860563543 Issue 2, June 2014 www.commscope.com UTP RJ45 Field Terminated Connector Kit General The redwood ® UTP RJ45, field terminated connector accepts cables with nominal outside diameters of 0.180” to 0.235” (4.6 to 6mm) with either solid or stranded conductors that have an outside insulation diameter between 0.033” and 0.042” (0.84 to 1.07mm). This instruction sheet provides information on installing the connector on non-OMT UTP and OMT UTP-type cable. Ordering information is listed below: Material ID Description 760189191 UTP RJ45 field terminated connector kit How to Contact Us To find out more about CommScope ® products, visit us on the web at www.commscope.com/ For technical assistance: - Within the United States, contact your local account representative or technical support at 1-800-344-0223. Outside the United States, contact your local account representative or PartnerPRO Network Partner. - Within the United States, report any missing/damaged parts or any other issues to CommScope Customer Claims at 1-866-539-2795 or email to [email protected]. Outside the United States, contact your local account representative or PartnerPRO Network Partner. redwood ® UTP RJ45 Connector Tools Required Cable jacket scoring tool (such as Xcelite ® 2CSKY or JOKARI ® No.1-Cat) Bel Stewart Connector ® termination tool (Part No. 2990003-01) Scissors Flush side cutters Needle-nose pliers (optional) Tweezers (optional) © 2014 CommScope, Inc. All rights reserved Page 1 of 7 For RoHS Inquiries: CommScope Inc. Corke Abbey, Bray Co. Dublin, Ireland Attn: Legal Department

UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

Embed Size (px)

Citation preview

Page 1: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

860563543 Issue 2, June 2014 www.commscope.com

UTP RJ45 Field Terminated Connector Kit

General The redwood® UTP RJ45, field terminated connector accepts cables with nominal outside diameters of 0.180” to 0.235” (4.6 to 6mm) with either solid or stranded conductors that have an outside insulation diameter between 0.033” and 0.042” (0.84 to 1.07mm). This instruction sheet provides information on installing the connector on non-OMT UTP and OMT UTP-type cable.

Ordering information is listed below:

Material ID Description 760189191 UTP RJ45 field terminated connector kit

How to Contact Us • To find out more about CommScope® products, visit us

on the web at www.commscope.com/

• For technical assistance:

- Within the United States, contact your local account representative or technical support at 1-800-344-0223. Outside the United States, contact your local account representative or PartnerPRO™ Network Partner.

- Within the United States, report any missing/damaged parts or any other issues to CommScope Customer Claims at 1-866-539-2795 or email to [email protected]. Outside the United States, contact your local account representative or PartnerPRO Network Partner.

redwood® UTP RJ45 Connector

Tools Required • Cable jacket scoring tool (such as Xcelite® 2CSKY or JOKARI® No.1-Cat) • Bel Stewart Connector® termination tool (Part No. 2990003-01) • Scissors • Flush side cutters • Needle-nose pliers (optional) • Tweezers (optional)

© 2014 CommScope, Inc. All rights reserved

Page 1 of 7

For RoHS Inquiries:CommScope Inc.Corke Abbey, BrayCo. Dublin, IrelandAttn: Legal Department

Page 2: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

860563543 Instruction Sheet

www.commscope.com

Parts List Verify parts against the parts list below:

Quantity Description 1 Plug body 1 Wire aligner 1 Clear load bar - for conductors 0.033”

to 0.038” dia. (0.84 to 0.97mm) 1 Black load bar - for conductors 0.037”

to 0.042” dia. (0.94 to 1.07mm) 1 Instruction sheet

Step 1 – Cable Preparation

Steps for preparing Non-OMT and OMT cables are provided first and then instructions for installing the connector follow.

Common Step for Both Cable Types 1. Orient strain relief boot as shown and slide it

over the cable jacket and out of the way for later assembly.

2. Score cable jacket approximately 2” (51mm) from the end using a precision jacket scoring tool that has fine adjustment settings, such as the Xcelite 2CSKY (shown) or JOKARI No.1-Cat.

3. Remove cable jacket back to the score line.

Step 1a – Preparation of Non-OMT UTP Cable

1. Spread apart pairs to access the center flute.

2. Pull flute off to one side and trim it as close to jacket as possible.

Page 2 of 7

Page 3: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

www.commscope.com 860563543

Instruction Sheet

Step 1b – Preparation of OMT UTP Cable Note: Preparation of OMT-type UTP cable is illustrated and described here. Other UTP cable preparation is the same except it may contain a center tape instead of a flute and may not have a separator tape between the twisted pairs.

1. Spread apart pairs to access the separator tape and flute.

2. Twist open pair end to expose the separator tape.

3. Using a counter-clockwise rotation, unwind separator tape down to the cable jacket without untwisting the pairs.

4. Pull flute and tapes off to one or more sides.

5. Trim flute and tapes off as close to jacket as possible.

Page 3 of 7

Page 4: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

860563543 Instruction Sheet

www.commscope.com

Step 2 – Assemble Connector

1. Spread the conductor pairs apart and untwist each pair to within approximately 1/4” (6.4mm) of the cable jacket, then place wire aligner between them with the tapered end toward the jacket. Place orange pair in channel on the left side and brown pair in channel on the right side. Place blue and green pairs into upper and lower center channels.

2. Push wire aligner towards cable jacket as far as it will go and pull pairs snugly into wire aligner channels. Flatten out pairs and arrange conductor colors so they match the T568B color map below. Keep orange pair on the left and brown pair on the right.

Important: On one end of the cable the blue pair will be in upper center channel and the green pair will be in lower center channel, while on the other end of the cable the green pair will be in upper center channel and the blue pair will be in lower center channel.

Shown above is the industry standard color sequence for T568B wiring. Wiring colors may vary by cable. Please verify the color pattern specific to your particular requirements.

Note: When aligning wires to the color pattern, maintain existing twist of the wire pairs. Do not add or remove more than half-a-twist to any pair to achieve the required color pattern.

Position 1 Position 8

Orange/White

Orange Green/White

Blue Blue/White

Green Brown/White

Brown

Page 4 of 7

Page 5: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

www.commscope.com 860563543

Instruction Sheet

3. If necessary, use needle-nose pliers or tweezers to pull on end of each conductor eliminating as much twist as possible on OMT solid conductor cable.

4. Using scissors or side cutters, trim the ends of conductors at an angle, as shown, to make it easier to insert conductors into the load bar.

Note: Remove the least amount of wire necessary to do this.

5. Select the correct load bar for the outside diameter of the conductors. Clear load bar for diameter 0.033” to

0.038” (0.84 to 0.97mm) or Black load bar for diameter 0.037” to 0.042” (0.94 to 1.07mm).

6. Position load-bar so the flared (angled) end is facing the conductors and slots are facing up. Insert conductors into the load bar while maintaining the T568B wire color sequence as shown.

Page 5 of 7

Page 6: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

860563543 Instruction Sheet

www.commscope.com

7. Slide load bar over the conductors until it is

tight against wire aligner, then trim conductors flush to the load bar using flush side cutters.

8. Orient assembly so orange pair is on the left and brown pair is on the right and aligned with plug body. The latch tab on plug body should face down.

9. Carefully insert assembly into plug body until it stops. The wires should come in contact with the inside front surface of the plug body.

10. Position un-terminated plug so the latch tab faces to the front, away from the tool handles, and insert it fully into the crimp tool. Make sure plug is fully seated in tool.

Page 6 of 7

Page 7: UTP RJ45 Field Terminated Connector Kit - · PDF fileUTP RJ45, field terminated connector accepts cables with nominal outside ... non-OMT UTP and OMT UTP-type cable. ... 760189191

www.commscope.com 860563543

Instruction Sheet

11. Squeeze handles of crimp tool together until fully depressed. The handles will automatically release after the

crimping function is complete. Remove terminated plug from crimp tool and inspect the end to confirm each conductor is properly seated in a slot.

12. Repeat the above procedure for the other end of cable, if required. Important: On other end of cable the pairs in the upper and lower center channels of wire aligner will be opposite from the end just completed. On one end of cable the blue pair will be in the upper center channel and the green pair will be in the lower center channel, while on the other end of the cable the green pair will be in the upper center channel and the blue pair will be in the lower center channel.

13. Test the completed cable assembly to ensure that it meets performance requirements.