Installation and serviceinstructionsfor contractors
VIESMANN
Vitotrol 300 RF
Wireless remote control for one, two or three heating circuits
For applicability, see the last page
VITOTROL 300 RF
5614 625 GB 4/2012 Please keep safe.
2
Please follow these safety instructions closely to prevent accidents and mate-rial losses.
Safety instructions explained
DangerThis symbol warns against therisk of injury.
! Please noteThis symbol warns against therisk of material losses and envi-ronmental pollution.
NoteDetails identified by the word "Note" con-tain additional information.
Target group
These instructions are exclusivelydesigned for qualified personnel.■ Work on gas equipment must only be
carried out by a qualified gas fitter.■ Work on electrical equipment must
only be carried out by a qualified elec-trician.
■ The system must be commissioned bythe system installer or a qualified per-son authorised by the installer.
Regulations
Observe the following when working onthis system■ all legal instructions regarding the pre-
vention of accidents,■ all legal instructions regarding envi-
ronmental protection,■ the Code of Practice of relevant trade
associations,
■ all current safety regulations asdefined by DIN, EN, DVGW, TRGI,TRF, VDE and all locally applicablestandards,
■ Gas Safety (Installation & Use) Regu-lations– the appropriate Building Regulation
either the Building regulations, theBuilding Regulation (Scotland),Building Regulations (Northern Ire-land),
– the Water Fittings Regulation orWater Bylaws in Scotland,
– the current I.E.E. Wiring Regula-tions.
If you smell gas
DangerEscaping gas can lead to explo-sions which may result in seriousinjury.■ Never smoke. Prevent naked
flames and sparks. Neverswitch lights or electrical appli-ances ON or OFF.
■ Close the gas shut-off valve.■ Open windows and doors.■ Remove all people from the
danger zone.■ Notify your gas or electricity
supplier from outside the build-ing.
■ Shut off the electricity supply tothe building from a safe place(outside the building).
Safety instructions
Safety instructions
5614
625
GB
3
If you smell flue gas
DangerFlue gas can lead to life-threat-ening poisoning.■ Shut down the heating system.■ Ventilate the boiler room.■ Close all doors leading to the
living space.
Working on the system
■ When using gas as fuel, also close themain gas shut-off valve and safeguardagainst unauthorised reopening.
■ Isolate the system from the power sup-ply and check that it is no longer 'live',e.g. by removing a separate fuse or bymeans of a main isolator.
■ Safeguard the system against unau-thorised reconnection.
! Please noteElectronic modules can be dam-aged by electro-static dis-charges.Touch earthed objects, such asheating or water pipes, to dis-charge static loads.
Repair work
! Please noteRepairing components which ful-fil a safety function can compro-mise the safe operation of yourheating system.Replace faulty components onlywith original Viessmann spareparts.
Ancillary components, spare andwearing parts
! Please noteSpare and wearing parts whichhave not been tested togetherwith the heating system can com-promise its function. Installingnon-authorised components andnon-approved modifications/con-version can compromise safetyand may invalidate our warranty.For replacements, use only orig-inal spare parts from Viessmannor those which are approved byViessmann.
Safety instructions
Safety instructions (cont.)
5614
625
GB
4
Installation instructionsPreparing for installationApplication information......................................................................................... 5Installation site...................................................................................................... 5Installation of the wall mounting bracket.............................................................. 7
Service instructionsCommissioning and adjustmentCommissioning the Vitotrol 300 RF...................................................................... 14Checking the field strength of the radio signal at the installation site................... 19Establishing a wireless connection at a later date................................................ 20Changing the configuration of the heating circuits after commissioning.............. 21Terminating configuration..................................................................................... 22
TroubleshootingFault display......................................................................................................... 23
Specification....................................................................................................... 24
Parts listVitotrol 300 RF with table-top dock...................................................................... 25Vitotrol 300 RF with wall mounting bracket.......................................................... 26
Declaration of Conformity................................................................................. 28
Index
Index
5614
625
GB
5
Vitotrol 300 RF with integral wirelesstransmitter for operation with the wire-less base station (accessory forVitotronic boiler and heating circuit con-trol units) and with Vitotronic 200 RF,type HO1C.
Up to three heating circuits can be oper-ated with one Vitotrol 300 RF; alterna-tively one Vitotrol 300 RF can beemployed for each heating circuit in asingle heating system.
Installation site
■ Vitotrol 300 RF with table-top dock■ Vitotrol 300 RF with wall mounting
bracket
Operation with or without room temperature hook-up
■ Weather-compensated modeInstallation in any room (preferably inthe main living room).
■ Operation with room temperaturehook-up (also see illustration onpage 7)The integral room temperature sensorcaptures the actual room temperatureand effects any necessary correctionof the flow temperature.The captured room temperature isdependent on the installation site:– On an internal wall in the main living
room, at a height of approx. 1.5 mfrom the floor.
– Not next to windows or doors.– Not above radiators.– Not on shelves, in recesses, etc.– Not near heat sources (direct sun-
light, fireplace, TV set, etc.).
Do not install further control devices inthis room. Any thermostatic radiatorvalves must always be fully opened.
Preparing for installation
Application information56
14 6
25 G
B
Inst
alla
tion
6
Wireless connection
Select the installation site of theVitotrol 300 RF so that the radio signalsare beamed as vertically as possiblethrough walls and floors to the wirelessbase station or Vitotronic 200 RF.
NoteConducting metallic materials (e.g.steel-reinforced concrete floors) have astrong negative effect on reception.
Prior to the final fitting, commission theVitotrol 300 RF and check the transmis-sion and reception quality at the intendedinstallation site.
Mittwoch 25.05.2011 13:42
Heizkreis 1 Menü
14° 20.5°
When looking for the right installationsite, a reception quality of at least threebars or –83 dBm should be displayed(see page 19).
Preparing for installation
Installation site (cont.)
5614
625
GB
7
1500
60
500
Preparing for installation
Installation of the wall mounting bracket56
14 6
25 G
B
Inst
alla
tion
8
GNYE
1.
2.
1/N230 V/50 Hz
230 V~
T40230 V~N L
4 V
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
9
230 V~
4 V
3.
4 V4 V
DC DC
230 V~
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
Inst
alla
tion
10
4.
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
11
7.
6.
DC
5.
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
Inst
alla
tion
12
7.
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
13
9.
8.
Preparing for installation
Installation of the wall mounting bracket (cont.)
5614
625
GB
Inst
alla
tion
14
Prior to commissioning, observe thefollowing:■ The wireless base station must be
connected to the control unit via KMBUS.
Separate installation and serv-ice instructions
■ The control unit to which the wireless
base station is connected must beswitched on.
■ Position the Vitotrol 300 RF for com-missioning close to the wireless basestation Vitotronic 200 RF.
■ Rechargeable batteries supply powerto the Vitotrol 300 RF. The table-topdock and wall mounting bracket arealso charging stations for the batteries.
NoteAs soon as there is a power supply tothe Vitotrol 300 RF, the commissioningassistant starts automatically.Charging batteries: See operatinginstructions for Vitotrol 300 RF.
Commissioning and adjustment
Commissioning the Vitotrol 300 RF
5614
625
GB
15
- +- +
1.
2.
Commissioning in connection with the wireless base station
1. Connect Vitotrol 300 RF to powersupply.The commissioning assistant startsautomatically.
Commissioning and adjustment
Commissioning the Vitotrol 300 RF (cont.)
5614
625
GB
Serv
ice
16
Select language
DE
DKDansk
Deutsch
GBEnglish
OK
Activate wireless connection
1. Initiate linking at the wireless base station or the heat source programming unit.2. Log on to the Vitotrol by pressing OK.
OK
2. Select language
NoteWhen the unit is first commissioned,"Select language [Sprache wäh-len]" is displayed in German .
"Activate wireless connection"appears.
A3. Press A on the wireless base sta-
tion:■ Operation without wireless
repeater: for 4 s.The green LED on the wirelessbase station flashes slowly.
■ Operation with wireless repeater:for 8 s.The green LED on the wirelessbase station flashes quickly.
4. On the Vitotrol 300 RF, touch "OK".The Vitotrol 300 RF transmits a signalto log on to the wireless base sta-tion.
Commissioning and adjustment
Commissioning the Vitotrol 300 RF (cont.)
5614
625
GB
17
Input wireless codeEnter wireless code and confirm with OK.
OK
000
5. Enter 3-digit PIN code.■ The PIN code is printed on the pro-
tective foil on the front of the wire-less base station.Make a note of it here _ _ _If the protective foil has beenremoved, use the PIN code given inthe installation and service instruc-tions for the wireless base station.
■ Use / to enter the PIN code.■ Confirm the PIN code with "OK".
NoteIf logging on was not successful:
Fault
In this case, activate the RF connec-tion again (see step 3).
Heating circuit selection
OK
Heating circuit 3 ç
Heating circuit 2 ç
Heating circuit 1
6. Select heating circuits that should beoperated via the Vitotrol 300 RF, andconfirm with "OK".Initialisation bar is running (can takeapprox. 5 min).After successful initialisation, thestandard menu appears.
NoteRadio transmission can take sometime, so there may be a delay in thedisplay of symbols.
Commissioning and adjustment
Commissioning the Vitotrol 300 RF (cont.)
5614
625
GB
Serv
ice
18
Commissioning in connection with Vitotronic 200 RF, type HO1C
1. Connect Vitotrol 300 RF to powersupply.The commissioning assistant startsautomatically.
Select language
DE
DKDansk
Deutsch
GBEnglish
OK
Activate wireless connection
1. Initiate linking at the wireless base station or the heat source programming unit.2. Log on to the Vitotrol by pressing OK.
OK
2. Select language.
NoteWhen the unit is first commissioned,"Select language [Sprache wäh-len]" is displayed in German .
"Activate wireless connection"appears.
3. On the Vitotrol 300 RF, touch "OK".The Vitotrol 300 RF transmits a signalto log on to the Vitotronic 200 RF.
Input wireless codeEnter wireless code and confirm with OK.
OK
000
4. Enter 3-digit PIN code. The PIN codeis displayed on theVitotronic 200 RF.
NoteIf logging on was not successful:
Fault
In this case, activate the RF connec-tion again (see step 3).
Commissioning and adjustment
Commissioning the Vitotrol 300 RF (cont.)
5614
625
GB
19
Heating circuit selection
OK
Heating circuit 3 ç
Heating circuit 2 ç
Heating circuit 1
5. Select heating circuits that should beoperated via the Vitotrol 300 RF, andconfirm with "OK".Initialisation bar is running (can takeapprox. 5 min).After successful initialisation, thestandard menu appears.
NoteRadio transmission can take sometime, so there may be a delay in thedisplay of symbols.
Checking the field strength of the radio signal at the installationsite
NoteWhen using the wall mounting bracket,check before installation whether thefield strength of the radio signal is satis-factory.
If the field strength is unsatisfactory,either select another location or use awireless repeater (accessory).
Display of the field strength in thestandard menu
Wednesday 25.05.2011 13:42
Heating circuit 1 Menu
14° 20.5°
Scanning and display of the fieldstrength in the extended menu1. "Menu"2. "Settings"3. "Configuration"
ConfigurationEnter wireless code and confirm with OK .
OK
000
Commissioning and adjustment
Commissioning the Vitotrol 300 RF (cont.)
5614
625
GB
Serv
ice
20
4. Enter the PIN code (see page 17/ 18)and confirm with "OK".
5. "Field strength subscriber"
Field strength subscriber
Remote control dBm>-79
Wireless base station dBm>-82
Outside temperature sensor dBm>-76
■ "Remote control"Radio path between wireless basestation and Vitotrol 300 RF
■ "Wireless base station"Radio path betweenVitotrol 300 RF and wireless basestation
■ "Outside temperature sensor"Radio path between wireless out-side temperature sensor andVitotrol 300 RF
StandardmenuSymbol
ExtendedmenuValue in dBm
Field strength of the radio signal (transmis-sion and reception quality)
0 to - 78 very good- 79 to - 83 good- 84 to - 87 adequate- 88 to - 91 inadequate- 92 to - ∞ no reception
Establishing a wireless connection at a later date
Extended menu1. "Menu"2. "Settings"3. "Configuration"
ConfigurationEnter wireless code and confirm with OK .
OK
000
4. Enter the PIN code (see page 17/ 18)and confirm with "OK".
Configuration
Field strength subscriber
Heating circuit selection
Activate wireless connection
Commissioning and adjustment
Checking the field strength of the radio signal… (cont.)
5614
625
GB
21
5. "Activate wireless connection"
Activate wireless connection
1. Initiate linking at the wireless base station or the heat source programming unit.2. Log on to the Vitotrol by pressing OK.
OK
With wireless base station, seepage 16.With Vitotronic 200 RF, see page 18.
6. On the Vitotrol 300 RF, touch "OK".Initialisation bar is running (can takeapprox. 5 min).After successful initialisation, thestandard menu appears.
Changing the configuration of the heating circuits after com-missioning
Subsequent addition (e.g. after build-ing an extension) or removal of heat-ing circuits:
Extended menu1. "Menu"2. "Settings"3. "Configuration"
ConfigurationEnter wireless code and confirm with OK .
OK
000
4. Enter the PIN code (see page 17/ 18)and confirm with "OK".
Configuration
Field strength subscriber
Heating circuit selection
Activate wireless connection
5. "Heating circuit selection"
Commissioning and adjustment
Establishing a wireless connection at a later… (cont.)
5614
625
GB
Serv
ice
22
6. Select heating circuits that should beoperated via the Vitotrol 300 RF, andconfirm with "OK".
Heating circuit selection
OK
Heating circuit 3 ç
Heating circuit 2 ç
Heating circuit 1
7. Initialisation bar is running (can take
approx. 5 min).After successful initialisation, thestandard menu appears.
Terminating configuration
The "Configuration" menu is automat-ically terminated after 30 min or via the"Terminate configuration?" menu.
Extended menu:1. "Menu"2. "Settings"3. "Terminate configuration?"4. "OK" to confirm.
Commissioning and adjustment
Changing the configuration of the heating… (cont.)
5614
625
GB
23
Heating system fault
Display:
Fault
OK
For troubleshooting, see theinstallation and service instruc-tions of the relevant control unit.
Wireless connection fault
Display:
Fault
For troubleshooting, log components offand then back on again. If required, usewireless repeaters (accessories).
Installation and service instruc-tions for the wireless base stationor the boiler.
Troubleshooting
Fault display56
14 6
25 G
B
Serv
ice
24
Power supply unit ■ With table-top dock 230 V~/5 V−■ With wall mounting bracket 230 V~/4 V−Batteries NiMH AA HR6 Mignon
1.2 V–, 2100 mAhBattery life Approx. 500 heating cyclesOperational duration with batteries Approx. 3 hRadio frequency 868.3 MHzWireless protocol EnOceanWireless range See "Wireless accessories" tech-
nical guideSafety category IIIP rating IP 30 to EN 60529Permissible ambient temperature■ During operation 0 to +40 °C■ During storage and transport −25 to +60 °CSet room temperature setting range 3 to 37 °C
Specification
Specification
5614
625
GB
25
The following information is required:■ Serial no. (see type plate)■ Position number of the part (from this
parts list)
Standard parts are available from yourlocal supplier.
Parts0001 Programming unit0002 Table-top dock
0003 USB cable0004 Plug-in power supply unit0005 Installation and service instruc-
tions0006 Operating instructions
Parts list
Vitotrol 300 RF with table-top dock56
14 6
25 G
B
Serv
ice
26
0002
0005
0006
0001
0003
0004
Vitotrol 300 RF with wall mounting bracket
The following information is required:■ Serial no. (see type plate)■ Position number of the part (from this
parts list)
Standard parts are available from yourlocal supplier.
Parts list
Vitotrol 300 RF with table-top dock (cont.)
5614
625
GB
27
Parts0001 Programming unit0002 Wall mounting bracket0003 Power supply unit
0005 Installation and service instruc-tions
0006 Operating instructions
0002
0005
0006
0001
0003
Parts list
Vitotrol 300 RF with wall mounting bracket (cont.)
5614
625
GB
Serv
ice
28
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm as sole respon-sible body that the product Vitotrol 300 RF complies with the following standards:
EN 301489-1 EN 300220EN 301489-3 EN 60730EN 55014-1 EN 60730-2-9EN 55014-2 EN 61000-3-2EN 55022 EN 62233
In accordance with the following Directives, this product is designated with _:
1999/5/EG2004/108/EG2006/95/EG
Allendorf, 01 March 2012 Viessmann Werke GmbH&Co KG
Authorised signatory Manfred Sommer
Applicability
Serial No.:7501915 7501916
Viessmann LimitedHortonwood 30, TelfordShropshire, TF1 7YP, GBTelephone: +44 1952 675000Fax: +44 1952 675040E-mail: [email protected]
Viessmann Werke GmbH&Co KGD-35107 AllendorfTelephone: +49 6452 70-0Fax: +49 6452 70-2780www.viessmann.com