64
28 CONDITIONS AND SPECIFIC ATIONS FOR ELECTRICAL WORKS 1. The electrical works shall be executed by the contractor himself if he registered in appropriate class for electrical works with CPWD / P & T / MES / Railways / State PWD / Public undertaking Banks etc. through subcontractor registered in appropriate class for electrical works with CPWD / P & T / MES / Railways / State PWD. 2. The work shall be carried out as per CPWD Specification 2007 Part- I (internal) & Part - II 2008 (external) both amended up to date. All the installation shall comply with the requirement of Indian electricity Rule 1956 amended up to date. If the specifications for any item is not available in the CPWD specifications cited above, relevant IS specifications shall be followed. In case ISI specifications are also not available, the decision of the Architect/Engineer-In-charge given in writing based on acceptable sound Architect/Engineering Practice and local usage shall be final and binding on the contractor. 3. All the material to be used on the work shall be of superior quality and shall have to be got approved from the Architect/Engineer-In-Charge before use at site. 4. The layout for running of the conduits, positions of switches fitting etc. shall have to be got approved from the Architect/Engineer-In-Charge before execution of the same. 5. Suitable size of TW block duly varnished shall be provided for Fl. fittings for which nothing extra shall be paid. 6. All the conduit to be laid shall be provided with fix wire or not less than 16 SWG for which nothing extra shall be paid.

Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

  • Upload
    hathu

  • View
    218

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

28

CONDITIONS AND SPECIFIC ATIONS FOR ELECTRICAL WORKS

1. The electrical works shall be executed by the contractor himself if he registered in appropriate class for electrical works with CPWD / P & T / MES / Railways / State PWD / Public undertaking Banks etc. through subcontractor registered in appropriate class for electrical works with CPWD / P & T / MES / Railways / State PWD.

2. The work shall be carried out as per CPWD Specification 2007 Part- I (internal) & Part - II 2008 (external) both amended up to date. All the installation shall comply with the requirement of Indian electricity Rule 1956 amended up to date. If the specifications for any item is not available in the CPWD specifications cited above, relevant IS specifications shall be followed. In case ISI specifications are also not available, the decision of the Architect/Engineer-In-charge given in writing based on acceptable sound Architect/Engineering Practice and local usage shall be final and binding on the contractor.

3. All the material to be used on the work shall be of superior quality and shall have to be got approved from the Architect/Engineer-In-Charge before use at site.

4. The layout for running of the conduits, positions of switches fitting etc. shall have to be got approved from the Architect/Engineer-In-Charge before execution of the same.

5. Suitable size of TW block duly varnished shall be provided for Fl. fittings for which nothing extra shall be paid.

6. All the conduit to be laid shall be provided with fix wire or not less than 16 SWG for which nothing extra shall be paid.

7. All the switches to be provided for lighting/ fans/ light plug/ power plug/ call bell etc. shall be of modular type of superior quality.

8. The switchboards shall be provided with decorative sheet of approved colour and quality, which shall be got approved from the Architect/Engineer-In-charge before use at site.

9. The contractor shall make his own arrangement for the safe custody/ storage of his material. Breakage, damage if any done during the storage/ execution, the same shall be replaced/ rectified by the contractor at his own cost.

10. The contractor is bound to sign the entry/ entries made by the Engineer-In-Charge or his representative in the site order book time to time.

11. Good workmanship is an essential requirements for compliance with the rules & specifications.

Page 2: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

29

12. The entire installation shall be at the risk and responsibility of the contractor until these are tested and handed over to the HPCL.

13. Earthing loop earthing shall invariably be along as per CPWD specifications.

14. Notwithstanding the schedule of quantity. All items of inter-related work considered necessary to make installation complete and seperative deemed to be included shall be provided by the contractor at no extra cost.

15. Contractor has to supply the layout / circuit drawings of installation after the completion of work.

16. The cover of all junction boxes shall be of bakelite sheet.

17. The tenderer shall submit a sample board, in-corporating in it the samples of all electrical wires, conduits etc. proposed to be used for approval of Engineer-in-charge before commencement of work. No extra payment shall be given for the same.

18. The electrical works shall be executed in close co-ordination with the progress of Building work. This being absence of the contract, no claim for idles labour will be entertained.

19. Any damage caused to Building as a result of execution of electrical work shall be responsibility of the electrical contractor. The damage if so caused shall be made good by the contractor promptly at his own cost to the entire satisfaction of the Engineer-In-charge.

20. Embedding of earth electrode shall be done in the presence of Architect/Engineer-in-charge for his authorized representative.

21. The contractor shall submit the completion plan separately for each floor for one particular building only in triplicate on Blue print showing the route of sub-mains etc.

22. The Architect/Engineer-in-charge will be at liberty to get the work inspected through

the C.T.E. or any other agency appointed by the Govt. or Municipal Corporation and the result of their finding will be binding on the contractor.

23. Contractor shall not assign or sub-let the work without prior approval of Architect/Engineer-in-charge.

Page 3: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

30

24. The Contractor shall appoint an authorized agency of relevant manufacturer for carrying out the works for the Data and Voice Networking and get a Certification of the executed work and installation and get it tested to the satisfaction of Architect/Engineer-in-Charge/client .The authorization certificate from the relevant manufacturer whether the agency doing the work is their authorized agent/system integrator has to be submitted before starting of the work. shall be produced . Without the performance certificate from the company, the executed work shall be deemed as incomplete and shall not be accepted by the client and all payments made in this head be recovered in totality and no subsequent payments shall be made for that particular Head. The performance certificate should be for 8/10 years from the relevant manufacturer as applicable .

25. For UPS wiring also the contractor shall appoint system integrator.

26. For Addressable Fire Alarm System, the Contractor shall appoint an authorized agency of the relevant principal manufacturer for carrying out the work and get a Certification of the executed work and installation and get it tested to the satisfaction of Engineer-in-Charge/client .

27. The civil contractor / Electrical Contractor combined shall appoint an Electrical Engineer / Diploma Holder / Foreman of sufficient experience not less than 3 years for the works to be executed at site as per the IE rules.

28. The contractor shall submit a sample board, incorporating in it all the samples of the Electrical Works, ie., Wires, Conduits etc. proposed to be used for approval of Architect/Engineer- in –charge before commencement of work. No extra payment shall be given for the same.

Page 4: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

31

ADDITIONAL SPECIAL CONDITIONS OF CONTRACT :

1.. The contractor shall take responsibility of getting approval of Building Authorities / Estate Officer and other Authority as required for executing the work during and off the office timings.

2.. The contractor shall make his/ her own arrangements for distribution of water and electrical supply for executing the work. 6.1 Electrical : the single point of supply would be from existing load. 6.2 Water : the single point of would be existing fresh water inlet.

3. On partial completion of work the contractor shall be furnished with a certificate, but not such certificate be given nor shall the work be considered to complete until the contractor shall have removed from the area of the premises ( to be distinctly marked by the Architect/ Project Manager in the site plan which, the work shall be executed) all scaffoldings, surplus materials and rubbish and clean the dirt from all wood work, doors, windows, walls, floors or other parts of any building, in or upon which the work is to executed, or of which he may have had in possession for the purpose of the execution hereof. If the contractor shall fail to comply with the requirements of the clause as to the removal of scaffoldings, surplus materials and rubbish and cleaning off dirt on or before the date fixed for the completion of the work, the architect may at the expense of the contractor remove such scaffolding, surplus materials, and the contractor shall forthwith pay the amount of all expense so incurred, and shall have no claim in respect of any such scaffolding or surplus materials aforesaid, except for any actually realized by the sale thereof.

Page 5: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

32

SPECIFICATIONS FOR INTERNAL ELECTRICAL INSTALLATION

SECTION 1. GENERAL AND TECHNICAL

1. POINT WIRING

A point (other than a socket outlet point) shall include all work necessary in complete wiring to the following outlets from the controlling switch or MCB. The scope of wiring for a point shall however, include the wiring work necessary in tapping from another point in the same distribution circuit.

a] Ceiling rose or connector (in the case of points for ceiling / exhaust fan points, prewired light fittings, and call bells).

b] Ceiling rose (in the case of pendants except stiff pendants).

c] Back plate (in the case of stiff pendants).

d] Lamp holder (in the case of goose neck type wall brackets, batten holders and fitting which are not prewired).

Note:- In the case of call bell points the words "from the controlling swich board or MCB" shall be read as "from the ceiling rose meant for connection to bell push".

1.1 Scope

a] Any special block required for neatly housing the connector in batten wiring system.

b] Control switch or MCB, as specified.

c] 3 pin or 6 pin socket, ceiling rose or connector as required. (2 pin and 5 pin socket outlet shall not be permitted)

d] Connection to ceiling rose, connector, socket outlet, lamp holder, switch etc.

1.2 Point wiring for socket outlet points

a] The light plug (5A / 6A) point and power (15A / 16A) point wiring shall be measured on linear basis, from the respective tapping points namely, switch box, another socket outlet point, or the sub distribution board as the case may be upto the socket outlet.

Page 6: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

33

b] The metal / PVC box with cover, switch / MCB, socket outlet and other accessories shall be measured and paid as separate item.

Note:- There shall normally be no "on the board" light plug point.

c] The power point outlet may 15A/ 5A or 16A/ 6A six pin socket outlet, where so specified in the tender documents.

1.3 Twin control light points wiring

a] A light point controlled by two numbers of two way switches shall be measured as two points from the fitting to the switches on either side.

b] No recovery shall be made for non-provision of more than one ceiling rose or connector in such cases.

1.4 Multiple controlled call bell points wiring

a] In the case of call bell points with a single call bell outlet, controlled from one more than one place, the points shall be measured in part i.e.(a) from one call bell outlet to one of the nearest ceiling rose meant for connection to bell push, treated as one point and classified from that ceiling rose to the next one and so on , shall be treated as separately point(s).

b] No recovery shall be made for non- provision of more than one ceiling rose or connector for connection to call bell in such cases.

2. CIRCUIT AND SUBMAIN WIRING

2.1 Circuit Wiring

Circuit wiring shall mean the wiring from the distribution board upto the tapping point for the nearest first point of that distribution circuit, viz. upto the nearest first switch box.

2.2 Submain wiring

Submain wiring shall mean the wiring from one main / distribution switchboard to another.

2.3 Measurement of circuit and submain wiring

a] circuit and submain wiring shall be measured on linear basis along the run of the wiring. The measurement shall include all lengths from end conduit as the case may,

Page 7: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

34

exclusive on interconnections inside the switch board etc. The increase on account of diversion or slackness shall not be included in the measurement.

b] The length of circuit wiring with two wires shall be measured from the distribution board to the first nearest switch box in the circuit irrespective of whether the neutral conductor is taken to switchbox or not.

c] When circuit wires and wires of point wiring are run in same conduit/ circuit wiring shall be measured on linear basis depending on the actual number and sizes of wires run in the existing conduit.

d] Protective (loop earthing) conductors which are run along the cicuit wiring and the submain wiring shall be measured on linear basis and paid for separately.

3. SYSTEM OF DISTRIBUTION AND WIRING

3.1 Distribution

a] Main distribution board shall be controlled by a circuit breaker or linked switch with fuse. Each outgoing circuit shall be controlled by a switch with fuse, circuit breaker or only a fuse on the phase or live conductor.

b] The branch distribution board shall be controlled by a linked switch fuse or circuit breaker. Each outgoing circuit shall be provided with a fuse or miniature circuit breaker (MCB) of specified rating on the phase or live conductor.

c] Triple pole distribution boards shall not be used for final circuit distribution, unless specific approval of the Engineer-in-charge is obtained. In such special cases, the triple pole distribution boards shall be of HRC fuse type or MCB type only.

d] The loads of the circuits shall be divided, as far as possible , evenly between the number of ways of the distribution boards, leaving at least one spare circuit for future extension.

e] 'Power' wiring shall be kept separate and distinct from 'Lighting' wiring, from the level of circuits i.e. beyond the branch distribution boards.

3.2 Wiring system

a] Unless and otherwise specified in the tender documents, wiring shall be done only by the "Looping system". Phase or live conductors shall be looped at the switch boxes and neutral conductors at the point outlets.

b] Lights, fans and call bells shall be wired in the 'lighting' circuits. 15A/ 16A socket outlets and other power outlets shall be wired in the 'Power' circuits. 5A/ 6A socket

Page 8: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

35

outlets shall be wired in the 'lighting' circuits in non residential buildings and in the 'power' circuit in residential buildings.

3.3 Passing through walls or floors a] Where a wall pipe passes outside a building so as to be exposed to weather, the outer

end shall be mounthed and turned downwards and properly bused on the open end.

3.4 Joints in wiring a] There shall be no joints in the through-runs of cables. If the length of final circuit or

sub-main is more than the length of a standard coil, thus necessiting a through joint, such joints shall be made by means of approved mechanical connectors in suitable junction boxes.

b] Termination of multi-stranded conductors shall be done using suitable crimping type

thimbles.

4. RATING OF OUTLETS (TO BE ADOPTED FOR DESIGN)

a] Ceiling fans shall be rated at 60 W. Exhaust fan, fluorescent tubes, compact fluorescent tubes, HPMV lamps, HPSV lamps etc. shall be rated according to their capacity. Control gear losses shall be also considered as applicable.

b] 5A / 6A and 15A / 16A socket outlet points shall be related at 100W and 1000W respectively, unless the actual values of loads are specified.

5. CAPACITY OF CIRCUITS :

a] "Lighting" circuit shall not have more than a total of 10 points of light, fan and socket outlets, or a total connected load of 800W, whichever is less.

b] "Power" circuit shall be designed with only one outlet per circuit in nonresidential

buildings. The circuit shall be designed based on the load. Where not specified, the load shall be taken as 1 KW per outlet.

c] "Power" circuit in residential buildings shall be designed for not more than two outlets

(15A/ 16A and / or 5A/ 6A) per circuit. The ratings for load calculation purposed shall

however be taken as per the type of outlets.

d] Load more than 1 KW shall be controlled by an isolator or miniature circuit breaker.

Page 9: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

36

6. WIRING ACCESSORIES

6.1 Control switches for points

a] All the Switches, Sockets, TV socket and Computer Socket shall be modular type.

b] Power (15A/ 16A) outlets shall be controlled by single pole modular type switches or by MCB's, where specified. Only MCB's shall be used for controlling industrial type socket outlets, and power outlets above 1 KW.

6.2 Socket outlets

a] Socket outlets shall be of the same type, namely modular type, as their control switches. These shall be rated either for 5A/ 6A, or 15A/16A. Combined 5A/ 15A, or 6A/ 16A six pin socket outlet may be provided in 'power circuits only where specified.

b] Outlet boxes for socket outlets (both 15A/ 16A ands 5A/ 6A) points in residential buildings.

7. FITTINGS

7.1 Indoor type fittings

a] Fittings using discharge lamps shall be complete with power factor correction capacitors, either integrally or externally. An earth terminal with suitable marking shall be provided for each fitting for discharge lamps.

b] Fittings shall be installed such that the lamp is at a height of 2.5m above floor level, unless otherwise directed by the Engineer-in-charge.

7.2 Bulk head fittings

Bulk head fittings shall be of cast iron / cast aluminium body, suitably painted white inside and gray outside, complete with heat resistant glass cover, gasket, BC lamp holder for 100W incandescent lamp.

8. MCB TYPE DISTRIBUTION BOARD (MCBDB)

a] MCBDB's may be of single phase, 3 phase (horizontal type) suitable for feeding single phase loads, or 3 phase (vertical type) suitable for feeding single phase as well as 3 phase loads, as specified. These shall be complete with accessories, but without MCB's which shall be specified as a separate item in the tender documents.

Page 10: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

37

b] The current ratings and the number of ways shall be as specified. Blanking plates shall be provided to close unused ways. These shall be indicated as separate item in the Schedule of work.

9. PRE-WIRED MCB DISTRIBUTION BOARDS a] The board shall also be provided with a loose wire box as a compartment for the

complete width and , depth of the board, and of minimum height of 125mm in case of TPN DB's, and 100mm in case of SPN DB's.

b] The board shall be provided with a hinged cover of 1.6mm thick sheet steel in the front. Only the knobs of the MCB's shall protrude out of the front covers through openings neatly machine made for the purpose.

c] The board shall be complete with the following accessories:-

i) 200 A copper busbar (s). ii) Neutral link. iii) Common earth bar. iv) DIN bar for mounting MCB's. v) Elemex type terminal connectors suitable for incoming and outgoing cables. vi) A set of indication lamps with HRC cartridge fuses for each phase of the incoming

supply. vii) Earthing stud.(s)

Note:- MCB's and blanking plates shall be specified as separate items, as required.

10. SWITCH BOARD LOCATIONS

10.1 Cubicle type switchboards

Cubicle type switchboards shall be conform to section 4 of "General Specifications for Electrical Works (Part - IV - Substation), 1982".

11. SWITCH BOARD INSTALLATION

a] Unless and otherwise specified in the tender documents, a switchboard shall not be installed so that its bottom is within 1.25 m above the floor.

b] There shall be a clear distance of 1 m in front of the switch boards. The space behind the switchboards shall be either less than 20 cm or more than 75 cm. If there are any attachments or bare connections at the back of the switch board. Rule 51 (c) of the Indian Electricity Rules shall apply.

Page 11: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

38

c] Where it is required to terminate a number of conduits on a board. it may be convenient to provide a suitable MS adopter box for the purpose. Such boxes shall be provided with the prior approval of the Engineer-in-charge and this will be paid for separately.

d] No apparatus shall project beyond any edge of the panel. No fuse body shall be mounted within 2.5cm of any edge of the panel.

e] Busbars and interconnecting strips in fabricated boards shall be PVC tapped or sleeved in Red, Yellow and Blue for phases, and Black for neutral. The interconnecting cables shall also follow this colour coding.

12. ATTACHMENT OF FITTINGS AND ACCESSORIES

12.1 Conduit wiring system

a] All accessories like switches, socket outlets, call bell pushes and regulators shall be fixed in flush pattern inside the switch/ regulator boxes.

b] Aluminum alloy or cadmium plated iron screws shall be used to fix the accessories to their bases.

c] The switch box/ regulator box shall normally be mounted with their bottom 1.25cm from floor level, unless otherwise directed by the Engineer-in-charge.

13 FIXING TO WALLS AND CEILING

a] Wooden plugs for ordinary walls or ceiling shall not be used in view of the ban on use of timber in Govt. works. However, where so specified, these shall be of well seasoned teak or other approved hard wood not less than 5 cm long by 2.5cm square on the inner end, and 2cm square on the outer end. They shall be cemented into walls within 6.5mm of the surface, the remainder being finished according to the nature of the surface with plaster or lime punning.

b] PVC sleeves/ dash fasteners should normally be used for fixing to walls or ceiling.

M.S. CONDUIT WIRING SYSTEM

APPLICATION

a] Recessed conduit is suitable generally for all applications. Surface conduit work may be adopted in places like wiring above false ceiling / below false flooring, and at locations where recessed work may not be possible to be done. The type of work, viz. surface or recessed, shall be as specified in the respective works.

Page 12: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

39

b] Flexible conduits may only be permitted for interconnections between switchgear, DB's and conduit terminations in wall.

MATERIALS

Conduitssa] All rigid conduit pipes shall be of MS and ISI marked. The wall thickness shall not be

less than 1.6mm (16 SWG) for conduits up-to 32mm dia. and not less than 2mm ( 14 SWG ) for conduits above 32mm dia.

b] No MS conduit less than 20mm in diameter shall be used.

Conduit accessories

a] All conduit accessories shall be of solid type.

b] Saddles for surface conduit work on wall shall not be less than 0.55mm (24 gauge) for conduits upto 25mm dia. and not less than 0.9mm (20 gauge) for larger diameter. The corresponding widths shall be 19mm & 25mm.

Outlets

a] The switch box or regulator box shall be made of metal on all sides, except on the front. In the case of cast boxes, the wall thickness shall be at least 3mm and in case of welded mild steel sheet boxes, the wall thickness shall not be less than 1.2mm (18 gauge) for boxes upto a size of 20cm x 30cm, and above this size 1.6mm (16 gauge) thick MS boxes shall be used. The metallic boxes shall be duly painted with anticorrosive paint before erection as per chapter 10 of these specifications.

b] Outlet boxes shall be of one of the size, covered in the Schedule of Rates (Elect.), Part I- Internal.

c] Where a large number of control switches and/ or fan regulators are required to be installed at one place, these shall be installed in more than one outlet box adjacent to each other for ease of maintenance.

d] An earth terminal with stud and 2 metal washers shall be provided in each MS box for termination of protective conductors and for connection to socket outlet/ metallic body of fan regulator etc.

e] Clear depth of the box shall not be less than 50mm, and this shall be increased suitably to accordance mounting of fan regulators in flush pattern.

Page 13: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

40

INSTALLATION

Common aspects for recessed and surface conduit works.

a] Bends in conduit

i) All necessary bends in the system, including diversion, shall be done either by neatly bending the pipes without cracking with a bending radius, or alternatively, by inserting suitable solid type normal bends or similar fittings, whichever is most suitable.

ii) No length of conduit shall have more than the equivalent of four quarter bends from outlet to outlet.

Additional requirements for surface conduit work.

a] Fixing conduit on surface

i) Conduit pipes shall be fixed by saddles, secured to suitable approved plugs with screws in an approved manner at an interval of not more than one metre, but on either side of the couplers or bends or similar fittings, saddles shall be fixed at a distance of 30 cm from the centre of such fittings.

b] Fixing outlet boxes

i) Only a portion of the switch box shall be sunk in the wall, the other portion being projected out for suitable entry of conduit pipes into the box.

Additional requirements for recessed conduit work

a] Fixing conduits in chase

i) The conduit pipe shall be fixed by means of J-hooks, or by means of saddles, not more than 60 cm apart, or by any other approved means of fixing.

ii) All joints of conduit pipes shall be treated with some approved preservative compound to secure protection against rust.

b] Fixing conduits in RCC work

i) The conduit pipes shall be laid in position and fixed to the steel reinforcement bars by steel binding wires before the concreting is done. The conduit pipes shall be fixed firmly to

Page 14: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

41

the steel reinforcement bars to avoid their dislocation during pouring of cement concrete and subsequent tamping of the same.

ii) Fixing of standard bends or elbows shall be avoided as far as practicable, and all curves shall be maintained by bending the conduit pipe itself with a long radius which will permit easy drawing in of conductors.

c] Fixing inspection boxes

i) Suitable inspection boxes to the minimum requirement shall be provided to permit inspection, and to facilitate replacement of wires, if necessary.

ii) These shall be mounted flush with the wall or ceiling concrete. Minimum 65mm depth junction boxes shall be used on roofslabs and the depth of the boxes in other places shall be as per IS: 2667 - 1977.

d] Fixing switch boxes and accessories

i) Switch boxes shall be mounted flush with the wall. All outlets such as switches, socket outlets etc. shall be flush mounting type, unless otherwise specified in the Additional Specifications.

Page 15: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

42

e] Fish wire

i) To facilitate subsequent drawing of wires in the conduit, GI fish wire of 1.6mm / 1.2mm ( 16/ 18 SWG ) shall be provided along with the laying of the recessed conduit.

TABLE - IMaximum number of PVC insulated 650/ 1100 V grade aluminium / copper conductor

cable conforming to IS: 694/ 1990.Clause 2.2 a]

------------------------------------------------------------------------------------------------------------Nominal 20mm 25mm 32mm 38mm cross-sectionalarea ofconductorin sq.mm. S B S B S B S B ------------------------------------------------------------------------------------------------------------1 2 3 4 5 6 7 8 9 ------------------------------------------------------------------------------------------------------------

1.50 5 4 10 8 18 12 - -

2.50 5 3 8 6 12 10 - -

4 3 2 6 5 10 8 - -

6 2 - 5 4 8 7 - -

10 2 - 4 3 6 5 8 6

16 - - 2 2 3 3 6 5

25 - - - - 3 2 5 3

35 - - - - - - 3 2

50 - - - - - - - -

70 - - - - - - - -

Page 16: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

43

MEDIUM VOLTAGE DISTRIBUTION BOARDS FOR POWER AND LIGHTING DISTRIBUTION

General

Distribution board shall be suitable for 415 Volt, 3 phase AC supply or 230 volt single phase AC supply as required. Distribution boards shall generally conform to IS 2675 or BS 214. However, the specifications hereinafter described shall take precedence over the above wherever this specification call for a higher standard or material or workmanship.

Type and construction

Distribution boards shall be of totally enclosed dead front safety type. The enclosure be made of best quality sheet steel of not less than 14 gauge. The sheet steel shall be treated with a rigorous rust inhibited process before fabrication. The distribution boards shall comprise of MCB isolator or moulded case circuit breaker as incoming and required number of miniature circuit breaker as outgoings. The main and outgoings shall have rating as specified on the drawings and schedule.

Busbar

Suitable bus bars made of high conductivity copper strips and mounted on non-hygroscopic insulating supports shall be provided.

Circuit Breaker

Moulded case circuit breaker and miniature circuit breakers shall be of approved design and make. Circuit breakers shall be equipped with individually insulated, traced and protected connectors. The front face of all the breakers shall be flush with each other. Each breaker shall be provided with card holder and neatly printed card identifying the circuit. The position of handle of the breaker shall clearly indicate the condition of breakers such as "ON/OFF/TRIPPED".

Safety & Interlocks

All the live parts shall be shrouded such that accident contacts with live parts are totally avoided. Distribution board shall be provided with a front hinged door. Distribution board shall be provided with a front hinged door. Distribution board interior assembly shall be dead front with the front cover removed. Main lugs shall be shrouded on five sides. Suitable insulating barrier made of arc resistant material shall be provided for phase separation. Ends of the bus structures shall also be shrouded.

Page 17: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

44

Cabinet Design

The distribution board cabinet shall be totally enclosed type with dust and vermin proof construction. The cabinet shall be stove enamelled to grey shade finish. The interior surface shall be finished to an off-white shade. The interior components shall be mounted on a separate sheet steel which is mounted and locked on to the studs provided inside the cabinet. Over this, a cover made of hylam sheet or stove enamelled sheet steel shall be provided with slots for operating handles of breakers. The cabinet shall be provided with a front door having a spring latch and vault lock. Cabinets shall have detachable gland plates at both top and bottom.

Terminals

Distribution boards shall be provided with a terminal block of adequate size to receive mains and outgoings circuits. The location of the terminal block shall be so located that crowding of wires in the proximity of live parts is avoided. A neutral link having rating equal to that of phase bus shall be provided.

Directory

Distribution boards shall be provided with a directory indicating the area or loads served by each circuit breaker, the rating of breakers, size of conductors etc. The directory shall be mounted in metal holder with a clear plastic sheet on inside surface of the front door.

Installation

Distribution boards shall be surface mounted or recessed mounted as required by the Architects and at the locations shown on the drawings. The boards shall be fixed with suitable angle iron clamps and bolts. All the cables / conduits shall be properly terminated using glands / grips / check nuts etc. Wiring shall be terminated properly using crimping lugs / sockets and PVC identification ferrules. No bare conductor shall be allowed inside the boards. Distribution boards shall be bonded to the earth at least at two points using brass bolts and lugs. Suitable name plate, danger plate, indicating the voltage shall be fixed to the front cover.

Testing

Distribution board shall be tested at factory as per IS 2675 or BS 214. The tests shall include insulation test, high voltage test etc.

Distribution boards shall be tested for insulation resistance after the erection.

CUBICLE TYPE BOARDS

Cubicle type switch board shall be fabricated out of sheet steel not less than 2.0 mm thick. Wherever necessary, such sheet steel members shall be stiffened by angle iron frame work. General construction shall employ the principle of compartmentalisation and segregation for each circuit. Unless otherwise approved, incomer and bus section panels or sections shall be

Page 18: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

45

separate and independent and shall not be mixed with sections required for feeders. Each section of the rear accessible type board shall have hinged access doors at the rear. Overall height of the board shall not exceed 2.0 meters. Operating levers, handle etc, of highest unit shall not be at a height more then 1.7 m. Multi-tier mounting of feeders is permissible. The general arrangement for multi-tier construction shall be such that the horizontal tiers formed present a pleasing and aesthetic look. The general arrangement shall be got approved before fabrication. Cable entries for various feeders shall be either from the rear or from the front through cable alleys located in between two circuit sections. All cable entries shall be through gland plates. There shall be separate gland start plate for each cable entry so that there will not be dislocation of already wired circuit when new feeders are added. Cable entry plates shall therefore be sectionalised. The construction shall include necessary cable supports for clamping the cable in the cable alloy or rear cable chamber.

SWITCH BOARD INSTALLATION

a] Switchboard shall not be installed so that its bottom is within 1.25 m above the floor.

b] There shall be a clear distance of 1 m in front of the switch boards. The space behind the switchboards shall be either less than 20 cm or more than 75 cm. If there are any attachments or bare connections at the back of the switchboard. Rule 51 (c) of the Indian Electricity Rules shall apply.

c] Where it is required to terminate a number of conduits on a board. it may be convenient to provide a suitable MS adopter box for the purpose. Such boxes shall be provided with the prior approval of the Engineer-in-charge and this will be paid for separately.

d] No apparatus shall project beyond any edge of the panel. No fuse body shall be mounted within 2.5cm of any edge of the panel.

e] Busbars and interconnecting strips in fabricated boards shall be PVC tapped or sleeved in Red, Yellow and Blue for phases, and Black for neutral. The interconnecting cables shall also follow this color coding.

TESTING OF INSTALLATION GENERAL

Tests On completion of installation, the following tests shall be carried out:-

a] Insulation resistance test.b] Polarity test of switch.

Page 19: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

46

Witnessing of Tests Testing shall be carried out for the completed installations, in presence of and to the satisfaction of the Engineer-in-Charge by the contractor. All test result shall be recorded and submitted to the Department.

INSULATION RESISTANCE

The insulation resistance in mega ohms measured as above shall not be less than 12.5 mega ohms for the wiring PVC insulated cables, subject to a minimum of 1 mega ohm.

A preliminary and similar test may be made before the lamps etc. are installed, and in this event the insulation resistance to earth should not be less than 25 mega ohms for the wiring with PVC insulated cables, subject to a minimum of 2 mega ohms.

The term "outlet" includes every point along with every switch, except that a switch combined with a socket outlet, appliance or lighting fitting is regarded as one outlet.

Page 20: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

47

POLARITY TEST OF SWITCH The installation shall be connected to the supply for testing. The terminals of all switches shall be tested by a test lamp, one lead of which is connected to the earth. Glowing of test lamp to its full brilliance, when the switch is in "on" position irrespective of appliance in position or not, shall indicate that the switch is connected to the right polarity.

TABLE - 2

Aluminium / Copper busbar sections--------------------------------------------------------------------------------------------------------

Recommended rectangular cross-section------------------------------------------------------------------------------------------------------- Current Aluminium Copperratings in Amps. ---------------------------------------------------------------------------------- upto No.of strips/ Size No.of strips/ Size phase in mm. phase in mm.-------------------------------------------------------------------------------------------------------

100 1 20x5 1 20x3200 1 30x5 1 25x5300 1 50x5 1 40x5400 1 50x6 1 50x5500 1 75x6 1 60x6600 1 80x6800 1 100x61000 1 100x101200 1 125x101600 2 100x102000 2 125x102500 3 125x10-------------------------------------------------------------------------------------------------------

Page 21: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

48

EARTHING

INSTALLATION

a] Plate electrode shall be buried in ground with its faces vertical, and its top not less than 3 m below the ground level.

b] When more than one electrode (Plate/pipe) is to be installed, a separation of not less than 2 m shall be maintained between two adjacent electrode.

c] i) The strip or conductor electrode shall be buried in trench not less than 0.5m deep.

ii) If conditions necessitate the use of more than one strip or conductor electrode, they shall be laid as widely distributed as possible. In a single trench where feasible, or preferably in a number of trenches radiating from one point.

iii) If the electrode cannot be laid in a straight length, it may laid in a zig-zag manner with a deviation upto 45 degrees from the axis of the strip. It can also be laid in the form of an arc with curvature more than 1 m or a polygon.

Watering arrangement

a] In the case of plate earth electrodes, a watering pipe 20mm dia. medium class pipe shall be provided and attached to the electrodes.

b] In the case of pipe electrodes, a 40mm x 20mm reducer shall be used for fixing the funnel with mesh.

c] The watering funnel attachement shall be housed in a masonary enclosure of size not less than 30cm x 30cm x 30cm.

d] A cast iron/ MS cover, 6mm thick, and having locking arrangement shall be suitably embeded in masonary enclosure.

Earthing conductor (Main earthing lead)

a] In the case pf pipe earth electrode, wire type earthing conductor shall be secured , using a through bolts, nuts and washers and teminating socket.

b] The earthing conductor from the electrode up to the electrode upto the building shall be protected form mechanical injury by a medium class by 40mm dia, medium class GI pipe in the case of strip. The protection pipe in ground shall be buried at least 30 cm deep (to be increased to 60 cm in case of road crossing and pavements). The portion within the building shall be recessed in walls and floors to adequate depth in due co-ordination with the building work.

Page 22: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

49

TECHNICAL SPECIFICATION OF ADDRESSABLE FIRE ALARM SYSTEM

PART 1.0 -GENERAL

DescriptionA. The fire alarm system shall include furnishing, installation, and connection of the

Analog/Addressable Microprocessor based LCD/LED Fire Alarm Control Panel consisting of system cabinet(s), main chassis with power supply, with or without UDACT dialer, stand-by batteries, initiating and indicating, optional city tie/reverse polarity module, optional relay modules, detection and signaling devices, and any auxiliary modules, remote annunciator assemblies, and miscellaneous peripheral devices to form a complete coordinated system ready for operation as shown on the drawings or herein specified.

B. The fire alarm system shall comply with requirements of NFPA Standard No. 72 for protected premises signaling systems except as modified and supplemented by this specification. The system field wiring shall be supervised electrically. The system and all associated equipment shall be fully approved and listed by the following agency and regulatory controls:

1. System:

a. Must comply with applicable National, State, and/or local Building code recognized at time of installation.

b. Must comply with NFPA 101 70, 72 fire alarm installation standard recognized at time of installation.

c. Installation must comply with requirements of Local Authority Having Jurisdiction.

2. Devices & Control equipment:

a. Equipment described here in must be UL listed under the current issue of the standard indicated:

b. Manual fire alarm stations No. 38

c. Heat detectors: No. 521

d. Smoke detectors for Fire Protective Signaling Systems: No. 268

e. Audible signal devices: NO. 464

f. Control Units for Fie Protective Signaling systems: No. 864

Page 23: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

50

g. Visual Notification Appliances: 1971

h. Power Supplies for Fire Protective Signaling Systems: No. 1481

i. Smoke Detectors for Duct Applications: No. 268A

j. Water flow Indicators for Fire Protective Signaling Systems: No. 346

Submittals and Shop drawings:

A. Sufficient information shall be clearly presented and shall include manufacturer’s name, model numbers, power requirements, equipment layout, device arrangement and complete wiring.

B. Sequence and description of operation.

C. Product Data for each type of equipment, initiating device, signal device, peripheral device and cable provided on the project.

D. Shop drawings shall include battery calculations, floor plans and wiring diagrams.

Operation Manual Operation manual shall include:

1. Installation instructions for use by installing contractor.2. Operational instructions or manual for use by building personnel, including

name and phone number of service representative.3. Maintenance instructions as required for use by building personnel.4. Copy of approved shop drawings.

Basic System

The fire detection system shall be capable of integrating multiple control command centers and remote network annunciators. Each panel shall be capable of fire detection, equipment supervision and control, alarm management, and historical data collection and archiving, and of integrating multiple annunciator units and remote command centers, each capable of alarm display and system control functions. Up to 254 units may be networked together utilizing "Peer to Peer" communication technology. Systems that are of the OEM nature (under private label) and not fully field programmable will not be considered. The fire detection system shall consist of the following:Network capability of up to 254 unitsTouch screen color graphics capabilityStand alone capability of each control unit on loss of data channel

Page 24: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

51

Conventional and Analog Devices250 software groups/zones14.5" wide cabinet construction to ensure fitting between wall studsPortable Operator's Terminals (POT)Up to 16 Class "B" or 8 Class “A" intelligent SLC'sUp to 16 Class "B" or 8 Class "A" conventional zones (IDC’s)8 Class "B" or 4 Class "A" notification circuits (NAC’s)Minimum 10Amp power supplyField programmableAlarm/Trouble/Supervisory LED's per circuitIndividual ground fault detection and reporting by circuit80 character back-lighted LCD read-out60 characters dedicated to user text messaging per device/circuitThe system shall permit expansion of both capacity and functionality through the

addition of units, modules, addressable devices and detectors.High-speed data transfer rates for alarm reporting, quick report generation from

multiple systems/transponders and upload/download capability between network systems. The maximum response time shall be 5 seconds between initiation of alarm and signal output. Each control unit shall support a minimum of 1584 addressable devices in Class “A” Loop wiring & 3168 addressable devices in Class ”B" Loop wiring. The entire "peer-to-peer" network shall have a minimum capacity of 402336 intelligent points.

Each unit shall have sufficient memory to support its own operating system and databases including:

Fire ManagementAlarm ManagementHistorical/Trend DataMaintenance Support ApplicationsCustom ProcessesOperator I/OExpandability: The system shall be expandable in nature and shall permit easy

expansion through the addition of software applications, additional units and devices.

Serial Communication Ports: provide data communication ports for simultaneous operation of devices such as industry standard printers, programming terminal, personal computer, transponder and annunciators.

Integrated on-line Diagnostics: Each unit shall continuously perform self-diagnostics, communication diagnostics and diagnostics on all subsidiary equipment.

Surge and Transient Protection: Each unit shall provide isolation and transient protection at all network terminations and all field point terminations to suppress induced voltage transients where required.

1.5 System SoftwareAll necessary software to form a complete operating system as described in this

specification shall be provided.

Page 25: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

52

The software programs specified in this section shall be provided as an integral part of the unit and shall not be dependent upon any higher level computer for execution.

Status Change Report: All alarm or point change reports shall include the point's English language description, and the time and date of occurrence.

Report Routing: Alarm reports shall be archived for future recall.Alarm Messages: In addition to the point's description and the time and date, the user

shall be able to print, display or store a custom alarm message to more fully describe the alarm condition or direct operator response.

Each control unit shall be capable of storing a library of at least 1000 events. The event log shall have the ability to be printed via a parallel printer port built-into the FACP.

The FACP shall have a parallel printer port which allows the internal software the ability to print the following reports:

System event logSensitivity for all devicesRelation routing, this shows all input and output relationships of the entire systemAlarm Verification: The alarm verification feature shall be used to delay acceptance of

alarms until they can be confirmed, and shall meet all applicable code requirements and standards. Any or all circuits may be selected for verification through field configuration, which shall be done without removal of an EPROM. If a circuit is selected for alarm verification, it will only verify two-wire smoke detectors. Contact devices, such as manual stations, connected to a verified circuit will be discriminated and will not be verified.

When the unit detects an alarm on an initiating circuit programmed for alarm verification, the unit shall automatically reset the power to that circuit.

If the alarm condition is still present after a pre-set time period of 30 seconds, then the system will automatically enter the Alarm mode.

History Mode: The system shall be able to store and display at least 1000 system events that have occurred in a non-volatile buffer memory. Display of these events shall be accomplished on-site through the use of the front control panel indicators and switches.

Field Configurable: The system shall be fully configurable and expandable at the owner's site without the need for EPROM programmers. All configurations shall be accomplished through downloading of programs from a computer. Reconfiguration shall not require knowledge of any programming languages or require any special training. All programs shall be stored in non-volatile memory. Entry into program mode shall require a special key and a special password entered into the front panel.

Releasing Function: The notification appliance circuit shall be software configurable for Continuous Output, Strobes, Door Holders and releasing functions. The panel will support Abort and Hold operation as well as have Cross Zoning.

The software residing in the FACP shall be capable of reporting initiating devices even if they are not in the database. In the event that an initiating device, which is not in the database, reports an alarm state, the FACP shall turn on all Notification Appliance Circuits. This ensures all devices are active, whether they are

Page 26: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

53

programmed in the database or not. Panels which do not respond to un-programmed devices in alarm shall not be considered equal.

1.6 NetworkingIf utilized or for future use, the network shall be Style 7 wiring, with each control unit

talking directly with two other units and the network will be a closed loop. Units which require a host or head end controller will not be accepted.

The network will be "peer-to-peer" with each unit generating commands to other units as required.

System architecture in networked configuration shall eliminate dependence upon any single control unit for alarm reporting and control execution. Each control unit shall operate independently by performing its own specified control, alarm management, and historical data collection. The failure of any single component or network connection shall not interrupt the operation of the balance of the system.

Control units on the network shall be able to send control commands directly to any other unit on the network without dependence upon a central processing unit.

Optionally, each unit can, through programming, send operating commands, such as Acknowledge, to other units on the network.

Prioritization: Each unit shall send commands to other units on the network based upon the priority of the initiating signal. Alarm events/commands shall be sent before supervisory conditions, which will be sent before commands for a Trouble condition.

In case of a partial communications failure, each unit will continue to send commands to those units it can still communicate with.

Each unit will be able to work in a stand-alone mode in case of a total loss of network communications.

Any control unit in the network can be made the master unit of the network by software changes only.

Each control unit will have error detection, correction, and retransmissions to guarantee data integrity.

Remote Annunciators/Command Centers will be an equal peer in the network.

1.7 Sequence of OperationA. When a fire alarm condition is detected by one of the system initiating devices, the

following shall occur:All automatic programs assigned to the alarm point shall be executed and the associated

indicating devices and relays activated.The System Alarm on appropriate unit will indicate an alert condition.The corresponding zone(s) in alert alarm will be indicatedSecond stage operation shall occur when a key is inserted into the key-operated switch

of any manual pull station causing all fire alarm speakers/bells to sound the general alarm (evacuation) at a rate of 120 strokes per minute throughout the building.

If the fire alarm condition is not acknowledged at the unit within five (5) minutes of the sounding of the first stage alarm, the fire alarm system shall automatically

Page 27: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

54

indicate a second stage alarm causing all bells in the building to sound the general alarm (evacuation) throughout the building. Activation of the second stage shall be identified at the operator's workstation.

Activate all control by event functions related to the alarmSend signal to U.L. Certified monitoring central stationFan systems, i.e., shutdown, exhaust and pressurization operations to be initiated.Doors with hold open devices shall be signaled to releaseWhen a trouble condition is detected by one of the system initiating or indicating

circuits, the following functions shall immediately occur:System Trouble will be indicted on the unit and system annunciator(s).A local trouble-sounding device in the unit and annunciator shall be activated. This

sound shall be distinct from the alarm sound.The trouble for the corresponding initiating or indicating circuit shall be indicated on

the unit.The appropriate message will appear on the LCD display.

1.8 Conventional Interface ModuleAny Initiating Circuit may be configured to be a Supervisory Circuit. If so configured,

it will not activate the System Alarm indication when a supervisory condition is detected but will instead activate a separate supervisory indication. Open-circuit conditions will be reported as trouble and must be differentiated from supervisory conditions.

Each circuit shall be definable in software as an alarm or supervisory circuit.1.9 Analog ModuleEach network control panel shall be capable of supporting 8 class “A” or 16 class "B"

SLC circuits within one cabinet.Each Intelligent Loop circuit shall be capable of supporting up to 198 (Class A or Class

B) intelligent devices consisting of 99 intelligent detectors and 99 addressable modules per loop. The basic unit shall be capable of supporting up to two (2) modules. Each module has four (4) class A or eight (8) class B circuits.

One analog interface module shall monitor and control up to four Class A or eight Class B loops of intelligent detectors and addressable modules. The analog interface board shall contain its own microprocessor control.

The analog interface board shall communicate and provide power to all devices on its loop over a single pair of wires. For Class B operation, the loop is not returned and branch circuits ("T-tap") connections may be made off of the loop. Class A operation shall be available.

The analog interface board shall receive analog information from all intelligent detectors and shall process this information to determine normal, alarm, supervisory or trouble conditions. The analog information may also be used for automatic test and determination of maintenance requirements.

It shall be possible to display on the control unit LCD display, the current analog value of any addressable device, as well as the programmed trip points.

Page 28: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

55

Communication with all connected devices shall be performed every 5 seconds or less. Average time to detect an alarm shall be less than 5 seconds (longer for alarm verification detectors).

PART 2- FIRE ALARM EQUIPMENT 2.0 Control PanelThe CPU shall communicate with the operator interface, LCD display, LED display

and control all other modules in the unit. Removal, disconnection or failure of any control unit module shall be detected and reported by the Central Processing Unit.

The CPU shall contain and execute all control-by-event programs for specific action to be taken if a fire situation is detected in the system. Such control-by-event programs shall be held in non-volatile programmable memory, and shall not be lost even if system primary and secondary power failure occurs. The CPU shall also provide a real time clock for time annotation on the display and remote optional printer.

2.1 Notification CircuitsThe Control Unit shall provide up to 8 fully supervised Class B notification circuits.

The notification circuit capacity shall be 1.0 amperes maximum per circuit. If a short circuit trouble occurs on one of the notification circuits it will not affect the operation of the remaining circuits.

2.2 Function RelaysThe Control Unit shall provide 4 sets of Form "C" relay contacts rated at 2 A at 30

VDC. These relays may be programmed to activate on alarm from any initiating zone or any combination of initiating zones, analog devices or addressable modules.

2.3 System RelaysThe Control Unit shall provide 3 sets of Form "C" relay contacts rated at 2 A at 30

VDC. These relays have a fixed operation, alarm, supervisory, and trouble. 2.4 Operator DisplayThe operator display shall provide all controls and indicators used by the system

operator. The display shall contain, and display, as needed, custom alphanumeric message for all intelligent detectors and addressable modules. Such message information shall be stored in programmable non-volatile memory.

The display board shall provide an 80-character alphanumeric Liquid Crystal Display (LCD). It shall also provide 3 x 24 Light Emitting Diodes (LED's) for zone alarm indication and a further 24 LED's for system indication such as AC POWER; SYSTEM ALARM; SYSTEM TROUBLE; DISPLAY TROUBLE; GROUND FAULT; TROUBLE ACKNOWLEDGE; ALARM ACKNOWLEDGE and SIGNAL SILENCE.

Factory programmable system indications and keys shall be available for unique functions. Keys shall be referred to as "Hot Keys".

The operator display shall provide a 20-key touch keypad with control capability to command all system functions, and entry of any alphabetic or numeric information. The keypad shall include means to enter a minimum of two different passwords to prevent unauthorized manual control.

Page 29: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

56

Conventional LED lamp indication shall be provided for all zones. Separate alarm, supervisory and trouble, indication shall be available on a per zone basis. Operator intervention shall not be required for display of all zones in alarm condition.

Ground fault indication shall be displayed on a circuit basis.2.5 One Person TestThe control unit shall include a special one-person test feature, which will allow a

single person to test all initiating devices and indicating appliance in a system without returning to the panel to Reset the system. A special password shall be required to enter the test mode. The serviceman shall be able to pre-select the initiating and indicating circuits that are to be included in the one person test mode. The Walk-Test shall include a special audible indication that a trouble has been detected on an analog device, for the serviceman to check proper system wiring.

Historical Data and Trend Analysis: A variety of historical data collection utilities shall be provided to automatically sample, store, and display system data.

In network configuration it shall be possible to download programming information from the master to the slave units.

2.6 Communication PortsThe system shall provide the following interfaces:Two ports for System networkingOne port for dialer/city tie, PC or Voice Evac connectionOne port for service and field programmingOne port for Printer 2.7 Power SupplyThe power supply for the unit and all fire alarm peripherals shall be integral to the

control unit. The power supply shall provide all control unit and peripheral power needs as well as a minimum of 300 mA of regulated 24 VDC power for external devices.

All circuits are Power Limited using positive-temperature-coefficient thermistors, circuit breakers, or other over-current protection.

Input power shall be 240 VAC 50 Hz. The power supply shall provide an integral battery charger. Internal battery capacity shall be sized as required to meet UL and NFPA requirements.

The Main Power Supply shall provide a battery charging circuit consisting of a fully automatic standby battery charger, rate compensated, capable of maintaining battery in fully charged state and be capable of recharging batteries to 70% of alarm capacity within 12 hours. Provide for normal operation of entire system for 24 hours with power remaining to sound alarms for 5 minutes.

Provide charger with following supervised functions: circuit protection for shorts, open, disconnected or reversed polarity battery connection, supervision or protection of high or low voltage, overcharging and charger failure. Automatic load shedding or battery disconnects on deep discharge to prevent battery damage.

Maintenance free, long-life batteries, 24 V, rechargeable, gelled electrolyte, totally sealed, fully charged with all interconnections ready for service.

2.8 Mechanical Design

Page 30: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

57

The control unit shall be housed in a cabinet designed for surface mounting directly to a wall or vertical surface or semi flush with integral trim ring. The back box and door shall be constructed with provisions for electrical conduit connections. The door shall provide a key lock and shall include a glass opening for viewing. The back box shall be 14.5" wide for between stud mounting.

The control unit shall be modular in structure for ease of installation, maintenance, and future expansion.

The control panel will not require fans or other means of active cooling.

2.9 System Components

NOTIFICATION DEVICES

A. Audible/Visual Devices1. The notification devices shall be of a low profile design and combination that

provides a selection of high or low dBA as well as field selectable candela options of 15,30,60,75 and 110 candela. Each device shall have input terminals of 12 to 18 AWG and be provided with a tamperproof Re-entrant Grill. Notification devices must have capability of switching for Temporal 3, Chime, or Whoop Tones. Device shall have capability of silencing the horn while allowing strobes to remain flashing.

2. Alarm signals shall comply with UL, 464, UL 1971, UL 1638 and the Americans with Disabilities Act (ADA). Audible signals shall sound in accordance with a Code 3 temporal pattern. Strobes shall have a flash rate of 1 hertz. Where so indicated and required to comply with standards, increased candela intensities shall be provided.

A. Exterior Audible/Visual Alarm Signals:1. Audible signals shall be horns that shall provide a sound level of at least 85

dBA, measured 10 feet from the horn on axis. Visual signals shall have 75 candela xenon strobes behind protruding clear lenses. The word “FIRE” shall be imprinted on the appliance. Audible and visual signals shall be mounted as per manufacture instructions using proper listed back box; the exterior signal appliances shall be listed for outdoor use and shall be weather-proof.

C. Interior Audible/Visual Alarm Signals:

1. Audible signals shall be horns that shall provide a selectable sound level consisting of at least two levels separated by a minimum of 4 dB within the range of 89 to 99 dBA, as measured 10 feet from the horn on axis. Visual signals shall have xenon strobes behind clear lenses with the word “FIRE”. Device shall be of the selectable candela type.

D. Voice Evacuation Speakers:

1. All speakers shall operate on 25 VRMS or with field selectable output taps from 0.25 to 2.0 Watts.

Page 31: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

58

2. Speakers in corridors and public spaces shall produce a nominal sound output of 84 dBA at 10 feet (3m). 3. Frequency response shall be a minimum of 400 HZ to 4000 HZ.4. The back of each speaker shall be sealed to protect the speaker cone from damage and dust.

E. Detection Devices:

A. Addressable Devices - General

1. Addressable devices shall provide an address-setting means using rotary decimal switches.

2. Addressable devices shall use simple to install and maintain decade (numbered 0 to 9) type address switches. Devices which use a binary address or special tools for setting the device address, such as a dip switch are not an allowable substitute.

3. Detectors shall be Analog and Addressable, and shall connect to the fire alarm control panel's Signaling Line Circuits.

4. Addressable smoke and thermal detectors shall provide dual (2) status LED’s. Both LED’s shall flash under normal conditions, indicating that the detector is operational and in regular communication with the control panel, and both LED’s shall be placed into steady illumination by the control panel, indicating that an alarm condition has been detected. If required, the flashing mode operation of the detector LED’s can be programmed off via the fire control panel program.

5. The fire alarm control panel shall permit detector sensitivity adjustment through field programming of the system. Sensitivity can be automatically adjusted by the panel on a time-of-day basis.

6. Using software in the FACP, detectors shall automatically compensate for dust accumulation and other slow environmental changes that may affect their performance. The detectors shall be listed by UL as meeting the calibrated sensitivity test requirements of NFPA Standard 72, Chapter 7.

7. The detectors shall be ceiling-mount and shall include a separate twist-lock base which includes a tamper proof feature.

8. The following bases and auxiliary functions shall be available :

a. Sounder base rated at 85 DBA minimum.b. Form-C Relay base rated 30VDC, 2.0Ac. isolator base

9. The detectors shall provide a test means whereby they will simulate an alarm condition and report that condition to the control panel. Such a test may be initiated at the detector itself (by activating a magnetic switch) or initiated remotely on command from the control panel.

10. Detectors shall also store an internal identifying type code that the control panel shall use to identify the type of device (example: ION, PHOTO, THERMAL).

B. Addressable Manual Alarm Pull Station

Page 32: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

59

1. The alarm pull station shall be a low profile design, with terminal or pigtail connection. It shall have 10AMP SPST, SPDT, or DPDT Gold Plated contacts and be single or double action. The pull station shall be equipped with Allen wrench or key lock/reset.

2. Addressable manual alarm pull station shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. They shall use a key operated test-reset lock, and shall be designed so that after actual emergency operation, they cannot be restored to normal use except by the use of a key.

3. All operated stations shall have a positive, visual indication of operation and utilize a key type reset.

C. Intelligent Photoelectric Smoke Detector

1. The detector shall use the light-scattering principal to measure smoke density and shall send data to the FACP indicating analog level of smoke density.

Detectors shall be Analog and Addressable, and shall connect to the Fire Alarm Control Panel using Signaling Line Circuits. The addressable smoke detectors shall utilize a decade (numbered 0-99) type address switch. Devices that use binary address or special tools for setting the device address shall not be allowed.

2. The detectors shall provide dual status LED’s. Detectors shall be ceiling mount and shall include a separate twist-lock base that includes a tamper proof feature. The following features must also be capable for the detector: Sounder base rated at 85 dBA minimum, Form C relay, or Isolator base.

3. The detector shall provide a test means for simulation of alarm condition and report that condition to the main control panel. This test may be initiated by activation with a magnetic switch.

4. Detector must store internal identity type indicating the device is a photo type at the panel.

D. Intelligent Laser Photo Smoke Detector

1. The intelligent laser photo smoke detector shall be a spot type detector that incorporates an extremely bright laser diode and an integral lens that focuses the light beam to a very small volume near a receiving photo sensor. The scattering of smoke particles shall activate the photo sensor.

2. The laser detector shall have conductive plastic so that dust accumulation is reduced significantly.

3. The intelligent laser photo detector shall have nine sensitivity levels and be sensitive to a minimum obscuration of 0.03 percent per foot.

4. The laser detector shall not require expensive conduit, special fittings or PVC pipe.

5. The intelligent laser photo detector shall support standard, relay, isolator and sounder detector bases.

Page 33: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

60

6. The laser photo detector shall not require other cleaning requirements than those listed in NFPA 72. Replacement, refurbishment or specialized cleaning of the detector head shall not be required.

7. The laser photo detector shall include two bicolor LED’s that flash green in normal operation and turn on steady red in alarm.

E. Intelligent Ionization Smoke Detector

1. The detectors shall use the dual-chamber ionization principal to measure products of combustion and shall, on command from the control panel, send data to the panel representing the analog level of products of combustion.

F. Intelligent Multi Criteria Acclimating Detector

1. The intelligent multi criteria Acclimate detector shall be an addressable device that is designed to monitor a minimum of photoelectric and thermal technologies in a single sensing device. The design shall include the ability to adapt to its environment by utilizing a built-in microprocessor to determine it's environment and choose the appropriate sensing settings. The detector design shall allow a wide sensitivity window, no less than 1 to 4% per foot obscuration. This detector shall utilize advanced electronics that react to slow smoldering fires and thermal properties all within a single sensing device.

2. The microprocessor design shall be capable of selecting the appropriate sensitivity levels based on the environment type it is in (office, manufacturing, kitchen etc.) and then have the ability to automatically change the setting as the environment changes (as walls are moved or as the occupancy changes).

3. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena.

G. Intelligent Thermal Detectors

1. The heat detector shall be an intelligent addressable device rated for 135 degrees and have a rate-of-rise element. The detector shall connect to the FACP using a Signaling Line Circuit. The heat detector shall utilize a decade (numbered 0-99) type address switch. Devices that use binary address or special tools for setting the device address shall not be allowed.

H. Intelligent Duct Smoke Detector

1. The smoke detector housing shall accommodate either an intelligent ionization detector or an intelligent photoelectric detector, of that provides continuous analog monitoring and alarm verification from the panel.

Page 34: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

61

2. When sufficient smoke is sensed, an alarm signal is initiated at the FACP, and appropriate action taken to change over air handling systems to help prevent the rapid distribution of toxic smoke and fire gases throughout the areas served by the duct system.

3. The sampling tubes shall be in 3, 5, or 10-foot lengths as required. When required, provide a remote indicator light.

I. FILTEREX

1. The detector shall be designed to provide early warning smoke detection in environments where traditional smoke detectors are not practical.

2. The detector shall have a filter system to remove particles down to 25 microns.3. This filter system shall remove unwanted airborne particles and water mist. This

shall allow the detector to operate in environments where traditional smoke detectors would have nuisance alarms.

4. The filter system shall consist of 2 filters one of which is field replaceable.5. The filter system shall have an intake fan to draw air and smoke through the

filters into the sensing chamber.6. The filter system shall be supervised so that if the filter is clogged or the fan fails

the control panel reports trouble.7. The filter system shall be powered from 24 VDC separate from the SLC

communications.8. The detector shall utilize a photoelectric sensing chamber.

J. Addressable Dry Contact Monitor Module

1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional alarm initiating devices (any N.O. dry contact device) to one of the fire alarm control panel SLC’s.

2. The IDC zone shall be suitable for Style D or Style B operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel.

3. For difficult to reach areas, the monitor module shall be available in a miniature package and shall be no larger than 2-3/4 inch (70 mm) x 1-1/4 inch (31.7 mm) x 1/2 inch (12.7 mm). This version need not include Style D or an LED.

K. Two Wire Detector Monitor Module

1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional 2-wire smoke detectors or alarm initiating devices (any N.O. dry contact device).

2. The IDC zone may be wired for Class A or B (Style D or Style B) operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel.

Page 35: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

62

L. Addressable Control Module

1. Addressable control modules shall be provided to supervise and control the operation of one conventional NACs of compatible, 24 VDC powered, polarized audio/visual notification appliances.

2. The control module NAC may be wired for Style Z or Style Y (Class A/B) with up to 1 amp of inductive A/V signal, or 2 amps of resistive A/V signal operation.

3. Audio/visual power shall be provided by a separate supervised power circuit from the main fire alarm control panel or from a supervised UL listed remote power supply.

4. The control module shall be suitable for pilot duty applications and rated for a minimum of 0.6 amps at 30 VDC.

M. Addressable Relay Module

1. Addressable Relay Modules shall be available for HVAC control and other building functions. The relay shall be form C and rated for a minimum of 2.0 Amps resistive or 1.0 Amps inductive. The relay coil shall be magnetically latched to reduce wiring connection requirements, and to insure that 100% of all auxiliary relay or NACs may be energized at the same time on the same pair of wires.

N. Isolator Module

1. Isolator modules shall be provided to automatically isolate wire-to-wire short circuits on an SLC Class A or Class B branch. The isolator module shall limit the number of modules or detectors that may be rendered inoperative by a short circuit fault on the SLC loop segment or branch. At least one isolator module shall be provided for each floor or protected zone of the building.

2. If a wire-to-wire short occurs, the isolator module shall automatically open-circuit (disconnect) the SLC. When the short circuit condition is corrected, the isolator module shall automatically reconnect the isolated section.

3. The isolator module shall not require address-setting, and its operations shall be totally automatic. It shall not be necessary to replace or reset an isolator module after its normal operation.

4. The isolator module shall provide a single LED that shall flash to indicate that the isolator is operational and shall illuminate steadily to indicate that a short circuit condition has been detected and isolated.

Page 36: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

63

PART 3 -INSTALLATION & TESTING

3.1 Installation1. Conduit:

a. Conduit shall be in accordance with The National Electrical Code (NEC), local and state requirements.

b. All wiring shall be installed in conduit or raceway, unless otherwise indicated on drawings. Conduit fill shall not exceed 40 percent fill as per NEC. Conduit size shall be ¾ inch minimum.

c. Wiring for 24 volt control, alarm notification, emergency communication and similar power-limited auxiliary functions shall be installed as per the manufacturer’s installation requirements

d. Conduits shall not enter the Fire Alarm Control Panel, except where conduit entry is specified by the manufacturer.

e. Cable must be separated from any open conductors of Power, or Class 1 circuits, and shall not be placed in any conduit, junction box or raceway containing these conductors, as per NEC Article 760-29.

2. Wire:a. All wiring shall be in accordance with local, state and national codes

(e.g., NEC Article 760) and as recommended by the manufacturer of the fire alarm system. Number and size of conductors shall be as recommended by the fire alarm system manufacturer

b. Wire and cable not installed in conduit shall have a fire resistance rating suitable for the installation as indicated in NFPA 70. All field wiring shall be completely supervised.

c. The Fire Alarm Control Panel shall be connected to a separate dedicated branch circuit, maximum 20 amperes. This circuit shall be labeled at the Main Power Distribution Panel as FIRE ALARM. Fire Alarm Control Panel Primary Power wiring shall be 12 AWG. The Control Panel Cabinet shall be grounded securely to either a cold water pipe or grounding rod.

3.General Installation:a. Installation shall conform to the wiring diagrams submitted as shop

drawings and to the manufacturer’s instructions.b. Installation of equipment, devices, wire and cable terminations,

programming, adjusting, testing and demonstration shall be performed by a qualified installer to perform fire alarm system work. Final connections shall be made under the supervision of an authorized manufacturer representative.

4. Verification TestingProvide the service of a factory-trained technician authorized by the manufacturer of the system to technically supervise and participate during

Page 37: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

64

all of the adjustments and tests for the system. All testing shall be in accordance with NFPA and the manufacturer.

a. Check for correct connections and test for short circuits, ground faults, continuity, and insulation.

b. Close each sprinkler system flow valve and verify supervisory alarm at the FACP.

c. Verify activation of all flow switches.

d. Open initiating and indicating device circuits and verify trouble signal activation.

e. Ground all circuits and verify response of trouble signals.

f. Check for audibility of tone at all alarm notification devices.

g. Check installation, supervision, and operation of all smoke and duct smoke detectors.

h. Verify the proper alarm and trouble receipt and processing of signals at the FACP and any remote annunciators.

i. Perform all tests in accordance with the manufacturer’s testing procedures.

j. Correct any deficiencies discovered as a result of the testing and retest the work affected by such corrections.

3.2 Final inspection and instruction

A. A factory trained representative of the manufacturer shall demonstrate that the system functions properly.

B. Instructions for operating the system shall be provided in a hands-on demonstration as

stated elsewhere in the specification or as indicated on the drawings. C. Written operating instructions shall be provided.

D. Record of Completion indicating certification of the fire alarm system installation and testing shall be submitted to the Consultant at completion in accordance with Tender Requirements. A copy of all Record of Completion certificates together with Inspections and Testing Forms shall be delivered to the Owner’s Representative. Photocopies shall be included in the Operating and Maintenance Manuals.

Page 38: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

65

3.3 Warranty

A. The FACP shall have a 2 year manufacturers warranty against product defects. This warranty shall be for material only. Installation and labor shall be warranted for a period of 1 year or as indicated elsewhere in this specification.

TECHNICAL SPECIFICATION FOR DIESEL GENERATING SET

DIESEL ENGINEReliable rugged diesel engine AIR /Water cooled, electric start, four stroke multi cylinder, conforming to relevant IS/BS with 10% overloading for one hour in any twelve hours. The engine will be fitted with following accessories:

COOLING SYSTEM- Blower / Radiator - Automatic belt tensioning device / Centrifugal water pump

EXHAUST SYSTEM- Exhaust manifold

- Flexible pipe for silencer

FUEL SYSTEM- Fuel pump- Fuel injectors- Fuel filter

LUB OIL SYSTEM- Lub oil pump- Lub oil filter

AIR SYSTEM- Air intake manifold- Air cleaner assembly

GOVERNOR- Mechanical

STARTING SYSTEM

Page 39: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

66

- Electric starting – 12V- Battery charging alternator

COUPLING ARRANGEMENT- Flexible coupling- Flywheel to suit flexible coupling- Flywheel housing

ENGINE INSTRUMENT PANEL- Starting switch with key- Lub oil pressure gauge- Battery charging ammeter

SAFETIES- Low lub oil pressure- High water temperature (Only for water cooled engine)

MANUALS- Engine operation and maintenance chart- Parts catalogue- Engine routine test certificate - Engine warranty card

ALTERNATOR

Synchronous three phase alternator of make suitable for continuous operation at 1500RPM generating 415lts at 0.8power factor (lag) suitable for 50Hz, Three phase, 4wire, system. The alternator shall be self excited, self regulated, foot mounted fitted with ball and/or roller bearings. The alternator will generally conforming to BS:2613/ IS:4722.

ACCESSORIES

BASE FRAMEHeavy duty base frame of sturdy design made of M.S. channel with necessary reinforcement and pre drilled holesFUEL TANKDaily service fuel tank made out of 14SWG MS sheet suitable for 100Litres complete with drain plug, air vent, inlet and outlet connection

Page 40: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

67

BATTERY One no. Battery of 12V each in dry and uncharged conditions with its leads of Exide/Kirloskar make.

AUTOMATIC MAINS FAILURE PANEL

The panel will be made out of fabricated sheet steel suitable for indoor mounting installation, hinged front panel door for easy accessibility and suitable rated bus bars complete with internal wiring, fuses with suitable provision for connecting incoming and outgoing cables. The panel will be fitted with following instruments:

Alternator contactor of suitable rating with over load relay and HRC fuses for short circuit protectionMain contactor of suitable ratingOne ammeter One voltmeter One frequency meterOne set of mains supply voltage monitor to identify low voltage/ complete failure and initiate necessary signal for operation of automatic control gear.Set of push buttons for Start, Stop, Reset, AcknowledgeMaster switch for Auto/Manual/Test/OffOne set of indicating lamps for indicating- Load on mains- Load on set- Set fails to start- Low lub oil pressure- Battery charger ONOne hooterBattery charger for charging battery when set is not in operation, connecting to the load side so that it will energized from the mains. The battery charger will comprise of the following:- Transformer of suitable capacity- Rectifier- D.C.ammeter- D.C.voltmeter- Charger rate selector switch for trickle or boost chargingAll control fuses will be so located as to be easily accessible for replacement

Relay section will comprise of the following- Automatic starting of D.G.set in the event of mains voltage failure/ falling below a preset

value- When the main supply is restored, it’s quality will be monitored for a period of set time,

then load is automatically transferred on the mains and the D.G.set will shut down after a preset idle running period

- In the event of failure of diesel engine to start on failure of mains supply on one attempt, two more starting impulse will be automatically given and if still the engine does not start

Page 41: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

68

due to some defects within thirty seconds of first starting impulse, it will get disconnected and locked out automatically and audio and visual signal will operate

- In the event of failure of diesel generating set due to faulty starting, the mains supply contactor will get energized without any delay on the restoration of mains supply

The circuitry will make use of minimum number of relays and control wiring will be neatly provided with adequate size of copper conductor cable of suitable cross section voltage grading and tag number at either end.

In the manual operation the diesel generating set will be started by the attendant by pressing start push button irrespective of the conditions of the main supply. Thus with this arrangement it will be possible to exercise routine test of the diesel generating set on the load without interrupting the supply of essential circuit.

In the test mode of operation conditions similar to mains failure will be simulated by operating the master switch on the Test.

By pass system with the help of two nos. changeover switch of suitable rating

Acoustic Enclosure:

Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven-tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE-RETARDANT foam as acoustic material. Four hinged doors shall be provided to canopy, one door shall have glass window for control panel.

Base Frame:

Base frame is fabricated either in ISMC channel or in sheet metal. The base frame will be primer coated and painted. The base frame is rugged in construction and designed for mounting Diesel engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator.

Color Scheme

The base plate and top is powder coated with OXFORD BLUE/PEPSI BLUE, the canopy is powder coated with IVORY color.

Performance Parameters

Page 42: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

69

The average sound level, when measured in green field condition (ISO 3744 OR 8528 PT 10) at 1-meter distance from all four sides shall be less than 75-dBA averages or as per CPCB norms.The average stabilized hot air temperature rise with in the canopy is maintained with in 10 C over and above ambient temperature.

CANOPY FEATURES

Canopy fabricated on machines with dimensional accuracy of 1mm.Canopy is powder coated after passing through seven tank processes.Canopy is lined with acoustic foam, which is non-igniting /Fire Retardant (confirming to BS 4735/BIS 7888).No grouting required on the ground, only a level surface capable of withstanding the DG weight.Designed for installation in open-air conditions.Lockable doors provided.Lockable fuel filling arrangement provided external to the canopy.Residential Silencer is housed in the canopy.Externally accessible emergency stop button.The exhaust gases shall be taken out through a suitable flexible pipe to prevent any back pressure on the engine.

Thermal Insulation:

The exhaust system and noise suppressor shall be provided with thermal insulation by using fire retardant/non igniting foam conforming to BIS7888/BS 4735 to prevent excess heat radiation on the engine and safe for operatorNoise suppressor: (Silencer)

Absorption type Non resistance Residential Silencer insulated from inside with glass wool shall be provided to suppress exhaust noise from the engine.

Wiring and Lighting:

PVC copper wire concealed in flexible conduit with florescent tube light/bulb with MCB shall be provided.

Surface Treatment-Painting:

The enclosure surface shall be suitably treated for degreasing, de-rusting and phosphating. High quality powder coat treatment/paint shall be used.

Canopy lights: one no. DC bulb to be fitted with suitable toggle switch and wiring.

Temperature rise inside the canopy

Page 43: Ptenders.hpcl.co.in/tenders/tender_prog/TenderFiles/2010... · Web viewAluminium / Copper busbar sections----- Recommended rectangular cross-section -----Current Aluminium Copper

70

The maximum permissible temperature rise above the ambient shall be 10oC.

Emergency Push Stop Button

The canopy shall have provision of emergency push button, which shall be housed in a protective enclosure with a glass front.

Performance:

The sound level shall be less than 75 dbA at a distance of 1 meter. The temperature difference between ambient and air inlet at air cleaner within the enclosure will be maintained well within 5-7 deg centigrade. The measurement of noise will be as per ISO 3744/ISO 8528 (part 10) standard. This meets CPCB norms.

All other requirements that are essential to make the DG set compliant to CPCB norms for noise reduction shall form part of technical requirements.