VAC Controller CVS/VIP Tel. +47 70 03 91 00 www.jetsgroup.com Product No. 121315143 Doc. Rev.: 5 (2020-11-30) 1 Technical Data ................................... Outside Dimensions 190 x 80 x 60 mm (LxWxH) ............................................................................. Generic Material ABS ................................................................................. Net Weight 0.67 kg Operating Data .............................................................................. Voltage 100-240VAC 12-24VDC Disclaimer Note: Our products and services are offered and sold subject to Jets Vacuum AS’ General Sales Conditions, copies of which will be furnished upon request. Information provided herein is solely for information purposes, does not constitute any warranty or representation of any kind and is subject to change without notice. We strive to reproduce product colors reasonably accurate. Without prior written approval, this document or any part of may not be reproduced in any form. Jets™, Vacuumarator™, Helivac™, VC™, VOD™, CVS™ and Softsound™ are trademarks and/or registered trademarks of Jets. © Jets AS. All rights reserved. Components 1 | Power Supply 12VDC, complete .............................. 121201627* Additional Components | US plug adapter ......................................................... 121201621 | UK plug adapter ......................................................... 121201622 | AUS plug adapter ....................................................... 121201623 * Component/s avaliable as replacement parts.

VAC Controller CVS/VIP

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

1

Technical Data

......................................Outside Dimensions 190 x 80 x 60 mm (LxWxH)

................................................................................Generic Material ABS

....................................................................................Net Weight 0.67 kg

Operating Data

................................................................................Voltage 100-240VAC12-24VDC

Disclaimer

Note: Our products and services are offered and sold subject to Jets Vacuum AS’ General Sales Conditions, copies of which will be furnished upon request. Information provided herein is solely for information purposes, does not constitute any warranty or representation of any kind and is subject to change without notice. We strive to reproduce product colors reasonably accurate. Without prior written approval, this document or any part of may not be reproduced in any form. Jets™, Vacuumarator™, Helivac™, VC™, VOD™, CVS™ and Softsound™ are trademarks and/or registered trademarks of Jets. © Jets AS. All rights reserved.

Components

1 | Power Supply 12VDC, complete .................................121201627*

Additional Components

| US plug adapter ............................................................121201621

| UK plug adapter ............................................................121201622

| AUS plug adapter .........................................................121201623

* Component/s avaliable as replacement parts.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

2

Function and Principle

The VAC Controller is programmed to control the following:

● Automatic start and stop of a Vacuumarator™ pump.

● Manual start and stop of a Vacuumarator™ pump.

● Vacuum level monitoring.

● Auto stop after delayed run time (default 10 min).

● Tank level monitoring from a level switch in a tank.

● Activation of an alarm signal.

● Ready signal from a presence sensor (optional). Starts the Vacuumarator™ pump and produces vacuum to a set vacuum level.

Alarm

The VAC Controller is programmed with the following alarm settings:

● Power ON - Engages closed contact at alarm output F.

● Low Vacuum - Engages and activates alarm output G.

● Full Tank - Alarm is based on a level indication from a tank. Requires a level switch (not included).

● Long Running Time - Engages and activates alarm output I.

● Vacuum Transmitter Fault - Alarm is based on vacuum transmitter not connected, connected wrong, not working.

● Full Tank Warning - If the time setting in "runtime after full tank" has been set over 00, a pre-warning alarm will sound. This means that the pump will run in xx-minutes before the full tank alarm sounds. Start planning to have the tank emptied.

Operation

● AUTO Mode 1.1

When the system is intended to be used as a constant vacuum system (CVS), and the motion/presence sensors are not connected to the VAC Controller.

● VIP Mode 1.2

When the system is used with motion/presence sensors that are connected to the VAC Controller. Vacuum is produced when activating the zone of the motion sensor.

● Manual Mode 1.3

Starts and stops the Vacuumarator™ pump via the VAC Controller, regardless of the vacuum transmitter (vacuum level).

WARNING: This can cause the vacuum to reach a very high level in the system and the pump will not stop.

● OFF Mode 1.4

System OFF, the VAC Controller will not start in this mode.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

3

Important Health and Safety Information

Installation, operation and maintenance must be carried out in strict accordance with this guide and with all applicable regulations. For your own protection and the protection of others, it is necessary to familiarize yourself with, and always follow, the contained safety and environmental precautions for our products.

This manual is an integral part of the product/delivery. Always keep it in a safe place for future reference. It is entirely the owner’s responsibility to ensure that all safety and environmental measures, in accordance with local, state and federal laws are followed. Jets Vacuum AS assumes no responsibility for equipment damage, personal injury or death and/or delays that result from a lack of respect for the instructions for installation and/or use as stated in this documentation. Disregarding these instructions may invalidate all warranties.

Safety information references are in accordance with Jets Vacuum AS documentation system. If you do not understand the warnings, stop work immediately and contact Jets Vacuum AS (citing the safety reference number) for further clarification.

For further information about the included warnings or any other safety concerns please contact Jets Vacuum AS.

Important Health and Safety Warnings

3.1 WarningAll wiring should be performed by a licensed or certified electrician.

3.2 WarningNever work on the equipment when mains power is applied. For equipment fitted with a frequency converter: After disconnecting the input power, always wait for 5 min to let the intermediate circuit capacitors discharge before you start working on the equipment.

1.2 WarningBe thoroughly familiar with the controls and the proper use of the equipment prior to installing, starting or using the equipment. Know the equipment application, limitations and potential hazards.

3.3 WarningAvoid kinking and protect electrical cord/s from sharp objects, hot surfaces, oil and chemicals. Replace or repair damaged or worn cords immediately. In case of cable damage contact a qualified technician for replacement.

3.4 WarningShoreside applications only: For maximum safety, the equipment should be connected to a grounded circuit equipped with a ground fault interrupter device. Before installing the equipment, have the electrical outlet checked by a licensed or certified electrician to make sure the outlet is properly grounded. Make sure that grounding conductors are adequately sized as required by safety regulations.

3.5 WarningEnsure that the line voltage and frequency of electrical current supply agrees with the equipment specifications

3.21 WarningDo not use plugs or connectors that are damaged.

3.24 WarningAvoid touching the connector with wet hands. Do not disconnect the plug by pulling the electrical cord

2.14 WarningThe equipment safety is guaranteed only if used in compliance with the instructions provided. Do not exceed the limits provided.

6.11 NoticeImmediately upon receipt check the equipment for external damage. Any damage detected after dispatch should be reported immediately to Jets Vacuum AS and commissioning must be postponed until equipment has been inspected. Do not dispose of damaged items. Your direct supplier will advise you of the procedure to follow.

6.3 NoticeCheck total quantities of each item against shipping records. Ensure that all items have been received as per Jets™ order confirmation. Any discrepancies must be reported to the carrier and to your direct supplier or Jets Vacuum AS immediately.

6.4 NoticeAfter unpacking the equipment carefully inspect and tighten any parts, nuts, bolts or screws that may have become loose in transit.

6.6 NoticeGoods to be protected against shock, falls, dust, foreign matter, grinding, welding, humidity and moisture.

3.6 WarningRisk of electric shock. Never connect the green (or green and yellow) wire to a live terminal.

3.31 CautionJets Vacuum AS electrical supply includes cables outfitted with a Shuko 2 pole plugs + PE dependent on equipment specifications. Do not alter this configuration without authorization from a specialized technician.

Delivery, Receipt of Goods and Transportation

Goods to be protected against shock, dust, humidity and frost. Suitable adequately dimensioned transporting equipment is to be used. Note that the equipment may contain components that are easily damaged as a result of inappropriate handling. Jets Vacuum AS is not responsible for or liable for delivery delays resulting from occurrences outside of Jets Vacuum AS' immediate control. On receipt of goods, check for visual damage. Any damage detected after dispatch should be reported immediately to Jets Vacuum AS. Damages and/or discrepancies must be reported in writing no later than eight (8) days after receipt of goods. Commissioning must be postponed until the equipment has been inspected. Do not dispose of damaged items. Your direct supplier will advise you of the procedure to follow.

Storage

Unless otherwise specified, goods are to be stored in a dry environment between 0°C and +40°C prior to installation. The storage location must be dust free, low humidity (≤95%) and be free from moisture. Keep clear of foreign objects.

Installation to End Use

Site to be a dry environment between +0°C and +45°C. The site is to be dust free and protected from grinding and welding. During installation, the site is to be protected from water, frost and moisture. Goods are to be stored as per the instructions for delivery, storage and transport. A visual inspection is to be carried out on receipt of goods as well as at the time of installation to ensure that storage and transport conditions after receipt have not compromised the quality of the product/s.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

4

Installation

Prior to Installation

Before starting any work on the VAC Controller, ensure that the power has been disconnected.

3.2 WarningNever work on the equipment when mains power is applied. For equipment fitted with a frequency converter: After disconnecting the input power, always wait for 5 min to let the intermediate circuit capacitors discharge before you start working on the equipment.

3.1 WarningAll wiring should be performed by a licensed or certified electrician.

Prior to installing the VAC Controller, read all technical information in this document. The document contains important information related to the installation and settings for your installation.

Electrical Connections Diagram

A - Pre-wiredB - Signal cable to the Vacuumarator™ pumpC - Vacuum transmitterD - VIP signal (optional)E - Tank level (optional)F - Alarm - Power on (normally open contact)G - Alarm - Low vacuum

H - Alarm - Full tankI - Alarm - Long running timeJ - Optional power supplyK - Power supplyL - Presence detectors (max 10 sensors)M - Grey water tank level switch connections (max 5 grey water tanks)

Power Supply

● J - Optional 12/24VDC Power SupplyOptional power output or VIP sensor power supply, if needed.

● K - Power SupplyThe power supply includes an EU plug adapter. If needed, US, UK and AUS plug adapters are also available.

If connecting to a 12/24V battery supply, a 12VDC power cable (pn 121201625) is required.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

5

Electrical Connections Diagram if VIP Presence Detectors are Installed

Installation Steps

1.

Insert a screwdriver into both of the slots on the front cover to open the controller.

2.

Lift the display out of the housing.

3.

Using the four screw holes in the corners of the housing, secure the controller to the wall (screws not provided).

4.

Return the display back into position on the housing.

5.

Close both side covers. Ensure both sides are locked in place.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

6

Operation

Start-up Procedures

First Start-up / Power-up the VAC Controller

At first start-up, CVS (Auto Mode) and English language is set as default. All vacuum and alarm settings are pre-set.

The VAC Controller is not a touch screen. Use the arrow keys to navigate through the system (refer to Navigation Principles below for more information).

To change the mode for the VAC Controller, go to Operations menu 1:

1.1 - CVS (Auto Mode)1.2 - Auto VIP Mode1.3 - Manual Mode1.4 - System Off

To change the date and time, go to Menu 2.6:

2.6.1 - Date2.6.2 - Time

To change the language, go to menu 2.7.

Navigation Principle

● A dark frame around a setting or an arrow (►) insde the selection indicates which setting you are currently on.

● Arrow up/down indicates that there are several choices in the menu you are currently on.

● Activating and changing values occurs by having a blue frame around a current setting, then OK is pressed and the value begins to blink. Use the arrow keys to adjust, then press OK or Done to save. The blinking will stop and the value will be saved.

● Each time a keystroke activates a button, a small beep will be heard, if the alarm sound is turned on/off in menu 2.6.8.

● Press and hold the return button for 5 seconds to restart the VAC Controller. The controller's long running time and warning tank level values will reset.

● Press the return button to go back to the main menu.

Factory Settings

CVS (Auto Mode) and English language is set as default. All vacuum and alarm settings are pre-set.

The default setting is based on:

● The Vacuumarator™ is set to start at 30% vacuum, and stop at 50% vacuum.

● Maximum run time for the Vacuumarator™ is set to 10 minutes.

● Low vacuum alarm is set at 20%.

● Maximum run time after full tank alarm is 00 minutes.

● Vacuum if present setting is set at 5 minute delay run time.

If the default setting can be used, the system is ready for immediate use.

Manual Mode

Manual mode may be required in troubleshooting, i.e. to provide an extra powerful flush or when emptying a tank.

To run the Vacuumarator™ pump MANUALLY:

Go to Manual Mode in the Operations 1 menu. Press On to run the pump manually and Off to stop the pump. The pump will automatically stop after the long running time is reached.

WARNING: The pump will not stop at high vacuum when in manual mode.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

7

Turning the VAC Controller OFF

From the main menu, press Auto and scroll down to System OFF. Press OK.

Service and Maintenance

Turn the VAC Controller Off and unplug the power supply.

This must always be done before installation, maintenance or repair.

Note: If the Vacuumarator™ pump's power is disconnected, the VAC Controller's power must also be disconnected.

3.28 WarningNever work on the equipment when power is applied.

Setting Selections

1. Menu screen

2. Return/Reset button

3. Scroll down button

4. Scroll right button

5. Scroll left button

6. Scroll up button

7. OK/Save selection button

8. Power light

Main Menu

● Vacuum Level - Shows the current vacuum level.

● Menu - To enter Main Menu 2 screen.

● Auto - To enter Operation 1 screen.

___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

8

Selecting Auto from the main menu screen will take you to the the Operations 1 menu.

1.1 - Auto Mode (CVS) Constant Vacuum System Controlled

- Shows the current vacuum level.

1.2 - Auto VIP ModeVacuum if Present System Controlled

- Shows the current vacuum level.

1.3 - Manual Mode

- Manual start and stop of the Vacuumarator™ pump

1.4 - System OFF

___________________________________________________________________________________________________________________

Main Menu 2

Selecting Menu from the main menu screen will take you to Main Menu 2.

AlarmAlarm historyAlarm settingVacuum settingVIP settingOperation dataLanguageFactory setting

2.12.22.32.42.52.62.72.8

___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

9

Main Menu 2 Settings

● Active Alarm 2.1 Displays the 'current" date and time and will list any active alarms in the system.

___________________________________________________________________________________________________________________

● Alarm history 2.2 Use the up and down arrow keys to view a history log, including dates and times, of the last 100 alarms.

The newest alarm will show in the display when the history log opens.

___________________________________________________________________________________________________________________

● Alarm setting 2.3 2.3.1 - Long running timeDefault: 10 minutesMaximum constant pump running time: 1-60 minutes

2.3.2 - Low vacuum alarmDefault: 20%Low vacuum alarm: 0-30%

2.3.3 - Runtime after full tankDefault: 0 minutesMaximum time it is possible to run the pump after the high level tank alarm has been activated. When this runtime expires, the pump will stop. Empty the tank.

___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

10

● Vacuum setting 2.4 2.4.1 - Start vacuum levelDefault: 30%Pump start level: 30-50% vacuum

2.4.2 - Stop vacuum levelDefault: 50%Stop pump level: 40-70% vacuum

___________________________________________________________________________________________________________________

● VIP setting 2.5 Runtime after VIP signal (minutes)Default: 5 minute delay active operation time (the pump will hold the vacuum betwen set point in xx-minutes) after activated sensor or level switch: 1-60 minutes.

___________________________________________________________________________________________________________________

● Operation data 2.6 2.6.1 - DatePress OK and the value will blink. Arrow up and down and press OK to set the day, month and year.

2.6.2 - TimePress OK and the value will blink. Arrow up and down and press OK to set the hour and minutes, using the 24-hour clock.

2.6.3 - Running hoursTotal count of pump running time in hours.

This is a read out only and cannot be reset.

2.6.4 - Total PowerUp countA counter for the total time the controller has been connected to power.

This is a read out only and cannot be reset.

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

11

2.6.5 - Pump start-up countThe total number of times the pump has started.

This is a read out only and cannot be reset.

2.6.6 - Full tank countA counter for the number of times the full tank alarm has been activated.

This is a read out only and cannot be reset.

2.6.7 - Reset countersTo reset the number of times the pump has started and the number of operating minutes.

Will reset this counter only.

2.6.8 - System Status

Firmware - Shows the current software version on the controller.

Alarm sound - ON (default) / OFF function will deactivate all the sound from the controller (alarm and key stroke sounds).

Alarm outputs - NC (default) (normally closed) / NO (normally open) alarm output. Choose if alarm output "long running time", "full tank" and "low vacuum" should be normally open or normally closed. Alarm output "Power ON" should always be pre-set at NO and is not included in this selection. This setting will not reset after power failure or factory setting.

___________________________________________________________________________________________________________________

● Language 2.7 2.7.1 - English (Default)

2.7.2 - Norwegian

2.7.3 - German

2.7.4 - Spanish

___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00www.jetsgroup.com

Product No. 121315143 Doc. Rev.: 5 (2020-11-30)

12

● Factory setting 2.8 To restore the controller back to the factory settings.

___________________________________________________________________________________________________________________

Troubleshooting

Jets Vacuum AS provides the following troubleshooting information to assist in resolving issues that may arise with your installation. For more detailed information or assistance, please contact Jets Vacuum AS.

Problem Cause Action

Long Running Time If the pump is constantly running, more than the set maximum running time, an alarm will activate and the pump will stop. There is also a limitation on how long it is possible to run the pump in manual mode.

The pump will stop when the alarm is activated. The pump/unit must be restarted. The alarm output long running time is activated.

Press and hold the return/reset button for 5 seconds to reset the controller.

Full Tank Warning The full tank warning alarm will activate when the high level tank signal/input is active (closed signal). The pump does not stop immediately, but a running time count starts (runtime after full tank alarm). The runtime time is adjustable in the settings menu 2.3.3. The counter will be reset by a power failure.

The full tank alarm is activated. The runtime after full tank time in alarm setting 2.3.3. can be adjusted.

Start planning to have the tank emptied.

Full Tank Alarm A full tank alarm will show on the display. The pump will stop immediately when the runtime after full tank alarm counts down completely to 0.

The full tank alarm is activated and the pump stops immediately. Empty the tank.

Low Vacuum Alarm The alarm is only activated in automode, not in auto VIP or manual mode. When vacuum in the system is less than the set value in 2.3.2 for longer than 1 continuous minute, a low vacuum alarm will show in the display.

When the vacuum level goes back above the set value in 2.3.2, the alarm will disappear. Adjust the low vacuum alarm level in 2.3.2

Vacuum Transmitter Fault The vacuum transmitter is not connected, which will show the level as 125 on the display. The vacuum transmitter is connected wrong or is broken.

Check the vacuum transmitter connections. Replace the transmitter, if necessary.