO

TE

S

Ma

ins

In

pu

t: 2

30

v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

lla

tio

n i

ns

tru

cti

on

s.

Warn

ing

: H

igh

vo

lta

ges

pre

se

nt

at

the

ig

nit

ion

e

lec

tro

de

wh

en

th

e u

nit

att

em

ps

to

lig

ht.

N

Main

Fan

On

ly 2

30

V In

pu

t

Lo

cko

ut

Ind

ica

tor

230v O

utp

ut

Lo

cko

ut

Re

set

- N

eu

tra

l S

wit

ch

Ex

tern

al C

on

tro

ls

Co

nn

ecti

on

s

B

°C °C

5 C

ore

C

ab

le

Ye

l 0.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Or

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Blu 0.5

AJK

MC

20

0 f

ue

lsave

r

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

inal N

um

bers

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

inal N

um

bers

R

NL

Heat

Dem

an

d 2

30

V In

pu

t

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite R

od

gers

alt

ern

ati

ve s

tat

(143000

307)

No

te:

Fan

Sta

t -

Rig

ht

Han

d S

ide

Lim

it S

tat

- L

eft

Han

d S

ide

16

15

8

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Yel 1.5

4 C

ore

C

ab

le

Br 0.5

16

16

17

17

DNC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

1.0

Blk

1.0

Blu

1.0

Gry

1.0

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Or

0.5Blu 0.5

No

te:

Rem

ove M

od

e L

ink 'B

'

Br

0.5

Or

0.5

Br 0.5

CO

M NO

NC

U

Br 0.5

Blu 0.5

NO

TE

S

Ma

ins

In

pu

t: 2

30

v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

lla

tio

n i

ns

tru

cti

on

s.

Warn

ing

: H

igh

vo

lta

ges

pre

se

nt

at

the

ig

nit

ion

e

lec

tro

de

wh

en

th

e u

nit

att

em

ps

to

lig

ht.

2.5 Wiring Diagrams

Page 21: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 21 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 30-80 Hi/Low Gas Cabinet 1Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N

Wir

ing

Leg

en

d

Co

nn

ec

tio

ns

mad

e b

y C

on

tro

l b

oard

As

se

mb

ler

Co

nn

ec

tio

ns

mad

e b

y F

ina

l A

ss

em

ble

r

Co

nn

ec

tio

ns

mad

e b

y I

ns

tall

er

1 1

CO

MP

ON

EN

T L

IST

Po

wrm

ati

c p

art

#

A. B

rah

ma

Co

ntr

ol

DM

N32

B. H

on

ey

we

ll F

an

/Lim

it T

he

rmo

sta

t

C

. L

imit

In

dic

ato

r / R

es

et

Bu

tto

nD

. A

ir P

res

su

re S

wit

ch

E

. M

ain

Gas

Va

lve

F.

Ex

ha

ust

/ C

om

bu

sti

on

Fa

n

G.

Ma

in f

an

H. H

yle

c T

erm

inal

Blo

ck

3 W

ay

I. N

Vx

Ve

r 2

Wir

ing

Lo

om

J

. Ig

nit

ion

Ele

ctr

od

eK

. R

ec

tifi

ca

tio

n P

rob

e

L.

Fu

se

Ho

lder

3.1

5A

M.

Hig

h L

imit

In

terf

ac

e B

oa

rd

N. In

tern

al

Lo

ck

ou

t R

es

et

Bu

tto

nO

. H

i-L

o G

as V

alv

e H

ead

P.

En

gin

ee

rs O

ve

rrid

e S

wit

ch

Q.

MC

20

0 F

ue

l S

av

er

R. P

ow

rtro

l R

em

ote

Re

set

S.

Kte

c C

on

tac

tor

T.

Ote

c O

ve

rlo

ad

U. J

ox

Re

lay

14

50

30

844

14

30

00

306

14

30

70

274

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

14

31

00

603

14

76

00

101

M

od

el sp

ec

ific

14

24

23

003

14

30

00

526

14

24

03

600

/31

430

70

274

14

24

66

402

14

31

00

663

MC

200

BL

Po

wrt

rol/

RR

Mo

del sp

ec

ific

Mo

del sp

ec

ific

1

430

00

816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

NO

TE

S

Ma

ins

In

pu

t: 2

30

v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

lla

tio

n i

ns

tru

cti

on

s.

Warn

ing

: H

igh

vo

lta

ges

pre

se

nt

at

the

ig

nit

ion

e

lec

tro

de

wh

en

th

e u

nit

att

em

ps

to

lig

ht.

N

B

°C °C

5 C

ore

C

ab

le

Ye

l 0.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Or

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Br 0.5

Blu 0.5

AJK

O

7 8

No

te:

Wh

en

th

e v

alv

e

is d

e-e

ne

rgiz

ed

th

e

he

ate

r o

pe

rate

s i

n

low

fir

e.

Br

0.5

Blu

0.5

MC

20

0 f

ue

lsave

r

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

inal N

um

bers

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

inal N

um

bers

R

NL

Heat

Hi D

em

an

d 2

30V

In

pu

t

Main

Fan

On

ly 2

30

V In

pu

t

Lo

cko

ut

Ind

ica

tor

230v O

utp

ut

Lo

cko

ut

Re

set

- N

eu

tra

l S

wit

ch

Ex

tern

al C

on

tro

ls

Co

nn

ecti

on

s

Heat

Lo

Dem

an

d 2

30V

In

pu

t

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite R

od

gers

alt

ern

ati

ve s

tat

(143000

307)

No

te:

Fan

Sta

t -

Rig

ht

Han

d S

ide

Lim

it S

tat

- L

eft

Han

d S

ide

16

15

8

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Yel 1.5

4 C

ore

C

ab

le

Br

0.5

Or 0.5

17

17

DNC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

1.0

Blk

1.0

Blu

1.0

Gry

1.0

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Or

0.5Blu 0.5

Br

0.5

16

16

No

te:

Rem

ove M

od

e L

ink 'B

'

CO

M NO

NC

U

Br 0.5

Blu 0.5

Page 22: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 22 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 30-80 Modulating Gas Cabinet 1Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N

Wir

ing

Leg

en

d

Co

nn

ec

tio

ns

mad

e b

y C

on

tro

l b

oard

As

se

mb

ler

Co

nn

ec

tio

ns

mad

e b

y F

ina

l A

ss

em

ble

r

Co

nn

ec

tio

ns

mad

e b

y I

ns

tall

er

1 1

CO

MP

ON

EN

T L

IST

Po

wrm

ati

c p

art

#

A. B

rah

ma

Co

ntr

ol

DM

N32

B. H

on

ey

we

ll F

an

/Lim

it T

he

rmo

sta

t

C

. L

imit

In

dic

ato

r / R

es

et

Bu

tto

nD

. A

ir P

res

su

re S

wit

ch

E

. M

ain

Gas

Va

lve

F.

Ex

ha

ust

/ C

om

bu

sti

on

Fa

n

G.

Ma

in f

an

H. H

yle

c T

erm

inal

Blo

ck

3 W

ay

I. N

Vx

Ve

r 2

Wir

ing

Lo

om

J

. Ig

nit

ion

Ele

ctr

od

eK

. R

ec

tifi

ca

tio

n P

rob

e

L

. F

use

Ho

lder

3.1

5A

M

. H

igh

Lim

it I

nte

rfac

e B

oa

rd

N.

O.

P.

En

gin

ee

rs O

ve

rrid

e S

wit

ch

Q.

MC

20

0 F

ue

l S

av

er

R. P

ow

rtro

l R

em

ote

Re

set

S.

Kte

c C

on

tac

tor

T.

Ote

c O

ve

rlo

ad

U. M

od

ula

tin

g D

rive

r B

oa

rdV

. M

od

ula

tin

g D

rive

r H

ea

dW

Jo

x R

ela

y

14

50

30

844

14

30

00

306

14

30

70

274

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

Mo

del sp

ec

ific

14

31

00

603

14

76

00

101

M

od

el sp

ec

ific

14

24

23

003

14

30

00

526

14

24

03

600

/3

14

31

00

663

MC

200

BL

Po

wrt

rol/

RR

Mo

del sp

ec

ific

Mo

del sp

ec

ific

14

24

00

305

14

24

66

403

14

30

00

816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

16

16

17

17

NO

TE

S

Ma

ins

In

pu

t: 2

30

v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

lla

tio

n i

ns

tru

cti

on

s.

Warn

ing

: H

igh

vo

lta

ges

pre

se

nt

at

the

ig

nit

ion

e

lec

tro

de

wh

en

th

e u

nit

att

em

ps

to

lig

ht.

C

B

°C °C

5 C

ore

C

ab

le

Ye

l 0.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Or

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Br 0.5

Blu 0.5

AJK

Blu

0.5

Br

0.5

Ye

l 0.5

Or

0.5

Blu

0.5

Br

0.5

Main

Fan

On

ly 2

30

V In

pu

t

Lo

cko

ut

Ind

ica

tor

230v O

utp

ut

Lo

cko

ut

Re

set

- N

eu

tra

l S

wit

ch

Ex

tern

al C

on

tro

ls

Co

nn

ecti

on

sM

od

ula

tin

g S

ign

al 0v

Mo

du

lati

ng

Sig

nal 0-1

0v

Heat

Dem

an

d 2

30

V In

pu

t

MC

20

0 f

ue

lsave

r

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

inal N

um

bers

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

inal N

um

bers

R

NL

43

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite R

od

gers

alt

ern

ati

ve s

tat

(143000

307)

No

te:

Fan

Sta

t -

Rig

ht

Han

d S

ide

Lim

it S

tat

- L

eft

Han

d S

ide

16

15

8

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Yel 1.5

4 C

ore

C

ab

le

V

7 8

U

Ye

l 0.5

Or

0.5

12

35

6

61

62

63

64

65

66

ON

12

Or

0.5

D

NC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

0.7

5

Blk

0.7

5

Blu

0.7

5

Gry

0.7

5

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Blu 0.5

P

Br

0.5

Br

0.5

Or

0.5Br

0.5

No

te:

Rem

ove M

od

e L

ink 'B

'

CO

M NO

NC

W

Br 0.5

Blu 0.5

Page 23: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 23 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 110-130 On/Off Gas Cabinet 3Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N

Wir

ing

Leg

en

d

Co

nn

ecti

on

s m

ad

e b

y C

on

tro

l b

oard

Ass

em

ble

r

Co

nn

ecti

on

s m

ad

e b

y F

inal A

sse

mb

ler

Co

nn

ecti

on

s m

ad

e b

y In

sta

ller

1 1

CO

MP

ON

EN

T L

IST

P

ow

rmati

c p

art

#

A. B

rah

ma C

on

tro

l D

MN

32

B. H

on

ey

well F

an

/Lim

it T

herm

osta

t

C

. L

imit

In

dic

ato

r / R

eset

Bu

tto

nD

. A

ir P

ressu

re S

wit

ch

E. M

ain

Gas V

alv

eF

.E

xh

au

st

/ C

om

bu

sti

on

Fan

G.

Main

fan

mo

tor

H. H

yle

c T

erm

inal B

lock

3 W

ay

I. N

Vx V

er

2 W

irin

g L

oo

m

J. Ig

nit

ion

Ele

ctr

od

e

K. R

ecti

ficati

on

Pro

be

L.

Fu

se H

old

er

3.1

5A

M. H

igh

Lim

it In

terf

ace

Bo

ard

N. In

tern

al L

ocko

ut

Reset

Bu

tto

n

P. E

ng

ineers

Ove

rrid

e S

wit

ch

Q.

MC

200 F

uel

Sa

ver

R. P

ow

rtro

l R

em

ote

Res

et

S. K

tec C

on

tacto

rT

.O

tec O

ve

rlo

ad

U. Jo

x R

ela

y

145

030844

143

000306

143

070274

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

143

100603

147

600101

M

od

el s

pe

cif

ic

142

423003

143

000526

142

403600

/3143

070274

143

100663

MC

200B

LP

OW

RT

RO

L/R

R

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

143

000816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

16

16

17

17

NO

TE

S

Main

s In

pu

t: 2

30v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

llati

on

in

str

ucti

on

s.

Wa

rnin

g:

Hig

h v

olt

ag

es p

res

en

t at

the ig

nit

ion

ele

ctr

od

e w

hen

th

e u

nit

att

em

ps t

o lig

ht.

N

Main

Fa

n O

nly

23

0V

In

pu

t

Lo

ck

ou

t In

dic

ato

r 23

0v O

utp

ut

Lo

ck

ou

t R

es

et

- N

eu

tral

Sw

itc

h

Ex

tern

al

Co

ntr

ols

C

on

ne

cti

on

s

B

°C °C

5 C

ore

C

ab

le

Ye

l 0

.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Or

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1

.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Br 0.5

Blu 0.5

AJK

MC

200

fu

els

av

er

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

ina

l N

um

be

rs

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

ina

l N

um

be

rs

R

NL

He

at

De

ma

nd

23

0V

In

pu

t

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite

Ro

dg

ers

alt

ern

ati

ve s

tat

(143

00

030

7)

No

te:

Fa

n S

tat

- R

igh

t H

an

d S

ide

Lim

it S

tat

- L

eft

Ha

nd

Sid

e

16

15

8

LN M

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Ye

l 1

.5

4 C

ore

C

ab

le

NC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

1.0

Blk

1.0

Blu

1.0

Gry

1.0

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Or

0.5Blu 0.5

No

te:

Re

mo

ve M

od

e L

ink 'B

'

Br

0.5

Br

0.5

P

CO

M NO

NC

U

Br 0.5

Blu 0.5

Br 0.5

Br 0.5

Page 24: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 24 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 110-130 Hi/Low Gas Cabinet 3Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N

Wir

ing

Leg

en

d

Co

nn

ecti

on

s m

ad

e b

y C

on

tro

l b

oard

Ass

em

ble

r

Co

nn

ecti

on

s m

ad

e b

y F

inal A

sse

mb

ler

Co

nn

ecti

on

s m

ad

e b

y In

sta

ller

1 1

CO

MP

ON

EN

T L

IST

P

ow

rmati

c p

art

#

A. B

rah

ma C

on

tro

l D

MN

32

B. H

on

ey

well F

an

/Lim

it T

herm

osta

t

C

. L

imit

In

dic

ato

r / R

eset

Bu

tto

nD

. A

ir P

ressu

re S

wit

ch

E. M

ain

Gas V

alv

eF

.E

xh

au

st

/ C

om

bu

sti

on

Fan

G.

Main

fan

mo

tor

H. H

yle

c T

erm

inal B

lock

3 W

ay

I. N

Vx V

er

2 W

irin

g L

oo

m

J. Ig

nit

ion

Ele

ctr

od

e

K. R

ecti

ficati

on

Pro

be

L.

Fu

se H

old

er

3.1

5A

M. H

igh

Lim

it In

terf

ace

Bo

ard

N. In

tern

al L

ocko

ut

Reset

Bu

tto

nO

.H

i-L

o G

as V

alv

e H

ead

P. E

ng

ineers

Ove

rrid

e S

wit

ch

Q.

MC

200 F

uel

Sa

ver

R. P

ow

rtro

l R

em

ote

Res

et

S. K

tec C

on

tacto

rT

.O

tec O

ve

rlo

ad

U. Jo

x R

ela

y

145

030844

143

000306

143

070274

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

143

100603

147

600101

M

od

el s

pe

cif

ic

142

423003

143

000526

142

403600

/3143

070274

142

466402

143

100663

MC

200B

LP

ow

rtro

l/R

RM

od

el s

pe

cif

ic

Mo

de

l s

pe

cif

ic

143

000816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

16

16

17

17

NO

TE

S

Main

s In

pu

t: 2

30v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

llati

on

in

str

ucti

on

s.

Wa

rnin

g:

Hig

h v

olt

ag

es p

res

en

t at

the ig

nit

ion

ele

ctr

od

e w

hen

th

e u

nit

att

em

ps t

o lig

ht.

N

B

°C °C

5 C

ore

C

ab

le

Ye

l 0

.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1

.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Br 0.5

Blu 0.5

AJK

O

7 8

No

te:

Wh

en

th

e v

alv

e

is d

e-e

ne

rgiz

ed

th

e

he

ate

r o

pe

rate

s in

lo

w f

ire.

Br

0.5

Blu

0.5

MC

200

fu

els

av

er

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

ina

l N

um

be

rs

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

ina

l N

um

be

rs

R

NL

He

at

Hi

Dem

an

d 2

30

V I

np

ut

Main

Fa

n O

nly

23

0V

In

pu

t

Lo

ck

ou

t In

dic

ato

r 23

0v O

utp

ut

Lo

ck

ou

t R

es

et

- N

eu

tral

Sw

itc

h

Ex

tern

al

Co

ntr

ols

C

on

ne

cti

on

s

He

at

Lo

De

ma

nd

23

0V

In

pu

t

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite

Ro

dg

ers

alt

ern

ati

ve s

tat

(143

00

030

7)

No

te:

Fa

n S

tat

- R

igh

t H

an

d S

ide

Lim

it S

tat

- L

eft

Ha

nd

Sid

e

16

15

8

LN M

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Ye

l 1

.5

4 C

ore

C

ab

le

Or 0.5

NC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

1.0

Blk

1.0

Blu

1.0

Gry

1.0

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Or

0.5Blu 0.5

No

te:

Re

mo

ve M

od

e L

ink 'B

'

Br

0.5

Br

0.5

P

CO

M NO

NC

U

Br 0.5

Blu 0.5

Br 0.5

Br 0.5

Page 25: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 25 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

VPC 110-130 Modulating Gas Cabinet 3Pha

EA

RT

H

NE

UT

RA

L

LIV

E

MA

INS

SU

PP

LY

LL

L

L

EE E

EN

N N

N

Wir

ing

Leg

en

d

Co

nn

ecti

on

s m

ad

e b

y C

on

tro

l b

oard

Ass

em

ble

r

Co

nn

ecti

on

s m

ad

e b

y F

inal A

sse

mb

ler

Co

nn

ecti

on

s m

ad

e b

y In

sta

ller

1 1

CO

MP

ON

EN

T L

IST

P

ow

rmati

c p

art

#

A. B

rah

ma C

on

tro

l D

MN

32

B. H

on

ey

well F

an

/Lim

it T

herm

osta

t

C

. L

imit

In

dic

ato

r / R

eset

Bu

tto

nD

. A

ir P

ressu

re S

wit

ch

E. M

ain

Gas V

alv

eF

.E

xh

au

st

/ C

om

bu

sti

on

Fan

G.

Main

fan

mo

tor

H. H

yle

c T

erm

inal B

lock

3 W

ay

I. N

Vx V

er

2 W

irin

g L

oo

m

J. Ig

nit

ion

Ele

ctr

od

e

K. R

ecti

ficati

on

Pro

be

L.

Fu

se H

old

er

3.1

5A

M. H

igh

Lim

it In

terf

ace

Bo

ard

N. In

tern

al L

ocko

ut

Reset

Bu

tto

n

P. E

ng

ineers

Ove

rrid

e S

wit

ch

Q.

MC

200 F

uel

Sa

ver

R. P

ow

rtro

l R

em

ote

Res

et

S. K

tec C

on

tacto

rT

.O

tec O

ve

rlo

ad

U. G

M4

4 M

od

ula

tin

g D

riv

er

Bo

ard

V. M

od

ula

tin

g D

riv

er

Head

W. J

ox R

ela

y

145

030844

143

000306

143

070274

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

Mo

de

l s

pe

cif

ic

143

100603

147

600101

M

od

el s

pe

cif

ic

142

423003

143

000526

142

403600

/3143

070274

143

100663

MC

200B

LP

ow

rtro

l/R

RM

od

el s

pe

cif

ic

Mo

de

l s

pe

cif

ic

142

400303

142

466403

143

000816

L

10

10

E F

2 2

3 3

4 4

5 5

6 6

7 7

7 7

8 8

8 8

9 9

11

11

12

12

13

13

14

14

15

15

HI

1234567

8

9

10

11

12

4AFUSE

16171819131415

J5

J6

JT2

JT1

BRAHMACODE 3756400Type DMN32

16

16

17

17

NO

TE

S

Main

s In

pu

t: 2

30v 5

0H

z 1

ph

Su

pp

ly.

Fo

r in

pu

t p

ow

er

refe

r to

In

sta

llati

on

in

str

ucti

on

s.

Wa

rnin

g:

Hig

h v

olt

ag

es p

res

en

t at

the ig

nit

ion

ele

ctr

od

e w

hen

th

e u

nit

att

em

ps t

o lig

ht.

N

B

°C °C

5 C

ore

C

ab

le

Ye

l 0

.5

Wh

0.5

Or

0.5

Br

0.5

Blu

0.5

Blu

0.5

Wh

0.5

Blk

0.5

Br

0.5

Blu

0.5

Gry

1.0

Br

1.0

Blk

1.0

Ye

l 1

.0

Or

0.5

Or

0.5

Blk

0.5

Wh

0.5

Blu

0.5

Wh 0.5

Br 0.5

Blu 0.5

AJK

Blu

0.5

Br

0.5

Ye

l 0

.5

Or

0.5

Main

Fa

n O

nly

23

0V

In

pu

t

Lo

ck

ou

t In

dic

ato

r 23

0v O

utp

ut

Lo

ck

ou

t R

es

et

- N

eu

tral

Sw

itc

h

Ex

tern

al

Co

ntr

ols

C

on

ne

cti

on

sM

od

ula

tin

g S

ign

al 0

v

Mo

du

lati

ng

Sig

na

l 0

-10

v

He

at

De

ma

nd

23

0V

In

pu

t

MC

200

fu

els

av

er

SEN 1

COM

IN 2

0-10v +

0-10v -

Reset

Lockout

Heat Hi In

Heat Hi Out

Heat Lo In

Heat Lo Out

Fan In

Fan Out

L Out

N

E

L

Q

LN

21

56

NV

x T

erm

ina

l N

um

be

rs

L/OReset

L/OLAMP

CLOCKO/P

HEATIN

HEATOUT

L

NPO

WR

TR

OL

RR

VENT

VENT

65

21

NV

x T

erm

ina

l N

um

be

rs

R

NL

43

Br

0.5

Blu

0.5

Br

0.5

Blu

0.5

LIMIT

FAN

ºc

Wh

ite

Ro

dg

ers

alt

ern

ati

ve s

tat

(143

00

030

7)

No

te:

Fa

n S

tat

- R

igh

t H

an

d S

ide

Lim

it S

tat

- L

eft

Ha

nd

Sid

e

16

15

8

LN M

13

L3

L2

L1

14

T3

T2

T1

A1 A2 95 96

T1

T2

T3

G

3 C

ore

C

ab

le

S T

Blk

1.5

Br 1.5

Blu

1.5

Br 1.5

Br 1.5

Blu 1.5

Gr/Yel 1.5

Br

1.5

Gr/

Ye

l 1

.5

4 C

ore

C

ab

le

Blu

0.5

Br

0.5

V

7 8

U

Ye

l 0

.5

Or

0.5

12

35

6

61

62

63

64

65

66

ON

12

Or

0.5

Br

0.5

P

NC

NO

C

C

M

18

18

19

19

20

20

21

21

Br

1.0

Blk

1.0

Blu

1.0

Gry

1.0

65 4

2 3 1

109

11

87 N

O

CO

M

NC

R/S

TR

P

N L

Blu 0.5

Gry 0.5

Blk 0.5

Br 0.5

Or

0.5Blu 0.5

No

te:

Re

mo

ve M

od

e L

ink 'B

'

Br

0.5

Br

0.5

CO

M NO

NC

W

Br 0.5

Blu 0.5

Br 0.5

Br 0.5

Page 26: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 26 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

2.6.1. Electrical Installation

Checks to ensure electrical safety must be carried out by a qualified person.

2.6.2. Gas Installation

For new installations, the whole of the gas installation, including the meter, should be inspected and tested for soundness and purged in accordance with the recommendations of IGE/UP/1 (Edition 2) or IGE/UP/2A as appropriate.

2.6.3. First Start Sequence

Follow the sequence below before lighting the heater(s) for the first time.

a) Ensure that the gas supply to the unit is turned OFF.b) Turn on the electrical supply to the heater and program the controls in accordance with their instructions.

c) Ensure that the controls are not calling for heat i.e. the thermostat is at minimum or the clock control is set to an OFF period or the function switch is set to OFF.

d) If necessary reset the internal control from lockout by pressing the reset button on the external control for 1-2 seconds.

e) Press the limit interlock reset switch on the electrical panel.

f) Ensure that the Summer/Winter switch is in the Winter position.

g) On ducted systems check that all warm air delivery outlets are open.

h) Turn ON the gas supply.

2.6.4. Lighting the Air Heater

NOTES: On initial lighting of the heater(s), it may take some time to purge the internal pipe work of air.

IMPORTANT: The internal pipe work of the appliance has been tested for soundness before leaving the factory. After establishing the main burners test round

the gas inlet connection using a leak detection fluid.

1. Switch on the electrical supply at the isolator.

2. If the limit indicator light comes on press the limit thermostat interlock relay reset switch on the inside panel. The Red indicator light will go out and the ignition sequence will commence. After a delay of approximately 45 seconds the ignition spark will be generated and the main gas valves energized. The burners will then light.

3. If the burners fail to light the control box will complete a further four ignition attempts. If at the end of five attempts the burners have still not lit the control box will go to lockout and the amber indicator light, internal and remote lockout lights will be illuminated. To restart the ignition sequence depress the illuminated reset button for about 1-2 seconds.

2.6.5 Adjustments

2.6.5.1. Burner Gas Pressures

This is set for the required heat input before despatch. In the case of Hi/Lo and Modulating units both high and low pressures are set. Pressures should be checked in the following manner.

2.6.5.1.1. Standard On/Off Units

1. Set external controls to ensure that the main burner is off. Open the front access door. Connect a pressure gauge to the burner pressure test point on the multifunctional control.

2. Set external controls so as to turn on the main burner. Compare the measured burner gas pressure to that stated on the data plate. If necessary adjust the burner gas pressure by turning the regulator screw anticlockwise to decrease the pressure, or clockwise to increase the pressure.

3. In addition it is advisable to check the gas rate using the gas meter dial pointer. Ensure that no other appliances supplied through the meter are in operation.

2.6 Commissioning and Testing

Page 27: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 27 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

2.6.5.1.2. High/Lo Regulator

1. Set external controls to ensure the main burner is off. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the multifunctional control.

2. Set external controls to turn on the main burner and maintain high fire. Compare the measured burner gas pressure to that stated on the data plate. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation.

3. Repeat 2 above with external controls set to maintain low fire.

4. If it is necessary to adjust either the high fire or low fire pressures proceed as follows after levering off the plastic cover from the Hi/Lo regulator.

Note: High fire setting must be adjusted first after which the low fire setting can be set. Any adjustment of the high fire setting alters the minimum setting.

Maximum SettingWith the controls set to high fire use an adjustable or 8mm spanner to turn the adjustment screw for high fire pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Turn the burner On and OFF several times to check the pressure setting and then turn off.

Minimum SettingDisconnect electrical connection of high/low regulator and turn burners back on and wait until the burner pressure has stabilized. Use a screwdriver to turn the slotted adjustment screw for low fire pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Reconnect high/low regulator and check high fire pressure. Repeat both steps if necessary and then replace cover cap.

4. If required, after checking or setting the burner pressures, the CO2 content in the flue gases can be checked by sampling in the first section of flue fitted to the flue outlet of the unit. Nominal CO2 values are given for guidance in the Table above.

5. Turn off the main burner and disconnect the pressure gauge and replace the sealing screw. Turn on the main burner as above and test for gas soundness around pressure test joint using a leak detection fluid e.g. soap solution.

Governor adjustment screw under cover cap (Honeywell VR4605AB1027)

Fitted to the VPC 30 - 80

Governor adjustment screw under cover cap (Honeywell VK425AB1007)

Fitted to the NVx 110 and 130

Model 30 52 80 110 130

Natural Gas G20

High Fire CO2 % 8.6 8.2 8.0 9.0 7.2

Low Fire CO2 % 3.7 3.1 2.7 3.2 3.4

Propane G31

High Fire CO2 % 11.0 8.9 9.4 10.4 9.0

Low Fire CO2 % 4.6 4.0 3.4 4.0 3.6

Page 28: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 28 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

5. Turn off the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection fluid. Replace access panel.

CoverLever point

Hexagonal adjustment screw for maximum pressure setting

Internal slotted adjustment screw for minimum pressure setting

Hi/Low Regulator

2.6.5.1.3. Modulating Regulator

1. Set external controls to ensure that the main burner is off. Open the front access panel. Connect a pressure gauge to the burner pressure test point on the multifunctional control.

2. Set external controls so as to turn on the main burner and maintain high fire. Compare the measured burner gas pressure to that stated on the data plate. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation.

3. Repeat 2 above with external controls set to maintain low fire.

4. If it is necessary to adjust either the high fire or low fire pressures proceed as follows after removing the plastic cover from the Modulating regulator.

Note: Minimum fire setting must be adjusted first after which the high fire setting can be set. Any adjustment of the minimum fire setting alters the maximum setting.

‘O’ ring

Adjustment nut (9mm)for minimum pressure setting

Adjustment nut (7mm)for maximum pressure setting

Cap

Shaft

6.3mm AMP terminals

Modulatiing Regulator

Minimum SettingDisconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilized. Turn 9mm adjustment nut for low fire pressure clockwise to increase and counter-clockwise to decrease until the required pressure is obtained. Reconnect modulating regulator and check high fire pressure, readjust if necessary.

Maximum SettingDisconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilized. Push shaft gently downwards to the maximum adjustment screw and hold there. Turn 7mm adjustment nut for high fire pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Release shaft. Repeat both settings if necessary and then replace cover cap.

5. Turn off the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection fluid.

Page 29: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 29 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

P2%

P3%

Drop Out Volts

5 10 20 30 40 50 60 70 80 90 100Hold-in Voltage

0 0.3 0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

10 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

20 2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0

30 3.0 3.5 4.0 5.0 6.0 7.0 8.0 9.0 10.0

40 4.0 4.5 5.0 6.0 7.0 8.0 9.0 10.0

2.6.5.2. Modulating Interface Board

Modulating Interface Board

The MIB interfaces between a 0-10VDC control signal and the modulating regulator. The following are applicable to this application.

1. The setting of the slide switches 1 & 2 should both be to OFF.

2. Potentiometer P1 (Default setting 100%)

The control current of the V7335A is controlled by P1, varying between 50% and 100% of the input signal.E.g.-When P1 is set at 100% (fully clockwise) maximum power (165mA @ 22VDC) is provided to the modulation coil with a 10VDC input control signal.-When P1 is set at 50% (fully anticlockwise) maximum power (165mA @ 22VDC) is provided to the modulation coil with a 5VDC input control signal.

3. Potentiometer P2Controls the minimum drop-out voltage between 0% and 40% E.g.- When P2 is set at 0% the drop-out voltage with an input control signal of 0-10V-DC is 0.3V-DC.- When P2 is set at 40% the drop-out voltage with an input control signal of 0-10V-DC is 4.0V-DC.

4. Potentiometer P3 (Default setting 100%)Controls the maximum hold-in voltage. Its proportional value is added to the P2 setting E.g.- When P2 is set at 0% and P3 is set at 5%, the hold-in voltage of the burner relay is adjustable between 5% and 100% of the input control signal. If the input control signal is set at 0-10V-DC the hold-in voltage of the relay is 0.5V-DC.- When P2 is set at 40% and P3 is set at 5%, the hold-in voltage of the burner relay is adjustable between 45% and 100% of the input control signal. If the input control signal is set at 0-10V-DC the hold-in voltage of the relay is 4.5V-DC.The following table shows the relationship between P2 and P3 settings.

2.6.5.2. Flame Current

1. To measure the flame current connect a multimeter capable of measuring micro amps as shown in the following diagram.

Page 30: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 30 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

WARNING: Always switch off and disconnect electricity supply and close the gas service valve before carrying out any servicing work or replacement of failed components.

NOTE: If a suspended air heater is to be serviced do not lean ladders against the heater. Ensure that an access tower or equivalent is used.

2.7.1. General

Full maintenance should be undertaken not less than once per year by a qualified person. After any servicing work has been complete, or any component replaced, the air heater(s) must be fully commissioned and tested for soundness as described in Section 2.6.

2.7.2. Main Burner Assembly Removal

1. Ensure that the gas service valve is turned OFF and then unscrew the union nut situated immediately downstream of it.

2. Disconnect the spark and rectification leads from the control box and remove the electrical plug connections from the top of the gas control valve assembly.

3. Remove the burner heat shield, 3 screws.

4. Release the inlet connection flange from the gas valve by removing the four screws.

5. If required remove the manifold by removing the four screws securing it to the burner assembly.6. Remove the two screws that secure the top of the burner assembly to the bulkhead and lift out burner assembly.

7. Using a stiff brush, not a wire brush, brush the burners to dislodge accumulated deposits. Inspect the burners both internally and externally to ensure that they are clean. Examine the injectors and if damaged or deteriorated, replace with new ones of the correct size and marking. If deemed necessary, clean the injectors. Do not broach out with wire.

8. Reassemble the injectors, manifold and burners in reverse order to that above.

2. Minimum current reading is 0.5µA and normal value should be 1.5µA or higher.

Flame Current Measurement

2.6.5.3. Air Heater Controls

1. Close the gas service tap and ensure that the gas valve is heard to close within 1 second and that the lockout light is illuminated. Note that the heater may attempt five re-ignitions before going to lockout. Open the gas service tap and reset the unit from lockout.

2. Check that the room thermostat and all automatic controls are operating satisfactorily.

2.6.6. Fan/Limit Thermostat

Ensure that the fan and limit settings are as follows:-Thermostat settings:-

Fan Off: 86°F/30°C Fan On: 122°F/50°C Limit: VPC 30, 52 212°F/100°C VPC 80, 110,130 230°F/110°C

2.6.7. Handing over the Air Heater

Hand these instructions to the user or purchaser for retention and instruct in the efficient and safe operation of the air heater and associated controls. Adjust the automatic controls to those values required by the User.

Finally, advise the user or purchaser that, for continued efficient and safe operation of the air heater, it is important that servicing is carried out annually.

In the event that the premises are not yet occupied turn off the gas and electricity supplies and leave instructional literature adjacent to gas meter.

2.7 Servicing

Page 31: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 31 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

2.7.3. Ignition and Rectification Electrodes

Note: The ignition electrode is located at the bottom of the burner assembly, the rectification electrode is located at the top of the burner assembly.

Inspect the electrodes, making sure that they are in a sound and clean condition. In particular check that the ignition electrode is clean and undamaged. Check that the spark gap is 2.5mm and that the rectification probe is 10 - 12mm forward of the burner.

2.5mm

Ignition Electrode Spark Gap

2.7.4. Heat Exchanger

Whilst the main burner assembly is removed from the unit, check that the primary sections that the burners fire into are clean.

2.7.5 Main Fan Assembly

Inspect the fan blades to see that they are not damaged and that there is no excessive build up of deposits that could give rise to an imbalance.

2.7.6. Replacement of Faulty Components

2.7.6.1 Multifunctional Control

1. If there is movement available on the incoming gas pipe work e.g. a flexible connection has been used go to step 2 otherwise remove the burner assembly as previously described in Section 2.7.2.

2. Remove the electrical plug connections from the top of the multifunctional control.

3. Release the flanged connections at the inlet and outlet of the multifunctional control and remove the multifunctional control.

4. Reconnect the new valve in the reverse order to that above ensuring that the valve is correctly orientated. Renew the sealing 'O' rings if necessary.

2.7.6.2. Burners

1. Remove the burner assembly as described in Section 2.7.2.

2. Remove the end plates of the burner assembly and the central burner support plate.

3. Exchange burners as required and reassemble components in reverse order.

4. Re-commission the appliance as described in Section 2.6.

2.7.6.3. Electrode Assemblies

1. Disconnect the electrode leads from the control box as appropriate.

2. Remove the screw securing the electrode assembly to the burner assembly side plate and withdraw the assembly.

3. Fit replacement and reassemble in reverse order. Check that the spark gap is 2.5mm (See section 2.7.3) and the rectification electrode is 10 - 12mm forward of the burner.

2.7.6.4. Fan/Limit Thermostat

Thermostat settings:-Fan Off: 86°F/30°C Fan On: 122°F/50°C Limit: VPC 30, 52 212°F/100°C VPC 80, 110,130 230°F/110°C

1. Undo cover retaining screw

2. Squeeze the sides of the cover and remove cover by pulling forward.

3. Release wiring from clamp terminals by pushing a small screwdriver into the clamp release holes adjacent to the clamps.

4. Remove the 2 screws securing the thermostat to the heater panel and withdraw thermostat.

5. Reassemble new unit in reverse order referring to the heater wiring diagram to ensure correct wiring as detailed in section 2.5.

Page 32: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 32 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Important: A replacement fan/limit thermostat may have a brass link between the terminals. This MUST be removed, before the replacement thermostat is installed.

CA

UT

IO

N

DO N

OT RO

TAT E -

HOLD

DIAL W

HEN S

ETTIN

G POIN

TER

50 100 150 2

00

250

F A N L

IMIT

O F F O N

OF

F

Fan Circuit OUT

Fan Circuit IN

Brass Link Location

Limit Circuit OUT

Limit Circuit IN

Mechanical Limiter

Limit Set Point

Adjuster

Fan ON Override

Fan ON Set Point Adjuster

Fan OFF Set Point Adjuster

Set Point DialMechanical Limiter

Release Point

Thermostat Fan / Limit – Honeywell L4064B NOTE: Temperature points on the dial are in Fahrenheit

2.7.6.5. Exhaust Fan

1. Remove the flexi flue from the flue outlet socket.

2. Disconnect the fan electrical connections from the main terminal strip

3. Remove the screws securing the fan mounting box to the exhaust header plate.4. Remove fan assembly.

5. If needed, transfer the fan mounting box to the replacement fan.

6. Fit replacement exhaust fan, using new gaskets and silicon sealant as necessary, and reassemble in reverse order.

7. Replace the flexi flue

2.7.6.6. Air Pressure Switch

1. Remove the two screws securing the cover and remove cover.

2. Disconnect electrical connections.

3. Pull off the sensing tube from the air pressure switch.

4. Note the setting of the old pressure switch.

5. Remove the screws fixing the air pressure switch and remove switch.

6. Fit replacement in reverse order refitting the sensing tube to the negative (- or L) tapping on the pressure switch. Adjust setting to that of the old pressure switch.

2.7.6.7. Control Box

1. Unplug all the electrical connections.

2. Remove the two screws that secure the control box in place.

3. Fit replacement in reverse order.

2.7.6.8. Centrifugal Fan/Motor

1. Disconnect the electrical connections to the centrifugal fan section.

2. Remove the lower and top side panels of the unit for access to the fan and motor.

3. Remove the screws securing the fan to the fan shroud and slide fan out. Note that the fans on the VPC110 and 135 are removed through the rear of the heater.

4. Fit replacements as appropriate and reassemble in reverse order.

Note: If a 3ph motor is being replaced ensure that the direction of rotation is correct. If it is not interchange any two of the three phases connected to the motor.

Page 33: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 33 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Note: APS = Air Pressure Switch

Check Fuse ‘L’

Gas & Electrical supplies present at heater? No Turn supplies on, Check fuses/connections

230V Between 1 & 2 on Brahma control?

Limit thermostat tripped (red lamp on front panel on)?

Check fuse on Brahma control

Press reset switch on front panel when unit is coolIf it will not reset when cold - check/change thermostat, check limit interlock relay operation

Yes

No

Unit at lockout (lockout lamp on low level controls and on internal control panel alight)?

No

Check for 230V at terminal 19

Yes

Replace (3.15A), ascertain cause of failure and rectify

Replace (4A), ascertain cause and rectify

Failed

Failed

Check for faulty connection. Replace as necessary.

Yes

START

OK

OK

Yes

Yes

No Check APS sensing tube. Check negative pressure developed by exhaust fan. Adjust APS set point. Change APS

Yes

Yes

Ignition sparks? Check/replace ignition probe/lead. Faulty Brahma control box

Yes

Burners light? Check ignition electrode position. Is gas pipe work purged of air? Check gas pressures. Replace gas valve

4 more ignition attempts then lock out.

Exhaust fan continues to run APS has lost C. to N.O. continuity, slightly reduce APS set point.

Check for 230V between terminals 7 & 15 of the terminal strip Absent

Replace motor, capacitor or fan/motor assembly

Check connections, overloads etc as applicable Absent

Finish

Burners remain alight?

Check for 230V between terminals12 & 11 of the terminal strip

Check connections, Faulty Brahma Control

Yes

230V at APS Terminal C ?

Present

230V at APS Terminal N.O ?

No

Check for 230V between terminals 13 & 14of the terminal strip Check connections, Faulty Brahma ControlNo

Faulty Gas ValveYesNo

No

No

NoMain fan runs?

Main fan running - wait for unit temperature to reduce - Press reset switch on front panel. If it will not reset when cold - change thermostat, check limit interlock relay operation

Check for 230V at terminal 1 of terminal strip Absent

Absent

Absent

Absent

Absent

External control circuit not calling for heat

Press lockout reset button on low level controls or on internal control panel

Continuity between APS C and NO connections - check for reason, adjust APS setting or change APS. Faulty Brahma control or connections.

Check connections, Faulty exhaust fan and/or capacitor

Yes

Yes

Yes

Exhaust fan runs? No

Yes

Yes

Gas valve opens?

Depending on fan /motor type - Check for 230V at the main fan motor

Check connections. Fan/limit thermostat faulty - check/replace

Present

Present

3.1 Fault Finding

Page 34: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 34 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Item Description Usage Part No.

Gas Valve VR4605AB 30-80 145035204/KIT

Gas Valve V425AB 110, 130 141378715/KIT

Ignition Electrode30-80110, 130

142423002142400004

Rectification (Flame Sensor) Probe All 142423003

Burner30-80110, 130

142400240142400241

Fan & Limit Thermostat L4064 All 143000306

Control Box (Sequence Controller) All 145030844

Hi/Lo Governor Head 30-130 -/HL 142466402

Modulation Governor Head 30-130 -/MOD 142466403

Modulation Driver (GM44) 30-130 -/MOD 142400303

Limit Interlock P.C.B. MkIII All 142403600/3

3.2 List of Parts

Page 35: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 35 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

'JOX' 230V Relay All 143000816

Pressure Switch Dungs LGW All 146522174

Exhaust Fan 30/52 VP3052EXH

Exhaust Fan 80 - 130 VP80130EXH

Main Centrifugal Blower

305280110/130

1402CFAN280/T/151402CFAN210/T/151402CFAN580/T/151402CFAN240/T/2DECK

Contactor30/5280/110/130

143000601143000600

Overload

30/5280/1101301P1303P

143000801143000801142000800142000802

Motor

110 1p110 3P130 1P130 3P

140001908140001915140001998140002000

Motor Pulley110130

142000602142000601

Motor Taperlock110130

142003350142161028

Fan Pulley110 1P110 3P130

142001689142001619142001675

Fan Taperlock ALL 142003370

Belts110130

142109801142110507

Page 36: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 36 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

3.3 Gas ConversionGas Safety (Installation & Use) (Amendment) Regulations

It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the current issue of the

above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with. * An approved class of person listed on the gas safe register.

3.3.1. GeneralHeater conversion between gases will require a change of burner injectors, alteration of burner pressure and re-commissioning of the heater. (Refer to section 2.6 for commissioning details.)

Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas. (Refer to tables opposite for new gas inlet pressures.)

3.3.2. Burner Conversion

1. Ensure that the gas service valve is turned OFF.2. Remove the burner heat shield, 3 screws.3. Release the outlet connection flange from the gas valve by removing the four screws.4. Remove the manifold by removing the four screws securing it to the burner assembly.5. Remove the main burner injectors and washers.6. Replace with the new injectors/washers for the new gas ensuring a gas tight seal.7. Refit all other components in reverse order.

3.3.3. Gas ValvesAll gas valves used on the VPC range have pressure regulators that may be set to operate on natural gas or propane (LPG).

Conversion is carried out by adjusting the high and low burner pressures to the value in the tables opposite.(Refer to full regulator adjustment in section 2.6.5.1)

Note*: Ensure the original data badge is removed and replaced with new data badge and "change of gas" stickers.

3.3.3.1. Sigma 843 Adjustment

Adjustment nut (10mm) for maximum pressure setting

Cap

Adjustment screw for minimum pressure setting

3.3.3.2. Honeywell High/Low Adjustment

CoverLever point

Hexagonal adjustment screw for maximum pressure setting

Internal slotted adjustment screw for minimum pressure setting

3.3.3.3. Honeywell Modulating Adjustment

‘O’ ring

Adjustment nut (9mm)for minimum pressure setting

Adjustment nut (7mm)for maximum pressure setting

Cap

Shaft

6.3mm AMP terminals

Page 37: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 37 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Natural Gas to Propane (LPG) Conversion Data

Nominal Inlet Pressure = 37mbar, Minimum Inlet Pressure = 37mbar High Fire Low Fire

Injectors Burner Pressure

Burner Pressure

MODEL Conversion Kit part number No. Size (mm) Marked Injector part

number mbar mbar

VPC30 VPC30LPG 6 1.36 136 142401661 21.7 7.0

VPC52 VPC52LPG 12 1.25 125 142401675 27.0 8.0

VPC80 VPC80LPG 12 1.55 155 142401675 24.1 6.0

VPC110 VPC110LPG 10 1.94 194 142401664 26.5 7.0

VPC130 VPC130LPG 12 1.94 194 142401664 25.0 7.9

Propane (LPG) to Natural Gas Conversion Data

Nominal Inlet Pressure = 20mbar, Minimum Inlet Pressure = 17.5mbar High Fire Low Fire

Injectors Burner Pressure

Burner Pressure

MODEL Conversion Kit part number No. Size (mm) Marked Injector part

number mbar mbar

VPC30 VPC30NG 6 1.94 194 142401664 13.8 4.6

VPC52 VPC52NG 12 1.94 194 142401664 10.4 3.0

VPC80 VPC80NG 12 2.54 254 142401665 8.1 2.1

VPC110 VPC110NG 10 3.00 300 142401670 10.2 3.2

VPC130 VPC130NG 12 3.00 300 142401670 10.0 3.6

Page 38: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 38 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Appendices

Model 30 52 80 110 130

Rated Heat Capacity kW 30.4 52.7 80.0 11.4 139.7

Low Heat Input Nett CV kW 18.9 30.0 41.6 62.2 81.2

Minimum Heat Capacity kW 16.6 26.4 36.9 55.9 72.4

Useful EfficiencyHigh Fire % 92% 92% 92% 93% 93%

Low Fire % 88% 88% 89% 90% 89%

Electrical Power Consumption*

High Fire kW 0.05 0.05 0.05 0.05 0.05

Low Fire kW 0.05 0.05 0.05 0.05 0.05

Standby kW <0.01 <0.01 <0.01 <0.01 <0.01

Ignition kW 0.00 0.00 0.00 0.00 0.00

NOx Seasonal (Gross) mg/kWh 132.4 115.5 128.8 139.9 139.7

Envelope Loss Factor % n/a n/a n/a n/a n/a

Emission Effiency % hs, flow 94.8% 94.8% 95.0% 94.2% 93.9%

Seasonal Space Heating Energy Efficiency % hs,h 72.02% 72.08% 73.56% 72.58% 72.89%

Information required for ecodesign (ErP) Directive 2009/125

Page 39: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 39 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

Notes

Page 40: VPC Gas Cabinet Heater Range - powrmatic.co.uk · Appliance Categories are Cat II2H3P (GB, IE). ... VPC heaters feature a closed combustion circuit and have an internal exhaust fan,

page no. 40 of 40 VPC Range Users, Installation & Servicing Instructions Doc Ref M202 issue 5.4 May 2018.

HEATING DIVISIONHort Bridge

Ilminster, Somerset TA19 9PSTel: 01460 53535Fax: 01460 52341

Every effort is made to ensure accuracy at time of going to press. However as part of continued product improvement, we reserve the right to alter specification without prior notice.

More information is available from our web site on:-

http://www.powrmatic.co.uk/products/heating/browse/view/product/vpc-gas-cabinet-heaters-2/