©John Roberts DESIGN EXAMPLE V2 Taking Design Example 1 recalculate the characteristic strength (f k ) of masonry made from Group 1 solid concrete block masonry units with a normalised compressive strength (f b ) of 9,5 N/mm 2 . The attestation of conformity (manufacturing control) is Category I and the masonry will be constructed using a thin layer mortar using Class 1 execution control. The masonry units are 120 mm in thickness. Again check that the load capacity of such a wall is sufficient to withstand the design loading of 180 kN/m applied.

v2 Design Example

Embed Size (px)

DESCRIPTION

Masonry Wall Example no2

Citation preview

  • John Roberts

    DESIGN EXAMPLE V2

    Taking Design Example 1 recalculate the characteristic strength (fk) of masonry made from Group 1 solid concrete block masonry units with a normalised compressive strength (fb) of 9,5 N/mm2. The attestation of conformity (manufacturing control) is Category I and the masonry will be constructed using a thin layer mortar using Class 1 execution control. The masonry units are 120 mm in thickness. Again check that the load capacity of such a wall is sufficient to withstand the design loading of 180 kN/m applied.