TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS 1. SAFETY PRECAUTION ······································ 2 2. OVERVIEW OF UNITS ········································ 5 3. SPECIFICATIONS ············································· 12 4. DATA ··································································13 5. OUTLINES AND DIMENSIONS ························ 17 6. WIRING DIAGRAM············································ 18 7. NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION ··· 20 8. TROUBLESHOOTING ······································· 22 9. ELECTRICAL WIRING ······································ 56 10. WIRING SPECIFICATIONS . ······························ 58 11. SYSTEM CONTROL ·········································· 59 12. REFRIGERANT PIPING TASK·························· 61 13. DISASSEMBLY PROCEDURE ·························· 64 INDOOR UNITS COMBINATION SHEETS No. OCH480 REVISED EDITION-D [Service Ref.] MXZ-8B140VA MXZ-8B160VA MXZ-8B140YA MXZ-8B160YA HFC utilized R410A March 2014 NOTE: • This service manual describes technical data of outdoor unit. As for indoor units and branch box (OCH508), refer to its service manual. • RoHS compliant products have <G> mark on the spec name plate. OUTDOOR UNIT Model name indication PARTS CATALOG (OCB480) Revision: Added connectable indoor unit MFZ-KJ25VE, MFZ-KJ35VE, and MFZ-KJ50VE in REVISED EDITION-D. • Some descriptions have been modified. • Please void OCH480 REVISED EDITION-C. <Outdoor unit> [Model Name] MXZ-8B140VA MXZ-8B160VA MXZ-8B140YA MXZ-8B160YA

utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type) The lineup of a connectable indoor

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

TECHNICAL & SERVICE MANUAL

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

CONTENTS1. SAFETY PRECAUTION ······································ 22. OVERVIEW OF UNITS ········································ 53. SPECIFICATIONS ············································· 124. DATA ·································································· 135. OUTLINES AND DIMENSIONS ························ 176. WIRING DIAGRAM ············································ 187. NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION ··· 208. TROUBLESHOOTING ······································· 229. ELECTRICAL WIRING ······································ 56

10. WIRING SPECIFICATIONS. ······························ 5811. SYSTEM CONTROL ·········································· 5912. REFRIGERANT PIPING TASK·························· 6113. DISASSEMBLY PROCEDURE ·························· 64

INDOOR UNITS COMBINATION SHEETS

No. OCH480REVISED EDITION-D

[Service Ref.]

MXZ-8B140VAMXZ-8B160VAMXZ-8B140YAMXZ-8B160YA

HFCutilized

R410A

March 2014

NOTE:•Thisservicemanualdescribestechnicaldataofoutdoorunit.Asforindoorunitsandbranchbox(OCH508),refertoitsservicemanual.

•RoHScompliantproductshave<G>markonthespecnameplate.

OUTDOOR UNIT

Modelnameindication

PARTS CATALOG (OCB480)

Revision:•Addedconnectableindoorunit MFZ-KJ25VE, MFZ-KJ35VE,and MFZ-KJ50VEinREVISEDEDITION-D.

•Somedescriptionshavebeenmodified.

•PleasevoidOCH480REVISEDEDITION-C.

<Outdoor unit>[Model Name]MXZ-8B140VA

MXZ-8B160VA

MXZ-8B140YA

MXZ-8B160YA

Page 2: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

2

1 SAFETY PRECAUTION

Cautions for units utilizing refrigerant R410A

1-1. ALWAYS OBSERVE FOR SAFETY

Use new refrigerant pipes.

Charge refrigerant from liquid phase of gascylinder.If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.

Do not use refrigerant other than R410A.

If other refrigerant (R22 etc.) is used, chlorine in refrige-rant can cause deterioration of refrigerant oil etc.

Use a vacuum pump with a reverse flow check valve.Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.

Use the following tools specifically designed for use with R410A refrigerant.The following tools are necessary to use R410A refrigerant.

Handle tools with care.

If dirt, dust or moisture enters into refrigerant cycle, that cancause deterioration of refrigerant oil or malfunction of com-pressor.

Do not use a charging cylinder.

If a charging cylinder is used, the composition of refrigera-nt will change and the efficiency will be lowered.

Flare tool

Electronic refrigerant charging scale

Vacuum pump adaptorSize adjustment gauge

Gauge manifold

Torque wrenchGas leak detectorCharge hose

Tools for R410AContamination inside refrigerant piping can cause deterio-ration of refrigerant oil etc.

If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com-pressor.

If large amount of mineral oil enters, that can cause deterio-ration of refrigerant oil etc.

Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)

Make sure that the inside and outside of refrige-rant piping is clean and it has no contaminantssuch as sulfur, oxides, dirt, shaving particles, etc,which are hazard to refrigerant cycle.In addition, use pipes with specified thickness.

The refrigerant oil applied to flare and flangeconnections must be ester oil, ether oil or alkylbenzene oil in a smalll amount.

Never use any refrigerant other than that specified.Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.Correct refrigerant is specified in the manuals and on the spec labels provided with our products.We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.

Use the specified refrigerant only.

Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact witha flame, poisonous gases will be released.

1-2. CAUTIONS RELATED TO NEW REFRIGERANT

Before obtaining access to terminal, all supply circuit must be disconnected.

OCH480D

Page 3: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

3

Gravimeter

Unit

[3] Service tools(1) Use the below service tools as exclusive tools for R410A refrigerant.

[2] Additional refrigerant chargeWhen charging directly from cylinder·CheckthatcylinderforR410Aonthemarketissyphontype.·Chargingshouldbeperformedwiththecylinderofsyphonstoodvertically.(Refrigerantischargedfromliquidphase.)

[1] Cautions for service(1) Perform service after recovering the refrigerant left in unit completely.(2) Do not release refrigerant in the air.(3) After completing service, charge the cycle with specified amount of refrigerant.(4) When performing service, install a filter drier simultaneously.

Be sure to use a filter drier for new refrigerant.

No. Toolname Specifications

1 Gaugemanifold·OnlyforR410A·Usetheexistingfittingspecifications.(UNF1/2)·Usehigh-tensionsidepressureof5.3MPa·Gorover.

2 Chargehose ·OnlyforR410A·Usepressureperformanceof5.09MPa·Gorover.

3 Electronicscale4 Gasleakdetector ·UsethedetectorforR134a,R407CorR410A.5 Adaptorforreverseflowcheck ·Attachonvacuumpump.6 Refrigerantchargebase

7 Refrigerantcylinder·OnlyforR410A·Topofcylinder(Pink)·Cylinderwithsyphon

8 Refrigerantrecoveryequipment

OCH480D

Page 4: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

4

(2) Cautions for refrigerant piping workNewrefrigerantR410Aisadoptedforreplacementinverterseries.AlthoughtherefrigerantpipingworkforR410AissameasforR22,exclusivetoolsarenecessarysoasnottomixwithdifferentkindofrefrigerant.FurthermoreastheworkingpressureofR410Ais1.6timeshigherthanthatofR22,theirsizesofflaredsectionsandflarenutsaredifferent.

1ThicknessofpipesBecausetheworkingpressureofR410AishighercomparedtoR22,besuretouserefrigerantpipingwiththicknessshownbelow.(Neverusepipesof0.7mmorbelow.)

2DimensionsofflarecuttingandflarenutThecomponentmoleculesinHFCrefrigerantaresmallercomparedtoconventionalrefrigerants.Inadditiontothat,R410Aisarefrigerant,whichhashigherriskofleakagebecauseofitsworkingpressurehigherthanthatofotherrefriger-ants.Therefore,toenhanceairtightnessandintensity,flarecuttingdimensionofcopperpipeforR410Ahasbeenspeci-fiedseparatelyfromthedimensionsforotherrefrigerantsasshownbelow.ThedimensionBofflarenutforR410Aalsohaspartlybeenchangedtoincreaseintensityasshownbelow.SetcopperpipecorrectlyreferringtocopperpipeflaringdimensionsforR410Abelow.For1/2”and5/8”,thedimensionBchanges.Usetorquewrenchcorrespondingtoeachdimension.

3ToolsforR410A(Thefollowingtableshowswhetherconventionaltoolscanbeusedornot.)

1/4 3/81/25/83/4

6.359.5212.7015.8819.05

0.80.80.81.0—

0.80.80.81.01.0

Nominaldimensions(inch)

Diagram below: Piping diameter and thicknessOutside

diameter (mm)Thickness (mm)

R410A R22

1/43/81/25/83/4

6.359.5212.7015.8819.05

9.113.216.619.7—

9.013.016.219.423.3

Nominaldimensions (inch)

Flare cutting dimensions Outsidediameter

Dimension A ( )+0-0.4 (mm)

R410A R22(mm)1/43/81/25/83/4

6.359.5212.7015.8819.05

17.022.026.029.0—

17.022.024.027.036.0

Nominaldimensions (inch)

Flare nut dimensionsOutside

diameter Dimension B (mm)

R410A R22(mm)

Gauge manifoldCharge hoseGas leak detectorRefrigerant recovery equipmentRefrigerant cylinderApplied oil

Safety charger

Charge valve

Vacuum pump

Flare tool

BenderPipe cutterWelder and nitrogen gas cylinderRefrigerant charging scaleVacuum gauge or thermis-tor vacuum gauge and vacuum valveCharging cylinder

Air purge, refrigerant chargeand operation checkGas leak checkRefrigerant recoveryRefrigerant chargeApply to flared section

Prevent compressor malfunction when charging refrigerant by spraying liquid refrigerantPrevent gas from blowing out when detaching charge hoseVacuum drying and airpurge

Flaring work of piping

Bend the pipesCut the pipesWeld the pipesRefrigerant chargeCheck the degree of vacuum. (Vacuum valve prevents back flow of oil and refri-gerant to thermistor vacuum gauge)Refrigerant charge

Tool exclusive for R410ATool exclusive for R410ATool for HFC refrigerantTool exclusive for R410ATool exclusive for R410AEster oil and alkylbenzeneoil (minimum amount)Tool exclusive for R410A

Tool exclusive for R410A

Tools for other refrigerants can be used if equipped with adap-ter for reverse flow checkTools for other refrigerants can be used by adjusting flaring dimensionTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be used

Tool exclusive for R410A

Tools and materials Use R410A tools Can R22 tools be used?

(Usable if equipped with adapter for rever- se flow) (Usable by adjusting flaring dimension)

Can R407C tools be used?

Ester oil: Alkylbenzene oil: minimum amount

(Usable if equipped with adapter for rever- se flow) (Usable by adjusting flaring dimension)

: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions.: Tools for other refrigerants can be used.

DimensionA

DimensionB

OCH480D

Page 5: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

5

2 OVERVIEW OF UNITS2-1. CONSTRUCTION OF SYSTEM

MXZ-8B140YA/160YA6HP

MXZ-8B140VA/160VA5HP14.016.0

15.518.0

R410A

Indoor unit that can be connected

Branch boxthat can be connected

Capacity

Refrigerant

Ratedcapacity (kW)

CoolingHeating

Number of unitsTotal system wide capacity

Type 15 ~ Type 100

2 ~ 8 units

1 ~ 2 units

21 ~ 132 % of outdoor unit capacity (3.0 kW ~ 18.5 kW) 19 ~ 130 % of outdoor unit capacity (3.0 kW ~ 20.2 kW)

Number of units

Outdoor unit

Ceilingconcealed

4-wayceiling cassette

Wallmounted

Model type Model name

Deluxe

Standard

CompactLow static pressure

Middle static pressureHigh static pressure

2 by 2 typeStandard

MSZ-FA25/35VAMSZ-FB25/35/50VA(H)MSZ-FD25/35/50VAMSZ-FH25/35/50VEMSZ-GA22/25/35/50/60/71/80VA MSZ-GB50VA MSZ-GC22/25/35VAMSZ-GC22/25/35/50/60/71NAMSZ-GE22/25/35/42/50/60/71/80VAMSZ-SF25/35/42/50VEMSZ-GE22/25/35/42/50/60/71NAMSZ-GF60/71VEMSZ-EF18/22/25/35/42/50VEMSZ-SF15/20VASEZ-KA/KC25/35/50/60/71VASEZ-KD25/35/50/60/71VA(L)PEAD-RP50/60/71/100JA(L)Q.UKPEA-RP71EA/RP100EA2MCFZ-GA35/50/60VASLZ-KA25/35/50VA(L)PLA-RP35/50/60/71AA(.UK)/BA(.UK)PLA-RP71BA2.UKPLA-RP100BA/BA3MFZ-KA25/35/50VAMFZ-KJ25/35/50VEMLZ-KA25/35/50VA

Floor standing

Capacity class (kW)2.2 2.5 3.5 5.0 6.0 7.1 8.0 10.0*

Connectable indoor unit lineup (Heat pump inverter type)

<NOTE> The lineup of a connectable indoor unit depends on a district/areas/country.* When connectiing the indoor unit with the number 100, use the PAC-AK52YP-E Y-shape connection pipe (Optional part).

Branch box PAC-AK53BC5 branches

(MAX. 5 units)

PAC-AK32BC3 branches

(MAX. 3 units)Number of branches Indoor unit that can be connected( )

Max. 2 branch boxes can be connected to 1 outdoor unit.

According to the connection method, you can choose the favorite one.

2- branch pipe (joint) : Optional partsIn case of using 1- branch box

In case of using 2- branch boxes

No need

Model name Connection methodflare

brazingMSDD-50AR-EMSDD-50BR-E

Option Optional accessories of indoor units and outdoor units are available.

CAUTION : The indoor unit which rated capability exceeds 10.0kW (100 type) can NOT be connected.

2.01.5 1.8 4.2

1-way ceiling cassette

OCH480D

Page 6: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

6

Indoor unit (Ceiling concealed type)

Indoor unit (Wall mounted type)

Outdoor unit Branch Box

2-2. SYSTEM OUTLINETheadditionalconnectionoftheBranchBoxtogetherwithemploymentofthecompacttrunk-lookingoutdoorunitcansuccessfullyrealizesalongdistancepipingforbighouses.Equippedwithamicroprocessor,theBranchBoxcantrans-latethetransmissionsignalofindoorunitstoachievetheoptimumcontrol.

2-2-1. System example

2-2-2. Method for identifying■ Outdoor unit

Model type

Power supplyV: Single phase 220/230/240V 50HzY: 3-Phase 380/400/415V 50Hz

Multi type heat pumpinverter outdoor unit

Indicates equivalent to rated cooling capacity.(O0.1kW)

Number of connectable indoor units (MAX.)

Control and refrigerantA : New A control and R410A

Branch box (Controller)

Number of branches5 : 5 branches3 : 3 branches

Model type

Symbol of factory

Applicable refrigerantA : R410A

(Indispensable)Optional parts

M X Z – 8 B 140 V A

P A C – A K 5 3 BC

■ Branch box

OCH480D

Page 7: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

7

2-3. TYPICAL COMBINATION EXAMPLEBranch box is located INSIDE of condominium

Branch box(Inside)

Installing branch box indoorsOnly1pipingisrequiredbetweentheoutdoorandindoorofferingafineexternalview.

Branch box (5 branch type)

Outdoor unit

SEZ-60 MSZ-35 MSZ-35 MSZ-25 MSZ-25

Living Dining Bedroom (1) Bedroom (2)Masterbedroom

■ System example of 5 indoor units

■ VerificationTheratedcapacityshouldbedeterminedbyobservingthetablebelow.Theunit’squantitiesarelimitedin2to8units.Forthenextstep,makesurethattheselectedtotalratedcapacityisinarangeasshownbelow.Thetotalindoorunitcapacityshouldbewithintheoutdoorunits.Combinationofexcessiveindoorunitsandanoutdoorunitmayreducethecapacityofeachindoorunit.Theratedindoorcapacityisasthetablebelow.• MXZ-8B140 3.0 ~ 18.5 kW• MXZ-8B160 3.0 ~ 20.2 kW

Example: MXZ-8B140

Total rated capacity

18.0 18.5kW

MSZ-25 = 2.5+

+

+

+SEZ-60 = 6.0

MSZ-35 = 3.5

MSZ-35 = 3.5

MSZ-25 = 2.5

Indoorunittype(capacityclass) 15 18 20 22 25 35 42 50 60 71 80 100Ratedcapacity(cooling)(kW) 1.5 1.8 2.0 2.2 2.5 3.5 4.2 5.0 6.0 7.1 8.0 10.0

OCH480D

Page 8: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

8

2-4. INSTALLATION2-4-1. Outdoor unit installation location Forbestperformance,selectproperposition. ●Avoidplaceswherecombustiblegasmaybegeneratedorleak. ●Avoiddirectsunlightorothersourcesofheat. ●Installsunshadetoprotecttheoutdoorunitifdirectsunlighthitstheunit. ●Installtheoutdoorunitwithenoughdistancebetweenneighboursasoperationnoisemaydisturbtheneighbours. ●Avoidthepositionthattheunitiscoveredbysnoworsnowblowsdirectlyagainsttheairoutlet.Thesnowblockorblowwill

reducetheairflowoftheoutdoorunit.Intheareasofheavysnow,specialcountermeasuresmustbetakenatinstallationtoprotecttheoutdoorunitfrommalfunc-tioncausedbysnow.

●Selectalocationpermittingeasywiringandpipeaccesstothepowersourceandindoorunit. ●Drainwatermustbedrainedfreelyduringoperation.Checkfordraining.

2-4-2. Ventilation and service space (1) Windy location installation

Wheninstallingtheoutdoorunitonarooftoporotherlocationunprotectedfromthewind,situatetheairoutletoftheunitsothatitisnotdirectlyexposedtostrongwinds.Strongwindenteringtheairoutletmayimpedethenormalairflowandamal-functionmayresult.Thefollowingshows3examplesofprecautionsagainststrongwinds.

●Facetheairoutlettowardsthenearestavailablewallabout50cmawayfromthewall.(Fig.2-1) ●Installanoptionalairguideiftheunitisinstalledinalocationwherestrongwindsfromatyphoon,etc.maydirectlyenter

theairoutlet.(Fig.2-2) AAirguide ●Positiontheunitsothattheairoutletblowsperpendicularlytotheseasonalwinddirection,ifpossible.(Fig.2-3) BWinddirection

Fig. 2-1

Fig. 2-2 Fig. 2-3

OCH480D

Page 9: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

9

(2) When installing a single outdoor unit Minimumdimensionsareasfollows,exceptforMax.,meaningMaximumdimensions,indicated. Refertothefiguresforeachcase. ●Obstaclesatrearonly(Fig.2-4) ●Obstaclesatrearandaboveonly(Fig.2-5) ·Donotinstalltheoptionalairoutletguidesforupwardairflow. ●Obstaclesatrearandsidesonly(Fig.2-6) ●Obstaclesatfrontonly(Fig.2-7) *Whenusinganoptionalairoutletguide,theclearanceis500mmormore. ●Obstaclesatfrontandrearonly(Fig.2-8) *Whenusinganoptionalairoutletguide,theclearanceis500mmormore. ●Obstaclesatrear,sides,andaboveonly(Fig.2-9) ·Donotinstalltheoptionalairoutletguidesforupwardairflow.

150

250

250

1500

500

Max. 500

1000

200

300200Fig. 2-4

Fig. 2-8Fig. 2-7

Fig. 2-5 Fig. 2-6

Fig. 2-9

unit : mm

300

1000

Max. 500

150

1000

OCH480D

Page 10: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

10

(3) When installing multiple outdoor units Leave10mmspaceormorebetweentheunits. ●Obstaclesatrearonly(Fig.2-10) ●Obstaclesatrearandaboveonly(Fig.2-11) •Nomorethan3unitsmustbeinstalledsidebyside.Inaddition,leavespaceasshown. •Donotinstalltheoptionalairoutletguidesforupwardairflow. ●Obstaclesatfrontonly(Fig.2-12) *Whenusinganoptionalairoutletguide,theclearanceis1000mmormore. ●Obstaclesatfrontandrearonly(Fig.2-13) *Whenusinganoptionalairoutletguide,theclearanceis500mmormore. ●Singleparallelunitarrangement(Fig.2-14) *Whenusinganoptionalairoutletguideinstalledforupwardairflow,theclearanceis1000mmormore. ●Multipleparallelunitarrangement(Fig.2-15) *Whenusinganoptionalairoutletguideinstalledforupwardairflow,theclearanceis1500mmormore. ●Stackedunitarrangement(Fig.2-16) •Theunitscanbestackedupto2unitshigh. •Nomorethan2stackedunitsmustbeinstalledsidebyside.Inaddition,leavespaceasshown.

300

1500

500

1500Max. 300

1000600

2000

150

1500500

1500

1500800

150

1500600

3000

500

Fig. 2-14Fig. 2-13

Fig. 2-12Fig. 2-11Fig. 2-10

Fig. 2-15

Fig. 2-16

unit : mm

OCH480D

Page 11: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

11

2-5. SIMPLIFIED PIPING SYSTEMPiping connection size

Liquid (mm)

Gas (mm)

{9.52

{15.88

The piping connection size differs according to the type and capacity of indoor units. Match the piping connection size of branch box with indoor unit.If the piping connection size of branch box does not match the piping connection size ofindoor unit, use optional different-diameter (deformed) joints to the branch box side.(Connect deformed joint directly to the branch box side.)

A B

Flareconnectionemployed.(Nobrazing!)

A

B B B B B

Branch box

■Incaseofusing1-branchboxFlareconnectionemployed(Nobrazing)

A A

A

B B B B B

2 branches pipe (joint) : optional parts

Branch box #1

Branch box #2

■Incaseofusing2-branchboxes

■Installationprocedure(2branchpipe(joint))RefertotheinstallationmanualsofMSDD-50AR-EandMSDD-50BR-E.

ForP100indoorunits,theindividualY-shapeconnectionpipesuse2portsonthebranchboxasshownbelow.

Port A

Port B

Port C

Port D

Port E

Indoor unit(P100)a

a

bY-shape connection pipe

Branch box

ToconnecttwoP100indoorunits,useportAandportB,andportCandportDonthebranchbox.

Port A

Port B

Port C

Port D

Port E

Indoor unit(P100)a

a

a

a

b

Indoor unit(P100)b

Y-shape connection pipe

Y-shape connection pipe

Branch box

ToconnectasingleP100indoorunit,useportAandportBonthebranchbox.

OCH480D

Page 12: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

12

3 SPECIFICATIONS

kW

W

kWK/min (CFM)

dBdB

mm (in.)mm (in.)mm (in.)kg (lbs)

kg (lbs)L

mmmm

External finish Refrigerant control Compressor Model Motor output Starter type Protection devicesCrankcase heaterHeat exchanger Fan Fan (drive) o No. Fan motor output AirflowDefrost method Noise level Dimensions

Weight Refrigerant Charge Oil (Model)Pipe size O.D.

Connection method

CoolingHeating

WDH

LiquidGas

Indoor sideOutdoor side

Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F) Heating : Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F), W.B. 6°C (43°F) Refrigerant piping length (one way) : Main Piping (From outdoor unit to branch box) : 5m Branch Piping (From branch box to each indoor units) : each 3m

2. Guaranteed operating range

Upper limitLower limitUpper limitLower limit

M-series, S-seriesD.B. 32°C, W.B. 23°C

D.B. 21°C, W.B. 15°CD.B. 27°CD.B. 20°C

P-seriesD.B. 35°C, W.B. 22.5°CD.B. 19°C, W.B. 15°C

D.B. 28°CD.B. 17°C

Outdoor

D.B. 46°CD.B. –5°C

D.B. 21°C, W.B. 15°CD.B. –15°C, W.B. –15°C

Cooling

Heating

Service Ref.

OU

TDO

OR

UN

ITRE

FRIGE

RANT

PIPIN

G

MXZ-8B140VA MXZ-8B160VA MXZ-8B140YA MXZ-8B160YA

Power supply (phase, cycle, voltage)

BreakerMax. current (Outdoor unit only)

Conversion formula:

Conversion formula

kcal/h = kW o 860Btu/h = kW o 3412CFM = m3/min o 35.31

[6.35mm1/4 inch

[9.52mm3/8 inch

[12.7mm1/2 inch

[15.88mm5/8 inch

[19.05mm3/4 inch

Indoor

3. Guaranteed voltage MXZ-8B140/160VA: 198~264V, 50Hz MXZ-8B140/160YA: 342~456V, 50Hz

4. Above data are based on the indicated voltage. MXZ-8B140/160VA: Single, 50Hz, 220/230/240V MXZ-8B140/160YA: 3-phase, 50Hz, 380/400/415V 5. Refer to the service manual of indoor unit for the indoor unit's specifications.

14.0 15.5 14.0 15.5

17.62/16.85/16.15 21.63/20.69/19.82 5.93/5.63/5.43 7.24/6.87/6.633.86 4.71 3.86 4.71

99.6 99.0 98.9 98.9

16.0 18.0 16.0 18.03.87 4.77 3.87 4.77

17.68/16.91/16.21 21.90/20.95/20.08 5.95/5.65/5.44 7.32/6.95/6.7099.5 99.0 98.9 99.0

2.9 3.3 2.9 3.3

100(3,530) 106(3,742) 100(3,530) 106(3,742)

50 51 50 5152 54 52 54

714

714Please refer to "9.ELECTRICAL WIRING"

29.5 13Single, 50Hz, 220/230/240V 3-phase, 50Hz, 380/400/415V

Munsall 3Y 7.8/1.1Linear Expansion Valve (In branch box)

HermeticANB33FNBMTANB33FDSMT

Line startHP switch, LP switch, Discharge thermo

-Plate fin coil

Propeller fan × 20.060+0.060

Reverse cycle

950(37-3/8)330+30(13+1-3/16)

1,350(53-1/8)139(306)129(284)

FlaredFlared

R410A8.5(18.7),40m

2.3(FV50S)[9.52[15.88

Sta

ndar

d pe

rform

ance Rated Cooling capacity

Rated power consumption *1Operating current *1Operating power factor *1Starting current (Outdoor unit)Rated Heating capacity Rated power consumption *1Operating current *1Operating power factor *1Starting current (Outdoor unit)

kWkWA%A

kWkWA%A

A

Hea

ting

Coo

ling

*1 Electrical data is only for outdoor unit.

MXZ-8B140VA MXZ-8B140YAMXZ-8B160VA MXZ-8B160YA

OCH480D

Page 13: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

13

4-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS4-1-1. Method for obtaining system cooling and heating capacity:Toobtainthesystemcoolingandheatingcapacityandtheelectricalcharacteristicsoftheoutdoorunit,firstadduptheratingsofalltheindoorunitsconnectedtotheoutdoorunit(seetablebelow),andthenusethistotaltofindthestandardcapacitywiththehelpofthetablesatthebackofthemanual"INDOORUNITSCOMBINATIONSHEETS".

(1) Capacity of indoor unit

4-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:

(1) The capacity of each indoor unit (kW)=thecapacityA(orB)o

(2) Sample calculation (using the system described above in 4-1-1. (2) ):

modelcapacitytotalmodelcapacityofallindoorunits

During cooling: During heating:

•Thetotalmodelcapacityoftheindoorunitis:2.5o2+5.0o2=15.0kWTherefore,thecapacityofMSZ-EF25VEandPEAD-RP50JAQwillbecalculatedasfollowsbyusingtheformulain4-1-2.(1):

Model25=14.0o=2.33kW

Model50=14.0o=4.67kW

•Thetotalmodelcapacityofindoorunitis:2.5o2+5.0o2=15.0Therefore,thecapacityofMSZ-EF25VEandPEAD-RP50JAQwillbecalculatedasfollowsbyusingtheformulain4-1-2.(1):

Model25=16.0o=2.67kW

Model50=16.0o=5.33kW

2.515.05.015.0

5.015.0

2.515.0

(2) Sample calculation1Systemassembledfromindoorandoutdoorunit(inthisexamplethetotalcapacityoftheindoorunitsisgreaterthanthatoftheoutdoorunit)

•Outdoorunit MXZ-8B140VA •IndoorunitMSZ-EF25VEo2,PEAD-RP50JAQo 22Accordingtotheconditionsin1,thetotalcapacityoftheindoorunitwillbe:2.5o2+5.0o2=15.03Thefollowingfiguresareobtainedfromthe150totalcapacityrowofthestandardcapacitydiagram(INDOORUNITSCOMBINATIONSHEETS:atthebackofthemanual).

Capacity(kW) Outdoorunitpowerconsumption(kW) Outdoorunitcurrent(A)/230V

Cooling Heating Cooling Heating Cooling Heating

A14.0 B16.0 5.22 5.01 22.9 22.0

4 DATA

Modelnumberforindoorunit

Model15

Model18

Model20

Model22

Model25

Model35

Model42

Model50

Model60

Model71

Model80

Model100

Modelcapacity 1.5 1.8 2.0 2.2 2.5 3.5 4.2 5.0 6.0 7.1 8.0 10.0

OCH480D

Page 14: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

14

4-2. CORRECTING COOLING AND HEATING CAPACITY4-2-1. Correcting Changes in Air Conditions(1)Theperformancecurvecharts(Figure4-1,4-2,4-3,4-4)showthechangeratioofcapacityandinput(powerconsumption)

accordingtotheindoorandoutdoortemperatureconditionwhendefinetheratedcapacity(totalcapacity)andratedinputunderthestandardconditioninstandardpipinglength(5m)as“1.0”.

•Standardconditions:

•Usetheratedcapacityandratedpowervaluesgiveninthecharacteristicstableforeachindoorunit. •Thecapacityisthesinglevalueonthesideoftheoutdoorunit; Thecapacityonthesidesofeachindoorunitmustbeaddedtoobtainthetotalcapacity.

(2) Thecapacityofeachindoorunitmaybeobtainedbymultiplyingthetotalcapacityobtainedin(1)bytheratiobetweenthe

individualcapacityattheratedtimeandthetotalcapacityattheratedtime.

IndividualcapacityattheratedtimeIndividualcapacityunderstatedconditions=Totalcapacityunderthestatedconditionso

Totalcapacityattheratedtime

Rated cooling capacity

Rated heating capacity

Indoor D.B. 27 °C / W.B. 19 °COutdoor D.B. 35 °CIndoor D.B. 20 °COutdoor D.B. 7 °C / W.B. 6 °C

-5 0 5 10 15 20 25 30 35 40 46

1618

20

22

0.6

0.8

1

1.2

1.4

Coo

ling

capa

city

ratio

Outdoor intake air dry-bulb temperature <:D.B. >

-5 0 5 10 15 20 25 30 35 40 46

1618

2022

0.4

0.6

0.8

1.0

1.2

Coo

ling

inpu

t rat

io

Outdoor intake air dry-bulb temperature <:D.B. >

Fig.4-1Coolingcapacity

Fig.4-3Heatingcapacity

Fig.4-4Heatinginput

Fig.4-2Coolinginput

Outdoorintakeairwet-bulbtemperature<:W.B.> Outdoorintakeairwet-bulbtemperature<:W.B.>

Indoorintakeairwet-bulbtemperature<:W.B.> Indoorintakeairwet-bulbtemperature<:W.B.>

Indoorintakeairdry-bulbtemperature<:D.B.>Indoorintakeairdry-bulbtemperature<:D.B.>

Note :Thesediagramsshowthecasewheretheoperationfrequencyofacompressorisfixed.

(3)Capacitycorrectionfactorcurve

OCH480D

Page 15: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

15

4-2-2. Correcting Capacity for Changes in the Length of Refrigerant PipingToobtaintheratio(andthecorrectedpipinglength)oftheoutdoorunitsratedcapacityandthetotalin-useindoorcapacity,firstfindthecapacityratiocorrespondingtothestandardpipinglengthfromFig.4-5,Fig.4-6andthenmultiplybythecapacityfromFig.4-1,4-2,Fig.4-3,4-4toobtaintheactualcapacity.

(2) Method for Obtaining the Corrected Piping LengthCorrectedpipinglength=(Actualpipinglengthbetweenoutdoorunitandthefarthestindoorunit)+(0.30onumberofbendsinthepiping)(m)

2.2 (15.7%)7.0 (50%)10.5 (75%)14.0 (100%)18.5 (132%)

0.6520 40 60 80

20 40 60 80

0.70

0.75

0.80

0.85

0.90

0.95

1.00

CoolingCa

pacity(ra

tio)[%]

Correctedpipinglength(m)

0.920 40 60 80

0.95

1

HeatingCapacity(ratio)[%]

Correctedpipinglength(m)

Fig. 4-6 Heating capacity correction curveMXZ-8B140VA, MXZ-8B140YA, MXZ-8B160VA, MXZ-8B160YA

2.5(16%)7.8 (50%)

0.6520 40 60 80

20 40 60 80

0.70

0.75

0.80

0.85

0.90

0.95

1.00

15.5 (100%)20.2 (130%)

11.6 (75%)

(1) Capacity correction factorFig. 4-5 Cooling capacity correction curve

MXZ-8B140VA, MXZ-8B140YA MXZ-8B160VA, MXZ-8B160YA

Correctedpipinglength(m)

Totalratedcapacityofindoorunits(kW)

CoolingCa

pacity(ra

tio)[%] Totalratedcapacity

ofindoorunits(kW)

OCH480D

Page 16: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

16

1.5m

1mMICROPHONE

UNIT

GROUND

4-3. NOISE CRITERION CURVES

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

OC

TAVE

BA

ND

SO

UN

D P

RES

SUR

E LE

VEL,

dB

(0 d

B =

0.0

002

µbar

)

BAND CENTER FREQUENCIES, Hz

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

MXZ-8B140VAMXZ-8B140YA COOLING

MODE

HEATING50

SPL(dB)

52

LINE

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE

OC

TAVE

BA

ND

SO

UN

D P

RES

SUR

E LE

VEL,

dB

(0 d

B =

0.0

002

µbar

)

BAND CENTER FREQUENCIES, Hz

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

MXZ-8B160VAMXZ-8B160YA COOLING

MODE

HEATING51

SPL(dB)

54

LINE

OCH480D

Page 17: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

17

5 OUTLINES AND DIMENSIONS

MXZ-8B140VA MXZ-8B140YA MXZ-8B160VA MXZ-8B160YA unit : mm

Over

Ove

rO

ver

Over

Less

than

Piping and wiring connectionscan be made from 4 directions:front, right, rear and below.

4 PIPING-WIRING DIRECTIONS3 FOUNDATION BOLTS2 SERVICE SPACE1 FREE SPACE (Around the unit)Please secure the unit firmlywith 4 foundation (M10) bolts.(Bolts and washers must be purchased locally.)

<Foundation bolt height>

Dimensions of space neededfor service access areshown in the below diagram.

The diagram below shows a basic example.Explanation of particular details aregiven in the installation manuals etc.

30

FOUNDATION10

500

500

150

Service space

Over 150Over 1000

FRE

E

Over 10Over 10

Example of Notes1···Refrigerant GAS pipe connection (FLARE)[15.88(5/8 inch)2···Refrigerant LIQUID pipe connection (FLARE)[9.52(3/8 inch) Indication of STOP VALVE connection location

Terminal connectionLeft ····Power supply wiringRight ··Indoor/Outdoor wiringEarth terminal

Handle for moving

Service panel

Handle for moving

2

1

A

1507

1423

23

950322

1350

635

371

Installation Feet

2-12×36 Oval holes(Foundation Bolt M10)

2-U Shaped notched holes(Foundation Bolt M10)

3033

0

175 600 175

56

4270

37 5653

1937

041

728

Air Discharge

Side Air Intake

Rear Air Intake

Rear piping coverFront piping cover

Bottom piping hole(Knock-Out)

71

71

219

81

14514514522030

Side Air Intake

Handle for moving

Handle for moving

Rear Air Intake

Handle for moving

Air Intake

( )

Drain hole( 5-[33)

Piping Knockout Hole Details

6373

2355

27

9265

4045Power supply wiring hole(2-[27Knockout)

Rear trunking hole(Knockout)

Rear piping hole(Knockout)

[929227

2363

73

4075

92

5519

Power supply wiring hole(2-[27Knockout)

Right trunking hole(Knockout)

Right piping hole(Knockout)

[926373

23

5527

40 45

65

92

Power supply wiring hole(2-[27Knockout)

Front trunking hole(Knockout)

Front piping hole(Knockout)

[92

MODEL AMXZ-8B140VA/160VA 1079MXZ-8B140YA/160YA 930

OCH480D

Page 18: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

18

6 WIRING DIAGRAM

MXZ-8B140VA MXZ-8B160VA

Power turned on

LED on the controller board display the operation and inspection status as follows.If LED does not light, it indicates that no power is supplied to the board:

Operation / Inspection Display

Normal status

Faulty status(blinking)

Details

● WARNING:When the main supply is turned off, the voltage[340 V]in the main capacitor will drop to 20 V in approx. 2 minutes (input voltage : 240 V). when servicing, make sure that LED on the outdoor circuit board goes out, and then wait for at least 1 minute.● Components other than the outdoor board may be faulty : Check and take corrective action, referring to the service manual. Do not replace the outdoor board without checking.

Cautions when Servicing

Code

(blinks)

Operation status display, such as C5. H7F3F5F9E8

E9

EA

EbEcE0 - E7EE, EFEd

63L connector (red) is open.63H connector (yellow) is open.2 connectors (63H/63L) are open.Branch box/outdoor communication error (Signal receiving error)(Outdoor unit)Indoor/branch box communication error (Signal receiving error)(Branch box)Branch box/outdoor communication error (Transmitting error)(Outdoor unit)Indoor/branch box communication error (Transmitting error)(Branch box)•Mis-Wiring of indoor-branch box / branch box-outdoor unit connecting wire.•Too many indoor units / branch box are in the system.Mis-wiring of indoor-branch box/branch box-outdoor unit connecting wire (converse wiring or disconnection)Startup time overCommunication error except for outdoor unitCombination errer, undefined errorSerial communication error

SYMBOL NAMETB1MCMF1, MF221S4

SV1,SV2

63L

TH3TH4TH6TH7DCL

52C

CB

P. B.

63H

Terminal Block <Power Supply, Branch Box>Motor for CompressorFan MotorsSolenoid Valve <Four-Way Valve>

Solenoid Valve <Bypass Valve>

High Pressure Switch

High Pressure SensorLow Pressure Switch

63HS

Thermistor <Outdoor Pipe>Thermistor <Compressor>Thermistor <Outdoor 2 - Phase Pipe>Thermistor <Outdoor>Reactor

52C Relay

Main Smoothing CapacitorCY1,CY2 Capacitor

Power Circuit Board

LI / NI

EI,E2,E3,E4

F1 ~ F4X51,X52,X54,X55

SW1

SW2SW4

Connection Terminal <L / N - Phase>P2,N2 Connection Terminal <CB>DCL1,DCL2 Connection Terminal <DCL>IGBT Power Module

Connection Terminal <Ground>

Controller Circuit Board

Fuse <T6.3AL250V>Relay

Switch <Forced Defrost, Defect History Record Reset>Switch <Self Diagnosis Switch>Switch <Test Operation>

Connection Terminal <U / V / W - Phase>U / V / W

SW5 Switch <Function Switch>SW6SW7SW8SW9

SSCN3SCNIT

Switch <Model Select>Switch <Function Setup>Switch <Function Setup>Switch <Function Setup>

CN31 Connector

LED3 Light Emitting Diode<Operation Inspection Indicators>

Connector <Connection for Option>Connector <Connection for Option>

CNDM Connector <Connected for Option (Contact Input)>

CN51 Connector <Connection for Option>

Connector <Connection for Option>

C. B.

Details CodeU2U7

U1ULU6UFUHUPU3U4

U5U8U9PA

Compressor temperature faultLow-discharge superheating fault, Erroneous connection of refrigerant pipes or the connecting wiresHigh pressure fault (63H operates)Low pressure fault (63L operates)Abnormality of power modulsCompressor over current shutoff (Start up locked)Current sensor fault (P. B.)Compressor overcurrent shutoff faultCompressor thermistor (TH4) open or short-circuitOutdoor unit thermistors (TH3, TH6, TH7, and TH8), 63HS, and branch doxthermistors open or short-circuitRadiator panel temperature faultAbnormality in outdoor fan motorVoltage fault, current sensor faultForced compressor stop(Overlap malfunction of drain pump in indoor unitand linear expansion valve in branch box)

MODEL

140V

SW6

ONOFF

1 2 3 4 5 6 7 8

160V ONOFF

1 2 3 4 5 6 7 8

MS3~

MF1 1

3

1

7CNF1(WHT)

TRANS

MS3~

MF2 17

CNF2(WHT)

CNDC(PNK)

2

41 1 2 12TH7/6(RED)

TH3(WHT)

TH4(WHT)

TH7

t° t° t° t°

TH6 TH3 TH4

31

63HS

63HS(WHT)

63L(RED)

31

63L

63H(YLW)

31

63H

1 7

3 1

CNS(WHT)

2

7

CN2(WHT)

F3

1 2

1313

CNAC(WHT)

CN4(WHT)

1 2

3 4

F4

F2

F1 21S4(GRN)

SV2(BLU)

X52

X55

21S4 SV2

13 SV1(GRY)

X54

SV1

13 SS(WHT)

X51

1 14CNM(WHT)

1 3

3

CN52C(RED)

1 5CNIT(RED)

P. B.

711 2

2

2

CN2(WHT)CN4

(WHT)

C. B.

DCL

LINI

N2

P2

U

U DCL2 DCL1

IGBT

CB

V

V

W

W

MC

RED

RED

WHT

WHT

BLK

MS3~

13

CNDC(PNK)

1

3

52C

52C

CNAC

2(R

ED)

CNAC

1(W

HT)

E3E2

BLK

BLK

BLK

BLK

EI

1 3

3

CN52C(RED)

1

3

E4

BLU

S1NL S2 S3

YLW

ORN

GRN

/ YL

W

BRN

RED

TB1

CY1

CY2

BRANCH BOX

POWER SUPPLY~/N220/230/240V 50HZ220V 60HZ

LED3

1

5

CN51

(WHT

)

13CN

DM(W

HT)

13CN

3S(W

HT)

SW8

SW5

SW1

CN31

SW6

SW9

SW2

SW7

SW4

w1

The black square ( ) indicates a switch position.*1 MODEL SELECT

The black square ( ) indicates a switch position.

OCH480D

Page 19: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

19

MXZ-8B140YA MXZ-8B160YA

Power turned on

LED on the controller board display the operation and inspection status as follows.If LED does not light, it indicates that no power is supplied to the board:

Operation / Inspection Display

Normal status

Faulty status(blinking)

Details

● WARNING:When the main supply is turned off, the voltage[540 V]in the main capacitor will drop to 20 V in approx.5 minutes (input voltage : 380 V). when servicing, make sure that LED on the outdoor circuit board goes out, and then wait for at least 5 minute.● Components other than the outdoor board may be faulty : Check and take corrective action, referring to the service manual. Do not replace the outdoor board without checking.

Cautions when Servicing

Code

(blinks)

Operation status display, such as C5. H7F3F5F9E8

E9

EA

EbEcE0 - E7EE, EFEd

63L connector (red) is open.63H connector (yellow) is open.2 connectors (63H/63L) are open.Branch box/outdoor communication error (Signal receiving error)(Outdoor unit)Indoor/branch box communication error (Signal receiving error)(Branch box)Branch box/outdoor communication error (Transmitting error)(Outdoor unit)Indoor/branch box communication error (Transmitting error)(Branch box)•Mis-Wiring of indoor-branch box / branch box-outdoor unit connecting wire.•Too many indoor units / branch box are in the system.Mis-wiring of indoor-branch box/branch box-outdoor unit connecting wire (converse wiring or disconnection)Startup time overCommunication error except for outdoor unitCombination errer, undefined errorSerial communication error

SYMBOL NAMETB1

MCMF1, MF221S4

SV1,SV2

63L

TH3TH4TH6TH7

CONV.B.

63H

Terminal Block <Power Supply>TB2 Terminal Block <Branch Box>

Motor for CompressorFan MotorsSolenoid Valve <Four-Way Valve>

Solenoid Valve <Bypass Valve>

High Pressure SwitchLow Pressure Switch

Thermistor <Outdoor Pipe>Thermistor <Compressor>Thermistor <Outdoor 2 - Phase Pipe>Thermistor <Outdoor>

ACL1~ACL4CB1, CB2CKRS

Reactor

CapacitorRush Current Protect Resistor

Main Smoothing Capacitor

Controller Circuit Board

F1 ~ F4X51,X52,X54,X55

SW1

SW2SW4

Connection Terminal <Ground>

Controller Circuit Board

Fuse <T6.3AL250V>Relay

Switch <Forced Defrost, Defect History Record Reset>Switch <Self Diagnosis Switch>Switch <Test Operation>

52C Relay

TB-C1

X52A

Connection Terminal TB-N1 Connection Terminal IGBT Power Module

Connection Terminal TB-P2

P. B. Power Circuit Board

TB-L1/L2/L3 Connection Terminal <L1/L2/L3-Power Supply>Connection Terminal <U / V / W - Phase>TB-U/V/W

GD1, GD3

N. F. Noise Filter Circuit Board

LO1/LO2/LO3/NOConnection Terminal <L1/L2/L3/N-Power Supply>Connection Terminal <L1/L2/L3/N-Power Supply>

Connection Terminal <L1-Power Supply>

LI1/LI2/LI3/NI

SW5 Switch <Function Switch>SW6SW7SW8SW9

SSCN3SCNIT

Switch <Model Select>Switch <Function Setup>Switch <Function Setup>Switch <Function Setup>

CN31 Connector

LED3 Light Emitting Diode<Operation Inspection Indicators>

Connector <Connection for Option>Connector <Connection for Option>

CNDM Connector <Connected for Option (Contact Input)>

CN51 Connector <Connection for Option>

Connector <Connection for Option>

C. B.

L1-A1 / INConnection Terminal <L1-Power Supply>L1-A2 / OUConnection Terminal <L2-Power Supply>L2-A2 / OUConnection Terminal <L3-Power Supply>L3-A2 / OUConnection Terminal <N-Power Supply>N-INConnection Terminal <CK>CK-OU

Details CodeU2U7

U1ULU6UFUHUPU3U4

U5U8U9PA

Compressor temperature faultLow-discharge superheating fault, Erroneous connection of refrigerant pipes or the connecting wiresHigh pressure fault (63H operates)Low pressure fault (63L operates)Abnormality of power modulsCompressor over current shutoff (Start up locked)Current sensor fault (P. B.)Compressor overcurrent shutoff faultCompressor thermistor (TH4) open or short-circuitOutdoor unit thermistors (TH3, TH6, TH7), 63HS, and branch doxthermistors open or short-circuitRadiator panel temperature faultAbnormality in outdoor fan motorVoltage fault, current sensor faultForced compressor stop(Overlap malfunction of drain pump in indoor unitand linear expansion valve in branch box)

MODEL

140Y

SW6

ONOFF

1 2 3 4 5 6 7 8

160Y ONOFF

1 2 3 4 5 6 7 8

CY1,CY2 Capacitor

High Pressure Sensor63HS

MS3~

MF1 1

3

1

7CNF1(WHT)

TRANS

MS3~

MF2 17

CNF2(WHT)

CNDC(PNK)

2

41 1 2 12TH7/6(RED)

TH3(WHT)

TH4(WHT)

TH7

t° t° t° t°

TH6 TH3 TH4

31

63HS

63HS(WHT)

63L(RED)

31

63L

63H(YLW)

31

63H

1 7

3 1

CNS(WHT)

2

7

CN2(WHT)

F3

1 2

1313

CNAC(WHT)

CN4(WHT)

1 2

3 4

F4

F2

F1 21S4(GRN)

SV2(BLU)

X52

X55

21S4 SV2

13 SV1(GRY)

X54

SV1

IGBTTB-W

TB-V

TB-UTB-L3

13 SS(WHT)

X51

1 14CNM(WHT)

LED3

1 5CNIT(RED)

1

5

CN51

(WHT

)

13CN

DM(W

HT)

13CN

3S(W

HT)

SW8

SW5

SW1

CN31

SW6

SW9

SW2

SW7

SW4

P. B.

71

7

CN2(WHT)CN7

(WHT)

122 CN4

(WHT)

122

2

CN5(RED)

2CNCT(RED)

N. F.

CONV. B.

C. B.

RED

WHT

CNDC(PNK)

CNL(BLU)

1 3 13

11 31 3CNAC2(RED)

CNAC1(WHT)

BLK

BLK

ACL4

ACL1

ACL2

ACL3BLK

GD1

1

33

CN7

(WHT

)

UVW MC

REDWHT

RED

RED

RED

RS

X52A

WHT

BLK

BLK

RED

RED

RED

WHT

WHT

WHT

WHT

BLK

BLK

MS3~

TB-L2TB-L1

TB-P2

CB1 CB2 CKBL

K

BRN

GD3

S1

N

L1

L2

L3

S2

S3

BLU

GRN/YLW

YLW

ORN

WHT

BRN

RED

BRANCH BOX

TB1

TB2

POWER SUPPLY3N~380/400/415V 50HZ

RED

RED BL

K

BLU

BLU

1 3

3

TB-C1 TB-N1

L3-O

UBL

KL3

-A2

L2-O

U

L2-A

2

L1-A

1

LO1LI1

LO2LI2

LO3LI3

NONI

L1-IN N-IN

L1-O

U

CK-O

UL1

-A2

2

CY1

CY2

w1

The black square ( ) indicates a switch position.

*1 MODEL SELECTThe black square ( ) indicates a switch position.

OCH480D

Page 20: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

20

7 NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION

REFRIGERANT SYSTEM DIAGRAM MXZ-8B140VA MXZ-8B140YA MXZ-8B160VA MXZ-8B160YA

Piping connection size

■Incaseofusing2-branchboxes

A

B B B B B

Branch box

A A

A

B B B B B

2 branches pipe (joint) : optional parts

Branch box #1

Branch box #2

Thermistor TH6(Pipe temperature : condenser)

Thermistor TH7(Outdoor temperature)

Thermistor TH3(Pipe temperature : liquid)

Strainer#100

Strainer#100

Oil separatorLow pressure switch 63L

High pressure switch 63H

Compressor

Thermistor TH4(Compressor temperature)

Thermistor TH8(Fin temperature)

Strainer#100

Strainer#50

Check valve(High Pressure)

Check valve(Low Pressure)

Capillary tube3Capillary

tube4

Capillary tube2

Capillary tube1

EDCBA

Strainer#100

Condenser / evaporatortemperature thermistor(TH5 or RT12)

Pipe temperaturethermistor / liquid(TH2 or RT13)

Strainer#100

Indoor units Branch box Outdoor unit

Thermistor (TH-A~E)(Gas pipe temperature)

LEV A~E(Linear expansion valve)

Room temperaturethermistor (TH1 or RT11)

Service port

Service port

Ball valve

Stop valve

Bypass valve(SV2)

Bypass valve (SV1)

High pressure sensordischarge pressure sensor 63HS

Accumulator

4-way valve

Distributor with Strainer

Refrigerant flow in coolingRefrigerant flow in heating

Outdoor unitMXZ-8B140VAMXZ-8B160VAMXZ-8B140YAMXZ-8B160YAPAC-AK53BC

PAC-AK32BCBranch box

Capillary tube 1(For return of oil from oil separator)

Capillary tube 2(For SV2)

Capillary tube 3ahead of LEV (in cooling mode)

Capillary tube 4behind LEV(in cooling mode)

[2.5 o [0.8 o L1000 [4 o [2.4 o L250

([4 o [2.4 o L140) o 5 ([4 o [2.2 o L130) o 5

([4 o [2.4 o L140) o 3 ([4 o [2.2 o L130) o 3

unit : mm

■Incaseofusing1-branchboxFlareconnectionemployed(Nobrazing)

A B

Liquid(mm) {9.52

Gas(mm) {15.88

Thepipeconnectionsizediffersaccordingtothetypeandcapacityofindoorunits.Matchthepipingconnectionsizeofbranchboxwithindoorunit.Ifthepipingconnectionsizeofbranchboxdoesnotmatchthepipingconnectionsizeofindoorunit,useoptionaldifferent-diameter(deformed)jointstothebranchboxside.(Connectdeformedjointdirectlytothebranchboxside.)

■installationprocedure(2branchpipe(joint))RefertotheinstallationmanualsofMSDD-50AR-EandMSDD-50BR-E.

OCH480D

Page 21: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

21

Indoor unit type

Pipe size (mm)

(kW)LiquidGas

22[6.35[9.52

25[6.35[9.52

35[6.35[9.52

50[6.35[12.7

60[6.35[15.88 *

71[9.52[15.88

80[9.52[15.88

15[6.35[9.52

18[6.35[9.52

20[6.35[9.52

42[6.35[9.52

■Pipesize(Branchbox-Indoorunit)*ForMseriesorSseriesIndoorunit

Indoor unit typePipe size(mm)

(kW)LiquidGas

35[6.35[12.7

50[6.35[12.7

60[9.52[15.88

71[9.52[15.88

100w[9.52[15.88

■Pipesize(Branchbox-Indoorunit)*ForPseriesIndoorunit

When using 35, 50 type indoor unit of P series, use the flare nut (for R410A) attached to the indoor unit.Do not use the flare nut (for R407C) in the indoor unit accessory. If it is used, a gas leakage or even a pipe extraction may occur.* For the connection of P100 indoor unit(s), use the refrigerant pipes specified in the table below.

For liquidFor gas

[9.52 mm[15.88 mm

A UNIT

B UNIT

C UNIT

D UNIT

E UNIT

Liquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipe

[6.35 mm[9.52 mm[6.35 mm[9.52 mm[6.35 mm[9.52 mm[6.35 mm[9.52 mm[6.35 mm[12.7 mm

* 3- branch type is only for A, B, and C unit.

*

*

*

[6.35mm[9.52mm[12.7mm[15.88mm[19.05mm

Conversion formula1/4 inch3/8 inch1/2 inch5/8 inch3/4 inch

(1) Valve size for outdoor unit

(2) Valve size for branch unit

Different-diameter joint (optional parts) (Fig.7-1)

Fig.7-1

MAC-A454JPMAC-A455JPMAC-A456JPPAC-493PIPAC-SG76RJ-E

{9.52 ➝ {12.7{12.7 ➝ {9.52{12.7 ➝ {15.88{6.35 ➝ {9.52{9.52 ➝ {15.88

{9.52{12.7{12.7{6.35 {9.52

{12.7{9.52{15.88{9.52 {15.88

Connected pipes diametermm

Diameter Amm

Diameter BmmModel name

A B

When using 60 type indoor unit of MEXZ series, use the flare nut in the indoor unit accessory for the gas side connecting of indoor unit.Do not use the flare nut (gas side) attached to the indoor unit. If it is used, a gas leakage or even a pipe extraction may occur.

Y-shape connection pipe for 100 type indoor unit (optional parts) (Fig.7-2)Modelname Connectedpipediameter DiameterA DiameterB

mm mm mmPAC-AK52YP-E Liquid ø6.35→ø9.52 ø6.35 ø9.52

Gas ø9.52→ø15.88 ø9.52 ø15.88B

A

Fig.7-2

DistancebetweenbranchboxandY-shapeconnectionpipe(=a)

Liquid Gas

a b a b

1to10[m] 6.35 9.52 9.52 15.8810[m]ormore 6.35 9.52 12.7*1 15.88

*1Toconnecta 12.7gaspipe,useajointpipe(MAC-A454JP)

Port A

Port B

Port C

Port D

Port E

Indoor unit(P100)a

a

bY-shape connection pipe

Branch box

<Length limit>1[m]≤aa+b≤15[m]

OCH480D

Page 22: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

22

8 TROUBLESHOOTING

<Check code display by self-diagnosis and actions to be taken for service (summary)>Presentandpastcheckcodesareloggedanddisplayedonthewiredremotecontrollerandcontrolboardofoutdoorunit.Actionstobetakenforservice,whichdependsonwhetherornotthetroubleisreoccurringatservice,aresummarizedinthetablebelow.Checkthecontentsbelowbeforeinvestigatingdetails.

8-1. TROUBLESHOOTING

Unit conditions at service Check code Actions to be taken for service (summary)

The trouble is reoccurring.

Displayed

Not displayed

Judge what is wrong and take a corrective action according to “8-3. SELF-DIAGNOSIS ACTION TABLE”.

Conduct trouble shooting and ascertain the cause of thetrouble according to “8-4. TROUBLESHOOTINGOF PROBLEMS”.

The trouble is not reoccurring.

Logged

Not logged

1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc. 2Reset check code logs and restart the unit after finishing service.3There is no abnormality concerning of parts such as electrical component, controller board, remote controller, etc.

1Re-check the abnormal symptom.2Conduct trouble shooting and ascertain the cause of the trouble according to “8-4. TROUBLESHOOTING OF PROBLEMS”.3Continue to operate unit for the time being if the cause is not ascertained.4There is no abnormality concerning of parts such as electrical component, controller board, remote controller, etc.

OCH480D

Page 23: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

23

8-2. CHECK POINTS FOR TEST RUN8-2-1. Before test run● Turnonthemainpowerswitchmorethan12hoursbeforestartingoperation.Startingoperationjustafterturningonthe

powerswitchcanseverelydamagetheinternalparts.Keepthemainpowerswitchturnedonduringtheoperationseason.● Aftercompletinginstallationandthewiringandpipingoftheindoorandoutdoorunits,checkforrefrigerantleakage,loose-

nessinthepowersupplyorcontrolwiring,wrongpolarity,andnodisconnectionofonephaseinthesupply.● Usea500-voltM-ohmtestertocheckthattheresistancebetweenthepowersupplyterminalsandgroundisatleast1M".● Donotcarryoutthistestonthecontrolwiring(lowvoltagecircuit)terminals.

Warning: Do not use the air conditioner if the insulation resistance is less than 1 M".

Insulation resistanceAfterinstallationorafterthepowersourcetotheunithasbeencutforanextendedperiod,theinsulationresistancewilldropbelow1M"duetorefrigerantaccumulatinginthecompressor.Thisisnotamalfunction.Performthefollowingprocedures.1.Removethewiresfromthecompressorandmeasuretheinsulationresistanceofthecompressor.2. Iftheinsulationresistanceisbelow1M",thecompressorisfaultyortheresistancedroppedduetotheaccumulationof

refrigerantinthecompressor.3.Afterconnectingthewirestothecompressor,thecompressorwillstarttowarmupafterpowerissupplied.Aftersupplying

powerforthetimesindicatedbelow,measuretheinsulationresistanceagain.•Theinsulationresistancedropsduetoaccumulationofrefrigerantinthecompressor.Theresistancewillriseabove1M" afterthecompressoriswarmedupfor4hours.(Thetimenecessarytowarmupthecompressorvariesaccordingtoatmosphericconditionsandrefrigerantaccumulation.)

•Tooperatethecompressorwithrefrigerantaccumulatedinthecompressor,thecompressormustbewarmedupatleast12hourstopreventbreakdown.

4. Iftheinsulationresistancerisesabove1M",thecompressorisnotfaulty.

Caution: • The compressor will not operate unless the power supply phase connection is correct.• Turn on the power at least 12 hours before starting operation.Staringoperationimmediatelyafterturningonthemainpowerswitchcanresultinseveredamagetointernalparts.Keepthepowerswitchturnedonduringtheoperationalseason.

●The followings must be checked as well.•Theoutdoorunitisnotfaulty.LEDonthecontrolboardoftheoutdoorunitflasheswhentheoutdoorunitisfaulty.•Boththegasandliquidstopvalvesarecompletelyopen.

8-2-2. Test run (1)UsingremotecontrollerRefertotheindoorunitinstallationmanual.

•Besuretoperformthetestrunforeachindoorunit.Makesureeachindoorunitoperatesproperlyfollowingtheinstallationmanualattachedtotheunit.

•Ifyouperformthetestrunforallindoorunitsatonce,youcannotdetectanyerroneousconnection,ifany,oftherefrigerantpipesandtheconnectingwires.*Thecompressoroperationisnotavailablefor3minutesatleastafterthepowerissupplied.

•Thecompressorcanemitnoisejustafterturnonthepowersupplyorincaseoflowoutsideairtemperature.

About the restart protective mechanismOncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner.

OCH480D

Page 24: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

24

Duringthetestrunsetwiththeoutdoorunit,operationon/offoroperationmodechangecannotbeperformedbytheremotecontroller,andtheoperationrelatingtothetestrunwhichismadewiththeoutdoorunitwillbepriortoanyothercommandsfromtheremotecontroller.SettheSW4-1toOFF( )tofinishtestrun.Emergencyoperationisnotavailableforthismodel.

8-2-3. Test run by outdoor unit SW4Thesettingoftestrun(ON/OFF)anditsoperationmode(cooling/heating)canbesetbySW4onthecontrollerboardofout-doorunit.1Setoperationmode(coolingorheating)bySW4-2.2StarttestrunbysettingSW4-1toON( )withtheindicatedoperationmodeofSW4-2.3FinishtestrunbysettingSW4-1toOFF( ).•OperationmodecannotbechangedbySW4-2duringtestrun.StoptestruntochangeoperationmodebySW4-1,andrestarttestrunbySW4-1afterthemodeischanged.

•Testrunautomaticallystops2hourslaterby2-hourOFFtimerfunction.•Testruncanbeperformedbytheremotecontroller.•Theremotecontrollerdisplayoftestrunbyoutdoorunitisthesameasthatoftestrunbyremotecontroller.

•Iftestrunissetwiththeoutdoorunit,thetestrunisperformedforallindoorunits.•Theremotecontrolleroperationbecomesunavailableoncethetestrunissetwiththeoutdoorunit.

ON

SW4

1 2

A StopB CoolingC OperationD Heating

A

C D

B

(Initial setting)

In case of the test run from outdoor unit, all indoor units operate. Therefore, you cannot detect any erroneous con-nection of refrigerant pipes and the connecting wires. If it aims at detection of any erroneous connection, be sure to carry out the test run from remote controller with reference to "(1) Using remote controller."

SW4-1SW4-2SW4-1SW4-2

ONOFFONON

Cooling operation

Heating operation

Note: After performing the test run, set SW4-1 to OFF.

•Afewsecondsafterthecompressorstarts,aclangingnoisemaybeheardfromtheinsideoftheoutdoorunit.Thenoiseiscomingfromthecheckvalveduetothesmalldifferenceinpressureinthepipes.Theunitisnotfaulty.The test run operation mode cannot be changed by DIP switch SW4-2 during the test run. To change the test run operation mode during the test run, stop the test run by DIP switch SW4-1. After changing the test run operation mode, resume the test run by switch SW4-1.

• After power is supplied or after an operation stop for a while, a small clicking noise may be heard from the inside of the branch box. The electronic expansion valve is opening and closing. The unit is not faulty.

When a test run is started by “Using SW4 in outdoor unit”, even if it carries out stop instructions by remote controller, outdoor unit does not stop. A test run is not ended. In this case, please set SW4 in outdoor unit to off.

Note:Besuretowaitatleast3minutesafterturningonthepowersupplybeforesettingSW4-1andSW4-2.IftheDIPswitchesaresetbefore3minuteshaveelapsed,thetestrunmaynotstart.

(2)UsingSW4inoutdoorunit

OCH480D

Page 25: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

25

8-3. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is put on> (Note1)RefertoindoorunitsectionforcodePandcodeE.Check code Abnormal point and detection method Case Judgment and action

None —

1Novoltageissuppliedtotermi-nalblock(TB1)ofoutdoorunit.a)Powersupplybreakeristurnedoff.

b)Contactfailureordisconnec-tionofpowersupplyterminal

c)Openphase(LorNphase)

2Electricpowerisnotchargedtopowersupplyterminalofout-doorpowercircuitboard.a)Contactfailureofpowersupplyterminal

b)Openphaseontheoutdoorpowercircuitboard

DisconnectionofconnectorSC-RorSC-S

3Electricpowerisnotsuppliedtooutdoorcontrollercircuitboard.a)Disconnectionofconnector(CNDC)

4Disconnectionofreactor(DCL)

5Disconnectionofoutdoornoisefiltercircuitboardorpartsfail-ureinoutdoornoisefiltercircuitboard

6Defectiveoutdoorpowercircuitboard

7Defectiveoutdoorcontroller circuitboard

1Checkfollowingitems.a)Powersupplybreakerb)Connectionofpowersupplyterminalblock.

(TB1)c)Connectionofpowersupplyterminalblock.

(TB1)2Checkfollowingitems.

a)Connectionofpowersupplyterminalblock.

(TB1)b)Connectionofterminalonoutdoorpowercircuitboard.

DisconnectionofconnectorSC-Ror SC-S Referto"8-7.TESTPOINTDIAGRAM".

3 Check connectionoftheconnector(CNDC)ontheoutdoorcontrollercircuitboard.

Check connectionoftheconnector,CNDContheoutdoorpowercircuitboard.Referto"8-7.TESTPOINTDIAGRAM".

4 Check connectionofreactor.(DCL) Checkconnectionof“L1”and“L2” ontheactivefiltermodule.(ACTM)

5a)Checkconnectionofoutdoornoisefilter circuitboard. b)Replaceoutdoornoisefiltercircuitboard.

Referto"8-7.TESTPOINTDIAGRAM".

6Replaceoutdoorpowercircuitboard.

7Replacecontrollerboard(Whenitemsabovearecheckedbuttheunitscannotberepaired.)

F3(5202)

63L connector openAbnormalif63Lconnectorcircuitisopenfor3minutescontinuouslyafterpowersup-ply63L:Low-pressureswitch

1Disconnectionorcontactfailureof63Lconnectoronoutdoorcontrollercircuitboard

2Disconnectionorcontactfailureof63L

363Lisoperatingduetorefriger-antleakageordefectiveparts.

4Defectiveoutdoorcontroller circuitboard

1Checkconnectionof63Lconnectoron outdoorcontrollercircuitboard. Referto"8-7.TESTPOINTDIAGRAM".2Checkthe63Lsideofconnectingwire.

3Checkrefrigerantpressure. Chargeadditionalrefrigerant. Checkcontinuitybytester. Replacethepartsifthepartsaredefective.4Replaceoutdoorcontrollercircuitboard.

F9(4119)

2 connector openAbnormalifboth63Hand63Lconnectorcircuitsareopenfor3minutescontinuouslyafterpowersupply

63H:High-pressureswitch63L:Low-pressureswitch

1Disconnectionorcontactfailureofconnector(63H,63L)on

outdoorcontrollercircuitboard.2Disconnectionorcontactfailureof63H,63L

363Hand63Lareoperatingduetodefectiveparts.

4Defectiveoutdoorcontrollerboard

1Checkconnectionofconnector(63H,63L)on outdoorcontrollercircuitboard. Referto"8-7.TESTPOINTDIAGRAM".2Checkthe63Hand63Lsideofconnectingwire.

3Checkcontinuitybytester. Replacethepartsifthepartsaredefective.4Replaceoutdoorcontrollercircuitboard.

F5(5201)

63H connector openAbnormalif63Hconnectorcircuitisopenfor3minutescontinuouslyafterpowersup-ply63H:High-pressureswitch

1Disconnectionorcontactfailureof63Hconnectoronoutdoorcontrollercircuitboard

2Disconnectionorcontactfailureof63H

363Hisoperatingduetodefec-tiveparts.

4Defectiveoutdoorcontroller circuitboard

1Checkconnectionof63Hconnectoron outdoorcontrollercircuitboard. Referto"8-7.TESTPOINTDIAGRAM".2Checkthe63Hsideofconnectingwire.

3Checkcontinuitybytester. Replacethepartsifthepartsaredefective.4Replaceoutdoorcontrollercircuitboard.

OCH480D

Page 26: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

26

Check code Abnormal point and detection method Judgment and action

Eb(6845)

Miswiring of indoor–branch box/branch box–outdoor unit connecting wire (converse wiring or dis-connection)Outdoor/branchboxcontrollercircuitboardcanautomaticallysettheunitnumberofindoorunits.Abnormaliftheindoorunitnumbercannotbesetwithin4minutesafterpoweronbecauseofmiswiring(conversewiringordisconnection)ofindoor–branchbox/branchbox–outdoorunitconnectingwire.

EC(6846)

Start-up time overTheunitcannotfinishstart-upprocesswithin4minutesafterpoweron.

Case

1Contactfailureofindoor– branchbox/branchbox–outdoorunitconnectingwire

2Diameterorlengthofindoor– branchbox/branchbox–outdoorunitconnectingwireis

outofspecifiedcapacity.3Noisehasenteredintopowersupplyorindoor–branchbox/branchbox–outdoorunitcon-nectingwire.

1Contactfailureormiswiringofindoor–branchbox/branchbox

–outdoorunitconnectingwire2Diameterorlengthofindoor– branchbox/branchbox–out-doorunitconnectingwireisoutofspecifiedcapacity.

4Defectivetransmittingreceivingcircuitofoutdoor/branchboxcontrollercircuitboard

5Defectivetransmittingreceiv-ingcircuitofindoor/branchboxcontrollerboard

6Defectiveindoor/branchboxpowerboard

7Noisehasenteredintopowersupplyorindoor–branchbox/branchbox–outdoorunitcon-nectingwire.

Indoor–branch box/branch box–outdoor unit connector miswiring, excessive number of unitsOutdoor/branchboxcontrollercircuitboardcanautomaticallycheckthenumberofconnectedindoorunits.Abnormalifthenumbercannotbecheckedautomaticallyduetomiswiringofindoor–branchbox/branchbox–outdoorunitconnectingwireandetc.afterpoweristurnedonfor4min-utes.

1Checkdisconnectionorloosenessorpolar-ityofindoor–branchbox/branchbox–outdoorunitconnectingwireofindoorandoutdoorunits.

BeforeconnectingP100indoorunit(s),checktherequirementsdescribedin"9-2.WIRINGTOP100INDOORUNITS".

2Checkdiameterandlengthofindoor–branchbox/branchbox–outdoorunitconnectingwire.

Totalwiringlength:55m(outdoor–branchbox) (includingwiringconnectingeachbranchboxunitandbetweenbranchboxandoutdoorunit)

AlsocheckiftheconnectionorderofflatcableisS1,S2,S3.

Iftheerror“EA”isdetected,checkthenumberoftheindoorunits,thebranchboxandP100indoorunit(s)inthesystem.

3–5Turnthepoweroffonce,andonagaintocheck.

Replaceoutdoorcontrollercircuitboard,branchboxcontrollerboard,indoorcontrollerboardorindoorpowerboardifabnormalityoccursagain.

6Checktransmissionpath,andremovethecause.

Note:Thedescriptionsabove,1-6,areforEA,EbandEC.

1Contactfailureormiswiringofindoor/outdoorunitconnectingwire

2Diameterorlengthofindoor– branchbox/branchbox–out-doorunitconnectingwireisoutofspecifiedcapacity.

Thereare9ormoreindoorunitsinthesystem.

Thereare3ormorebranchboxesinthesystem.

MorethantwoP100indoorunitsareconnectedtothebranchbox.

3Defectivetransmittingreceivingcircuitofoutdoor/branchboxcontrollercircuitboard

4Defectivetransmittingreceiv-ingcircuitofbranchbox/indoorcontrollerboard

5Defectivebranchbox/indoorpowerboard

6Noisehasenteredintopowersupplyorindoor–branchbox/branchbox–outdoorunitcon-nectingwire.

EA(6844)

OCH480D

Page 27: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

27

Check code Abnormal point and detection method Judgment and actionCaseFaulty connection of LEVFortheconnectionofP100indoorunit(s),theconnectingwire(s)mustbeconnectedtothespecifiedterminalblock(s)inthebranchbox.Incorrectwiring

1Checkdisconnectionorloosenessorpolar-ityofindoor–branchbox/branchbox–outdoorunitconnectingwireofindoorandoutdoorunits.

BeforeconnectingP100indoorunit(s),checktherequirementsdescribedin"9-2.WIRINGTOP100INDOORUNITS".

2Checkdiameterandlengthofindoor–branchbox/branchbox–outdoorunitconnectingwire.

Totalwiringlength:55m(outdoor–branchbox) (includingwiringconnectingeachbranchboxunitandbetweenbranchboxandoutdoorunit)

AlsocheckiftheconnectionorderofflatcableisS1,S2,S3.

Iftheerror“EA”isdetected,checkthenumberoftheindoorunits,thebranchboxandP100indoorunit(s)inthesystem.

3–5Turnthepoweroffonce,andonagaintocheck.

Replaceoutdoorcontrollercircuitboard,branchboxcontrollerboard,indoorcontrollerboardorindoorpowerboardifabnormalityoccursagain.

6Checktransmissionpath,andremovethecause.

Note:Thedescriptionsabove,1-6,areforEA,EbandEC.

1Contactfailureormiswiringofindoor/outdoorunitconnectingwire

Theconnectingwire(s)fromP100indoorunit(s)arenotcon-nectedtothespecifiedterminalblock(s)inthebranchbox.

Theconnectingwire(s)fromP100indoorunit(s)arecon-nectedtoanincorrectterminalblock(s)inthebranchbox.

2Diameterorlengthofindoor– branchbox/branchbox–out-doorunitconnectingwireisoutofspecifiedcapacity.

3Defectivetransmittingreceivingcircuitofoutdoor/branchboxcontrollercircuitboard

4Defectivetransmittingreceiv-ingcircuitofbranchbox/indoorcontrollerboard

5Defectivebranchbox/indoorpowerboard

6Noisehasenteredintopowersupplyorindoor–branchbox/branchbox–outdoorunitcon-nectingwire.

EE(7130)

OCH480D

Page 28: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

28

Check code Abnormal point and detection method Judgment and action

U1(1302)

(1) High-pressure switch (63H) operatedAbnormalifhigh-pressureswitch63Hoper-ated(*)duringcompressoroperation.*4.15MPa

63H:High-pressureswitch

(2) High pressure(High-pressuresensor63HSdetect)1Whenhigh-pressuresensor detects4.31MPaormore(orover 4.15MPafor3minutes)(1stdetection) duringthecompressoroperation,the compressorstopsandrestartsopera- tionin3minutes.2Whenthesensordetects4.31MPaormore(orover4.15MPafor3minutes)again(2nddetection)within30minutessincethecompressorhasstopped,thecompressorstopsagainandrestartsoperationin3minutes.

3Whenthesensordetects4.31MPaormore(orover4.15MPafor3minutes)again(3rddetection)within30minutessincethecompressorhasstopped,thecompressorstopsagainandrestartsoperationin3minutes.

4Whenthesensordetects4.31MPaormore(orover4.15MPafor3minutes)again(4thdetection)within30minutesafter3rdcompressorstop,itstopsabnormally.Inthistime<U1>isdis-played.

5Whenthesensordetects4.31MPaormore(orover4.15MPafor3minutes)after30minutessincethecompressorhasstopped(1stor2ndor3rdtime),itbecomesthe1stdetectionorthesameperformanceasabove-mentioned1.

6Itisbeingdelayforabnormalstopduring30minutessincethecompressorhasstopped.Inthistime,checkdelaycode<U1>willbedisplayed.

1)Shortcycleofindoorunit2)Cloggedfilterofindoorunit3)Decreasedairflowcausedbydirtofindoorfan

4)Dirtofindoorheatexchanger5)Lockedindoorfanmotor6)Malfunctionofindoorfanmotor7)Defectiveoperationofstopvalve(Notfullyopened)

8)Cloggedorbrokenpipe9)Lockedoutdoorfanmotor10)Malfunctionofoutdoorfan

motor11)Shortcycleofoutdoorunit12)Dirtofoutdoorheatexchang-

er13)Decreasedairflowcausedby

defectiveinspectionofoutsidetemperaturethermistor

(Itdetectslowertemperaturethanactualtemperature.)

14)Disconnectionorcontactfailureofconnector(63H)onoutdoorcontrollerboard

15)Disconnectionorcontactfail-ureof63Hconnection

16)Defectiveoutdoorcontrollerboard

17)Defectiveactionoflinearexpansionvalve

18)Malfunctionoffandrivingcir-cuit

19)Solenoidvalve(SV1)per-formancefailure(High-pressurecannotbecontrolledbySV1)

20)High-pressuresensordefec-tive

21)High-pressuresensorinputcircuitdefectiveinmulticon-trollerboard

1)–6)Checkindoorunitandrepairdefect.

7)Checkifstopvalveisfullyopen.

8)Checkpipingandrepairdefectives.9)–12)Checkoutdoorunitandrepairdefect.

13)Checkthedetectedtemperatureofoutside temperaturethermistoronLEDdisplay.

14)–16)PutthepoweroffandcheckF5is displayedwhenthepowerisputagain. WhenF5isdisplayed,referto “Judgmentandaction”forF5.

17)Checklinearexpansionvalve. Referto "8-6.HOWTOCHECKTHEPARTS".18)Replaceoutdoorcontrollerboard.

19)Checkthesolenoidvalveperformance.

20)Checkthehigh-pressuresensor.

21)Checkthehigh-pressuresensor.

Case

<Abnormalities detected while unit is operating>

OCH480D

Page 29: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

29

U2(1102)

(1) High discharging temperature Abnormalifcompressortemperature

thermistor(TH4)exceeds125: or110:continuouslyfor5minutes.

Abnormalifpressuredetectedbyhighpressuresensorandconvertedtosatu-rationtemperatureexceeds40:duringdefrostingandcompressortemperaturethermistor(TH4)exceeds110:.

(2) Refrigerant shortage abnormality1 Whentheconditionsofbelowdetecting

mode1or2aresatisfied(1stdetec-tion)duringthecompressoroperation,thecompressorstopsandrestartsoperationin3minutes.

<Detectingmode1> Whenthebelowconditionsaresatisfied

completely.1.CompressorisoperatinginHEATmode.

2.Dischargesuperheatis70 :ormore.3.Differenceofoutertemperaturethermistor(TH7)andoutdoorpipingtemp.thermistor(TH3)appliestotheformulaof(TH7-TH3)<5:.

4.High-pressuresensorisbelowabout2.04MPa.

<Detectingmode2> Whenthebelowconditionsaresatisfied completely.

1.Compressorisoperating.2.Whencooling,dischargesuperheatis

80:ormore. Whenheating,dischargesuperheat

is90:ormore. Highpressuresensorisbelowabout

2.32MPa.2Whentheconditionsofdetectingmode

1and2aresatisfiedagain(2nddetection)within30minutessincethecompressorhasstoppedandrestartsoperationin3minutes.

3Whentheconditionsofdetectingmode1and2aresatisfiedagain(3rddetec-tion)within30minutessincethecom-pressorhasstopped,itstopsabnormal-ity.inthistime,<U2>isdisplayed.

4Whentheconditionsofdetectingmode 1and2aresatisfiedagainafter30minutessincethecompressorhasstopped(1sttime),itbecomesthe1stdetectionandsameperformanceasabove1.

5Itisbeingdelayforabnormalstopdur-ing30minutessincethecompressorhasstopped.Inthistime,checkdelaycode<U2>willbedisplayed.

1Overheatedcompressoropera-tioncausedbyshortageofrefrigerant

2Defectiveoperationofstopvalve

3Defectivethermistor4Defectiveoutdoorcontrollerboard

5Defectiveactionoflinearexpansionvalve

1Gasleakage,Gasshortage2Whenheatingoperation,scantrefrigerantoperation

(Whenheating,airfloworther-moOFFaremixed-operation,itcausearefrigerantshortageoperation.)

3Ballvalveperformancefailure(Notfullyopened.)

4Errordetectionofdischargesuperheat1)High-pressuresensordefec-tive

2)Dischargetemperaturether-mistordefective

3)Thermistorinputcircuitdefectiveandhigh-pressuresensordefectiveinmulticontrollerboard

5ErrordetectionofTH7/TH31)Thermistordefective

2)Thermistorinputcircuitdefectiveinmulticontrollerboard

1Checkintakesuperheat. Checkleakageofrefrigerant. Chargeadditionalrefrigerant.2Checkifstopvalveisfullyopen.34TurnthepoweroffandcheckifU3isdis-

playedwhenthepoweristurnedonagain. WhenU3isdisplayed,referto“Judgement

andaction”forU3.5Checklinearexpansionvalve. Referto"8-6.HOWTOCHECKTHEPARTS".1Checktherefrigerantamount.2Checktheoperationconditionandrefrigerantamount.

3Checktheballvalveisfullyopened.

41)Checktheballvalveisfullyopened.

2)Checktheresistanceofdischargetem-peraturethermistor.

3)Accordingto“Monitoringfunctionforout-doorunit”,settheSW2andcheckthehigh-pressuresensorlevel.

Accordingto“Monitoringfunctionforoutdoorunit”,settheSW2andcheckthedischargetemp.thermistorlevel.

Whenthehigh-pressuresensoranddis-chargetemp.thermistorarenormal,iftheabovementioneddetectingpressurelevelandtemp.arebigdifferentfromtheactualpressureandtemp.,replacethemulticontrol-lerboard.

51)Checktheresistanceofthermistor.

2)Accordingto“Monitoringfunctionforout-doorunit”,settheSW2andchecktheout-doorpipetemp.thermistorlevel.

3)Accordingto“Monitoringfunctionforout-doorunit”,settheSW2andchecktheoutertemp.thermistorlevel.

Check code Abnormal point and detection method Judgment and actionCase

U3(5104)

Open/short circuit of compressor temperature thermistor (TH4)Abnormalifopen(3:orless)orshort(217: ormore)isdetectedduringcompressoropera-tion.(Detectionisinoperativefor10minutesofcompressorstartingprocessandfor10minutesafterandduringdefrosting.)

1Disconnectionorcontactfailureofconnector(TH4)ontheout-doorcontrollercircuitboard

2Defectivethermistor

3 Defectiveoutdoorcontrollercircuitboard

1Checkconnectionofconnector(TH4)ontheoutdoorcontrollercircuitboard.

Checkbreakingoftheleadwireforthermistor(TH4).Referto"8-6.HOWTOCHECKTHEPARTS".

2Checkresistancevalueofthermistor(TH4)ortemperaturebymicroprocessor.

(Thermistor/TH4:Referto"8-6.HOWTOCHECKTHEPARTS".)

(SW2onA-ControlServiceTool: Referto"8-8.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS")

3Replaceoutdoorcontrollerboard.

OCH480D

Page 30: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

30

ThermistorsOpen detection Short detectionSymbol Name

TH3TH7TH8

Branch box unitTH-A~E(Room A-E)

– 40: or below– 40: or below– 27: or below

90: or above90: or above

102: or above

– 40: or below 90: or above

Thermistor <Outdoor pipe>

Thermistor(Gas pipe temperature detection)

Thermistor <Outdoor>Thermistor <Heatsink>

Check code Abnormal point and detection method Case Judgment and action

U4(TH3:5105)(TH7:5106)(TH8:5110)(63HS:5201)

TH-A~E:5131

(1) Open/short circuit in the outdoor unit thermistors (TH3, TH7, and TH8) and branch box’s thermistors (TH-A~E)

Abnormalifopenorshortcircuitisdetectedwhilethecompressorisoperating.OpendetectionofthermistorsTH3isinop-erativefor10secondsto10minutesaftercompressorstartingand10minutesafterandduringdefrosting.Note:Checkwhichunithasabnormalityinitsthermis-torbyswitchingthemodeofSW2.(Referto"8-8.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS")Open/shortcircuitinthebranchboxthermistor.(TH-A–TH-E)

1Oneormoreconnectorsonoutdoorcontrollercircuitboard(TH3,TH7andTH8)andbranchboxcontrollerboard(TH-A~E)havecontactfailureordiscon-nection.

2Defectivethermistor

3Outdoorcontrollercircuitboardisdefective.

1Checktheconnector’scontactandtheelectricwiresofthermistor.

2Checktheresistancevalueofthermistorsorthetemperaturesbyreferringtothesectionof“Monitoringfunctionforoutdoorunit”.

(ConvertmodesbySW2.)3Replacethewholeoutdoorcontrollerboard.

U5(4230)

Abnormal temperature of heatsinkAbnormalifheatsinkthermistor(TH8)detectstemperatureindicated85:

1 Theoutdoorfanmotorislocked.2Failureofoutdoorfanmotor3Airflowpathisclogged.4Riseofambienttemperature

5Defectivethermistor

6Defectiveinputcircuitof outdoorpowercircuitboard7Failureofoutdoorfandrive circuit

12Checkoutdoorfan.3Checkairflowpathforcooling.4Checkifthereissomethingwhichcausestemperaturerisearoundoutdoorunit.(Upperlimitofambienttemperatureis46:.)Turnoffpower,andonagaintocheckifU5isdisplayedwithin30minutes.IfU4isdisplayedinsteadofU5,followtheactiontobetakenforU4.

5Checkresistancevalueofthermistor(TH8)ortemperaturebymicroprocessor.

(Thermistor/TH8:Referto"8-6.HOWTOCHECKTHEPARTS".)

(SW2onA-ControlServiceTool:Referto"8-8.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".)

6Replaceoutdoorpowercircuitboard.7Replaceoutdoorcontrollercircuitboard.

U6(4250)

Abnormality of power moduleCheckabnormalitybydrivingpowermoduleincaseovercurrentisdetected.(UForUPerrorcondition)

1Outdoorstopvalveisclosed.2Decreaseofpowersupplyvoltage3Looseness,disconnectionorconverseofcompressorwiringconnection

4Defectivecompressor5Defectiveoutdoorpowercircuitboard

1Openstopvalve.2Checkfacilityofpowersupply.3Correctthewiring(U·V·Wphase)to compressor.Referto"8-7.TESTPOINTDIAGRAM"

4Checkcompressorreferringto"8-6.HOWTOCHECKTHEPARTS".

5Replaceoutdoorpowercircuitboard.

( ) (2) High-Pressure sensor (63HS) abnormality1Whendetectedpressureinhigh-pressure

sensoris1MPaorlessduringtheopera-tion,thecompressorstopsandrestartsoperationin3minutes.

2Whenthedetectedpressureis1MPaorlessatjustbeforeofrestarting,thecom-pressorstopsabnormally.Inthistime,<U4>isdisplayed.

3For3minutesafterthecompressorstops,theunitdelaystoabnormalstop.Then,theoutdoorunitaddressNo.andcheckdelaycode<U4>blinksalternatelyonthe7SEGdigitaldisplay.

4For3minutesafterstartingcompres-sor,fordefrostingorfor3minutesafterrecoveryfromdefrosting,abnormalityisnotdeterminedasabnormality.

1Checkthehigh-pressuresensor.

2Checktheinternalpressure.

3Checkthehigh-pressuresensor.

4Checkthecontrollerboard

1High-pressuresensorfailure

2Internalpressuredecreasebygasleakage

3Connectorcontactfailuredis-connection

4Controllerboardinputcircuitfailure

OCH480D

Page 31: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

31

U9(4220)

Detailedcodes

Overvoltage error•IncreaseinDCbusvoltageto;Vmodel:400VYmodel:760V

1Abnormalincreaseinpowersourcevoltage2Disconnectionofcompressorwiring3Defectiveoutdoorpowercircuitboard4Compressorhasagroundfault.

1Checkthefieldfacilityforthepowersupply.2Correctthewiring(U.V.Wphase)tocom-pressor.Referto"8-7.Outdoorpowercircuitboard".

3Replaceoutdoorpowercircuitboard.4Checkcompressorforelectricalinsulation.Replacecompressor.

TofindoutthedetailsaboutU9error,turnONSW2-1,2-2,2-3,2-4,2-5and2-6whenU9erroroccurs.Referto"8-8.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".

Check code Abnormal point and detection method Judgment and actionCase

U7(1520)

(1) Too low superheat due to low dis-charge temperature

Abnormalifdischargesuperheatiscontin-uouslydetected-15:orlesseventhoughlinearexpansionvalvehasminimumopenpulseaftercompressorstartsoperatingfor10minutes.

(2) Erroneous connection of refrigerant pipes or the connecting wires

Considerthestoppingindoorunitabnor-malifcondenser/evaporatortemperaturethermistor(TH5orRT12)detects-5:orbelowcontinuouslyfor5minutesduringacompressor’soperationincoolingmode.

1Disconnectionorloose connectionofcompressor temperaturethermistor.(TH4)2Defectiveholderofdischargetemperaturethermistor

1Failureinpiping/wiring

2Pipe(liquid)iscloggedorcrushed.

12Checktheinstallationconditionsof compressortemperaturethermistor(TH4).

1Checkpiping/wiringbetweenbranchboxandindoorunit.

Referto“Testrun(Usingremotecontroller)”.2Checkthepipeforrefrigerantandchangethewrongparts.

U8(4400)

Outdoor fan motorTheoutdoorfanmotorisconsideredtobeabnormaliftherotationalfrequencyoffanmotorisabnormalwhendetectedduringoperation.Fanmotorrotationalfrequencyisabnormalif;•100rpmorbelowdetectedcontinuouslyfor15secondsat26:ormoreoutsideairtemperature

•50rpmorbelowor1500rpmormoredetectedcontinuouslyfor1minute.

1FailureintheoperationoftheDCfanmotor

2Failureintheoutdoorcircuitcontrollerboard

1CheckorreplacetheDCfanmotor.

2Checkthevoltageoftheoutdoorcircuitcontrollerboardduringoperation.

3Replacetheoutdoorcircuitcontrollerboard.(whenthefailureisstillindicatedevenafterperformingtheremedy1above.)

01

Undervoltage error•InstantaneousdecreaseinDCbusvoltageto;Vmodel:200VYmodel:350V

1Decreaseinpowersourcevoltage,instantaneousstop.2DisconnectionorlooseconnectionofCN52Contheoutdoorpowercircuitboard/ controllercircuitboard(Vmodel)3Defectiveconverterdrivecircuitinoutdoorpowercircuitboard(Vmodel)4Defective52Cdrivecircuitinoutdoorpowercircuitboard5Defectiveoutdoorconvertercircuitboard(Ymodel)6DisconnectionorlooseconnectionofrushcurrentprotectresistorRS(Ymodel)7DefectiverushcurrentprotectresistorRS(Ymodel)8DisconnectionorlooseconnectionofmainsmoothingcapacitorCB(Vmodel)9DisconnectionorlooseconnectionofCN2ontheoutdoorpowercircuitboard/ controllercircuitboard(Vmodel)0PowercircuitfailureonDCsupplyfor18VDCoutputonoutdoorcontrollercircuitboard(Vmodel)

1Checkthefieldfacilityforthepowersupply.2CheckCN52Cwiring.(Vmodel)

3Replaceoutdoorpowercircuitboard.(Vmodel)

4Replaceoutdoorpowercircuitboard.

5Replaceoutdoorconvertercircuitboard.(Ymodel)6CheckRSwiring.(Ymodel)

7ReplaceRS.(Ymodel)

8CheckCBwiring.(Vmodel)

9CheckCN2wiring.(Vmodel)

0Replaceoutdoorcontrollercircuitboard.(Vmodel)

02

OCH480D

Page 32: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

32

04

Input current sensor error/L1-phase open error•Decreaseininputcurrentthroughoutdoorunitto0.1Aonlyifoperationfrequencyismorethanorequalto40Hzorcompressorcurrentismorethanorequalto6A.

1L1-phaseopen(Ymodel)

2DisconnectionorlooseconnectionbetweenTB1andoutdoornoisefiltercircuitboard(Ymodel)

3 DisconnectionorlooseconnectionofCN5ontheoutdoorpowercircuitboard/CNCTontheoutdoornoisefilterboard

4DefectiveACCT(ACcurrenttrans)ontheoutdoornoisefiltercircuitboard(Ymodel)

5Defectiveinputcurrentdetectioncircuitinoutdoorpowercircuitboard

6 Defectiveoutdoorcontrollercircuitboard

1Checkthefieldfacilityforthepowersupply.(Ymodel)

2CheckthewiringbetweenTB1andout-doornoisefiltercircuitboard.(Ymodel)

3CheckCN5/CNCTwiring.(Ymodel)

4Replaceoutdoornoisefiltercircuitboard.(Ymodel)

5Replaceoutdoorpowercircuitboard.

6Replaceoutdoorcontrollercircuitboard.

08

Abnormal power synchronous signal•Noinputofpowersynchronoussignaltopowercircuitboard

•Powersynchronoussignalof44Hzorless,or65Hzormoreisdetectedonpowercircuitboard.

1Distortionofpowersourcevoltage,noisesuperimposition.2Disconnectionorlooseconnectionofearthwiring3DisconnectionorlooseconnectionofCN2ontheoutdoorpowercircuitboard/controllercircuitboard4 Defectivepowersynchronoussignalcircuitinoutdoorcontrollercircuitboard5Defectivepowersynchronoussignalcircuitinoutdoorpowercircuitboard

1Checkthefieldfacilityforthepowersupply.

2Checkearthwiring.

3CheckCN2wiring.

4Replaceoutdoorcontrollercircuitboard.

5Replaceoutdoorpowercircuitboard.

20

PFC/IGBT error(Undervoltage)•WhenCompressorisrunning,DCbusvoltagestaysat310Vorlowerforconsecutive10seconds

(Vmodelonly)

1Incorrectswitchsettingsontheoutdoorcontrollercircuitboardformodelselect2Defectiveoutdoorpowercircuitboard

3Defectiveoutdoorcontrollercircuitboard

1Correctionofamodelselect

2Replaceoutdoorpowercircuitboard.

3Replaceoutdoorcontrollercircuitboard.

Detailedcodes

Check code Abnormal point and detection method Case Judgment and action

U9(4220)

UF(4100)

Compressor overcurrent interruption (When compressor locked)AbnormalifovercurrentofDCbusorcompressorisdetectedwithin30secondsaftercompressorstartsoperating.

1Stopvalveisclosed.2Decreaseofpowersupply voltage3Looseness,disconnectionor converseofcompressorwiring connection4Defectivecompressor

5Defectiveoutdoorpowerboard

1Openstopvalve.2Checkfacilityofpowersupply. 3Correctthewiring(U·V·Wphase)to compressor. Referto"8-7.TESTPOINTDIAGRAM".4Checkcompressor. Referto"8-6.HOWTOCHECKTHEPARTS".

5Replaceoutdoorpowercircuitboard.

UL(1300)

Low pressure (63L operated)Abnormalif63Lisoperated(under-0.03MPa)duringcompressoroperation.63L:Low-pressureswitch

1Stopvalveofoutdoorunitisclosedduringoperation.

2Disconnectionorlooseconnectionofconnector(63L)onoutdoorcon-trollerboard

3Disconnectionorlooseconnectionof63L

4Defectiveoutdoorcontrollerboard5 Leakageorshortageofrefrigerant6Malfunctionoflinearexpansionvalve

1Checkstopvalve.

2–4TurnthepoweroffandonagaintocheckifF3isdisplayedonrestart-ing.

IfF3isdisplayed,followtheF3pro-cessingdirection.

5Correcttoproperamountofrefrigerant.6Checklinearexpansionvalve.Referto"8-6.HOWTOCHECKTHEPARTS".

UH(5300)

Current sensor errorAbnormalifcurrentsensordetects-1.5Ato1.5Aduringcompressoroperation.(Thiserrorisignoredincaseoftestrunmode.)

1Disconnectionofcompressorwiring

2Defectivecircuitofcurrentsensoronoutdoorpowercircuitboard

1Correctthewiring(U·V·Wphase)tocompressor.Referto"8-7.TESTPOINTDIAGRAM".

2Replaceoutdoorpowercircuitboard.

Abnormalifinputcurrentexceeds38Aor34Acontinuously10seconds.(Currentsen-soronnoisefilterboarddetectsinputcurrent)

1Decreaseofpowersupplyvoltage 1Checkthefacilityofpowersupply.

OCH480D

Page 33: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

33

Check code Abnormal point and detection method Judgment and actionCase

E0(Nodisplay)

Remote controller communication error (Signal receiving error)(1)AbnormalifanysignalfromICof

refrigerantaddress“0”couldnotbenormallyreceivedfor3minutes.

(2)Abnormalifsubremotecontrollercouldnotreceiveanysignalfor2minutes.

1Defectivecommunicationcircuitofremotecontroller

2Defectivecommunicationcircuitofindoorcontrollerboardofrefrigerantaddress“0”

3Noisehasenteredintotransmis-sionlineofremotecontroller.

4Allremotecontrollersaresetas“sub”remotecontroller.Inthiscase,E4isdisplayedatoutdoorLED,andE0isdis-playedatremotecontroller.

1–3 Diagnoseremotecontroller. Takeactionsasfollowsaccordingto

diagnosisresult.a)When“RCOK”isdisplayed,remotecontrollershavenoproblem.Turnthepoweroff,andonagaintocheck.If,“PLEASEWAIT”or“H0”isdisplayedfor4minutesormore,replaceindoorcontrollerboard.

b)When“RCNG”isdisplayed,replaceremotecontroller.

c)When“RCE3”or“ERC00-66”isdis-played,noisemaybecausingabnor-mality.

4Setaremotecontrollertomain,andtheothertosub.

Note:Thedescriptionsabove,1-3,areforE0andE3.

E3(Nodisplay)

Remote controller communication error (Transmitting error)(1)Abnormalifsubremotecontrollercould

notfindblankoftransmissionpathfor6seconds.

(2)Abnormalifremotecontrollercouldnotfinishtransmitting30timescontinuously.

1Defectivecommunicationcircuitofremotecontroller

2Noisehasenteredintotrans-missionlineofremotecontroller.

3Tworemotecontrollersaresetas"main."

(Incaseof2remotecontrollers)

E8(6840)

Indoor - branch box/branch box - outdoor unit communication error (Signal receiving error)(Branch box/outdoor unit)Abnormalifbranchbox/outdoorcontrollercircuitboardcouldnotreceiveanythingnormallyfor3minutes.

1Contactfailureofindoor/out-doorunitconnectingwire

2Defectivecommunicationcircuitofbranchbox/outdoorcontrollercircuitboard

3Defectivecommunicationcircuitofindoor/branchboxcontrollerboard

4Noisehasenteredintoindoor–branchbox/branchbox–

outdoorunitconnectingwire.

1Checkdisconnectionorloosenessofindoor–branchbox/branchbox–outdoorunit

connectingwireofindoororbranchboxoroutdoorunits.

2–4 Turnthepoweroff,andonagaintocheck.Replaceindoorcontrollerboardorbranchcontrollerboardoroutdoorcontrol-lercircuitboardifabnormalityisdisplayedagain.

UP(4210)

Compressor overcurrent interruptionAbnormalifovercurrentDCbusorcom-pressorisdetectedaftercompressorstartsoperatingfor30seconds.

1Stopvalveofoutdoorunitisclosed.

2Decreaseofpowersupplyvolt-age

3Looseness,disconnectionorconverseofcompressorwiringconnection

4Defectivefanofindoor/outdoorunits

5Shortcycleofindoor/outdoorunits

6Defectiveinputcircuitofout-doorcontrollerboard

7Defectivecompressor

1Openstopvalve.2Checkfacilityofpowersupply.3Correctthewiring(U·V·Wphase)tocom-pressor.Referto"8-7.TESTPOINTDIAGRAM".

4Checkindoor/outdoorfan.5Solveshortcycle.6Replaceoutdoorcontrollercircuitboard.7Checkcompressor.Referto"8-6.HOWTO

CHECKTHEPARTS".Note:Beforethereplacementoftheoutdoorcon-trollercircuitboard,disconnectthewiringforcompressorfromtheoutdoorpowercircuitboardandchecktheoutputvoltageamongphases,U,V,W,duringtestrun.Nodefectonboardifvoltageamongphases(U-V,V-WandW-U)issame.Makesuretoperformthevolt-agecheckwithsameperformingfrequency.

E9(6841)

Indoor - branch box/branch box - outdoor unit communication error (Transmitting error) (Branch box/outdoor unit)(1)Abnormalif“0”receivingisdetected

30timescontinuouslythoughbranchbox/outdoorcontrollercircuitboardhastransmitted“1”.

(2)Abnormalifbranchbox/outdoorcontrollercircuitboardcouldnotfindblankoftransmissionpathfor3minutes.

1Indoor–branchbox/ branchbox–outdoorunitconnectingwirehascontactfailure.

2Defectivecommunicationcircuitofoutdoorcontrollercircuitboard

3Noisehasenteredpowersupply.

4NoisehasenteredIndoor– branchbox/branchbox– outdoorunitconnectingwire.

1Checkdisconnectionorloosenessofindoor–branchbox/branchbox–outdoorunitconnect-ingwire.

2–4 Turnthepoweroff,andonagaintocheck.Replaceoutdoorcontrollercircuitboardifabnormalityisdisplayedagain.

EF(6607or

6608)

Non defined check codeThiscodeisdisplayedwhennondefinedcheckcodeisreceived.

1Noisehasenteredtransmissionwireofremotecontroller.

2NoisehasenteredIndoor– branchbox/branchbox– outdoorunitconnectingwire.3ModelnameofremotecontrollerisPAR-S25A.

12Turnthepoweroff,andonagaintocheck. Replaceindoorcontrollerboardorbranch

controllerboardoroutdoorcontrollercircuit boardifabnormalityisdisplayedagain.

3ReplaceremotecontrollerwithMAremotecontroller.

OCH480D

Page 34: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

34

Check code Abnormal point and detection method Judgment and actionCase

Ed(0403)

Serial communication errorAbnormalifserialcommunicationbetweenoutdoorcontrollercircuitboardandoutdoorpowercircuitboardisdefective.

1BreakingofwireorcontactfailureofconnectorCN2betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercircuitboard

2BreakingofwireorcontactfailureofconnectorCN4betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercircuitboard

3Defectivecommunicationcircuitofoutdoorpowercircuitboard

4Defectivecommunicationcircuitofoutdoorcontrollercircuitboardforoutdoorpowercircuitboard

12CheckconnectionofeachconnectorCN2andCN4betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercircuitboard.

3Replaceoutdoorpowercircuitboard.

4Replaceoutdoorcontrollercircuitboard.

PA(2520)

Forced compressor stop.(Overlapmalfunctionofdrainpumpinindoorunitandlinearexpansionvalveinbranchbox.)

Whenconditionoftheoutdoorunitisforcefullystopped,whichmeansthedrainsensordetectscontinuouslytogounderwater5times,andalsodetects"[liquidpipetemperature-suctiontemperature][–10deg"for30minutescontinuously,theindoorunitandindoorunitsinsamerefrigerantsystemwhichoperatesincooling,heatingordrymodestopsabnormally.Also,theoutdoorunitwhichisconnectedtothatindoorunitwithrefrigerantsystemstopsabnormally(compressorissuspendedtooperate).Inthistime,<PA>isdisplayed.

1Drainpumptrouble

2Draindefective ·Drainpumpclogging ·Drainpipeclogging

3Opencircuitofdrainsensorsideheater

4Contactfailureofdrainsensorconnector

5Dewcondensationondrainsensor·Drainwaterdescendsalongleadwire.

· Drainwaterwavingduetofilterclogging

6Indoorcontrollerboarddefective ·Drainpumpdrivecircuitfailure · Drainheateroutputcircuitfailure

7Bothofabovementioned1–6 andthelinearexpansionvalvefullclosedfailurehappenssynchronistically.

1Checkthedrainpump.

2Pleaseconfirmwhetherwatercanbedrained.

3Confirmtheresistanceofthedrainsensorsideheater.

4Checktheconnectorcontactfailure.

5Checkthedrainsensorleadwiremounted.Checkthefilterclogging.

6Iftheabovementionedcheckpointshasanyproblem,replacetheindoorcontrollerboard.

7Checkwhethertheindoorlinearexpansionvalveleaksornot.

OCH480D

Page 35: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

35

Phenomena Factor Countermeasure

2.Remotecontrollerdisplayoperatesnormallyandtheunitperformsheatingoperation,however,thecapacitycannotbefullyobtained.

1LinearexpansionvalvefaultOpeningcannotbeadjustedwellduetolinearexpan-sionvalvefault.

2Refrigerantshortage

3Lackofinsulationforrefrigerantpiping4Filterclogging

5Heatexchangerclogging

6Airductshortcycle7Bypasscircuitofoutdoorunitfault

1 Dischargingtemperatureandindoorheatexchangertemperaturedoesnotrise.

Inspectthefailurebycheckingdischarg-ingpressure.

Replacelinearexpansionvalve.

2Ifrefrigerantleaks,dischargingtempera-turerisesandLEVopeningincreases.

Inspectleakagebycheckingthetem-peratureandopening.

Checkpipeconnectionsforgasleakage.3Checktheinsulation.4Openintakegrilleandcheckthefilter.

Cleanthefilterbyremovingdirtordustonit.

5Ifthefilterisclogged,indoorpipetem-peraturerisesanddischargingpressureincreases.Checkifheatexchangeriscloggedbyinspectingdischargingpres-sure.

Cleantheheatexchanger.6Removetheblockage.7Checkrefrigerantsystemduringopera-

tion.

3.1For3minutesaftertemperatureadjusterturnsoff,thecompres-sorwillnotstartoperatingeveniftemperatureadjusteristurnedon.

2For3minutesaftertemperatureadjusterturnson,thecompressorwillnotstopoperatingeveniftem-peratureadjusteristurnedoff.

(Compressorstopsoperatingimmediatelywhenturningoffbytheremotecontroller.)

12Normaloperation(Forprotectionofcompressor)

12Normaloperation

1.Remotecontrollerdisplayoperatesnormallyandtheunitperformscool-ingoperation,however,thecapacitycannotbefullyobtained.(Theairdoesnotcoolwell.)

1Refrigerantshortage

2Filterclogging

3Heatexchangerclogging

4Airductshortcycle

1 Ifrefrigerantleaks,dischargingtempera-turerisesandLEVopeningincreases.Inspectleakagebycheckingthetem-peratureandopening.

Checkpipeconnectionsforgasleakage.2 Openintakegrilleandcheckthefilter.

Cleanthefilterbyremovingdirtordustonit.

3 Ifthefilterisclogged,indoorpipetem-peraturerisesanddischargingpressureincreases.Checkifheatexchangeriscloggedbyinspectingdischargingpres-sure.

Cleantheheatexchanger.4 Removetheblockage.

8-4. TROUBLESHOOTING OF PROBLEMS

OCH480D

Page 36: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

36

CN51

X

543

A C

D

5E

1

1

3

B

G

Y

L1 : Error display lampL2 : Compressor operation lampX, Y : Relay (Coil standard of 0.9W or less for DC 12V)

F

A C

D

E

B

GF

CN3SX

Y

SW1

SW2

123

X, Y : Relay (DC1mA)

SW1SW2

ONHeating

Validity of SW1

OFFCooling

Invalidity of SW1

A Distant control boardB Relay circuitC External output adapter (PAC-SA88HA-E)D Outdoor unit control board

A Remote control panelB Relay circuitC External input adapter (PAC-SC36NA)D Outdoor unit control board

E Relay power supplyF Procure locallyG Max. 10m

* The indoor unit, which is operating in the mode different from the one determined by external signal (CN3S), will be a state of standby.* The setting becomes effective when the outdoor unit is under stop.* The operation mode specified by test run will be prior to the mode of this function.

E Lamp power supplyF Procure locallyG Max. 10m

F

E

A B C

H

I

J

D

1

3

G

~

~

YX

Y

X

L1

L2

Y

CNDM

SW2

1

2

3

A Remote control panelB Relay circuitC External input adapter (PAC-SC36NA)D Outdoor unit control boardE Replay power supply

F Procure locallyG Max. 10mH OrangeI BrownJ Red

~

Y

SW7-1 Power consumption when SW2 is on

OFF 0% (Forced compressor stop)

ON 50%

Fig. 8-1

8-5. SPECIAL FUNCTIONS8-5-1. Low noise mode (on-site modification) (Fig. 8-1)Byperformingthefollowingmodification,operationnoiseoftheoutdoorunitcanbereducedbyabout3-4dB.ThelownoisemodewillbeactivatedwhenacommerciallyavailabletimerorthecontactinputofanON/OFFswitchisaddedtotheCNDMconnector(optionalparts)onthecontrolboardoftheoutdoorunit.•Thecapacitymaybeinsufficientaccordingtotheoutdoortemperatureandconditions,etc. 1Completethecircuitasshownwhenusingtheexternalinputadapter(PAC-SC36NA).(Optionalparts)

SW1X

CNDM

X

B C

H

I

J

G

D

1

3

A

E

F

1

23

A Remote control panelB Relay circuitC External input adapter (PAC-SC36NA)D Outdoor unit control boardE Replay power supply

F Procure locallyG Max. 10mH OrangeI BrownJ Red

~

Fig. 8-2

8-5-2. Demand function (on-site modification) (Fig. 8-2)•Itispossibletoreduceelectricityconsumptionwithinarangefrom0to100%byperformingthefollowingon-siteinstallation.ThedemandfunctioncanbeenabledbyaddingacommerciallyavailableinputcontactpointON/OFFswitchtotheCNDMconnector(thecontactpointdemandinput,optionalparts).

1Incorporatethe“Adapterforexternalinput(PAC-SC36NA)”intothecircuitasshowninthediagrambelow.2ByswitchingSW7-1onthecontrolcircuitboardfortheoutdoorunit,thefollowingpowerconsumptionrestrictions(comparedtoratedpower)canbeset.

8-5-3. Error and compressor operation monitoring function (CN51)

Fig. 8-38-5-4. Auto change over - Operation mode locking function by external signal (CN3S)

Fig. 8-4

OCH480D

Page 37: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

37

8-6. HOW TO CHECK THE PARTSMXZ-8B140VA MXZ-8B140YA MXZ-8B160VA MXZ-8B160YA

Parts name Check points

Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 10:~30:)Thermistor (TH3)

<Outdoor pipe>

Thermistor (TH4)<Compressor>

Thermistor (TH7)<Outdoor>

Thermistor (TH8)<Heatsink>

Normal160k" ~ 410k"

4.3k"

~

9.6k"

39k" ~ 105k"

TH4TH3TH7TH8

Abnormal

Open or short

Measure the resistance between the terminals with a tester. (At the ambient temperature 20:)

Solenoid valve coil<Four-way valve> (21S4)

Motor for compressor(MC)

Normal Abnormal

Open or short

Measure the resistance between the terminals with a tester.(At the ambient temperature 20:)

Normal Abnormal

Open or short

Solenoid valve coil<Bypass valve> (SV2)

Measure the resistance between the terminals with a tester.(At the ambient temperature 20:)

Normal1327 ± 10"

AbnormalOpen or short

Solenoid valve coil<Bypass valve> (SV1)

Fan motor(MF1,MF2)

0.188" 0.302"

Measure the resistance between the terminals with a tester. (Winding temperature 20:)

Normal Abnormal

Open or short

W

V

U

Refer to next page.

MXZ-8B140VA/160VAMXZ-8B140YA/160YA

MXZ-8B140VA/160VA MXZ-8B140YA/160YA

MXZ-8B140VA/160VAMXZ-8B140YA/160YA

1435 ± 150"

1450 ± 150"

OCH480D

Page 38: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

38

Notes · High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNF1, 2) for the motor with the power supply on. (It causes trouble of the outdoor controller circuit board and fan motor.)Self checkSymptom : The outdoor fan cannot turn around.

1

2

Check method of DC fan motor (fan motor / outdoor controller circuit board)

No

NG

NG

Wiring contact checkContact of fan motor connector (CNF1, 2)

Fuse checkCheck the fuse (F5) on outdoorcontroller board.

Power supply check (Remove the connector (CNF1, 2))Measure the voltage in the outdoor controller circuit board.TEST POINT 1 : VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC250~330VTEST POINT 2 : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V

Wiring recovery

Replace outdoor controller board.

Replace the fan motor.

Replace outdoor controller board (C.B)and fan motor (MF1, 2).

Replace outdoor controller board.

Replace the fan motor.

Is the voltage normal?

Is there contact failure? Yes

Yes

No

Did the fuse blow?

No

Yes

Check the operation of fan. END

Yes OK

Check the operation. END

OK

OCH480D

Page 39: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

39

<Thermistor feature chart>Low temperature thermistors

Pipetemperaturethermistor<Liquid>(TH3)Pipetemperaturethermistor<Cond.>(TH6)Outdoortemperaturethermistor(TH7)Gaspipetemperaturethermistor(TH-A~TH-E)····Branchbox

0: 15k"10: 9.6k"20: 6.3k"25: 5.4k"

30: 4.3k"40: 3.0k"

ThermistorR0=15k"±3%Bconstant=3480±2%

Rt=15exp{3480(273+t–273)}1 1

0

10

20

30

40

50

-20 -10 0 10 20 30 40 50Temperature (:)

Res

ista

nce

(k"

)

Medium temperature thermistor

0: 180k"25: 50k"50: 17k"70: 8k"90: 4k"

ThermistorR50=17k"±2%Bconstant=4170±3%

Rt=17exp{4170(273+t–323 )}1 1

Heatsinktemperaturethermistor(TH8)

High temperature thermistor

ThermistorR120=7.465k"±2%Bconstant=4057±2%

Rt=7.465exp{4057(273+t–393)}1 1

20: 250k"30: 160k"40: 104k"50: 70k"60: 48k"

70: 34k"80: 24k"90: 17.5k"100: 13.0k"110: 9.8k"

Compressortemperaturethermistor(TH4)

200

150

100

50

025 50 75 100110 125

Temperature (:)

Res

ista

nce

(k"

)

500

400

300

200

100

025 50 75 100 120

Temperature (:)

Res

ista

nce

(k"

)

0.5

2.5 5

2.5

4.5

Vout (V)

PRESSURE (MPa)

3

2

1

WHT

BLU

BLKSE

NS

OR

5V DC

GND63HS

Vout MICROPROCESSOR

OUTDOOR CONTROLLERCIRCUIT BOARD

3-1 : 5V (DC)2-1 : Output Vout (DC)

<HIGH PRESSURE SENSOR>

OCH480D

Page 40: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

40

8-7. TEST POINT DIAGRAM8-7-1. Outdoor controller circuit boardMXZ-8B140VA MXZ-8B140YA MXZ-8B160VA MXZ-8B160YA

<CAUTION>TESTPOINT1ishighvoltage.

CommunicationpowersupplyD71Voltage24VDC

CNSS1-S2:220-240VAC(Branchbox/outdoorunitconnectingwire)

CNAC2to4:Powersupplyforoutdoorcontrollercircuitboard(220V-240VAC)1to3:Powersupplyforindoorandoutdoorunitconnectionwire(220-240VAC)

CNF1,CNF2Connecttothefanmotor1-4:250-330VDC5-4:15VDC6-4:0-6.5VDC7-4:15VDC(Whenstopped)7.5VDC(Whenoperated)(0V-15Vpulse)

21S4Four-wayvalve

63HHighpressureswitch

CN4Transmissiontoout-doorpowercircuitboard(CN4)

SW4Testoperation

SW6Modelselect

SW5Functionswitch

SW1Forceddefrost,detecthistoryrecordreset

CNDM1to2:Inputoflow-levelsoundprioritymode1to3:Inputofexternalcontactpoint

TH4Thermistor<Compressor>

TH3Thermistor<Outdoorpipe>

TH7/6Thermistor<Outdoor2-phasepipe>

CNDC250-330VDC(1+, 3-)(OutdoorpowercircuitboardforVA)(NoisefiltercircuitboardforYA)

+ -

VFG

(VoltagebetweenrightpinsofPC5CandPC5D,pin3andpin4)(Sameas(CNF17(+)-4(-))

VSP(VoltagebetweenpinsofC5A,C5B):DC0V(whenstopped),DC1–6.5V(whenoperated)

SW7

CN51

SW8

CN2Connecttotheoutdoorpowercircuitboard(CN2)1-5:Receptionfrom powercircuitboard2-5:Zerocrosssignal(0-5VDC)3,4:Notused6-5:16VDC7-5:16VDC

CN52CConnecttothenoisefil-tercircuitboard(CN52C) (MXZ-8B140/160VA)

SW9 SW2 CN3S

LEDSV1Solenoidvalve1

SV2Solenoidvalve2

63HSHighpressuresensor

63LLowpressureswitch

OCH480D

Page 41: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

41

8-7-2. Outdoor noise filter circuit boardMXZ-8B140YAMXZ-8B160YA

LI1,LI2,LI3,NIPOWERSUPPLYLI1-LI2/LI-LI3/LI3-LI1:AC380/400/415VinputLI1-NI/LI2-NI/LI3-NI:AC220/230/240Vinput(Connecttotheterminalblock(TB1))

GD1Connecttotheearth

CNAC1,CNAC2AC220/230/240V(Connecttotheoutdoorcontrollercircuitboard(CNAC))

CNDC(Connecttotheoutdoorcontrollercircuitboard(CNDC))

LO1,LO2,LO3POWERSUPPLYLO1-LO2/LO2-LO3/LO3-LO1:AC380/400/415VOUTPUT

CNCTPrimarycurrent(Connecttotheoutdoorpowercircuitboard(CN5))

NOConnecttotheoutdoorconvertercircuitboard(N-IN)

CNLConnecttotheACL4

GD3Connecttotheearth

OCH480D

Page 42: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

42

8-7-3. Outdoor power circuit boardMXZ-8B140VAMXZ-8B160VA

CNAC1,CNAC2220-240VACConnecttotheout-doorcontrollercircuitboard(CNAC)

NI, LIVoltageof220-240VACisinput(Connecttotheterminalblock(TB1))

EI,E4ConnecttotheearthDCL1,DCL2

ConnecttoDCL

P2Connecttothesmooth-ingcapacitorCB+

U/V/WConnecttothecompres-sor(MC)Voltageamongphases:10V-180VAC

CNDC280-380VDC(1+, 3-)Connecttotheoutdoorcontrollercircuitboard(CNDC) E2, E3

Connecttotheearth

CN52C52CdrivingsignalConnecttotheoutdoorcontrollercircuitboard(CN52C)

CN2Connecttotheoutdoorcontrollercircuitboard(CN2)1-5:Transmittingsignaltooutdoorcontrollercircuit board(0-5VDC)2-5:Zerocrosssignal(0-5VDC)3-4:18VDC6-5:16VDC7-5:16VDC

N2ConnecttothesmoothingcapacitorCB-

CN4Connecttotheoutdoorcontrollercircuitboard(CN4)

OCH480D

Page 43: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

43

Outdoor power circuit boardMXZ-8B140YAMXZ-8B160YA

CN5Detectionofprimarycurrent(Connecttotheoutdoornoisefiltercircuitboard(CNCT))

CN4Connecttotheoutdoorcontrollercircuitboard(CN4)

CN2Connecttotheoutdoorcontrollercircuitboard(CN2)1-5:Powercircuitboard→Transmittingsignaltothecontrollerboard(0-5VDC)2-5:Zerocrosssignal(0-5VDC)3-4:Notused6-5:16VDC7-5:16VDC

[5:– 1, 2, 6, 7:+]

W

N2N1P2

P1 L1

L2

L3

W

W

TABconnecteronX52AConnecttotheRSresistor

POWERMODULE

TB-C1ConnecttothesmoothingcapacitorCB1– , CB2 +

TB-P2ConnecttothesmoothingcapacitorCB1+

TB-U,TB-V,TB-WConnecttothecompressor(MC)Voltageamongphases:10V-400VAC

TB-L1,TB-L2,TB-L3Connecttotheoutdoorconvertercircuitboard(L1-OU,L2-OU,L3-OU)(140/160VA)Connecttotheoutdoornoisefiltercircuitboard(LO1,LO2,LO3)(140/160YA)380V-415VAC

TB-N1ConnecttothesmoothingcapacitorCB2 –,CKcapacitor(CKcapacitoronlyfor140/160VA)

CN7Connecttotheoutdoorconvertercircuitboard(CN7)

BriefCheckofPOWERMODULE*Usually,theyareinastateofbeingshort-circuitediftheyarebroken.Measuretheresistanceinthefollowingpoints(connectors,etc.).Iftheyareshort-circuited,itmeansthattheyarebroken.1.CheckofPOWERMODULE1CheckofDIODEcircuitL1-P1,L2-P1,L3-P1,L1-N1,L2-N1,L3-N12CheckofIGBTcircuitP2-U,P2-V,P2-W,N2-U,N2-V,N2-WNote:Themarks,L1,L2,L3,N1,N2,P1,P2,U,VandWshowninthediagramarenotactuallyprintedontheboard.

OCH480D

Page 44: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

44

8-7-4. Outdoor converter circuit boardMXZ-8B140YAMXZ-8B160YA

L1-A2,L2-A2,L3-A2ConnecttotheACL1,ACL2,ACL3

CN7Connecttotheoutdoorpowercircuitboard(CN7)

CK-OUConnecttotheCKcapacitor

L1-IN,N-INConnecttothenoisefiltercircuitboard(LO1,No)

L1-A1ConnecttotheACL1

L1-OU,L2-OU,L3-OUConnecttotheoutdoorpowercircuitboard(TB-L1,L2,L3)

OCH480D

Page 45: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

45

Forced defrost Start Normal

Normal—

When compressor is operating in heating operation. *

Abnormal history clearNo function

Self-diagnosis(Indoor unit selection)

Indicating a particularself-diagnosis

Clear—

off or operating—

Test run Operating OFFUnder suspension

Test run mode setting Heating Cooling

Indoor No.1

Indoor No.4

Indoor No.7

Indoor No.2

Indoor No.5

Indoor No.8

Indoor No.3

Indoor No.6

1

23

4

5

6

12

ON OFFNo. Function Effective timingAction by the switch operationSwitch

SW1Dipswitch

SW4

Type ofSwitch

OC

<Example>

A B C D E A B C

IC

RC

IC IC

RC

IndoorNo.1

IndoorNo.2

IndoorNo.3

IndoorNo.4

IndoorNo.5

RC

IC

RC

IC

RC

BC#1 (5- branch type) BC#2 (3- branch type)

BC#1 : branch box controller unit Number 1 1 blinking LED2 (branch box controller board)BC#2 : branch box controller unit Number 2 2 blinking LED2 (branch box controller board)

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

8-8. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS (1) Function of switches The black square (■) indicators a switch position.

Forceddefrostshouldbedoneasfollows.1ChangetheDIPSW1-1ontheoutdoorcontrollerboardfromOFFtoON.2Forceddefrostwillstartbytheaboveoperation1iftheseconditionswrittenbelowaresatisfied.

•Heatmodesetting•10minuteshavepassedsincecompressorstartedoperatingorpreviousforceddefrostfinished.•Pipetemperatureislessthanorequalto8:.

3Forceddefrostwillfinishifcertainconditionsaresatisfied.*ForceddefrostcanbedoneifaboveconditionsaresatisfiedwhenDIPSW1-1ischangedfromOFFtoON.AfterDIPSW1-1ischangedfromOFFtoON,thereisnoproblemifDIPSW1-1isleftONorchangedtoOFFagain.Thisdependsontheserviceconditions.

OCH480D

Page 46: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

46

SW6

SW9

Model selection

Switching function of defrosting prohibited time

During the FAN or COOL mode, and thermo - OFF in heating operation, set the opening of liner expansion valve on branch box

LEV opening setting function for stopping unit during heating operation

Switching the Input Current Limit Level

1

3

2

4

Always

Always

Before turning the power on

While unit stopping

Normal

Normal

Inactive

Normal

Changed

For high humidity

3 A down

Active

1

2

3, 45, 6

1

23456123

ON OFFNo. Function Effective timingAction by the switch operation

No function

Switching the target

sub-cool (Heating mode)

No functionNo function

Demand switchingfunction

No functionMax. Frequency down

No functionNo functionNo functionNo functionNo functionNo function

Switch

SW5

SW7

Dipswitch

SW8

Type ofSwitch

Target sub-cool down

——

Capability cut50%—

Active——————

Normal

——

Normal

—Normal

——————

Always

——

Always

—Always

——————

12345678

140V ONOFF

1 2 3 4 5 6 7 8

160V ONOFF

1 2 3 4 5 6 7 8

140Y ONOFF

1 2 3 4 5 6 7 8

160Y ONOFF

1 2 3 4 5 6 7 8

(2) Function of connector

CN31

Types Connector Function Effective timing

Connector Open a little bit

Pin 1-2 Short Pin 2-3 Short

Action by Pin short operation

LEV opening function(at start-up) When power supply ONNormal

The black square (■) indicators a switch position.

OCH480D

Page 47: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

47

<Outdoor unit operation monitor function>DigitalindicatorLED3displays2digitnumberorcodetoinformoperationconditionandthemeaningofcheckcodebycontrollingDIPSW2onoutdoorcontroller.OperationindicatorSW2:IndicatorchangeofselfdiagnosisSW2setting

1

ON

2 3 4 5 6

Displaydetail Explanationfordisplay Unit

<Digital indicator LED3 working details>(Besurethat1to6intheSW2aresettoOFF.)

(1)DisplaywhenthepowersupplyisON.WhenthepowersupplyisON,blinkingdisplaysbyturns.Waitfor4minutesatthelongest.(2)Whenthedisplaylights(Normaloperation) 1Operationmodedisplay

1

ON

2 3 4 5 6

(Initialsetting)

SW2

1 secondinterval

LED3(Lighting)

Display Operation ModelThe tens digit : Operation mode The ones digit : Relay output

OCHd

Display

012345678A

CompressorWarming-upCompressor 4-way valve Solenoid valve

(SV1, 2)————ONONONON——

————————ONON

——ONON——ONON—ON

—ON—ON—ON—ON——

OFF / FANCOOLING / DRY

HEATINGDEFROSTING

2DisplayduringerrorpostponementPostponementcodeisdisplayedwhencompressorstopsduetotheworkofprotectiondevice.Postponementcodeisdisplayedwhileerrorisbeingpostponed.

(3)WhenthedisplayblinksInspectioncodeisdisplayedwhencompressorstopsduetotheworkofprotectiondevices.

Display Contents to be inspected (When power is turned on)F3F5F9

E8

E9

EA

EbEc

E0~E7EE, EF

Ed

63L connector(red) is open.63H connector(yellow) is open.2 connectors (63H/63L) are open.Branch box/outdoor communication error (Signal receiving error) (Outdoor unit)Indoor/branch box communication error (Signal receiving error) (Branch box)Branch box/outdoor communication error (Transmitting error) (Outdoor unit)Indoor/branch box communication error (Transmitting error) (Branch box)• Miswiring of indoor - branch box/branch box - outdoor unit connecting wire• Too many indoor units/branch box are in the system.Miswiring of indoor - branch box/branch box - outdoor unit connecting wire(converse wiring or disconnection)Startup time overCommunication error except for outdoor unitCombination error, undefined errorSerial communication error

Display Inspection unit0

1

Outdoor unit, Branch box unitIndoor unit

Display Contents to be inspected (During operation)U2

U7

U1ULU6UFUHUPU3

U4

U5U8U9

PA

Discharge temperature faultLow-discharge superheating fault, Erroneous connection of refrigerant pipes or theconnecting wiresHigh pressure fault (63H operates)Low pressure fault (63L operates)Abnormality of power modulesCompressor overcurrent shutoff (Start up locked)Current sensor fault (P. B.)Compressor overcurrent shutoff faultDischarge pipe/compressor thermistor (TH4) open or short-circuitOutdoor unit thermistors (TH3, TH6, TH7, and H8), 63HS, and branch box thermistorsopen or short-circuitHEATSINK temperature faultAbnormality in outdoor fan motorVoltage fault, current sensor fault (N. F.)Forced compressor stop(Overlap malfunction of drain pump in indoor unit and linear expansion valve in branch box.)

OCH480D

Page 48: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

48

SW2setting

1

ON

2 3 4 5 6

Displaydetail Explanationfordisplay UnitPipetemperature/Liquid(TH3)-40to90

-40to90(Whenthecoilthermistordetects0:orbelow,“–”andtemperaturearedisplayedbyturns.)(Example)When-10:;0.5secs.0.5secs.2secs.

:

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Compressortemperature(TH4)3to217

OutputstepofoutdoorFAN0to10

ThenumberofON/OFFtimesofcom-pressor0to9999

Compressorintegratingoperationtimes0to9999

3to217(Whenthedischargethermistordetects100:ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When105:;0.5secs.0.5secs.2secs.

:

Step

100times

10hours

0to10

0to9999(Whenthenumberoftimesis100ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When42500times(425→100times);0.5secs.0.5secs.2secs.

0to9999(Whenitis100hoursormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When2450hours(245→10hours);0.5secs.0.5secs.2secs.

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Compressoroperatingcurrent0to50

LEVopeningpulse0to500

0to50Note:Omitthefiguresafterthedecimalfractions.

0to500(Whenitis100pulseormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.(Example)When150pulse;0.5secs.0.5secs.2secs.

A

Pulse

Errorpostponementcodehistory(1)ofoutdoorunit

PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.

Codedisplay

Codedisplay

Operationmodeonerroroccurring OperationmodeofwhenoperationstopsduetoerrorisdisplayedbysettingSW2likebelow.

1

ON

2 3 4 5 6

(SW2)

10

1

ON

2 3 4 5 6

Compressoroperatingfrequency0to225

0to255(Whenitis100Hzormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.(Example)When125Hz;0.5secs.0.5secs.2secs.

Hz

1 05

4 25

2 45

1 25

1 50

1

ON

2 3 4 5 6

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Theblacksquare(■)indicatesaswitchposition.

OCH480D

Page 49: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

49

SW2setting

1

ON

2 3 4 5 6

Displaydetail Explanationfordisplay UnitPipetemperature/Liquid(TH3)onerroroccurring-40to90

-40to90(Whenthecoilthermistordetects0:orbelow,“–”andtemperaturearedisplayedbyturns.)(Example)When-15:;0.5secs.0.5secs.2secs.

:

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Compressortemperature(TH4)ordischargetemperature(TH4)onerroroccurring3to217

Compressoroperatingcurrentonerroroccurring0to50

Checkcodehistory(1)(latest)Alternatedisplayofabnormalunitnumberandcode

Checkcodehistory(2)Alternatedisplayoferrorunitnumberandcode

3to217(Whenthetemperatureis100:ormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When-15:;0.5secs.0.5secs.2secs.

:

A

Codedisplay

Codedisplay

0to50

Whennocheckcodehistory,“0”and“–”aredisplayedbyturns.

Whennocheckcodehistory,“0”and“–”aredisplayedbyturns.

1

ON

2 3 4 5 6

ThermostatONtime0to999

Testrunelapsedtime0to120

0to999(Whenitis100minutesormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When245minutes;0.5secs.0.5secs.2secs.

0to120(Whenitis100minutesormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When105minutes;0.5secs.0.5secs.2secs.

Minute

Minute

15

1 30

2 45

1 05

1

ON

2 3 4 5 6

Capacitycodeofindoorunit(Qj)

Codedisplay

Thecapacitycodeofindoorunitisdisplayed.

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Theblacksquare(■)indicatesaswitchposition.

OCH480D

Page 50: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

50

SW2setting

1

ON

2 3 4 5 6

Displaydetail Explanationfordisplay Unit

Capacitysettingdisplay Displayedasanoutdoorcapacitycode.Codedisplay

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Outdoorunitsettinginformation

Indoorpipetemperature/Liquid-39to88

Codedisplay

:

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Indoorroomtemperature8to39

Setting details• The tens digit (Total display for applied setting)

• The ones digit

H·P / Cooling onlySingle phase / 3 phase

Display details

0 : H·P 1 : Cooling only0 : Single phase 2 : 3 phase

Setting details

Defrosting switch

Display details

0 : Normal 1 : For high humidity(Example)MXZ-8B140VA,“00”isdisplayed.

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Indoorpipetemperature/Cond./Eva.Indoor-39to88

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

:

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

:

:of/f

:

8to39

Branchboxpipetemperature/gas-39to88

Targetedevaporatingtemperature:ETm(Cooling)Targetedhighpressure:Pdm(Heating)-39to88

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Theblacksquare(■)indicatesaswitchposition.

Capacity CodeMXZ-8B140VA/YA 25MXZ-8B160VA/YA 28

OCH480D

Page 51: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

51

1

ON

2 3 4 5 6

°C

Dischargesuperheat.SHd0to255

0to255(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

°C

Sub-cool.SC(coolingmode)0to130

0to130(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

0.1A

Inputcurrentofoutdoorunit 0to500(Whenitis100ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

0.1of/f

Highpressure63HS 0to500(Whenitis100ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(0to4.9MPa)

Hz

Targetedoperationfrequency0to255

0to255(Whenitis100Hzormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

DCbusvoltageVmodel:180to370Ymodel:300to750

180to370(Whenitis100Vormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.) V

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

SW2setting

1

ON

2 3 4 5 6

Displaydetail Explanationfordisplay Unit

:

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Indoorsettingtemperature17to30

Outdoorheatsinktemperature(TH8)-40to200

17to30

:

:

-40to200(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)(Whenthethermistordetects100:ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

Outdoortemperature(TH7)-39to88

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Theblacksquare(■)indicatesaswitchposition.

1

ON

2 3 4 5 6

:

Outdoorpipetemperature/2-phase(TH6)-39to88

-39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)

:

TargetSub-cool(Coolingmode):SCm 0to255

1

ON

2 3 4 5 6

OCH480D

Page 52: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

52

SW2setting Displaydetail Explanationfordisplay Unit

Codedisplay

Errorpostponementcodehistory(2)ofoutdoorunit

PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.

Codedisplay

Errorpostponementcodehistory(3)ofoutdoorunit

PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.

Codedisplay

Checkcodehistory(3)(Oldest)Alternatedisplayofabnormalunitnumberandcode

Whennocheckcodehistory,“0”and“–“aredis-playedbyturns.

:Outdoorpipetemperature/Liquid(TH3) :Outdooroutsidetemperature(TH7) :Outdoorradiatorpanel(TH8) :Branchboxpipetemperature/Gas(TH–AtoE) :Highpressuresensor(63HS)

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

Errorthermistordisplay

Whenthereisnoerrorthermistor,“–“isdisplayed.

Codedisplay

Operationfrequencyonerroroccurring0to255

0to255(Whenitis100Hzormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When125Hz;0.5secs.0.5secs.2secs.1

ON

2 3 4 5 6

Hz

Fansteponerroroccurring0to15

0to15

1

ON

2 3 4 5 6

Step

251

1

ON

2 3 4 5 6 Pulse

LEVopeningpulseonerroroccurring0to500

0to500(Whenitis100pulseormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When130pulse;0.5secs.0.5secs.2secs.

FortheuseofaP100indoorunit,thesumof2pulsevaluesisdisplayed.(Example)Indoorunit1(P100)=750pulseIndoorunit2(P100other)=400pulse

SW1 Display4 5 6

Indoorunit1 0 0 0 5001 0 0 250

Indoorunit2 0 1 0 400

301

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

:

Indoorroomtemperatureonerroroccurring8to39

8to39

1

ON

2 3 4 5 6

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

378

2363

Theblacksquare(■)indicatesaswitchposition.

OCH480D

Page 53: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

53

SW2setting Displaydetail Explanationfordisplay Unit

:

Indoorpipetemperature/Liquidonerroroccurring-39to88

-39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When-15°C;0.5secs.0.5secs.2secs.

Indoorpipetemperature/Cond./Eva.onerroroccurring-39to88

-39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When-15°C;0.5secs.0.5secs.2secs.

Outdoorpipetemperature/2-phase(TH6)onerroroccurring-39to88

-39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When-15°C;0.5secs.0.5secs.2secs.

Outdooroutsidetemperature(TH7)onerroroccurring-39to88

-39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When-15°C;0.5secs.0.5secs.2secs.

Outdoorheatsinktemperature(TH8)onerroroccurring-40to200

-40to200(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

1

ON

2 3 4 5 6

15

15

15

15

:

:

:

:

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

:

0to255(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When150°C;0.5secs.0.5secs.2secs.

Sub-coolonerroroccurring.SC0to130

0to130(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When115°C;0.5secs.0.5secs.2secs.

501

1

ON

2 3 4 5 6

DischargesuperheatonerroroccurringSHd0to255

1

ON

2 3 4 5 6 :

151

Theblacksquare(■)indicatesaswitchposition.

OCH480D

Page 54: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

54

SW2setting Displaydetail Explanationfordisplay UnitThermostat-ontimeuntilerrorstops0to999

0to999(Whenitis100minutesormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When415minutes;0.5secs.0.5secs.2secs.

1

ON

2 3 4 5 6

Minute

154

1

ON

2 3 4 5 6

NormalOvervoltage errorUndervoltage errorL1 phase interruption errorAbnormal power synchronous signalPFC/ IGBT error(Undervoltage)

* Display examples for multiple errors:Overvoltage (01) + Undervoltage (02) = 03Undervoltage (02) + Power-sync signal error (08) = 0AT phase interruption (04) + PFC error (10) = 14

Description Display0001020408

20

U9ErrorstatusduringtheErrorpostponementperiod

Codedisplay

1

ON

2 3 4 5 6

Codedisplay

Codeofthedifferencebetweenroomtemperatureandsettemperature("∆Tj":0to99)■Tensdigitofcode:current∆Tj■Unitsdigitofcode:∆Tjaminuteago

∆tjCooling Heating

∆tj = room temp. - Set temp. ∆tj = Set temp. - room temp.

Code of the difference between room temperature and set temperature ("∆tj")

0123456789

000100010110001101011111

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

∆tj [ - 0.5 - 1.0 < ∆tj [ - 0.5- 0.5 < ∆tj [ - 0.5

0.0 < ∆tj [ 0.00.5 < ∆tj [ 0.51.0 < ∆tj [ 1.01.5 < ∆tj [ 0.52.0 < ∆tj [ 2.02.5 < ∆tj [ 2.53.0 < ∆tj [ 3.0

∆tj [ - 0.5 - 0.5 < ∆tj [ 0.0

0.0 < ∆tj [ 0.50.5 < ∆tj [ 1.01.0 < ∆tj [ 1.51.5 < ∆tj [ 2.02.0 < ∆tj [ 2.52.5 < ∆tj [ 3.03.0 < ∆tj [ 3.5

3.5 < ∆tj

SW setting (1 to 4, 5, 6) Target unit

Targetrotationofoutdoorfanmotor 0to999

1

ON

2 3 4 5 6

rpm

Sub-cool(Heatingmode) 0to130

:1

ON

2 3 4 5 6

Indoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4Indoor unit 5Indoor unit 6Indoor unit 7Indoor unit 8

01010101

00110011

00001111

SW1654

Theblacksquare(■)indicatesaswitchposition.

OCH480D

Page 55: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

55

8-9. SELECTING FUNCTIONS USING THE REMOTE CONTROLLEREachfunctioncanbesetaccordingtonecessityusingtheremotecontroller.Thesettingoffunctionforeachunitcanonlybedonebytheremotecontroller.Selectfunctionavailablefromthetable1.(1)Functionsavailablewhensettingtheunitnumberto00

*1ThefunctionstablebelowareavailableonlywhenP-seriesindoorunitandthewiredremotecontrollerisused.*2Afterthepowersupplyreturns,theindoorunitdoesnotoperatefor3minutes(Somekindofindoorunitsoperatefor30

seconds,afterthat,itstopsfor3minutes).Aboveoperationisnormal.

<Table1>Functionselections

Function Settings Mode No. Setting No. : Initial setting (when sent from the factory) Remarks

Power failure automatic recoveryIndoor temperature detecting

LOSSNAY connectivity

Power supply voltageFrost prevention temperatureHumidifier control

OFFON *2Data from the indoor unit with remote controllerData from main remote controllerNot supportedSupported (Indoor unit does not intake outdoor air through LOSSNAY)Supported (Indoor unit intakes outdoor air through LOSSNAY)240V220V,230V2: (Normal)3:When the compressor operates, the humidifier also operates.When the fan operates, the humidifier also operates.

12123123121212

01

02

03

04

15

16

The setting is applied to all the units in the same refrigerant system.

OCH480D

Page 56: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

56

Warning:Besuretoconnectthepowersupplycordsandcon-nectingwiresfortheindoorunits,outdoorunits,branchboxesdirectlytotheunits(nointermediateconnections).Intermediateconnectionscanleadtocommunicationerrorsinthecordsorwiresandcausesinsufficientinsu-lationtogroundorapoorelectricalcontactattheinter-mediateconnectionpoint.(Ifanintermediateconnectionisnecessary,besuretotakemeasurestopreventwaterfromenteringthecordsandwires.)

9 ELECTRICAL WIRING

9-1. EXTERNAL WIRING PROCEDURE (Fig. 9-1) EPowersupply:140/160VSingle220/230/240,50Hz220V,60Hz, 140/160Y3-phase380/400/415V,50Hz Max.PermissivesystemImpedance:0.22(")Note: 1Powersupplyinput:Outdoorunitonly.Connectthelines(C),(D)inaccordancewiththeterminalblocknamestoensure

correctpolarity. 2Asforlines(C),S1andS2areforconnectingthepowersource.AndS2andS3areforsignals.S2isacommoncablefor

thepowersourceandsignal.

Whenusingtwistedwireforthewiring,theuseofroundterminalisrequired.*1Max45m(“Outdoorunit-Branchbox#1”plus“branchbox#1-Branchbox#2”).If2.5mm² used,Max55m.Notes:1.Wiringsizemustcomplywiththeapplicablelocalandnationalcode. 2.PowersupplycordsandIndoorunit/Branchbox/Outdoorunitconnectingcordsshallnotbelighterthanpolychloro-

prenesheathedflexiblecord.(Design60245IEC57) 3.Installanearthlinelongerthanpowercables.

Warning:ThereishighvoltagepotentialontheS3terminalcausedbyelectricalcircuitdesignthathasnoelectricalinsulationbetweenpowerlineandcommunicationsignalline.Therefore,pleaseturnoffthemainpowersupplywhenservicing.AnddonottouchtheS1,S2,S3terminalswhenthepowerisenergized.Ifisolatorshouldbeusedbetweenindoorunit,branchboxandoutdoorunit,pleaseuse3-poletype.

LN

S1S2S3

S1S2S3

S1S2S3

S1S2S3

TB3A

S1S2S3

S1S2S3

TB3BTB2B

S1S2S3

S1S2S3

TB3C

S1S2S3

S1S2S3

TB3D

S1S2S3

S1S2S3

TB3E

(A)E

(A)

(B)

S1S2S3

S1S2S3

TB3A

S1S2S3

S1S2S3

S1S2S3

TB3B

S1S2S3

S1S2S3

TB3C

(C)

(D)

(D)

(D)

(D)

(D)

(D)

(D)

(D)

(C)

Circuit breaker

Outdoor unit

Circuit breaker

Outdoor unit

Indoor unitBranch box #1(5- branch type)

<Example 1>(In case of 2- branch boxes)

Branch box #2(3- branch type)

A ROOM

B ROOM

C ROOM

D ROOM

E ROOM

F ROOM

G ROOM

H ROOM

TB2

L3L2L1

N

S1S2S3

(A)

E

■For 140-160Y

■For 140-160V

(A)

(B)(C)

Fig. 9-1

IMPORTANTMake sure that the current leakage breaker is one compatible with higher harmonics.Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.The use of an inadequate breaker can cause the incorrect operation of inverter.

Model

Wirediameter Breaker(A)Mainpowerline (B)Earthline (C)Signalline/

Earthline(D)Signalline/Earthline

Interruptingcurrent

Performancecharacteristic

140/160V 6.0mm² 6.0mm² 1.5mm²*1/Min.1.5mm²

1.5mm²/Min.1.5mm² 40A 40A,30mA

for0.1sec.orless

140/160Y 1.5mm² 1.5mm² 1.5mm²*1/Min.1.5mm²

1.5mm²/Min.1.5mm² 25A 25A,30mA

for0.1sec.orless

OCH480D

Page 57: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

57

TB3ES1S2S3

TB3DS1S2S3

S1S2S3

S1S2S3

S1S2S3

S1S2S3

S1S2S3

S1S2S3

S1S2S3

S1S2S3

TB3C

N

TB2B

L

TB3A

TB3B

(A)E

(A)

(B) (C)

(D)

(D)

Fig. 9-2

Notes:• When wiring a single P100 indoor unit, ONLY use TB3A.If a single P100 indoor unit is wired to the other terminal block, an alarm will be activated, and the indoor unit will not operate.

• When a single P100 indoor unit is wired to TB3A, do not wire any indoor unit to TB3B. Otherwise, an alarm will be activated, and the indoor unit will not operate.

• TB3C, TB3D, and TB3E are available for wiring of indoor units that are not P100.

9-2. WIRING TO P100 INDOOR UNITS (Fig. 9-2)• WhenwiringP100 indoorunit(s),onlyusePAC-AK52BCbranchbox.

• WhenwiringasingleP100indoorunit,useTB3A.

Notes:• When wiring two P100 indoor units, ONLY use TB3A and TB3C. If two P100 indoor units are wired to the other terminal blocks, an alarm will be activated, and the indoor units will not operate.

• When two P100 indoor units are wired to TB3A and TB3C respectively, do not wire any indoor unit to TB3B or TB3D. Otherwise, an alarm will be activated, and the indoor unit will not operate.

• WhenwiringtwoP100indoorunits,useTB3AandTB3C.

Circuitbreaker

<Example2>(incaseofwiringtoP100indoorunit(s))

BranchBox(PAC-AK52BConly)

Indoorunit

P100Indoorunit

B ROOMP100Indoorunit

A ROOM

OCH480D

Page 58: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

58

10 WIRING SPECIFICATIONS

Warning:IncaseofA-controlwiring,thereishighvoltagepotentialontheS3terminalcausedbyelectricalcircuitdesignthathasnoelectricalinsulationbetweenpowerlineandcommunicationsignalline.Therefore,pleaseturnoffthemainpowersupplywhenservicing.AnddonottouchtheS1,S2,S3terminalswhenthepowerisenergized.Ifisolatorshouldbeusedbetweenoutdoorunitandbranchbox/indoorunitsandbranchbox,pleaseuse3-poletype.

S1

S2

S3

S1

S2

S3

S1

S2

S3

S1

S2

S3Branch - box

Outdoor unit

Isolator (Switch)

Power supply

3 poles isolator (Switch)

"A-Control"Indoor unit

Cross section of cable Wire size (e) Number of wires Polarity L (m) w 6Clockwise : S1-S2-S3w Pay attention to stripe of yellow and green.

Not applicable(Because center wire has no cover finish)

From left to right : S1-Open-S2-S3

Clockwise : S1-S2-S3-Openw Connect S1 and S3 to the opposite angle.

(50)w 2

Not applicablew 5(45)w 3

(55)w 4

Round

Flat

Round

Flat

2.5 3

3

4

4

2.5

1.5

2.5

WIRING SPECIFICATIONS(OUTDOOR-BRANCH BOX CONNECTING CABLE)

*1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or 60227 IEC.*2 : In case that cable with stripe of yellow and green is available.*3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm2.*4 : In case of regular polarity connection (S1-S2-S3).*5 : In the flat cables are connected as this picture, they can be used up to 55 m.*6 : Mentioned cable length is just a reference value. It may be different depending on the condition of installation, humidity or materials, etc.

S1 S2 S3

(3C Flat cable o 2)

Besuretoconnecttheoutdoor-branchbox/indoorunits-branchboxconnectingcablesdirectlytotheunits(nointermediateconnections).Intermediateconnectionscanleadtocommunicationerrorsifwaterentersthecablesandcausesinsufficientinsulationtogroundorapoorelectricalcontactattheintermediateconnectionpoint.(Ifanintermediateconnectionisnecessary,besuretotakemeasurestopreventwaterfromenteringthecables.)

<CAUTION>After using isolator, be sure to turn off and on the main power supply to reset the system.Otherwise, outdoor unit may not be able to detect the branch box(es) or indoor units.

OCH480D

Page 59: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

59

OC

BC (3- branch type)A B C

IC

RC

IC

RC

IC

RC

OC

BC(3- branch type)A B C

IC

RC

IC

RC

RC

IC

BC(3- branch type)A B C

IC

RC

IC

RC

RC

IC

OC

11-2-1. Only 3-branch type 11-2-3. 2-branch boxes (3-branch type)11-2-2. Only 5-branch type

BC(5- branch type)A B C D E

IC

RC

IC

RC

IC

RC

IC

RC

IC

RC

OC

BC (5- branch type)A B C D E

IC

RC

IC

RC

IC

RC

IC

RC

IC

RC

BC (5- branch type)A B C D E

IC

RC

IC

RC

IC

RC

IC

RC

IC

RC

1. Up to 2 branch boxes can be connected to a single outdoor unit.

2. Up to 8 indoor units can be connected to the system.

11-2-4. 2-branch boxes (5-branch type, maximum 8 indoor units)

OCOC : Outdoor unitBC : Branch boxIC : Indoor unitRC : Remote controller

BC (5- branch type)A B C D E

BC (3- branch type)A B C

RC

ICIC IC IC IC

RCRC

RC

RC

IC IC

RC

IC

RC

RC

OC

A B C D E A B C

IC

RC

IC IC

RC RC

IC

RC

IC

RC

NOTE: The indoor units can be connected to any of the 5 connectors (5- branch type) or 3 connectors (3- branch type) of the branch box.

BC (5- branch type) BC (3- branch type)

11 SYSTEM CONTROL

11-1. BASIC SYSTEMS

11-2. STANDARD SYSTEMS

OCH480D

Page 60: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

60

OC

BC (3- branch type)A B C

IC

RC

IC IC

RC

11-3-1. Group operation by single remote controller

• Plural indoor units cannot be operated by a single remote controller.

OC OC

BC (3- branch type)A B C

IC

RC

BC (3- branch type)A B C

IC IC

RC

11-3-2. Group operation between different refrigerant systems

• Different refrigerant systems cannot be connected together.

OC Master controller(G-50. etc.)

Power supply unit

ADP001

M-NETBC (3- branch type)

A B C

IC

RC RC

IC IC

RC

11-3-3. Connection of M-NET adapter to outdoor unit

• A M-NET adapter cannot be connected to an outdoor unit.

11-3. INCORRECT SYSTEMS

OCH480D

Page 61: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

61

12 REFRIGERANT PIPING TASK

12-1. ADDITIONAL REFRIGERANT CHARGE

A

A

B

C

B

BC C CC

C CC

C

L

Ih2

b2b1

a6a5a4a3a2

h3

h1H

a1a7 a8

Outdoor unitBranch boxIndoor unit

Permissiblelength(one-way)

*2 Branch box should be placed with in the level between the outdoor unit and indoor units.

Permissibleheight difference(one-way)

Total piping lengthFarthest piping length (L)Piping length between outdoor unit and branch boxesFarthest piping length after branch box (I)Total piping length between branch boxes and indoor unitsIn indoor / outdoor section (H) *2

In branch box / indoor unit section (h1)In each branch unit (h2)In each indoor unit (h3)

*1

b1 + b2 + a1+ a2 + a3 + a4 + a5 + a6 + a7 + a8 [ 115mb2 + a8 [ 70m (b2 [ 55m, a8 [ 15m)

b1 + b2 [ 55m

a8 [ 15m

a1+ a2 + a3 + a4 + a5 + a6 a7 + a8 [ 60m

H [ 30m (In case of that outdoor unit is set higher than indoor unit)H [ 20m (In case of that outdoor unit is set lower than indoor unit)h1 + h2 [ 15mh2 [ 15mh3 [ 12m| b1 + a1 |,| b1 + a2 |,| b1 + a3 |,| b1 + a4 |,| b1 + a5 |,| b2 + a6 |,| b2 + a7 |,| b2 + a8 | [ 15

Number of bends

•Additionalchargingisnotnecessaryforthisunitifthetotalpipelength(b1+b2+a1+a2+a3+a4+a5+a6+a7+a8)doesnotexceed40m.

•Ifthetotalpipelengthexceeds40m,chargetheunitwithadditionalR410Arefrigerantaccordingtothepermittedpipelengthsinthechartonthenextpage.

Afterchargingtheunitwithrefrigerant,notetheaddedrefrigerantamountontheservicelabel(attachedtotheunit).

Refertothe“installationmanual”formoreinformation.

1Indoorunit[P100type]2Y-shapeconnectionpipea1=c1+c2CB

12

c1 c2

*1AlthoughtworefrigerantpipesareusedbetweenthebranchboxandtheY-shapeconnectionpipewhenconnectingtheP100indoorunit,calculatethepipinglengthsusingonlythelengthofonepipe.

OCH480D

Page 62: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

62

Total piping length(b1+ b2 + a1+ a2 + a3 + a4 + a5 + a6 + a7 + a8)

If connecting an indoor unit with [9.52 liquid pipes (model number 71 or more for M-and S-series and model number 60 or morefor P-series), the additional refrigerant charging amount in Table 1 must be corrected (add the following R value from the valuegiven in Table 1).

Additional refrigerant charging correction amountR=0.01 [kg/m] o [9.52 branch pipe (liquid pipe) total length [m]

Example) b1 = 20m, b2 = 25m

<Table 1>

Total piping length : b1 + b2 + a1 + a2 + a6 + a7 = 95m➝ According to Table 1, the additional refrigerant charging amount is 3.2kg.Because indoor units with [9.52 liquid pipes are connected (indoor units A and D in this example), the additional refrigerant charging amount must be corrected.

Additional refrigerant charging correction amountR = 0.01 [kg/m] o [9.52 branch pipe (liquid pipe) total length (a1 + a7)

= 0.01 o (12 + 13m)= 0.25kg

Therefore, the additional refrigerant charging amount is 3.2kg + 0.25kg = 3.45kg.

* Reference The refilling amount of refrigerant at servicing

Example) 3.45 + 8.5 = 11.95kg The amount of refrigerant of initial charge (8.5kg) is added.

Additional refrigerant charging amount

Indoor unit BIndoor unit CIndoor unit D

Indoor unit A[6.35 liquid pipe[6.35 liquid pipe[9.52 liquid pipe

[9.52 liquid pipea2 = 11ma6 = 14ma7 = 13m

a1 = 12m

41 – 50m 51 – 70m 71 – 90m 91 – 115m

0.6kg

40m or less

0kg (no need)8.5kg

(8.5 + 0)9.1kg

(8.5 + 0.6)9.9kg

(8.5 + 1.4)11.7kg

(8.5 + 3.2)10.7kg

(8.5 + 2.2)

1.4kg 2.2kg 3.2kg* Reference (for service)The amount of refilling refrigerant charge

*Althoughtwoø6.35liquidpipesareusedbetweenthebranchboxandtheY-shapeconnectionpipewhenconnectingtheP100indoorunit,calculatetheadditionalrefrigerantchargingamountassumingonlyoneø9.52liquidpipeisused.

12-2. REFRIGERANT COLLECTING (PUMP DOWN)Performthefollowingprocedurestocollecttherefrigerantwhenmovingtheindoorunitortheoutdoorunit.1Turnoffthecircuitbreaker.2Connectthelowpressuresideofthegaugemanifoldtotheserviceportofthegassidestopvalve.3Closetheliquidstopvalue.4Supplypower(circuitbreaker).*Start-upoftheindoor-outdoorcommunicationtakesabout3minutesafterthepower(circuitbreaker)isturnedon.Startthepump-downopera-tion3to4minutesafterthepower(circuitbreaker)isturnedON.

5Performthetestrunforcoolingoperation(SW4-1:ONandSW4-2:OFF).Thecompressor(outdoorunit)andventilators(indoorandoutdoorunits)startoperatingandtestrunforcoolingoperationbegins.

*OnlysettheSW4-1andSW4-2toONiftheunitisstopped.However,eveniftheunitisstoppedandtheSW4-1andSW4-2aresettoONlessthan3minutesafterthecompressorstops,therefrigerantcollectingoperationcannotbeperformed.Waituntilcompressorhasbeenstoppedfor3minutesandthensettheSW4-1andSW4-2toONagain.

6Fullyclosethegasstopvalvewhenthepressurereadingonthegaugedrops0.05-0.00MPa(approximately0.5-0.0kgf/cm²)7Stoptheairconditioneroperation.(SW4-1:OFFandSW4-2:OFF)8Turnoffthepowersupply(circuitbreaker).*Iftoomuchrefrigeranthasbeenaddedtotheairconditionersystem,thepressuremaynotdropto0.5kgf/cm².Ifthisoccurs,usearefrigerantcollectingdevicetocollectalloftherefrigerantinthesystem,andthenrechargethesystemwiththecorrectamountofrefrigerantaftertheindoorandoutdoorunitshavebeenrelocated.

Warning:When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it.

OCH480D

Page 63: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

63

Indoor unit

The smallestroom

The secondsmallest room

Outdoor unitVentilation apparatus

Branch box

Indoor unit

Branch box

Opening

Wall

Outdoor unit

(situation in which thereare no door openings orin which there are open-ings above and belowdoors that occupy atleast 0.15% of the floorarea)

Indoor unit

Branch boxOutdoor unit

12-3. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE12-3-1. IntroductionR410Arefrigerantofthisairconditionerisnon-toxicandnon-flammablebutleakingoflargeamountfromanindoorunitintotheroomwheretheunitisinstalledmaybedeleteri-ous.Topreventpossibleinjury,theroomsshouldbelargeenoughtokeeptheR410AconcentrationspecifiedbyISO5149-1asfollows.

Note:Whensinglerefrigerationsystemconsistsofseveralinde-pendentrefrigerationcircuit,figureoutthetotalrefrigerantamountbyeachindependentrefrigerantcircuit.

(1) Calculate total refrigerant amount by each refrig-erant system.Total refrigerant amount is precharged refrigerant at ex-factory plus additional charged amount at field installation.

(2) Calculate room volumes (m³) and find the room with the smallest volume

Thepartwithrepresentstheroomwiththesmallestvolume. (a) Situation in which there are no partitions

(3) Use the results of calculations (1) and (2) to cal-culate the refrigerant concentration:

Ifthecalculationresultsdonotexceedthemaximumconcen-tration,performthesamecalculationsforthelargersecondandthirdroom,etc.,untilithasbeendeterminedthatthemaximumconcentrationdoesnotexceedineachroom.

Indoor unit

All refrigerant of this system will leak out to thisroom if there is leakage at this indoor unit.

Directionof refrigerant flow

Outdoor unit

Branch box

MaximumconcentrationMaximumrefrigerantconcentrationofR410Aofaroomis0.44kg/KaccordancewithISO5149-1. Tofacilitatecalculation,themaximumconcentrationisexpressedinunitsofO/K(kgofR410AperK)

(ISO5149-1)MaximumconcentrationofR410A:0.44O/K

12-3-2. Confirming procedure of R410A concentrationFollow(1)to(3)toconfirmtheR410Aconcentrationandtakeappropriatetreatment,ifnecessary.

(b) There are partitions, but there are openings that allow the effective mixing of air.

(c) If the smallest room has mechanical ventilation appa-ratus that is linked to a household gas detection and alarm device, the calculations should be performed for the second smallest room.

Totalrefrigerantintherefrigeratingunit(O) [ Maximumconcentration(O/K)Thesmallestroominwhichanindoorunithasbeeninstalled(K)MaximumconcentrationofR410A:0.44O/K

OCH480D

Page 64: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

64

13 DISASSEMBLY PROCEDURE

OPERATING PROCEDURE PHOTOS & ILLUSTRATION 1. Removing the service panel and top panel (1)Remove3servicepanelfixingscrews(5×12)andslide

thehookontherightdownwardtoremovetheservicepanel.

(2)Removescrews(3forfront,3forrear/5×12)ofthetoppanelandremoveit.

2. Removing the fan motor (MF1, MF2) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Remove5fangrillefixingscrews(5×12)todetachthefan

grille.(SeePhoto1) (4)Removeanut(forrighthandedscrewofM6)todetachthe

propeller.(SeePhoto2) (5)Disconnecttheconnectors,CNF1andCNF2oncontroller

circuitboardinelectricalpartsbox. (6)Remove4fanmotorfixingscrews(5×25)todetachthe

fanmotor.(SeePhoto3)

3. Removing the electrical parts box (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Disconnecttheindoor/outdoorconnectingwirefromtermi-

nalblock. (4)Removeallthefollowingconnectorsfromcontrollercircuitboard;

fanmotor,thermistor<Outdoorpipe>,thermistor<Compressor>, thermistor<Outdoor2-phasepipe>,thermistor<Outdoor>,highpressureswitch,highpressuresensor,lowpressureswitch,solenoidvalvecoil<4-wayvalve>andsolenoidvalvecoil<Hotgasbypass>,solenoidvalvecoil<Returningoilbypass>.Thenremoveascrew(4×8)fromthevalvebedtoremovetheleadwire.Pulloutthedisconnectedwirefromtheelectricalpartsbox.

<Diagramsymbolintheconnectorhousing> •Fanmotor(CNF1,CNF2) •Thermistor<Outdoorpipe>(TH3) •Thermistor<Compressor>(TH4) •Thermistor<Outdoor2-phasepipe,Outdoor>(TH7/6) •Highpressureswitch(63H) •Highpressuresensor(63HS) •Lowpressureswitch(63L) •Solenoidvalvecoil<4-wayvalve>(21S4) •Solenoidvalvecoil<Bypassvalve>(SV1) •Solenoidvalvecoil(Returningoilbypass) <Bypassvalve>(SV2) (5)Removetheterminalcoveranddisconnectthecompressor

leadwire. (6)Removeanelectricalpartsboxfixingscrew(4×10)and

detachtheelectricalpartsboxbypullingitupward.Theelectricalpartsboxisfixedwith2hooksontheleftand1hookontheright.

Fanmotorfixingscrews

Photo 2 Fanmotor

Fanmotorfixingscrews

PropellerFrontpanel

Nut

Photo 3

Photo 4

Electricalpartsbox

Controllercircuitboard(C.B.)

Electricalpartsboxfixingscrew

Terminalcover

Coverpanel(Front)

Coverpanelfixingscrews

Compressor(MC)

Terminalblock(TB1)

ValvebedScrew

MXZ-8B140VA MXZ-8B140YA MXZ-8B160VA MXZ-8B160YA

Photo 1 Toppanelfixingscrews Toppanel

Servicepanelfixingscrews

Servicepanel

Grillefixingscrews

Fangrille

Grillefixingscrews

Slide

Frontpanel

Photo: MXZ-8B140/160VA

OCH480D

Page 65: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

65

OPERATING PROCEDURE PHOTOSPhoto 5 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)

(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Disconnecttheconnectors,TH6andTH7(red),onthe

controllercircuitboardintheelectricalpartsbox. (4)Loosentheclampfortheleadwireintherearofthe

electricalpartsbox. (5)Pulloutthethermistor<Outdoor2-phasepipe>(TH6)from

thesensorholder.

Note:Incaseofreplacingthermistor<Outdoor2-phasepipe>(TH6),replaceittogetherwiththermistor<Outdoor>(TH7)sincetheyarecombinedtogether.RefertoNo.5belowtoremovethermistor<Outdoor>.

5. Removing the thermistor <Outdoor> (TH7)(1)Removetheservicepanel.(SeePhoto1)(2)Removethetoppanel.(SeePhoto1)(3)DisconnecttheconnectorTH7(red)onthecontrollercircuit

boardintheelectricalpartsbox.(4)Loosentheclampfortheleadwireintherearofthe

electricalpartsbox.(SeePhoto5)(5)Pulloutthethermistor<Outdoor>(TH7)fromthesensor

holder.

Note:Incaseofreplacingthermistor<Outdoor>(TH7),replaceittogetherwiththermistor<Outdoor2-phasepipe>(TH6),sincetheyarecombinedtogether.RefertoNo.4abovetoremovethermistor<Outdoor2-phasepipe>.

Photo 7

Photo 6

Leadwireofthermistor<Outdoor>(TH7)

Sensorholder

Thermistor<Compressor>(TH4)

Thermistor<Outdoorpipe>(TH3)

Compressor(MC)

Clamp

Controllercircuitboard(C.B.)

Thermistor<Outdoor2-phasepipe>(TH6)

6. Removing the thermistor <Outdoor pipe> (TH3) and thermistor <Compressor> (TH4)

(1)Removetheservicepanel.(SeePhoto1) (2)Disconnecttheconnectors,TH3(white)andTH4(white),

onthecontrollercircuitboardintheelectricalpartsbox. (3)Loosentheclampfortheleadwireintherearofthe

electricalpartsbox.(SeePhoto5) (4)Pulloutthethermistor<Outdoorpipe>(TH3)and

thermistor<Compressor>(TH4)fromthesensorholder.

OCH480D

Page 66: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

66

9. Removing solenoid valve coil <Bypass valve> (SV1) and bypass valve

(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto5) (4)Remove3rightsidepanelfixingscrews(5×12)inthe

rearoftheunitandremovetherightsidepanel. (5)Removethebypassvalvecoilfixingscrew(M4×6). (6)Removethesolenoidvalvecoil<Bypassvalve>(SV1)by

slidingthecoilupward. (7)Recoverrefrigerant. (8)Removetheweldedpartofbypassvalve.

Note1:Recoverrefrigerantwithoutspreadingitintheair. Note2:Theweldedpartcanberemovedeasilybyremoving

therightsidepanel.

10. Removing solenoid valve coil (Returning oil bypass) <Bypass valve> (SV2) and bypass valve

(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto5) (4)Remove3rightsidepanelfixingscrews(5×12)inthe

rearoftheunitandremovetherightsidepanel. (5)Removethebypassvalvecoilfixingscrew(M5×6). (6)Removethesolenoidvalvecoil(Returningoilbypass)

<Bypassvalve>(SV2)byslidingthecoilupward. (7)Recoverrefrigerant. (8)Removetheweldedpartofbypassvalve.

Note1:Recoverrefrigerantwithoutspreadingitintheair. Note2:Theweldedpartcanberemovedeasilybyremoving

therightsidepanel.

Photo 9

Solenoidvalvecoil<Bypassvalve>(Returningoilbypass)(SV2)

Bypassvalve(SV2)

Solenoidvalvecoil<Bypassvalve>(SV1)

Bypassvalve(SV1)

OPERATING PROCEDURE PHOTOS 7. Removing the solenoid valve coil <4-way valve> (21S4) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1)

[Removing the solenoid valve coil <4-way valve>] (3)Remove4-wayvalvesolenoidcoilfixingscrew

(M5×6). (4)Removethesolenoidvalvecoil<4-wayvalve>bysliding

thecoiltowardyou. (5)Disconnecttheconnector21S4(green)onthecontroller

circuitboardintheelectricalpartsbox.

8. Removing the 4-way valve (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Remove3valvebedfixingscrews(4×10)and4ball

valveandstopvalvefixingscrews(5×16)andthenremovethevalvebed.

(4)Remove4rightsidepanelfixingscrews(5×12)intherearoftheunitandthenremovetherightsidepanel.

(5)Removethesolenoidvalvecoil<4-wayvalve>.(SeePhoto8)

(6)Recoverrefrigerant. (7)Removetheweldedpartof4-wayvalve.

Note1:Recoverrefrigerantwithoutspreadingitintheair.Note2:Theweldedpartcanberemovedeasilybyremoving

therightsidepanel.Note3:Wheninstallingthe4-wayvalve,coveritwithawet

clothtopreventitfromheating(120°Cormore),thenbrazethepipessothattheinsideofpipesarenotoxidized.

Photo 8

Solenoidvalvecoil<4-wayvalve>(21S4)

4-wayvalve

Solenoidvalvecoil<4-wayvalve>fixingscrew

OCH480D

Page 67: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

67

11. Removing the high pressure switch (63H) and low pres-sure switch (63L)

(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto5) (4)Remove3rightsidepanelfixingscrews(5×12)inthe

rearoftheunitandremovetherightsidepanel. (5)Pullouttheleadwireofhighpressureswitchandlow

pressureswitch. (6)Recoverrefrigerant. (7)Removetheweldedpartofhighpressureswitchandlow

pressureswitch.

Note1:Recoverrefrigerantwithoutspreadingitintheair. Note2:Theweldedpartcanberemovedeasilybyremoving

therightsidepanel. Note3:Wheninstallingthehighpressureswitchandlow

pressureswitch,coverthemwithawetclothtopre-ventthemfromheating(100°Cormore),thenbrazethepipessothattheinsideofpipesarenotoxidized.

12. Removing the high pressure sensor (63HS) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto5) (4)Remove3rightsidepanelfixingscrews(5×12)inthe

rearoftheunitandremovetherightsidepanel. (5)Pullouttheleadwireofhighpressuresensor. (6)Recoverrefrigerant. (7)Removetheweldedpartofhighpressuresensor.

Note1:Recoverrefrigerantwithoutspreadingitintheair. Note2:Theweldedpartcanberemovedeasilybyremoving

therightsidepanel. Note3:Wheninstallingthehighpressuresensor,coverit

withawetclothtopreventitfromheating(100°Cormore),thenbrazethepipessothattheinsideofpipesarenotoxidized.

OPERATING PROCEDURE PHOTOSPhoto 10

Lowpressureswitch(63L)

Highpressuresensor(63HS)

Highpressureswitch(63H)

OCH480D

Page 68: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

cCopyright2011MITSUBISHIELECTRICCORPORATIONDistributedinMar.2014No.OCH480REVISEDEDITION-DDistributedinJun.2013No.OCH480REVISEDEDITION-CDistributedinApr. 2013No.OCH480REVISEDEDITION-BDistributedinSep.2011No.OCH480REVISEDEDITION-ADistributedinJul. 2011No.OCH480MadeinJapan

Newpublication,effectiveMar.2014Specificationsaresubjecttochangewithoutnotice.

HEADOFFICE:TOKYOBLDG.,2-7-3,MARUNOUCHI,CHIYODA-KU,TOKYO100-8310,JAPAN

Page 69: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating15 1500 1700 0.80 0.58 3.7 2.7 3.5 2.5 3.4 2.416 1600 1800 0.84 0.62 3.9 2.8 3.7 2.7 3.5 2.617 1700 1900 0.87 0.65 4.0 3.0 3.8 2.9 3.7 2.718 1800 2100 0.91 0.72 4.2 3.3 4.0 3.2 3.8 3.019 1900 2200 0.95 0.76 4.4 3.5 4.2 3.3 4.0 3.220 2000 2300 0.98 0.79 4.5 3.6 4.3 3.5 4.1 3.321 2100 2400 1.02 0.82 4.7 3.8 4.5 3.6 4.3 3.522 2200 2500 1.05 0.86 4.8 3.9 4.6 3.8 4.4 3.623 2300 2600 1.08 0.89 5.0 4.1 4.7 3.9 4.5 3.724 2400 2700 1.11 0.93 5.1 4.3 4.9 4.1 4.7 3.925 2500 2900 1.14 1.00 5.2 4.6 5.0 4.4 4.8 4.226 2600 3000 1.17 1.03 5.4 4.7 5.1 4.5 4.9 4.327 2700 3100 1.20 1.06 5.5 4.9 5.3 4.7 5.1 4.528 2800 3200 1.23 1.10 5.6 5.1 5.4 4.8 5.2 4.629 2900 3300 1.26 1.13 5.8 5.2 5.5 5.0 5.3 4.830 3000 3400 1.28 1.17 5.9 5.4 5.6 5.1 5.4 4.931 3100 3500 1.31 1.20 6.0 5.5 5.8 5.3 5.5 5.132 3200 3700 1.33 1.27 6.1 5.8 5.8 5.6 5.6 5.333 3300 3800 1.36 1.31 6.2 6.0 6.0 5.8 5.7 5.534 3400 3900 1.38 1.34 6.3 6.2 6.1 5.9 5.8 5.635 3500 4000 1.41 1.37 6.5 6.3 6.2 6.0 5.9 5.836 3600 4100 1.43 1.41 6.6 6.5 6.3 6.2 6.0 5.937 3700 4200 1.45 1.44 6.7 6.6 6.4 6.3 6.1 6.138 3800 4300 1.47 1.48 6.7 6.8 6.5 6.5 6.2 6.239 3900 4500 1.49 1.55 6.8 7.1 6.5 6.8 6.3 6.540 4000 4600 1.51 1.58 6.9 7.3 6.6 6.9 6.4 6.641 4100 4700 1.53 1.61 7.0 7.4 6.7 7.1 6.4 6.842 4200 4800 1.55 1.65 7.1 7.6 6.8 7.2 6.5 6.943 4300 4900 1.57 1.68 7.2 7.7 6.9 7.4 6.6 7.144 4400 5000 1.59 1.72 7.3 7.9 7.0 7.6 6.7 7.245 4500 5100 1.61 1.75 7.4 8.0 7.1 7.7 6.8 7.446 4600 5300 1.63 1.82 7.5 8.4 7.2 8.0 6.9 7.747 4700 5400 1.65 1.86 7.6 8.5 7.2 8.2 6.9 7.848 4800 5500 1.66 1.89 7.6 8.7 7.3 8.3 7.0 8.049 4900 5600 1.68 1.92 7.7 8.8 7.4 8.4 7.1 8.150 5000 5700 1.70 1.96 7.8 9.0 7.5 8.6 7.2 8.251 5100 5800 1.73 2.00 7.9 9.2 7.6 8.8 7.3 8.452 5200 5900 1.76 2.03 8.1 9.3 7.7 8.9 7.4 8.553 5300 6100 1.79 2.10 8.2 9.6 7.9 9.2 7.5 8.854 5400 6200 1.82 2.14 8.4 9.8 8.0 9.4 7.7 9.055 5500 6300 1.85 2.18 8.5 10.0 8.1 9.6 7.8 9.256 5600 6400 1.88 2.21 8.6 10.1 8.3 9.7 7.9 9.357 5700 6500 1.91 2.25 8.8 10.3 8.4 9.9 8.0 9.558 5800 6600 1.94 2.29 8.9 10.5 8.5 10.1 8.2 9.659 5900 6700 1.97 2.32 9.0 10.7 8.7 10.2 8.3 9.860 6000 6900 2.00 2.40 9.2 11.0 8.8 10.5 8.4 10.161 6100 7000 2.03 2.43 9.3 11.2 8.9 10.7 8.5 10.262 6200 7100 2.06 2.47 9.5 11.3 9.0 10.8 8.7 10.463 6300 7200 2.08 2.51 9.6 11.5 9.1 11.0 8.8 10.664 6400 7300 2.11 2.54 9.7 11.7 9.3 11.2 8.9 10.765 6500 7400 2.14 2.58 9.8 11.8 9.4 11.3 9.0 10.966 6600 7500 2.17 2.62 10.0 12.0 9.5 11.5 9.1 11.067 6700 7700 2.20 2.69 10.1 12.4 9.7 11.8 9.3 11.368 6800 7800 2.23 2.73 10.2 12.5 9.8 12.0 9.4 11.569 6900 7900 2.26 2.77 10.4 12.7 9.9 12.2 9.5 11.770 7000 8000 2.29 2.81 10.5 12.9 10.1 12.3 9.6 11.871 7100 8100 2.31 2.84 10.6 13.0 10.1 12.5 9.7 12.072 7200 8200 2.34 2.88 10.7 13.2 10.3 12.6 9.8 12.173 7300 8300 2.37 2.92 10.9 13.4 10.4 12.8 10.0 12.374 7400 8500 2.40 2.99 11.0 13.7 10.5 13.1 10.1 12.675 7500 8600 2.43 3.03 11.2 13.9 10.7 13.3 10.2 12.876 7600 8700 2.45 3.07 11.2 14.1 10.8 13.5 10.3 12.977 7700 8800 2.48 3.11 11.4 14.3 10.9 13.7 10.4 13.178 7800 8900 2.51 3.15 11.5 14.5 11.0 13.8 10.6 13.379 7900 9000 2.54 3.19 11.7 14.6 11.2 14.0 10.7 13.4

Before calculating the sum of total capacity of indoor units, please convert the value into the kW model capacityfollowing the formula on "4-1-2. Method of obtaining the heating and cooling capacity of an indoor unit:".

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W)Power Consumption

(kW)

1 / 12

Page 70: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W)Power Consumption

(kW)

80 8000 9100 2.56 3.22 11.8 14.8 11.2 14.1 10.8 13.681 8100 9300 2.59 3.30 11.9 15.2 11.4 14.5 10.9 13.982 8200 9400 2.62 3.34 12.0 15.3 11.5 14.7 11.0 14.183 8300 9500 2.65 3.38 12.2 15.5 11.6 14.8 11.2 14.284 8400 9600 2.67 3.42 12.3 15.7 11.7 15.0 11.2 14.485 8500 9700 2.70 3.45 12.4 15.8 11.9 15.2 11.4 14.586 8600 9800 2.73 3.49 12.5 16.0 12.0 15.3 11.5 14.787 8700 9900 2.75 3.53 12.6 16.2 12.1 15.5 11.6 14.988 8800 10100 2.78 3.61 12.8 16.6 12.2 15.9 11.7 15.289 8900 10200 2.81 3.65 12.9 16.8 12.3 16.0 11.8 15.490 9000 10300 2.83 3.69 13.0 16.9 12.4 16.2 11.9 15.591 9100 10400 2.86 3.73 13.1 17.1 12.6 16.4 12.0 15.792 9200 10500 2.88 3.77 13.2 17.3 12.6 16.6 12.1 15.993 9300 10600 2.91 3.81 13.4 17.5 12.8 16.7 12.2 16.094 9400 10700 2.94 3.85 13.5 17.7 12.9 16.9 12.4 16.295 9500 10900 2.96 3.92 13.6 18.0 13.0 17.2 12.5 16.596 9600 11000 2.99 3.96 13.7 18.2 13.1 17.4 12.6 16.797 9700 11100 3.01 4.00 13.8 18.4 13.2 17.6 12.7 16.898 9800 11200 3.04 4.04 14.0 18.5 13.4 17.7 12.8 17.099 9900 11300 3.06 4.08 14.0 18.7 13.4 17.9 12.9 17.2100 10000 11400 3.09 4.12 14.2 18.9 13.6 18.1 13.0 17.3101 10100 11500 3.13 4.15 14.4 19.1 13.7 18.2 13.2 17.5102 10200 11700 3.18 4.22 14.6 19.4 14.0 18.5 13.4 17.8103 10300 11800 3.23 4.25 14.8 19.5 14.2 18.7 13.6 17.9104 10400 11900 3.27 4.28 15.0 19.7 14.4 18.8 13.8 18.0105 10500 12000 3.32 4.32 15.2 19.8 14.6 19.0 14.0 18.2106 10600 12100 3.37 4.35 15.5 20.0 14.8 19.1 14.2 18.3107 10700 12200 3.41 4.38 15.7 20.1 15.0 19.2 14.4 18.4108 10800 12300 3.46 4.41 15.9 20.2 15.2 19.4 14.6 18.6109 10900 12500 3.51 4.48 16.1 20.6 15.4 19.7 14.8 18.9110 11000 12600 3.56 4.51 16.3 20.7 15.6 19.8 15.0 19.0111 11100 12700 3.61 4.54 16.6 20.8 15.9 19.9 15.2 19.1112 11200 12800 3.66 4.57 16.8 21.0 16.1 20.1 15.4 19.2113 11300 12900 3.71 4.60 17.0 21.1 16.3 20.2 15.6 19.4114 11400 13000 3.76 4.63 17.3 21.3 16.5 20.3 15.8 19.5115 11500 13100 3.81 4.66 17.5 21.4 16.7 20.5 16.0 19.6116 11600 13300 3.87 4.73 17.8 21.7 17.0 20.8 16.3 19.9117 11700 13400 3.92 4.76 18.0 21.9 17.2 20.9 16.5 20.0118 11800 13500 3.97 4.79 18.2 22.0 17.4 21.0 16.7 20.2119 11900 13600 4.03 4.82 18.5 22.1 17.7 21.2 17.0 20.3120 12000 13700 4.08 4.85 18.7 22.3 17.9 21.3 17.2 20.4121 12100 13800 4.14 4.88 19.0 22.4 18.2 21.4 17.4 20.5122 12200 13900 4.19 4.91 19.2 22.5 18.4 21.6 17.6 20.7123 12300 14100 4.25 4.98 19.5 22.9 18.7 21.9 17.9 21.0124 12400 14200 4.30 5.01 19.7 23.0 18.9 22.0 18.1 21.1125 12500 14300 4.36 5.04 20.0 23.1 19.1 22.1 18.4 21.2126 12600 14400 4.42 5.07 20.3 23.3 19.4 22.3 18.6 21.3127 12700 14500 4.48 5.10 20.6 23.4 19.7 22.4 18.9 21.5128 12800 14600 4.54 5.13 20.8 23.6 19.9 22.5 19.1 21.6129 12900 14700 4.60 5.16 21.1 23.7 20.2 22.7 19.4 21.7130 13000 14900 4.66 5.23 21.4 24.0 20.5 23.0 19.6 22.0131 13100 15000 4.72 5.26 21.7 24.2 20.7 23.1 19.9 22.1132 13200 15100 4.78 5.29 21.9 24.3 21.0 23.2 20.1 22.3133 13300 15200 4.84 5.32 22.2 24.4 21.3 23.4 20.4 22.4134 13400 15300 4.91 5.35 22.5 24.6 21.6 23.5 20.7 22.5135 13500 15400 4.97 5.38 22.8 24.7 21.8 23.6 20.9 22.6136 13600 15500 5.01 5.37 23.0 24.7 22.0 23.6 21.1 22.6137 13700 15700 5.05 5.40 23.2 24.8 22.2 23.7 21.3 22.7138 13800 15800 5.09 5.40 23.4 24.8 22.4 23.7 21.4 22.7139 13900 15900 5.14 5.39 23.6 24.7 22.6 23.7 21.6 22.7140 14000 16000 5.18 5.38 23.8 24.7 22.7 23.6 21.8 22.6141 14000 16000 5.18 5.34 23.8 24.5 22.7 23.5 21.8 22.5142 14000 16000 5.19 5.31 23.8 24.4 22.8 23.3 21.8 22.3143 14000 16000 5.19 5.27 23.8 24.2 22.8 23.1 21.8 22.2144 14000 16000 5.20 5.23 23.9 24.0 22.8 23.0 21.9 22.0145 14000 16000 5.20 5.19 23.9 23.8 22.8 22.8 21.9 21.8146 14000 16000 5.21 5.16 23.9 23.7 22.9 22.7 21.9 21.7147 14000 16000 5.21 5.12 23.9 23.5 22.9 22.5 21.9 21.5

2 / 12

Page 71: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W)Power Consumption

(kW)

148 14000 16000 5.22 5.09 24.0 23.4 22.9 22.4 22.0 21.4149 14000 16000 5.22 5.05 24.0 23.2 22.9 22.2 22.0 21.3150 14000 16000 5.22 5.01 24.0 23.0 22.9 22.0 22.0 21.1151 14000 16000 5.15 4.96 23.6 22.8 22.6 21.8 21.7 20.9152 14000 16000 5.08 4.90 23.3 22.5 22.3 21.5 21.4 20.6153 14000 16000 5.01 4.85 23.0 22.3 22.0 21.3 21.1 20.4154 14000 16000 4.95 4.80 22.7 22.0 21.7 21.1 20.8 20.2155 14000 16000 4.89 4.74 22.5 21.8 21.5 20.8 20.6 19.9156 14000 16000 4.82 4.69 22.1 21.5 21.2 20.6 20.3 19.7157 14000 16000 4.76 4.64 21.9 21.3 20.9 20.4 20.0 19.5158 14000 16000 4.71 4.60 21.6 21.1 20.7 20.2 19.8 19.4159 14000 16000 4.65 4.55 21.3 20.9 20.4 20.0 19.6 19.1160 14000 16000 4.59 4.50 21.1 20.7 20.2 19.8 19.3 18.9161 14000 16000 4.54 4.46 20.8 20.5 19.9 19.6 19.1 18.8162 14000 16000 4.49 4.41 20.6 20.2 19.7 19.4 18.9 18.6163 14000 16000 4.43 4.37 20.3 20.1 19.5 19.2 18.6 18.4164 14000 16000 4.38 4.33 20.1 19.9 19.2 19.0 18.4 18.2165 14000 16000 4.33 4.28 19.9 19.7 19.0 18.8 18.2 18.0166 14000 16000 4.28 4.24 19.7 19.5 18.8 18.6 18.0 17.8167 14000 16000 4.24 4.20 19.5 19.3 18.6 18.4 17.8 17.7168 14000 16000 4.19 4.16 19.2 19.1 18.4 18.3 17.6 17.5169 14000 16000 4.14 4.12 19.0 18.9 18.2 18.1 17.4 17.3170 14000 16000 4.10 4.09 18.8 18.8 18.0 18.0 17.3 17.2171 14000 16000 4.06 4.05 18.6 18.6 17.8 17.8 17.1 17.0172 14000 16000 4.01 4.01 18.4 18.4 17.6 17.6 16.9 16.9173 14000 16000 3.97 3.98 18.2 18.3 17.4 17.5 16.7 16.8174 14000 16000 3.93 3.94 18.0 18.1 17.3 17.3 16.5 16.6175 14000 16000 3.89 3.91 17.9 18.0 17.1 17.2 16.4 16.5176 14000 16000 3.86 3.87 17.7 17.8 16.9 17.0 16.2 16.3177 14000 16000 3.81 3.84 17.5 17.6 16.7 16.9 16.0 16.2178 14000 16000 3.78 3.80 17.4 17.4 16.6 16.7 15.9 16.0179 14000 16000 3.74 3.77 17.2 17.3 16.4 16.6 15.7 15.9180 14000 16000 3.70 3.74 17.0 17.2 16.2 16.4 15.6 15.7181 14000 16000 3.67 3.71 16.9 17.0 16.1 16.3 15.4 15.6182 14000 16000 3.63 3.68 16.7 16.9 15.9 16.2 15.3 15.5183 14000 16000 3.60 3.65 16.5 16.8 15.8 16.0 15.2 15.4184 14000 16000 3.57 3.62 16.4 16.6 15.7 15.9 15.0 15.2185 14000 16000 3.53 3.59 16.2 16.5 15.5 15.8 14.9 15.1

3 / 12

Page 72: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating15 1500 1700 0.80 0.58 3.7 2.7 3.5 2.5 3.4 2.416 1600 1900 0.84 0.65 3.9 3.0 3.7 2.9 3.5 2.717 1700 2000 0.87 0.69 4.0 3.2 3.8 3.0 3.7 2.918 1800 2100 0.91 0.72 4.2 3.3 4.0 3.2 3.8 3.019 1900 2200 0.95 0.76 4.4 3.5 4.2 3.3 4.0 3.220 2000 2300 0.98 0.79 4.5 3.6 4.3 3.5 4.1 3.321 2100 2400 1.02 0.82 4.7 3.8 4.5 3.6 4.3 3.522 2200 2600 1.05 0.89 4.8 4.1 4.6 3.9 4.4 3.723 2300 2700 1.08 0.93 5.0 4.3 4.7 4.1 4.5 3.924 2400 2800 1.11 0.96 5.1 4.4 4.9 4.2 4.7 4.025 2500 2900 1.14 1.00 5.2 4.6 5.0 4.4 4.8 4.226 2600 3000 1.17 1.03 5.4 4.7 5.1 4.5 4.9 4.327 2700 3100 1.20 1.06 5.5 4.9 5.3 4.7 5.1 4.528 2800 3300 1.23 1.13 5.6 5.2 5.4 5.0 5.2 4.829 2900 3400 1.26 1.17 5.8 5.4 5.5 5.1 5.3 4.930 3000 3500 1.28 1.20 5.9 5.5 5.6 5.3 5.4 5.131 3100 3600 1.31 1.24 6.0 5.7 5.8 5.4 5.5 5.232 3200 3700 1.33 1.27 6.1 5.8 5.8 5.6 5.6 5.333 3300 3800 1.36 1.31 6.2 6.0 6.0 5.8 5.7 5.534 3400 3900 1.38 1.34 6.3 6.2 6.1 5.9 5.8 5.635 3500 4100 1.41 1.41 6.5 6.5 6.2 6.2 5.9 5.936 3600 4200 1.43 1.44 6.6 6.6 6.3 6.3 6.0 6.137 3700 4300 1.45 1.48 6.7 6.8 6.4 6.5 6.1 6.238 3800 4400 1.47 1.51 6.7 6.9 6.5 6.6 6.2 6.439 3900 4500 1.49 1.55 6.8 7.1 6.5 6.8 6.3 6.540 4000 4600 1.51 1.58 6.9 7.3 6.6 6.9 6.4 6.641 4100 4800 1.53 1.65 7.0 7.6 6.7 7.2 6.4 6.942 4200 4900 1.55 1.68 7.1 7.7 6.8 7.4 6.5 7.143 4300 5000 1.57 1.72 7.2 7.9 6.9 7.6 6.6 7.244 4400 5100 1.59 1.75 7.3 8.0 7.0 7.7 6.7 7.445 4500 5200 1.61 1.79 7.4 8.2 7.1 7.9 6.8 7.546 4600 5300 1.63 1.82 7.5 8.4 7.2 8.0 6.9 7.747 4700 5500 1.65 1.89 7.6 8.7 7.2 8.3 6.9 8.048 4800 5600 1.66 1.92 7.6 8.8 7.3 8.4 7.0 8.149 4900 5700 1.68 1.96 7.7 9.0 7.4 8.6 7.1 8.250 5000 5800 1.70 1.99 7.8 9.1 7.5 8.7 7.2 8.451 5100 5900 1.73 2.03 7.9 9.3 7.6 8.9 7.3 8.552 5200 6000 1.76 2.07 8.1 9.5 7.7 9.1 7.4 8.753 5300 6200 1.79 2.14 8.2 9.8 7.9 9.4 7.5 9.054 5400 6300 1.82 2.17 8.4 10.0 8.0 9.5 7.7 9.155 5500 6400 1.85 2.21 8.5 10.1 8.1 9.7 7.8 9.356 5600 6500 1.88 2.25 8.6 10.3 8.3 9.9 7.9 9.557 5700 6600 1.91 2.28 8.8 10.5 8.4 10.0 8.0 9.658 5800 6700 1.94 2.32 8.9 10.7 8.5 10.2 8.2 9.859 5900 6900 1.97 2.39 9.0 11.0 8.7 10.5 8.3 10.160 6000 7000 2.00 2.43 9.2 11.2 8.8 10.7 8.4 10.261 6100 7100 2.03 2.47 9.3 11.3 8.9 10.8 8.5 10.462 6200 7200 2.06 2.50 9.5 11.5 9.0 11.0 8.7 10.563 6300 7300 2.08 2.54 9.6 11.7 9.1 11.2 8.8 10.764 6400 7400 2.11 2.58 9.7 11.8 9.3 11.3 8.9 10.965 6500 7500 2.14 2.62 9.8 12.0 9.4 11.5 9.0 11.066 6600 7700 2.17 2.69 10.0 12.4 9.5 11.8 9.1 11.367 6700 7800 2.20 2.73 10.1 12.5 9.7 12.0 9.3 11.568 6800 7900 2.23 2.77 10.2 12.7 9.8 12.2 9.4 11.769 6900 8000 2.26 2.80 10.4 12.9 9.9 12.3 9.5 11.870 7000 8100 2.29 2.84 10.5 13.0 10.1 12.5 9.6 12.071 7100 8200 2.31 2.88 10.6 13.2 10.1 12.6 9.7 12.172 7200 8400 2.34 2.95 10.7 13.5 10.3 13.0 9.8 12.473 7300 8500 2.37 2.99 10.9 13.7 10.4 13.1 10.0 12.674 7400 8600 2.40 3.03 11.0 13.9 10.5 13.3 10.1 12.875 7500 8700 2.43 3.07 11.2 14.1 10.7 13.5 10.2 12.976 7600 8800 2.45 3.11 11.2 14.3 10.8 13.7 10.3 13.177 7700 8900 2.48 3.14 11.4 14.4 10.9 13.8 10.4 13.278 7800 9100 2.51 3.22 11.5 14.8 11.0 14.1 10.6 13.679 7900 9200 2.54 3.26 11.7 15.0 11.2 14.3 10.7 13.7

Before calculating the sum of total capacity of indoor units, please convert the value into the kW model capacityfollowing the formula on "4-1-2. Method of obtaining the heating and cooling capacity of an indoor unit:".

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

4 / 12

Page 73: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

80 8000 9300 2.56 3.30 11.8 15.2 11.2 14.5 10.8 13.981 8100 9400 2.59 3.33 11.9 15.3 11.4 14.6 10.9 14.082 8200 9500 2.62 3.37 12.0 15.5 11.5 14.8 11.0 14.283 8300 9600 2.65 3.41 12.2 15.7 11.6 15.0 11.2 14.484 8400 9800 2.67 3.49 12.3 16.0 11.7 15.3 11.2 14.785 8500 9900 2.70 3.53 12.4 16.2 11.9 15.5 11.4 14.986 8600 10000 2.73 3.57 12.5 16.4 12.0 15.7 11.5 15.087 8700 10100 2.75 3.60 12.6 16.5 12.1 15.8 11.6 15.288 8800 10200 2.78 3.64 12.8 16.7 12.2 16.0 11.7 15.389 8900 10300 2.81 3.68 12.9 16.9 12.3 16.2 11.8 15.590 9000 10500 2.83 3.76 13.0 17.3 12.4 16.5 11.9 15.891 9100 10600 2.86 3.80 13.1 17.4 12.6 16.7 12.0 16.092 9200 10700 2.88 3.84 13.2 17.6 12.6 16.9 12.1 16.293 9300 10800 2.91 3.88 13.4 17.8 12.8 17.0 12.2 16.394 9400 10900 2.94 3.92 13.5 18.0 12.9 17.2 12.4 16.595 9500 11000 2.96 3.96 13.6 18.2 13.0 17.4 12.5 16.796 9600 11100 2.99 4.00 13.7 18.4 13.1 17.6 12.6 16.897 9700 11300 3.01 4.08 13.8 18.7 13.2 17.9 12.7 17.298 9800 11400 3.04 4.12 14.0 18.9 13.4 18.1 12.8 17.399 9900 11500 3.06 4.16 14.0 19.1 13.4 18.3 12.9 17.5100 10000 11600 3.09 4.19 14.2 19.2 13.6 18.4 13.0 17.6101 10100 11700 3.13 4.22 14.4 19.4 13.7 18.5 13.2 17.8102 10200 11800 3.18 4.26 14.6 19.6 14.0 18.7 13.4 17.9103 10300 12000 3.23 4.32 14.8 19.8 14.2 19.0 13.6 18.2104 10400 12100 3.27 4.36 15.0 20.0 14.4 19.1 13.8 18.4105 10500 12200 3.32 4.39 15.2 20.2 14.6 19.3 14.0 18.5106 10600 12300 3.37 4.42 15.5 20.3 14.8 19.4 14.2 18.6107 10700 12400 3.41 4.45 15.7 20.4 15.0 19.5 14.4 18.7108 10800 12500 3.46 4.48 15.9 20.6 15.2 19.7 14.6 18.9109 10900 12700 3.51 4.55 16.1 20.9 15.4 20.0 14.8 19.1110 11000 12800 3.56 4.58 16.3 21.0 15.6 20.1 15.0 19.3111 11100 12900 3.61 4.61 16.6 21.2 15.9 20.2 15.2 19.4112 11200 13000 3.66 4.64 16.8 21.3 16.1 20.4 15.4 19.5113 11300 13100 3.71 4.67 17.0 21.4 16.3 20.5 15.6 19.7114 11400 13200 3.76 4.70 17.3 21.6 16.5 20.6 15.8 19.8115 11500 13400 3.81 4.77 17.5 21.9 16.7 20.9 16.0 20.1116 11600 13500 3.87 4.80 17.8 22.0 17.0 21.1 16.3 20.2117 11700 13600 3.92 4.83 18.0 22.2 17.2 21.2 16.5 20.3118 11800 13700 3.97 4.86 18.2 22.3 17.4 21.3 16.7 20.5119 11900 13800 4.03 4.89 18.5 22.5 17.7 21.5 17.0 20.6120 12000 13900 4.08 4.92 18.7 22.6 17.9 21.6 17.2 20.7121 12100 14100 4.14 4.99 19.0 22.9 18.2 21.9 17.4 21.0122 12200 14200 4.19 5.02 19.2 23.0 18.4 22.0 17.6 21.1123 12300 14300 4.25 5.05 19.5 23.2 18.7 22.2 17.9 21.3124 12400 14400 4.30 5.08 19.7 23.3 18.9 22.3 18.1 21.4125 12500 14500 4.36 5.11 20.0 23.5 19.1 22.4 18.4 21.5126 12600 14600 4.42 5.14 20.3 23.6 19.4 22.6 18.6 21.6127 12700 14700 4.48 5.17 20.6 23.7 19.7 22.7 18.9 21.8128 12800 14900 4.54 5.24 20.8 24.1 19.9 23.0 19.1 22.1129 12900 15000 4.60 5.27 21.1 24.2 20.2 23.1 19.4 22.2130 13000 15100 4.66 5.30 21.4 24.3 20.5 23.3 19.6 22.3131 13100 15200 4.72 5.33 21.7 24.5 20.7 23.4 19.9 22.4132 13200 15300 4.78 5.36 21.9 24.6 21.0 23.5 20.1 22.6133 13300 15400 4.84 5.39 22.2 24.7 21.3 23.7 20.4 22.7134 13400 15600 4.91 5.45 22.5 25.0 21.6 23.9 20.7 22.9135 13500 15700 4.97 5.48 22.8 25.2 21.8 24.1 20.9 23.1136 13600 15800 5.03 5.51 23.1 25.3 22.1 24.2 21.2 23.2137 13700 15900 5.10 5.54 23.4 25.4 22.4 24.3 21.5 23.3138 13800 16000 5.16 5.57 23.7 25.6 22.7 24.5 21.7 23.4139 13900 16100 5.23 5.60 24.0 25.7 23.0 24.6 22.0 23.6140 14000 16300 5.33 5.64 24.5 25.9 23.4 24.8 22.4 23.7141 14100 18000 5.40 6.23 24.8 28.6 23.7 27.4 22.7 26.2142 14200 18000 5.48 6.22 25.2 28.6 24.1 27.3 23.1 26.2143 14300 18000 5.55 6.21 25.5 28.5 24.4 27.3 23.4 26.1144 14400 18000 5.63 6.20 25.8 28.5 24.7 27.2 23.7 26.1145 14500 18000 5.71 6.19 26.2 28.4 25.1 27.2 24.0 26.1146 14600 18000 5.79 6.18 26.6 28.4 25.4 27.1 24.4 26.0147 14700 18000 5.88 6.18 27.0 28.4 25.8 27.1 24.7 26.0

5 / 12

Page 74: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160VA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/220V Current(A)/230V Current(A)/240VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

148 14800 18000 5.96 6.17 27.4 28.3 26.2 27.1 25.1 26.0149 14900 18000 6.04 6.16 27.7 28.3 26.5 27.1 25.4 25.9150 15000 18000 6.15 6.16 28.2 28.3 27.0 27.1 25.9 25.9151 15100 18000 6.19 6.16 28.4 28.3 27.2 27.1 26.1 25.9152 15200 18000 6.23 6.16 28.6 28.3 27.4 27.1 26.2 25.9153 15300 18000 6.27 6.16 28.8 28.3 27.5 27.1 26.4 25.9154 15400 18000 6.31 6.16 29.0 28.3 27.7 27.1 26.6 25.9155 15500 18000 6.37 6.17 29.2 28.3 28.0 27.1 26.8 26.0156 15500 18000 6.32 6.14 29.0 28.2 27.8 27.0 26.6 25.8157 15500 18000 6.28 6.10 28.8 28.0 27.6 26.8 26.4 25.7158 15500 18000 6.23 6.06 28.6 27.8 27.4 26.6 26.2 25.5159 15500 18000 6.18 6.02 28.4 27.6 27.1 26.4 26.0 25.3160 15500 18000 6.14 5.98 28.2 27.5 27.0 26.3 25.8 25.2161 15500 18000 6.09 5.94 28.0 27.3 26.7 26.1 25.6 25.0162 15500 18000 6.05 5.91 27.8 27.1 26.6 26.0 25.5 24.9163 15500 18000 6.00 5.87 27.5 27.0 26.4 25.8 25.3 24.7164 15500 18000 5.96 5.83 27.4 26.8 26.2 25.6 25.1 24.5165 15500 18000 5.91 5.80 27.1 26.6 26.0 25.5 24.9 24.4166 15500 18000 5.87 5.76 27.0 26.4 25.8 25.3 24.7 24.2167 15500 18000 5.83 5.73 26.8 26.3 25.6 25.2 24.5 24.1168 15500 18000 5.79 5.69 26.6 26.1 25.4 25.0 24.4 23.9169 15500 18000 5.75 5.66 26.4 26.0 25.3 24.9 24.2 23.8170 15500 18000 5.71 5.63 26.2 25.8 25.1 24.7 24.0 23.7171 15500 18000 5.67 5.59 26.0 25.7 24.9 24.5 23.9 23.5172 15500 18000 5.63 5.56 25.8 25.5 24.7 24.4 23.7 23.4173 15500 18000 5.59 5.53 25.7 25.4 24.5 24.3 23.5 23.3174 15500 18000 5.55 5.50 25.5 25.3 24.4 24.2 23.4 23.1175 15500 18000 5.52 5.47 25.3 25.1 24.2 24.0 23.2 23.0176 15500 18000 5.48 5.43 25.2 24.9 24.1 23.8 23.1 22.9177 15500 18000 5.44 5.40 25.0 24.8 23.9 23.7 22.9 22.7178 15500 18000 5.41 5.37 24.8 24.7 23.8 23.6 22.8 22.6179 15500 18000 5.37 5.34 24.7 24.5 23.6 23.5 22.6 22.5180 15500 18000 5.34 5.31 24.5 24.4 23.5 23.3 22.5 22.3181 15500 18000 5.30 5.28 24.3 24.2 23.3 23.2 22.3 22.2182 15500 18000 5.27 5.26 24.2 24.2 23.1 23.1 22.2 22.1183 15500 18000 5.23 5.23 24.0 24.0 23.0 23.0 22.0 22.0184 15500 18000 5.20 5.20 23.9 23.9 22.8 22.8 21.9 21.9185 15500 18000 5.17 5.17 23.7 23.7 22.7 22.7 21.8 21.8186 15500 18000 5.14 5.14 23.6 23.6 22.6 22.6 21.6 21.6187 15500 18000 5.10 5.11 23.4 23.5 22.4 22.4 21.5 21.5188 15500 18000 5.07 5.09 23.3 23.4 22.3 22.4 21.3 21.4189 15500 18000 5.04 5.06 23.1 23.2 22.1 22.2 21.2 21.3190 15500 18000 5.01 5.03 23.0 23.1 22.0 22.1 21.1 21.2191 15500 18000 4.98 5.01 22.9 23.0 21.9 22.0 21.0 21.1192 15500 18000 4.95 4.98 22.7 22.9 21.7 21.9 20.8 21.0193 15500 18000 4.92 4.95 22.6 22.7 21.6 21.7 20.7 20.8194 15500 18000 4.89 4.93 22.5 22.6 21.5 21.7 20.6 20.7195 15500 18000 4.86 4.90 22.3 22.5 21.3 21.5 20.5 20.6196 15500 18000 4.83 4.88 22.2 22.4 21.2 21.4 20.3 20.5197 15500 18000 4.81 4.85 22.1 22.3 21.1 21.3 20.2 20.4198 15500 18000 4.78 4.83 21.9 22.2 21.0 21.2 20.1 20.3199 15500 18000 4.75 4.80 21.8 22.0 20.9 21.1 20.0 20.2200 15500 18000 4.71 4.77 21.7 21.9 20.7 21.0 19.9 20.1201 15500 18000 4.70 4.76 21.6 21.9 20.6 20.9 19.8 20.0202 15500 18000 4.67 4.73 21.4 21.7 20.5 20.8 19.7 19.9

6 / 12

Page 75: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating15 1500 1700 0.80 0.58 1.2 0.9 1.2 0.8 1.1 0.816 1600 1800 0.84 0.62 1.3 1.0 1.2 0.9 1.2 0.917 1700 1900 0.87 0.65 1.3 1.0 1.3 0.9 1.2 0.918 1800 2100 0.91 0.72 1.4 1.1 1.3 1.0 1.3 1.019 1900 2200 0.95 0.76 1.5 1.2 1.4 1.1 1.3 1.120 2000 2300 0.98 0.79 1.5 1.2 1.4 1.2 1.4 1.121 2100 2400 1.02 0.82 1.6 1.3 1.5 1.2 1.4 1.222 2200 2500 1.05 0.86 1.6 1.3 1.5 1.3 1.5 1.223 2300 2600 1.08 0.89 1.7 1.4 1.6 1.3 1.5 1.324 2400 2700 1.11 0.93 1.7 1.4 1.6 1.4 1.6 1.325 2500 2900 1.14 1.00 1.7 1.5 1.7 1.5 1.6 1.426 2600 3000 1.17 1.03 1.8 1.6 1.7 1.5 1.6 1.427 2700 3100 1.20 1.06 1.8 1.6 1.7 1.5 1.7 1.528 2800 3200 1.23 1.10 1.9 1.7 1.8 1.6 1.7 1.529 2900 3300 1.26 1.13 1.9 1.7 1.8 1.6 1.8 1.630 3000 3400 1.28 1.17 2.0 1.8 1.9 1.7 1.8 1.631 3100 3500 1.31 1.20 2.0 1.8 1.9 1.7 1.8 1.732 3200 3700 1.33 1.27 2.0 1.9 1.9 1.9 1.9 1.833 3300 3800 1.36 1.31 2.1 2.0 2.0 1.9 1.9 1.834 3400 3900 1.38 1.34 2.1 2.1 2.0 2.0 1.9 1.935 3500 4000 1.41 1.37 2.2 2.1 2.1 2.0 2.0 1.936 3600 4100 1.43 1.41 2.2 2.2 2.1 2.1 2.0 2.037 3700 4200 1.45 1.44 2.2 2.2 2.1 2.1 2.0 2.038 3800 4300 1.47 1.48 2.3 2.3 2.1 2.2 2.1 2.139 3900 4500 1.49 1.55 2.3 2.4 2.2 2.3 2.1 2.240 4000 4600 1.51 1.58 2.3 2.4 2.2 2.3 2.1 2.241 4100 4700 1.53 1.61 2.3 2.5 2.2 2.3 2.2 2.342 4200 4800 1.55 1.65 2.4 2.5 2.3 2.4 2.2 2.343 4300 4900 1.57 1.68 2.4 2.6 2.3 2.4 2.2 2.444 4400 5000 1.59 1.72 2.4 2.6 2.3 2.5 2.2 2.445 4500 5100 1.61 1.75 2.5 2.7 2.3 2.6 2.3 2.546 4600 5300 1.63 1.82 2.5 2.8 2.4 2.7 2.3 2.647 4700 5400 1.65 1.86 2.5 2.9 2.4 2.7 2.3 2.648 4800 5500 1.66 1.89 2.5 2.9 2.4 2.8 2.3 2.749 4900 5600 1.68 1.92 2.6 2.9 2.4 2.8 2.4 2.750 5000 5700 1.70 1.96 2.6 3.0 2.5 2.9 2.4 2.851 5100 5800 1.73 2.00 2.7 3.1 2.5 2.9 2.4 2.852 5200 5900 1.76 2.03 2.7 3.1 2.6 3.0 2.5 2.953 5300 6100 1.79 2.10 2.7 3.2 2.6 3.1 2.5 3.054 5400 6200 1.82 2.14 2.8 3.3 2.7 3.1 2.6 3.055 5500 6300 1.85 2.18 2.8 3.3 2.7 3.2 2.6 3.156 5600 6400 1.88 2.21 2.9 3.4 2.7 3.2 2.6 3.157 5700 6500 1.91 2.25 2.9 3.5 2.8 3.3 2.7 3.258 5800 6600 1.94 2.29 3.0 3.5 2.8 3.3 2.7 3.259 5900 6700 1.97 2.32 3.0 3.6 2.9 3.4 2.8 3.360 6000 6900 2.00 2.40 3.1 3.7 2.9 3.5 2.8 3.461 6100 7000 2.03 2.43 3.1 3.7 3.0 3.5 2.9 3.462 6200 7100 2.06 2.47 3.2 3.8 3.0 3.6 2.9 3.563 6300 7200 2.08 2.51 3.2 3.9 3.0 3.7 2.9 3.564 6400 7300 2.11 2.54 3.2 3.9 3.1 3.7 3.0 3.665 6500 7400 2.14 2.58 3.3 4.0 3.1 3.8 3.0 3.666 6600 7500 2.17 2.62 3.3 4.0 3.2 3.8 3.0 3.767 6700 7700 2.20 2.69 3.4 4.1 3.2 3.9 3.1 3.868 6800 7800 2.23 2.73 3.4 4.2 3.3 4.0 3.1 3.869 6900 7900 2.26 2.77 3.5 4.3 3.3 4.0 3.2 3.970 7000 8000 2.29 2.81 3.5 4.3 3.3 4.1 3.2 3.971 7100 8100 2.31 2.84 3.5 4.4 3.4 4.1 3.2 4.072 7200 8200 2.34 2.88 3.6 4.4 3.4 4.2 3.3 4.073 7300 8300 2.37 2.92 3.6 4.5 3.5 4.3 3.3 4.174 7400 8500 2.40 2.99 3.7 4.6 3.5 4.4 3.4 4.275 7500 8600 2.43 3.03 3.7 4.7 3.5 4.4 3.4 4.376 7600 8700 2.45 3.07 3.8 4.7 3.6 4.5 3.4 4.377 7700 8800 2.48 3.11 3.8 4.8 3.6 4.5 3.5 4.478 7800 8900 2.51 3.15 3.9 4.8 3.7 4.6 3.5 4.479 7900 9000 2.54 3.19 3.9 4.9 3.7 4.7 3.6 4.5

Before calculating the sum of total capacity of indoor units, please convert the value into the kW model capacityfollowing the formula on "4-1-2. Method of obtaining the heating and cooling capacity of an indoor unit:".

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

7 / 12

Page 76: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

80 8000 9100 2.56 3.22 3.9 4.9 3.7 4.7 3.6 4.581 8100 9300 2.59 3.30 4.0 5.1 3.8 4.8 3.6 4.682 8200 9400 2.62 3.34 4.0 5.1 3.8 4.9 3.7 4.783 8300 9500 2.65 3.38 4.1 5.2 3.9 4.9 3.7 4.784 8400 9600 2.67 3.42 4.1 5.2 3.9 5.0 3.8 4.885 8500 9700 2.70 3.45 4.1 5.3 3.9 5.0 3.8 4.886 8600 9800 2.73 3.49 4.2 5.4 4.0 5.1 3.8 4.987 8700 9900 2.75 3.53 4.2 5.4 4.0 5.1 3.9 5.088 8800 10100 2.78 3.61 4.3 5.5 4.1 5.3 3.9 5.189 8900 10200 2.81 3.65 4.3 5.6 4.1 5.3 3.9 5.190 9000 10300 2.83 3.69 4.3 5.7 4.1 5.4 4.0 5.291 9100 10400 2.86 3.73 4.4 5.7 4.2 5.4 4.0 5.292 9200 10500 2.88 3.77 4.4 5.8 4.2 5.5 4.0 5.393 9300 10600 2.91 3.81 4.5 5.8 4.2 5.6 4.1 5.494 9400 10700 2.94 3.85 4.5 5.9 4.3 5.6 4.1 5.495 9500 10900 2.96 3.92 4.5 6.0 4.3 5.7 4.2 5.596 9600 11000 2.99 3.96 4.6 6.1 4.4 5.8 4.2 5.697 9700 11100 3.01 4.00 4.6 6.1 4.4 5.8 4.2 5.698 9800 11200 3.04 4.04 4.7 6.2 4.4 5.9 4.3 5.799 9900 11300 3.06 4.08 4.7 6.3 4.5 5.9 4.3 5.7100 10000 11400 3.09 4.12 4.7 6.3 4.5 6.0 4.3 5.8101 10100 11500 3.13 4.15 4.8 6.4 4.6 6.1 4.4 5.8102 10200 11700 3.18 4.22 4.9 6.5 4.6 6.2 4.5 5.9103 10300 11800 3.23 4.25 5.0 6.5 4.7 6.2 4.5 6.0104 10400 11900 3.27 4.28 5.0 6.6 4.8 6.2 4.6 6.0105 10500 12000 3.32 4.32 5.1 6.6 4.8 6.3 4.7 6.1106 10600 12100 3.37 4.35 5.2 6.7 4.9 6.3 4.7 6.1107 10700 12200 3.41 4.38 5.2 6.7 5.0 6.4 4.8 6.2108 10800 12300 3.46 4.41 5.3 6.8 5.0 6.4 4.9 6.2109 10900 12500 3.51 4.48 5.4 6.9 5.1 6.5 4.9 6.3110 11000 12600 3.56 4.51 5.5 6.9 5.2 6.6 5.0 6.3111 11100 12700 3.61 4.54 5.5 7.0 5.3 6.6 5.1 6.4112 11200 12800 3.66 4.57 5.6 7.0 5.3 6.7 5.1 6.4113 11300 12900 3.71 4.60 5.7 7.1 5.4 6.7 5.2 6.5114 11400 13000 3.76 4.63 5.8 7.1 5.5 6.8 5.3 6.5115 11500 13100 3.81 4.66 5.8 7.2 5.6 6.8 5.4 6.5116 11600 13300 3.87 4.73 5.9 7.3 5.6 6.9 5.4 6.6117 11700 13400 3.92 4.76 6.0 7.3 5.7 6.9 5.5 6.7118 11800 13500 3.97 4.79 6.1 7.4 5.8 7.0 5.6 6.7119 11900 13600 4.03 4.82 6.2 7.4 5.9 7.0 5.7 6.8120 12000 13700 4.08 4.85 6.3 7.4 5.9 7.1 5.7 6.8121 12100 13800 4.14 4.88 6.4 7.5 6.0 7.1 5.8 6.9122 12200 13900 4.19 4.91 6.4 7.5 6.1 7.2 5.9 6.9123 12300 14100 4.25 4.98 6.5 7.6 6.2 7.3 6.0 7.0124 12400 14200 4.30 5.01 6.6 7.7 6.3 7.3 6.0 7.0125 12500 14300 4.36 5.04 6.7 7.7 6.4 7.3 6.1 7.1126 12600 14400 4.42 5.07 6.8 7.8 6.4 7.4 6.2 7.1127 12700 14500 4.48 5.10 6.9 7.8 6.5 7.4 6.3 7.2128 12800 14600 4.54 5.13 7.0 7.9 6.6 7.5 6.4 7.2129 12900 14700 4.60 5.16 7.1 7.9 6.7 7.5 6.5 7.3130 13000 14900 4.66 5.23 7.2 8.0 6.8 7.6 6.5 7.3131 13100 15000 4.72 5.26 7.2 8.1 6.9 7.7 6.6 7.4132 13200 15100 4.78 5.29 7.3 8.1 7.0 7.7 6.7 7.4133 13300 15200 4.84 5.32 7.4 8.2 7.1 7.8 6.8 7.5134 13400 15300 4.91 5.35 7.5 8.2 7.2 7.8 6.9 7.5135 13500 15400 4.97 5.38 7.6 8.3 7.2 7.8 7.0 7.6136 13600 15500 5.01 5.37 7.7 8.2 7.3 7.8 7.0 7.5137 13700 15700 5.05 5.40 7.8 8.3 7.4 7.9 7.1 7.6138 13800 15800 5.09 5.40 7.8 8.3 7.4 7.9 7.2 7.6139 13900 15900 5.14 5.39 7.9 8.3 7.5 7.9 7.2 7.6140 14000 16000 5.18 5.38 7.9 8.3 7.6 7.8 7.3 7.6141 14000 16000 5.18 5.34 7.9 8.2 7.6 7.8 7.3 7.5142 14000 16000 5.19 5.31 8.0 8.1 7.6 7.7 7.3 7.5143 14000 16000 5.19 5.27 8.0 8.1 7.6 7.7 7.3 7.4144 14000 16000 5.20 5.23 8.0 8.0 7.6 7.6 7.3 7.3145 14000 16000 5.20 5.19 8.0 8.0 7.6 7.6 7.3 7.3146 14000 16000 5.21 5.16 8.0 7.9 7.6 7.5 7.3 7.3147 14000 16000 5.21 5.12 8.0 7.9 7.6 7.5 7.3 7.2

8 / 12

Page 77: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B140YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

148 14000 16000 5.22 5.09 8.0 7.8 7.6 7.4 7.3 7.2149 14000 16000 5.22 5.05 8.0 7.8 7.6 7.4 7.3 7.1150 14000 16000 5.22 5.01 8.0 7.7 7.6 7.3 7.3 7.0151 14000 16000 5.15 4.96 7.9 7.6 7.5 7.2 7.2 7.0152 14000 16000 5.08 4.90 7.8 7.5 7.4 7.1 7.1 6.9153 14000 16000 5.01 4.85 7.7 7.4 7.3 7.1 7.0 6.8154 14000 16000 4.95 4.80 7.6 7.4 7.2 7.0 7.0 6.7155 14000 16000 4.89 4.74 7.5 7.3 7.1 6.9 6.9 6.7156 14000 16000 4.82 4.69 7.4 7.2 7.0 6.8 6.8 6.6157 14000 16000 4.76 4.64 7.3 7.1 6.9 6.8 6.7 6.5158 14000 16000 4.71 4.60 7.2 7.1 6.9 6.7 6.6 6.5159 14000 16000 4.65 4.55 7.1 7.0 6.8 6.6 6.5 6.4160 14000 16000 4.59 4.50 7.0 6.9 6.7 6.6 6.5 6.3161 14000 16000 4.54 4.46 7.0 6.8 6.6 6.5 6.4 6.3162 14000 16000 4.49 4.41 6.9 6.8 6.5 6.4 6.3 6.2163 14000 16000 4.43 4.37 6.8 6.7 6.5 6.4 6.2 6.1164 14000 16000 4.38 4.33 6.7 6.6 6.4 6.3 6.2 6.1165 14000 16000 4.33 4.28 6.6 6.6 6.3 6.2 6.1 6.0166 14000 16000 4.28 4.24 6.6 6.5 6.2 6.2 6.0 6.0167 14000 16000 4.24 4.20 6.5 6.4 6.2 6.1 6.0 5.9168 14000 16000 4.19 4.16 6.4 6.4 6.1 6.1 5.9 5.8169 14000 16000 4.14 4.12 6.4 6.3 6.0 6.0 5.8 5.8170 14000 16000 4.10 4.09 6.3 6.3 6.0 6.0 5.8 5.7171 14000 16000 4.06 4.05 6.2 6.2 5.9 5.9 5.7 5.7172 14000 16000 4.01 4.01 6.2 6.2 5.8 5.8 5.6 5.6173 14000 16000 3.97 3.98 6.1 6.1 5.8 5.8 5.6 5.6174 14000 16000 3.93 3.94 6.0 6.0 5.7 5.7 5.5 5.5175 14000 16000 3.89 3.91 6.0 6.0 5.7 5.7 5.5 5.5176 14000 16000 3.86 3.87 5.9 5.9 5.6 5.6 5.4 5.4177 14000 16000 3.81 3.84 5.8 5.9 5.6 5.6 5.4 5.4178 14000 16000 3.78 3.80 5.8 5.8 5.5 5.5 5.3 5.3179 14000 16000 3.74 3.77 5.7 5.8 5.5 5.5 5.3 5.3180 14000 16000 3.70 3.74 5.7 5.7 5.4 5.5 5.2 5.3181 14000 16000 3.67 3.71 5.6 5.7 5.4 5.4 5.2 5.2182 14000 16000 3.63 3.68 5.6 5.6 5.3 5.4 5.1 5.2183 14000 16000 3.60 3.65 5.5 5.6 5.2 5.3 5.1 5.1184 14000 16000 3.57 3.62 5.5 5.6 5.2 5.3 5.0 5.1185 14000 16000 3.53 3.59 5.4 5.5 5.1 5.2 5.0 5.0

9 / 12

Page 78: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating15 1500 1700 0.80 0.58 1.2 0.9 1.2 0.8 1.1 0.816 1600 1900 0.84 0.65 1.3 1.0 1.2 0.9 1.2 0.917 1700 2000 0.87 0.69 1.3 1.1 1.3 1.0 1.2 1.018 1800 2100 0.91 0.72 1.4 1.1 1.3 1.0 1.3 1.019 1900 2200 0.95 0.76 1.5 1.2 1.4 1.1 1.3 1.120 2000 2300 0.98 0.79 1.5 1.2 1.4 1.2 1.4 1.121 2100 2400 1.02 0.82 1.6 1.3 1.5 1.2 1.4 1.222 2200 2600 1.05 0.89 1.6 1.4 1.5 1.3 1.5 1.323 2300 2700 1.08 0.93 1.7 1.4 1.6 1.4 1.5 1.324 2400 2800 1.11 0.96 1.7 1.5 1.6 1.4 1.6 1.325 2500 2900 1.14 1.00 1.7 1.5 1.7 1.5 1.6 1.426 2600 3000 1.17 1.03 1.8 1.6 1.7 1.5 1.6 1.427 2700 3100 1.20 1.06 1.8 1.6 1.7 1.5 1.7 1.528 2800 3300 1.23 1.13 1.9 1.7 1.8 1.6 1.7 1.629 2900 3400 1.26 1.17 1.9 1.8 1.8 1.7 1.8 1.630 3000 3500 1.28 1.20 2.0 1.8 1.9 1.7 1.8 1.731 3100 3600 1.31 1.24 2.0 1.9 1.9 1.8 1.8 1.732 3200 3700 1.33 1.27 2.0 1.9 1.9 1.9 1.9 1.833 3300 3800 1.36 1.31 2.1 2.0 2.0 1.9 1.9 1.834 3400 3900 1.38 1.34 2.1 2.1 2.0 2.0 1.9 1.935 3500 4100 1.41 1.41 2.2 2.2 2.1 2.1 2.0 2.036 3600 4200 1.43 1.44 2.2 2.2 2.1 2.1 2.0 2.037 3700 4300 1.45 1.48 2.2 2.3 2.1 2.2 2.0 2.138 3800 4400 1.47 1.51 2.3 2.3 2.1 2.2 2.1 2.139 3900 4500 1.49 1.55 2.3 2.4 2.2 2.3 2.1 2.240 4000 4600 1.51 1.58 2.3 2.4 2.2 2.3 2.1 2.241 4100 4800 1.53 1.65 2.3 2.5 2.2 2.4 2.2 2.342 4200 4900 1.55 1.68 2.4 2.6 2.3 2.4 2.2 2.443 4300 5000 1.57 1.72 2.4 2.6 2.3 2.5 2.2 2.444 4400 5100 1.59 1.75 2.4 2.7 2.3 2.6 2.2 2.545 4500 5200 1.61 1.79 2.5 2.7 2.3 2.6 2.3 2.546 4600 5300 1.63 1.82 2.5 2.8 2.4 2.7 2.3 2.647 4700 5500 1.65 1.89 2.5 2.9 2.4 2.8 2.3 2.748 4800 5600 1.66 1.92 2.5 2.9 2.4 2.8 2.3 2.749 4900 5700 1.68 1.96 2.6 3.0 2.4 2.9 2.4 2.850 5000 5800 1.70 1.99 2.6 3.1 2.5 2.9 2.4 2.851 5100 5900 1.73 2.03 2.7 3.1 2.5 3.0 2.4 2.952 5200 6000 1.76 2.07 2.7 3.2 2.6 3.0 2.5 2.953 5300 6200 1.79 2.14 2.7 3.3 2.6 3.1 2.5 3.054 5400 6300 1.82 2.17 2.8 3.3 2.7 3.2 2.6 3.055 5500 6400 1.85 2.21 2.8 3.4 2.7 3.2 2.6 3.156 5600 6500 1.88 2.25 2.9 3.5 2.7 3.3 2.6 3.257 5700 6600 1.91 2.28 2.9 3.5 2.8 3.3 2.7 3.258 5800 6700 1.94 2.32 3.0 3.6 2.8 3.4 2.7 3.359 5900 6900 1.97 2.39 3.0 3.7 2.9 3.5 2.8 3.460 6000 7000 2.00 2.43 3.1 3.7 2.9 3.5 2.8 3.461 6100 7100 2.03 2.47 3.1 3.8 3.0 3.6 2.9 3.562 6200 7200 2.06 2.50 3.2 3.8 3.0 3.6 2.9 3.563 6300 7300 2.08 2.54 3.2 3.9 3.0 3.7 2.9 3.664 6400 7400 2.11 2.58 3.2 4.0 3.1 3.8 3.0 3.665 6500 7500 2.14 2.62 3.3 4.0 3.1 3.8 3.0 3.766 6600 7700 2.17 2.69 3.3 4.1 3.2 3.9 3.0 3.867 6700 7800 2.20 2.73 3.4 4.2 3.2 4.0 3.1 3.868 6800 7900 2.23 2.77 3.4 4.3 3.3 4.0 3.1 3.969 6900 8000 2.26 2.80 3.5 4.3 3.3 4.1 3.2 3.970 7000 8100 2.29 2.84 3.5 4.4 3.3 4.1 3.2 4.071 7100 8200 2.31 2.88 3.5 4.4 3.4 4.2 3.2 4.072 7200 8400 2.34 2.95 3.6 4.5 3.4 4.3 3.3 4.173 7300 8500 2.37 2.99 3.6 4.6 3.5 4.4 3.3 4.274 7400 8600 2.40 3.03 3.7 4.7 3.5 4.4 3.4 4.375 7500 8700 2.43 3.07 3.7 4.7 3.5 4.5 3.4 4.376 7600 8800 2.45 3.11 3.8 4.8 3.6 4.5 3.4 4.477 7700 8900 2.48 3.14 3.8 4.8 3.6 4.6 3.5 4.478 7800 9100 2.51 3.22 3.9 4.9 3.7 4.7 3.5 4.579 7900 9200 2.54 3.26 3.9 5.0 3.7 4.8 3.6 4.6

Before calculating the sum of total capacity of indoor units, please convert the value into the kW model capacityfollowing the formula on "4-1-2. Method of obtaining the heating and cooling capacity of an indoor unit:".

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

10 / 12

Page 79: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

80 8000 9300 2.56 3.30 3.9 5.1 3.7 4.8 3.6 4.681 8100 9400 2.59 3.33 4.0 5.1 3.8 4.9 3.6 4.782 8200 9500 2.62 3.37 4.0 5.2 3.8 4.9 3.7 4.783 8300 9600 2.65 3.41 4.1 5.2 3.9 5.0 3.7 4.884 8400 9800 2.67 3.49 4.1 5.4 3.9 5.1 3.8 4.985 8500 9900 2.70 3.53 4.1 5.4 3.9 5.1 3.8 5.086 8600 10000 2.73 3.57 4.2 5.5 4.0 5.2 3.8 5.087 8700 10100 2.75 3.60 4.2 5.5 4.0 5.2 3.9 5.188 8800 10200 2.78 3.64 4.3 5.6 4.1 5.3 3.9 5.189 8900 10300 2.81 3.68 4.3 5.6 4.1 5.4 3.9 5.290 9000 10500 2.83 3.76 4.3 5.8 4.1 5.5 4.0 5.391 9100 10600 2.86 3.80 4.4 5.8 4.2 5.5 4.0 5.392 9200 10700 2.88 3.84 4.4 5.9 4.2 5.6 4.0 5.493 9300 10800 2.91 3.88 4.5 6.0 4.2 5.7 4.1 5.594 9400 10900 2.94 3.92 4.5 6.0 4.3 5.7 4.1 5.595 9500 11000 2.96 3.96 4.5 6.1 4.3 5.8 4.2 5.696 9600 11100 2.99 4.00 4.6 6.1 4.4 5.8 4.2 5.697 9700 11300 3.01 4.08 4.6 6.3 4.4 5.9 4.2 5.798 9800 11400 3.04 4.12 4.7 6.3 4.4 6.0 4.3 5.899 9900 11500 3.06 4.16 4.7 6.4 4.5 6.1 4.3 5.8100 10000 11600 3.09 4.19 4.7 6.4 4.5 6.1 4.3 5.9101 10100 11700 3.13 4.22 4.8 6.5 4.6 6.2 4.4 5.9102 10200 11800 3.18 4.26 4.9 6.5 4.6 6.2 4.5 6.0103 10300 12000 3.23 4.32 5.0 6.6 4.7 6.3 4.5 6.1104 10400 12100 3.27 4.36 5.0 6.7 4.8 6.4 4.6 6.1105 10500 12200 3.32 4.39 5.1 6.7 4.8 6.4 4.7 6.2106 10600 12300 3.37 4.42 5.2 6.8 4.9 6.4 4.7 6.2107 10700 12400 3.41 4.45 5.2 6.8 5.0 6.5 4.8 6.3108 10800 12500 3.46 4.48 5.3 6.9 5.0 6.5 4.9 6.3109 10900 12700 3.51 4.55 5.4 7.0 5.1 6.6 4.9 6.4110 11000 12800 3.56 4.58 5.5 7.0 5.2 6.7 5.0 6.4111 11100 12900 3.61 4.61 5.5 7.1 5.3 6.7 5.1 6.5112 11200 13000 3.66 4.64 5.6 7.1 5.3 6.8 5.1 6.5113 11300 13100 3.71 4.67 5.7 7.2 5.4 6.8 5.2 6.6114 11400 13200 3.76 4.70 5.8 7.2 5.5 6.9 5.3 6.6115 11500 13400 3.81 4.77 5.8 7.3 5.6 7.0 5.4 6.7116 11600 13500 3.87 4.80 5.9 7.4 5.6 7.0 5.4 6.7117 11700 13600 3.92 4.83 6.0 7.4 5.7 7.0 5.5 6.8118 11800 13700 3.97 4.86 6.1 7.5 5.8 7.1 5.6 6.8119 11900 13800 4.03 4.89 6.2 7.5 5.9 7.1 5.7 6.9120 12000 13900 4.08 4.92 6.3 7.6 5.9 7.2 5.7 6.9121 12100 14100 4.14 4.99 6.4 7.7 6.0 7.3 5.8 7.0122 12200 14200 4.19 5.02 6.4 7.7 6.1 7.3 5.9 7.1123 12300 14300 4.25 5.05 6.5 7.8 6.2 7.4 6.0 7.1124 12400 14400 4.30 5.08 6.6 7.8 6.3 7.4 6.0 7.1125 12500 14500 4.36 5.11 6.7 7.8 6.4 7.5 6.1 7.2126 12600 14600 4.42 5.14 6.8 7.9 6.4 7.5 6.2 7.2127 12700 14700 4.48 5.17 6.9 7.9 6.5 7.5 6.3 7.3128 12800 14900 4.54 5.24 7.0 8.0 6.6 7.6 6.4 7.4129 12900 15000 4.60 5.27 7.1 8.1 6.7 7.7 6.5 7.4130 13000 15100 4.66 5.30 7.2 8.1 6.8 7.7 6.5 7.4131 13100 15200 4.72 5.33 7.2 8.2 6.9 7.8 6.6 7.5132 13200 15300 4.78 5.36 7.3 8.2 7.0 7.8 6.7 7.5133 13300 15400 4.84 5.39 7.4 8.3 7.1 7.9 6.8 7.6134 13400 15600 4.91 5.45 7.5 8.4 7.2 7.9 6.9 7.7135 13500 15700 4.97 5.48 7.6 8.4 7.2 8.0 7.0 7.7136 13600 15800 5.03 5.51 7.7 8.5 7.3 8.0 7.1 7.7137 13700 15900 5.10 5.54 7.8 8.5 7.4 8.1 7.2 7.8138 13800 16000 5.16 5.57 7.9 8.5 7.5 8.1 7.3 7.8139 13900 16100 5.23 5.60 8.0 8.6 7.6 8.2 7.3 7.9140 14000 16300 5.33 5.64 8.2 8.7 7.8 8.2 7.5 7.9141 14100 18000 5.40 6.23 8.3 9.6 7.9 9.1 7.6 8.8142 14200 18000 5.48 6.22 8.4 9.5 8.0 9.1 7.7 8.7143 14300 18000 5.55 6.21 8.5 9.5 8.1 9.1 7.8 8.7144 14400 18000 5.63 6.20 8.6 9.5 8.2 9.0 7.9 8.7145 14500 18000 5.71 6.19 8.8 9.5 8.3 9.0 8.0 8.7146 14600 18000 5.79 6.18 8.9 9.5 8.4 9.0 8.1 8.7147 14700 18000 5.88 6.18 9.0 9.5 8.6 9.0 8.3 8.7

11 / 12

Page 80: utilized TECHNICAL & SERVICE MANUALR410A [Service Ref ... tecnico aire... · Connectable indoor unit lineup (Heat pump inverter type)  The lineup of a connectable indoor

MXZ-8B160YA

Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating

Current(A)/380V Current(A)/400V Current(A)/415VTotal capacity ofindoor unit

Capacity (W) Power Consumption (kW)

148 14800 18000 5.96 6.17 9.1 9.5 8.7 9.0 8.4 8.7149 14900 18000 6.04 6.16 9.3 9.5 8.8 9.0 8.5 8.7150 15000 18000 6.15 6.16 9.4 9.5 9.0 9.0 8.6 8.7151 15100 18000 6.19 6.16 9.5 9.5 9.0 9.0 8.7 8.7152 15200 18000 6.23 6.16 9.6 9.5 9.1 9.0 8.8 8.7153 15300 18000 6.27 6.16 9.6 9.5 9.1 9.0 8.8 8.7154 15400 18000 6.31 6.16 9.7 9.5 9.2 9.0 8.9 8.7155 15500 18000 6.37 6.17 9.8 9.5 9.3 9.0 9.0 8.7156 15500 18000 6.32 6.14 9.7 9.4 9.2 9.0 8.9 8.6157 15500 18000 6.28 6.10 9.6 9.4 9.2 8.9 8.8 8.6158 15500 18000 6.23 6.06 9.6 9.3 9.1 8.8 8.8 8.5159 15500 18000 6.18 6.02 9.5 9.2 9.0 8.8 8.7 8.5160 15500 18000 6.14 5.98 9.4 9.2 9.0 8.7 8.6 8.4161 15500 18000 6.09 5.94 9.3 9.1 8.9 8.7 8.6 8.3162 15500 18000 6.05 5.91 9.3 9.1 8.8 8.6 8.5 8.3163 15500 18000 6.00 5.87 9.2 9.0 8.7 8.6 8.4 8.2164 15500 18000 5.96 5.83 9.1 8.9 8.7 8.5 8.4 8.2165 15500 18000 5.91 5.80 9.1 8.9 8.6 8.5 8.3 8.2166 15500 18000 5.87 5.76 9.0 8.8 8.6 8.4 8.2 8.1167 15500 18000 5.83 5.73 8.9 8.8 8.5 8.4 8.2 8.1168 15500 18000 5.79 5.69 8.9 8.7 8.4 8.3 8.1 8.0169 15500 18000 5.75 5.66 8.8 8.7 8.4 8.3 8.1 8.0170 15500 18000 5.71 5.63 8.8 8.6 8.3 8.2 8.0 7.9171 15500 18000 5.67 5.59 8.7 8.6 8.3 8.1 8.0 7.9172 15500 18000 5.63 5.56 8.6 8.5 8.2 8.1 7.9 7.8173 15500 18000 5.59 5.53 8.6 8.5 8.1 8.1 7.9 7.8174 15500 18000 5.55 5.50 8.5 8.4 8.1 8.0 7.8 7.7175 15500 18000 5.52 5.47 8.5 8.4 8.0 8.0 7.8 7.7176 15500 18000 5.48 5.43 8.4 8.3 8.0 7.9 7.7 7.6177 15500 18000 5.44 5.40 8.3 8.3 7.9 7.9 7.6 7.6178 15500 18000 5.41 5.37 8.3 8.2 7.9 7.8 7.6 7.5179 15500 18000 5.37 5.34 8.2 8.2 7.8 7.8 7.5 7.5180 15500 18000 5.34 5.31 8.2 8.1 7.8 7.7 7.5 7.5181 15500 18000 5.30 5.28 8.1 8.1 7.7 7.7 7.4 7.4182 15500 18000 5.27 5.26 8.1 8.1 7.7 7.7 7.4 7.4183 15500 18000 5.23 5.23 8.0 8.0 7.6 7.6 7.3 7.3184 15500 18000 5.20 5.20 8.0 8.0 7.6 7.6 7.3 7.3185 15500 18000 5.17 5.17 7.9 7.9 7.5 7.5 7.3 7.3186 15500 18000 5.14 5.14 7.9 7.9 7.5 7.5 7.2 7.2187 15500 18000 5.10 5.11 7.8 7.8 7.4 7.5 7.2 7.2188 15500 18000 5.07 5.09 7.8 7.8 7.4 7.4 7.1 7.2189 15500 18000 5.04 5.06 7.7 7.8 7.3 7.4 7.1 7.1190 15500 18000 5.01 5.03 7.7 7.7 7.3 7.3 7.0 7.1191 15500 18000 4.98 5.01 7.6 7.7 7.3 7.3 7.0 7.0192 15500 18000 4.95 4.98 7.6 7.6 7.2 7.3 7.0 7.0193 15500 18000 4.92 4.95 7.6 7.6 7.2 7.2 6.9 7.0194 15500 18000 4.89 4.93 7.5 7.6 7.1 7.2 6.9 6.9195 15500 18000 4.86 4.90 7.5 7.5 7.1 7.1 6.8 6.9196 15500 18000 4.83 4.88 7.4 7.5 7.0 7.1 6.8 6.9197 15500 18000 4.81 4.85 7.4 7.4 7.0 7.1 6.8 6.8198 15500 18000 4.78 4.83 7.3 7.4 7.0 7.0 6.7 6.8199 15500 18000 4.75 4.80 7.3 7.4 6.9 7.0 6.7 6.7200 15500 18000 4.71 4.77 7.2 7.3 6.9 7.0 6.6 6.7201 15500 18000 4.70 4.76 7.2 7.3 6.9 6.9 6.6 6.7202 15500 18000 4.67 4.73 7.2 7.3 6.8 6.9 6.6 6.6

12 / 12