Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 1 03.31.16
ViveT Maestro Wireless® Dimmers and SwitchesThe Maestro Wireless® solution incorporates Maestro Wireless® load controls, wireless sensors, and wireless remote controls, which provide a system that delivers energy savings, convenience, and ease of installation.Maestro Wireless® dimmers and switches use Lutron® patented Clear Connect® RF Technology, which enables wireless communication with Radio Powr SavrTM sensors and Pico® remote controls for light control and general switched loads.
These products are also compatible with the ViveTM hub which enables a simple setup process using a standard web browser on any Wi-Fi enabled phone, tablet or computer. It also enables control and monitoring of all ViveTM devices. The ViveTM hub can be added at any time and preserves existing system setup by extracting local programming from each device. For a complete list of features supported with the ViveTM hub, see specification submittal 369902. Note for Replacement: MRF2S - the “S” model can replace the non-”S” model.
Features• TheMaestroWireless® solution provides dimming/
switching of multiple load types, occupancy/vacancy sensing, daylight harvesting, and high-end trim.
• Lutron® patented Clear Connect® RF Technology works through walls and floors.
• IncorporatesadvancedfeaturessuchasfadeON / fade OFF, high-end trim, and rapid full-ON.
• ControlsincludeFrontAccessibleServiceSwitch(FASSTM) for safe lamp replacement.
• Two-wiredimmersandswitchesavailableforretrofitapplications.
• Powerfailurememory:Ifpowerisinterrupted,thecontrol will return to its previously set level prior to interruption.
Receiving DevicesMaestro Wireless® Controls
Neutral and Non-Neutral Dimmers
Neutral and Non-Neutral Switches
Transmitting DevicesRadio Powr SavrTM Sensors
Pico® Remote Controls
Ceiling-Mounted Occupancy and Vacancy Sensors
Wall-Mounted Occupancy and Vacancy Sensors
Daylight Sensors
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 2 03.31.16
Maestro Wireless® Dimmers
Models AvailableDimmersCFL / LED/Halogen / Incandescent / Magnetic Low-VoltageMRF2S-6CL-XX 1 150 W CFL / LED Dimmer; 600W/600VAIncandescent/MLVDimmer120V~
Electronic Low Voltage DimmerMRF2S-6ELV120-XX1 600 W ELV Dimmer 120 V~ (neutral required)
Companion DimmersClaro® Gloss FinishesMA-R-XX1,2 Companion Dimmer 120 V~
MA-R-277-XX1,2 CompanionDimmer277V~
Satin Colors® Satin FinishesMSC-AD-XX1 Companion Dimmer 120 V~
MSC-AD-277-XX1 CompanionDimmer277V~
1 “XX” in the model number represents color / finish code. See Colors and Finishes at end of document.2 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
Dimmer
Companion Dimmer
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 3 03.31.16
Ganging and DeratingWhen combining controls in the same wallbox, derating is required (see Load Type and Capacity tables). Dimmer Load Type and Capacity
No Neutral RequiredA B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6CL 1,2 120 V~CFL / LED, Incandescent 50 W (see lamp list) See Mixing Lamp Types, page 4MLV 2 50W/VA 450W/600VA 400W/500VA 300W/400VA
Note: do not mix ELV and MLV load types on a single control.1 DimmerLoadType:
• MRF2S-6CLisdesignedforusewithpermanently-installedincandescent,CFL,LED,ortungstenhalogenonly.2 Low-VoltageApplications:
• UseMRF2S-6CLwithmagnetic(coreandcoil)low-voltagetransformersonly.Notforusewithelectronic(solid-state)low-voltagetransformers.
Mixing Lamp TypesMixing lamp types (using a combination of CFL / LED, and Incandescent / Halogen bulbs) and ganging with other dimmers or electronic switches may reduce maximum wattage, as shown.Example:Iffinsfromonesideofdimmer are removed and you have two 24 W bulbs installed (total CFL Wattage = 48 W), you may add up to 300 W of incandescent or halogen lighting.
Do not remove outside fins on ends of ganged controls (shaded areas below)
A B B B C B
Total CFL/LED WattageTotal Incandescent/Halogen Wattage
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6CL0 W + 50 W – 600 W Or 50 W – 500 W Or 50 W – 400 W1 W – 25 W + 0 W – 500 W Or 0 W – 400 W Or 0 W – 300 W26 W – 50 W + 0 W – 400 W Or 0 W – 300 W Or 0 W – 200 W51W–75W + 0 W – 300 W Or 0 W – 200 W Or 0 W – 100 W76W–100W + 0 W – 200 W Or 0 W – 100 W Or 0 W – 50 W101 W – 125 W + 0 W – 100 W Or 0 W – 50 W Or 0 W126 W – 150 W + 0 W Or 0 W Or 0 W
Maximum LoadTotal MLV Wattage 450W/600VA 400W/500VA 300W/400VA
Example If a dimmer is installed in location “B” above and there are two 24 W CFL bulbs installed (Total CFL Wattage = 48 W), you may add up to 300 W of incandescent or halogen lighting.
Neutral RequiredA B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6ELV 120 V~ ELV 5 W 600 W 500 W 400 W
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 4 03.31.16
Maestro Wireless® Switches
Models AvailableSwitchesLighting and motor loadsMRF2S-6ANS-XX1,2,4 6ALighting/3AFan(1/10HPmotor), Electronic Switch 120 V~
MRF2S-8ANS120-XX1,2,4 8ALighting,5.8AFan(1/4HPmotor),Spec-Grade Electronic Switch 120 V~
MRF2S-8S-DV-XX 2,3,4 8ALighting,3AFan(1/10HPmotor,120V~ only), Spec-GradeElectronicSwitch120–277V~, no neutral wire required
Companion SwitchesClaro® Gloss FinishesMA-AS-XX2,4 Companion Switch 120 V~
MA-AS-277-XX2,4 CompanionSwitch277V~
Satin Colors® Satin FinishesMSC-AS-XX4 Companion Switch 120 V~
MSC-AS-277-XX4 CompanionSwitch277V~
1 Neutral wire required.
2 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
3 MayrequireLUT-MLC(includedwithMRF2S-8S-DVmodels)toensureproperfunctionwithlow-wattageloadtypes. See page 12 for details.
4 “XX” in the model number represents color / finish code. See Colors and Finishes at end of document.
Switch
Companion Switch
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 5 03.31.16
Switch Load Type and Capacity
No Neutral RequiredA B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-8S-DV 1,5
120–277V~ Incandescent/Halogen 25 W 8A 8A/7A4 7A120–277V~ Fluorescent/LED/CFL 40W(LUT-MLC)3 8A 8A/7A4 7A120 V~ Fan Motor 0.4A 1/10HP(3A) 1/10HP(3A) 1/10HP(3A)
1 SwitchLoadType:• MRF2S-8ANS120isdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/4HP(5.8A).
• MRF2S-8S-DVisdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/10HP(3A,120V~ only).
• MRF2-6ANSisdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/10HP(3A).
2 Forloadslargerthan8A(120V~),theMRF2S-8ANS120switchcanbeusedwiththePHPM-SW-DV-WHpowerbooster.
3 TheLUT-MLCensuresproperfunctionwithlow-wattagefluorescent,CFL,andLEDloadtypes.See page 12 for details.
4 Maximumloadfordouble-gangapplicationis8A.Triple-gangapplicationderatesmaximumloadto7A.
5 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
Neutral Required
Do not remove outside fins on ends of ganged controls (shaded areas below)
A B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-8ANS1201,2,5 120 V~Lighting 25 W 8A 6.5A 5AFan Motor 0.2A 1/4HP(5.8A) 1/4HP(5.8A) 1/6HP(4.4A)
MRF2-6ANS1 120 V~Lighting 25 W 6A 5A 3.5AFan Motor 0.2A 1/10HP(3A) 1/10HP(3A) 1/10HP(3A)
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 6 03.31.16
SpecificationsRegulatory Approvals
• UL® Listed.• cUL® Listed (MRF2S-6CL only).• CSACertified(exceptforMRF2S-6CL).• FCCApproved.ComplieswiththelimitsforaClassB
digital device, pursuant to Part 15 of the FCC Rules.• IndustryCanadaCertified.• Thefollowingmodelnumbershavebeentestedand
foundcompliantwithUL2043foruseinairhandlingspaces:MRF2S-6CL-GR
PowerOperatingvoltage:
• 120V~ 50/60 Hz (all models)• 277V~ 50/60 Hz (MRF2S-8S-DV)
Environment• Ambientoperatingtemperature:32°Fto104°F
(0 °Cto40°C)• 0%to90%humidity,non-condensing.• Indooruseonly.
Key Design FeaturesDimmers
• Onasingle-tap,lightsfadeUPorDOWN.• Onadouble-tap,lightsgotofullON.• WhenON,pressandholdtoengage20-secondfade
to OFF.• Lightlevelscanbefine-tunedbypressingand
holding the dimming rocker until the desired light level is reached.
• Two-wiredimmersavailable.
Switches• Onasingle-tap,lightsturnONorOFF.• Two-wireswitchesavailable.
All RF Local Controls• Testedtowithstandelectrostaticdischargewithout
damage or memory loss, in accordance with IEC 61000-4-2.
• Testedtowithstandsurgevoltageswithout damage or loss of operation, in accordance with IEEE C62.41-1991 Recommended Practice on SurgeVoltagesinLow-VoltageACPowerCircuits.
• Controlsalwaysoperatelocallyanddonotrequiresystem control.
• Powerfailurememory:shouldpowerbeinterrupted,the control will return to its previously-set level prior to the interruption when power is restored.
• Usesconventional3-wayand4-waywiring.• MultiplelocationcontrolfromDimmer/Switchandup
to nine Companion Dimmers / Switches.• UseLutron® Designer (Claro® and Satin Colors®)
wallplates or designer-style wallplates from other manufacturers. Wallplates are sold separately.
• Lutron® Claro® and Satin Colors® wallplates snap on with no visible means of attachment.
• Requiresaone-gangU.S.wallbox;31⁄2 in (89 mm) deep recommended, 21⁄4in(57mm)deepminimum.
• Greenindicatorlights.
System Communications and Capacity• MaestroWireless® controls communicate with the
Pico® remote controls and Radio Power SavrTM sensors through radio frequency (RF).
•Receiveswirelessinputsfromupto10Pico® remote controls, 10 Radio Powr SavrTM occupancy / vacancy sensors, and 1 Radio Powr SavrTM daylight sensor
• MaestroWireless® local controls must be located within 60 ft (18 m) line-of-sight or 30 ft (9 m) through walls, of Radio Power SavrTM sensors.
• MaestroWireless® local controls must be located within 60 ft (18 m) line-of-sight or 30 ft (9 m) through walls, of a Pico® remote control.
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c703.31.16
WallplateAdapter/Wallplatepurchasedseparately
WallplateAdapter Wallplate
Wallbox
Control
AdapterMountingScrews
Control Mounting Screws
Mounting
DimensionsAlldimensionsareshownas:in(mm)
Side View
5/16(8)
1 1⁄8(30)
Front View
4 11⁄16(119)
2 15⁄16(75)
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 8 03.31.16
Operation
Status LEDsIndicate light level; glow softly as night light when light is OFF
Dimming RockerPress to brightenPress to dim
TapswitchTap ON / OFF;Double-tap:lightsgotofullON
FASSTM
FrontAccessibleServiceSwitchFASSTM
FrontAccessibleServiceSwitch
FASSTM Front Accessible Service SwitchImportant Notice: To service load, removepowerbypullingtheFASSTM out completely on either the Dimmer / Switch orCompanionDimmer/Switch.Afterservicingload,pushtheFASSTM back in fully to restore power to the control.
Dimmer
TapswitchTap ON / OFF
SwitchStatus LEDIndicates load status; glows softly as night light when light is OFF
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 9 03.31.16
1 When using controls in single location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
2 UptonineMaestro® Companion Dimmers may be connected to the Maestro Wireless®Dimmer.Totalblueterminalwirelengthmaybeupto250ft(76m).
Wiring DiagramsSingle-Location Dimmer Installation without NeutralMRF2S-6CL
Dimmer
Load
Brass
Black
Line / Hot
Green
Blue 1
Ground
Neutral
120 V~ 60 Hz
Multi-Location Dimmer Installation without Neutral 2MRF2S-6CLwithMA-R/MSC-AD
Companion Dimmer Companion Dimmer Dimmer
BrassBrassBrass
BlackBlackBlack
Line / Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~ 60 Hz Load
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 10 03.31.16
1 When using controls in single location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
2 UptonineMaestro® Companion Dimmers / Switches may be connected to the Maestro Wireless® Dimmer / Switch. Total blue terminal wire length may be up to250ft(76m).
3 Neutral-wire Dimmers / Switches must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Multi-Location Switch Installation with Neutral 2,3
MRF2S-6ELV120,-8ANS120,and-6ANSwithMA-AS/MSC-AS
Companion Dimmer / Switch
Companion Dimmer / Switch Dimmer / Switch
Brass
Silver
BrassBrass
BlackBlackBlack
Line / Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~ 60 Hz Load
Single-Location Switch Installation with NeutralMRF2S-6ELV120,-8ANS120,and-6ANS
Dimmer/Switch
Load
Brass
Black
Silver
Line / Hot
Green
Blue 1
Ground
Neutral
120 V~ 60 Hz
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 11 03.31.16
1 ALUT-MLCensuresproperfunctionwhenfluorescent,CFL,orLEDloadsareused.InstalltheLUT-MLCinsidealoadfixtureorinaseparateJ-boxwithinthecircuit.
2 When using controls in single-location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
3 UptonineMaestro® Companion Switches may be connected to the Maestro Wireless®Switch.Totalblueterminalwirelengthmaybeupto250ft(76m).4 RequiresMA-AS/MSC-ASfor120V~applications,andMA-AS-277/MSC-AS-277for277V~ applications.
Single-Location Switch Installation with LUT-MLC 1MRF2S-8S-DV
Switch
Load LUT-MLC1
Brass
Black
Line / Hot
Green
Optional *
Blue 2
Ground
Neutral
120 V~ 60 Hz or 277V~ 60 Hz
Multi-Location Switch Installation with LUT-MLC 1,2,3
MRF2S-8S-DVwithMA-AS/MA-AS-277orMSC-AS/MSC-AS-2774
Companion Switch Companion Switch Switch
BrassBrassBrass
BlackBlackBlack
Line / Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~ 60 Hz or 277V~ 60 Hz
Load LUT-MLC1
Optional *
Wiring Diagrams (continued)
* Optional Procedure: UsingLUT-MLCwithMRF2S-8S-DV-XX
•InstallMRF2S-8S-DV-XXfirstwithoutLUT-MLCtoseeif required. Check for problems with load.
•Problemscanoccurwhenlow-wattageloadsareused (< 40 W).
•WatchforflickeringloadswhendimmerisinelectronicOFF state.
•Ifrequired,LUT-MLCcanbeinstalledbetweenswitched hot and neutral in wallbox if neutral is present, or in any fixture on the switched circuit.
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 12 03.31.16
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestro® Companion Switches may be connected to the Maestro Wireless®Switch.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Switches must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Single FeedMRF2S-8ANS120and-6ANSwithPHPM-SW-DV-WH
Switch
Brass Blue 1
Zone In
Black
Silver
Line / Hot
Switched Line / Hot
Line / Hot
NeutralNeutral
Neutral
Ground
Ground
Green
120 V~ 60 Hz
Load
Multi-Location Switch Installation with Power Booster Single Feed 2,3
MRF2S-8ANS120and-6ANSwithMA-AS/MSC-ASandPHPM-SW-DV-WH
Companion Switch Switch
Brass BlueBlue
Zone In
Black
Silver
Line / Hot
Switched Line / Hot
Line / Hot
Brass
Black
NeutralNeutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~ 60 Hz
Load
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 13 03.31.16
Multi-Location Switch Installation with Power Booster Dual Feed 1,2
MRF2S-8ANS120and-6ANSwithMA-AS/MSC-ASandPHPM-SW-DV-WH
Companion Switch Switch
Brass BlueBlue
Zone In
Black
Silver
Line / Hot
Switched Line / Hot
Line / Hot
Brass
Black
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~ 60 Hz or 277V~ 60 Hz
120 V~ 60 Hz
Load
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Dual FeedMRF2S-8ANS120and-6ANSwithPHPM-SW-DV-WH
Switch
Brass Blue 1
Zone In
Black
Silver
Line / Hot
Switched Line / Hot
Line / Hot
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
120 V~ 60 Hz or 277V~ 60 Hz
120 V~ 60 Hz
Load
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestro® Companion Switches may be connected to the Maestro Wireless®Switch.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Switches must be connected on the Load side of a multi-location installation.
RF Local Controls
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
ViveTM Designer-style: Maestro®
369904c 14 03.31.16
Colors and Finishes
Gloss Finishes Satin Finishes
Metal Finish (wallplate only)
Stainless Steel SS
Taupe TP
Turquoise TQ
Plum PL
Merlot MR
Terracotta TC
Sienna SI
Midnight MN
Hot HT
Desert Stone DS
Eggshell ES
Biscuit BI
Snow SW
Palladium PD
Greenbriar GB
Bluestone BG
Mocha Stone MS
Goldstone GS
Stone ST
Limestone LS
White WH
Ivory IV
Almond AL
LightAlmond LA
Gray GR
Brown BR
Black BL
• Duetoprintinglimitations,colorsand finishes shown cannot be guaranteed to perfectly match actual product colors.
• Colorchipkeychainsareavailableformoreprecisecolormatching: GlossFinishes:DG-CK-1 SatinFinishes:SC-CK-1