MODUCONTROL

ELECTRONIC REGULATION

SERVICE MANUAL

��

santinello
Casella di testo
software 4.2
Page 2: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Service manual Technical specification Modu_control ANR ANL ANLI ANF ANK

Pag. 1/2

Edition 1.3 Date 20 September 2010 Author SAT

Modu_Control software update version 4.2

With the software version 4.2 in production from September 2010 some new features were introduced as listed below:

1. Installer Menu (pwd 30)

N Description Name Min Default Max Meaning

Inlet/outlet

0 0 2

If 0, the unit works with inlet water temperature regulation. If 1 the unit works with outlet water temperature regulation. If 2 (new) the unit works according to water temperature measured by the sensor of VMF-ACS in the plant buffer tank. (in case of failure of this sensor, the probe in the unit will be used, and an alarm 157 will be activated.) If the production of hot water is activated, the regulation is automatically forced to outlet water temperature irrespective of the value of this parameter.

Table 1 - Set menu installer

2. Advanced reading Menu (pwd 10)

This menu contains further information about the unit operation, in addition to that in the main reading menu. N Description Name Meaning

5 dHt Water temperature of the plant buffer tank

Water temperature of the plant buffer tank measured by the VMF-ACS sensor.

Table 2 – Second reading menu (displaying only)

Page 3: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Service manual Technical specification Modu_control ANR ANL ANLI ANF ANK

Pag. 2/2

Edition 1.3 Date 20 September 2010 Author SAT

3. Installer Menu 2 (pwd 31) N Name Min Default Max Meaning

3 Pump Switch OFF by thermostat

0 0 1

0 = The pump is always working even upon reaching the set point. 1 = The pump is switched Off when the set point is reached. (when this option is activated, the regulation is forced to the inlet water temperature). This parameter is shown only with inlet water temperature regulation (parameter 0 (pwd 30) =1 or 2).

Table 3 – Second installer menu

4. Maintenance Menu 2 (pwd 84)

N Nome Min Default Max Meaning

0 Number of prealarms (thousand)

0 0 999 Reading only. Contains the total number (in thousands) of warnings from the first installation of the card.

1 Number of prealarms (units)

0 0 999 Reading only. Contains the total number (in units) of warnings from the first installation of the card.

2 Number of alarms (thousand)

0 0 999 Reading only. Contains the total number (in thousand) of alarms from the first installation of the card.

3 Number of alarms (units)

0 0 999 Reading only. Contains the total number (in units) of alarms from the first installation of the card.

Table 4 – Second maintenance menu

5. Electric heater management

The temperature control is according to the value of the parameter 0 (pwd 30). Previously it was only in

relation to the outlet temperature.

6. Domestic hot water management

In case of DHW enabling, the regulation is automatically forced to the outlet water temperature,

independently from the value of the parameter 0 (pwd 30).

Page 4: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

ANK dip switches setting

DIP UNIT VERSION Description 1 H ON: heat pump version 2 ALL ON: Defrost by reversing

cycle 3 Y,Z ON: To adjust antifreeze

setpoint 4 OFF only 5 ALL ON: safety partial. activated 6 A ON: Low water volume

content 7 With DCPX ON: fan speed control

activated 8 OFF 9 OFF 10 OFF 11 Not used 12 Not used

Trasducers dip switches setting table

1 ALL OFF: LP trasducer ratiometric type

2 ALL OFF: HP trasducer ratiometric type

ANK parameters configuration:

Group Unit version to adjust default

software settings

To activate: Parameter to change

Menù

A All version with integrated electric heaters

To enable electric heaters

PAR (8) = 1 INSTALLER Psw(30)

B With antifreeze heater on

basement/dip tray

To enable antifreeze

basement-dip tray electric

heater

PAR (1) = 2 INSTALLER 2 Psw(31)

C With Smart starter

mounted

Set the delay time to restart

compressor after power

failure

Smart starter Gavazzi (RSBS2325A2V12C24)

PAR (t) = 60

COMPRESSOR Psw(72)

Page 5: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

To set HP differential

alarm

PAR (2) = 0.5 FACTORY Psw(125)

To set high discharge gas temperature

PAR (6) = 110 FACTORY Psw(125)

To set end defrost

temperature

PAR (9) = 20 MAINTENANCEPsw(83)

To set max time to reverse

the cycle

PAR (C) = 600 MAINTENANCEPsw(83)

To set force off PAR (2) = 63 INSTALLER Psw(30)

To set low external

temperature limit

PAR (o) = - 20 INSTALLER Psw(30)

To set low water

temperature limit

PAR (p) = 53 INSTALLER Psw(30)

To set high water

temperature limit

PAR (r) = 62 INSTALLER Psw(30)

To set max set point limit in

heating

PAR (t) = 60 INSTALLER Psw(30)

D

ALL

To set 3 way valve logic

PAR (3) = 1 MAINTENANCE 2

Psw(333)

Page 6: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Menù USER (pwd 000) Passw N° Abbrev. ver.4.2 Tandem100-150-200

DREGavazzi

DREEmerson

0 DefaultFunc. Mode 0 0 Sta 0Cooling Set (°C) 0 1 Stf 7Diff. Cooling (°C) 0 2 bnF 5Heating Set (°C) 0 3 StC 45Diff. Heating (°C) 0 4 bnC 5Compensation Set 0 5 CSt 0Cool Set 1 (°C) 0 6 SF1 12TAE cool 1 (°C) 0 7 Tf1 18Cool Set 2 (°C) 0 8 SF2 7TAE cool 2 (°C) 0 9 tF2 30Heating Set 1 (°C) 0 A SC1 45TAE heat 1 (°C) 0 b tC1 0Heating Set 2 (°C) 0 C SC2 35TAE heat 2 (°C) 0 d tC2 18HDW Set point (°C) 0 E SAS 50Diff. HDW (°C) 0 F bAS 10Menù Resistance (pwd 1) 1Antifreeze heater Set (°C) 1 0 SrA 4Diff. Antifreeze heater Set (°C) 1 1 brA 1Electric heaters Set (°C) 1 2 Sri 3Diff. Electric heaters Set (°C) 1 3 bri 4TAE Set 1 (°C) 1 4 tA1 5TAE Set 2 (°C) 1 5 tA2 -30TAE Diff. (°C) 1 6 bA 22nd Menù readings (pwd 10) 10Inverter current 10 0 CorInverter voltage output 10 1 UoBus voltage 10 2 UobInverter voltage dissipator (only model APY) 10 3 HStDiFF dynamic Force OFF 10 4 dFoMenù installer (pwd 30) 30In / Out 30 0 i-u 0Cooling Force off (°C) 30 1 oFF 4Heating Force off (°C) 30 2 oFC 54Diff. force off, (°C) 30 3 SAF 5Integral time (sec) 30 4 int 600Derivativ time (sec) 30 5 dEr 0Antifreeze setpoint (°C) 30 6 AG 3Frost protection 30 7 FrP 3Electric heating Resistence 30 8 rin 0Remote panel Config 30 9 PAn 0HDW 30 A ASA 1Capacity in HDW mode (%) 30 b ASP 70Delay time IN-OUT from/To HDW (sec) 30 C AAS 0TRA 30 d trA 0Enable bypass flow switch 30 E bAF 0Time by-pass flow switch (sec) 30 F tbF 180Standby from high TAE (ext air temp) 30 G OAE 45High water temp IN 30 H Ati 64Config screensaver 30 I SCr 1

VisentinG
Casella di testo
ANL
Page 7: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Modbus Supervisor address 30 J Ad1 1Bauderate Supervisor 30 L Bd1 1Enable writing by supervisor 30 Π AS1 0Limit Temp air 1 30 o LA1 -15Limit Temp water 1 30 P St1 43Limit Temp air 2 30 q LA2 -10Limit Temp water 2 30 r St2 58Max heating setpoint limit 30 t LSP 55Menù installer 2 (pwd 31) 31T Delta reset after OFF by ForceOff dynamic (°C) 31 0 - 6Config Heating Cable 31 1 - 0Heating cable Set point (°C) 31 2 - 0Stop unit water pump by setpoint 31 3 - 0Menù Maintenance (pwd 83) 83Tae enable defrost (°C) 83 0 - 10T air exch enable defrost (°C) 83 1 - -2P delta (bar) 83 2 - 0.4P delta end injections (bar) 83 3 - 0.3time stable pressure (sec) 83 4 - 300time timeout low water temp (sec) 83 5 - 900time min injection (sec) 83 6 - 120time max injections (sec) 83 7 - 300Max exits per time 83 8 - 3Temp end defrost by 4way valve (°C) 83 9 - 12Pressure to force defrost by 4 way valve (bar) 83 A - 2.8Time min 4way valve (sec) 83 b - 120Time max 4 way valve (sec) 83 C - 300Time min between two 4 way cycles (min.) 83 d - 20Time max functioning without defrost (min) 83 E - 240Press Set DCPX in heating (bar) 83 F - 30Press Diff. DCPX in heating (bar) 83 G - 5TAE min DCPX (°C) 83 H - -5TAE max DCPX (°C) 83 I - 40P set min (bar) 83 J - 18P set max (bar) 83 L - 18P band T min (bar) 83 Π - 17P band T max (bar) 83 o - 12Volt signal min to DCPX 83 P - 1.5Pressure control during defrost (bar) 83 q - 30Diff. Pressure control during defrost (bar) 83 r - 5Pressure to enable only defrosts by 4way valve (bar 83 t - 4 5.5Min discharge temp to force defrost by 4 way valve ( 83 u - 50Max FL prealarms 83 y - 02nd Menù Maintenance (pwd 84) 84prealarms number (thousand) 84 0 -prealarms number (unit) 84 1 -alarms number (thousand) 84 2 -alarms number (unit) 84 3 -Menù Factory (pwd 125) 125Factory reset 125 0 - 0Config. Pressure trasducer 125 1 - 0Differential HP safety injection 125 2 - 1Differential LP safety injection 125 3 - 0.1

Page 8: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Differential TGP safety injection 125 4 - 5Max injections number 125 5 - 5Tgp alarm (°C) 125 6 - 135Temp Diff. To alarm reset (°C) 125 7 - 10HP pressure alarm (bar) 125 8 - 40.5LP pressure alarm in cooling (bar) 125 9 - 4LP alarm in heating 125 A - 2LP diff. To alarm reset 125 b - 2Timeout alarm 125 C - 60Max prealarms 125 d - 5Decrement alarm (h) 125 E - 1Delta T capacity control 125 F - 1Timeout capacity control (sec) 125 G - 150Antifreeze/LP timeout (sec) 125 H - 180Time before to activate 4way valve (sec) 125 I - 15Differential to antifreeze reset (°C) 125 J - 1Menù compressor and pump (pwd 72) 72Percentage 2nd compressor (%) 72 0 CPA 0 50Min. cp working time (sec) 72 1 On 120Min cp off time (sec) 72 2 OFF 180Start up max per hour 72 3 SPn 12Timeout between two compressor start up 72 4 int 30Start up timeout to probes temp control 72 5 PPc 150Timeout for FL alarm 72 6 FL 5Start up FL timeout 72 7 APP 40Water pump off time (sec) 72 8 PP 120Pulldown (°C) 72 9 PLd 1Cp timeout after a power failure 72 t Stt 0 60 180Menù Maintenance 2 (pwd 333) 333Delta P to activate 4 way valve (bar) 333 0 1Timeout delta P after CP1 On (sec) 333 1 15Timeout delta P after CP2 On (sec) 333 2 154 way valve logic 333 3 0Unit only heat pump version 333 4 0

DIP position Defau

ltH

Version Y/ZA

version DCPX ANL-C1 ON2 OFF3 ON4 ON5 OFF6 ON7 ON8 OFF9 OFF10 ON11 OFF12 OFF

DIP trasducer1 OFF2 OFF

Page 9: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Passwo N° Sigla ver.4.2 ANK KR DREMenù set utente (pwd 000) 0 Default Tutti Min MaxFunc. Mode 0 0 Sta 0 0 1Cooling Set (°C) 0 1 Stf 7 -20 26Diff. Cooling (°C) 0 2 bnF 5 1 20Heating Set (°C) 0 3 StC 45 25 55/70Diff. Heating (°C) 0 4 bnC 5 1 20Compensation Set 0 5 CSt 0 0 3Cool Set 1 (°C) 0 6 SF1 12 -20 26TAE cool 1 (°C) 0 7 Tf1 18 -40 50Cool Set 2 (°C) 0 8 SF2 7 -20 26TAE cool 2 (°C) 0 9 tF2 30 -40 50Heating Set 1 (°C) 0 A SC1 45 15 70TAE heat 1 (°C) 0 b tC1 0 -40 50Heating Set 2 (°C) 0 C SC2 35 25 65TAE heat 2 (°C) 0 d tC2 18 -40 50HDW Set point (°C) 0 E SAS 50 25 65Diff. HDW (°C) 0 F bAS 10 1 20Menù Resistance (pwd 1) 1Antifreeze heater Set (°C) 1 0 SrA 4 -20 50Diff. Antifreeze heater Set (°C) 1 1 brA 1 0.3 10Electric heaters Set (°C) 1 2 Sri 3 0 70Diff. Electric heaters Set (°C) 1 3 bri 4 0 20TAE Set 1 (°C) 1 4 tA1 5 -40 50TAE Set 2 (°C) 1 5 tA2 -30 -40 50TAE Diff. (°C) 1 6 bA 2 0 202nd Menù readings (pwd 10) 10Inverter current 10 0 CorInverter voltage output 10 1 UoBus voltage 10 2 UobInverter voltage dissipator (only model APY) 10 3 HStDiFF dynamic Force OFF 10 4 dFoRemote sensor value 10 5 dHtMenù installer (pwd 30) 30In / Out 30 0 i-u 0 0 2Cooling Force off (°C) 30 1 oFF 4 -25 25Heating Force off (°C) 30 2 oFC 54 63 30 70Diff. force off, (°C) 30 3 SAF 5 0.5 20Integral time (sec) 30 4 int 600 0 999Derivativ time (sec) 30 5 dEr 0 0 120Antifreeze setpoint (°C) 30 6 AG 3 -50 20Frost protection 30 7 FrP 3 0 4Electric heating Resistence 30 8 rin 0 0 4Remote panel Config 30 9 PAn 0 0 3HDW 30 A ASA 1 0 1Capacity in HDW mode (%) 30 b ASP 70 0 100Delay time IN-OUT from/To HDW (sec) 30 C AAS 0 0 600TRA 30 d trA 0 0 3Enable bypass flow switch 30 E bAF 0 0 1Time by-pass flow switch (sec) 30 F tbF 180 0 300Standby from high TAE (ext air temp) 30 G OAE 45 0 70High water temp IN 30 H Ati 64 40 80Config screensaver 30 I SCr 1 0 2

VisentinG
Casella di testo
ANK
Page 10: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Modbus Supervisor address 30 J Ad1 1 1 999Bauderate Supervisor 30 L Bd1 1 0 2Enable writing by supervisor 30 Π AS1 0 0 1Limit Temp air 1 30 o LA1 -15 -20 -25 45Limit Temp water 1 30 P St1 43 53 0 70Limit Temp air 2 30 q LA2 -10 -25 45Limit Temp water 2 30 r St2 58 62 0 70Max heating setpoint limit 30 t LSP 55 60 15 65Menù installer 2 (pwd 31) 31T Delta reset after OFF by ForceOff dyn. (°C) 31 0 - 6 0 30Config Heating Cable 31 1 - 0 2 0 2Heating cable Set point (°C) 31 2 - 0 -20 10Menù Maintenance (pwd 83) 83Tae enable defrost (°C) 83 0 - 10 -20 50T air exch enable defrost (°C) 83 1 - -2 -20 50P delta (bar) 83 2 - 0.4 0.1 10P delta end injections (bar) 83 3 - 0.3 0.1 10time stable pressure (sec) 83 4 - 300 30 900time timeout low water temp (sec) 83 5 - 900 0 999time min injection (sec) 83 6 - 120 30 900time max injections (sec) 83 7 - 300 60 900Max exits per time 83 8 - 3 1 20Temp end defrost by 4way valve (°C) 83 9 - 12 20 4 35Pressure to force defrost by 4 way valve (bar) 83 A - 2.8 0.5 15Time min 4way valve (sec) 83 b - 120 15 900Time max 4 way valve (sec) 83 C - 300 600 60 900Time min between two 4 way cycles (min.) 83 d - 20 2 40Time max functioning without defrost (min) 83 E - 240 0 840Press Set DCPX in heating (bar) 83 F - 30 15 40Press Diff. DCPX in heating (bar) 83 G - 5 2 20TAE min DCPX (°C) 83 H - -5 -20 32TAE max DCPX (°C) 83 I - 40 34 45P set min (bar) 83 J - 18 5 24P set max (bar) 83 L - 18 5 38P band T min (bar) 83 Π - 17 2 20P band T max (bar) 83 o - 12 2 20Volt signal min to DCPX 83 P - 1.5 0.1 9Pressure control during defrost (bar) 83 q - 30 12 45Diff. Pressure control during defrost (bar) 83 r - 5 1 20Pressure to enable only defrosts by 4way valve 83 t - 4 1 15Min discharge temp to force defrost by 4 way v 83 u - 50 30 100Max FL prealarms 83 y - 0 0 52nd Menù Maintenance (pwd 84) 84prealarms number (thousand) 84 0 - 0 999prealarms number (unit) 84 1 - 0 999alarms number (thousand) 84 2 - 0 999alarms number (unit) 84 3 - 0 999Menù Factory (pwd 125) 125Factory reset 125 0 - 0 0 1Config. Pressure trasducer 125 1 - 0 0 255Differential HP safety injection 125 2 - 1 0.5 0 10Differential LP safety injection 125 3 - 0.1 0 10Differential TGP safety injection 125 4 - 5 0 50

Page 11: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

Max injections number 125 5 - 5 0 100Tgp alarm (°C) 125 6 - 135 110 80 145Temp Diff. To alarm reset (°C) 125 7 - 10 0.2 20HP pressure alarm (bar) 125 8 - 40.5 20 45LP pressure alarm in cooling (bar) 125 9 - 4 0.5 15LP alarm in heating 125 A - 2 0.5 15LP diff. To alarm reset 125 b - 2 0.5 20Timeout alarm 125 C - 60 10 900Max prealarms 125 d - 5 1 20Decrement alarm (h) 125 E - 1 0 12Delta T capacity control 125 F - 1 0.5 10Timeout capacity control (sec) 125 G - 150 15 600Antifreeze/LP timeout (sec) 125 H - 180 0 900Time before to activate 4way valve (sec) 125 I - 15 0 600Differential to antifreeze reset (°C) 125 J - 1 0.5 20Menù compressor and pump (pwd 72) 72Percentage 2nd compressor (%) 72 0 CPA 0 0 80Min. cp working time (sec) 72 1 On 120 20 900Min cp off time (sec) 72 2 OFF 180 20 900Start up max per hour 72 3 SPn 12 6 30Timeout between two compressor start up 72 4 int 30 10 600Start up timeout to probes temp control 72 5 PPc 150 30 600Timeout for FL alarm 72 6 FL 5 2 120Start up FL timeout 72 7 APP 40 2 360Water pump off time (sec) 72 8 PP 120 10 999Pulldown (°C) 72 9 PLd 1 0 10Cp timeout after a power failure 72 t Stt 0 60 0 360Menù Maintenance 2 (pwd 333) 333Delta P to activate 4 way valve (bar) 333 0 1 0.5 5Timeout delta P after CP1 On (sec) 333 1 15 0 60Timeout delta P after CP2 On (sec) 333 2 15 0 604 way valve logic 333 3 0 1 0 1Unit only heat pump version 333 4 0 0 1

DIP position Defau

lt Y/Z Aversion DCPX

1 ON2 ON3 ON4 ON5 ON6 ON7 ON8 OFF9 OFF10 OFF11 OFF12 OFF

DIP trasducer1 OFF2 OFF

Note

Page 12: Variants Moducontrol Vers. 4.2 EN - aermec.us sales service manuals sent from the... · the unit will be used, and an alarm 157 will be activated.) ... Time by-pass flow switch (sec)

AERMEC S.p.A.I-37040 Bevilacqua (VR) - ItaliaVia Roma, 996 - Tel. (+39) 0442 633111Telefax (+39) 0442 93730 - (+39) 0442 93566www.aermec.com

I dati tecnici riportati nella presente documentazione non sono impegnativi.AERMEC S.p.A. si riserva la facoltà di apportare in qualsiasi momento tutte le modifiche ritenute necessarie per il miglioramento del prodotto.Les données mentionnées dans ce manuel ne constituent aucun engagement de notre part. Aermec S.p.A. se réserve le droit de modifier à tous moments les données considérées nécessaires à l’amelioration du produit.Technical data shown in this booklet are not binding.Aermec S.p.A. shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product.Im Sinne des technischen Fortsschrittes behält sich Aermec S.p.A. vor, in der Produktion Änderungen und Verbesserungen ohne Ankündigung dur-chzuführen.ILos datos técnicos indicados en la presente documentación no son vinculantes.Aermec S.p.A. se reserva el derecho de realizar en cualquier momento las modificaciones que estime necesarias para mejorar el producto.