VCB Mechanical Operation Checks - FAT During FAT, there will be a Mechanical Operation Check to be done to ensure the mechanical operation and interlocking for the followings are in order : 1. VCB a. the breaker can be racked in and out smoothly b. when in the Connected Position : earth switch cannot be closed, control plug cannot be removed, when VCB closed - breaker cannot rack out, when VCB opened - breaker can rack out, VCB door cannot be opened c. when in Intermediate Position : VCB cannot be closed and control plug cannot be removed d. when in Disconnected Position : VCB door can be opened, earth switch can be closed and control plug can be removed Note : VCB cannot be connected when the VCB is closed, there is no control plug inserted, earth switch is closed and the door is opened.

VCB Mechanical Operation Checks

  • Upload
    ir-mrb

  • View
    132

  • Download
    3

Embed Size (px)

DESCRIPTION

operation check

Citation preview

Page 1: VCB Mechanical Operation Checks

VCB Mechanical Operation Checks - FAT

During FAT, there will be a Mechanical Operation Check to be done to ensure the mechanical operation and interlocking for the followings are in order :

1. VCB

a. the breaker can be racked in and out smoothly

b. when in the Connected Position : earth switch cannot be closed, control plug cannot be removed, when VCB closed - breaker cannot rack out, when VCB opened - breaker can rack out, VCB door cannot be opened

c. when in Intermediate Position : VCB cannot be closed and control plug cannot be removed

d. when in Disconnected Position : VCB door can be opened, earth switch can be closed and control plug can be removed

Note :

VCB cannot be connected when the VCB is closed, there is no control plug inserted, earth switch is closed and the door is opened.

2. EARTH SWITCH

a. it can be opened and closed smoothly

Page 2: VCB Mechanical Operation Checks

b. minimal rebounce on the blade

c. the padlock facility is provided

d. there is mechanical / electrcal interlock

3. SAFETY SHUTTER

a. smoothly open and close

b. the padlock facility is provided

c. latching facility provided

d. self-cancellation for latching facility in working condition

4. PT SHUTTER

a. smooth opening and closing

b. padlock facility provided

5. KEY INTERLOCKS

Page 3: VCB Mechanical Operation Checks

a. the key is released when breaker in disconnected position

b. VCB cannot rack in unless key is inserted

~ the above notes have been taken during my FAT at one of the well-known manufacturer of VCB in Malaysia

Posted by Ir. Fadzilayaty Ramli at 12:23 PM No comments:

Labels: HT, TnC, VCB

Sunday, December 5, 2010

Kerja-Kerja Pengujian di Tapak

Setelah semua peralatan di pasang di pencawang, kerja-kerja pengujian perlu di jalankan di tapak sebelum PE tersebut boleh ditauliahkan. Ujian –ujian ini adalah untuk mengesahkan bahawa kesemua peralatan elektrik adalah berada dalam keadaan normal dan sudah bersedia untuk dimulatugas.

Berikut pula adalah senarai ujian yang perlu dilakukan di tapak :

Page 4: VCB Mechanical Operation Checks

Posted by Ir. Fadzilayaty Ramli at 2:02 AM 2 comments:

Labels: EE, HT, LV, TnC

Friday, December 3, 2010

FAT

Kerja-kerja pengujian terbahagi kepada dua. Pertama adalah ujian rutin yang dilakukan di kilang (Factory Acceptance Test, FAT) di mana ujian tersebut akan disaksikan oleh pihak klien, kontraktor dan perunding. Kedua adalah ujian di tapak sebelum kerja-kerja pentauliahan dilaksanakan.

Berikut adalah senarai ujian rutin / semakan yang dijalankan semasa FAT :

Page 6: VCB Mechanical Operation Checks

Remote Control Panel (RCP) digunakan sebagai perkakasan untuk melakukan pensuisan. Dengan adanya RCP ini, setiap operasi VCB (ON, OFF) dapat dilakukan pada panel lain yang ditempatkan berdekatan dengan pintu di dalam bilik 11KV Switchgear.

Dengan adanya RCP ini, keselamatan pengendali akan lebih terjamin dan segala urusan pengsuisan dapat dijalankan dengan lebih mudah iaitu dengan hanya perlu menekan butang ON/OFF sahaja.

Posted by Ir. Fadzilayaty Ramli at 1:29 AM No comments:

Labels: Design, HT, RCP

Sunday, September 26, 2010

Sistem Perlindungan

Page 8: VCB Mechanical Operation Checks

Arus (I) maksimum bagi keseluruhan beban pada voltan rendah adalah :

Untuk mendapatkan saiz TX

Page 9: VCB Mechanical Operation Checks

Oleh itu parameter TX yang dipilih adalah seperti berikut:

Page 10: VCB Mechanical Operation Checks

Posted by Ir. Fadzilayaty Ramli at 10:09 PM No comments:

Labels: Design, HT, TX

Sunday, August 22, 2010

Kenapa 2no. TX dan Bukan 1?

Kenapa kadang kala pihak perunding merekabentuk 2nos TX walaupun mengikut kiraan hanya 1no. diperlukan. Di antara sebab-sebabnya adalah seperti berikut :

meningkatkan kebolehharapan (reliability) sistem - masih boleh membekalkan bekalan elektrik sekiranya salah satu dari TX tersebut rosak

memanjangkan jangkahayat TX - hanya 50% - 70%dari keupayaan TX digunakan

menampung keperluan beban akan datang

Walau bagaimanapun, semuanya bergantung kepada bajet klien dan sama ada sesuatu pemasangan itu kritikal (contoh: hospital) atau tidak.

Posted by Ir. Fadzilayaty Ramli at 11:26 PM No comments:

Labels: Design, HT, TX

Thursday, July 29, 2010

Pemilihan Saiz VCB

Pemilihan saiz VCB adalah bergantung kepada kadaran voltan VCB itu dan arus ketahanan VCB itu membuka litar sekiranya arus litar pintas wujud (short circuit current).Melalui rumus

Berikut adalah nilai short circuit current yang dikehendaki oleh TNB bagi sistem bekalan elektrik di negara ini :

Page 12: VCB Mechanical Operation Checks

Vacuum Circuit Breaker (VCB) ialah salah satu alat pemutus voltan tinggi (VT). Ciri-ciri yang terdapat pada VCB adalah :

a) Menggunakan vakum sebagai medium untuk mematikan arka semasa kerja-kerja pensuisan dijalankan. Ini akan mengurangkan risiko berlakunya kebakaran.

b) Memutuskan litar dengan selamat sekiranya berlaku kerosakan / litar pintas / arus lampau.

c) Boleh membuka dan menutup litar dalam keadaan biasa dan bila berlaku kerosakan.

d) Mudah dari segi penyelenggaraan.

e) Mudah diperolehi di pasaran.

Pemilihan saiz VCB adalah bergantung kepada kadaran voltan VCB itu dan arus ketahanan VCB itu membuka litar sekiranya arus litar pintas wujud (short circuit current).

Posted by Ir. Fadzilayaty Ramli at 1:12 AM No comments:

Labels: CB, Design, HT, VCB

Tuesday, June 15, 2010

Pemilihan Kabel Voltan Tinggi (VT)

Pemilihan kabel VT juga bergantung kepada sistem agihan (saiz arus, voltan, bilangan fasa dan susut voltan) serta pepasangan (cara pepasangan dan lokasi kabel). Walau bagaimanapun, kesan susut voltan (voltage drop) tidak diambilkira kerana voltan yang diterima boleh diubah di TX melalui tap-changer.

Bagi sistem VT , pemilihan saiz kabel ditumpukan kepada dua (2) faktor utama :a) keupayaan membawa arusb) kapasiti arus litar pintas

Terdapat dua (2) jenis konduktor yang terdapat di pasaran iaitu jenis copper (Cu.) dan aluminium (Al.).

Berikut adalah perbandingan di antara kedua-dua jenis kabel :

Page 13: VCB Mechanical Operation Checks

Posted by Ir. Fadzilayaty Ramli at 12:33 AM No comments:

Labels: Cable, Design, HT

Sunday, May 30, 2010

Perkakas Suis Voltan Tinggi (VT)

Perkakas suis VT ataupun juga dikenali sebagai pemutus litar VT merupakan peranti pensuisan mekanikal yang berupaya membawa, menerima dan mematikan arus dalam keadaan normal dan tidak normal yang terkawal (ditetapkan).

Perkakas suis VT diklasifikasikan mengikut medium apa yang digunakan untuk menghilangkan atau memadamkan arka. Terdapat pelbagai jenis perkakas suis di pasaran.

Contohnya Oil Circuit Breaker, Air Circuit Breaker, Gas Circuit Breaker dan Vacuum Circuit Breaker (VCB).

Posted by Ir. Fadzilayaty Ramli at 2:35 AM No comments:

Labels: CB, Design, HT

Saturday, April 24, 2010

Alatubah (Transformer, TX)

Alatubah (transfomer, TX) merupakan alat elektrik yang boleh menukarkan voltan dari tinggi ke rendah dan dari rendah ke tinggi pada ulangan yang sama (same frequency).

Terdapat dua jenis TX yang terdapat di pasaran iaitu jenis kering (cast resin TX) dan jenis minyak (oil immersed TX). Pemilihan jenis TX selalunya bergantung kepada saiz serta tempat pemasangan serta ciri-ciri bagi kedua-dua TX tersebut.

Berikut adalah perbandingan di antara kedua-dua jenis TX:

Page 14: VCB Mechanical Operation Checks

Posted by Ir. Fadzilayaty Ramli at 2:18 AM No comments:

Labels: Design, HT, TX

Saturday, March 27, 2010

Rekabentuk Terperinci Untuk Sebuah Pencawang 11KV

Dalam merekabentuk sistem 11KV bagi sesebuah pencawang, terdapat beberapa komponen yang perlu dikenalpasti dah diambilkira. Berikut adalah komponen-komponen tersebut berserta pilihan peralatan yang terdapat di pasaran yang boleh digunapakai dalam sesuatu pemasangan :

1. Punca Bekalan 11KV- Pencawang Masuk Utama (PMU)- Stesen Suis Utama (SSU)- Pencawang Elektrik (PE)

2. Keperluan Beban- Kehendak Maksimum (Maximum Demand) dalam

Page 15: VCB Mechanical Operation Checks

a) Kilo Watt (KW)b) Ampere (A)c) KVA

3. Pemilihan Perkakas Suis Voltan Tinggi- Perkakas Suis (Switchgear) – Vacuum Circuit Breaker (VCB), Air Circuit Breaker (ACB), Oil Circuit Breaker (OCB) dan Gas Insulated Switchgear (GIS).- Ring Main Unit (RMU)

4. Pemilihan Alatubah- Oil Transformer- Cast Resin Transformer

5. Pemilihan Kabel Voltan Tinggi- Aluminium (Al.)- Copper (Cu.)

6. Papan Suis Voltan Rendah - LV Board- Papan suis utama (Main switch board) - MSB- Sub-Switch board - SSB- Distribution Board - DB

7. Kabel Voltan Rendah- Aluminium (Al.)- Copper (Cu.)

8. Auxiliary Supply - Bekalan DC- Bekalan AC- Bekalan dari Janakuasa tunggu sedia

9. Sistem Perlindungan- Tx Relay- OC/EF Relay- Sistem Pembumian- Sistem Pelindung Kilat

10. Pensuisan- Remote Control panel (RCP)

Posted by Ir. Fadzilayaty Ramli at 1:24 AM No comments:

Labels: Design, HT

Wednesday, January 20, 2010

Page 16: VCB Mechanical Operation Checks

Contoh Skop Kerja: Pencawang Elektrik 11KV di USIM, Bandar Baru Nilai.

Sebagai seorang Jurutera Kanan Elektrik bagi SAFF Consultants, saya telah ditugaskan untuk mengendalikan projek ini dari awal sehingga pencawang tersebut ditauliah dan dimulatugas.

Berikut adalah ringkasan skop kerja yang telah dilakukan :

1. Rekabentuk Awalan- Mendapatkan saiz beban dari USIM (untuk Fakulti Ekonomi dan Muamalat) dan dari perunding M&E voltan rendah (bagi Pusat Komersil dan Dataran Selera).- Mengenalpasti skop kerja dengan membuat perbincangan dengan pihak USIM dan perunding bangunan.

2. Rekabentuk Terperinci- Melakukan kerja-kerja pengiraan bagi mengenalpasti saiz alat suis voltan tinggi, saiz alatubah, saiz kabel serta setiap komponen yang terlibat.- Mengkaji dan menilai jenis-jenis perkakasan yang terdapat di pasaran untuk dimasukkan dalam tender.

3. Pemanggilan Tender- Menyediakan dokumen tender yang terdiri daripada lukisan tender, jadual kadar harga serta spesifikasi tender.- Membuat anggaran harga projek.

4. Penilaian Tender- Menilai dari segi teknikal kesemua dokumen tender yang telah dihantar oleh kontraktor.- Membuat laporan penilaian tender dari segi teknikal dan mencadangkan nama kontraktor yang telah berjaya.

5. Kerja-kerja Pembinaan Bermula di Tapak- Menyediakan dokumen kontrak.- Menyelia pemasangan di tapak dan memastikan semua kerja yang dijalan oleh kontraktor yang telah dilantik mengikut spesifikasi dan skop kerja sepertimana di dalam kontrak.- Menyemak dan memberi kelulusan bagi bahan yang dicadangkan oleh kontraktor dan lukisan syop yang dikemukakan oleh kontraktor. - Membuat kerja-kerja penilaian di tapak serta menyediakan sijil untuk bayaran kemajuan kerja kontraktor.

6. Kerja-kerja Pengujian- Menghadiri segala pengujian yang terdapat di dalam kontrak (ujian di kilang dan ujian di tapak).- Memastikan segala ujian yang dijalankan adalah lengkap dan betul serta mengikut prosedur.- Menyemak keputusan ujian yang dijalankan.

7. Kerja-kerja Pentauliahan- Memastikan kesemua kerja-kerja yang terdapat di dalam kontrak dilakukan oleh pihak kontraktor.

Page 17: VCB Mechanical Operation Checks

- Memastikan kesemua dokumen yang berkaitan dikemukakan oleh pihak kontraktor sebelum kerja-kerja pentauliahan dilakukan.- Menyediakan senarai kecacatan kerja.- Mencadangkan CPC kepada pihak USIM.- Menyediakan akaun muktamad projek serta Arahan Perubahan Kerja (sekiranya ada). - Mengemukakan CMGD kepada kontraktor.