User’sManual EJX110A, EJX120A, EJX130A,

EJX310A, EJX430A, and EJX440ADifferential Pressure andPressure Transmitters

IM 01C25B01-01E

IM 01C25B01-01E10th Edition

Page 2: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

i

IM 01C25B01-01E

EJX110A, EJX120A, EJX130A,EJX310A, EJX430A, and EJX440ADifferential Pressure and Pressure Transmitters

IM 01C25B01-01E 10th Edition

10th Edition: Apr. 2010 (YK)All Rights Reserved, Copyright © 2004, Yokogawa Electric Corporation

Contents1. Introduction ............................................................................................... 1-1

Regarding This Manual ................................................................................................1-11.1 Safe Use of This Product .................................................................................1-21.2 Warranty .............................................................................................................1-31.3 ATEX Documentation .......................................................................................1-4

2. Handling Cautions .................................................................................... 2-12.1 ModelandSpecificationsCheck .....................................................................2-12.2 Unpacking ..........................................................................................................2-12.3 Storage ...............................................................................................................2-12.4 Selecting the Installation Location ................................................................2-22.5 Pressure Connection ........................................................................................2-22.6 WaterproofingofCableConduitConnections .............................................. 2-22.7 Restrictions on Use of Radio Transceivers ................................................... 2-22.8 Insulation Resistance and Dielectric Strength Test ...................................... 2-22.9 Installation of an Explosion-Protected Instrument ....................................... 2-3

2.9.1 FM Approval .......................................................................................2-3

2.9.2 CSACertification ................................................................................2-5

2.9.3 CENELECATEX(KEMA)Certification .............................................. 2-7

2.9.4 IECExCertification ...........................................................................2-10

2.10 EMC Conformity Standards ........................................................................... 2-112.11 Pressure Equipment Directive (PED) ........................................................... 2-112.12 Low Voltage Directive .....................................................................................2-12

3. Component Names .................................................................................. 3-14. Installation ................................................................................................. 4-1

4.1 Precautions .......................................................................................................4-14.2 Mounting ...........................................................................................................4-14.3 Changing the Process Connection .................................................................4-24.4 Swapping the High/Low-pressure Side Connection ..................................... 4-3

4.4.1 Rotating Pressure-detector Section 180° ......................................... 4-3

4.4.2 Using the Communicator ...................................................................4-3

4.5 Rotating Transmitter Section ...........................................................................4-44.6 Changing the Direction of Integral Indicator ................................................. 4-4

Page 3: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

ii

IM 01C25B01-01E

5. Installing Impulse Piping ......................................................................... 5-15.1 Impulse Piping Installation Precautions ........................................................ 5-1

5.1.1 Connecting Impulse Piping to a Transmitter ...................................... 5-1

5.1.2 Routing the Impulse Piping ................................................................5-3

5.2 Impulse Piping Connection Examples ...........................................................5-4

6. Wiring ......................................................................................................... 6-16.1 Wiring Precautions ...........................................................................................6-16.2 Selecting the Wiring Materials .........................................................................6-16.3 Connections of External Wiring to Terminal Box .......................................... 6-1

6.3.1 Power Supply Wiring Connection ......................................................6-1

6.3.2 External Indicator Connection............................................................6-1

6.3.3 Communicator Connection ................................................................6-1

6.3.4 Check Meter Connection ...................................................................6-2

6.3.5 Status Output Connection ..................................................................6-2

6.4 Wiring .................................................................................................................6-26.4.1 LoopConfiguration ............................................................................6-2

6.4.2 Wiring Installation ...............................................................................6-2

6.5 Grounding ..........................................................................................................6-36.6 Power Supply Voltage and Load Resistance ................................................. 6-3

7. Operation ................................................................................................... 7-17.1 Preparation for Starting Operation .................................................................7-17.2 Zero Point Adjustment .....................................................................................7-2

7.2.1 Adjusting Zero Point for Differential Pressure Transmitters .............. 7-3

7.2.2 Adjusting Zero Point for Gauge/Absolute Pressure Transmitters .... 7-3

7.3 Starting Operation ............................................................................................7-37.4 Shutting Down the Transmitter .......................................................................7-47.5 Venting or Draining Transmitter Pressure-detector Section ....................... 7-4

7.5.1 Draining Condensate .........................................................................7-4

7.5.2 Venting Gas........................................................................................7-5

7.6 Setting the Range Using the Range-setting Switch ...................................... 7-5

8. Maintenance .............................................................................................. 8-18.1 Overview ............................................................................................................8-18.2 CalibrationInstrumentsSelection ..................................................................8-18.3 Calibration .........................................................................................................8-18.4 DisassemblyandReassembly ........................................................................8-3

8.4.1 Replacing the Integral Indicator .........................................................8-3

8.4.2 Replacing the CPU Board Assembly ................................................. 8-4

8.4.3 Cleaning and Replacing the Capsule Assembly ............................... 8-4

8.4.4 Replacing the Process Connector Gaskets ....................................... 8-6

Page 4: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

iii

IM 01C25B01-01E

8.5 Troubleshooting ................................................................................................8-68.5.1 Basic Troubleshooting .......................................................................8-6

8.5.2 Troubleshooting Flowcharts ...............................................................8-7

8.5.3 Alarms and Countermeasures ...........................................................8-9

9. GeneralSpecifications ............................................................................ 9-19.1 StandardSpecifications ...................................................................................9-19.2 ModelandSuffixCodes ...................................................................................9-59.3 OptionalSpecifications .................................................................................9-129.4 Dimensions ......................................................................................................9-15

Revision Information

When using the EJX in a Safety Instrumented Systems(SIS) application, refer to Appendix A in either IM 01C25T01-01E for the HART protocol or IM 01C25T03-01E for the BRAIN protocol.

Page 5: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<1. Introduction> 1-1

IM 01C25B01-01E

1. IntroductionThank you for purchasing the DPharp EJX Differential Pressure and pressure transmitter.

Your EJX Pressure Transmitter was precisely calibrated at the factory before shipment. To ensure bothsafetyandefficiency,pleasereadthismanualcarefully before you operate the instrument.

NOTEThis manual describes the hardware configurationsofEJXseriestransmitters.Forinformationonthesoftwareconfigurationandoperation, please refer to either IM 01C25T03-01E for the EJX series BRAIN communication type or IM 01C25T01-01E for the EJX series HART communication type.

For FOUNDATION Fieldbus protocol type, please refer to IM 01C25T02-01E.

To ensure correct use of this instrument, read both the hardware and software manuals thoroughly before use.

WARNING

When using the EJX in a Safety Instrumented Systems (SIS) application, refer to Appendix A in either IM 01C25T01-01E for the HART protocol or IM 01C25T03-01E for the BRAIN protocol. The instructions and procedures in this section must be strictly followed in order to maintain the transmitter for this safety level.

NOTEThis manual covers the EJX110A, EJX120A and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A absolute pressure transmitter whose style codes are as described in the following table. Unless otherwise stated, the illustrations in this manual are of the EJX110A differential pressure transmitter. Users of the other models should bear in mind that certain features of their instrument will differ from those shown in the illustrations of the EJX110A.

Model Style codeEJX110A S3EJX120A S1EJX130A S2EJX310A S2EJX430A S2EJX440A S2

Regarding This Manual• This manual should be provided to the end

user.

• The contents of this manual are subject to change without prior notice.

• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.

• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitnessforaparticularpurpose.

• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.

• Thespecificationscoveredbythismanualarelimited to those for the standard type under the specifiedmodelnumberbreak-downanddonotcover custom-made instruments.

• Pleasenotethatchangesinthespecifications,construction, or component parts of the instrumentmaynotimmediatelybereflectedin this manual at the time of change, provided that postponement of revisions will not cause difficultytotheuserfromafunctionalorperformance standpoint.

• Yokogawa assumes no responsibilities for this product except as stated in the warranty.

• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.

• The following safety symbols are used in this manual:

Page 6: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<1. Introduction> 1-2

IM 01C25B01-01E

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTIONIndicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

IMPORTANTIndicates that operating the hardware or software in this manner may damage it or lead to system failure.

NOTEDraws attention to information essential for understanding the operation and features.

Direct current

1.1 Safe Use of This Product For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:

(a) Installation

• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.

• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.

• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process fluids.

• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and thecontactoftoxicprocessfluidswiththeskinor eyes.

• When removing the instrument from a hazardousprocess,avoidcontactwiththefluidand the interior of the meter.

• All installation shall comply with local installation requirements and the local electrical code.

(b) Wiring

• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.

• Before connecting the power cables, please confirmthatthereisnocurrentflowingthroughthe cables and that the power supply to the instrument is switched off.

Page 7: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<1. Introduction> 1-3

IM 01C25B01-01E

(c) Operation

• Wait 5 min. after the power is turned off, before opening the covers.

(d) Maintenance

• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearestYokogawaoffice.

• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.

(e) Explosion Protected Type Instrument

• Users of explosion proof instruments should referfirsttosection2.9(InstallationofanExplosion Protected Instrument) of this manual.

• The use of this instrument is restricted to those who have received appropriate training in the device.

• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.

(f) Modification

• Yokogawa will not be liable for malfunctions or damageresultingfromanymodificationmadeto this instrument by the customer.

1.2 Warranty• The warranty shall cover the period noted on

the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.

• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawaoffice.

• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed,includingthemodelspecificationand serial number. Any diagrams, data and other information you can include in your communication will also be helpful.

• Thepartyresponsibleforthecostoffixingtheproblem shall be determined by Yokogawa following an investigation conducted by Yokogawa.

• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:

- Improper and/or inadequate maintenance by the purchaser.

- Malfunction or damage due to a failure to handle, use, or store the instrument in accordancewiththedesignspecifications.

- Use of the product in question in a location notconformingtothestandardsspecifiedbyYokogawa, or due to improper maintenance of the installation location.

- Failureordamageduetomodificationorrepair by any party except Yokogawa or an approved representative of Yokogawa.

- Malfunction or damage from improper relocation of the product in question after delivery.

- Reasonofforcemajeuresuchasfires,earthquakes,storms/floods,thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.

Page 8: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<1. Introduction> 1-4

IM 01C25B01-01E

1.3 ATEX DocumentationThis is only applicable to the countries in European Union.

GB

DK

I

E

NL

SF

P

F

D

S

LT

LV

PL

EST

SLO

H

BG

RO

M

CZ

SK

GR

Page 9: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-1

IM 01C25B01-01E

2. Handling CautionsThis chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter.

EJX Series transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.

Also check that all transmitter mounting hardware showninfigure2.1isincluded.Ifthetransmitteris ordered without the mounting bracket and the process connector, the transmitter mounting hardware will not be included. After checking the transmitter, carefully repack it in its box and keep it there until you are ready to install it.

BoltProcess connector (Note 1)

Process connectorGasket

U-bolt nut

U-bolt

Mounting bracket(L type)

Transmitter mounting bolt

Mounting bracket(Flat type)

F0201.ai

Figure 2.1 Transmitter Mounting Hardware

2.1 ModelandSpecificationsCheck

Themodelnameandspecificationsarewrittenonthe name plate attached to the case.

F0202.ai

Figure 2.2 Name Plate (EJX110A)

2.2 UnpackingKeep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installation site.

2.3 StorageThe following precautions must be observed when storing the instrument, especially for a long period.

(a) Select a storage area which meets the following conditions:• It is not exposed to rain or subject to water

seepage/leaks.• Vibration and shock are kept to a minimum.• It has an ambient temperature and relative

humidity within the following ranges.

Ambient temperature: –40* to 85°C without integral indicator –30* to 80°C with integral indicator

*–15°Cwhen/HEisspecified.Relative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx. 25°C and 65% R.H.

(b) When storing the transmitter, repack it carefully in the packaging that it was originally shipped with.

(c) If the transmitter has been used, thoroughly cleanthechambersinsidethecoverflanges,sothatthereisnoprocessfluidremaininginside.Before placing it in storage, also make sure that the pressure-detector is securely connected to the transmitter section.

Page 10: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-2

IM 01C25B01-01E

2.4 Selecting the Installation Location

The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.

(a) Ambient TemperatureAvoid locations subject to wide temperature variationsorasignificanttemperaturegradient.If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation.

(b) Ambient AtmosphereDo not install the transmitter in a corrosive atmosphere. If this cannot be avoided, there must be adequate ventilation as well as measures to prevent the leaking of rain water and the presence of standing water in the conduits.

(c) Shock and VibrationAlthough the transmitter is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.

(d) Installation of Explosion-protected TransmittersAn explosion-protected transmitters is certifiedforinstallationinahazardousareacontainingspecificgastypes.Seesubsection2.9 “Installation of an Explosion-Protected Transmitters.”

2.5 Pressure Connection

WARNING

• Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled releaseofprocessfluid.

• Whendrainingtoxicprocessfluidsthathavecondensed inside the pressure detector, take appropriate steps to prevent the contact ofsuchfluidswiththeskinoreyesandtheinhalationofvaporsfromthesefluids.

The following precautions must be observed in order to safely operate the transmitter under pressure.

(a) Make sure that all the process connector bolts aretightenedfirmly.

(b) Make sure that there are no leaks in the impulse piping.

(c) Never apply a pressure higher than the specifiedmaximumworkingpressure.

2.6 WaterproofingofCableConduit Connections

Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections.(Seefigure6.8,6.9and6.10.)

2.7 Restrictions on Use of Radio Transceivers

IMPORTANTAlthough the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the transceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside therangewherethenoiseeffectswerefirstobserved.

2.8 Insulation Resistance and Dielectric Strength Test

Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:

(a) Do not perform such tests more frequently than is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.

Page 11: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-3

IM 01C25B01-01E

(b) Never apply a voltage exceeding 500 V DC (100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.

(c) Before conducting these tests, disconnect all signal lines from the transmitter terminals. The procedure for conducting these tests is as follows:

• Insulation Resistance Test

1) Short-circuit the + and – SUPPLY terminals in the terminal box.

2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (–) leadwire to the grounding terminal.

3) Turn ON the insulation tester power and measure the insulation resistance. The voltage shouldbeappliedasbrieflyaspossibletoverifythattheinsulationresistanceisatleast20MΩ.

4) After completing the test and being very careful not to touch exposed conductors disconnect the insulationtesterandconnecta100kΩresistorbetween the grounding terminal and the short-circuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.

• Dielectric Strength Test

1) Short-circuit the + and – SUPPLY terminals in the terminal box.

2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.

3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to thespecifiedvoltage.

4)Whenthespecifiedvoltageisreached,holditfor one minute.

5) After completing this test, slowly decrease the voltage to avoid any voltage surges.

2.9 Installation of an Explosion-Protected Instrument

NOTEFor FOUNDATION Fieldbus explosion protected type, please refer to IM 01C22T02-01E.

Ifacustomermakesarepairormodificationtoan intrinsically safe or explosionproof instrument and the instrument is not restored to its original condition, its intrinsically safe or explosionproof construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modificationtoaninstrument.

CAUTIONThisinstrumenthasbeentestedandcertifiedas being intrinsically safe or explosionproof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.

WARNING

Maintaining the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair. Please read the following sections very carefully.

WARNING

The range setting switch must not be used in a hazardous area.

2.9.1 FM Approval

a. FM Intrinsically Safe Type

Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM022-A12”)

Page 12: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-4

IM 01C25B01-01E

Note 1. Model EJX Series Differential, gauge and absolute pressure transmitters with optional code /FS1 are applicable for use in hazardous locations.

• Applicable Standard: FM3600, FM3610, FM3611, FM3810

• Intrinsically Safe for Class I, Division 1, Groups A, B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0 in Hazardous Locations, AEx ia IIC

• Nonincendive for Class I, Division 2, Groups A, B, C & D. Class II, Division 2, Groups F & G and Class III, Division 1, Class I, Zone 2, Groups IIC, in Hazardous Locations.

• Outdoor hazardous locations, NEMA 4X.• Temperature Class: T4• Ambient temperature: –60* to 60°C

*–15°Cwhen/HEisspecified.

Note 2. Entity Parameters• Intrinsically Safe Apparatus Parameters [Groups A, B, C, D, E, F and G]

Vmax = 30 V Ci = 6 nFImax = 200 mA Li = 0 µHPmax = 1 W

* Associated Apparatus Parameters (FM approved barriers)

Voc≤30V Ca > 6 nFIsc≤200mA La > 0 µHPmax≤1W

• Intrinsically Safe Apparatus Parameters [Groups C, D, E, F and G]

Vmax = 30 V Ci = 6 nFImax = 225 mA Li = 0 µHPmax = 1 W

* Associated Apparatus Parameters (FM approved barriers)

Voc≤30V Ca > 6 nFIsc≤225mA La > 0 µHPmax≤1W

• Entity Installation Requirements Vmax≥VocorUoorVt,Imax≥IscorIoorIt, Pmax(orPo)≤Pi,CaorCo≥Ci+Ccable, LaorLo≥Li+Lcable

Note 3. Installation• Barrier must be installed in an enclosure that

meets the requirements of ANSI/ISA S82.01.• Control equipment connected to barrier must

not use or generate more than 250 V rms or V dc.

• Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically SafeSystemsforHazardous(Classified)Locations” and the National Electric Code (ANSI/NFPA 70).

• Theconfigurationofassociatedapparatusmust be FMRC Approved.

• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.

• Associated apparatus manufacturer’s installation drawing must be followed when installing this apparatus.

• The maximum power delivered from the barrier must not exceed 1 W.

• Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. No. IFM022-A12”

Note 4. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Intrinsically safe and Nonincendive Approval.

F0203-1.ai

Class I, II, III, Division 1,Groups A, B, C, D, E, F, GClass 1, Zone 0 in Hazardous (Classified) Locations AEx ia IICEJX Series Pressure Transmitters Safety Barrier

Supply

Hazardous Location Nonhazardous Location

GeneralPurposeEquipment

+

+

+

+

[Intrinsically Safe]

F0203-2.ai

EJX Series Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

Class I, II, Division 2,Groups A, B, C, D, F, GClass III, Division 1.Class 1, Zone 2, Group IIC,in Hazardous (Classified)Locations

Not UseSafety Barrier

[Nonincendive]

GeneralPurposeEquipment

Page 13: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-5

IM 01C25B01-01E

b. FMExplosionproofType

Caution for FM explosionproof type.

Note 1. Model EJX Series pressure transmitters with optional code /FF1 are applicable for use in hazardous locations.

• Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250

• Explosionproof for Class I, Division 1, Groups B, C and D.

• Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.

• Enclosure rating: NEMA 4X.• Temperature Class: T6• Ambient Temperature: –40* to 60°C

*–15°Cwhen/HEisspecified.• Supply Voltage: 42 V dc max.• Output signal: 4 to 20 mA

Note 2. Wiring• All wiring shall comply with National Electrical

Code ANSI/NFPA70 and Local Electrical Codes.

• When installed in Division 1, “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”

Note 3. Operation• Keep the “WARNING” nameplate attached to

the transmitter. WARNING: OPEN CIRCUIT BEFORE

REMOVING COVER. FACTORY SEALED, CONDUIT SEAL NOT REQUIRED. INSTALL IN ACCORDANCE WITH THE USERS MANUAL IM 01C25.

• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.

Note 4. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.

c. FM Intrinsically Safe Type/FM Explosionproof Type

Model EJX Series pressure transmitters with optional code /FU1 or /V1U can be selected the type of protection (FM Intrinsically Safe or FM Explosionproof) for use in hazardous locations.

Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.

Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

2.9.2 CSACertification

a. CSA Intrinsically Safe Type

Caution for CSA Intrinsically safe and nonincendive type. (Following contents refer to “DOC No. ICS013-A13”)

Note 1. Model EJX Series differential, gauge, and absolute pressure transmitters with optional code /CS1 are applicable for use in hazardous locations

Certificate:1606623[For CSA C22.2]• Applicable Standard: C22.2 No.0, C22.2

No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.1010.1

• Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1

• Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups E, F & G, Class III, Division 1

• Enclosure: Type 4X • Temp. Code: T4• Amb. Temp.:–50* to 60°C

*–15°Cwhen/HEisspecified.• Process Temperature: 120°C max.[For CSA E60079]• Applicable Standard: CAN/CSA E60079-0,

CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529:2001-02

• Ex ia IIC T4, Ex nL IIC T4 • Ambient Temperature: –50* to 60°C

*–15°Cwhen/HEisspecified.• Max. Process Temp.: 120°C• Enclosure: IP66 and IP67

Note 2. Entity Parameters• Intrinsically safe ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH

Page 14: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-6

IM 01C25B01-01E

• Type "n" or Nonincendive ratings are as follows:

Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH• Installation Requirements Uo≤Ui,Io≤Ii,Po≤Pi, Co≥Ci+Ccable,Lo≥Li+Lcable Voc≤Vmax,Isc≤Imax, Ca≥Ci+Ccable,La≥Li+Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are

parameters of barrier.

Note 3. Installation• In any safety barreir used output current

must be limited by a resistor 'R' such that Io=Uo/R or Isc=Voc/R.

• ThesafetybarriermustbeCSAcertified.• Input voltage of the safety barrier must be

less than 250 Vrms/Vdc.• Installation should be in accordance with

Canadian Electrical Code Part I and Local Electrical Code.

• Dust-tight conduit seal must be used when installed in Class II and III environments.

• Theinstrumentmodificationorpartsreplacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Intrinsically safe and nonincendiveCertification.

F0204-1.ai

Class I, II, III, Division 1,Groups A, B, C, D, E, F, G

EJX Series Pressure Transmitters Safety Barrier

Supply

Hazardous Location Nonhazardous Location

GeneralPurposeEquipment

+

+

+

+

[Intrinsically Safe]

Group IIC, Zone 0

F0204-2.ai

EJX Series Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

Class I, II, Division 2,Groups A, B, C, D, E, F, GClass III, Division 1.

Not UseSafety Barrier

[Nonincendive]

CSA Certified Equipment([nL] or nonincendive)

EJX Series Pressure Transmitters

Group IIC, Zone 2

b. CSAExplosionproofType

Caution for CSA explosionproof type.

Note 1. Model EJX Series pressure transmitters with optional code /CF1 are applicable for use in hazardous locations:

• Certificate:2014354• Applicable Standard: C22.2 No.0,

C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.61010-1-04, C22.2 No.60079-0, C22.2 No.60079-1

• Explosion-proof for Class I, Groups B, C and D.

• Dustignition-proof for Class II/III, Groups E, F and G.

• Enclosure: TYPE 4X• Temperature Code: T6...T4• Ex d IIC T6...T4 • Enclosure: IP66 and IP67• Maximum Process Temperature: 120°C (T4),

100°C (T5), 85°C (T6)• Ambient Temperature: –50* to 75°C (T4),

–50* to 80°C (T5), –50* to 75°C (T6)*–15°Cwhen/HEisspecified.

• Supply Voltage: 42 V dc max.• Output Signal: 4 to 20 mA dc

Note 2. Wiring• All wiring shall comply with Canadian

Electrical Code Part I and Local Electrical Codes.

• In hazardous location, wiring shall be in conduitasshowninthefigure.

• WARNING: A SEAL SHALL BE INSTALLED WITHIN

50cm OF THE ENCLOSURE. UN SCELLEMENT DOIT ÊTRE INSTALLÉ À

MOINS DE 50cm DU BOÎTIER.• WARNING: WHEN INSTALLED IN CL.I, DIV 2, SEAL

NOT REQUIRED. UNE FOIS INSTALLÉ DANS CL I, DIV 2,

AUCUN JOINT N'EST REQUIS.

Non-hazardousLocationEquipment

42 V DC Max. 4 to 20 mA DC Signal

Non-HazardousLocations

Hazardous Locations Division 1

50 cm Max.

Sealing FittingConduit

SUPPLY

PULS

E

CHECKALARM

EJX SeriesF0205-1.ai

Page 15: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-7

IM 01C25B01-01E

Non-HazardousLocations

Hazardous Locations Division 2

Non-hazardousLocationEquipment

42 V DC Max. 4 to 20 mA DC Signal

Sealing Fitting

SUPPLY

PULS

E

CHECKALARM

EJX SeriesF0205-2.ai

• All wiring shall comply with local installation requirements and local electrical code.

• In hazardous locations, the cable entry devicesshallbeofacertifiedflameprooftype, suitable for the conditions of use and correctly installed.

• Unused apertures shall be closed with suitableflameproofcertifiedblankingelements.(Theplugattachedisflameproofcertified.)

Note 3. Operation• WARNING: AFTER DE-ENERGIZING, DELAY 5

MINUTES BEFORE OPENING. APRÉS POWER-OFF, ATTENDRE 5

MINUTES AVANT D'OUVRIR.• WARNING: WHENAMBIENTTEMPERATURE≥65°C,USETHEHEAT-RESISTINGCABLES≥90°C.

QUAND LA TEMPÉRATURE AMBIANTE ≥65°C,UTILISEZDESCÂBLESRÉSISTANTESÁLACHALEUR≥90°C.

• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.

Note 4. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian StandardsExplosionproofCertification.

c CSA Intrinsically Safe Type/CSA Explosionproof Type

Model EJX Series pressure transmitters with optional code /CU1 or /V1U can be selected the type of protection (CSA Intrinsically Safe or CSA Explosionproof) for use in hazardous locations.

Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.

Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

2.9.3 CENELEC ATEX (KEMA) Certification

(1) Technical Data

a. CENELEC ATEX (KEMA) Intrinsically Safe Type

Caution for CENELEC ATEX (KEMA) Intrinsically safe type.

Note 1. Model EJX Series pressure transmitters with optional code /KS2 for potentially explosive atmospheres:

• No. KEMA 03ATEX1544 X• Applicable Standard:

EN 50014:1997, EN 50020:2002, EN 50284:1999, EN 50281-1-1:1998

• Type of Protection and Marking code: EEx ia IIC T4

• Group: II• Category: 1GD• Ambient Temperature for gas-proof:

–50* to 60°C*–15°Cwhen/HEisspecified.

• Process Temperature (Tp.): 120°C max.• Maximum Surface Temperature for dust-

proof: T85°C (Tamb.: –40* to 60°C, Tp.: 80°C) T100°C (Tamb.: –40* to 60°C, Tp.: 100°C) T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)*–15°Cwhen/HEisspecified.

• Enclosure: IP66 and IP67

Note 2. Electrical Data• In type of explosion protection intrinsic

safety EEx ia IIC only for connection to a certifiedintrinsicallysafecircuitwithfollowingmaximum values:

Ui = 30 V Ii = 200 mA Pi = 0.9 W Effective internal capacitance; Ci = 10 nF Effective internal inductance; Li = 0 mH

Page 16: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-8

IM 01C25B01-01E

Note 3. Installation• All wiring shall comply with local installation

requirements. (Refer to the installation diagram)

Note 4. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA IntrinsicallysafeCertification.

Note 5. Special Conditions for Safe Use• In the case where the enclosure of the

Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.

Transmitter

Supply Safety Barrier *1

Nonhazardous Location

[Installation Diagram]

Hazardous Location

+

+

F0206.ai

*1: In any safety barriers used the output current must be limited by a resistor “R” such that Imaxout-Uz/R.

WARNING

To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.

b. CENELECATEX(KEMA)FlameproofType

Caution for CENELEC ATEX (KEMA) flameprooftype.

Note 1. Model EJX Series pressure transmitters with optional code /KF21 for potentially explosive atmospheres:

• No. KEMA 07ATEX0109• Applicable Standard: EN 60079-0:2006,

EN 60079-1:2004, EN 61241-0:2006, EN 61241-1:2004

• Type of Protection and Marking Code: Ex d IIC T6...T4, Ex tD A21 IP6x T85, T100, T120

• Group: II• Category: 2G, 2D• Enclosure: IP66 and IP67

• Temperature Class for gas-poof: T6, T5, and T4

• Ambient Temperature for gas-proof: –50* to 75°C (T6), –50* to 80°C (T5), and –50* to 75°C (T4)*–15°Cwhen/HEisspecified.

• Maximum Process Temperature (Tp.) for gas-proof:

85°C (T6), 100°C (T5), and 120°C (T4)• Maximum Surface Temperature for dust-

proof: T85°C (Tamb.: –40* to 40°C, Tp.: 80°C) T100°C (Tamb.: –40* to 60°C, Tp.: 100°C) T120°C (Tamb.: –40* to 80°C, Tp.: 120°C)*–15°Cwhen/HEisspecified.

Note 2. Electrical Data• Supply voltage: 42 V dc max.• Output signal: 4 to 20 mA

Note 3. Installation• All wiring shall comply with local installation

requirement.• Thecableentrydevicesshallbeofacertifiedflameprooftype,suitablefortheconditionsofuse.

Note 4. Operation• Keep the “WARNING” label attached to the

transmitter. WARNING: AFTER DE-ENERGIZING,

DELAY 5 MINUTES BEFORE OPENING. WHENTHEAMBIENTTEMP.≥65°C,USEHEAT-RESISTING CABLES≥90°C.

• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.

Note 5. Maintenance and Repair• Theinstrumentmodificationorpart

replacement by other than an authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA FlameproofCertification.

WARNING

To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.

Page 17: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-9

IM 01C25B01-01E

c. CENELEC ATEX (KEMA) Intrinsically Safe Type/CENELEC ATEX (KEMA) Flameproof Type/CENELEC ATEX Type n

Model EJX Series pressure transmitters with optional code /KU21 or /V1U can be selected the type of protection CENELEC ATEX (KEMA) Intrinsically Safe, Flameproof or CENELEC ATEX Type n for use in hazardous locations.

Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this user’s manual.

Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

CENELEC ATEX Type of Protection “n”

• Applicable Standard: EN 60079-15• Referential Standards: IEC60079-0,

IEC 60079-11• Type of Protection and Marking Code:

Ex nL IIC T4• Temperature Class: T4• Enclosure: IP66 and IP67• Process Temperature: 120°C max.• Ambient Temperature: –50* to 60°C

*–15°Cwhen/HEisspecified.

Note 1. Electrical Data Ui = 30 V Effective internal capacitance; Ci = 10 nF Effective internal inductance; Li = 0 mH

Note 2. Installation• All wiring shall comply with local installation

requirements. (refer to the installation diagram)

Note 3. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Type of Protection “n”.

[Ex nL]Power Supply

(Zone 2 only)Transmitter

Supply

Nonhazardous Location

[Installation Diagram]

Hazardous Location

+

+

F0207.ai

Ratings of the Power Supply as follows; Maximum Voltage: 30 V

(2) Electrical Connection

A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as followed.

F0208.ai

Location of the mark

Screw Size Marking

ISO M20 × 1.5 female

ANSI 1/2 NPT female

M

A or W

(3) Installation

WARNING

• All wiring shall comply with local installation requirements and the local electrical code.

• There is no need for conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory.

(4) Operation

WARNING

• OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER’S MANUAL

• Take care not to generate mechanical sparking when access to the instrument and peripheral devices in a hazardous location.

Page 18: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-10

IM 01C25B01-01E

(5) Maintenance and Repair

WARNING

Theinstrumentmodificationorpartsreplacementby other than an authorized Representative of Yokogawa Electric Corporation is prohibited and willvoidthecertification.

(6) Name Plate

Name plate

Tag plate for flameproof type

Tag plate for intrinsically safe type

Tag plate for type n protection

F0209.ai

D

D

AFTER DE-ENERGIZING, DELAY 5 MINUTESBEFORE OPENING. WHEN THE AMBIENT TEMP. ≥ 65°C,USE THE HEAT-RESISTING CABLES ≥ 90°C

No. KEMA 07ATEX0109Ex d IIC T6...T4, Ex tD A21, IP6XEnlcosure : IP66, IP67TEMP. CLASS T6 T5 T4MAX PROCESS TEMP.(Tp.) 85 100 120 °CTamb. -50(-15) to 75 80 75 °C T85°C(Tamb.:40°C, Tp.:80°C),T100°C(Tamb.:60°C, Tp.:100°C), T120°C(Tamb.:80°C, Tp.:120°C) Min.Tamb.:-40(-15)°C(for Dust)

No. KEMA 03ATEX1544 X EEx ia IIC T4IP66 and IP67Tamb. -50(-15) to 60°C MIN. Tamb.:-40(-15)°C(for DUST)MAX. PROCESS TEMP.(Tp.) 120°CT85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)Ui=30V, Ii=200mA , Pi=0.9W, Ci=10nF, Li=0

WARNING

EEx nLIIC T4IP66 and IP67Tamb. -50(-15) to 60°C MAX. PROCESS TEMP.(Tp.) 120°CUi=30V, Ci=10nF, Li=0

MODEL:Specifiedmodelcode.STYLE: Style code.SUFFIX:Specifiedsuffixcode.SUPPLY: Supply voltage.OUTPUT: Output signal. MWP: Maximum working pressure. CALRNG:Specifiedcalibrationrange.NO.: Serial number and year of production*1.TOKYO 180-8750 JAPAN: The manufacturer name and the address*2.

*1:Thefirstdigitinthefinalthreenumbersoftheserialnumber appearing after “NO.” on the nameplate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010:

The year 2010

91K819857 032

*2: “180-8750” is a zip code which represents the following address.

2-9-32 Nakacho, Musashino-shi, Tokyo Japan

2.9.4 IECExCertificationModel EJX Series pressure transmitters with optional code /SU2 can be selected the type of protection (IECEx Intrinsically Safe/type n or flameproof)foruseinhazardouslocations.

Note 1. For the installation of this transmitter, once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.

Note 2. In order to avoid confusion, unnecessary marking is crossed out on the label other than the selected type of protection when the transmitter is installed.

a. IECEx Intrinsically Safe Type / type n

Caution for IECEx Intrinsically safe and type n.

Note 1. Model EJX Series differential, gauge, and absolute pressure transmitters with optional code /SU2 are applicable for use in hazardous locations

• No. IECEx CSA 05.0005• Applicable Standard: IEC 60079-0:2000,

IEC 60079-11:1999, IEC 60079-15:2001 • Ex ia IIC T4, Ex nL IIC T4 • Ambient Temperature: –50* to 60°C

*–15°Cwhen/HEisspecified.• Max. Process Temp.: 120°C• Enclosure: IP66 and IP67

Note 2. Entity Parameters• Intrinsically safe ratings are as follows:

Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH

• Type "n" ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH

• Installation Requirements Uo≤Ui,Io≤Ii,Po≤Pi, Co≥Ci+Ccable,Lo≥Li+Lcable Voc≤Vmax,Isc≤Imax, Ca≥Ci+Ccable,La≥Li+Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of barrier.

Page 19: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-11

IM 01C25B01-01E

Note 3. Installation• In any safety barrier used output current

must be limited by a resistor 'R' such that Io=Uo/R.

• ThesafetybarriermustbeIECExcertified.• Input voltage of the safety barrier must be

less than 250 Vrms/Vdc.• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation and will void IECEx Intrinsically safeandtypencertification.

F0210-1.ai

EJX Series Pressure Transmitters

IECEx certifiedSafety Barrier

Supply

Hazardous Location Nonhazardous Location

General PurposeEquipment

+

+

+

+

[Intrinsically Safe]

Group IIC, Zone 0

F0210-2.ai

EJX Series Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

–Not UseSafety Barrier

[type n]

IECEx Certified Equipment [nL]

EJX Series Pressure Transmitters

Group IIC, Zone 2

b. IECExFlameproofType

CautionforIECExflameprooftype.

Note 1. Model EJX Series pressure transmitters with optional code /SF2 or /SU2 are applicable for use in hazardous locations:

• No. IECEx CSA 07.0008• Applicable Standard: IEC60079-0:2004,

IEC60079-1:2003• Flameproof for Zone 1, Ex d IIC T6...T4• Enclosure: IP66 and IP67• Maximum Process Temperature: 120°C (T4),

100°C (T5), 85°C (T6)• Ambient Temperature: –50* to 75°C (T4),

–50* to 80°C (T5), –50* to 75°C (T6)*–15°Cwhen/HEisspecified.

• Supply Voltage: 42 V dc max.• Output Signal: 4 to 20 mA dc

Note 2. Wiring• In hazardous locations, the cable entry devicesshallbeofacertifiedflameprooftype, suitable for the conditions of use and correctly installed.

• Unused apertures shall be closed with suitableflameproofcertifiedblankingelements.

Note 3. Operation• WARNING:

AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING.

• WARNING: WHENAMBIENTTEMPERATURE≥65°C,USETHEHEAT-RESISTINGCABLES≥90°C.

• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.

Note 4. Maintenance and Repair• Theinstrumentmodificationorparts

replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void IECEx Certification.

2.10 EMC Conformity StandardsEN61326-1 Class A, Table2 (For use in industrial locations)EN61326-2-3

CAUTIONTo meet EMC regulations, Yokogawa recommends that customers run signal wiring through metal conduits or use shielded twisted-pair cabling when installing EJX series transmitters in a plant.

2.11 Pressure Equipment Directive (PED)

(1) General

• EJX Series pressure transmitters are categorized as piping under the pressure accessories section of directive 97/23/EC, which corresponds to Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).

Page 20: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<2. Handling Cautions> 2-12

IM 01C25B01-01E

• EJX110A-MS, EJX110A-HS, EJX110A-VS, EJX130A, EJX440A, EJX510A-D, and EJX530A-D can be used above 200 bar and therefore considered as a part of a pressure retaining vessel where category III, Module H applies. These models with option code /PE3 conform to that category.

(2) Technical Data

• Models without /PE3 Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).

• Models with /PE3 Module: H Type of Equipment: Pressure Accessory-Vessel Typeoffluid:LiquidandGas Groupoffluid:1and2

Model Capsulecode

PS*1

(bar) V(L) PS.V(bar.L) Category*2

EJX110AL 160 0.01 1.6 Article 3,

Paragraph 3(SEP)M, H, V 250 0.01 2.5

EJX110Awith code

/PE3M, H, V 250 0.01 2.5 III

EJX130A M, H 500 0.01 5.0Article 3,

Paragraph 3(SEP)

EJX130Awith code

/PE3M, H 500 0.01 5.0 III

EJX310A L, M, A, B 160 0.01 1.6Article 3,

Paragraph 3(SEP)

EJX430A H, A, B 160 0.01 1.6Article 3,

Paragraph 3(SEP)

EJX440A C, D 500 0.1 5.0Article 3,

Paragraph 3(SEP)

EJX440Awith code

/PE3C, D 500 0.1 5.0 III

EJX510AA, B, C 100 0.1 10 Article 3,

Paragraph 3(SEP)D 700 0.1 70

EJX510Awith code

/PE3D 700 0.1 70 III

EJX530AA, B, C 100 0.1 10 Article 3,

Paragraph 3(SEP)D 700 0.1 70

EJX530Awith code

/PE3D 700 0.1 70 III

*1: PS is maximum pressure for vessel itself based on Pressure Equipment Directive 97/23/EC. Refer to GeneralSpecificationformaximumworkingpressureofatransmitter.

*2: Referred to Table 1 covered by ANNEX II of EC Directive on Pressure Equipment Directive 97/23/EC

(3) Operation

CAUTION• Thetemperatureandpressureoffluidshould

be maintained at levels that are consistent with normal operating conditions.

• The ambient temperature should be maintained at a level that is consistent with normal operating conditions.

• Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS.

• Take appropriate measures at the device or system level to protect transmitters if they are to be operated near an external heat source.

2.12 Low Voltage DirectiveApplicable standard: EN61010-1

(1) Pollution Degree 2

"Pollution degree" describes the degree to which a solid, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condensation must be expected.

(2) Installation Category I

"Overvoltage category (Installation category)" describesanumberwhichdefinesatransientovervoltage condition. It implies the regulation for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means (interfaces) are provided.

Page 21: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<3. Component Names> 3-1

IM 01C25B01-01E

3. Component Names

HIGH LOW

Slide switch

Burnout direction switch

Write protection switch

Burnout DirectionSwitch Position

BO H L

WR E D

H L H L

Burnout direction switch (BO)

Burnout Direction

F0301.ai

Write ProtectionSwitch Position

H L

E D

H L

E D

Write Protection

Hardware write protection switch (WR)

YES(Write disabled)

NO(Write enabled)

Vertical impulse piping type

Pressure-detector section

Cover flange

Terminal box cover

Horizontal impulse piping type

External indicatorconduit connection (Note 1)

Vent plug

Drain plug

Transmitter section

Integralindicator (Note 1)

Mounting screw

Range-settingswitch (Note 1)

(See section 7.6)

Amplifier Cover

CPU assembly

Zero-adjustmentscrew

Conduitconnection

Processconnector (Note 1)

Processconnection

(Note 2)

Note1: Seesubsection9.2,“ModelandSuffixCodes,”fordetails.AprocessconnectorwillnotbeappliedforlowersideofEJX310A,EJX430A, and EJX440A.

Note2: ApplicableforBRAIN/HARTcommunicationtype.Settheswitchesasshowninthefigureabovetosettheburn-outdirectionandwriteprotection.TheBurnoutswitchissettotheHsidefordelivery(unlessoptioncode/C1or/C2isspecifiedintheorder),andthehardwarewriteprotectionswitchissettoEside.Thesettingoftheswitchescanbeconfirmedviacommunication.Anexternal zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating the hardware write protect function. See each communication manual.

Figure 3.1 Component Names

Table3.1 DisplaySymbolDisplay Symbol Meaning of Display Symbol

Display mode is ‘square root’. (Display is not lit when ‘linear’ mode.)The output signal being zero-adjusted is increasing.The output signal being zero-adjusted is decreasing.

F0302.aiWrite protect function is enabled.

Page 22: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<4. Installation> 4-1

IM 01C25B01-01E

4. Installation4.1 Precautions Before installing the transmitter, read the cautionary notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to subsection 9.1 “Standard Specifications.”

IMPORTANT• When welding piping during construction,

take care not to allow welding currents to flowthroughthetransmitter.

• Do not step on this instrument after installation.

• For the EJX430A and EJX440A, the atmospheric opening is located on the low pressuresidecoverflange.Theopeningmust not face upward. See section 9.4, “Dimensions,” for the location of the opening.

4.2 Mounting Thetransmitterisshippedwiththeprocess

connection, according to the ordering specifications.Tochangetheorientationoftheprocess connections, refer to section 4.3.

With differential pressure transmitters, the distance between the impulse piping connectionportsisusually54mm(figure4.1).By changing the orientation of the process connector, the dimension can be changed to 51 mm or 57 mm.

The transmitter can be mounted on a nominal 50 mm (2-inch) pipe using the mounting bracketsupplied,asshowninfigure4.2and4.3 The transmitter can be mounted on either a horizontal or a vertical pipe.

When mounting the bracket on the transmitter, tighten the (four) bolts that hold the transmitter with a torque of approximately 39 N·m 4kgf·m.

57 mm 54 mm 51 mmF0401.ai

Figure 4.1 Process Connector Impulse Piping Connection Distances for Differential Pressure Transmitters

Figure 4.1 and 4.2 shows the mounting of the transmitter for horizontal piping and vertical piping with using the mounting bracket. The transmitters withtheinstallationcode-U(Universalflange)canbe used for either type of mounting.

Horizontal pipe mounting

Vertical pipe mounting

Transmittermounting bolt

U-bolt nut

Mounting bracket

U-bolt nut

Mounting bracket

50 mm(2-inch) pipe

50 mm(2-inch) pipe

U-bolt

U-bolt

F0402.ai

Transmittermounting bolt

Figure 4.2 Transmitter Mounting (Horizontal Impulse Piping Type)

Page 23: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<4. Installation> 4-2

IM 01C25B01-01E

F0403.ai

Vertical pipe mounting(Process connector upside)

Vertical pipe mounting(Process connector downside)

Transmittermounting bolt

Transmittermounting bolt

Mounting bracket

Mounting bracket

U-bolt nut

U-bolt nut

U-bolt

U-bolt

50 mm(2-inch) pipe

50 mm(2-inch) pipe

Figure 4.3 Transmitter Mounting (Vertical Impulse Piping Type)

4.3 Changing the Process Connection

The transmitter is shipped with the process connectionspecifiedatthetimeofordering.Tochange the process connection, the drain (vent) plug must be repositioned.

To reposition a drain (vent) plug, use a wrench to slowly and gently unscrew it. Then, remove and remount it on the opposite side. Wrap sealing tape aroundthedrain(vent)plugthreads(*1inthefigurebelow), and apply a lubricant to the threads of the drain (vent) screw(s) (*2 below). To tighten the drain (vent) plugs, apply a torque of 34 to 39 N·m (3.5 to 4 kgf·m). Process connector bolts are to be tightened uniformly to a torque shown in table 4.1.

Table4.1 Torque

Model

EJX110AEJX120AEJX130AEJX310AEJX430A

EJX440A

C capsule D capsule

Torque(N·m)kgf·m 39 to 49 4 to 5 49 to 59

5 to 6

F0404.ai

*1*2Drain/vent plug Note: For a horizontal impulse

piping type, moving theprocess connectors fromthe front side to theback cannot be made.

Vertical impulse piping type Horizontal impulse piping type

Bolt

Processconnector gasket

Figure 4.4 Changing Process Connection

Page 24: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<4. Installation> 4-3

IM 01C25B01-01E

4.4 Swapping the High/Low-pressure Side Connection

IMPORTANTThis section is applicable only for EJX110A, EJX120A, and EJX130A differential transmitters, and not applicable for gauge or absolute pressure transmitters.

4.4.1 Rotating Pressure-detector Section 180°

This procedure can be applied only to a transmitter with a vertical impulse piping type.

The procedure below can be used to turn the pressure detector assembly 180°. Perform this operation in a maintenance shop with the necessary tools laid out and ready for use, and then installthetransmitterinthefieldaftermakingthechange.

1) Use an Allen wrench (JIS B4648, nominal 2.5 mm) to remove the two setscrews at the joint between the pressure-detector section and transmitter section.

2) Leaving the transmitter section in position, rotate the pressure-detector section 180°.

3)Tightenthetwosetscrewstofixthepressure-detector section and transmitter section together (at a torque of 1.5 N·m).

Reposition the process connector and drain (vent) plugs to the opposite side as described in subsection 4.3.

F0405.ai

Process connector

Setscrew

Before After rotating 180°

Figure4.5 BeforeandAfterModification

4.4.2 Using the CommunicatorThis method is applicable only to the Model EJX110A, EJX120A, and EJX130A.

With a communicator, you can change which process connection is used as the high-pressure side without mechanically rotating the pressure-detector section 180 as described in subsection 4.4.1. To change, call parameter ‘D15: H/L SWAP’ for BRAIN Communication or ‘H/L swap’ for HART Communication and select REVERSE (right side: low pressure; left side: high pressure) or select NORMAL to change back to normal (right side: high pressure; left side: low pressure).

Output

Input

NORMAL

REVERSEF0406.ai

Figure 4.6 Input/Output Relationship

IMPORTANTSince the H/L label plate on the capsule assembly will remain unchanged, use this function only when you cannot switch the impulse piping. If the ‘H/L SWAP’ parameter setting is changed, the input/output relationship isreversedasshowninfigure4.6;besurethisisunderstood by all.

Page 25: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<4. Installation> 4-4

IM 01C25B01-01E

4.5 Rotating Transmitter SectionThe transmitter section can be rotated approximately 360° (180° to either direction or 360° to one direction from the original position at shipment,dependingontheconfigurationoftheinstrument.)Itcanbefixedatanyanglewithinabove range.

1) Remove the two setscrews that fasten the transmitter section and capsule assembly, using the Allen wrench.

2) Rotate the transmitter section slowly and stop it at designated position.

3) Tighten the two setscrews to a torque of 1.5 N·m.

IMPORTANTDo not rotate the transmitter section more than the above limit.

F0407.ai

Vertical impulse piping type

Horizontal impulse piping type

Pressure-detector section

Transmitter section

Rotate 0 to ±180° segments

Rotate 0 to ±180° segments

Transmitter section

Pressure-detector section

Conduit connection

Conduit connectionZero-adjustment screw

Stopper

Figure 4.7 Rotating Transmitter Section (Left Side High Pressure Type)

4.6 Changing the Direction of Integral Indicator

IMPORTANTAlways turn OFF power, release pressure and remove a transmitter to non-hazardous area before disassembling and reassmbling an indicator.

An integral indicator can be installed in the following three directions. Follow the instructions in section 8.4 for removing and attaching the integral indicator.

F0408.ai

Figure 4.8 Integral Indicator Direction

Page 26: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<5. Installing Impulse Piping> 5-1

IM 01C25B01-01E

5. Installing Impulse Piping5.1 Impulse Piping Installation

PrecautionsThe impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects inaliquid-filledimpulseline,orthedrainforagas-filledimpulselinebecomesplugged,itwillnot convey the pressure accurately. Since this will cause errors in the measurement output, select theproperpipingmethodfortheprocessfluid(gas, liquid, or steam). Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to a transmitter.

5.1.1 Connecting Impulse Piping to a Transmitter

(1) ChecktheHighandLowPressureConnections on the Transmitter (Figure 5.1)

Symbols “H” and “L” have been placed on the capsule assembly to indicate high and low pressure side. With differential pressure transmitters, connect the high pressure side impulse line to the “H” side, and the low pressure side impulse line to the “L” side.

With gauge/absolute pressure transmitters, connect the impulse line to the ‘H’ side.

F0501.ai

Pressureconnection

“H” and “L” are shown

Process connection

Process connector

Bolt

Differential Pressure Transmitter

“H” and “L” are shown

Process connection

Process connector

Bolt

Gauge/Absolute Pressure Transmitters

Figure5.1 “H”and“L”SymbolsonaCapsuleAssembly

(2) Changing the Process Connector Piping Connections (Figure 4.1) (for differential pressure transmitters)

The impulse piping connection distances can be changed between 51 mm, 54 mm and 57 mm by changing the orientation of the process connectors. This is convenient for aligning an impulse line with a process connectors.

(3) Tightening the Process Connector Mounting Bolts

After connecting an impulse line, tighten the process connector mounting bolts uniformly.

(4) Removing the Impulse Piping Connecting Port Dustproof Cap

The impulse piping connecting port on the transmitter is covered with a plastic cap to keep out dust. This cap must be removed before connecting the line. (Be careful not to damage the threads when removing this cap. Never insert a screwdriver or other tool between the cap and port threads to remove the cap.)

(5) Connecting the Transmitter and 3-Valve Manifold (for differential pressure transmitters)

A 3-valve manifold consists of two stop valves to block process pressure and an equalizing valve to equalize the pressures on the high and low pressure sides of the transmitter. Such a manifold makes it easier to disconnect the transmitter from the impulse piping, and is convenient when adjusting the transmitter zero point.

There are two 3-valve manifold types: the pipe-mounting type and the direct-mounting type; care should be taken with respect to the following points when connecting the manifold to the transmitter.

Page 27: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<5. Installing Impulse Piping> 5-2

IM 01C25B01-01E

Pipe-Mounting Type 3-Valve Manifold (Figure 5.2)

1) Screw nipples into the connection ports on the transmitter side of the 3-valve manifold, and into the impulse piping connecting ports on the process connectors. (To maintain proper sealing, wind sealing tape around the nipple threads.)

2) Mount the 3-valve manifold on the 50 mm (2-inch) pipe by fastening a U-bolt to its mounting bracket. Tighten the U-bolt nuts only lightly at this time.

3) Install the pipe assemblies between the 3-valve manifold and the process connectors and lightly tighten the ball head lock nuts. (The ball-shaped ends of the pipes must be handled carefully, since they will not seal properly if the ball surface is scratched or otherwise damaged.)

4) Now tighten the nuts and bolts securely in the following sequence:

Processconnectorbolts→transmitter-endballheadlocknuts→3-valvemanifoldballheadlocknuts→3-valvemanifoldmountingbracketU-bolt nuts

F0502.ai

Nipple

Nipple

Processconnector

Ball headlock nut

Pipe

Ball headlock nut

Processconnector bolts

50 mm(2-inch) pipe

Pipes

3-valvemanifold

Impulse piping

Vent plug(optional)

Stop valve(low pressure side)

Equalizing valve(balancing)

Stop valve(high pressure side)

Figure 5.2 3-Valve Manifold (Pipe-Mounting Type)

Direct-Mounting Type 3-Valve Manifold (Figure 5.3)

1) Mount the 3-valve manifold on the transmitter. (When mounting, use the two gaskets and the

four bolts provided with the 3-valve manifold. Tighten the bolts evenly.)

2) Mount the process connectors and gaskets on the top of the 3-valve manifold (the side on which the impulse piping will be connected).

BoltsProcess

connector

Gasket

GasketProcess

connector

Bolts

Stop valve

Stop valve

3-valvemanifold

3-valvemanifold

Equalizing valve

Equalizingvalve

Stop valveImpulsepiping

Impulsepiping

Stop valve

F0503.ai

Figure 5.3 3-Valve Manifold (Direct-Mounting Type)

NOTEAfter completing the connection of the transmitter and 3-valve manifold, be sure to CLOSE the low pressure and high pressure stop valves, OPEN the equalizing valve, and leave the manifold with the equalizing valve OPEN. You must do this in order to avoid overloading the transmitter from either the high or the low pressure side when beginning operation. This instruction must also be followed as part of the startup procedure (chapter 7.)

Page 28: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<5. Installing Impulse Piping> 5-3

IM 01C25B01-01E

5.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles

If condensate, gas, sediment or other extraneous material in the process piping gets into the impulse piping, pressure measurement errors may result. To prevent such problems, the process pressure taps mustbeangledasshowninfigure5.4accordingtothekindoffluidbeingmeasured.

NOTE• Iftheprocessfluidisagas,thetapsmustbe

vertical or within 45° either side of vertical.• Iftheprocessfluidisaliquid,thetapsmust

be horizontal or below horizontal, but not more than 45° below horizontal.

• Iftheprocessfluidissteamorothercondensing vapor, the taps must be horizontal or above horizontal, but not more than 45° above horizontal.

[Gas]

Pressuretaps

Processpiping

[Steam][Liquid]

45°

45°

45° 45°

45°

45°

F0504.ai

Figure 5.4 Process Pressure Tap Angle (For Horizontal Piping)

(2) Position of Process Pressure Taps and Transmitter

If condensate (or gas) accumulates in the impulse piping, it should be removed periodically by opening the drain (or vent) plugs. However, this will generate a transient disturbance in the pressure measurement, and therefore it is necessary to position the taps and route the impulse piping so that any extraneous liquid or gas generated in the leadlines returns naturally to the process piping.

• Iftheprocessfluidisagas,thenasarulethetransmitter must be located higher than the process pressure taps.

• Iftheprocessfluidisaliquidorsteam,thenasarule the transmitter must be located lower than the process pressure taps.

(3) Impulse Piping Slope

The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.

(4) Temperature Difference Between Impulse Lines (for differential pressure transmitters)

If there is a temperature difference between the high and low impulse lines, the density difference ofthefluidsinthetwolineswillcauseanerrorinthemeasurementpressure.Whenmeasuringflow,impulse lines must be routed together so that there is no temperature difference between them.

(5) Condensate Pots for Steam Flow Measurement (for differential pressure transmitters)

If the liquid in the impulse piping repeatedly condenses or vaporizes as a result of changes in the ambient or process temperature, this will causeadifferenceinthefluidheadbetweenthehigh pressure and low pressure sides. To prevent measurement errors due to these head differences, condensate pots are used when measuring steam flow.

(6) Preventing Wind Speed Effects in Very Low Differential Pressure Measurement (for differential pressure transmitters)

IMPORTANTWhen using a differential pressure transmitter to measure very low pressures (draft pressure), the low pressure connection port is left open to atmospheric pressure (the reference pressure). Any wind around the differential pressure transmitter will therefore cause errors in the measurement. To prevent this, it will be necessary either to enclose the transmitter in a box, or to connect an impulse line to the low pressure side and insert its end into a wind-excluding pot (cylindrical with a base plate).

Page 29: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<5. Installing Impulse Piping> 5-4

IM 01C25B01-01E

(7) Preventing Freezing

Ifthereisanyriskthattheprocessfluidintheimpulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature ofthefluid.

NOTEAfter completing the connections, close the valves on the process pressure taps (main valves), the valves at the transmitter (stop valves), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping.

5.2 Impulse Piping Connection Examples

Figure 5.5 and 5.6 show examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, andthecharacteristicsoftheprocessfluid(corrosiveness,toxicity,flammability,etc.),inorderto make appropriate changes and additions to the connectionconfigurations.

Note the following points when referring to these piping examples.

• The high pressure connecting port on the transmitter is shown on the right (as viewed from the front).

• The transmitter impulse piping connection is shown for a vertical impulse piping connection configurationinwhichthedirectionofconnection is either upwards or downwards.

• If the impulse line is long, bracing or supports should be provided to prevent vibration.

• The impulse piping material used must be compatible with the process pressure, temperature, and other conditions.

• A variety of process pressure tap valves (main valves) are available according to the type ofconnection(flanged,screwed,welded),construction (globe, gate, or ball valve), temperature and pressure. Select the type of valve most appropriate for the application.

Tee

3-valvemanifold

Drainvalve

Orifice

Drainplug

Tapvalve

Unionor flange

Liguid Gas

Condensate pot

Steam

F0505.ai

Figure 5.5 Impulse Piping Connection Examples for Differential Pressure Transmitters

F0506.ai

Liquid Gas Steam

Union or flange

TeeTee

Drain plug

Drain valve

Drain valveDrain plug

Union or flange

Union or flange

Union or flange

Tap valve

Tap valve

Tee

Drain valveDrain plug

Tap valve

Figure 5.6 Impulse Piping Connection Examples forGauge/absolutePressureTransmitters

Page 30: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<6. Wiring> 6-1

IM 01C25B01-01E

6. Wiring6.1 Wiring Precautions

IMPORTANT• Lay wiring as far as possible from electrical

noise sources such as large capacity transformers, motors, and power supplies.

• Remove the electrical connection dust cap before wiring.

• All threaded parts must be treated with waterproofingsealant.(Anon-hardeningsilicone group sealant is recommended.)

• To prevent noise pickup, do not pass signal and power cables through the same ducts.

• Explosion-protected instruments must bewiredinaccordancewithspecificrequirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosion-protected features.

• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on ATEX flameprooftypetransmitters.Whentheshrouding bolt is driven clockwise using an Allen wrench, it goes in. The cover lock can then be released and the cover can be opened by hand. See subsection 8.4 “Disassembly and Reassembly” for details.

• Plug and seal an unused conduit connection.

6.2 Selecting the Wiring Materials

(a) Use stranded leadwires or cables which are the same as or better than 600 V grade PVC insulated wire (JIS C3307) or its equivalent.

(b) Use shielded wires in areas that are susceptible to electrical noise.

(c) In areas with higher or lower ambient temperatures, use appropriate wires or cables.

(d) In environment where oils, solvents, corrosive gases or liquids may be present, use wires or cables that are resistant to such substances.

(e) It is recommended that crimp-on solderless terminal lugs (for 4 mm screws) with insulating sleeves be used for leadwire ends.

6.3 Connections of External Wiring to Terminal Box

6.3.1 Power Supply Wiring ConnectionConnect the power supply wiring to the SUPPLY + and–terminals.When/ALisspecified,alsorefertosubsection 6.3.5.

Power supply–

+Transmitter terminal box

F0601.ai

SUPPLY

PULS

E

CHECKALARM

Figure 6.1 Power Supply Wiring Connection

6.3.2 External Indicator ConnectionAvailableonlywhen/ALisnotspecified.

Connect wiring for external indicators to the CHECK + and – terminals.(Note)Useaexternalindicatorwhoseinternalresistanceis10Ω

or less.

Transmitter terminal box

External indicator

F0602.ai

Power supply

+

SUPPLY

PULS

E

CHECKALARM

Figure 6.2 External Indicator Connection

6.3.3 Communicator ConnectionConnect the BT200 or HART275 HHT to the SUPPLY + and – terminals. (Use hooks.)

SUPPLY

PULS

E

CHECKALARM

Transmitter terminal box

BT200 F0603.ai

Power supply

+

Ignore the polarity since the BT200 is AC-coupled to the terminal box.

Figure 6.3 BT200 Connection

Page 31: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<6. Wiring> 6-2

IM 01C25B01-01E

6.3.4 CheckMeterConnectionAvailableonlywhen/ALisnotspecified.

Connect the check meter to the CHECK + and – terminals. (Use hooks.)

• A 4 to 20 mA DC output signal from the CHECK + and – terminals.

(Note)Useacheckmeterwhoseinternalresistanceis10Ωorless.

SUPPLY

PULS

E

CHECKALARM

Transmitter terminal box

F0604.ai

Power supply

+Check meter

Figure6.4 CheckMeterConnection

6.3.5 Status Output ConnectionWhenoptioncode/ALisspecified,connecttheexternal wiring as shown in Figure 6.5.

Toconfigureandactivatetheprocessalarmfunction and status output, it is necessary to set some parameters. Refer to each communication manual for procedures.

SUPPLY

PULS

E

CHECKALARM

Transmitter terminal box

Magneticvalve

AC power supply

External power supply 30V DC, 120mA max

+

– 250Ω

24V DC

Use two-wire separately shielded cables.

Distributor

Shielded cable

F0605.ai

Figure 6.5 Status Output Connection

6.4 Wiring

6.4.1 LoopConfigurationSince the DPharp uses a two-wire transmission system, signal wiring is also used as power wiring.

DC power is required for the transmitter loop. The transmitter and distributor are connected as shown below.

For details of the power supply voltage and load resistance, see section 6.6; for communications line requirements, see section 9.1.

(1) General-use Type and Flameproof Type

Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor(Power supply unit)

Receiverinstrument

F0606.ai

SUPPLY

PULS

E

CHECKALARM

Figure6.6 ConnectionbetweenTransmitterandDistributor

(2) Intrinsically Safe Type

With the intrinsically safe type, a safety barrier must be included in the loop.

Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor(Power supply unit)

Receiverinstrument

Safety barrier F0607.ai

SUPPLY

PULS

E

CHECKALARM

Figure6.7 ConnectionbetweenTransmitterandDistributor

6.4.2 Wiring Installation

(1) General-use Type and Intrinsically Safe Type

With the cable wiring, use a metallic conduit or waterproof glands.

• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flexiblemetalconduitforwaterproofing.

F0608.ai

Flexible metal conduit

Wiring metalconduit

Tee

Drain plug

Apply a non-hardeningsealant to the threads forwaterproofing.

Figure6.8 TypicalWiringUsingFlexibleMetalConduit

Page 32: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<6. Wiring> 6-3

IM 01C25B01-01E

(2) Flameproof Type

Wirecablesthroughaflameproofpackingadapter,oruseaflameproofmetalconduit.

Wiringcablethroughflameproofpackingadapter.

• Apply a non-hardening sealant to the terminal box connection port and to the threads on the flameproofpackingadapterforwaterproofing.

Flameproof packing adapter

Flexible metal conduit

Wiring metalconduit

Tee

Drain plug

Apply a non-hardeningsealant to the threads forwaterproofing.

F0609.ai

Figure6.9 TypicalCableWiringUsingFlameproofPackingAdapter

Flameproof metal conduit wiring• Asealfittingmustbeinstalledneartheterminal

box connection port for a sealed construction.• Apply a non-hardening sealant to the threads of theterminalboxconnectionport,flexiblemetalconduitandsealfittingforwaterproofing.

F0610.ai

Non-hazardous area

Hazardous areaFlameproofheavy-gaugesteel conduit

Tee

Drain plugSeal fitting

Gas sealing device

Flameproof flexiblemetal conduit

Apply a non-hardeningsealant to the threads ofthese fittings forwaterproofing

After wiring, impregnate the fittingwith a compound to seal tubing.

Figure 6.10 Typical Wiring Using Flameproof Metal Conduit

6.5 GroundingGrounding is always required for the proper operation of transmitters. Follow the domestic electrical requirements as regulated in each country. For a transmitter with a built-in lightning protector, grounding should satisfy ground resistanceof10Ωorless.

Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.

Ground terminal(inside)

Ground terminal(outside)

F0611.ai

SUPPLY

PULS

E

CHECKALARM

Figure 6.11 Ground Terminals

6.6 Power Supply Voltage and Load Resistance

Whenconfiguringtheloop,makesurethattheexternal load resistance is within the range in the figurebelow.(Note) In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

600

250

0 10.5 16.6 25.2 42

Externalload

resistanceR (Ω)

Power supply voltage E (V DC)F0612.ai

Communicationapplicable range BRAIN and HART

R= E–10.50.0244

Figure6.12 RelationshipbetweenPowerSupplyVoltage and External Load Resistance

Page 33: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-1

IM 01C25B01-01E

7. Operation7.1 Preparation for Starting

OperationThis section describes the operation procedure fortheEJX110AandEJX120Aasshowninfigure7.1a (vertical impulse piping type, high-pressure connection: right side) when measuring the liquid flowrate,andEJX430A,EJX440AandEJX310Aasshowninfigure7.1bwhenmeasuringpressure.

NOTECheck that the process pressure tap valves, drain valves, and 3-valve manifold stop valves on both the low pressure and high pressure sides are closed, and that the 3-valve manifold equalizing valve is opened.

(a) Follow the procedures below to introduce process pressure into the impulse piping and transmitter.

DifferentialPressureTransmitters

1) Open the low pressure and high pressure tap valvestofilltheimpulsepipingwithprocessliquid.

2)Slowlyopenthehighpressurestopvalvetofillthe transmitter pressure-detector section with process liquid.

3) Close the high pressure stop valve.4) Gradually open the low pressure stop valve and completelyfillthetransmitterpressure-detectorsection with process liquid.

5) Close the low pressure stop valve.6) Gradually open the high pressure stop valve. At

this time, equal pressure is applied to the low and high pressure sides of the transmitter.

7) Check that there are no liquid leaks in the impulse piping, 3-valve manifold, transmitter, or other components.

Gauge/AbsolutePressureTransmitters

1)Openthetapvalve(mainvalve)tofilltheimpulsepipingwithprocessfluid.

2) Gradually open the stop valve to introduce processfluidintothetransmitterpressure-detector section.

3)Confirmthatthereisnopressureleakinthe impulse piping, transmitter, or other components.

Venting Gas from the Transmitter Pressure-detector Section

• Sincethepipingintheexampleoffigure7.1is constructed to be self-venting, no venting operation is required. If it is not possible to make the piping self-venting, refer to subsection 7.5 for instructions. Leave the equalizing valve open even after venting gas.

(b) Turn ON power and connect the communicator. Open the terminal box cover, and connect

the communicator to the SUPPLY + and – terminals.

(c) Usingthecommunicator,confirmthatthetransmitter is operating properly. Check parameter values or change the setpoints as necessary. See IM 01C25T03-01E (BRAIN communication) or IM 01C25T01-01E (HART communication) for communicator operation.

If the transmitter is equipped with an integral indicator,itsindicationcanbeusedtoconfirmthat the transmitter is operating properly.

F0701.ai

OrificeTap valve(high pressure)Tap valve

(low pressure)

3-valve manifold

Drain valve(high pressure)

Stop valve(low pressure)

Stop valve(high pressure)

Equalizing valve

Figure 7.1a Liquid Flow Measurement

Page 34: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-2

IM 01C25B01-01E

Vent plug (Fill plug)

Tap valve

Stop valve

Drain valve

F0702.ai

Figure7.1b LiquidPressureMeasurement

ConfirmingthatTransmitterisOperatingProperly

Using the BT200

• If the wiring system is faulty, ‘communication error’ appears on the display.

• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.

communication error

PARAM C60:SELF CHECK ERROR

Communication error (Faulty wiring)

Self-diagnostic error(Faulty transmitter)

DATA DIAG PRNT ESC

F0703.ai

Figure 7.2 BT200 Display

Using the integral indicator

• If the wiring system is faulty, the display stays blank.

• If the transmitter is faulty, an error code is displayed.

Self-diagnostic error on the integral indicator(Faulty transmitter) F0704.ai

Figure 7.3 Integral Indicator with Error Code

NOTEIf any of the above errors are indicated on the display of the integral indicator or the communicator, refer to subsection 8.5.3 for the corrective action.

Verify and Change Transmitter Parameter Setting and Values

The parameters related to the following items are setatfactoryasspecifiedinorder.

• Calibration range• Integral indicator display• Output mode• Software damping (optional)

Other parameters like following are shipped with the default setting.

• Low-cut• Process alarm setting• Static pressure range• Signal characterizer• Write protection Toconfirmorchangethevalues,seeIM01C25T01-01E or 01C25T03-01E.

7.2 Zero Point AdjustmentAfter completing preparations for operating the transmitter, adjust the zero point.

Zero point adjustment can be done by turning the transmitter’s zero-adjustment screw or by using the communicator. This section describes the procedure for the zero-adjustment screw. For the communicator procedure, see the communication manual.

IMPORTANTDo not turn off the power to the transmitter immediately after performing a zero point adjustment. Powering off within 30 seconds of performing this procedure will return the zero point to its previous setting.

NOTEBefore performing this adjustment, make sure that the external zero adjustment function has NOT been disabled by a parameter setting.

To check the output signal, use a digital multimeter, calibrator, or communicator.

Page 35: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-3

IM 01C25B01-01E

7.2.1 Adjusting Zero Point for Differential Pressure Transmitters

Before adjusting zero point, make sure that the equalizing valve is open.

Zero-adjustmentscrew cover

F0705.ai

Figure 7.4 External Zero Adjustment Screw

The zero-adjustment screw is located inside the cover. Use a slotted screwdriver to turn the zero-adjustment screw. Equalize the transmitter, then turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed; turnthescrewslowlytomakeafineadjustment,quickly to make a rough adjustment.

When using differential pressure transmitters for level measurement and if you cannot obtain the lower range value from the actual measurement value of 0%, refer to subsection 7.2.2(2).

7.2.2 Adjusting Zero Point for Gauge/AbsolutePressureTransmitters

(1) WhenyoucanobtaintheLowRangeValuefrom the actual measured value of 0% (0 kPa,atmosphericpressure);

For pressure measurement using gauge pressure transmitters, follow the steps below before performing zero point adjustment.

1) Close the tap valve (main valve).2) Loosenthefillplugsothatthepressureapplied

to the transmitter is only the head of the seal liquid.

3) Adjust the zero point at this status.4) Aftertheadjustment,closethefillplugandthen

gradually open the tap valve.

Use a slotted screwdriver to turn the zero-adjustment screw. Turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. Since the degree of the zero adjustment varies with the screw turning speed, turn the screw slowlytomakeafineadjustmentandquicklytomake a rough adjustment.

(2) WhenyoucannotobtaintheLowRangeValue from the actual measured value of 0%;

Adjust the transmitter output to the actual measured value obtained by a digital manometer or a glass gauge.

[Example]

The measuring range of 50 to 250 kPa; the actual measured value of 130 kPa.

130–50250–50

Actual measured value= x100=40.0%(=10.4mA)

Turn the screw to match the output signal to the actual measured value.

7.3 Starting OperationAfter completing the zero point adjustment, follow the procedures below to start operation. Steps 1)and2)arespecifictothedifferentialpressuretransmitters.

1) Close the equalizing valve.2) Gradually open the low pressure stop valve. This places the transmitter in an operational

condition.3) Confirmtheoperatingstatus.Iftheoutput

signalexhibitswidefluctuations(hunting)duetoperiodic variation in the process pressure, use the communicator to dampen the transmitter outputsignal.Confirmthehuntingusingareceiving instrument or the integral indicator, and set the optimum damping time constant.

4) Afterconfirmingtheoperatingstatus,performthe following.

Page 36: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-4

IM 01C25B01-01E

IMPORTANT• Remove the communicator from the terminal box,andconfirmthatnoneoftheterminalscrews are loose.

• Close the terminal box cover and the amplifiercover.Screweachcoverintightlyuntil it will not turn further.

• There are two covers that must be locked on the ATEX Flameproof type transmitters. An Allen head bolt (shrouding bolt) under the edge of each cover is used to lock the cover. When the shrouding bolt is driven counterclockwise with an Allen wrench, the bolt rotates upward and locks the cover. (See section8.4.)Afterlockingthecovers,confirmthat they are secure and cannot be opened by hand. Tighten the zero-adjustment cover mounting screw to secure the cover.

• Tighten the zero-adjustment cover mounting screw to secure the cover.

7.4 Shutting Down the Transmitter

Shut down the transmitter as follows. Steps2)and3)arespecifictothedifferentialpressure transmitters.

1) Turn off the power.2) Close the low pressure stop valve.3) Open the equalizing valve.4) Close the high pressure stop valve.5) Close the high pressure and low pressure tap

valves.

NOTE• Whenever shutting down the transmitter for a longperiod,removeanyprocessfluidthatisin the transmitter pressure-detector section.

• The equalizing valve must be left OPEN.

7.5 Venting or Draining Transmitter Pressure-detector Section

Since this transmitter is designed to be self-draining and self-venting with vertical impulse piping connections, neither draining nor venting willberequirediftheimpulsepipingisconfiguredappropriately for self-draining or self-venting operation.

If condensate (or gas) collects in the transmitter pressure-detector section, the measured pressure maybeinerror.Ifitisnotpossibletoconfigurethepiping for self-draining (or self-venting) operation, you will need to loosen the drain (vent) screw on the transmitter to completely drain (vent) any stagnated liquid (gas.)

However, since draining condensate or bleeding off gas disturbs the pressure measurement, this should not be done when the loop is in operation.

WARNING

Since the accumulated liquid (or gas) may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors.

7.5.1 Draining Condensate1) Gradually open the drain screw or drain plug

and drain the transmitter pressure-detector section.(Seefigure7.5.)

2) When all accumulated liquid is completely removed, close the drain screw or drain plug.

3) Tighten the drain screw to a torque of 10 N·m, and the drain plug to a torque of 34 to 39 N·m.

When you loosen the drain screw or drainplug, the accumulated liquid will be expelledin the direction of the arrow.

F0706.ai

Drain screw

Drain plug

Figure 7.5 Draining the Transmitter

Page 37: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-5

IM 01C25B01-01E

7.5.2 Venting Gas1) Gradually open the vent screw to vent gas from

the transmitter pressure-detector section. (See figure7.6.)

2) When the transmitter is completely vented, close the vent screw.

3) Tighten the vent screw to a torque of 10 N·m.

When you loosen the vent screw, the gasescpes in the direction of the arrow.

F0707.ai

Vent screw

Vent screw

Figure 7.6 Venting the Transmitter

7.6 Setting the Range Using the Range-setting Switch

WARNING

The range setting switch must not be used in the hazardous area. When it is necessary to use the switch, operate it in a non-hazardous location.

When pressure is applied to the transmitter, the low- and high-limit values for the measurement range (LRV and URV) can be changed (re-ranged) using the range-setting switch (push-button) located on the optional integral indicator plate and the external zero adjustment screw. This procedure does not require use of the communicator. However, changes in the scale range and engineering unit display settings for the integral indicator require use of the communicator.

Follow the procedure below to change the LRV and URV settings.

[Example]

Rerange LRV to 0 and URV to 3 MPa.

1) Connect the transmitter and apparatus as shown in Figure 8.1 and warm it up for at least fiveminutes.

2) Press the range-setting push-button. The integral indicator then displays “LRV.SET.”

3) Apply a pressure of 0 kPa (atmospheric pressure) to the transmitter. (Note 1)

4) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)

5) Adjust the output signal to 0% (1 V DC) by rotating the external zero-adjustment screw. Doing so completes the LRV setting.

6) Press the range-setting push-button. The integral indicator then displays “URV.SET.”

7) Apply a pressure of 3 MPa to the transmitter. (Note 1)

8) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %. (Note 2)

9) Adjust the output signal to 100% (5 V DC) by rotating the external zero-adjustment screw. Doing so completes the URV setting.

10) Press the range-setting push-button. The transmitter then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.

Note 1: Wait until the pressure inside the pressure-detector section has stabilized before proceeding to the next step.

Note 2: If the pressure applied to the transmitter exceeds the previous LRV (or URV), the integral indicator may display error number “AL.30” (In this case, the output signal percent and “AL.30” are displayed alternately every two seconds). Although “AL.30” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to , “Errors and Countermeasures” in each communication manual.

Page 38: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<7. Operation> 7-6

IM 01C25B01-01E

IMPORTANT• Do not turn off the power to the transmitter

immediately after completion of the change in the LRV and/or URV setting(s). Note that powering off within thirty seconds after setting will cause a return to the previous settings.

• Changing LRV automatically changes URV to the following value.

URV=previous URV+(new LRV–previous LRV)

• If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter automatically switches back to the normal operation mode.

F0708.ai

Integral indicator

Range-setting switch(Push-button)

Note 1: Use a thin bar which has a blunt tip, e.g., a hexagonal wrench, to press the range-setting push-button.

Note 2: The push-button is located in either lower right or lower left portion of the LCD indicator.

Figure 7.7 Range-setting Switch

Page 39: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8.Maintenance> 8-1

IM 01C25B01-01E

8. Maintenance8.1 Overview

WARNING

Since the accumulated process fluid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance.

Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement.

Transmitters are precision instruments. Please carefully and thoroughly read the following sections for information on how to properly handle them while performing maintenance.

IMPORTANT• As a rule, maintenance of this transmitter

should be done in a shop that has all the necessary tools.

• The CPU assembly contains sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed CPU assembly into a bag with an antistatic coating.

8.2 CalibrationInstrumentsSelection

Table 8.1 lists the instruments that can be used to calibrate a transmitter. When selecting an instrument, consider the required accuracy level. Exercise care when handling these instruments to ensure they maintain the specified accuracy.

8.3 CalibrationUse the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting.

1) Connect the instruments as shown in figure 8.1 and warm up the instruments for at least five minutes (ten minutes for EJX310A.)

IMPORTANT• To adjust the transmitter for highest

accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.

• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied as shown in the figure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using a vacuum pump.

2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter. Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from 100% to 0%, and confirm that the errors are within the required accuracy.

Page 40: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-2

IM 01C25B01-01E

Table8.1 InstrumentsRequiredforCalibration

Name Yokogawa-recommendedInstrument RemarksPower supply Model SDBT or SDBS distributor 4 to 20 mA DC signalLoad resistor Model2792standardresistor[250Ω±0.005%,3W]

Loadadjustmentresistor[100Ω±1%,1W]Voltmeter Model 2501 A digital multimeter

Accuracy(10VDCrange):±(0.002%ofrdg+1dgt)Digital manometer

Model MT220 precision digital manometer1) For 10 kPa class Accuracy:±(0.015%ofrdg+0.015%ofF.S.). . . . for 0 to 10 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -10 to 0 kPa2) For 130 kPa class Accuracy:±0.02%ofrdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa3) For 700 kPa class Accuracy:±(0.02%ofrdg+3digits) . . . . . . . . . . . for 100 to 700 kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa4) For 3000 kPa class Accuracy:±(0.02%ofrdg+10digits) . . . . . . . . . . for 0 to 3000 kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for -80 to 0 kPa5) For 130 kPa abs class Accuracy:±(0.03%ofrdg+6digits) . . . . . . . . . . . for 0 to 130 kPa abs

Select a manometer having a pressure range close to that of the transmitter.

Pressure generator

Model 7674 pneumatic pressure standard for 200 kPa 2 kgf/cm2, 25 kPa 2500 mmH2O

Accuracy:±0.05%ofF.S.

Requires air pressure supply.

Dead weight gauge tester 25 kPa 2500 mmH2OAccuracy:±0.03%ofsetting

Select the one having a pressure range close to that of the transmitter.

Pressure source

Model 6919 pressure regulator (pressure pump)Pressure range: 0 to 133 kPa 1000 mmHg

Prepare the vacuum pump for negative pressure ranges.

Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% orhigherlevel,theremaybedifficultiesincalibrationtothislevelinthefield.Forcalibrationtothe0.1%level,contactYokogawarepresentativesfromwhichtheinstrumentwaspurchasedorthenearestYokogawaoffice.

V

RRc

P

Using pressuregenerator

Reference pressure

High pressure side High pressure side

Low pressure sideopen to atmosphere

Low pressure sideopen to atmosphere

Supply pressure

Pressure generator

Load resistance,250Ω

Loadadjustingresistance,100Ω Digital voltmeter

PowersupplyE

V

RRc

P

Using pressuresource withmanometer

Reference pressure

Pressure source

Model MT220 precision digital manometer

Load resistance,250Ω

Loadadjustingresistance,100Ω Digital voltmeter

PowersupplyE

F0801.ai

Figure 8.1 Instrument Connections (EJX110A)

Page 41: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-3

IM 01C25B01-01E

8.4 DisassemblyandReassembly

This section describes procedures for disassembly and reassembly for maintenance and component replacement.

Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 8.2 shows the tools required.

Table8.2 ToolsforDisassemblyandReassembly

Tool Quantity RemarksPhillips screwdriver

1 JIS B4633, No. 2

Slotted screwdriver

1

Allen wrenches 3 JIS B4648 One each, nominal 3, 4 and 2.5 mm Allen wrenches

Wrench 1 Widthacrossflats,17mmTorque wrench 1Adjustable wrench

1

Socket wrench 1 Widthacrossflats,16mmSocket driver 1 Widthacrossflats,5.5mmTweezers 1

CAUTIONPrecautions for ATEX Flameproof Type Transmitters

• Flameproof type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state.

• Ontheflameprooftypetransmittersthetwocovers are locked, each by an Allen head bolt (shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.

When a cover is closed it should be locked by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m.

Shrouding Bolt

Shrouding Bolt F0802.ai

Figure 8.2 Shrouding Bolts

8.4.1 Replacing the Integral Indicator

CAUTIONCautions for Flameproof Type TransmittersUsers are prohibited by law from modifying the constructionofaflameprooftypetransmitter.This would invalidate the agency approval for the use of the transmitter in a rated area. It follows that the user is prohibited from using aflameprooftypetransmitterwithitsintegralindicator removed, or from adding an integral indicatortoatransmitter.Ifsuchmodificationisabsolutely required, contact Yokogawa.

This subsection describes the procedure for replacinganintegralindicator.(Seefigure8.3)

Removing the Integral Indicator

1) Remove the cover.2) While supporting the integral indicator with one

hand, loosen its two mounting screws.3) Dismount the LCD board assembly from the

CPU assembly. When doing this, carefully pull the LCD board

assembly straight forward so as not to damage the connector pins between it and the CPU assembly.

Attaching the Integral Indicator

1) Align both the LCD board assembly and CPU assembly connectors and engage them.

2) Insert and tighten the two mounting screws.3) Replace the cover.

F0803.ai

Pressforward

Output terminal cable

Zero-adjustmentscrew pin

Slideswitch

Boss Zero-adjustmentscrew

Integralindicator

Mounting screwAmplifier Cover

CPU assemblyBracket(for zero-adjustmentscrew pin)

LCD board assembly

Figure 8.3 Removing and Attaching LCD Board AssemblyandCPUAssembly

Page 42: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-4

IM 01C25B01-01E

8.4.2 ReplacingtheCPUBoardAssemblyThis subsection describes the procedure for replacingtheCPUassembly.(Seefigure8.3)

RemovingtheCPUAssembly

1) Remove the cover. If an integral indicator is mounted, refer to subsection 8.4.1 and remove the indicator.

2) Turn the zero-adjustment screw to the position (where the screw head slot is horizontal) as showninfigure8.3.

3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.

4) Useasocketdriver(widthacrossflats,5.5mm)to loosen the two bosses.

5) Carefully pull the CPU assembly straight forward to remove it.

6) Disconnecttheflatcable(cablewithwhiteconnector at the end) that connects the CPU assembly and the capsule.

NOTEBe careful not to apply excessive force to the CPU assembly when removing it.

MountingtheCPUAssembly

1) Connecttheflatcable(withwhiteconnector)between the CPU assembly and the capsule.

2) Connect the output terminal cable (with brown connector).

NOTEMake certain that the cables do not get pinched between the case and the edge of the CPU assembly.

3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straightontothepostintheamplifiercase.

4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to subsection 8.4.1 to mount the indicator.

NOTEConfirmthatthezero-adjustmentscrewpinisplaced properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero-adjustment mechanism will be damaged.

5) Replace the cover.

8.4.3 Cleaning and Replacing the Capsule Assembly

This subsection describes the procedures for cleaning and replacing the capsule assembly. (See figure8.4.)

CAUTIONCautions for Flameproof Type TransmittersUsers are prohibited by law from modifying the constructionofaflameprooftypetransmitter.Ifyou wish to replace the capsule assembly with one of a different measurement range, contact Yokogawa.The user is permitted, however, to replace a capsule assembly with another of the same measurement range. When doing so, be sure to observe the following.

• The replacement capsule assembly must have the same part number as the one being replaced.

• The section connecting the transmitter and capsule assembly is a critical element in preservationofflameproofperformance,andmust be checked to verify that it is free of dents, scratches, and other defects.

• After completing maintenance, be sure to securely tighten the setscrews that fasten the transmitter section and pressure-detector section together.

Page 43: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-5

IM 01C25B01-01E

RemovingtheCapsuleAssembly

IMPORTANTExercise care as follows when cleaning the capsule assembly.

• Handle the capsule assembly with care, and be especially careful not to damage or distort the diaphragms that contact the process fluid.

• Do not use a chlorinated or acidic solution for cleaning.

• Rinse thoroughly with clean water after cleaning.

1) Remove the CPU assembly as shown in subsection 8.4.2.

2) Remove the two setscrews that connect the transmitter section and pressure-detector section.

3) Remove the hexagon-head screw and the stopper.

4) Separate the transmitter section and pressure-detector section.

5) Removethenutsfromthefourflangebolts.6) While supporting the capsule assembly with

onehand,removethecoverflange.7) Remove the capsule assembly.8) Clean the capsule assembly or replace with a

new one.

ReassemblingtheCapsuleAssembly

1) Insertthecapsuleassemblybetweentheflangebolts, paying close attention to the relative positions of the H (high pressure side) and L (low pressure side) marks on the capsule assembly.

Replace the two capsule gaskets with new gaskets.

2) Installthecoverflangeonthehighpressureside, and use a torque wrench to tighten the four nuts uniformly to a torque shown below.

ModelEJX110A, EJX310A, EJX430A

EJX120AWetted parts material codeS H,M,T,A,D,B

Torque(N·m)kgf·m

171.7

404.1

404.1

ModelEJX130A EJX440A

Bolts & nuts material codeG, C J G, C J

Torque(N·m) kgf·m

909.2

11011.2

707.1

100 10.2

3) After the pressure-detector section has been reassembled, a leak test must be performed to verify that there are no pressure leaks.

4) Reattach the transmitter section to the pressure-detector section. Reattach the stopper with the hexagon-head screw.

5) Tighten the two setscrews. (Tighten the screws to a torque of 1.5 N·m)

6) Install the CPU assembly according to subsection 8.4.2.

7) After completing reassembly, adjust the zero point and recheck the parameters.

F0804.ai

Transmitter section

Pressure-detector sectionCover flange

Capsule gasket

Flange bolt

Setscrew

Nut

Figure 8.4 Removing and Mounting the Pressure-detector Section

IMPORTANTIf you remove the drain/vent plugs when disassembling EJX130A and EJX440A transmitters, install the plugs again before reassemblingthecoverflangeswiththecapsuleassmbly.

Page 44: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8.Maintenance> 8-6

IM 01C25B01-01E

8.4.4 ReplacingtheProcessConnectorGaskets

This subsection describes process connector gasket replacement. (See figure 8.5.)

(a) Loosen the two bolts, and remove the process connectors.

(b) Replace the process connector gaskets.(c) Remount the process connectors. Tighten the

bolts securely and uniformly to a torque shown below, and verify that there are no pressure leaks.

Model

EJX110AEJX120AEJX130AEJX310AEJX430A

EJX440A

C capsule D capsule

Torque(N·m) kgf·m

39 to 49 4 to 5

49 to 595 to 6

F0805.ai

Bolt

Process connector

Process connector gasket

Figure8.5 RemovingandMountingtheProcessConnector

8.5 TroubleshootingIf any abnormality appears in the measured values, use the troubleshooting flow chart below to isolate and remedy the problem. Since some problems have complex causes, these flow charts may not identify all. If you have difficulty isolating or correcting a problem, contact Yokogawa service personnel.

8.5.1 BasicTroubleshootingFirst determine whether the process variable is actually abnormal or a problem exists in the measurement system.

If the problem is in the measurement system, isolate the problem and decide what corrective action to take.

This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting, and the transmitter equipped with an integral indicator will show an alarm code as a result of self-diagnosis. See subsection 8.5.3 for the list of alarms. See also each communication manual.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variableitself abnormal?

Inspect theprocess system.

Isolate problem inmeasurement system.

Does problem exist inreceiving instrument?

Check/correctenvironmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operatingconditions.

Measurement system problem

F0806.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure8.6 BasicFlowandSelf-Diagnostics

Page 45: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-7

IM 01C25B01-01E

8.5.2 TroubleshootingFlowcharts

Connect communicator and check self-diagnostics.

Does the self-diagnosticindicate problem location?

Contact Yokogawa service personnel.

F0807.ai

The following sorts of symptoms indicate that transmitter may not be operating properly.Example : • There is no output signal. • Output signal does not change even though process variable is known to be varying. • Output value is inconsistent with value inferred for process variable.

Is power supplypolarity correct?

Are powersupply voltage and load

resistance correct?

Refer to Section 6.3 to check/correctpolarity at each terminal from powersupply to the terminal box.

Fix pressure leaks, paying particularattention to connections for impulsepiping,pressure-detector section, etc.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

Refer to Section 6.6 for rated voltage and load resistance.

Find/correct broken conductor or wiring error.

Are valves opened orclosed correctly?

Is there any pressure leak?

Is therecontinuity through the

transmitter loop wiring?Do the loop numbers

match?

YES

NO

YES

NO

NO

YES

NO

NO

YES

YES

NO

YES

Refer to error message summary in Subsection 8.5.3 or in each communication manual to take actions.

Connect a communicator and check self-diagnostics.

Does the self-diagnostic indicate problem

location?

Contact Yokogawa service personnel.F0808.ai

Is power supplypolarity correct?

Are valves opened or closed correctly?

Refer to error message summary ineach communication manual to take actions.

YES

NO

NO

YES Refer to Section 6.3 to check/correctpolarity at each terminal from powersupply to the terminal box.

Refer to individual model user manualsand connect piping as appropriate for the measurement purpose.

Fix pressure leaks, paying particularattention to connections for impulsepiping, pressure-detector section, etc.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

NO

YES

YES

NO

YES

Adjust the zero point.

NO

NO

YES

Is there any pressure leak?

Is impulse piping to high pressure and lowpressure side correct?

Is zero point adjusted correctly?

Output travels beyond 0% or 100%.

Page 46: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8. Maintenance> 8-8

IM 01C25B01-01E

Connect a communicator and check self-diagnostics.

Contact Yokogawa service personnel.

F0809.ai

Are valves opened orclosed correctly?

Is impulse pipingconnected correctly?

Refer to error message summary ineach communication manual to take actions.

Refer to Section 6.6 for rated voltageand load resistance.

Provide lagging and/or cooling, or allowadequate ventilation.

Refer to Section 8.2 when selectinginstruments for calibration.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

Refer to individual model user manualsand connect piping as appropriate for the measurement purpose.

Adjust the output.

Is transmitterinstalled where there is

marked variation intemperature?

Is output adjusted correctly?

Large output error.

Does the self-diagnostic indicate problem

location?

Are power supplyvoltage and load resistance

correct?

Were appropriateinstruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

Page 47: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<8.Maintenance> 8-9

IM 01C25B01-01E

8.5.3 AlarmsandCountermeasures

Table8.3 AlarmMessageSummary

Indicator Cause OutputOperationduringError Countermeasure

NoneAL. 01CAP. ERR

Sensor problem. Outputs the signal (Hold, High, or Low) set with parameter.

Replace capsule when error keeps appearing even after restart.

Capsule temperature sensor problem.Capsule EEPROM problem.

AL. 02AMP. ERR

Amplifier temperature sensor problem.

Outputs the signal (Hold, High, or Low) set with parameter.

Replace amplifier.

Amplifier EEPROM problem.Amplifier problem.

AL. 10PRESS

Input is outside measurement range limit of capsule.

Outputs high range limit value or low range limit value.

Check input or replace capsule when necessary.

AL. 11ST. PRSS

Static pressure exceeds limit. Continues to operate and output.

AL. 12CAP. TMP

Capsule temperature is outside range (–50 to 130°C).

Use heat insulation or make lagging to keep temperature within range.AL. 13

AMP. TMPAmplifier temperature is outside range (–50 to 95°C)

AL. 30RANGE

Output is outside upper or lower range limit value.

Outputs high range limit value or low range limit value.

Check input and range setting, and change them as needed.

AL. 31SP. RNG

Static pressure exceeds specified range.

Holds output immediately before error occurred.

AL. 35 *1

P. HIInput pressure exceeds specified threshold.

Continues to operate andoutput.

Check input.

AL. 36 *1

P. LOAL. 37 *1

SP. HIInput static pressure exceeds specified threshold.

AL. 38 *1

SP. LOAL. 39 *1

TMP. HIDetected temperature exceeds specified threshold.

AL. 40 *1

TMP. LOAL. 50P. LRV

Specified value is outside of setting range.

Holds output immediately before error occurred.

Check setting and change them as needed.

AL. 51P. URVAL. 52P. SPNAL. 53P. ADJ

Continues to operate and output. Check input.

AL. 54SP. RNG

Continues to operate and output holding static pressure in %.

Check setting and change them as needed.

AL. 55SP. ADJ

Continues to operate and output. Check input.

AL. 60SC. CFG

Specified values or settings to define signal characterizer function do not satisfy the condition.

Check setting and changethem as needed.

AL. 79OV. DISP

Displayed value exceeds limit.

*1: These alarms may appear only when process alarm function is activated.

Page 48: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-1

IM 01C25B01-01E

9. GeneralSpecifications9.1 StandardSpecificationsRefer to IM 01C25T02-01E for FOUNDATION Fieldbuscommunicationtypemarkedwith“◊”.

PerformanceSpecifications

SeeGeneralSpecificationssheetofeachmodel.

FunctionalSpecifications

Span & Range Limits

EJX110A Measurement Span/Range

kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)

LSpan 0.1 to 10 0.4 to 40 1 to 100 10 to 1000

Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000

MSpan 0.5 to 100 2 to 400 5 to 1000 50 to 10000

Range -100 to 100 -400 to 400 -1000 to 1000-10000 to

10000

HSpan 2.5 to 500 10 to 2000 25 to 5000

0.025 to 5 kgf/cm2

Range -500 to 500 -2000 to 2000 -5000 to 5000-5 to 5

kgf/cm2

VSpan

0.07 to 14 MPa

10 to 2000 psi 0.7 to 140 bar0.7 to140 kgf/cm2

Range-0.5 to 14

MPa-71 to 2000

psi-5 to 140 bar

-5 to 140 kgf/cm2

EJX120A Measurement Span/Range

kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)

ESpan 0.025 to 1 0.1 to 4 0.25 to 10 2.5 to 100

Range -1 to 1 -4 to 4 -10 to 10 -100 to 100

EJX130A Measurement Span/Range

kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)

MSpan 1 to 100 4 to 400 10 to 1000 100 to 10000

Range -100 to 100 -400 to 400 -1000 to 1000 -10000 to 10000

HSpan 5 to 500 20 to 2000 50 to 5000 0.05 to 5 kgf/cm2

Range -500 to 500 -2000 to 2000 -5000 to 5000 -5 to 5 kgf/cm2

EJX310A Measurement Span/Range

kPa abspsi abs(/D1)

mbar abs(/D3)

mmHg abs(/D4)

LSpan 0.5 to 10

0.15 to 2.95 inHg

5 to 100 3.8 to 75

Range 0 to 10 0 to 2.95 inHg 0 to 100 0 to 75

MSpan 1.3 to 130

0.39 to 38 inHg

13 to 1300 9.8 to 970

Range 0 to 130 0 to 38 inHg 0 to 1300 0 to 970

ASpan

0.0175 to 3.5 MPa

2.5 to 5000.175 to 35

bar0.175 to 35

kgf/cm2

Range 0 to 3.5 MPa 0 to 500 0 to 35 bar 0 to 35 kgf/cm2

BSpan

0.08 to 16 MPa

12 to 23000.8 to 160

bar0.8 to 160 kgf/cm2

Range 0 to 16 MPa 0 to 2300 0 to 160 bar 0 to 160 kgf/cm2

EJX430A Measurement Span/Range

MPa psi (/D1) bar(/D3)kgf/cm2

(/D4)

HSpan

2.5 to 500 kPa

10 to 2000 inH2O

0.025 to 5 0.025 to 5

Range-100 to 500

kPa-400 to 2000

inH2O-1 to 5 -1 to 5

ASpan 0.0175 to 3.5 2.5 to 500 0.175 to 35 0.175 to 35

Range -0.1 to 3.5 -15 to 500 -1 to 35 -1 to 35

BSpan 0.08 to 16 12 to 2300 0.8 to 160 0.8 to 160

Range -0.1 to 16 -14.7 to 2300 -1 to 160 -1 to 160

EJX440A Measurement Span/Range

MPa psi (/D1) bar(/D3) kgf/cm2(/D4)

CSpan 0.25 to 32 36 to 4500 2.5 to 320 2.5 to 320

Range -0.1 to 32 -14.5 to 4500 -1 to 320 -1 to 320

DSpan 0.25 to 50 36 to 7200 2.5 to 500 2.5 to 500

Range -0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500

Output “◊”Two wire 4 to 20 mA DC output with digital communications, linear or square root programmable. BRAIN or HART FSK protocol are superimposed on the 4 to 20 mA signal.Output range: 3.6 mA to 21.6 mAOutput limits conform to NAMUR NE43 can be pre-set by option C2 or C3.

Failure Alarm “◊”Output status at CPU failure and hardware error;

Up-scale: 110%, 21.6 mA DC or more (standard)Down-scale: –5%, 3.2 mA DC or lessNote: Applicable for Output signal code D and E

Page 49: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-2

IM 01C25B01-01E

Damping Time Constant (1st order)Amplifierdampingtimeconstantisadjustablefrom 0 to 100.00 seconds and added to response time.

Note: ForBRAINprotocoltype,whenamplifierdampingis set to less than 0.5 seconds, communication may occasionally be unavailable during the operation, especially while output changes dynamically. The default setting of damping ensures stable communication.

Update Period “◊”Differential Pressure: 45 msecStatic Pressure: 360 msec

Zero Adjustment LimitsZero can be fully elevated or suppressed, within the lower and upper range limits of the capsule.

External Zero Adjustment “◊”External Zero is continuously adjustable with 0.01% incremental resolution of span. Re-range can be done locally using the digital indicator with range-setting switch.

Integral Indicator (LCD display) 5-digit Numerical Display, 6-digit Unit Display and Bar graph.Theindicatorisconfigurabletodisplayoneorup to four of the following variables periodically.;Differential pressure in %, Scaled Differential pressure, Differential Pressure in Engineering unit, Static Pressure in Engineering unit.See “Setting When Shipped” for factory setting.

Burst Pressure Limits [EJX110A, EJX310A, EJX430A]

69 MPa (10000 psi)[EJX130A, EJX440A]

132 MPa (19100 psi)

Normal Operating Condition (Selected features may affect limits.)

AmbientTemperatureLimits–40 to 85°C (–40 to 185°F)–30 to 80°C (–22 to 176°F) with LCD display–25 to 80°C (–40 to 176°F) for EJX120A

Process Temperature Limits –40 to 120°C (–40 to 248°F)–25 to 80°C (–40 to 176°F) for EJX120A–40 to 100°C (–40 to 212°F) for EJX310A

L capsule

AmbientHumidityLimits0 to 100% RH

WorkingPressureLimits(Siliconeoil)EJX120A -50 to 50 kPa

Maximum Pressure Limits

EJX110ACapsule PressureL 16 MPa (2300 psi)M, H, V 25 MPa (3600 psi)*

* 16 MPa for wetted parts material code H, M, T, A, D, and B.

EJX130ACapsule PressureM, H 32 MPa (4500 psi)

EJX310ACapsule PressureL 10 kPa abs (2.95 inHg abs)M 130 kPa abs (38 inHg abs)A 3.5 MPa abs (500 psia)B 16 MPa abs (2300 psia)

EJX430ACapsule PressureH 500 kPa (2000 inH2O)A 3.5 MPa (500 psi)B 16 MPa (2300 psi)

EJX440ACapsule PressureC 32 MPa (4500 psi)D 50 MPa (7200 psi)

Minimum Pressure Limit

See graph below

Page 50: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-3

IM 01C25B01-01E

EJX110A, EJX130A, EJX430A, EJX440A

Atmosphericpressure

-40(-40)

0(32)

40(104)

80(176)

120(248)

1(0.14)

2.7(0.38)

10(1.4)

(psi abs)

100(14.5)

Process temperature °C (°F)

WorkingpressurekPa abs

Applicable range

F0901.ai

EJX310A

-40(-40)

0(32)

40(104)

80(176)

120 (248)

0.1(0.75)0.13(1)

1(7.5)

100(750)

10(75)

2.7(20)

0.46(3.45)

0.01(0.075)0.013(0.1)

85 (185)

(mmHg abs)

WorkingpressurekPa abs

Applicable range

Process temperature °C (°F)

M,A and B capsule

L capsule

F0902.ai

Figure9.1 WorkingPressureandProcessTemperature

Maximum Over PressureEJX310A

Capsule PressureL, M 500 kPa abs (72 psia)A 16 MPa abs (2300 psia)B 25 MPa abs (3600 psia)

EJX430ACapsule PressureH, A 16 MPa (2300 psi)B 25 MPa (3600 psi)*

* 24 MPa for wetted parts material code H, M, T, A, D, and B.

EJX440ACapsule PressureC 48 MPa (6750 psi)D 75 MPa (10800 psi)

Supply&LoadRequirements“◊”(Optionalfeatures or approval codes may affect electrical requirements.)With24VDCsupply,uptoa550Ωloadcanbeused. See graph below.

E-10.5 0.0244

(Ω)

Power supply voltage E (V DC)

600

250

R

10.5 16.6 25.2 42

Externalloadresistance

DigitalCommunication

rangeBRAIN and HART

R=

F0903.ai

Figure 9.2 Relationship Between Power Supply Voltage and External Load Resistance

Page 51: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-4

IM 01C25B01-01E

Supply Voltage10.5to42VDCforgeneraluseandflameproof

type.10.5 to 32 V DC for lightning protector (Option

code /A).10.5 to 30 V DC for intrinsically safe, type n or

non-incendive type.Minimum voltage limited at 16.6 V DC for digital

communications, BRAIN and HART

Load (Output signal code D and E) 0to1290Ωforoperation250to600Ωfordigitalcommunication

Communication Requirements “◊”(Safety approvals may affect electrical requirements.)

BRAIN

Communication DistanceUp to 2 km (1.25 miles) when using CEV polyethylene-insulated PVC-sheathed cables. Communication distance varies depending on type of cable used.

Load Capacitance0.22μForless

Load Inductance3.3 mH or less

Input Impedance of communicating device10kΩormoreat2.4kHz.

HART

Communication DistanceUp to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies depending on type of cable used.

EMC Conformity Standards , EN61326-1 Class A, Table2 (For use in industrial locations)EN61326-2-3

PhysicalSpecifications

Wetted Parts Materials

Diaphragm, Cover Flange, Process Connector,CapsuleGasket,andVent/DrainPlugReferto“ModelandSuffixCode.”

ProcessConnectorGasket/o-ring[EJX110A, EJX120A, EJX430A, EJX310A]PTFETeflonFluorinated rubber for Option code /N2 and /N3[EJX130A]Fluorinated rubber (O-ring)[EJX440A]Fluorinated rubber (O-ring) for C capsuleGlassreinforcedTeflon(gasket)forDcapsule

Non-wetted Parts Materials

BoltingASTM-B7 carbon steel, 316L SST stainless steel, or ASTM grade 660 stainless steel

HousingLow copper cast aluminum alloy with polyurethane, mint-green paint (Munsell 5.6BG 3.3/2.9 or its equivalent) or ASTM CF-8M stainless steel

Degrees of ProtectionIP67, NEMA4X, JIS C0920

Cover O-ringsBuna-N,fluoro-rubber(option)

Name plate and tag304 SST, 316SST (option)

Fill FluidSilicone, Fluorinated oil (option)

Weight[Installation code 7, 8, and 9 and wetted parts material code S for EJX110A, EJX310A, and EJX430A]2.8 kg (6.2 lb) without integral indicator, mounting bracket, and process connector. [Installation code 7, 8, and 9 for EJX120A]3.7 kg (8.2 lb) without integral indicator, mounting bracket, and process connector. [Installation code 7, 8, and 9 for EJX130A]6.8 kg (14.3 lb) without integral indicator, mounting bracket, and process connector. [Installation code 7, 8, and 9 for EJX440A]4.9 kg (10.8 lb) without integral indicator, mounting bracket, and process connector.

Add1.5kg(3.3lb)foramplifierhousingcode2.

ConnectionsReferto“ModelandSuffixCode.”

Process Connection of Cover Flange (models except for EJX440A-D): IEC61518

Page 52: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-5

IM 01C25B01-01E

9.2 ModelandSuffixCodes

Model EJX110AModel SuffixCodes Description

EJX110A . . . . . . . . . . . . . . . . . . . . . . Differential pressure transmitterOutput signal

-D . . . . . . . . . . . . . . . . . . . .-E . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

L . . . . . . . . . . . . . . . . . . .M . . . . . . . . . . . . . . . . . .H. . . . . . . . . . . . . . . . . . .V . . . . . . . . . . . . . . . . . . .

0.1 to 10 kPa (0.4 to 40 inH2O)0.5 to 100 kPa (2 to 400 inH2O)2.5 to 500 kPa (10 to 2000 inH2O)0.07 to 14 MPa (10 to 2000 psi)

Wetted partsmaterial *1

. . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-11.

Process connections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)with Rc1/4 female process connectorwith Rc1/2 female process connectorwith 1/4 NPT female process connectorwith 1/2 NPT female process connectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Vertical piping, left side high pressure, and process connection downsideHorizontal piping and right side high pressureHorizontal piping and left side high pressureBottom Process Connection, left side high pressureUniversalflange

Amplifierhousing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mountingbracket B. . . . .D. . . . .G. . . . .J . . . . .K. . . . .M . . . .N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304 SST 2-inch pipe mounting, L type (for vertical piping)304 SST 2-inch pipe mounting (for bottom process connection type)316SST2-inchpipemounting,flattype(forhorizontalpiping)316 SST 2-inch pipe mounting, L type (for vertical piping)316 SST 2-inch pipe mounting (for bottom process connection type)None

Optional codes / Optionalspecification

The“”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosiveprocessfluids.

Page 53: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9. General Specifications> 9-6

IM 01C25B01-01E

Model EJX120AModel Suffix Codes Description

EJX120A ...................... Differential pressure transmitterOutput signal

-D. . . . . . . . . . . . . . . . . . . .-E. . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

E . . . . . . . . . . . . . . . . . . . 0.025 to 1 kPa (0.1 to 4 inH2O)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-11

Process connections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

without process connector (Rc1/4 female on the cover flanges)with Rc1/4 female process connectorwith Rc1/2 female process connectorwith 1/4 NPT female process connectorwith 1/2 NPT female process connectorwithout process connector (1/4 NPT female on the cover flanges)

Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-U. . . . . . . . . . .

Vertical piping, right side high pressure, and process connection down sideVertical piping, left side high pressure, and process connection down sideHorizontal piping and right side high pressureHorizontal piping and left side high pressureUniversal flange

Amplifier housing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mounting bracket B. . . . .D. . . . .G. . . . .J . . . . .K. . . . .N. . . . .

304 SST 2-inch pipe mounting, flat type (for horizontal piping)304 SST 2-inch pipe mounting, L type (for vertical piping)304 SST 2-inch pipe mounting (for bottom process connection type)316 SST 2-inch pipe mounting, flat type (for horizontal piping)316 SST 2-inch pipe mounting, L type (for vertical piping)None

Optional codes / Optional specification

The “” marks indicate the most typical selection for each specification.*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosive process fluids.

Page 54: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-7

IM 01C25B01-01E

Model EJX130AModel SuffixCodes Description

EJX130A . . . . . . . . . . . . . . . . . . . . . . Differential pressure transmitterOutput signal

-D . . . . . . . . . . . . . . . . . . . .-E . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

M . . . . . . . . . . . . . . . . . .H. . . . . . . . . . . . . . . . . . .

1 to 100 kPa (4 to 400 inH2O)5 to 500 kPa (20 to 2000 inH2O)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . Refer to Table. 2 Wetted Parts Materials on Page 9-11

Process connections

3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

with 1/4 NPT female process connector *2

with 1/2 NPT female process connector *2

withoutprocessconnector(1/4NPTfemaleonthecoverflanges)Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-U . . . . . . . . . . .

Vertical piping, left side high pressure, and process connection downsideHorizontal piping and right side high pressureHorizontal piping and left side high pressureUniversalflange

Amplifierhousing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mountingbracket B. . . . .D. . . . .J . . . . .K. . . . .N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304 SST 2-inch pipe mounting, L type (for vertical piping)316SST2-inchpipemounting,flattype(forhorizontalpiping)316 SST 2-inch pipe mounting, L type (for vertical piping)None

Optional codes / Optionalspecification

The “”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosiveprocessfluids.

*2: Lowerlimitofambientandprocesstemperatureis-15˚C.

Page 55: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-8

IM 01C25B01-01E

Model EJX310AModel SuffixCodes Description

EJX310A . . . . . . . . . . . . . . . . . . . . . . Absolute pressure transmitterOutput signal

-D . . . . . . . . . . . . . . . . . . . .-E . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

L . . . . . . . . . . . . . . . . . . .M . . . . . . . . . . . . . . . . . .A. . . . . . . . . . . . . . . . . . .B. . . . . . . . . . . . . . . . . . .

0.5 to 10 kPa abs (0.15 to 2.95 inHg abs)1.3 to 130 kPa abs (0.39 to 38 inHg abs)0.0175 to 3.5 MPa abs (2.5 to 500 psia)0.08 to 16 MPa abs (12 to 2300 psia)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-11.

Process connections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)with Rc1/4 female process connectorwith Rc1/2 female process connectorwith 1/4 NPT female process connectorwith 1/2 NPT female process connectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Vertical piping, right side high pressure, and process connection down sideVertical piping, left side high pressure, and process connection down sideHorizontal piping and right side high pressureHorizontal piping and left side high pressureBottom process connection, left side high pressureUniversalflange

Amplifierhousing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mountingbracket B. . . . .D. . . . .G. . . . .J . . . . .K. . . . .M . . . .N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304 SST 2-inch pipe mounting, L type (for vertical piping)304 SST 2-inch pipe mounting (for bottom process connection type)316SST2-inchpipemounting,flattype(forhorizontalpiping)316 SST 2-inch pipe mounting, L type (for vertical piping)316 SST 2-inch pipe mounting (for bottom process connection type)None

Optional codes / Optionalspecification

The “”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosiveprocessfluids.

Page 56: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-9

IM 01C25B01-01E

Model EJX430AModel SuffixCodes Description

EJX430A . . . . . . . . . . . . . . . . . . . . . . Gauge pressure transmitterOutput signal

-D . . . . . . . . . . . . . . . . . . . .-E . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

H. . . . . . . . . . . . . . . . . . .A. . . . . . . . . . . . . . . . . . .B. . . . . . . . . . . . . . . . . . .

2.5 to 500 kPa (10 to 2000 inH2O)0.0175 to 3.5 MPa (2.5 to 500 psi)0.08 to 16 MPa (12 to 2300 psi)

Wetted partsmaterial *1

. . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-11

Process connections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)with Rc1/4 female process connectorwith Rc1/2 female process connectorwith 1/4 NPT female process connectorwith 1/2 NPT female process connectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Vertical piping, right side high pressure, and process connection down sideVertical piping, left side high pressure, and process connection down sideHorizontal piping and right side high pressureHorizontal piping and left side high pressureBottom Process Connection, left side high pressureUniversalflange

Amplifierhousing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mountingbracket B. . . . .D. . . . .G. . . . .J . . . . .K. . . . .M . . . .N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304 SST 2-inch pipe mounting, L type (for vertical piping)304 SST 2-inch pipe mounting (for bottom process connection type)316SST2-inchpipemounting,flattype(forhorizontalpiping)316 SST 2-inch pipe mounting, L type (for vertical piping)316 SST 2-inch pipe mounting (for bottom process connection type)None

Optional codes / Optionalspecification

The “”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosiveprocessfluids.

Page 57: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-10

IM 01C25B01-01E

Model EJX440AModel SuffixCodes Description

EJX440A . . . . . . . . . . . . . . . . . . . . . . Gauge pressure transmitterOutput signal

-D . . . . . . . . . . . . . . . . . . . .-E . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . .

4 to 20 mA DC with digital communication (BRAIN protocol)4 to 20 mA DC with digital communication (HART protocol)Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01E)

Measurementspan (capsule)

C. . . . . . . . . . . . . . . . . . .D. . . . . . . . . . . . . . . . . . .

0.25 to 32 MPa (36 to 4500 psi)0.25 to 50 MPa abs (36 to 7200 psi)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . Refer to Table. 3 Wetted Parts Materials on Page 9-11.

Process connections

3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

with 1/4 NPT female process connector *2*3

with 1/2 NPT female process connector *2*3

withoutprocessconnector(1/4NPTfemaleonthecoverflanges)Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7 carbon steel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-U . . . . . . . . . . .

Vertical piping, right side high pressure, and process connection down sideVertical piping, left side high pressure, and process connection down sideHorizontal piping and right side high pressureHorizontal piping and left side high pressureUniversalflange

Amplifierhousing 1 . . . . . . . . . .2 . . . . . . . . . .

Cast alluminum alloyASTM CF-8M stainless steel

Electrical connection

0 . . . . . . . . .2 . . . . . . . . .4 . . . . . . . . .5 . . . . . . . . .7 . . . . . . . . .9 . . . . . . . . .A. . . . . . . . .C. . . . . . . . .D. . . . . . . . .

G1/2 female, one electrical connection without blind plugs1/2 NPT female, two electrical connections without blind plugsM20 female, two electrical connections without blind plugsG1/2 female, two electrical connections and a blind plug1/2 NPT female, two electrical connections and a blind plugM20 female, two electrical connections and a blind plugG1/2 female, two electrical connections and a 316 SST blind plug1/2 NPT female, two electrical connections and a 316 SST blind plugM20 female, two electrical connections and a 316 SST blind plug

Integral indicator

D. . . . . . .E . . . . . . .N. . . . . . .

Digital indicatorDigital indicator with the range setting switchNone

Mountingbracket B. . . . .D. . . . .J . . . . .K. . . . .N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304 SST 2-inch pipe mounting, L type (for vertical piping)316SST2-inchpipemounting,flattype(forhorizontalpiping)316 SST 2-inch pipe mounting, L type (for vertical piping)(None)

Optional codes / Optionalspecification

The “”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the corrosiveprocessfluids.

*2: Lower limit of ambient and process temperature is -15°C for capsule code C.*3: Specify the process connections code 3 or 4, when using the process connector for D capsule. Without the process connector, use

the1/4NPTmalepipingtodirectlyconnecttothecoverflange.

Page 58: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-11

IM 01C25B01-01E

Table.1 WettedPartsMaterialsforEJX110A,EJX120A,EJX310A,andEJX430A

Wetted partsmaterial code

Coverflangeandprocess connector Capsule Capsulegasket Drain/Vent plug

S # ASTM CF-8M Hastelloy C-276 (Diaphragm)F316L SST*1 (Others)

Teflon-coated316LSSTPTFE for EJX120A 316 SST

H ASTM CF-8M Hastelloy C-276 PTFE(Teflon) 316 SSTM ASTM CF-8M Monel PTFE(Teflon) 316 SSTT ASTM CF-8M Tantalum PTFE(Teflon) 316 SSTA Hastelloy C-276 equivalent Hastelloy C-276 PTFE(Teflon) Hastelloy C-276D Hastelloy C-276 equivalent Tantalum PTFE(Teflon) Hastelloy C-276B Monel equivalent Monel PTFE(Teflon) Monel

*1: 316L SST, F316 SST for EJX120A.The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST

material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

Table.2 WettedPartsMaterialsforEJX130A

Wetted partsmaterial code

Cover flange process connector Capsule Capsulegasket Drain/Vent plug

S # F316 SST ASTM CF-8M *1Hastelloy C-276*2

(Diaphragm)F316L SST, 316L SST (Others)

Teflon-coated316L SST 316 SST

*1: Cast version of 316 SST. Equivalent to SCS14A.*2: Hastelloy C-276 or ASTM N10276.The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

Table.3 WettedPartsMaterialsforEJX440A

Wetted partsmaterial code

Cover flange process connector Capsule Capsulegasket Drain/

Vent plug

S # F316 SST ASTM CF-8M *1 (C-capsule)F316L SST (D-capsule)

Hastelloy C-276 *2 (Diaphragm)F316L SST (Others)

Teflon-coated316L SST 316 SST

*1: Cast version of 316 SST. Equivalent to SCS14A.*2: Hastelloy C-276 or ASTM N10276.The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

Page 59: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-12

IM 01C25B01-01E

9.3 OptionalSpecificationsItem Description Code

Factory Mutual (FM) FM Explosionproof Approval *1

Explosionproof for Class I, Division 1, Groups B, C and DDust-ignitionproof for Class II/III, Division 1, Groups E, F and GHazardous(classified)locations,indoorsandoutdoors(NEMA4X)

FF1

FM Intrinsically safe Approval *1*3

Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations.Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division 2, Groups F and G, and Class III, Division 1 Hazardous Locations.

FS1

Combined FF1 and FS1 *1*3 FU1CENELEC ATEX CENELEC ATEX (KEMA) Flameproof Approval *1

II 2G Exd IIC T4, T5, T6 KF21

CENELEC ATEX (KEMA) Intrinsically safe Approval *1*3

II 1G EEx ia IIC T4 KS2

Combined KF21, KS2 and Type n *1*3

Type n: II 3G Ex nL IIC T4 KU21

Canadian StandardsAssociation (CSA)

CSA Explosionproof Approval *1

Explosionproof for Class I, Groups B, C and DDustignitionproof for Class II/III, Groups E, F and GEnclosure TYPE 4X, Temp.Code:T6...T4Ex d IIC T6...T4 Enclosure IP66 and IP67

ProcessSealingCertificationDualSealCertifiedbyCSAtotherequirementofANSI/ISA12.27.01No additional sealing requiredPrimary seal failure annuniciation: at the zero adjustment screw

CF1

CSA Intrinsically safe Approval *1 *3

[For CSA C22.2]Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1, Groups E, F and G, Class III, Division 1Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division 2, Groups E, F and G, Class III, Division 1[For CSA E60079]Ex ia IIC T4, Ex nL IIC T4

ProcessSealingCertificationDualSealCertifiedbyCSAtotherequirementofANSI/ISA12.27.01No additional sealing requiredPrimary seal failure annuniciation: at the zero adjustment screw

CS1

Combined CF1 and CS1 *1*3 CU1IECEx Scheme IECExflameproofApproval*1

Flameproof for Zone1, Ex d IIC T6...T4 SF2

IECExIntrinsicallysafe,typenandflameproofApproval*1*3

Intrinsically safe and type nEx ia IIC T4, Ex nL IIC T4FlameproofFlameproof for Zone1, Ex d IIC T6...T4

SU2

Combined Approvals Combination of /KU21, /FU1 and /CU1 *1*3 V1UPainting Color change Terminal cover only P

Bothsidesofamplifiercovers,Munsell7.5R4/14 PRCoating change Anti-corrosion coating X2

316 SST exterior parts 316 SST name plate, tag plate and zero adjustment screw HCFluoro-rubber O-ring AllO-ringsofamplifierhousing.Lowerlimitofambienttemperature:–15°C(5°F) HELightning protector Transmitter power supply voltage:

10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)Allowablecurrent:Max.6000A(1×40μs),Repeating1000A(1×40μs) 100 timesApplicable Standards: IEC 61000-4-4, IEC 61000-4-5

A

Status output *11 Transistor output (sink type)Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC AL

Oil-prohibited use *4 Degrease cleansing treatment. K1Degreasecleansingtreatmentandwithfluorinatedoilfilledcapsule.Operating temperature –20 to 80°C( –4 to 176°F) K2

Page 60: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-13

IM 01C25B01-01E

Item Description CodeOil-prohibited use with dehydrating treatment *4

Degrease cleansing treatment and dehydrating treatment. K5Degreasecleansingtreatmentanddehydratingtreatmentwithfluorinatedoilfilledcapsule. Operating temperature –20 to 80°C( –4 to 176°F) K6

Capsulefillfluid FluorinatedoilfilledincapsuleOperating temperature –20 to 80°C( –4 to 176°F) K3

Calibration units *5 P calibration (psi unit)(See Table for Span and

Range Limits.)

D1bar calibration (bar unit) D3M calibration (kgf/cm2 unit) D4

Long vent *6 Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code K1, K2, K5, and K6: 130 mm. Material: 316SST. U1

Gold-plated capsule gasket *13

Gold-plated 316L SST capsule gasket. No PTFE is used for wetted parts. GS

Gold-plated diaphragm *14 Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1130 Pa abs calibration *12 Minimum input puressure at calibration testing: 130 Pa abs (1 mmHg abs) S1Output limits and failure operation *7

Failure alarm down-scale: Output status at CPU failure and hardware error is –5%, 3.2 mA DC or less. C1

NAMUR NE43 CompliantOutput signal limits:

3.8 mA to 20.5 mA

Failure alarm down-scale: Output status at CPUfailure and hardware error is –5%, 3.2 mA DC or less. C2

Failure alarm up-scale: Output status at CPUfailure and hardware error is 110%, 21.6 mA or more. C3

Body option *8 Without drain and vent plugs N1N1 and Process connection, based on IEC61518 with female thread on both sides ofcoverflange,withblindkidneyflangesonback. N2

N2andMaterialcertificateforcoverflange,diaphragm,capsulebody,andblindkidneyflange N3

Stainless steel tag plate 304SST tag plate wired onto transmitter N4Dataconfigurationatfactory *9

DataconfigurationforHARTcommunication type

Software damping, Descriptor, Message CA

DataconfigurationforBRAINcommunication type

Software damping CB

European Pressure Directive *10

PED 97/23/ECCategory: III, Module: H, Type of Equipment; Pressure Accessory-Vessel, Type of Fluid; Liquid and gas, Group of Fluid: 1 and 2Lower limit of Process and Ambient temperature for EJX110A : –29°C

PE3

Advanced diagnostics *27 Multi-sensing process monitoring• Impulse line blockage detection *28

• Heat trace monitoringDG6

Materialcertificate*15 Coverflange*16 M01Coverflange,Processconnector*17 M11

Pressure test/Leaktestcertificate

Test Pressure: 16 MPa (2300 psi) *18

Nitrogen(N2) Gas *25

Retention time: one minute

T12Test Pressure: 25 MPa (3600 psi) *19 T13Test Pressure: 3.5 MPa (500 psi)* 20 T01Test Pressure: 500 kPa (2000 inH2O) *21 T11Test Pressure: 50 kPa (200 inH2O) *22 T04Test Pressure: 32 MPa (4500 psi) *23 Nitrogen(N2) Gas or water *26

Retention time: one minuteT09

Test Pressure: 50 MPa (7200 psi) *24 T08Contact Yokogawa representative for the codes indicated as ‘-’.*1: Applicable for Electrical connection code 2, 4, 7, and 9. *2: Applicable for Electrical connection code 2 and 7. *3: Not applicable for option code /AL. *4: Applicable for Wetted parts material code S, H, M, and T.*5: TheunitofMWP(Max.workingpressure)onthenameplateofthehousingisthesameunitasspecifiedbyOptioncodeD1,D3,

and D4.*6: Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S, H, M, and T. *7: ApplicableforoutputsignalcodeDandE.Thehardwareerrorindicatesfaultyamplifierorcapsule.*8: Applicable for Wetted parts material code S, H, M, and T; Process connection code 3, 4, and 5; Installation code 9; and Mounting

bracket code N. Process connection faces on the other side of zero adjustment screw.*9: Also see ‘Ordering Instructions’.*10: Applicable for M and H capsules of EJX110A with wetted parts material code S, and all the ranges of EJX130A and EJX440A.*11: Not applicable for output signal code F.*12: Applicable only for EJX310A M and A capsules whose upper range value is set as smaller than 53.3 kPa abs.

Page 61: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-14

IM 01C25B01-01E

*13: Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9. Not applicable for option code U1, N2, N3 and M11. Not applicable for EJX120A.

*14: Applicable for wetted parts material code S.*15: Materialtraceabilitycertification,perEN102043.1B.*16: Applicable for Process connections code 0 and 5.*17: Applicable for Process connections code 1, 2, 3, and 4.*18: Applicable for Capsule code L of EJX110A, Capsule code B of EJX430A and EJX310A, and all the capsules of EJX110A with

wetted parts maerial code H, M, T, A, D, and B.*19: Applicable for Capsule code M, H and V of EJX110A with wetted parts material code S.*20: Applicable for Capsule code A of EJX430A and EJX310A.*21: Applicable for Capsule code H of EJX430A.*22: Applicable for EJX120A and Capsule code L and M of EJX310A.*23: Applicable for EJX130A and Capsule code C of EJX440A.*24: Applicable for Capsule code D of EJX440A.*25: Pure nitrogen gas is used for oil-prohibited use (Option code K1, K2, K5, and K6).*26: Pure nitrogen gas or pure water is used for oil-prohibited use (Option code K1, K2, K5, and K6).*27: Applicable only for output signal code -E.*28: Thechangeofpressurefluctuationismonitoredandthendetectstheimpulselineblockage.SeeTI01C25A31-01Efordetailed

technical information required for using this function. The detection is for one side only.

Page 62: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-15

IM 01C25B01-01E

9.4 Dimensions

Model EJX110AUnit: mm (approx. inch)

95(3

.74)

242(9.53)

175(6.89)129(5.08)97

(3.82)

223(

8.78

)52

(2.0

5)97

(3.8

2)41 (1.6

1)

67(2

.64)

Electrical connectionfor code 5, 9, A, and D.

(optional)

External indicatorConduit connection

Integral indicator (optional)

Zero adjustment

Ground terminal

Mounting bracket(L-type,optional)

Process connectionConduit connection

110(4.33)

ø78(

3.07

)

ø70(

2.76

)

39(1.54)

12(0.47)

138(

5.43

)*2

54(2.13)

54(2

.13)

2-inch pipe(O.D. 60.5 mm)

Vent/Drainplugs

6(0.

24)

54(2.13)

6(0.24)

175(

6.89

)

145(

5.71

)12

4(4.

88)

47(1

.85)

95(3.74)

89(3.50)

115(4.53)

41(1.61)

110(4.33)12

(0.47)39

(1.54)

ø70

(2.7

6)12

9(5.

08)

ø78(

3.07

)

117(4.61)*3

67(2.64)

Drain plug*4

2-inch pipe(O.D. 60.5 mm)

Vent plug*4

Zeroadjustment

Ground terminal

Drain plug*4

Vent plug*4

Mounting bracket(Flat-type,optional)

Electrical connectionfor code 5, 9, A, and D.

Conduitconnection

(optional)

External indicatorConduit connection

Integral indicator (optional)

Processconnection 54(2.13)

Horizontal Impulse Piping Type (Installation code -9), Wetted Parts material code: S

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.*4: Not available when /GS is specified.

Vertical Impulse Piping Type (Installation code -7), Wetted Parts material code: S

Highpressureside

Lowpressureside

Lowpressureside

Highpressureside

Shrouding bolt(for flame-proof type)

Shrouding bolt(for flame-proof type)

(optional)Process connector

(optional)

Processconnector

F0904.ai

Page 63: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-16

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

Electrical connectionfor code 5, 9, A, and D.

Electrical connectionfor code 5, 9, A, and D.

54(2

.13)

6(0.

24)

Horizontal Impulse Piping Type (Installation code -9), Wetted parts material code : H, M, T, A, D, B

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.*4: 15 mm(0.59 inch) for right side high pressure.

Vertical Impulse Piping Type (Installation code -7), Wetted parts material code : H, M, T, A, D, B

Integral indicator (optional)

External indicatorConduit connection (optional)

Mounting bracket(Flat-type,optional)

Process connection

Process connector(optional)

Conduit connection72(2.83)94(3.70)

124(

4.88

)15

9(6.

26)

47(1

.85)

194(

7.64

)

125(4.92)

46(1.81)

95(3.75)

Ground terminal

Zeroadjustment

Vent plug

2-inch pipe(O.D. 60.5 mm)

Drain plug

143(

5.63

)

128*3

(5.04)

54(2.13)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

110(4.33)

9*4

(0.35)

Vent plug

Drain plug

Shrouding bolt(for flame-proof type)

Vent/Drain plugs

2-inch pipe(O.D. 60.5 mm)

148(

5.83

)*2

54(2.13)

12(0.47)

110(4.33)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

Process connection

Mounting bracket(L-type,optional)

Conduit connection

Integral indicator (optional)

External indicatorConduit connection (optional)

72(2

.83)

102(

4.02

)23

4(9.

21)

52(2

.05)

256(10.10)

143(5.63)194(7.64)

97(3.82)

95(3

.74)

46(1

.81)

Zero adjustment

Ground terminalShrouding bolt(for flame-proof type)

Highpressureside

Lowpressureside

F0905.ai

(optional)

Processconnector

Page 64: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-17

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.23)

129(5.08)

117(4.61)

54(2.13)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

12(0.47)

110(4.33)

188(7.40)95(3.74)79

(3.11)

109(

4.29

)

219(

8.62

)

Integral indicator (optional)

Ground terminal

Zeroadjustment

Extenal indicatorConduit connection(optional)

Vent plug

2-inch pipe(O.D. 60.5 mm)

Mounting bracket(optional)

Process connection

Process connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Bottom Process Connection (Installation code -B)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A and D.

F0906.ai

54(2.13)

6(0.24)

ø78(

3.07

)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

ZeroadjustmentExternal indicator

Conduit connection(optional)

Vent plug

Process connection

Process connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug

Drain plugVent plug

117*1

(4.61)

54(2.13)

110(4.33)

12(0.47)

39(1.54)

115(4.53)

41(1.61)

58(2.28)

67(2.64)

175(

6.89

)

129(

5.08

)

145(

5.71

)

95(3.74)

*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value. F0907.ai

Page 65: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-18

IM 01C25B01-01E

Model EJX120AUnit: mm (approx. inch)

54(2.13)

6(0.24)

Electrical connectionfor code 5, 9, A, and D.

Electrical connectionfor code 5, 9, A, and D.

54(2

.13)

6(0.

24)

Horizontal Impulse Piping Type (Installation code -9)

*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.

Vertical Impulse Piping Type (Installation code -7)

Integral indicator (optional)

Extenal indicatorConduit connection (optional)

Mounting bracket(Flat-type,optional)

Process connection

Conduit connection72(2.83)94(3.70)

124(

4.88

)15

9(6.

26)

47(1

.85)

194(

7.64

)

125(4.92)

46(1.81)

95(3.75)

Ground terminal

Zeroadjustment

Vent plug

2-inch pipe(O.D. 60.5 mm)

Drain plug

143(

5.63

)

128*3

(5.04)

54(2.13)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

110(4.33)

12(0.47)

Vent plug

Drain plug

Shrouding bolt(for flame-proof type)

Vent/Drain plugs

2-inch pipe(O.D. 60.5 mm)

148(

5.83

)*2

54(2.13)

12(0.47)

110(4.33)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

Process connection

Mounting bracket(L-type,optional)

Conduit connection

Integral indicator (optional)

Extenal indicatorConduit connection (optional)

72(2

.83)

102(

4.02

)23

4(9.

21)

52(2

.05)

256(10.10)

143(5.63)194(7.64)

97(3.82)

95(3

.74)

46(1

.81)

Zero adjustment

Ground terminalShrouding bolt(for flame-proof type)

Highpressureside

Lowpressureside

Process connector(optional)

Process connector(optional)

F0908.ai

Page 66: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-19

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

ø78(

3.07

)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

ZeroadjustmentExternal indicator

Conduit connection(optional)

Vent plug

Process connection

Process connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug

Drain plug

Vent plug

54(2.13)

110(4.33)

12(0.47)

39(1.54)

194(

7.64

)

143(

5.63

)

159(

6.26

)

95(3.74)

*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value.

46(1.81)

125(4.92) 128(5.04)*1

63(2.48)

72(2.83)

F0909.ai

Page 67: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-20

IM 01C25B01-01E

Model EJX130AUnit: mm (approx. inch)

54(2.13)

6(0.24)

Extenal indicatorConduit connection (optional)

Process connectionZero adjustment

Ground terminal

Mounting bracket(L-type,optional)

Conduit connection

Integral indicator (optional)

Vent/Drain plugs

Vertical Impulse Piping Type (Installation code -7)

143(5.63)197(7.76)

256(10.1)

97(3.82)

95(3

.74)

93(3

.66)

124

(4.8

8)

277(

10.9

)

52(2

.05)

39(1.54)

110(4.33)

ø70(

2.76

)

192(

7.56

)*2

ø78(

3.07

)

132(5.2)

9(0.35)

Lowpressureside

Highpressureside

2-inch pipe(O.D. 60.5 mm)

54(2.13)

6 (0.2

4)54

(2.1

3)

Electrical connectionfor code 5, 9, A, and D.

159(

6.26

)12

4(4.

88)

47(1

.85)

Mounting bracket(Flat-type,optional)

Conduit connection

(optional)

Extenal indicatorConduit connection

Integral indicator (optional)

Processconnection

Shrouding bolt(for flame-proof type)

Shrouding bolt(for flame-proof type)

(optional)

Processconnector

Electrical connectionfor code 5, 9, A, and D.

197(

7.76

)

95(3.74)

116(4.57)

169(6.65)

68(2.68)

93(3.66)

Drain plug*4

2-inch pipe(O.D. 60.5 mm)

Vent plug*4

Zeroadjustment

Ground terminal

Drain plug*4

Vent plug*4

54(2.13) Lowpressureside

High*1

pressureside

110(4.33)9*5

(0.35)39

(1.54)

ø70

(2.7

6)

143(

5.63

)

ø78(

3.07

)

154(6.06)*3

Horizontal Impulse Piping Type (Installation code -9)

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.*4: Not available when /GS is specified.*5: 15mm (0.59 inch) for right side high pressure.

F0910.ai

Process connector(optional)

Page 68: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-21

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24) ø7

8(3.

07)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

Zeroadjustment

External indicatorConduit connection(optional)

Vent plug

Process connection

Process connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug

Drain plugVent plug

54(2.13)

110(4.33)

9(0.35)

39(1.54)

197(

7.76

)

143(

5.63

)

159(

6.26

)

*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value.

85(3.35) 93(3.66)

68(2.68)

169(6.65)

95(3.74)

154(6.06)*1

F0911.ai

Page 69: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-22

IM 01C25B01-01E

Model EJX310AUnit: mm (approx. inch)

95(3

.74)

242(9.53)175(6.89)129(5.08)97

(3.82)

223(

8.78

)52

(2.0

5)97

(3.8

2)41 (1.6

1)

67(2

.64)

Electrical connectionfor code 5, 9, A, and D.

(optional)

Extenal indicatorConduit connection

Integral indicator (optional)

Zero adjustment

Ground terminal(optional)

Mounting bracket(L-type,optional)

Process connector

Conduit connection

110(4.33)

ø78(

3.07

)

ø70(

2.76

)

39(1.54)

12(0.47)

138(

5.43

)*2

27(1.06)

54(2

.13)

2-inch pipe(O.D. 60.5 mm)

Vent/Drainplugs

6(0.

24)

54(2.13)

6(0.24)

175(

6.89

)

145(

5.71

)12

4(4.

88)

47(1

.85)

95(3.74)

89(3.50)

115(4.53)

41(1.61)

110(4.33)

12(0.47)

39(1.54)

ø70

(2.7

6)12

9(5.

08)

ø78(

3.07

)

59*2

(2.32)

67(2.64)

Drain plug*3

2-inch pipe(O.D. 60.5 mm)

Vent plug*3

Zeroadjustment

Ground terminal

Mounting bracket(Flat-type,optional)

Electrical connectionfor code 5, 9, A, and D.

Conduitconnection

(optional)

Extenal indicatorConduit connection

Integral indicator (optional)

Processconnection 27(1.06)

Horizontal Impulse Piping Type (Installation code -9)

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: Not available when /GS is specified.

Vertical Impulse Piping Type (Installation code -7)

Highpressureside

Lowpressureside

Lowpressureside

Highpressureside

Shrouding bolt(for flame-proof type)

Shrouding bolt(for flame-proof type)

(optional)

Processconnector

F0912.ai

Page 70: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-23

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

129(5.08)

59(2.32)

27(1.06)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

12(0.47)

110(4.33)

188(7.40)95(3.74)79

(3.11)

109(

4.29

)

219(

8.62

)

Integral indicator (optional)

Ground terminal

Zeroadjustment

Extenal indicatorConduit connection(optional)

Vent plug2-inch pipe(O.D. 60.5 mm)

Mounting bracket(optional)

Process connection

Conduit connection

Shrouding bolt(for flame-proof type)

Process connector(optional)

Bottom Process Connection (Installation code -B)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

F0913.ai

54(2.13)

6(0.24)

ø78(

3.07

)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

ZeroadjustmentExternal indicator

Conduit connection(optional)

Vent plug

Process connectionProcess connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug59*1

(2.32)

110(4.33)

12(0.47)

39(1.54)

115(4.53)

41(1.61)

58(2.28)

67(2.64)

175(

6.89

)

129(

5.08

)

145(

5.71

)

95(3.74)

*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value. F0914.ai

Page 71: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-24

IM 01C25B01-01E

Model EJX430AUnit: mm (approx. inch)

95(3

.74)

242(9.53)175(6.89)129(5.08)97

(3.82)

223(

8.78

)

52(2

.05)

97(3

.82)

41 (1.6

1)

67(2

.64)

Electrical connectionfor code 5, 9, A, and D.

(optional)

External indicatorConduit connection

Integral indicator (optional)

Zero adjustment

Ground terminal

Mounting bracket(L-type,optional)

Process connection

Conduit connection

110(4.33)

ø78(

3.07

)

ø70(

2.76

)

39(1.54)

12(0.47)

138(

5.43

)*2

27(1.06)

54(2

.13)

2-inch pipe(O.D. 60.5 mm)

Vent/Drainplugs

6(0.

24)

54(2.13)

6(0.24)

175(

6.89

)

145(

5.71

)12

4(4.

88)

47(1

.85)

95(3.74)

89(3.50)

115(4.53)

41(1.61)

110(4.33)

12(0.47)

39(1.54)

ø70

(2.7

6)12

9(5.

08)

ø78(

3.07

)

59*2

(2.32)

67(2.64)

Drain plug*3

2-inch pipe(O.D. 60.5 mm)

Vent plug*3

Zeroadjustment

Ground terminal

Mounting bracket(Flat-type,optional)

Electrical connectionfor code 5, 9, A, and D.

Conduitconnection

(optional)

External indicatorConduit connection

Integral indicator (optional)

Processconnection 27(1.06)

Horizontal Impulse Piping Type (Installation code -9), Wetted parts material code : S

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: Not available when /GS is specified.

Vertical Impulse Piping Type (Installation code -7), Wetted parts material code : S

Highpressureside

Lowpressureside

Lowpressureside

Highpressureside

Shrouding bolt(for flame-proof type)

Shrouding bolt(for flame-proof type)

Open to atmosphereø5(0.20)

Open to atmosphereø10(0.39)

F0915.ai

(optional)Process connector

(optional)

Processconnector

Page 72: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-25

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

Electrical connectionfor code 5, 9, A, and D.

Electrical connectionfor code 5, 9, A, and D.

54(2

.13)

6(0.

24)

Horizontal Impulse Piping Type (Installation code -9), Wetted parts material code : H, M, T, A, D, B

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.

Vertical Impulse Piping Type (Installation code -7), Wetted parts material code : H, M, T, A, D, B

Integral indicator (optional)

External indicatorConduit connection (optional)

Mounting bracket(Flat-type,optional)

Process connection

Process connector(optional)

Conduit connection72(2.83)94(3.70)

124(

4.88

)15

9(6.

26)

47(1

.85)

194(

7.64

)

125(4.92)

46(1.81)

95(3.75)

Ground terminal

Zeroadjustment

Vent plug

2-inch pipe(O.D. 60.5 mm)

Drain plug

143(

5.63

)

64*2

(2.52)

54(2.13)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

110(4.33)

12(0.47)

Open to atmosphere ø10(0.39)

Open to atmosphere ø5(0.20)

Shrouding bolt(for flame-proof type)

Vent/Drain plugs

2-inch pipe(O.D. 60.5 mm)

148(

5.83

)*2

27(1.06)

12(0.47)

110(4.33)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

Process connection

Mounting bracket(L-type,optional)

Conduit connection

Integral indicator (optional)

External indicatorConduit connection (optional)

72(2

.83)

102(

4.02

)

234(

9.21

)

52(2

.05)

256(10.10)

143(5.63)194(7.64)

97(3.82)

95(3

.74)

46(1

.81)

Zero adjustment

Ground terminalShrouding bolt(for flame-proof type)

Highpressureside

Lowpressureside

F0916.ai

Processconnector(optional)

Page 73: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-26

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

129(5.08)

59(2.32)

27(1.06)

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

12(0.47)

110(4.33)

188(7.40)95(3.74)79

(3.11)

109(

4.29

)

219(

8.62

)

Integral indicator (optional)

Ground terminal

Zeroadjustment

Extenal indicatorConduit connection(optional)

Vent plug2-inch pipe(O.D. 60.5 mm)

Mounting bracket(optional)

Process connection

Process connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Bottom Process Connection (Installation code -B)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Open to atmosphereø10(0.39)

F0917.ai

54(2.13)

6(0.24)

ø78(

3.07

)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

ZeroadjustmentExternal indicator

Conduit connection(optional)

Vent plug

Process connectionProcess connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug59*1

(2.32)

110(4.33)

12(0.47)

39(1.54)

115(4.53)

41(1.61)

58(2.28)

67(2.64)

175(

6.89

)

129(

5.08

)

145(

5.71

)

95(3.74)

*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value.

Open to atmosphere (ø5)

F0918.ai

Page 74: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-27

IM 01C25B01-01E

Model EJX440A Unit: mm (approx. inch)

Electrical connectionfor code 5, 9, A and D.

54(2

.13)

6(0.

24)

54(2.13)

6(0.24)

Electrical connectionfor code 5, 9, A and D.

F0919.ai

Open toatmospher ø9(0.35)

Vent/Drain plugs

2-inch pipe(O.D. 60.5 mm)

Highpressureside

Lowpressureside

182(

7.17

)*2

ø70

(2.7

6)

ø78(

3.07

)

Extenal indicatorConduit connection(optional)

Integral indicator(optional)

Zero adjustment

Ground terminal

Mounting bracket(L-type,optional)

Process connection

Conduit connection

119(

4.69

)88

(3.4

6)52

(2.0

5)129(5.08)97

(3.82)63

(2.4

8)

267(

10.5

)

175(6.89)

242(9.53)

95(3

.74)

27(1.06)

110(4.33)39

(1.54)12

(0.47)

120(4.72)

Shrouding bolt(for flame-proof type)

Integral indicator (optional)

Extenal indicatorConduit connection(optional)

Vent plug*3

Drain plug*3

Mounting bracket(Flat-type,optional)

Process connection

Process connector(optional)

Conduit connection

124(

4.88

)14

5(5.

71)

47(1

.85)

88(3.46)

159(6.26)

63(2.48)

95(3.74)

175(

6.89

)

111(4.37)

Open toatmosphere ø5(0.20)

Groundterminal

Zeroadjustment

2-inch pipe(O.D. 60.5 mm)

Highpressureside

Lowpressureside

ø78(

3.07

)

ø70

(2.7

6)

39(1.54)

110(4.33)12

(0.47)

129(

5.08

)

27(1.06)

70*2

(2.76)

Shrouding bolt(for flame-proof type)

Horizontal Impulse Piping Type (Installation code -9)

*1: When Installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: Not available when /GS is specified.

Vertical Impulse Piping Type (Installation code -7)

Process connector(optional)

Page 75: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

<9.GeneralSpecifications> 9-28

IM 01C25B01-01E

Unit: mm (approx. inch)

54(2.13)

6(0.24)

ø78(

3.07

)

ø70

(2.7

6)

Integral indicator (optional)

Ground terminal

Zeroadjustment

External indicatorConduit connection(optional)

Vent plug

Process connectionProcess connector(optional)

Conduit connection

Shrouding bolt(for flame-proof type)

Universal Flange (Installation code -U)

Lowpressureside

Highpressureside

Electrical connectionfor code 5, 9, A, and D.

Drain plug

Drain plug

12(0.47)

39(1.54)

175(

6.89

)

129(

5.08

)

145(

5.71

)

*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value.

80(3.15)

88(3.46)

63(2.48)

159(6.26)

95(3.74)

110(4.33)

27(1.06)

70*1

(2.76)

Open to atmosphere(ø5)

F0920.ai

SUPPLY

CHECKor

ALARM

+–+–

Terminal Configuration

Power supply and output terminal

External indicator (ammeter) terminal*1*2

orStatus contact output terminal*2

(when /AL is specified)

Ground terminal

Communicationterminals (BT200 etc.)connection hook

Terminal Wiring

*1: When using an external indicator or check meter, the internal resistance must be 10 Ω or less. A check meter or indicator cannot be connected when /AL option is specified. *2: Not available for fieldbus communication type.

Check meter connection hook*1*2

SUPPLY +

SUPPLY – CHECK – or ALARM –

CHECK + orALARM +

+–

F0921.ai

< Factory Setting >Tag Number AsspecifiedinorderAmplifierDamping*2 ‘2sec.’orasspecifiedinorderOutput Mode ‘Linear’unlessotherwisespecifiedinorderCalibration Range Lower Range Value AsspecifiedinorderCalibration Range Upper Range Value AsspecifiedinorderCalibration Range Units Selectedfromthefollowings.Onlyoneunitcanbespecified.

[Differential/gauge pressure transmitter] mmH2O, mmH2O(68°F), mmAq, mmWG, mmHg, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O, inH2O(68°F), inHg, ftH2O, ftH2O(68°F) or psi. [Absolute pressure transmitter] torr, Pa abs, hPa abs, kPa abs, MPa abs, mbar abs, bar abs, mmH2O abs, mmH2O abs(68°F), mmHg abs, gf/cm2 abs, kgf/cm2 abs, inH2O abs, inH2O abs(68°F), inHg abs, ftH2O abs, ftH2O abs(68°F) , atm, or psia.

Display Setting Designateddifferentialpressurevaluespecifiedinorder.(%,Engineeringunit or user scaled value.) Display mode 'Linear' or 'Square root' is also as specifiedinorder.

Static Pressure Display Range*1 '0 to 25 MPa' for M, H, and V capsule of EJX110A, '0 to 16 MPa' for L capsule, and '0 to 32 MPa' for EJX130A. Display unit is selectable from the units listed in above 'Calibration Range Units'.

*1: For differential pressure transmitters only. *2: To specify these items at factory, /CA or /CB option is required.

Page 76: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

i

IM 01C25B01-01E

Revision Information Title : EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, and EJX440A Differential Pressure and Pressure Transmitters Manual No. : IM 01C25B01-01E

Edition Date Page Revised Item1st Mar. 2004 — New publication2nd Apr. 2004 — Revise words and phrases.

2-6 2.9.3 •CorrectAmbienttemperature–60→–504-4 4.5 • Change the description of rotation angle.8-3 8.4 • Add Allen wrench nominal 3mm to Table 8.4.1.

3rd Feb. 2005 — Re-numberfigureandtabletitle.i Add subsection 6.3.5.ii Add note for Safety Transmitter.

1-1 1. • Add note for Fieldbus communication type.1-3 1.1 •Add(f)Modification.2-3 2.9 •AddNOTEforfieldbuscommunicationtype.2-5 2.9.2 •ModifydescriptionsandinstructionsforCSAcertification2-72-8

2.9.3 •CorrectnumberinNote4.10MINUTES→5MINUTES• Delete WARNING on non-incendive power supply.•CorrectnumberforElectricaldataCi.6nF→10nF

3-1 3. •Correctlabeloftheswitchinthefigure.N→E,Y→ D• Add descriptions in Note 2.

4-3 4.4.1 • Add description about process connector in 3).4-4 4.6 • Add section 4.6.6-1 6.3.1, 6.3.2 •Addlimitation/notewhen/ALisspecified.6-2 6.3.4 •Addlimitationwhen/ALisspecified.6-2 6.3.5 • Add subsection 6.3.5.7-3 7.2.1 • Add descriptions about zero adjustment.

9-1, 9-2 9.1 •AddnotesforFOUNDATIONfieldbuscommunicationtype.• Add capsule code H.

9-4, 9-5 9.2 • Add output signal code -F and capsule code H.9-6 9.3 • Add CSA approvals and note *2 and *39-8 9.4 • Add note *3.9-10 9.4 • Add notes for /AL and FOUNDATION Fieldbus.

4th Sep. 2005 1-1 1. Add model names to the manual coverage.2-3 to 2-8 2. Addapplicablestandardandcertificatenumberforeach

approval.2-11 2.10 Change australian reference standard.2-11 2.11 Add descriptions for PED.2-12 2.11 Add section 2.12.4-1 4.1 Add model name.4-2 4.3 Add table 4.1.8-5 8.4.3 Add table for torque.

Add notes for reassembling EJX130A and EJX440A.8.4.4 Add table for torque.

9-1 to 9-18 9. Addspecifications,codes,anddimensionsforEJX130A,EJX310A and EJX440A.

5th July 2006 2-8- 2.9.3 Change applicable standards for ATEX type n.—6th Nov. 2007 1-1 1. Add model code table.

2-3 2.9 Add note for EJX130A.9-10 9.3 Add note for EJX130A.9-15 9.4 Modify dimensions of EJX130A.A-1 APPENDIX 1. Add "EJX130A ADDITIONAL INFORMATION."

Page 77: User’s Manual EJX110A, EJX120A, EJX130A, EJX310A, EJX430A, …€¦ · and EJX130A differential pressure transmitter, EJX430A and EJX440A gauge pressure transmitter and EJX310A

IM 01C25B01-01E

Edton Date Page Revsed Item7th Feb. 2008 — Change of the style code, add EJX120A.

General • Change the figure of amplifier housing.1-1 1 • Add style code table.2-1 2.1 • Update the Figure 2.2.2-5 2.9.1 • Add code /V1U.2-6 2.9.2 • Revise information for CSA Explosionproof type.2-7 2.9.2 • Add code /V1U.2-8 2.9.3 • Revise information for KEMA flameproof type. Add code /V1U.2-9 2.9.3 • Revise Figure in (2) Electrical connection and (6) Nameplate.2-10 2.9.4 • Revise information for IECEx flameproof type.

9-1 to 9-3 9.1 • Add information for EJX120A.9-5 to 9-10 9.2 • Add new suffix codes for 316 SST blind plugs and brackets.

Add EJX120A.9-11 9.3 • Remove /KF2 and /KU2. Add /KF21, /KU21, /SF2 and /V1U.9-12 • Add /HC.

9-14 to 9-20 9.4 • Revise external dimensions.Add EJX120A.— • Remove Appendix 1 'Additional Information for EJX130A.'

8th June 2008 2-6 2.9.2 • Correct certification number.2-8 2.9.3 • Revise applicabble standards for ATEX Type n.2-11 2.11 • Add EJX110A V capsule, wetted parts matterial code S and

EJX310A L capsule.4-1 4.2 • Add information of Universal flange.8-5 8.4.3 • Add wetted parts material code in the torque table.

9-1 to 9-27 9. • Add EJX110A V capsule, EJX110A/EJX430A wetted parts material code H, M, T, A, D, and B, EJX310A L capsule and option code /S1, and universal flange.

9-10 9.3 • Add statement of sealing certification for CSA approval.9th Aug. 2009 2-1 2.1 • Replace a name plate.

2-11 2.10 • Revise standards.2.11 • Revise information of PED.

9-4 to 9-9 9.2 • Modify descriptions of materials.9-11 to 9-12 9.3 • Add /GS, /A1,and /DG6.9-13 to 9-26 9.4 • Correct errors. Add note for /GS.

10th Apr. 2010 2-4 to 2-118-19-49-12

2.98.39.19.3

• Add limitation of ambient temperature for /HE. • Add description for warm up time.• Add O-ring material.• Add /HE.