Veris Differential Pressure Transducer Connection Instructions For use with HOBO ® H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes Applies to these Veris Differential Pressure Transducers: Onset Part No. Air Pressure Range Output Veris Part No. T-VER-PXU-L 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXULX05S (LCD display) T-VER-PXU-X 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXUXX05S (no display) This document provides instructions on connecting the Veris Differential Pressure Transducers listed above to each of the following: FlexSmart Analog Module used with HOBO H22 series data loggers Analog Sensor Port/Module used with HOBO U30 and RX3000 series data loggers Voltage adapter used with the U12 and UX120-006M data loggers and ZW series data nodes It also lists configuration values used by HOBOware ® software to configure the logger for each transducer. Note: For information on connecting the differential pressure transducer to the pressure source, and other transducer details, refer to the documentation provided by Veris. Required Selected Veris Differential Pressure Transducer HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW series) HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M); HOBOware Pro 3.0 or higher for ZW series HOBOlink (for RX3000 series data loggers) Customer-supplied length of 18 AWG, shielded, multi-conductor cable Connecting the Differential Pressure Transducer to the Analog Module or Port HOBO H22 Series Data Logger S-FS-CVIA FlexSmart Analog Module Customer-supplied 18 AWG shielded multi-conductor cable Differential Pressure Transducer Shld S1+ S1- Exc+ Exc- S2+ S2- Conductor Conductor POWER/4-20mA OUT (0-10V) COM Terminal Block inside transducer housing f or 4-20mA Output ZERO N/C N/C N/C Conductor Conductor POWER/4-20mA OUT (0-10V) COM for 0-5V/0-10V Output ZERO N/C N/C Conductor FlexSmart Analog Module Terminal Block inside transducer housing Shld S1+ S1- Exc+ Exc- S2+ S2- FlexSmart Analog Module H22 Connection Veris Differential Pressure Transducer (Onset Part No. T-VER-PXU-L shown) Office: Jl. Radin Inten II No. 62 Duren Sawit, Jakarta 13440 - Indonesia Workshop: Jl. Pahlawan Revolusi No. 22B, Jakarta 13430 - Indonesia Phone: 021-8690 6777 (Hunting) Fax: 021-8690 6777 Mobile: +62 816 1740 8925 Fax: 021-8690 6771

Veris Differential Pressure Transducer Connection Instrutions · Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and

  • Upload
    doannhu

  • View
    235

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Veris Differential Pressure Transducer Connection Instrutions · Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and

Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes

Applies to these Veris Differential Pressure Transducers:

Onset Part No. Air Pressure Range Output Veris Part No.

T-VER-PXU-L 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXULX05S (LCD display)

T-VER-PXU-X 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXUXX05S (no display)

This document provides instructions on connecting the Veris Differential Pressure Transducers listed above to each of the following:

• FlexSmart™ Analog Module used with HOBO H22 series data loggers

• Analog Sensor Port/Module used with HOBO U30 and RX3000 series data loggers

• Voltage adapter used with the U12 and UX120-006M data loggers and ZW series data nodes

It also lists configuration values used by HOBOware® software to configure the logger for each transducer. Note: For information on connecting the differential pressure transducer to the pressure source, and other transducer details, refer to the documentation provided by Veris.

Required • Selected Veris Differential Pressure Transducer

• HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node

• FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW series)

• HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M); HOBOware Pro 3.0 or higher for ZW series

• HOBOlink (for RX3000 series data loggers)

• Customer-supplied length of 18 AWG, shielded, multi-conductor cable

Connecting the Differential Pressure Transducer to the Analog Module or Port

HOBO H22 Series Data Logger

S-FS-CVIAFlexSmart Analog Module

Customer-supplied 18 AWG shielded multi-conductor cable

Differential Pressure Transducer

Shl

dS

1+S

1-E

xc+

Exc

-S

2+S

2-

Conductor

Conductor

POWER/4-20mAOUT (0-10V)COM

Terminal Blockinside transducer housing

for 4-20mA Output

ZE

RO

N/CN/C

N/CConductor

Conductor

POWER/4-20mAOUT (0-10V)COM

for 0-5V/0-10V Output

ZE

RO

N/CN/C

Conductor

FlexSmart Analog Module

Terminal Blockinside transducer housing

Shl

dS

1+

S1-

Exc

+E

xc-

S2+

S2-

FlexSmart Analog Module

H22 Connection

Veris Differential Pressure Transducer(Onset Part No. T-VER-PXU-L shown)

Office: Jl. Radin Inten II No. 62 Duren Sawit, Jakarta 13440 - IndonesiaWorkshop: Jl. Pahlawan Revolusi No. 22B, Jakarta 13430 - IndonesiaPhone: 021-8690 6777 (Hunting)

Fax: 021-8690 6777Mobile: +62 816 1740 8925Fax: 021-8690 6771

Page 2: Veris Differential Pressure Transducer Connection Instrutions · Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and

Veris Differential Pressure Transducer Connection Instructions

Page 2 of 3

U30 or RX3000 Connection (U30 Shown)

Shi

eld

Ch1

Sig

nal

Ch1

Ret

urn

Exc

Out

Analog Sensor Port

Shi

eld

Ch2

Sig

nal

Ch2

Ret

urn

Ext

Re

turn

Conductor

Conductor

POWER/4-20mAOUT (0-10V)COM

for 4-20mA Output

ZE

RO

N/CN/C

N/C

for 0-5V/0-10V Output

Conductor

Conductor

POWER/4-20mAOUT (0-10V)COM

ZE

RO

N/CN/C

Conductor

Terminal Blockinside transducer housing

Terminal Blockinside transducer housing

Analog Sensor PortHOBO U30 Series Data Logger

Shi

eld

Ch1

Sig

nal

Ch1

Ret

urn

Exc

Out

Analog Sensor Port

Shi

eld

Ch2

Sig

nal

Ch2

Ret

urn

Ext

Re

turn

Differential Pressure Transducer

Customer-supplied 18 AWG shielded multi-conductor cable

ZW, U12, and UX120-006M Connection

Connect to analog port

HOBO ZW Series Wireless Data Node or U12 Series Data Logger(ZW shown)

AC-SENS-1*

*CAUTION: Polarity is very important! Before plugging AC-SENS-1 into AC power, make sure the correct polarity lead connections to device are made as shown!

POWER/4-20mAOUT (0-10V)COM

for 4-20mA Output

ZE

RO

for 0-5V/0-10V Output

Terminal Blockinside transducer housing

CABLE-4-20MA (for 4-20mA output) or CABLE-ADAP5 (for 0-5VDC output) orCABLE-ADAP10 (for 0-10VDC output)

Differential Pressure Transducer

AC-SENS-1*

(+)

(-)

Yellow (+)

Blue (-)

CABLE-4-20MA

POWER/4-20mAOUT (0-10V)COM

ZE

RO

Terminal Blockinside transducer housingAC-SENS-1*

(+)

(-)

White (+)

Black (-)

CABLE-ADAP5 or CABLE-ADAP10

(Red wire not used)

N/CN/C

N/CN/C

N/C

Use appropriate termination for connection (denoted with )

HOBO ZW Series Wireless Data Node; U12 or UX120-006M Logger

Page 3: Veris Differential Pressure Transducer Connection Instrutions · Veris Differential Pressure Transducer Connection Instructions For use with HOBO® H22, U12, U30, UX120-006M, and

Veris Differential Pressure Transducer Connection Instructions

Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software

HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values that these files contain. For information on loading configuration files, refer to the software documentation.

Onset Part Nos. Channel Name

Warm-Up Measurement Type

Raw Value 1

Raw Value 2

Raw Units

Scaled Value 1

Scaled Value 2

Scaled Units

T-VER-PXU-L and T-VER-PXU-X

Diff Pressure 20 sec Current 4 20 mA 0 0.1 (or 0.25, 0.5, 1, 2.5, 5, or 10)

in WC

Voltage 0 5 (or 10) V

Notes: • Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog

Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or UX120-006M.

• Both differential pressure transducer models have switch-selectable ranges and scales, as listed.