1
Study of the Cooling System with Study of the Cooling System with Fluor Fluor o o inert Refrigerants inert Refrigerants V. Vinš, V. Vacek, M.Doubrava, M. Galuška [email protected] CTU, Faculty of Mechanical Engineering, Department of Applied Physics Technická 4, 16607 Praha 6 ©2004 V. Vinš & V. Vacek ABSTRACT: ABSTRACT: The goal of our project was an elaborate study of a lubricant-free cooling circuit working with a fluoroinert refrigerant. The cooling power of the studied circuit was set to be around 5 kW and the temperature in the evaporator around -20°C. A capillary behavior study was included into the project as well. The Department of Applied Physics has been participating in design of cooling systems and consecutive measurements on prototypes of Pixel and SCT detectors at the international nuclear research center CERN (Geneva) for several past years. Main interest of current work is the design of cooling system for the Inner Detector of the ATLAS experiment. The fluoroinert refrigerants, having the chemical structure CnF (2n+2), were considered according to specific needs of the cooling system. These refrigerants are non-conductive, have low viscosity and low impact on an environment. Prior to design of the cooling circuit, it was necessary to collect basic thermo-physical data of refrigerants. Our study has concentrated on the C3F8 (octofluoro-propane) and C4F10 (perfluoro-butane). Manufacturers, suppliers and scientific conference’s web pages were essential sources of information about the refrigerants. Using the Benedict-Webb-Rubin equation (MBWR) that contains 34 constants the log p-h and log p-T diagrams were prepared. Respecting all analyses one can conclude that the final design of ATLAS cooling system will use the C3F8 the most likely. Our study of the cooling circuit proposal assumes the use of non-lubricated compressor, sub- cooling of refrigerant in inter-heat exchanger and ideal phase changes were considered. The circuit consists of following main parts: non-lubricated (~ dry) compressor, condenser, sub- cooler, pressure reduction element (capillary) and evaporator, all of them connected with the appropriate pipelines. The refrigerant undergoes following phase changes: isentropic compression in the compressor, isobaric condensation in the condenser, isobaric sub-cooling in the recuperative heat exchanger, adiabatic throttling in the capillary, isobaric evaporation in the evaporator and isobaric super-heating in recuperative exchanger. The projected mass flow through the circuit should be around 65 g/s. A computational algorithm was made for all main components of the cooling circuit by use of MS-Excel. The input data can be simply changed to obtain optimal condenser, evaporator and recuperative exchanger parameters. We have been also involved in pilot type measurements on the test prototype of the cooling system installed at CERN. The main goal of our work was to design and test the various prototypes of the recuperative exchanger in which the refrigerant superheated vapor, leaving the evaporator, cools down the inlet liquid arriving from the condenser. Two main designs were studied. In the first case, the heat exchanger consisted of two capillaries (containing inlet liquid) coiled around the support tube (filled with outlet vapor). In the second case, there were three capillaries coiled inside of the support tube. As a supplementary part of the project, an experimental set-up for the measurement of capillary characteristics has been installed in the Prague laboratory. Data obtained from experiments on this set-up should provide better understanding of pressure-drop through a capillary as a function of its length and inner diameter. This knowledge is essential for the optimal design of cooling circuit that uses the capillary as the only pressure reduction element. The set-up consists of a DARI air compressor providing a maximum of 9 bars absolute, a pressure tank manufactured at the faculty workshop, capillary to be tested, scale for measurement of refrigerant mass flow, and connecting tubes with operating valves. Two temperature sensors Pt100 and one differential pressure sensor DMD 331 were installed to monitor changes of running parameters along the capillary. All sensors were connected to a mobile DAQ system MIC 2000 using Advantec cards and Eflab software. The set-up can be operated at normal room conditions (temperature, pressure) and with convenient testing medium (C8F18…or even with water). A similar test stand will be also installed at CERN for checking the reference capillaries that will be later delivered to the Inner detector assembly sites. This research has been supported by FRVŠ grant No. FRV 2417-G1. Design of the cooling circuit Set-up for the measurement of capillary characteristics Results from Measurements Summary: Summary: Basic thermo-physical data of fluoroinert refrigerants (C3F8, C4F10) has been collected; Using the MBWR equation the log p-h and log p-T diagrams were prepared The study of non-lubricant cooling system working with fluoroinert refrigerants has been elaborated; Cooling power has been 5kW and temperature in the evaporator -20°C An experimental set-up for the measurement of capillary characteristics has been installed in the laboratory We have been participating in design of the heat exchanger and testing measurements on the prototype of the cooling system installed at CERN Air escape & safety valve Liquid Air Capillary Air Liquid Measuring cylinder Filling valve Stopwatch Differential pressure sensor (app. 0 - 17 bar) Set-up for measuring the pressure drop along the capillary Liquid Filter Air compressor (app. 18 bar) Needle valve Scale Differential pressure sensor DMD331 Pressure drop along stainless capillary (ID=1.0mm) 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 1,5 2,5 3,5 4,5 5,5 6,5 mass flow [g/s] dp [bar] L=1.84m, C8F18 L=1.63m, C8F18 L=1.39m, C8F18 L=1.18m, C8F18 L=0.98m, C8F18 Pressure drop along copper capillary (ID=0.8mm) 0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 mass flow [g/s] dp [bar] L=1.72m, C8F18 L=1.0m, C8F18 L=0.7m, C8F18 L=1.07m, C8F18 weird L=1.05m, C8F18 weird L=1.07m, H2O Working layout of the “eflab” program based on TestPoint software Photo of the test stand Measurements at CERN Scheme of the cooling set-up installed at CERN Compressors 1: increase to ~ 2 bar 2: increase to ~ 15 bar (absolute) Pressure control valve AC Temperature control Chilled water as coolant 1 2 Pump Condenser AC Heating - warming the outlet vapour Vacuum pump - used to evacuate the system after use Water as coolant Heat Exchanger AC Heating - warming the inlet liquid Two capillaries Heat Exchanger Set-up for temperature control of the inlet liquid Cold box Pixel barrels Loop 8 Loop 9 Heat exchanger between the inlet and outlet pipe - outlet vapor cools inlet fluid Cross section: solder Liquid in Vapor out Liquid in Flow meter Study of flouroinert refrigerants Log p-T diagram for C3F8 P - T Diagram for C 3 F 8 p = 2E-08.T 4 + 9E-06.T 3 + 0,0016.T 2 + 0,1351.T + 4,1531 0,1 1 10 100 -70 -50 -30 -10 10 30 50 70 Pressure [bar] Temperature [C] = = - - + = 9 1 15 10 17 2 exp n n n n c n n v a v v v a P Benedict-Webb-Rubin equation: 17°C 46°C 2' 1' 3 4 5 6 1 p = 2 bar p = 8.7 bar Q k /m Q d /m Q d /m Q o /m Q o = 5000 W Q d = 1797 W Q k = 6093 W m = 0.0635 kg/s Kondenzátor Dochlazovač Kapilára Dochlazovač Výparník Kompresor Log p-h diagram for C3F8 with marked working points ( ) s kg h h Q m o / 0635 . 0 10 200 7 . 278 5000 3 6 1 = - = - = W h h m h h m Q W h h m Q d k 1797 ) 200 3 . 228 .( 0635 . 0 ) .( ) .( 4 . 6093 10 ). 3 . 228 3 . 324 .( 0635 . 0 ) .( 5 4 1 1 3 4 2 = - = - = - = = - = - = Mass flow: Power in the condenser and heat exchanger: Water as coolant Compressor Staves withpixels (evaporator) Cold box Condenser vapour (or two-phase flow) vapour Capillary vapour liquid liquid Heat Exchanger Results from CERN (capillaries coiled around the heat exchanger) Scheme of studied cooling circuit Various PT 100 sensors Pt 100 attached to the capillary outlet Scheme of the test stand installed in the laboratory

V. Vinš, V. Vacek, M.Doubrava, M. Galuška - cvut.czlin202.fsid.cvut.cz/research/documents/2004_VV_VV_MG_MD.pdf · The set-up consists of a DARI air compressor providing a maximum

  • Upload
    vannga

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Page 1: V. Vinš, V. Vacek, M.Doubrava, M. Galuška - cvut.czlin202.fsid.cvut.cz/research/documents/2004_VV_VV_MG_MD.pdf · The set-up consists of a DARI air compressor providing a maximum

Study of the Cooling System with Study of the Cooling System with FluorFluorooinert Refrigerants inert Refrigerants V. Vinš, V. Vacek, M.Doubrava, M. Galuška

[email protected]

CTU, Faculty of Mechanical Engineering, Department of Applied Physics

Technická 4, 16607 Praha 6

©2004 V. Vinš & V. Vacek

ABSTRACT:ABSTRACT:

The goal of our project was an elaborate study of a lubricant-free cooling circuit working with a fluoroinert refrigerant. The cooling power of the studied circuit was set to be around 5 kW and the temperature in the evaporator around -20°C. A capillary behavior study was included into the project as well.The Department of Applied Physics has been participating in design of cooling systems and consecutive measurements on prototypes of Pixel and SCT detectors at the international nuclear research center CERN (Geneva) for several past years. Main interest of current work is the design of cooling system for the Inner Detector of the ATLAS experiment. The fluoroinertrefrigerants, having the chemical structure CnF (2n+2), were considered according to specific needs of the cooling system. These refrigerants are non-conductive, have low viscosity and low impact on an environment. Prior to design of the cooling circuit, it was necessary to collect basic thermo-physical data of refrigerants. Our study has concentrated on the C3F8 (octofluoro-propane) and C4F10 (perfluoro-butane). Manufacturers, suppliers and scientific conference’s web pages were essential sources of information about the refrigerants. Using the Benedict-Webb-Rubin equation (MBWR) that contains 34 constants the log p-h and log p-T diagrams were prepared. Respecting all analyses one can conclude that the final design of ATLAS cooling system will use the C3F8 the most likely.Our study of the cooling circuit proposal assumes the use of non-lubricated compressor, sub-cooling of refrigerant in inter-heat exchanger and ideal phase changes were considered. The circuit consists of following main parts: non-lubricated (~ dry) compressor, condenser, sub-cooler, pressure reduction element (capillary) and evaporator, all of them connected with the appropriate pipelines. The refrigerant undergoes following phase changes: isentropic compression in the compressor, isobaric condensation in the condenser, isobaric sub-cooling in the recuperative heat exchanger, adiabatic throttling in the capillary, isobaric evaporation in the evaporator and isobaric super-heating in recuperative exchanger. The projected mass flow through the circuit should be around 65 g/s.

A computational algorithm was made for all main components of the cooling circuit by use of MS-Excel. The input data can be simply changed to obtain optimal condenser, evaporator and recuperative exchanger parameters. We have been also involved in pilot type measurements on the test prototype of the cooling system installed at CERN. The main goal of our work was to design and test the various prototypes of the recuperative exchanger in which the refrigerant superheated vapor, leaving the evaporator, cools down the inlet liquid arriving from the condenser. Two main designs were studied. In the first case, the heat exchanger consisted of two capillaries (containing inlet liquid) coiled around the support tube (filled with outlet vapor). In the second case, there were three capillaries coiled inside of the support tube.As a supplementary part of the project, an experimental set-up for the measurement of capillary characteristics has been installed in the Prague laboratory. Data obtained from experiments on this set-up should provide better understanding of pressure-drop through a capillary as a function of its length and inner diameter. This knowledge is essential for the optimal design of cooling circuit that uses the capillary as the only pressure reduction element. The set-up consists of a DARI air compressor providing a maximum of 9 bars absolute, a pressure tank manufactured at the faculty workshop, capillary to be tested, scale for measurement of refrigerant mass flow, and connecting tubes with operating valves. Two temperature sensors Pt100 and one differential pressure sensor DMD 331 were installed to monitor changes of running parameters along the capillary. All sensors were connected to a mobile DAQ system MIC 2000 using Advantec cards and Eflab software.The set-up can be operated at normal room conditions (temperature, pressure) and with convenient testing medium (C8F18…or even with water). A similar test stand will be also installed at CERN for checking the reference capillaries that will be later delivered to the Inner detector assembly sites.

This research has been supported by FRVŠ grant No. FRV 2417-G1.

Design of the cooling circuitSet-up for the measurement of capillary characteristics

Results from Measurements

Summary:Summary:

• Basic thermo-physical data of fluoroinert refrigerants (C3F8, C4F10) has been collected; Using the MBWR equation the log p-h and log p-T diagrams were prepared

• The study of non-lubricant cooling system working with fluoroinert refrigerants has been elaborated; Cooling power has been 5kW and temperature in the evaporator -20°C

• An experimental set-up for the measurement of capillary characteristics has been installed in the laboratory

•We have been participating in design of the heat exchanger and testing measurements on the prototype of the cooling system installed at CERN

Air escape

& safety valve

Liquid

Air

Capillary

AirLiquid

Measuring

cylinder

Filling valve

Stopwatch

Differential pressure

sensor (app. 0 - 17 bar)Set-up for measuring the

pressure drop along the capillary

Liquid

Filter

Air compressor

(app. 18 bar)

Needle

valve

Scale

Differential pressure sensor DMD331

Pressure drop along stainless capillary (ID=1.0mm)

1,0

2,0

3,0

4,0

5,0

6,0

7,0

8,0

1,5 2,5 3,5 4,5 5,5 6,5

mass flow [g/s]

dp [bar]

L=1.84m, C8F18 L=1.63m, C8F18L=1.39m, C8F18 L=1.18m, C8F18L=0.98m, C8F18

Pressure drop along copper capillary (ID=0.8mm)

0,0

1,0

2,0

3,0

4,0

5,0

6,0

7,0

8,0

0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0

mass flow [g/s]

dp [bar]

L=1.72m, C8F18 L=1.0m, C8F18

L=0.7m, C8F18 L=1.07m, C8F18 weird

L=1.05m, C8F18 weird L=1.07m, H2O

Working layout of the “eflab” program

based on TestPoint software

Photo of the test stand

Measurements at CERN

Scheme of the cooling set-up installed at CERN

Compressors1: increase to ~ 2 bar

2: increase to ~ 15 bar

(absolute)

Pressure

control valve

AC

Temperature

control

Chilled water

as coolant

1 2

Pump

CondenserAC

Heating -

warming the

outlet vapour

Vacuum pump - used to

evacuate the system after use

Water

as

coolant

Heat

Exchanger

AC

Heating -

warming the inlet

liquid

Two capillaries

Heat Exchanger

Set-up for temperature control of the inlet liquid

Cold box

Pixel barrels

Loop 8

Loop 9Heat exchanger between

the inlet and outlet pipe -

outlet vapor cools inlet fluid

Cross

section:

solder

Liquid

in

Vapor

out

Liquid

in

Flow

meter

Study of flouroinert

refrigerants

Log p-T diagram for C3F8

P - T Diagram for C3F8

p = 2E-08.T4 + 9E-06.T

3 + 0,0016.T

2 + 0,1351.T + 4,1531

0,1

1

10

100

-70 -50 -30 -10 10 30 50 70

Pressure [bar]

Temperature [C]

∑ ∑= =

−+

=

9

1

15

10172

expn n

nnc

nn

v

a

v

v

v

aP

Benedict-Webb-Rubin equation:

17°C

46°C

2'

1'

345

6

1p = 2 bar

p = 8.7 bar

Qk/m

Qd/m

Qd/m

Qo/m

Qo = 5000 W

Qd = 1797 W

Qk = 6093 W

m = 0.0635 kg/s

KondenzátorDochlazovač

Kapilára

DochlazovačVýparník

Kompresor

Log p-h diagram for C3F8 with marked

working points

( )skg

hh

Qm o /0635.0

102007.278

50003

61

=⋅−

=−

=

••

WhhmhhmQ

WhhmQ

d

k

1797)2003.228.(0635.0).().(

4.609310).3.2283.324.(0635.0).(

5411

3

42

=−=−=−′=

=−=−′=•••

••

Mass flow:

Power in the condenser and heat exchanger: Water as

coolant

Compressor

Staves with pixels

(evaporator)

Cold box

Condenser

vapour

(or two-phase flow)

vapour

Capillary

vapour

liquidliquid

Heat

Exchanger

Results from CERN (capillaries coiled around the heat exchanger)

Scheme of studied cooling circuit

Various PT 100

sensors

Pt 100 attached to the

capillary outlet

Scheme of the test stand

installed in the laboratory