User’s Manual Contents 1. Introduction 1.1 For Safe Use of Product..............................................2 1.2 Warranty ......................................................................3 1.3 ATEX Documentation..................................................4 2. Handling Cautions 2.1 Model and Specifications Check.................................6 2.2 Selecting the Installation Location ..............................6 2.3 Pressure Connection ..................................................6 2.4 Installation of an Explosion-Protected Instrument ......6 2.5 EMC Conformity Standards ..................................... 31 2.6 Pressure Equipment Directive (PED) ...................... 31 2.7 Safety Requirement Standards................................ 32 3. Installation 3.1 Mounting................................................................... 33 3.2 Mounting the Diaphragm Seals ......................................33 3.3 Diaphragm Seals Installation Consideration............ 34 3.4 Mounting the Flushing Connection Ring.................. 35 3.5 Affixing the Teflon Film ............................................. 36 3.6 Rotating Transmitter Section.................................... 37 3.7 Changing the Direction of Integral Indicator............. 37 4. Installing Impulse Piping 4.1 Impulse Piping Installation Precautions ................... 38 4.2 Impulse Piping Connection Examples ..................... 40 4.3 Process Piping Installation Precautions (EJ115)41 5. Wiring 5.1 Wiring Precautions ................................................... 43 5.2 Connections of External Wiring to Terminal Box...... 43 5.3 Wiring ....................................................................... 46 5.4 RTD Cable Connection (EJX910A/EJX930A) ......... 48 5.5 Grounding ................................................................ 50 5.6 Power Supply Voltage and Load Resistance........... 50 6. Operation 6.1 Preparation for Starting Operation ........................... 51 6.2 Zero Point Adjustment .............................................. 51 6.3 Local Parameter Setting .......................................... 52 7. Errors and Countermeasures 1 2 3 4 5 6 7 EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual IM 01C25A01-01E IM 01C25A01-01E 11th Edition

User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

User’sManual

Contents

1. Introduction1.1 For Safe Use of Product ..............................................21.2 Warranty ......................................................................31.3 ATEX Documentation ..................................................4

2. Handling Cautions2.1 ModelandSpecificationsCheck .................................62.2 SelectingtheInstallationLocation ..............................62.3 PressureConnection ..................................................62.4 InstallationofanExplosion-ProtectedInstrument ......62.5 EMCConformityStandards ..................................... 312.6 Pressure Equipment Directive (PED) ...................... 312.7 Safety Requirement Standards ................................ 32

3. Installation3.1 Mounting................................................................... 333.2 MountingtheDiaphragmSeals ......................................333.3 DiaphragmSealsInstallationConsideration ............ 343.4 MountingtheFlushingConnectionRing .................. 353.5 AffixingtheTeflonFilm ............................................. 363.6 Rotating Transmitter Section .................................... 373.7 ChangingtheDirectionofIntegralIndicator............. 37

4. Installing Impulse Piping4.1 ImpulsePipingInstallationPrecautions ................... 384.2 ImpulsePipingConnectionExamples ..................... 404.3 ProcessPipingInstallationPrecautions(EJ115) 41

5. Wiring5.1 Wiring Precautions ................................................... 435.2 ConnectionsofExternalWiringtoTerminalBox ...... 435.3 Wiring ....................................................................... 465.4 RTDCableConnection(EJX910A/EJX930A) ......... 485.5 Grounding ................................................................ 505.6 PowerSupplyVoltageandLoadResistance ........... 50

6. Operation6.1 Preparation for Starting Operation ........................... 516.2 Zero Point Adjustment .............................................. 516.3 LocalParameterSetting .......................................... 52

7. Errors and Countermeasures

1

2

3

4

5

6

7

EJX and EJA-E SeriesDifferential Pressure and Pressure TransmittersInstallation Manual

IM01C25A01-01E

IM01C25A01-01E11thEdition

Page 2: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<1. Introduction> 1

IM01C25A01-01E11thEdition:July2015(YK)AllRightsReserved,Copyright©2009,YokogawaElectricCorporation

1. IntroductionThisinstallationmanualprovidesthebasicguidelinesforinstallationandwiringproceduresoftheDPharpEJXseriesandEJA-EseriestransmitterswithBRAINandHARTprotocolsandiscomposedoftheinformationextractedfromtheproductusers’manualsaslistedinTable1.1.ItdoesnotprovidetheinformationincludingwiringproceduresofthetransmitterswithFOUNDATION Fieldbus,ProfibusandModbusprotocols,productspecificfunctionalspecificationsandexplanations,operation,maintenanceandtrouble-shooting.

WARNING

Toensurecorrectandsafeuseoftheinstrument,obtainthemanualsapplicabletodesignatedmodelsandspecificationsaslistedTable1.1,readthemthoroughlyandfullyunderstandhowtooperatetheinstrumentbeforeoperatingit.

Users’manualforeachproductconsistsofahardwaremanualdescribinginstallation,wiring,operation,maintenanceandspecificationincludingdetailedmodelandsuffixcodeinformation,andacommunicationmanualdescribinginformationspecifictoeachcommunicationprotocoltype,includingsafetymanualforsafety instrumented system.

ThesemanualscanbedownloadedfromthewebsiteofYokogawaorpurchasedfromtheYokogawarepresentatives.

Websiteaddress:http://www.yokogawa.com/fld/

Table 1.1 PDF Manual List and Applicable Style Code

[EJX series Hardware Manual]

Models Document No. StyleEJX110A

IM01C25B01-01E

S3EJX120A S1EJX130A,EJX310A,EJX430AandEJX440A S2

EJX210A IM01C25C01-01E S2EJX510AandEJX530A

IM01C25F01-01ES2

EJX610AandEJX630A S1EJX118AandEJX438A IM01C25H01-01E S2EJX115A IM01C25K01-01E S1EJX910A

IM01C25R01-01ES2

EJX930A S1

[EJX series Communication Manual]

Models Document No. StyleDPharpHART5/HART7CommunicationType IM01C25T01-06EN —

DPharpFOUNDATIONFieldbusCommunicationType IM01C25T02-01E —

DPharpBRAINCommunicationType IM01C25T03-01E —

DPharpPROFIBUSPACommunicationType IM01C25T04-01EN —

EJX910AandEJX930AHARTCommunicationType IM01C25R02-01E —

EJX910AandEJX930AFieldbusCommunicationType IM01C25R03-01E —

EJX910AandEJX930AModbusCommunicationType IM01C25R05-01E —

[EJA-E series Hardware Manual]

Models Document No. StyleEJA110E,EJA120E

IM01C25B01-01E S1EJA130E,EJA310E,EJA430EandEJA440EEJA210E IM01C25C01-01E S1EJA510EandEJA530E IM01C25F01-01E S1EJA118EandEJA438E IM01C25H01-01E S1EJA115E IM01C25K01-01E S1

[EJA-E series Communication Manual]

Models Document No. StyleDPharpHART5/HART7CommunicationType IM01C25T01-06EN —

DPharpFOUNDATIONFieldbusCommunicationType IM01C25T02-01E —

DPharpBRAINCommunicationType IM01C25T03-01E —

DPharpPROFIBUSPACommunicationType IM01C25T04-01EN —

Regarding This Manual

• Thismanualshouldbepassedontotheenduser.• Thecontentsofthismanualaresubjecttochange

withoutpriornotice.• Allrightsreserved.Nopartofthismanualmaybe

reproducedinanyformwithoutYokogawa’swrittenpermission.

• Yokogawamakesnowarrantyofanykindwithregardtothismanual,including,butnotlimitedto,impliedwarrantyofmerchantabilityandfitnessforaparticularpurpose.

• Ifanyquestionarisesorerrorsarefound,orifanyinformationismissingfromthismanual,pleaseinformthenearestYokogawasalesoffice.

1

Introduction

Page 3: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<1. Introduction> 2

IM01C25A01-01E

• Thespecificationscoveredbythismanualarelimitedtothoseforthestandardtypeunderthespecifiedmodelnumberbreak-downanddonotcovercustom-made instruments.

• Pleasenotethatchangesinthespecifications,construction,orcomponentpartsoftheinstrumentmaynotimmediatelybereflectedinthismanualatthetimeofchange,providedthatpostponementofrevisionswillnotcausedifficultytotheuserfromafunctional or performance standpoint.

• Yokogawaassumesnoresponsibilitiesforthisproductexceptasstatedinthewarranty.

• Ifthecustomeroranythirdpartyisharmedbytheuseofthisproduct,Yokogawaassumesnoresponsibilityforanysuchharmowingtoanydefectsintheproductwhichwerenotpredictable,orforanyindirectdamages.

• WhendescribingthemodelnamelikeEJ110 inthismanual,itshowstheapplicabilityforbothEJX110AandEJA110E.Thesamerepresentationsareusedfortheothermodels,too.

• Thefollowingsafetysymbolmarksareusedinthismanual:

WARNING

Indicatesapotentiallyhazardoussituationwhich,ifnotavoided,couldresultindeathorseriousinjury.

CAUTIONIndicatesapotentiallyhazardoussituationwhich,ifnotavoided,mayresultinminorormoderateinjury.Itmayalsobeusedtoalertagainstunsafepractices.

IMPORTANTIndicatesthatoperatingthehardwareorsoftwareinthismannermaydamageitorleadtosystemfailure.

NOTEDraws attention to information essential for understandingtheoperationandfeatures.

Direct current

Functional grounding terminal

CautionThissymbolindicatesthattheoperatormustrefertoanexplanationintheuser’smanualinordertoavoidtheriskofinjuryordeathofpersonnelordamagetotheinstrument.

1.1 For Safe Use of ProductFortheprotectionandsafetyoftheoperatorandtheinstrumentorthesystemincludingtheinstrument,pleasebesuretofollowtheinstructionsonsafetydescribedinthismanualwhenhandlingthisinstrument.Incasetheinstrumentishandledincontradictiontotheseinstructions,Yokogawadoesnotguaranteesafety.Pleasegiveyourattentiontothefollowings.

(a) Installation

WARNING

• Theinstrumentmustbeinstalledbyanexpertengineeroraskilledpersonnel.TheproceduresdescribedaboutINSTALLATIONarenotpermittedfor operators.

• Incaseofhighprocesstemperature,careshouldbetakennottoburnyourselfbecausethesurfaceofbodyandcasereachesahightemperature.

• Theinstrumentinstalledintheprocessisunderpressure.Neverloosentheprocessconnectorboltstoavoidthedangerousspoutingofprocessfluid.

• Duringdrainingcondensatefromthepressuredetectorsection,takeappropriatecaretoavoidcontactwiththeskin,eyesorbody,orinhalationofvapors,iftheaccumulatedprocessfluidmaybetoxicorotherwiseharmful.

• Whenremovingtheinstrumentfromhazardousprocesses,avoidcontactwiththefluidandtheinteriorofthemeter.

• Allinstallationshallcomplywithlocalinstallationrequirement and local electrical code.

(b) Wiring

WARNING

• Theinstrumentmustbeinstalledbyanexpertengineeroraskilledpersonnel.TheproceduresdescribedaboutWIRINGarenotpermittedforoperators.

• Pleaseconfirmthatvoltagesbetweenthepowersupplyandtheinstrumentbeforeconnectingthepowercablesandthatthecablesarenotpoweredbeforeconnecting.

Page 4: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<1. Introduction> 3

IM01C25A01-01E

(c) Operation

WARNING

• Wait5min.afterpoweristurnedoff,beforeopeningthecovers.

• Donotopenthecoverinwetweatherorhumidenvironment.Ifthecoverisopened,statedenclosureprotectionisnotapplicable.

(d) Maintenance

WARNING

• Pleasedonotcarryoutexceptbeingwrittentomaintenancedescriptions.Whentheseproceduresareneeded,pleasecontactnearestYOKOGAWAoffice.

• Careshouldbetakentopreventthebuildupofdrift,dustorothermaterialonthedisplayglassandnameplate.Incaseofitsmaintenance,softanddryclothisused.

(e) Explosion Protected Type Instrument

WARNING

• Usersofexplosionproofinstrumentsshouldreferfirsttosection2.4(InstallationofanExplosionProtectedInstrument)ofthismanual.

• ForTIISflameprooftypeinstruments,besuretoread“INSTALLATIONANDOPERATINGPRECAUTIONSFORTIISFLAMEPROOFEQUIPMENT”attheendofthismanual.

• Theuseofthisinstrumentisrestrictedtothosewhohavereceivedappropriatetraininginthedevice.

• Takecarenottocreatesparkswhenaccessingtheinstrumentorperipheraldevicesinahazardouslocation.

(f) Modification

WARNING

• Yokogawawillnotbeliableformalfunctionsordamageresultingfromanymodificationmadetothisinstrumentbythecustomer.

(g) Product Disposal

Theinstrumentshouldbedisposedofinaccordancewithlocalandnationallegislation/regulations.

(h) Authorized Representative in EEA

InrelationtotheCEMarking,TheauthorizedrepresentativeforthisproductintheEEA(EuropeanEconomicArea)is:YokogawaEuropeB.V.Euroweg2,3825HDAmersfoort,TheNetherlands

1.2 Warranty• Thewarrantyshallcovertheperiodnotedonthe

quotationpresentedtothepurchaseratthetimeofpurchase.Problemsoccurredduringthewarrantyperiodshallbasicallyberepairedfreeofcharge.

• Incaseofproblems,thecustomershouldcontacttheYokogawarepresentativefromwhichtheinstrumentwaspurchased,orthenearestYokogawaoffice.

• Ifaproblemariseswiththisinstrument,pleaseinformusofthenatureoftheproblemandthecircumstancesunderwhichitdeveloped,includingthemodelspecificationandserialnumber.Anydiagrams,dataandotherinformationyoucanincludeinyourcommunicationwillalsobehelpful.

• ResponsiblepartyforrepaircostfortheproblemsshallbedeterminedbyYokogawabasedonourinvestigation.

• ThePurchasershallbeartheresponsibilityforrepaircosts,evenduringthewarrantyperiod,ifthemalfunctionisdueto:

- Improperand/orinadequatemaintenancebythepurchaser.

- Failureordamageduetoimproperhandling,useorstoragewhichisoutofdesignconditions.

- UseoftheproductinquestioninalocationnotconformingtothestandardsspecifiedbyYokogawa,orduetoimpropermaintenanceoftheinstallation location.

- FailureordamageduetomodificationorrepairbyanypartyexceptYokogawaoranapprovedrepresentativeofYokogawa.

- Malfunctionordamagefromimproperrelocationoftheproductinquestionafterdelivery.

- Reasonofforcemajeuresuchasfires,earthquakes,storms/floods,thunder/lightening,orothernaturaldisasters,ordisturbances,riots,warfare,orradioactivecontamination.

Trademarks:• ‘DPharp’,‘EJX’,‘EJA’,‘FieldMate’and‘BRAIN

TERMINAL’areregisteredtrademarksofYokogawaElectricCorporation.Companynamesandproductnamesusedinthismaterialareregisteredtrademarksortrademarksoftheirrespectiveowners.

• Inthismanual,trademarksorregisteredtrademarksarenotmarkedwith™or®.

1

Introduction

Page 5: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<1. Introduction> 4

IM01C25A01-01E

1.3 ATEX DocumentationThisisonlyapplicabletothecountriesinEuropeanUnion.

GB

DK

I

E

NL

SF

P

F

D

S

LT

LV

PL

EST

SLO

H

BG

RO

M

CZ

SK

GR

Page 6: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 5

IM01C25A01-01E

2. Handling CautionsWhenthetransmitterisdelivered,visuallycheckthemtomakesurethatnodamageoccurredduringshipment.AlsocheckthatalltransmittermountinghardwareshowninFigure2.1isincluded.Ifthetransmitterwasorderedwithoutthemountingbracketorwithouttheprocessconnector,thetransmittermountinghardwareisnotincluded.

Table 2.1 Applicable Model Code for Mounting Hardware

Applicable model Suffixcode Part name Qty

EJ110EJ120EJ130EJX910A EJX930A

Process connections 1,2,3and4

Processconnectorbolt 4Process connector 2

Process connector gasket 2

EJ210EJ310EJ430EJ440

Process connections 1,2,3and4

Processconnectorbolt 2Process connector 1Process connector gasket 1

EJ110EJ120EJ130EJ310EJ430EJ440EJ118EJ438EJ115EJX910A EJX930A

Mountingbracket B,D,G,J,KandM *

U-bolt 1

U-boltnut 2

Mountingbracket (Lorflattype) 1

Transmitter mounting bolt 4

EJ110

Mounting bracketM(Formeasurement spancodeotherthanF)

U-bolt 1U-boltnut 2Mountingbracket 1Transmitter mounting bolt 2

EJ510EJ530EJX610A EJX630A

Mountingbracket FandL

U-bolt(LandS) 1 ea.U-boltnut(LandS) 2 ea.

Mountingbracket 1

EJX910A EJX930A

Externaltemperature input B,CandD RTDcable 1

Externaltemperature input 1,2,3and4 Cablegland 2

EJ210EJ438 Optioncode/TF1

Teflonfilm 1Fluorinated oil 1

EJ118 Optioncode/TF1Teflonfilm 2Fluorinated oil 2

*: FormeasurementspancodeF.

EJX910AEJX930A -

1234

1234BCD

-

BDGJKM

EJ110EJ120EJ130EJ310EJ430EJ440

-

1234

-

BDGJKM

- - BJ

EJ210

1234

- -

EJ510EJ530EJX610AEJX630A

EJ118EJ438

FL - -

F0201.ai

BDJK

EJ115 - -

Mounting bracket(Flat type)

F0202.ai

Teflon film

Fluorinated oil

BoltProcess connectorProcess connectorGasket

U-bolt nut

U-bolt

Mounting bracket(L type)

Transmitter mounting bolt

Cable gland and RTD cable(EJX910A and EJX930A only)

U-bolt nut (L)

Mounting bracket

U-bolt (L)

U-bolt (S)

U-bolt nut (S)

Figure 2.1 Transmitter Mounting Hardware

Handling C

autions

2

Page 7: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 6

IM01C25A01-01E

2.1 ModelandSpecificationsCheck

Themodelnameandspecificationsareindicatedonthenameplateattachedtothecase.

F0203.ai

Figure 2.2 Name Plate

2.2 Selecting the Installation Location

Thetransmitterisdesignedtowithstandsevereenvironmentalconditions.However,toensurethatitwillprovideyearsofstableandaccurateperformance,takethefollowingprecautionswhenselectingtheinstallationlocation.

(a)AmbientTemperatureAvoidlocationssubjecttowidetemperaturevariationsorasignificanttemperaturegradient.Ifthelocationisexposedtoradiantheatfromplantequipment,provideadequatethermalinsulationand/orventilation.

(b)AmbientAtmosphere Donotinstallthetransmitterinacorrosive

atmosphere.Ifthiscannotbeavoided,theremustbeadequate ventilation as well as measures to prevent theleakingofrainwaterandthepresenceofstandingwaterintheconduits.

(c)ShockandVibration Althoughthetransmitterisdesignedtoberelatively

resistanttoshockandvibration,aninstallationsiteshouldbeselectedwherethisiskepttoaminimum.

(d)InstallationofExplosion-protectedTransmitters Anexplosion-protectedtransmittersiscertifiedfor

installationinahazardousareacontainingspecificgastypes.Seesubsection2.4“InstallationofanExplosion-ProtectedInstrument.”

2.3 Pressure Connection

WARNING

• Neverloosentheprocessconnectorboltswhenaninstrumentisinstalledinaprocess.Thedeviceisunderpressure,andalossofsealcanresultinasuddenanduncontrolledreleaseofprocessfluid.

• Whendrainingtoxicprocessfluidsthathavecondensedinsidethepressuredetector,takeappropriatestepstopreventthecontactofsuchfluidswiththeskinoreyesandtheinhalationofvaporsfromthesefluids.

Thefollowingprecautionsmustbeobservedinordertosafelyoperatethetransmitterunderpressure.

(a)Makesurethattheprocessconnectorboltsaretightenedfirmly.

(b)Makesurethattherearenoleaksintheimpulsepiping.

(c) Neverapplyapressurehigherthanthespecifiedmaximumworkingpressure.

2.4 Installation of an Explosion-Protected Instrument

Ifacustomermakesarepairormodificationtoanintrinsicallysafeorexplosionproofinstrumentandtheinstrumentisnotrestoredtoitsoriginalcondition,itsintrinsicallysafeorexplosionproofconstructionmaybecompromisedandtheinstrumentmaybehazardoustooperate.PleasecontactYokogawabeforemakinganyrepairormodificationtoaninstrument.

CAUTIONThisinstrumenthasbeentestedandcertifiedasbeingintrinsicallysafeorexplosionproof.Pleasenotethatsevererestrictionsapplytothisinstrument’sconstruction,installation,externalwiring,maintenanceandrepair.Afailuretoabidebytheserestrictionscouldmaketheinstrumentahazardtooperate.

WARNING

Maintainingthesafetyofexplosionproofequipmentrequiresgreatcareduringmounting,wiring,andpiping. Safety requirements also place restrictions on maintenanceandrepair.Pleasereadthefollowingsections very carefully.

Page 8: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 7

IM01C25A01-01E

WARNING

Therangesettingswitchmustnotbeusedinahazardousarea.

IMPORTANTForcombinedapprovaltypesOnceadeviceofmultipleapprovaltypeisinstalled,itshouldnotbere-installedusinganyotherapprovaltypes.Applyapermanentmarkinthecheckboxoftheselectedapprovaltypeonthecertificationlabelonthetransmittertodistinguishitfromunusedapprovaltypes.

2.4.1 FM Approval

a. FM Intrinsically Safe for HART/BRAIN Protocol Type (Except for EJX90A)

CautionforFMintrinsicallysafetype.(Followingcontentsrefer“DOC.No.IFM022-A12”)

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/FS1areapplicableforuseinhazardouslocations.

• ApplicableStandard:FM3600,FM3610,FM3611,FM3810

• IntrinsicallySafeforClassI,Division1,GroupsA,B,C&D.ClassII,Division1,GroupsE,F&GandClassIII,Division1,ClassI,Zone0inHazardousLocations,AExiaIIC

• NonincendiveforClassI,Division2,GroupsA,B,C&D.ClassII,Division2,GroupsF&GandClassI,Zone2,GroupsIIC,inHazardousLocations.

• Enclosure:Type4X• TemperatureClass:T4• Ambienttemperature:–60to60°C

Note2. EntityParameters• IntrinsicallySafeApparatusParameters [GroupsA,B,C,D,E,FandG]

Vmax=30V Ci=6nFImax=200mA Li=0µHPmax=1W

* Associated Apparatus Parameters (FMapprovedbarriers)

Voc≤30V Ca>6nFIsc≤200mA La>0µHPmax≤1W

• IntrinsicallySafeApparatusParameters [GroupsC,D,E,FandG]

Vmax=30V Ci=6nFImax=225mA Li=0µHPmax=1W

* Associated Apparatus Parameters (FMapprovedbarriers)

Voc≤30V Ca>6nFIsc≤225mA La>0µHPmax≤1W

• EntityInstallationRequirements Vmax≥VocorUoorVt,Imax≥IscorIoorIt, Pmax(orPo)≤Pi,CaorCo≥Ci+Ccable, LaorLo≥Li+Lcable

Note3. Installation• Barriermustbeinstalledinanenclosurethat

meetstherequirementsofANSI/ISAS82.01.• Controlequipmentconnectedtobarriermustnot

useorgeneratemorethan250VrmsorVdc.• InstallationshouldbeinaccordancewithANSI/ISA

RP12.6“InstallationofIntrinsicallySafeSystemsforHazardous(Classified)Locations”andtheNationalElectricCode(ANSI/NFPA70).

• TheconfigurationofassociatedapparatusmustbeFMRCApproved.

• Dust-tightconduitsealmustbeusedwheninstalledinaClassII,III,GroupE,FandGenvironments.

• Associatedapparatusmanufacturer’sinstallationdrawingmustbefollowedwheninstallingthisapparatus.

• Themaximumpowerdeliveredfromthebarriermustnotexceed1W.

• Noteawarninglabelworded“SUBSTITUTIONOFCOMPONENTSMAYIMPAIRINTRINSICSAFETY,”and“INSTALLINACCORDANCEWITHDOC.No.IFM022-A12”

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidFactoryMutualIntrinsicallysafeandNonincendiveApproval.

F0204.ai

Class I, II, III, Division 1,Groups A, B, C, D, E, F, GClass 1, Zone 0 in Hazardous (Classified) Locations AEx ia IICPressure Transmitters Safety Barrier

Supply

Hazardous Location Nonhazardous Location

General PurposeEquipment

+

+

+

+

[Intrinsically Safe]

Handling C

autions

2

Page 9: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 8

IM01C25A01-01E

F0205.ai

Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

Class I, II, Division 2,Groups A, B, C, D, F, GClass 1, Zone 2, Group IIC,in Hazardous (Classified)Locations

Not UseSafety Barrier

[Nonincendive]

General PurposeEquipment

b. FM Intrinsically Safe for Fieldbus Type (Except for EJX90A)

EJX/EJA-ESeriespressuretransmitterswithoptionalcode/FS15areapplicableforuseinhazardouslocations.• Applicablestandard:

FM3600,FM3610,FM3611,FM3810, ANSI/NEMA250,IEC60079-27

• FMIntrinsicallySafeApproval[EntityModel] ClassI,II&III,Division1,GroupsA,B,C,D,E,F

&G,TemperatureClassT4Ta=60°C,Type4XandClassI,Zone0,AExiaIIC,TemperatureClassT4Ta=60°C,Type4X

[FISCOModel] ClassI,II&III,Division1,GroupsA,B,C,D,E,F

&G,TemperatureClassT4Ta=60°C,Type4XandClassI,Zone0,AExiaIIC,TemperatureClassT4Ta=60°C,Type4X

• NonincendiveApproval ClassI,Division2,GroupsA,B,C&D

TemperatureClassT4Ta=60°C,Type4XandClassII,Division2,GroupsF&GTemperatureClassT4Ta=60°C,Type4XandClassI,Zone2,GroupIIC,TemperatureClassT4Ta=60°C,Type4X

• ElectricalConnection:1/2NPTfemale,M20female

• CautionforFMIntrinsicallysafetype.(Followingcontentsreferto“DOC.No.IFM024-A12p.1,p.2,p.3,p.4-1andp.4-2.”)

IFM024-A12

Installation Diagram for Intrinsically Safe (Division 1 Installation)

Non-Hazardous Location

Hazardous Location

F0223.ai

Terminator

Safety Barrier

Field Instruments

PressureTransmitter

Field Instruments

+−

+−

+−

Terminator

+

−+

Note1. BarriermustbeinstalledinanenclosurethatmeetstherequirementsofANSI/ISA61010-1.

Note2. ControlequipmentconnectedtotheAssociated Apparatus must not use or generate more than250VrmsorVdc.

Note3. InstallationshouldbeinaccordancewithANSI/ISA12.06.01“InstallationofIntrinsicallySafeSystemsforHazardous(Classified)Locations”andtheNationalElectricalCode(ANSI/NFPA70) Sections 504 and 505.

Note4. TheconfigurationofAssociatedApparatusmustbeFactoryMutualResearchApprovedunderFISCOConcept.

Note5. AssociatedApparatusmanufacturer’sinstallationdrawingmustbefollowedwheninstallingthisequipment.

Note6. NorevisiontodrawingwithoutpriorFactoryMutualResearchApproval.

Note7. TerminatormustbeFMApproved.

Note8. Noteawarninglabelworded“SUBSTITUTIONOFCOMPONENTSMAYIMPAIRINTRINSICSAFETY”,and“INSTALLINACCORDANCEDOC.NO.IFM024-A12P.1TO4.”

Page 10: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 9

IM01C25A01-01E

Electrical Data:

•Rating1(Entity) ForGroupsA,B,C,D,E,F,andGorGroupIIC MaximumInputVoltageVmax:24V MaximumInputCurrentImax:250mA MaximumInputPowerPmax:1.2W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0µHor•Rating2(FISCO) ForGroupsA,B,C,D,E,F,andGorGroupIIC MaximumInputVoltageVmax:17.5V MaximumInputCurrentImax:380mA MaximumInputPowerPmax:5.32W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0µHor•Rating3(FISCO) ForGroupsC,D,E,F,andGorGroupIIB MaximumInputVoltageVmax:17.5V MaximumInputCurrentImax:460mA MaximumInputPowerPmax:5.32W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0µH

Note: Intherating1,theoutputcurrentofthebarriermustbelimitedbyaresistor“Ra”suchthatIo=Uo/Ra.Intherating2or3,theoutputcharacteristicsofthebarriermustbethetypeoftrapezoidwhicharecertifiedastheFISCOmodel(See“FISCORules”).Thesafetybarriermayincludeaterminator.Morethanonefieldinstrumentsmaybeconnectedtothepowersupplyline.

FISCO Rules

TheFISCOConceptallowstheinterconnectionofintrinsincally safe apparatus to associated apparatus notspecificallyexaminedinsuchcombination.Thecriterionforsuchinterconnectionisthatthevoltage(Ui),thecurrent(Ii)andthepower(Pi)whichintrinsicallysafe apparatus can receive and remain intrinsically safe,consideringfaults,mustbeequalorgreaterthanthevoltage(Uo,Voc,Vt),thecurrent(Io,Isc,It)andthepower(Po)whichcanbeprovidedbytheassociatedapparatus (supply unit).

Po≤Pi,Uo≤Ui,Io≤Ii

Inaddition,themaximumunprotectedresidualcapacitance(Ci)andinductance(Li)ofeachapparatus(otherthantheterminators)connectedtothefieldbusmustbelessthanorequalto5nFand10µHrespectively.

Ci≤5nF,Li≤10µH

IneachI.S.fieldbussegmentonlyoneactivesource,normallytheassociatedapparatus,isallowedtoprovidethenecessarypowerforthefieldbussystem.Theallowedvoltage(Uo,Voc,Vt)oftheassociatedapparatususedtosupplythebuscablemustbelimitedtotherangeof14Vdcto17.5Vdc.Allotherequipmentconnected

tothebuscablehastobepassive,meaningthattheapparatusisnotallowedtoprovideenergytothesystem,excepttoaleakagecurrentof50µAforeachconnecteddevice.

Supply unit

Trapezoidalorrectangularoutputcharacteristiconly

Uo=14...17.5V(I.S.maximumvalue)

Ioaccordingtosparktestresultorotherassessment.NospecificationofLo and Coisrequiredonthecertificateorlabel.

Cable

Thecableusedtointerconnectthedevicesneedstocomplywiththefollowingparameters:

LoopresistanceR’:15...150Ω/kmInductanceperunitlength L’:0.4...1mH/kmCapacitanceperunitlengthC’:45...200nF/km.C’=C’line/line+0.5C’line/screen,ifbothlinesarefloatingorC’=C’line/line+C’line/screen,ifthescreenis connected to one line.Lengthofspurcable:max.60mLengthoftrunkcable:max.1km(GroupIIC)or5km(GroupIIB)Lengthofsplice:max.1m

Terminators

AteachendofthetrunkcableanFMapprovedlineterminatorwiththefollowingparametersissuitable:

R=90...100ΩC=0...2.2mF

System evaluations

Thenumberofpassivedeviceliketransmitters,actuators,handheldterminalsconnectedtoasinglebussegmentisnotlimitedduetoI.S.reasons.Furthermore,iftheaboverulesarerespected,theinductanceandcapacitanceofthecableneednottobeconsideredandwillnotimpairtheintrinsicsafetyoftheinstallation.

SAFE AREAHAZARDOUS AREA

F0224.ai

Terminator(FISCO Model)

Ex i

Field Instruments(Passive)

Hand-held-

Terminal

Supply Unit and Safety Barrier(FISCO Model)

Terminator

Data

UU

I

I.S.fieldbussystemcomplyingwithFISCOmodel

Handling C

autions

2

Page 11: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 10

IM01C25A01-01E

Installation Diagram for Nonincendive (Division 2 Installation)

Non-Hazardous location

FM ApprovedAssociated Nonincendive FieldWiring Apparatus Vt or Voc It or Isc Ca La

Hazardous location

F0225.ai

Terminator

General PurposeEquipment

PressureTransmitter

SUPPLY

Terminator

+−

Transmitter+−

Transmitter+−

+ −

+ −

Note1. InstallationshouldbeinaccordancewiththeNationalElectricalCode®(ANSI/NFPA70)Article 500.

Note2. TheconfigurationofAssociatedNonincendiveFieldWiringApparatusmustbeFMApproved.

Note3. ApprovedunderFNICOConcept.

Note4. Dust-tightconduitsealmustbeusedwheninstalledinClassIIandClassIIIenvironments.

Note5. AssociatedApparatusmanufacturer’sinstallationdrawingmustbefollowedwheninstallingthisapparatus.

Note6. NorevisiontodrawingwithoutpriorFMApprovals.

Note7. TerminatormustbeFMApproved.

Note8. Thenonincendivefieldwiringcircuitconceptallowsinterconectionofnonincendivefieldwiringapparatuswithassociatednonincendivefieldwiringapparatus,usinganyofthewiringmethodspermittedforunclassifiedlocations.

Note9. Installationrequirements; Vmax≥VocorVt Imax=seenote10. Ca≥Ci+Ccable La≥Li+Lcable

Note10. Forthiscurrentcontrolledcircuit,theparameter(Imax 3 )isnotrequiredandneednotbealignedwithparameter(Isc 3 )ofthebarrierorassociatednonincendivefieldwiringapparatus.

Note11. Ifordinarylocationwiringmethodsareused,thetransmittershallbeconnectedtoFMApprovedassociatednon-incendivefieldwiringapparatus.

Electricaldata: Vmax:32V Ci:3.52nF Li:0µH

FNICO Rules

TheFNICOConceptallowstheinterconnectionofnonincendivefieldwiringapparatustoassociatednonincendivefieldwiringapparatusnotspecificallyexaminedinsuchcombination.Thecriterionforsuchinterconnectionisthatthevoltage(Vmax),thecurrent(Imax)andthepower(Pmax)whichnonincendivefieldwiringapparatuscanreceiveandremainnonincendive,consideringfaults,mustbeequalorgreaterthanthevoltage(Uo,VocorVt),thecurrent(Io,IscorIt)andthepower(Po)whichcanbeprovidedbytheassociatednonincendivefieldwiringapparatus(supplyunit).Inadditionthemaximumunprotectedresidualcapacitance(Ci)andinductance(Li)ofeachapparatus(otherthanterminators)connectedtotheFieldbusmustbelessthanor equal to 5nF and 10uH respectively.

IneachN.I.Fieldbussegmentonlyoneactivesource,normallytheassociatednonincendivefieldwiringapparatus,isallowedtoprovidethenecessarypowerfortheFieldbussystem.Theallowedvoltage(Uo,VocorVt)oftheassociatednonincendivefieldwiringapparatususedtosupplythebuscablemustbelimitedtotherange14Vdcto17.5Vdc.Allotherequipmentconnectedtothebuscablehastobepassive,meaningthattheapparatusisnotallowedtoprovideenergytothesystem,exceptaleakagecurrentof50ÉAforeachconnecteddevice.Separately powered equipment needs galvanic isolation toensurethenonincendivefieldwiringFieldbuscircuitremains passive.

Cable

Thecableusedtointerconnectthedevicesneedstocomplywiththefollowingparameters:

LoopresistanceR’:15...150Ω/kmInductanceperunitlengthL’:0.4...1mH/kmCapacitanceperunitlengthC’:80....200nF/kmC’=C’line/line+0.5C’line/screen,ifbothlinesarefloatingorC’=C’line/line+C’line/screen,ifthescreenisconnectedtooneline.Lengthofspurcable:max.30mLengthoftrunkcable:max.1kmLengthofsplice:max=1m

Terminators

AttheendofeachtrunkcableanFMApprovedlineterminatorwiththefollowingparametersissuitable:

R=90...100Ω C=0....2.2uF

Page 12: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 11

IM01C25A01-01E

c. FM Intrinsically Safe for Fieldbus Type for EJX90A

EJXmultivariabletransmitterwithoptionalcode /FS15areapplicableforuseinhazardouslocations.• Applicablestandard:FM3600,FM3610,FM3611,

FM3810,ANSI/NEMA250,IEC60079-27• FMIntrinsicallySafeApproval [EntityModel] ClassI,II&III,Division1,GroupsA,B,C,D,F&

G,TemperatureClassT4Ta=60ºC,Type4XandClassI,Zone0,AExiaIIC,TemperatureClassT4Ta=60ºC,Type4X

[FISCOModel] ClassI,II&III,Division1,GroupsA,B,C,D,F&

G,TemperatureClassT4Ta=60ºC,Type4XandClassI,Zone0,AExiaIIC,TemperatureClassT4Ta=60ºC,Type4X

• NonincendiveApproval ClassI,Division2,GroupsA,B,C&D

TemperatureClassT4Ta=60ºC,Type4XandClassII,Division2,GroupsF&GTemperatureClassT4Ta=60ºC,Type4XandClassI,Zone2,GroupIIC,TemperatureClassT4Ta=60ºC,Type4XandClassIII,Division1,TemperatureClassT4Ta=60ºC,Type4X

• ElectricalConnection:1/2NPTfemale,M20female

• CautionforFMIntrinsicallysafetype.(Followingcontentsreferto“DOC.No.IFM026-A12p.1top.4.”)

IFM026-A12

Installation Diagram for Intrinsically Safe (Division 1 Installation)

Non-Hazardous Location

Hazardous Location

F0226.ai

Terminator

Safety Barrier

Field Instruments

PressureTransmitter

Field Instruments

+–

+–

+–

Terminator

+

–+

Note1. BarriermustbeinstalledinanenclosurethatmeetstherequirementsofANSI/ISA61010-1.

Note2. ControlequipmentconnectedtotheAssociatedApparatusmustnotuseorgeneratemorethan250 Vrms or Vdc.

Note3. InstallationshouldbeinaccordancewithANSI/ISA12.06.01“InstallationofIntrinsicallySafeSystemsforHazardous(Classified)Locations”andtheNationalElectricalCode(ANSI/NFPA70) Sections 504 and 505.

Note4. TheconfigurationofAssociatedApparatusmustbeFactoryMutualResearchApprovedunderFISCOConcept.

Note5. AssociatedApparatusmanufacturer’sinstallationdrawingmustbefollowedwheninstallingthisequipment.

Note6. NorevisiontodrawingwithoutpriorFactoryMutualResearchApproval.

Note7. TerminatormustbeFMApproved.

Note8. Noteawarninglabelworded“SUBSTITUTIONOFCOMPONENTSMAYIMPAIRINTRINSICSAFETY”,and“INSTALLINACCORDANCEDOC.NO.IFM026-A12P.1TO4.”

Electrical Data:

•Rating1(Entity) ForGroupsA,B,C,D,F,andGorGroupIIC MaximumInputVoltageVmax:24V MaximumInputCurrentImax:250mA MaximumInputPowerPmax:1.2W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0μHor•Rating2(FISCO) ForGroupsA,B,C,D,F,andGorGroupIIC MaximumInputVoltageVmax:17.5V MaximumInputCurrentImax:380mA MaximumInputPowerPmax:5.32W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0μHor•Rating3(FISCO) ForGroupsC,D,F,andGorGroupIIB MaximumInputVoltageVmax:17.5V MaximumInputCurrentImax:460mA MaximumInputPowerPmax:5.32W MaximumInternalCapacitanceCi:3.52nF MaximumInternalInductanceLi:0μH

SensorCircuit:Uo=6.51V,Io=4mA, Po=6mW,Co=34µF,Lo=500mH

Note: Intherating1,theoutputcurrentofthebarriermustbelimitedbyaresistor“Ra”suchthatIo=Uo/Ra.Intherating2or3,theoutputcharacteristicsofthebarriermustbethetypeoftrapezoidwhicharecertifiedastheFISCOmodel(See“FISCORules”).Thesafetybarriermayincludeaterminator.Morethanonefieldinstrumentsmaybeconnectedtothepowersupplyline.

Handling C

autions

2

Page 13: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 12

IM01C25A01-01E

FISCORules

TheFISCOConceptallowstheinterconnectionofintrinsincally safe apparatus to associated apparatus notspecificallyexaminedinsuchcombination.Thecriterionforsuchinterconnectionisthatthevoltage(Ui),thecurrent(Ii)andthepower(Pi)whichintrinsicallysafe apparatus can receive and remain intrinsically safe,consideringfaults,mustbeequalorgreaterthanthevoltage(Uo,Voc,Vt),thecurrent(Io,Isc,It)andthepower(Po)whichcanbeprovidedbytheassociatedapparatus (supply unit).

Po≤Pi,Uo≤Ui,Io≤Ii

Inaddition,themaximumunprotectedresidualcapacitance(Ci)andinductance(Li)ofeachapparatus(otherthantheterminators)connectedtothefieldbusmustbelessthanorequalto5nFand10µHrespectively.

Ci≤5nF,Li≤10µH

IneachI.S.fieldbussegmentonlyoneactivesource,normallytheassociatedapparatus,isallowedtoprovidethenecessarypowerforthefieldbussystem.Theallowedvoltage(Uo,Voc,Vt)oftheassociatedapparatususedtosupplythebuscablemustbelimitedtotherangeof14Vdcto17.5Vdc.Allotherequipmentconnectedtothebuscablehastobepassive,meaningthattheapparatusisnotallowedtoprovideenergytothesystem,excepttoaleakagecurrentof50µAforeachconnecteddevice.

Supply unit

Trapezoidalorrectangularoutputcharacteristiconly

Uo=14...17.5V(I.S.maximumvalue)

Ioaccordingtosparktestresultorotherassessment.Nospecificationof Lo and Coisrequiredonthecertificateorlabel.

Cable

Thecableusedtointerconnectthedevicesneedstocomplywiththefollowingparameters:

LoopresistanceR’:15...150Ω/kmInductanceperunitlengthL’:0.4...1mH/kmCapacitanceperunitlengthC’:45...200nF/km.C’=C’line/line+0.5C’line/screen,ifbothlinesarefloatingorC’=C’line/line+C’line/screen,ifthescreenis connected to one line.Lengthofspurcable:max.60mLengthoftrunkcable:max.1km(GroupIIC)or5km(GroupIIB)Lengthofsplice:max.1m

Terminators

AteachendofthetrunkcableanFMapprovedlineterminatorwiththefollowingparametersissuitable:

R=90...100ΩC=0...2.2mF

System evaluations

Thenumberofpassivedeviceliketransmitters,actuators,handheldterminalsconnectedtoasinglebussegmentisnotlimitedduetoI.S.reasons.Furthermore,iftheaboverulesarerespected,theinductanceandcapacitanceofthecableneednottobeconsideredandwillnotimpairtheintrinsicsafetyoftheinstallation.

SAFE AREAHAZARDOUS AREA

F0227.ai

Terminator(FISCO Model)

Ex i

Field Instruments(Passive)

Hand-held-

Terminal

Supply Unit and Safety Barrier(FISCO Model)

Terminator

Data

UU

I

I.S.fieldbussystemcomplyingwithFISCOmodel

InstallationDiagramforNonincendive (Division 2 Installation)

Non-Hazardous Location

FM ApprovedAssociated Nonincendive FieldWiring Apparatus Vt or Voc It or Isc Ca La

Hazardous Location

F0228.ai

Terminator

General PurposeEquipment

PressureTransmitter

SUPPLY

Terminator

+–

Transmitter+–

Transmitter+–

+ –

+ –

Note1. InstallationshouldbeinaccordancewiththeNationalElectricalCode®(ANSI/NFPA70)Article 500.

Note2. TheconfigurationofAssociatedNonincendiveFieldWiringApparatusmustbeFMApproved.

Note3. ApprovedunderFNICOConcept.

Page 14: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 13

IM01C25A01-01E

Note4. Dust-tightconduitsealmustbeusedwheninstalledinClassIIandClassIIIenvironments.

Note5. AssociatedApparatusmanufacturer’sinstallationdrawingmustbefollowedwheninstallingthisapparatus.

Note6. NorevisiontodrawingwithoutpriorFMApprovals.

Note7. TerminatormustbeFMApproved.

Note8. Thenonincendivefieldwiringcircuitconceptallowsinterconectionofnonincendivefieldwiringapparatuswithassociatednonincendivefieldwiringapparatus,usinganyofthewiringmethodspermittedforunclassifiedlocations.

Note9. Installationrequirements; Vmax≥VocorVt Imax=seenote10. Ca≥Ci+Ccable La≥Li+Lcable

Note10. Forthiscurrentcontrolledcircuit,theparameter(Imax)isnotrequiredandneednotbealignedwithparameter(Isc)ofthebarrierorassociatednonincendivefieldwiringapparatus.

Note11. Ifordinarylocationwiringmethodsareused,thetransmittershallbeconnectedtoFMApprovedassociatednonincendivefieldwiringapparatus.

Electricaldata: Vmax:32V Ci:3.52nF Li:0µH

FNICORules

TheFNICOConceptallowstheinterconnectionofnonincendivefieldwiringapparatustoassociatednonincendivefieldwiringapparatusnotspecificallyexaminedinsuchcombination.Thecriterionforsuchinterconnectionisthatthevoltage(Vmax),thecurrent(Imax)andthepower(Pmax)whichnonincendivefieldwiringapparatuscanreceiveandremainnonincendive,consideringfaults,mustbeequalorgreaterthanthevoltage(Uo,VocorVt),thecurrent(Io,IscorIt)andthepower(Po)whichcanbeprovidedbytheassociatednonincendivefieldwiringapparatus(supplyunit).Inadditionthemaximumunprotectedresidualcapacitance(Ci)andinductance(Li)ofeachapparatus(otherthanterminators)connectedtotheFieldbusmustbelessthanor equal to 5nF and 20uH respectively.

IneachN.I.Fieldbussegmentonlyoneactivesource,normallytheassociatednonincendivefieldwiringapparatus,isallowedtoprovidethenecessarypowerfortheFieldbussystem.Theallowedvoltage(Uo,VocorVt)oftheassociatednonincendivefieldwiringapparatususedtosupplythebuscablemustbelimitedtotherange

14Vdcto17.5Vdc.Allotherequipmentconnectedtothebuscablehastobepassive,meaningthattheapparatusisnotallowedtoprovideenergytothesystem,exceptaleakagecurrentof50µAforeachconnecteddevice.Separately powered equipment needs galvanic isolation toensurethenonincendivefieldwiringFieldbuscircuitremains passive.

Cable

Thecableusedtointerconnectthedevicesneedstocomplywiththefollowingparameters:

LoopresistanceR’:15...150Ω/kmInductanceperunitlengthL’:0.4...1mH/kmCapacitanceperunitlengthC’:45....200nF/kmC’=C’line/line+0.5C’line/screen,ifbothlinesarefloatingorC’=C’line/line+C’line/screen,ifthescreen is connected to one line.Lengthofspurcable:max.60mLengthoftrunkcable:max.1km(GroupIIC)or5km(GroupIIB)Lengthofsplice:max=1m

Terminators

AttheendofeachtrunkcableanFMApprovedlineterminatorwiththefollowingparametersissuitable:

R=90...100ΩC=0....2.2mF

d. FM Explosionproof

CautionforFMexplosionprooftype.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/FF1or/V1Fareapplicableforuseinhazardouslocations.

• ApplicableStandard:FM3600,FM3615,FM3810,ANSI/NEMA250

• ExplosionproofforClassI,Division1,GroupsB,Cand D.

• Dust-ignitionproofforClassII/III,Division1,GroupsE,FandG.

• Enclosure:Type4X• TemperatureClass:T6• AmbientTemperature:–40to60°C• SupplyVoltage:42Vdcmax.

32Vdcmax.(FOUNDATIONFieldbusandPROFIBUSPAtype)9to28Vdc,27mW(LowPowertype)9to30Vdc,250mW(RS485ModbusCommunicationType)

• Outputsignal:4to20mA15 mA (FOUNDATIONFieldbusandPROFIBUSPAtype)1to5V(LowPowertype)RS485Modbus(RS485ModbusCommunicationType)

Handling C

autions

2

Page 15: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 14

IM01C25A01-01E

Note2. Wiring• AllwiringshallcomplywithNationalElectrical

CodeANSI/NFPA70andLocalElectricalCodes.• WheninstalledinDivision1,“FACTORYSEALED,

CONDUITSEALNOTREQUIRED.”• WiringconnectionforoutputsignalcodeQ(Low

Powertype)shallfollowthediagrambelow.

F0218.ai

Three-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Four-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Note3. Operation• Keepthe“WARNING”nameplateattachedtothe

transmitter. WARNING:OPENCIRCUITBEFORE

REMOVINGCOVER.FACTORYSEALED,CONDUITSEALNOTREQUIRED.INSTALLINACCORDANCEWITHTHEUSERSMANUALIM01C25.

• Takecarenottogeneratemechanicalsparkingwhenaccessingtotheinstrumentandperipheraldevicesinahazardouslocation.

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidFactoryMutualExplosionproofApproval.

e. FM Intrinsically Safe and Explosion Proof Combination for HART/BRAIN Protocol Type

EJX/EJA-ESeriespressuretransmitterswithoptionalcode/FU1or/V1U1canbeselectedthetypeofprotection(FMIntrinsicallySafeorFMExplosionproof)foruseinhazardouslocations.

Note1. Fortheinstallationofthistransmitter,onceaparticulartypeofprotectionisselected,anyothertypeofprotectioncannotbeused.Theinstallationmustbeinaccordancewiththedescriptionaboutthetypeofprotectioninthisinstruction manual.

Note2. Inordertoavoidconfusion,unnecessarymarkingiscrossedoutonthelabelotherthantheselectedtypeofprotectionwhenthetransmitter is installed.

2.4.2 CSACertification

a. CSA Intrinsically Safe for HART/BRAIN Protocol Type (Except for EJX90A)

CautionforCSAIntrinsicallysafeandnonincendivetype.(Followingcontentsreferto“DOCNo.ICS013-A13”)

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/CS1areapplicableforuseinhazardouslocations.

Certificate:1606623[ForCSAC22.2]• ApplicableStandard:C22.2No.0,C22.2No.0.4,

C22.2No.25,C22.2No.94,C22.2No.157, C22.2No.213,C22.2No.60079-0, C22.2No.61010-1,C22.2No.61010-2-030

• IntrinsicallySafeforClassI,Division1,GroupsA,B,C&D,ClassII,Division1,GroupsE,F&G,ClassIII,Division1

• NonincendiveforClassI,Division2,GroupsA,B,C&D,ClassII,Division2,GroupsF&G,ClassIII,Division 1

• Enclosure:Type4X• Temp.Code:T4• Amb.Temp.:–50*to60°C *–15°Cwhen/HEisspecified.• ProcessTemperature:120°Cmax.[ForCSAE60079]• ApplicableStandard:CAN/CSAE60079-11,

CAN/CSAE60079-15,IEC60529:2001• ExiaIICT4,ExnLIICT4• AmbientTemperature:–50to60°C• Max.ProcessTemp.:120°C• Enclosure:IP66/IP67

Note2. EntityParameters• Intrinsicallysaferatingsareasfollows: MaximumInputVoltage(Vmax/Ui)=30V MaximumInputCurrent(Imax/Ii)=200mA MaximumInputPower(Pmax/Pi)=0.9W MaximumInternalCapacitance(Ci)=10nF MaximumInternalInductance(Li)=0µH• Type"n"orNonincendiveratingsareasfollows: MaximumInputVoltage(Vmax/Ui)=30V MaximumInternalCapacitance(Ci)=10nF MaximumInternalInductance(Li)=0µH• InstallationRequirements Uo≤Ui,Io≤Ii,Po≤Pi, Co≥Ci+Ccable,Lo≥Li+Lcable Voc≤Vmax,Isc≤Imax, Ca≥Ci+Ccable,La≥Li+Lcable Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaare

parametersofbarrier.

Page 16: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 15

IM01C25A01-01E

Note3. Installation• Inanysafetybarreirusedoutputcurrentmust

belimitedbyaresistor'R'suchthatIo=Uo/RorIsc=Voc/R.

• ThesafetybarriermustbeCSAcertified.• Inputvoltageofthesafetybarriermustbeless

than250Vrms/Vdc.• InstallationshouldbeinaccordancewithCanadian

ElectricalCodePartIandLocalElectricalCode.• Dust-tightconduitsealmustbeusedwhen

installedinClassIIandIIIenvironments.• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationandYokogawaCorporationofAmericaisprohibitedandwillvoidCanadianStandardsIntrinsicallysafeandnonincendiveCertification.

F0206.ai

Class I, II, III, Division 1,Groups A, B, C, D, E, F, G

Pressure Transmitters Safety Barrier

Supply

Hazardous Location Nonhazardous Location

General PurposeEquipment

+

+

+

– +

[Intrinsically Safe]

Group IIC, Zone 0

F0207.ai

Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

Class I, II, Division 2,Groups A, B, C, D, F, GClass III, Division 1.

Not UseSafety Barrier

[Nonincendive]

CSA Certified Equipment([nL] or nonincendive)

Group IIC, Zone 2

b. CSA Intrinsically Safe for Fieldbus Type (Except for EJX90A)

EJX/EJA-ESeriespressuretransmitterswithoptionalcode/CS15areapplicableforuseinhazardouslocations.• Certificate:1689689• Applicablestandard:C22.2No.0,C22.2No.0.4,

C22.2No.25,C22.2No.94,C22.2No.157, C22.2No.213,C22.2No.61010-1, C22.2No.61010-2-030,C22.2No.60079-0,

CAN/CSAE60079-0,CAN/CSAE60079-11, CAN/CSAE60079-15,IEC60529

• CSAIntrinsicallySafeApproval ClassI,Division1,GroupsA,B,C,&D;ClassII,

Division1,GroupsE,F&G;ClassIII;ExiaIICT4 AmbientTemperature:–40*to60°C(–40*to

140°F)Encl.Type4X,IP66/IP67 *–15°Cwhen/HEisspecified.

• CSANonincendiveApproval ClassI,Division2,GroupsA,B,C,&D;ClassII,

Division2,GroupsF&G;ClassIII;ExnLIICT4 AmbientTemperature:–40*to60°C(–40*to

140°F)Encl.Type4X,IP66/IP67 *–15°Cwhen/HEisspecified.

Caution for CSA Intrinsically Safe Type. (Following Contents Refer to “DOC. No. ICS018)

Installation Diagram for Intrinsically Safe (Division 1 Installation)

Non-Hazardous Location

Hazardous Location

F0229.ai

Terminator

Safety Barrier

Field Instruments

PressureTransmitter

Field Instruments

+–

+–

+–

Terminator

+

–+

Note1. ThesafetybarriermustbeCSAcertified.

Note2. Inputvoltageofthesafetybarriermustbelessthan250Vrms/Vdc.

Note3. InstallationshouldbeinaccordancewithCanadianElectricalCodePartIandlocalElectricalCode.

Note4. DonotalterdrawingwithoutauthorizationfromCSA.

Electrical Data:

•Rating1(Entity) ForGroupsA,B,C,D,E,F,andGorGroupIIC Ui(vmax)=24Vdc Ii(Imax)=250mA Pi(Pmax)=1.2W Ci=3.52nF Li=0μHor

Handling C

autions

2

Page 17: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 16

IM01C25A01-01E

•Rating2(FISCO) ForGroupsA,B,C,D,E,F,andGorGroupIIC Ui(vmax)=17.5Vdc Ii(Imax)=380mA Pi(Pmax)=5.32W Ci=3.52nF

Li=0μHor• Rating3(FISCO) ForGroupsC,D,E,F,andGorGroupIIB Ui(vmax)=17.5Vdc Ii(Imax)=460mA Pi(Pmax)=5.32W Ci=3.52nF Li=0μHInstallationrequirements; Po≤PiUo≤UiIo≤Ii, Co≥Ci+CcableLo≥Li+Lcable Vmax≥VocImax≥Isc Ca≥Ci+CcableLa≥Li+Lcable Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaareparameters

ofbarrier.

Caution for CSA Non-incendive Type. (Following contents refer to “DOC. No. ICS018)

Installation Diagram for Non-incendive or Type of protection “n” (Division 2 Installation)

Non-Hazardous location

Hazardous location

F0230.ai

Terminator

CSA CertifiedEquipment [nL]

PressureTransmitter

SUPPLY

Terminator

+–

Transmitter+–

Transmitter+–

+ –

+ –

Note1. InstallationshouldbeinaccordancewithCanadianElectricalCodePartIandlocalElectricalCode.

Note2. Dust-tightconduitsealmustbeusedwheninstalledinclassIIandIIIenvironments.

Note3. DonotalterdrawingwithoutauthorizationfromCSA.

Electrical Data:

•Rating(includingFNICO) UiorVmax=32V Ci=3.52nF Li=0μH

c. CSA Explosionproof Type

CautionforCSAexplosionprooftype.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/CF1or/V1Fareapplicableforuseinhazardouslocations.

• Certificate:2014354• ApplicableStandard:C22.2No.0,

C22.2No.0.4,C22.2No.0.5,C22.2No.25, C22.2No.30,C22.2No.94,C22.2No.61010-1, C22.2No.61010-2-030,C22.2No.60079-0, C22.2No.60079-1

• Explosion-proofforClassI,GroupsB,CandD.• Dustignition-proofforClassII/III,GroupsE,Fand

G.• Enclosure:Type4X• TemperatureCode:T6...T4• ExdIICT6...T4• Enclosure:IP66/IP67• MaximumProcessTemperature:120°C(T4),

100°C(T5),85°C(T6)• AmbientTemperature:–50*to75°C(T4),

–50*to80°C(T5),–50*to75°C(T6) *–15°Cwhen/HEisspecified.• SupplyVoltage:42Vdcmax.

32Vdcmax.(FOUNDATIONFieldbusandPROFIBUSPAtype)9to28Vdc,27mW(LowPowertype)9to30Vdc,250mW(RS485ModbusCommunicationType)

• OutputSignal:4to20mAdc15 mA (FOUNDATIONFieldbusandPROFIBUSPAtype)1to5V(LowPowertype)RS485Modbus(RS485ModbusCommunicationType)

Note2. Wiring• AllwiringshallcomplywithCanadianElectrical

CodePartIandLocalElectricalCodes.• Inhazardouslocation,wiringshallbeinconduitas

showninthefigure.• WARNING: ASEALSHALLBEINSTALLEDWITHIN50cmOF

THEENCLOSURE. UNSCELLEMENTDOITÊTREINSTALLÉÀ

MOINSDE50cmDUBOÎTIER.

Page 18: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 17

IM01C25A01-01E

• WARNING: WHENINSTALLEDINCL.I,DIV2,SEALNOT

REQUIRED. UNEFOISINSTALLÉDANSCLI,DIV2,AUCUN

JOINTN'ESTREQUIS.

Non-hazardous Location Equipment

42 V DC Max. 4 to 20 mA DC Signal

Non-Hazardous Locations

Hazardous Locations Division 1

50 cm Max.

Sealing FittingConduit

TransmitterF0208.ai

Non-Hazardous Locations

Hazardous Locations Division 2

Non-hazardous Location Equipment

42 V DC Max. 4 to 20 mA DC Signal

Sealing Fitting

TransmitterF0209.ai

• Allwiringshallcomplywithlocalinstallationrequirements and local electrical code.

• Inhazardouslocations,thecableentrydevicesshallbeofacertifiedflameprooftype,suitablefortheconditionsofuseandcorrectlyinstalled.

• Unusedaperturesshallbeclosedwithsuitableflameproofcertifiedblankingelements.(Theplugattachedisflameproofcertified.)

• WiringconnectionforoutputsignalcodeQ(LowPowertype)shallfollowthediagrambelow.

F0219.ai

Three-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Four-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Note3. Operation• WARNING: AFTERDE-ENERGIZING,DELAY5MINUTES

BEFOREOPENING. APRÉSPOWER-OFF,ATTENDRE5MINUTES

AVANTD'OUVRIR.• WARNING: WHENAMBIENTTEMPERATURE≥65°C,USE

THEHEAT-RESISTINGCABLES≥90°C. QUANDLATEMPÉRATUREAMBIANTE≥65°C,

UTILISEZDESCÂBLESRÉSISTANTESÁLACHALEUR≥90°C.

• Takecarenottogeneratemechanicalsparkingwhenaccessingtotheinstrumentandperipheraldevicesinahazardouslocation.

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationandYokogawaCorporationofAmericaisprohibitedandwillvoidCanadianStandardsExplosionproofCertification.

d. CSA Intrinsically Safe and Explosion-proof Combination for HART/BRAIN Protocol Type (Except for EJX90A)

EJX/EJA-ESeriespressuretransmitterswithoptionalcode/CU1or/V1U1canbeselectedthetypeofprotection(CSAIntrinsicallySafeorCSAExplosionproof)foruseinhazardouslocations.

Note1. Fortheinstallationofthistransmitter,onceaparticulartypeofprotectionisselected,anyothertypeofprotectioncannotbeused.Theinstallationmustbeinaccordancewiththedescriptionaboutthetypeofprotectioninthisinstruction manual.

Note2. Inordertoavoidconfusion,unnecessarymarkingiscrossedoutonthelabelotherthantheselectedtypeofprotectionwhenthetransmitter is installed.

2.4.3 ATEXCertification

(1) Technical Data

a. ATEX Intrinsically Safe for HART/BRAIN Protocol Type (Except for EJX90A)

CautionforATEXIntrinsicallysafetype.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/KS21forpotentiallyexplosiveatmospheres.

• No.DEKRA11ATEX0228X• ApplicableStandard:

EN60079-0:2009,EN60079-11:2007, EN60079-26:2007,EN61241-11:2006

Handling C

autions

2

Page 19: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 18

IM01C25A01-01E

• TypeofProtectionandMarkingcode:ExiaIICT4Ga

ExiaIIICT85ºCT100ºCT120ºCDb• Group:II• Category:1G,2D• AmbientTemperatureforEPLGa:

–50to60°C• AmbientTemperatureforEPLDb:

–30*to60°C*–15°Cwhen/HEisspecified.

• ProcessTemperature(Tp.):120°Cmax.• MaximumSurfaceTemperatureforEPLDb:

T85°C(Tp.:80°C) T100°C(Tp.:100°C) T120°C(Tp.:120°C)

• Enclosure:IP66/IP67

Note2 ElectricalData• IntypeofexplosionprotectionintrinsicsafetyExia

IICorExiaIIIC,onlyforconnectiontoacertifiedintrinsicallysafecircuitwithfollowingmaximumvalues:

Ui=30V Ii=200mA Pi=0.9W (LinearSource) Maximuminternalcapacitance;Ci=27.6nF Maximuminternalinductance;Li=0µH

Note3. Installation• Refertothecontroldrawing.Allwiringshallcomply

withlocalinstallationrequirements.

Pressure Transmitters

Supply Safety Barrier *1

Nonhazardous Location

[Control Drawing]

Hazardous Location

+

+

F0210.ai

*1:Inanysafetybarriersusedtheoutputcurrentmustbelimitedbyaresistor“R”suchthatIo=Uz/R.

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidDEKRAIntrinsicallysafeCertification.

Note5. SpecialConditionsforSafeUse

WARNING

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminium,ifitismountedinanareawheretheuseofcategory1Gapparatusisrequired,itmustbeinstalledsuch,that,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Electrostaticchargemaycauseanexlosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• IncaseoftheenclosureofthePressureTransmitterwithpaintlayers,ifitismountedinanareawheretheuseofcategory2Dapparatusisrequired,itshallbeinstalledinsuchawaythattheriskfromelectrostaticdischargesandpropagatingbrushdischargescausedbyrapidflowofdustisavoided.

• TosatisfyIP66orIP67,applywaterproofglandstotheelectricalconnectionport.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyEN60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

b. ATEX Intrinsically Safe for HART Protocol Type for EJX90A

CautionforATEXIntrinsicallysafetype.

Note1. EJXmultivariabletransmitterwithoptionalcode/KS2areapplicableforuseinhazardouslocations.

• No.KEMA06ATEX0037X• ApplicableStandard:

EN50014:1997,EN50020:2002, EN50284:1999,EN50281-1-1:1998

• TypeofProtectionandMarkingcode:EExiaIICT4

• Group:II• Category:1G,1D• AmbientTemperatureforgas-proof:

–50*to60°C *–15°Cwhen/HEisspecified.• ProcessTemperature(Tp.):120°Cmax.• MaximumSurfaceTemperaturefordust-proof:

T85°C(Tamb.:–40*to60°C,Tp.:80°C) T100°C(Tamb.:–40*to60°C,Tp.:100°C) T120°C(Tamb.:–40*to60°C,Tp.:120°C)

*–15°Cwhen/HEisspecified.• Enclosure:IP66andIP67

Page 20: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 19

IM01C25A01-01E

Note2. ElectricalData[Supply/Outputcircuit(terminals+and-)] IntypeofexplosionprotectionintrinsicsafetyEEx

iaIIC,onlyforconnectiontoacertifiedintrinsicallysafecircuitwithfollowingmaximumvalues: Ui=30V Ii=200mA Pi=0.9W

Effectiveinternalcapacitance;Ci=10nF Effectiveinternalinductance;Li=0mH[PulseOutputcircuit(terminals-andpulse)] IntypeofexplosionprotectionintrinsicsafetyEEx

iaIIC,onlyforconnectiontoacertifiedintrinsicallysafecircuitwithfollowingmaximumvalues: Ui=30V

Ii=200mA Pi=0.9W Ci=10nF Li=0mH[Externaltemperatureinputcircuit(connector)] IntypeofexplosionprotectionintrinsicsafetyEEx

iaIIC,withfollowingmaximumvalues: Uo=30V

Io=95.4mA Po=468mW

Co=11nF Lo=3.9mH

Note3. Installation• Allwiringshallcomplywithlocalinstallation

requirements.(Refertotheinstallationdiagram)• Whentheanalogandpulsecircuitsareconnected

toseparatebarriers,itshallbeassuredthatthevoltagedifferencebetweentheseoutputcircuitsisnotmorethan30V.

• Whenusedinapotentiallyexplosiveatmosphere,Requiringtheuseofapparatusofequipmentcategory1Dor2D,certifiedcableentrydevicesshallbeusedthataresuitablefortheapplicationand correctly installed.

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidKEMAIntrinsicallysafeCertification.

Note5. SpecialConditionsforSafeUse• InthecasewheretheenclosureofthePressure

Transmitterismadeofaluminium,ifitismountedinanareawheretheuseofcategory1Gapparatusisrequired,itmustbeinstalledsuch,that,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

Pressure Transmitters

Supply Safety Barrier*1

Nonhazardous Location

[Installation Diagram] (for EJX910A and EJX930A)

Hazardous Location

+

+

F0211.ai

Sensor outRTD sensor *2

Without pulse output

With pulse output

Pressure Transmitters

Supply

Safety Barrier*1

Nonhazardous LocationHazardous Location

+

– +

+

Sensor outRTD sensor *2

Safety Barrier*1

+

Pulse

*1: • Inanysafetybarriersusedtheoutputcurrentmustbelimitedbyaresistor“R”suchthatIo=Uz/R.

• ThesafetybarriershallbecertifiedbynotifybodyEUasATEX.

• Whenusingnonisolationbarrier,connect toISearthingsystem.

*2: • RTDsensorispreparedbytheuser. • Thesensorsignallinemustwithstandatestvoltageof

500VAC.

WARNING

TosatisfyIP66orIP67,applywaterproofglandstotheelectrical connection port.

Handling C

autions

2

Page 21: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 20

IM01C25A01-01E

c. ATEX Intrinsically Safe for Fieldbus Type (Except for EJX90A)

CautionforATEXIntrinsicallysafetype.

Note1. EJX/EJA-Eseriespressuretransmitterswithoptionalcode/KS26areapplicableforuseinhazardouslocations.

• No.KEMA04ATEX1116X• ApplicableStandard:EN60079-0:2009, EN60079-11:2007/EN60079-11:2012,

EN60079-26:2007,EN60079-27:2008, EN61241-11:2006

Note2. RatingsTypeofProtectionandMarkingCode:

ExiaIIC/IIBT4Ga ExiaIIICT85°CT100°CT120°CDb

Group:IICategory:1G,2DAmbientTemperatureforEPLGa:–40to60°CAmbientTemperatureforEPLDb:–30*to60°C

*–15°Cwhen/HEisspecified.MaximumProcessTemperature(Tp.):120°CMaximumSurfaceTemperatureforEPLDb.

T85°C(Tp.:80°C) T100°C(Tp.:100°C) T120°C(Tp.:120°C)

AmbientHumidity: 0to100%(Nocondensation)

DegreeofProtectionoftheEnclosure: IP66/IP67

Electrical Data• WhencombinedwithTrapezoidalandRectangular

outputcharacteristicFISCOmodelIICbarrier Ui=17.5V,Ii=380mA,Pi=5.32W, Ci=3.52nF,Li=0μH• WhencombinedwithLinearcharacteristicbarrier Ui=24V,Ii=250mA,Pi=1.2W, Ci=3.52nF,Li=0μH• WhencombinedwithTrapezoidalorRectangular

outputcharacteristicFISCOmodelIIBbarrier Ui=17.5V,Ii=460mA,Pi=5.32W, Ci=3.52nF,Li=0μH

Note3. Installation• Allwiringshallcomplywithlocalinstallation

requirements.(Refertotheinstallationdiagram)

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidDEKRAIntrinsicallysafeCertification.

Note5. SpecialConditionsforSafeUse

WARNING

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminium,ifitismountedinanareawheretheuseofcategory1Gapparatusisrequired,itmustbeinstalledsuch,thatevenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminum,ifitismountedinanareawheretheuseofcategory2Dapparatusisrequired,itshallbeinstalledinsuchawaythattheriskfromelectrostaticdischargesandpropagatingbrushdischargescausedbyrapidflowofdustisavoided.

• TosatisfyIP66orIP67,applywaterproofglandstotheelectricalconnectionport.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyEN60079-11.

Thismustbetakenintoaccountwheninstallingtheapparatus.

Note6. InstallationInstructions

Non-Hazardous Location

Hazardous Location

F0231.ai

Terminator

Safety Barrier

Transmitter

PressureTransmitter

Transmitter

+−

+−

+−

Terminator

+

−+

[Installation Diagram]

SUPPLY

Page 22: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 21

IM01C25A01-01E

• Intherating1(*1),theoutputcurrentofthebarriermustbelimitedbyaresistor‘Ra’suchthatIo=Uo/Ra.

• Intherating2(*2),theoutputofthebarriermustbethecharacteristicsofthetrapezoidortherectangleandthistransmittercanbeconnectedtoFieldbusequipmentwhichareinaccordingtotheFISCOmodel.

• Theterminatorsmaybebuiltinbyabarrier.• Morethanonetransmittermaybeconnectedto

thepowersupplyline.• Theterminatorandthesafetybarriershallbe

certified.Electricaldata:MaximumInputVoltageUi:24V

*1:Rating 1

MaximumInputCurrentIi:250mAMaximumInputPowerPi:1.2WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5V

*2:Rating 2

MaximumInputCurrentIi:380mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5VMaximumInputCurrentIi:460mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

d. ATEX Intrinsically Safe for Fieldbus Type for EJX90A

CautionforATEXIntrinsicallysafetype.

Note1. EJXmultivariabletransmitterwithoptionalcode/KS26areapplicableforuseinhazardouslocations:

• No.KEMA06ATEX0278X• ApplicableStandard:EN60079-0:2009,

EN60079-11:2012,EN60079-26:2007

Note2. RatingsTypeofProtectionandMarkingCode:

ExiaIIC/IIBT4Ga ExiaIIICT85°CT100°CT120°CDb

Group:IICategory:1G,2D

AmbientTemperatureforEPLGa: –40to60°C

AmbientTemperatureforEPLDb: –30*to60°C

*–15°Cwhen/HEisspecified.MaximumProcessTemperature(Tp.):120°CMaximumSurfaceTemperatureforEPLDb.

T85°C(Tp.:80°C) T100°C(Tp.:100°C) T120°C(Tp.:120°C)

AmbientHumidity: 0to100%(Nocondensation)DegreeofProtectionoftheEnclosure:

IP66/IP67Electrical Data• WhencombinedwithTrapezoidalorRectanglar

outputcharacteristicFISCOmodelIICbarrier[Supplycircuit(terminals+and-)]

Ui=17.5V,Ii=380mA,Pi=5.32W,Ci=3.52nF,Li=0µH

[Sensorcircuit]Uo=7.63V,Io=3.85mA,Po=0.008W,Co=4.8µF,Lo=100mH• WhencombinedwithLinearcharacteristicbarrier

[Supplycircuit(terminals+and-)]Ui=24V,Ii=250mA,Pi=1.2W,Ci=3.52nF,Li=0µH

[Sensorcircuit]Uo=7.63V,Io=3.85mA,Po=0.008W,Co=4.8µF,Lo=100mH• WhencombinedwithTrapezoidalorRectanglar

outputcharacteristicFISCOmodelIIBbarrier[Supplycircuit(terminals+and-)]

Ui=17.5V,Ii=460mA,Pi=5.32W,Ci=3.52nF,Li=0µH

[Sensorcircuit]Uo=7.63V,Io=3.85mA,Po=0.008W,Co=4.8µF,Lo=100mH

Note3. Installation• Allwiringshallcomplywithlocalinstallation

requirements.(Refertotheinstallationdiagram)

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidDEKRAIntrinsicallysafeCertification.

Note5. SpecialConditionsforSafeUse

Handling C

autions

2

Page 23: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 22

IM01C25A01-01E

WARNING

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminium,ifitismountedinanareawheretheuseofcategory1Gapparatusisrequired,itmustbeinstalledsuch,thatevenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminum,ifitismountedinanareawheretheuseofcategory2Dapparatusisrequired,itshallbeinstalledinsuchawaythattheriskfromelectrostaticdischargesandpropagatingbrushdischargescausedbyrapidflowofdustisavoided.

• TosatisfyIP66orIP67,applywaterproofglandstotheelectricalconnectionport.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyEN60079-11.

Thismustbetakenintoaccountwheninstallingtheapparatus.

Note6. Installationinstructions

Non-Hazardous Location

Hazardous Location

F0232.ai

Terminator

Safety Barrier

Transmitter

PressureTransmitter

Transmitter

+−

+−

+−

Terminator

+

−+

SUPPLY

RTDPt100.3wire

[Installation Diagram]

• Intherating1(*1),theoutputcurrentofthebarriermustbelimitedbyaresistor‘Ra’suchthatIo=Uo/Ra.

• Intherating2(*2),theoutputofthebarriermustbethecharacteristicsofthetrapezoidortherectangleandthistransmittercanbeconnectedtoFieldbusequipmentwhichareinaccordingtotheFISCOmodel.

• Theterminatorsmaybebuiltinbyabarrier.• Morethanonetransmittermaybeconnectedto

thepowersupplyline.• Theterminatorandthesafetybarriershallbe

certified.Electricaldata:Supply circuitMaximumInputVoltageUi:24V

*1:Rating 1

MaximumInputCurrentIi:250mAMaximumInputPowerPi:1.2WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5V

*2:Rating 2

MaximumInputCurrentIi:380mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5VMaximumInputCurrentIi:460mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

Sensor circuitMaximumOutputVoltageUo:7.63VMaximumOutputCurrentIo:3.85mAMaximumOutputPowerPo:0.008WMaximumInternalCapacitanceCo:4.8μFMaximumInternalInductanceLo:100mH

• RTDsensorispreparedbytheuser. Thesensorsignallinemustsuitedatestvoltageof

500Vac.

e. ATEX Flameproof Type

CautionforATEXflameprooftype.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/KF22or/V1Fareapplicableforuseinhazardouslocations.

• No.KEMA07ATEX0109X• ApplicableStandard:EN60079-0:2009,

EN60079-1:2007,EN60079-31:2009• TypeofProtectionandMarkingCode: ExdIICT6...T4Gb,ExtbIIICT85°CDb• Group:II• Category:2G,2D• Enclosure:IP66/IP67• TemperatureClassforgas-poof:

T6,T5,andT4• AmbientTemperatureforgas-proof:

–50to75°C(T6),–50to80°C(T5),and –50to75°C(T4)

• MaximumProcessTemperature(Tp.)forgas-proof:

85°C(T6),100°C(T5),and120°C(T4)

Page 24: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 23

IM01C25A01-01E

• MaximumSurfaceTemperaturefordust-proof:T85°C(Tamb.:–30*to75°C,Tp.:85°C) *–15°Cwhen/HEisspecified.

Note2. ElectricalData• Supplyvoltage:42Vdcmax.

32Vdcmax.(FOUNDATIONFieldbusandPROFIBUSPAtype)9to28Vdc,27mW(LowPowertype)9to30Vdc,250mW(RS485ModbusCommunicationType)

• Outputsignal:4to20mA15 mA (FOUNDATIONFieldbusandPROFIBUSPAtype)1to5V(LowPowertype)RS485Modbus(RS485ModbusCommunicationType)

Note3. Installation• Allwiringshallcomplywithlocalinstallation

requirement.• Cableglands,adaptersand/orblankingelements

withasuitableIPratingshallbeofExdIIC/ExtbIIICcertifiedbyATEXandshallbeinstalledsoastomaintainthespecificdegreeofprotection(IPCode)oftheequipment.

• WiringconnectionforoutputsignalcodeQ(LowPowertype)shallfollowthediagrambelow.

F0220.ai

Three-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Four-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Note4. Operation• Keepthe“WARNING”labelattachedtothe

transmitter. WARNING:AFTERDE-ENERGIZING,DELAY

5MINUTESBEFOREOPENING.WHENTHEAMBIENTTEMP.≥65°C,USEHEAT-RESISTINGCABLEANDCABLEGLAND≥90°C.

• Takecarenottogeneratemechanicalsparkingwhenaccessingtotheinstrumentandperipheraldevicesinahazardouslocation.

Note5. SpecialConditionsforSafeUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• InthecasewheretheenclosureofthePressureTransmitterismadeofaluminium,ifitismountedinanareawheretheuseofcategory2Dapparatusisrequired,itshallbeinstalledinsuchawaythattheriskfromelectrostaticdischargesandpropagatingbrushdischargescausedbyrapidflowofdustisavoided.

• TheinstrumentmodificationorpartsreplacementbyotherthananauthorizedRepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidthecertification.

f. ATEX Intrinsically Safe and ATEX Flameproof Combination for HART/BRAIN Protocol Type (Except for EJX90A)

EJX/EJA-ESeriespressuretransmitterswithoptionalcode/KU22or/V1U1canbeselectedthetypeofprotectionATEXFlameproof,IntrinsicallySafe.Exia,orExicforuseinhazardousarea.

Note1. Fortheinstallationofthistransmitter,onceaparticulartypeofprotectionisselected,anyothertypeofprotectioncannotbeused.Theinstallationmustbeinaccordancewiththedescriptionaboutthetypeofprotectioninthisuser’smanual.

Note2. Forcombinedapprovaltypes Once a device of multiple approval type is installed,itshouldnotbere-installedusinganyotherapprovaltypes.Applyapermanentmarkinthecheckboxoftheselectedapprovaltypeonthecertificationlabelonthetransmittertodistinguishitfromunusedapprovaltypes.

ATEX Intrinsically Safe Ex ic

CautionforATEXintrinsicallysafeExic• ApplicableStandard:

EN60079-0:2009/EN60079-0:2012, EN60079-11:2012

• TypeofProtectionandMarkingCode: II3GExicIICT4Gc

• AmbientTemperature:–30*to+60°C*–15°Cwhen/HEisspecified.

• AmbientHumidity: 0to100%(Nocondensation)

• MaximumProcessTemperature:120°C• IPCode:IP66• Ambientpollutiondegree:2• Overvoltagecategory:I

Handling C

autions

2

Page 25: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 24

IM01C25A01-01E

Note1. ElectricalData Ui=30V Ci=27.6nF Li=0µH

Note2. Installation• Allwiringshallcomplywithlocalinstallation

requirements.(refertothecontroldrawing)• Cableglands,adaptersand/orblankingelements

shallbeofEx“n”,Ex“e”orEx“d”andshallbeinstalledsoastomaintainthespecifieddegreeofprotection(IPCode)ofthetransmitters.

Note3. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwill void ATEX intrinsically safe.

Pressure Transmitters

AssociatedApparatus

Nonhazardous Area

[Control Drawing]

Hazardous Area

+

F0212.ai

Note4. SpecificConditionsofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyEN60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

g. ATEX Intrinsically Safe Ex ic for Fieldbus Type (Except for EJX90A)

CautionforATEXIntrinsicallysafeExic.EJX/EJA-ESeriespressuretransmitterswithoptionalcode/KN26areapplicableforuseinhazardouslocations.• ApplicableStandard:

EN60079-0:2009/EN60079-0:2012, EN60079-11:2012

• TypeofProtectionandMarkingCode: II3GExicIICT4Gc

• AmbientTemperature:–30*to+60°C*–15°Cwhen/HEisspecified.

• MaximumProcessTemperature:120°C• AmbientHumidity:

0to100%(Nocondensation)• IPCode:IP66• Ambientpollutiondegree:2• Overvoltagecategory:I

Note1. ElectricalData Ui=32V Ci=3.52nF Li=0µH

Note2. Installation• Allwiringshallcomplywithlocalinstallation

requirements.(refertothecontroldrawing)• Wheninstallingthetransmitterin“ic”FISCO

systemorFNICOsystem,followtheinstallationrequirementsofeachsystem.

• Cableglands,adaptersand/orblankingelementsshallbeofEx“n”,Ex“e”orEx“d”andshallbeinstalledsoastomaintainthespecifieddegreeofprotection(IPCode)ofthetransmitters.

Note3. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwill void ATEX intrinsically safe.

Associated ApparatusTransmitter

Nonhazardous Area

[Control Drawing]

Hazardous Area

+

F0233.ai

• AbovedrawingshowstheinstallationofEntitysystem. Wheninstallingthetransmittersin“ic”FISCOsystemorFNICOsystem,followtheinstallationrequirementsofeachsystem.

Note4. SpecificConditionsofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegerenationofeletrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyEN60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

Page 26: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 25

IM01C25A01-01E

(2) Electrical Connection

Amarkindicatingtheelectricalconnectiontypeisstampedneartheelectricalconnectionport.Thesemarksareasfollowed.

F0214.ai

Location of the mark

Screw Size Marking

ISO M20 × 1.5 female

ANSI 1/2 NPT female

M

N or W

(3) Installation

WARNING

• Allwiringshallcomplywithlocalinstallationrequirementsandthelocalelectricalcode.

• ThereisnoneedforconduitsealinDivision1andDivision2hazardouslocationsbecausethisproductissealedatthefactory.

(4) Operation

WARNING

• OPENCIRCUITBEFOREREMOVINGCOVER.INSTALLINACCORDANCEWITHTHISUSER’SMANUAL

• Takecarenottogeneratemechanicalsparkingwhenaccesstotheinstrumentandperipheraldevicesinahazardouslocation.

(5) Maintenance and Repair

WARNING

TheinstrumentmodificationorpartsreplacementbyotherthananauthorizedRepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidthecertification.

(6) Name Plate

F0215-1.ai

Name plate

Tag plate for flameproof type

DWARNING

No. KEMA 07ATEX0109 XEx d IIC T6...T4 Gb, Ex tb IIIC T85°C DbEnlcosure : IP66/IP67TEMP. CLASS T6 T5 T4MAX PROCESS TEMP.(Tp.) 85 100 120 °CTamb. -50 to 75 80 75 °C T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)

AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°CPOTENTIAL ELECTROSTATIC CHARGING HAZARD

*3

F0215-2.ai

Tag plate for intrinsically safe Ex ia for HART/BRAIN

WARNING

D

No. DEKRA 11ATEX 0228 X Ex ia IIC T4 Ga Ta: -50 TO 60°CEx ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°CIP66/IP67MAX. PROCESS TEMP.(Tp.) 120°CT85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH

POTENTIAL ELECTROSTATIC CHARGING HAZARD- SEE USER’S MANUAL

[Except for EJX90A]

Tag plate for intrinsically safe Ex ia for Fieldbus

WARNING

No. KEMA 04ATEX1116 X Ex ia IIC/IIB T4 Ga Ta:-40 to 60°C Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) to 60°C MAX PROCESS TEMP.(Tp.):120°CT85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)Enclosure: IP66/IP67FISCO field device(IIC/IIB)Entity parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0μH

WARNING

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

D

Tag plate for intrinsically safe Ex ic for FieldbusEx ic IIC T4 GcIP66Tamb -30(-15) TO 60°C MAX. PROCESS TEMP. 120°CUi=32V, Ci=3.52nF, Li=0µH

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

*3

Tag plate for intrinsically safe Ex ic for HART/BRAIN

WARNING

Ex ic IIC T4 GcIP66Tamb -30(-15) TO 60°C MAX. PROCESS TEMP. 120°CUi=30V, Ci=27.6nF, Li=0µH

POTENTIAL ELECTROSTATIC CHARGING HAZARD- SEE USER’S MANUAL

*3

Handling C

autions

2

Page 27: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 26

IM01C25A01-01E

F0215-3.ai

Tag plate for intrinsically safe for HART/BRAIN

D

No. KEMA 06ATEX0037 XEEx ia IIC T4IP66 and IP67Tamb. -50(-15) to 60°C MIN Tamb.for DUST -40(-15°C)MAX PROCESS TEMP.(Tp) 120°CT85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)Supply/Pulse circuit Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=10 nF, Li=0 mHSensor circuitUo=30 V, Io=95.4 mA, Po=468 mW, Co=11 nF, Lo=3.9 mH

Tag plate for intrinsically safe Ex ia for FieldbusNo. KEMA 06ATEX0278 XEx ia IIC/IIB T4 Ga Ta: -40 to 60°CEx ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°CMAX PROCESS TEMP.(Tp.): 120°CT85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C)ENCLOSURE: IP66/IP67Supply circuitFISCO field device(IIC/IIB)Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µHSensor circuitUo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH

POTENTIAL ELECTROSTATIC CHARGING HAZARD-SEE USER'S MANUAL.

*3

[EJX90A]

*3

MODEL:Specifiedmodelcode.STYLE:Stylecode.SUFFIX:Specifiedsuffixcode.SUPPLY:Supplyvoltage.OUTPUT:Outputsignal.MWP:Maximumworkingpressure.CALRNG:Specifiedcalibrationrange.NO.:Serialnumberandyearofproduction*1.TOKYO180-8750JAPAN:Themanufacturernameandtheaddress*2.

*1:Thefirstnumberinthesecondblockof“NO.”columnisthelastonenumberoftheproductionyear.

second block

NO. 91K819857 132 7

The year 2011

*2:“180-8750”isazipcodewhichrepresentsthe following address.

2-9-32Nakacho,Musashino-shi,TokyoJapan

*3:TheidentificationnumberofNotifiedBody.

2.4.4 IECExCertificationModelEJXSeriespressuretransmitterswithoptionalcode/SU21canbeselectedthetypeofprotection(IECExIntrinsicallySafeExia,Exicorflameproof)foruseinhazardouslocations.EJXSeriespressuretransmitterswithoptionalcode /SS26canbeselectedthetypeofprotection(IECExintrinsicallysafeExiaorExic)foruseinhazardouslocations.EJXSeriespressuretransmitterswithoptionalcode/SU2canbeselectedthetypeofprotection(IECExIntrinsicallySafe/typenorflameproof)foruseinhazardouslocations.

Note1. Fortheinstallationofthistransmitter,onceaparticulartypeofprotectionisselected,anyothertypeofprotectioncannotbeused.Theinstallationmustbeinaccordancewiththedescriptionaboutthetypeofprotectioninthisinstruction manual.

Note2. Forcombinedapprovaltypes,onceadeviceofmultipleapprovaltypeisinstalled,itshouldnotbere-installedusinganyotherapprovaltypes.Applyapermanentmarkinthecheckboxoftheselectedapprovaltypeonthecertificationlabelonthetransmittertodistinguishitfromunusedapproval types.

a. IECEx Intrinsically Safe Ex ia for HART/BRAIN Protocol Type (Except for EJX90A)

CautionforIECExIntrinsicallysafeExia.

Note1. EJX/EJA-Eseriespressuretransmitterswithoptionalcode/SU21areapplicableforuseinhazardouslocations

• No.IECExDEK11.0081X• ApplicableStandard:IEC60079-0:2011,

IEC60079-11:2011,IEC60079-26:2006• ExiaIICT4Ga• AmbientTemperature:–50to60°C• Max.ProcessTemp.:120°C

Note2. ElectricalDataMaximumInputVoltage(Ui)=30VMaximumInputCurrent(Ii)=200mAMaximumInputPower(Pi)=0.9W(linearsource)MaximumInternalCapacitance(Ci)=27.6nFMaximumInternalInductance(Li)=0μH

Note3. Installation• Inanysafetybarrierusedoutputcurrentmustbe

limitedbyaresistor‘R’suchthatIo=Uz/R.• ThesafetybarriermustbeIECExcertified.• Inputvoltageofthesafetybarriermustbeless

than250Vrms/Vdc.• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidIECExcertification.

F0236.ai

EJX/EJA-E Series Pressure Transmitters

IECEx certifiedSafety Barrier

Supply

Hazardous Location Nonhazardous Location

+

+

[Ex ia]

Group IIC, Zone 0

(*1)*1: When using non isolation barrier,

connect (*1) to IS barrier system.

Page 28: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 27

IM01C25A01-01E

Note4. SpecificConditionofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• Inthecasewheretheenclosureofthepressuretransmitterismadeofaluminum,ifitismountedinanareawheretheuseofEPLGaequipmentisrequired,itshallbeinstalledinsuchawaythat,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyIEC60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

b. IECEx Intrinsically Safe Ex ic for HART/BRAIN Protocol Type (Except for EJX90A)

CautionforIECExIntrinsicallysafeExic.

Note1. EJX/EJA-Eseriespressuretransmitterswithoptionalcode/SU21areapplicableforuseinhazardouslocations

• No.IECExDEK13.0061X• ApplicableStandard:IEC60079-0:2011,

IEC60079-11:2011• ExicIICT4Gc• AmbientTemperature:–30*to60°C

*-15°Cwhen/HEisspecified.• Max.ProcessTemp.:120°C• IPCode:IP66• OvervoltageCategory:I

Note2. ElectricalDataMaximumInputVoltage(Ui)=30VMaximumInternalCapacitance(Ci)=27.6nFMaximumInternalInductance(Li)=0μH

Note3. Installation• Thepressuretransmitterisallowedtobeinstalled

in“nL”systems,onconditionthattheoutputparametersof“nL”source(associatedenergy-limitedapparatus)aresuitabletotheabovementionedinputparametersofthepressuretransmitterandthecableparameters.

• Cableglands,adaptersand/orblankingelementsshallbeofEx“n”,Ex“e”orEx“d”andshallbeinstalledsoastomaintainthespecifieddegreeofprotectionoftheequipment.

• TheinstrumentmodificationorpartsreplacementbyotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidIECExcertification.

F0237.ai

EJX/EJA-E Series Pressure Transmitters

Associated apparatus

Supply

Hazardous Location Nonhazardous Location

+

+

[Ex ic]

Note4. SpecificConditionofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• TheapparatusisnotcapableofdielectricstrengthtestsrequiredbyIEC60079-11. Thismustbetakenintoaccountwheninstallingtheapparatus.

c. IECEx Intrinsically Safe Ex ia for Fieldbus Type (Except for EJX90A)

CautionforIECExIntrinsicallysafeExia.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/SS26areapplicableforuseinhazardouslocations.

• No.IECExDEK12.0016X• ApplicableStandard:IEC60079-0:2011,

IEC60079-11:2011,IEC60079-26:2006• ExiaIIC/IIBT4Ga• AmbientTemperature:–40to60°C• Max.ProcessTemp.:120°C

Note2. ElectricalData• Intrinsicallysaferatingsareasfollows:[Entity] MaximumInputVoltage(Ui)=24V MaximumInputCurrent(Ii)=250mA MaximumInputPower(Pi)=1.2W MaximumInternalCapacitance(Ci)=3.52nF MaximumInternalInductance(Li)=0μH[FISCOIIC] MaximumInputVoltage(Ui)=17.5V MaximumInputCurrent(Ii)=380mA MaximumInputPower(Pi)=5.32W MaximumInternalCapacitance(Ci)=3.52nF MaximumInternalInductance(Li)=0μH[FISCOIIB] MaximumInputVoltage(Ui)=17.5V MaximumInputCurrent(Ii)=460mA MaximumInputPower(Pi)=5.32W MaximumInternalCapacitance(Ci)=3.52nF MaximumInternalInductance(Li)=0μH

Handling C

autions

2

Page 29: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 28

IM01C25A01-01E

Note3. Installation

Non-Hazardous Location

Hazardous Location

F0238.ai

Terminator

Safety Barrier

Field Instruments

PressureTransmitter

Field Instruments

+–

+–

+–

Terminator

+

–+

[Ex ia]

• Intherating1(*1),theoutputcurrentofthebarriermustbelimitedbyaresistor‘Ra’suchthatIo=Uo/Ra.

• Intherating2(*2),theoutputofthebarriermustbethecharacteristicsofthetrapezoidortherectangleandthistransmittercanbeconnectedtoFieldbusequipmentwhichareinaccordingtotheFISCOmodel.

• Theterminatorsmaybebuiltinbyabarrier.• Morethanonetransmittermaybeconnectedto

thepowersupplyline.• Theterminatorandthesafetybarriershallbe

certified.Electricaldata:MaximumInputVoltageUi:24V

*1:Rating 1

MaximumInputCurrentIi:250mAMaximumInputPowerPi:1.2WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5V

*2:Rating 2

MaximumInputCurrentIi:380mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

orMaximumInputVoltageUi:17.5VMaximumInputCurrentIi:460mAMaximumInputPowerPi:5.32WMaximumInternalCapacitanceCi:3.52nFMaximumInternalInductanceLi:0μH

Note4. SpecificConditionofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• Inthecasewheretheenclosureofthepressuretransmitterismadeofaluminum,ifitismountedinanareawheretheuseofEPLGaequipmentisrequired,itshallbeinstalledinsuchawaythat,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyIEC60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

d. IECEx Intrinsically Safe Ex ic for Fieldbus Type (Except for EJX90A)

CautionforIECExIntrinsicallysafeExic.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/SS26areapplicableforuseinhazardouslocations.

• No.IECExDEK13.0064X• ApplicableStandard:IEC60079-0:2011,

IEC60079-11:2011• ExicIICT4Gc• AmbientTemperature:–30*to60°C

*-15°Cwhen/HEisspecified.• Max.ProcessTemp.:120°C• IPCode:IP66• OvervoltageCategory:I

Note2. ElectricalData• Intrinsicallysaferatingsareasfollows: MaximumInputVoltage(Ui)=32V MaximumInternalCapacitance(Ci)=3.52nF MaximumInternalInductance(Li)=0μH

Note3. Installation• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationandwillvoidIECExIntrinsicallysafeandtypencertification.

• Thepressuretransmitterisallowedtobeinstalledin“nL”systems,onconditionthattheoutputparametersof“nL”source(associatedenergy-limitedapparatus)aresuitabletotheabovementionedinputparametersofthepressuretransmitterandthecableparameters.

Page 30: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 29

IM01C25A01-01E

• Wheninstallingthetransmitterin“ic”FISCOsystemorFNICOsystem,followtheinstallationrequirementsofeachsystem.

• Cableglands,adaptersand/orblankingelementsshallbeofEx“n”,Ex“e”orEx“d”andshallbeinstalledsoastomaintainthespecifieddegreeofprotectionoftheequipment.

• Formultipletypesofprotection,theselectedExmarkingonthemarkingplateshallbecheckedatthetimeofinstallation.

F0237.ai

EJX/EJA-E Series Pressure Transmitters

Associated apparatus

Supply

Hazardous Location Nonhazardous Location

+

+

[Ex ic]

• Abovedrawingshowstheinstallationofentitysystem.Wheninstallingthetransmitterin“ic”FISCOsystemorFNICOsystem,followtheinstallationrequirementsofeachsystem.

Note4. SpecificConditionofUse

WARNING

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

• Whenthelightningprotectoroptionisspecified,theapparatusisnotcapableofwithstandingthe500VinsulationtestrequiredbyIEC60079-11.Thismustbetakenintoaccountwheninstallingtheapparatus.

e. IECEx Intrinsically Safe / type n for HART/BRAIN Protocol Type (Except for EJX9A)

CautionforIECExIntrinsicallysafeandtypen.

Note1. EJXSeriesdifferential,gauge,andabsolutepressuretransmitterswithoptionalcode/SU2areapplicableforuseinhazardouslocations

• No.IECExCSA05.0005• ApplicableStandard:IEC60079-0:2000,

IEC60079-11:1999,IEC60079-15:2001• ExiaIICT4,ExnLIICT4• AmbientTemperature:–50to60°C• Max.ProcessTemp.:120°C• Enclosure:IP66/IP67

Note2. ElectricalData• Intrinsicallysaferatingsareasfollows:

MaximumInputVoltage(Vmax/Ui)=30V MaximumInputCurrent(Imax/Ii)=200mA MaximumInputPower(Pmax/Pi)=0.9W MaximumInternalCapacitance(Ci)=10nF MaximumInternalInductance(Li)=0µH

• Type"n"ratingsareasfollows:MaximumInputVoltage(Vmax/Ui)=30V MaximumInternalCapacitance(Ci)=10nF MaximumInternalInductance(Li)=0µH

• InstallationRequirementsUo≤Ui,Io≤Ii,Po≤Pi, Co≥Ci+Ccable,Lo≥Li+Lcable Voc≤Vmax,Isc≤Imax, Ca≥Ci+Ccable,La≥Li+Lcable Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaareparametersofbarrier.

Note3. Installation• Inanysafetybarrierusedoutputcurrentmustbe

limitedbyaresistor'R'suchthatIo=Uo/R.• ThesafetybarriermustbeIECExcertified.• Inputvoltageofthesafetybarriermustbeless

than250Vrms/Vdc.• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationandwillvoidIECExIntrinsicallysafeandtypencertification.

F0216.ai

EJX Series Pressure Transmitters

IECEx certifiedSafety Barrier

Supply

Hazardous Location Nonhazardous Location

General PurposeEquipment

+

+

+

+

[Intrinsically Safe]

Group IIC, Zone 0

F0217.ai

EJX Series Pressure Transmitters

Supply

Hazardous Location Nonhazardous Location

+

+

– Not UseSafety Barrier

[type n]

IECEx Certified Equipment [nL]

EJX Series Pressure Transmitters

Group IIC, Zone 2

Handling C

autions

2

Page 31: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 30

IM01C25A01-01E

f. IECEx Intrinsically Safe / type n for Fieldbus Type (Except for EJX90A)

CautionforIECExIntrinsicallysafeandtypen.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/SS25areapplicableforuseinhazardouslocations.

• No.IECExCSA05.0012• ApplicableStandard:

IEC60079-0:2000,IEC60079-11:1999, IEC60079-15:2001

• ExiaIIC/IIBT4,ExnLIICT4• AmbientTemperature:–40*to60°C

*–15°Cwhen/HEisspecified.• Max.ProcessTemp.:120°C• Enclosure:IP66andIP67

Note2. ElectricalData• Intrinsicallysaferatingsareasfollows:[Entity] MaximumInputVoltage(Vmax/Ui)=24V MaximumInputCurrent(Imax/Ii)=250mA MaximumInputPower(Pmax/Pi)=1.2W MaximumInternalCapacitance(Ci)=1.76nF MaximumInternalInductance(Li)=0µH[FISCOIIC] MaximumInputVoltage(Vmax/Ui)=17.5V MaximumInputCurrent(Imax/Ii)=380mA MaximumInputPower(Pmax/Pi)=5.32W MaximumInternalCapacitance(Ci)=1.76nF MaximumInternalInductance(Li)=0µH[FISCOIIB] MaximumInputVoltage(Vmax/Ui)=17.5V MaximumInputCurrent(Imax/Ii)=460mA MaximumInputPower(Pmax/Pi)=5.32W MaximumInternalCapacitance(Ci)=1.76nF MaximumInternalInductance(Li)=0µH• Type“n”ratingsareasfollows: MaximumInputVoltage(Vmax/Ui)=32V MaximumInternalCapacitance(Ci)=1.76nF MaximumInternalInductance(Li)=0µH• InstallationRequirements Uo≤Ui,Io≤Ii,Po≤Pi, Co≥Ci+Ccable,Lo≥Li+Lcable Voc≤Vmax,Isc≤Imax, Ca≥Ci+Ccable,La≥Li+Lcable Uo,Io,Po,Co,Lo,Voc,Isc,CaandLaare

parametersofbarrier.

Note 3. Installation

• Inanysafetybarrierusedoutputcurrentmustbelimitedbyaresistor‘R’suchthatIo=Uo/R.

• ThesafetybarriermustbeIECExcertified.• Inputvoltageofthesafetybarriermustbeless

than250Vrms/Vdc.• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationandwillvoidIECExIntrinsicallysafeandtypencertification.

Non-Hazardous Location

Hazardous Location

F0234.ai

Terminator

Safety Barrier

Field Instruments

PressureTransmitter

Field Instruments

+–

+–

+–

Terminator

+

–+

[Intrinsically safe]

Non-Hazardous location

Hazardous location

F0235.ai

Terminator

[nL] Equipment

PressureTransmitter

SUPPLY

Terminator

+−

Transmitter+−

Transmitter+−

+ −

+ −

[Type n]

g. IECEx Flameproof Type

CautionforIECExflameprooftype.

Note1. EJX/EJA-ESeriespressuretransmitterswithoptionalcode/SF2,/SU2,or/SU21areapplicableforuseinhazardouslocations:

• No.IECExCSA07.0008• ApplicableStandard:IEC60079-0:2011,

IEC60079-1:2007-4• FlameproofforZone1,ExdIICT6...T4Gb• Enclosure:IP66/IP67• MaximumProcessTemperature:120°C(T4),

100°C(T5),85°C(T6)

Page 32: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 31

IM01C25A01-01E

• AmbientTemperature:–50to75°C(T4),–50to80°C(T5),–50to75°C(T6)

• SupplyVoltage:42Vdcmax.32Vdcmax.(FOUNDATIONFieldbusandPROFIBUSPAtype)9to28Vdc,27mW(LowPowertype)9to30Vdc,250mW(RS485ModbusCommunicationType)

• OutputSignal:4to20mAdc15 mA (FOUNDATIONFieldbusandPROFIBUSPAtype)1to5V(LowPowertype)RS485Modbus(RS485ModbusCommunicationType)

Note2. Wiring• Inhazardouslocations,thecableentrydevices

shallbeofacertifiedflameprooftype,suitablefortheconditionsofuseandcorrectlyinstalled.

• Unusedaperturesshallbeclosedwithsuitableflameproofcertifiedblankingelements.

• WiringconnectionforoutputsignalcodeQ(LowPowertype)shallfollowthediagrambelow.

F0221.ai

Three-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Four-Wire Connection

Pressure Transmitters

Power SupplyVoltmeter

SUPPLY +

SUPPLY –

A

+

+

Note3. Operation• WARNING:

AFTERDE-ENERGIZING,DELAY5MINUTESBEFOREOPENING.

• WARNING: WHENTHEAMBIENTTEMP.≥65°C,USEHEAT-

RESISTINGCABLEANDCABLEGLAND≥90°C.• Takecarenottogeneratemechanicalsparking

whenaccessingtotheinstrumentandperipheraldevicesinahazardouslocation.

• Electrostaticchargemaycauseanexplosionhazard.Avoidanyactionsthatcausethegenerationofelectrostaticcharge,suchasrubbingwithadryclothoncoatingfaceoftheproduct.

Note4. MaintenanceandRepair• Theinstrumentmodificationorpartsreplacement

byotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidIECExCertification.

• ElectricalConnectionAmarkindicatingtheelectricalconnectiontypeisstampedneartheelectricalconnectionport.Thesemarksareasfollowed.

F0222.ai

Location of the mark

Screw Size Marking

ISO M20 × 1.5 female

ANSI 1/2 NPT female

M

N or W

2.5 EMC Conformity StandardsEN61326-1ClassA,Table2(foruseinindustriallocations) EN61326-2-3EN61326-2-5(forFieldbus)

CAUTIONTomeetEMCregulations,Yokogawarecommendsthatcustomersrunsignalwiringthroughmetalconduitsoruseshieldedtwisted-paircablingwheninstallingEJX/EJA-ESeriestransmittersinaplant.

2.6 Pressure Equipment Directive (PED)

(1) General

• EJX/EJA-ESeriespressuretransmittersarecategorizedaspipingunderthepressureaccessoriessectionofdirective97/23/EC,whichcorrespondstoArticle3,Paragraph3ofPED,denotedasSoundEngineering Practice (SEP).

• EJX110A-MS,EJX110A-HS,EJX110A-VS,EJA110Ewith/HG,EJ130,EJ440,EJ510-D,EJ530-D,EJX610A-D,andEJX630A-Dcanbeusedabove200barandthereforeconsideredasapartofapressureretainingvesselwherecategoryIII,ModuleHapplies.Thesemodelswithoptioncode/PE3conformtothatcategory.

Handling C

autions

2

Page 33: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<2. Handling Cautions> 32

IM01C25A01-01E

(2) Technical Data

• Modelswithout/PE3 Article3,Paragraph3ofPED,denotedasSoundEngineering Practice (SEP).

• Modelswith/PE3 Module:H TypeofEquipment:PressureAccessory-Vessel Typeoffluid:LiquidandGas Groupoffluid:1and2

Model Capsulecode

PS*1

(bar) V(L) PS.V(bar.L) Category*2

EJA110E M,H,V160 0.01 1.6

Article3,Paragraph3

(SEP)

EJ110 F,L

EJX110A

M,H,V 250 0.01 2.5EJA110Ewithcode/HG

EJ110withcode/

PE3M,H,V 250 0.01 2.5 III

EJ130 M,H 500 0.01 5.0Article3,

Paragraph3(SEP)

EJ130withcode/

PE3M,H 500 0.01 5.0 III

EJ310 L,M,A,B 160 0.01 1.6Article3,

Paragraph3(SEP)

EJ430 H,A,B 160 0.01 1.6Article3,

Paragraph3(SEP)

EJ440 C,D 500 0.1 5.0Article3,

Paragraph3(SEP)

EJ440withcode/

PE3C,D 500 0.1 5.0 III

EJ510EJX610A

A,B,C 100 0.1 10 Article3,Paragraph3

(SEP)D 700 0.1 70

EJ510,EJX610Awithcode/

PE3

D 700 0.1 70 III

EJ530,EJX630A

A,B,C 100 0.1 10 Article3,Paragraph3

(SEP)D 700 0.1 70

EJ530,EJX630Awithcode/

PE3

D 700 0.1 70 III

EJX910AL 160 0.01 1.6 Article3,

Paragraph3(SEP)M,H 250 0.01 2.5

EJX910Awithcode/

PE3M,H 250 0.01 2.5 III

EJX930A M,H 500 0.01 5.0Article3,

Paragraph3(SEP)

EJX930Awithcode/

PE3M,H 500 0.01 5.0 III

*1: PSismaximumpressureforvesselitselfbasedonPressureEquipmentDirective97/23/EC.RefertoGeneralSpecificationformaximumworkingpressureofatransmitter.

*2: ReferredtoTable1coveredbyANNEXIIofECDirectiveonPressureEquipmentDirective97/23/EC

(3) Operation

CAUTION• Thetemperatureandpressureoffluidshould

bemaintainedatlevelsthatareconsistentwithnormal operating conditions.

• Theambienttemperatureshouldbemaintainedatalevelthatisconsistentwithnormaloperatingconditions.

• Pleasetakecaretopreventwaterhammerandthelikefrominducingexcessivepressuresinpipesandvalves.Ifphenomenaarelikely,installasafetyvalveortakesomeotherappropriatemeasuretopreventpressurefromexceedingPS.

• Takeappropriatemeasuresatthedeviceorsystemleveltoprotecttransmittersiftheyaretobeoperatednearanexternalheatsource.

2.7 Safety Requirement Standards

Applicablestandard:EN61010-1,EN61010-2-30, C22.2No.61010-1,C22.2No.61010-2-030

(1) Pollution Degree 2

"Pollutiondegree"describesthedegreetowhichasolid,liquid,orgaswhichdeterioratesdielectricstrengthorsurfaceresistivityisadhering."2"appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.Occasionally,however,temporaryconductivitycausedbycondensationmustbeexpected.

(2) Installation Category I

"Overvoltagecategory(Installationcategory)"describesanumberwhichdefinesatransientovervoltagecondition.Itimpliestheregulationforimpulsewithstandvoltage."I"appliestoelectricalequipmentwhichissuppliedfromthecircuitwhenappropriate transient overvoltage control means (interfaces) are provided.

(3) Altitude of installation site:

Max.2,000mabovesealevel

(4) Indoor/Outdoor use

Page 34: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<3. Installation> 33

IM01C25A01-01E

3. InstallationIMPORTANT

• Whenweldingpipingduringconstruction,takecarenottoallowweldingcurrentstoflowthroughthetransmitter.

• Donotsteponthisinstrumentafterinstallation.• ForEJ430,EJ440andEJ438,

theatmosphericopeningislocatedonthelowpressuresidecoverflange.ForEJ530 and EJX630AwhosecapsulecodeisA,B,orC,thepipeoftheatmosphericopeningislocatedonthepressuredetectingsection.Theseopeningsmustnot face upward.

F00301.ai

Capsule code

Zero-adjustment screwPipe

(backside of the instrument)

6

Figure 3.1 EJ530 and EJX630A Horizontal Mounting Position

3.1 Mounting Thetransmittercanbemountedonanominal

50mm(2-inch)pipeusingthemountingbracketsupplied,asshowninFigure3.2and3.3.Tightenthe(four)boltsthatholdthetransmitterwithatorqueofapproximately39N·m4kgf·m.

Transmittermounting bolt

U-bolt nut

Mounting bracket

50 mm(2-inch) pipeU-bolt

F0302.ai

Figure 3.2 Transmitter Mounting (Horizontal Impulse Piping Type)

Vertical pipe mounting(Process connector upside)

Transmittermounting bolt

Mounting bracket

U-bolt nutU-bolt

50 mm(2-inch) pipe

Vertical pipe mounting(Process connector downside)

F0303.ai

Figure 3.3 Transmitter Mounting (Vertical Impulse Piping Type)

Vertical pipe mounting

50 mm (2-inch) pipe

U-bolt (L)

U-bolt (S)Mounting bracket

U-bolt nut (S)

U-bolt nut (L)

Horizontal pipe mounting

F0304.ai

Figure 3.4 EJ510 and EJ530 Mounting

3.2 Mounting the Diaphragm Seals

IMPORTANT• Pleaseuseagasketwithaninsidediameter(ød)

thatisgreaterthanthediameterofthediaphragmseal.Ifagasketwithasmallerinsidediameterisused,thediaphragmmaynotfunctioncorrectly.

• Duringthediaphragmsealinstallation,ensureasfaraspossiblethatnosealliquidheadpressureisappliedtothediaphragmseals.

• Exercisecaresoasnottodamagediaphragmsurfaces.Sincethediaphragmprotrudesapprox.1mmfromtheflangesurface,donotplacethepressure detector section face down on a surface asthiscandamagethediaphragm.

• Donotsharplybendortwistcapillarytubeorapplyexcessivestresstothem.

• Neverloosenthefourboltssecuringthecoverflangeorthescrewsatthejointsbetweenthecapillarytubeandcoverflanges.Ifthesealliquidleaks,thetransmittercannotbeused.

Installation

3

Page 35: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<3. Installation> 34

IM01C25A01-01E

3.2.1 EJ210ThetransmitterismountedonaprocessusingitshighpressuresideflangeasshowninFigure3.5.Thecustomershouldpreparethematingflange,gasket,studboltsandnuts.

F0305.ai

Gasket

Stud bolt

Nut

Figure 3.5 EJ210 Mounting

3.2.2 EJ118 and EJ438MountthediaphragmsealsusingtheflangesasshowninFigure3.6.Thematingflange,gasket,boltsandnutsaretobeprocuredbythecustomer.

NutFlangeDiaphragm

ødGasket

F0306.ai

Bolt

The product is shipped with these parts assembled.

Correctly install the diaphragm seals on the high and low pressure sides of the process (The label on each diaphragm seal is marked HIGH or LOW).

Figure 3.6 Mounting the Diaphragm Seals

3.3 Diaphragm Seals Installation Consideration

IMPORTANT• Whenmeasuringtheliquidlevelofthetank,the

minimumliquidlevel(zeropoint)mustbesettoalevelatleast50mmabovethecenterofthehighpressuresidediaphragmseal(seeFigure3.7).

• Correctlyinstallthediaphragmsealsonthehighandlowpressuresidesoftheprocess,checkingthelabeloneachseal.

• Toavoidmeasuringerrorduetstemperaturedifferencebetweenthetwodiaphragmseals,capillarytubemustbeboundtogether.Thecapillarytubemustbesecurelyfixedtothetankwalltopreventmovementbywindorvibration. Ifthecapillarytubeistoolong,looselycoiltheextratubeportion(coildiameterof300mmormore)andsecurethecoiledtubewithaclamp.

F0307.ai

50 mm minimum

Minimum liquid levelHigh

pressureside

Low pressure side

The transmitter should be installed as low as possible below the position where the high pressure side diaphragm seal is installed.

Install the sealed diaphragm so that the shank positions downward.

IMPORTANT

Figure 3.7 Installing the Diaphragm Seals to a Tank

Page 36: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<3. Installation> 35

IM01C25A01-01E

IMPORTANT

Thetransmittershouldbeinstalledatleast600mmbelowthehighpressure(HP)processconnectiontoensureapositiveheadpressureoffillfluid.Payspecialattentiontovacuum applications.Ifitcannotbeinstalledatleast600mmbelowtheHPprocessconnection,pleaseusetheequationbelow:

h= × 0.102 [mm](P–P0)

ds

h: VerticalheightbetweentheHPprocessconnectionandthetransmitter(mm)h≤0:Installthetransmitteratleasth(mm)belowthe

HP process connectionh>0:Installthetransmitteratmosth(mm)abovethe

HP process connectionP: Pressureinthetank(Paabs)P0:Minimumworkingpressurelimitofthetransmitter(Pa

abs)Seebelowtable.[ForfillfluidcodeA,B,C,D,E]Wetted parts

material code

Capillary length

Process connection size code

2, 8 3 4,WSW 1 to 5m 6790 3190

6 to 10m 10030 3520SE 1 to 5m 6790 3190

6 to 10m 10030 3520SY 1 to 5m 3190

6 to 10m 3520HW 1 to 5m 19150 6140

6 to 10m 8290TW 1 to 5m 9620 3620

6 to 10m 4210UW 1 to 5m 9540 4750

6 to 10m 6050

[Forfillfluidcode1,2,4]Wetted parts

material code

Capillary length

Process connection size code

2, 8 3 4,WSW 1 to 5m 2570 320

6 to 10m 4680 530SE 1 to 5m 2570 320

6 to 10m 4680 530SY 1 to 5m 320

6 to 10m 530HW 1 to 5m 10220 2050

6 to 10m 3450TW 1 to 5m 4270 570

6 to 10m 960

ds:Specificgravityoffillfluid(at25°C).Seebelowtable.Fillfluid

code A, 1, 4 B C, 2 D E

ds:Specificgravity 1.07 0.94 1.09 1.90to

1.92 1.09

F0308.ai

P

Low pressure side

Highpressureside

(+)

(–)

0

h

Figure 3.8 Example of Installation to Tank (Caution on Installation)

3.4 Mounting the Flushing Connection Ring

3.4.1 Mounting to Pressure Detector Section

TheflushingconnectionringismountedtothepressuredetectorsectionasshowninFigure3.9. Atthefactoryshipment,theflushingconnectionringisalreadyassembledandattachedtoprocessdetectorsection.

Ring holder

Spiral gasket

F0309.ai

View from pressure detector section

Groove for installingspiral gasket

Pressure-detector section

Vent/Drain plug

Ring

Figure 3.9 Mounting to Pressure Detector Section

(1)Mounttheringholderontheringandlooselytightenthemountingscrews.

(2)Placethespiralgasketintheringgroove.Withtheringcorrectlyalignedandflushwiththefaceofthepressuredetector,securelytighteneachringholder’smounting screws.

(3)Positiontheringsothatthevent/drainplugsarealignedstraightupanddown.

Installation

3

Page 37: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<3. Installation> 36

IM01C25A01-01E

3.4.2 Mounting to Process FlangeTightentheboltstocompletelyclosethegapbetweentheringandthepressuredetectorsection.Thematingflange,gasket,studboltsandnutsaretoprocuredbythecustomer.

F0310.ai

Ring

Diaphragm

Pressure-detector section

Gasket

Mating flangeSpiral gasket

Figure 3.10 Mounting to Process Flange

IMPORTANT• Confirmthatthereisnogapbetweenthering

andtheprocess-detectorsectionaftertheyaremountedontheprocessflange.Agapcanleadtoasudden,explosivereleaseofprocessfluids.

• Whenmountingorremovingthering,takecarenottotiltthepressuredetectordownwardastheringcan slip off and cause injury.

• Whenre-mountingthering,usethenewspiralgasketasshowninbelowtable.

Table 3.1 Spiral Gasket for Pressure Detector Section Side*

Part number Size DescriptionF9350SV ø100×ø120×t4.5 For3-inchflangeF9970XF ø100×ø120×t4.5 For3-inchflange**F9350ST ø70×ø90×t4.5 For2-inchflangeF9970XD ø70×ø90×t4.5 For2-inchflange**F9346ZH ø60×ø75×t4.5 For11/2-inchflangeF9970XB ø60×ø75×t4.5 For11/2-inchflange**

*: Material;316SST(Hoop),PTFETeflon(Filler)**: Foroil-prohibiteduse(Optioncode:/K1,/K2,/K5,/K6)

3.5 AffixingtheTeflonFilm

IMPORTANTTheFEPTeflonoptionincludesateflonfilmandfluorinatedoil.Beforemountingthetransmittertotheprocessflange,affixtheteflonfilmasfollows:

1)Positionthediaphragmsealsothatthediaphragmis in an upward position.

2)Pourthefluorinatedoilonthediaphragmandgasketareacoveringitcompletelyandevenly.Becarefulnottoscratchthediaphragmorchangetheitsshape.

3)Affixtheteflonfilmoverthediaphragmandgasketarea.

4)Next,carefullyinspectthecoverandtrytoidentifyanyentrappedairbetweenthediaphragmandtheteflonfilm.Theairmustberemovedtoensureoptimumperformance.Ifairpocketsarepresent,useyourfingerstoremovetheairbystartingatthecenterofthediaphragmandworkyourwayout.

5)PositionthegasketontheTeflonfilm.6)Mountthetransmitterontotheprocessflange.

F0311.ai

EJ210 F9347YDEJ118EJ438

F9347YA2 inch

F9347XA3 inch

Teflon filmPART No.

Diaphragm

Fluorinated oil[PART No. : F9145YN]

Gasket area

Figure3.11 AffixingtheTeflonFilm

Page 38: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<3. Installation> 37

IM01C25A01-01E

3.6 Rotating Transmitter SectionThetransmittersectioncanberotatedapproximately360°(180°toeitherdirectionor360°toonedirectionfromtheoriginalpositionatshipment,dependingontheconfigurationoftheinstrument.)Itcanbefixedatanyanglewithinaboverange.

1)Removethetwosetscrewsthatfastenthetransmittersectionandcapsuleassembly,usingtheAllenwrench.

2)Rotatethetransmittersectionslowlyandstopitatdesignated position.

3)Tightenthetwosetscrewstoatorqueof1.5N·m.

IMPORTANTDonotrotatethetransmittersectionmorethantheabovelimit.

F0312.ai

Vertical impulse piping type

Horizontal impulse piping type

Pressure-detector section

Transmitter section

Rotate 0 to ±180° segments

Rotate 0 to ±180° segments

Transmitter section

Pressure-detector section

Conduit connection

Conduit connectionZero-adjustment screw

Stopper

Figure 3.12 Rotating Transmitter Section (Left Side High Pressure Type)

3.7 Changing the Direction of Integral Indicator

IMPORTANTAlwaysturnOFFpower,releasepressureandremoveatransmittertonon-hazardousareabeforedisassemblingandreassmblinganindicator.

Anintegralindicatorcanbeinstalledinthefollowingthreedirections.

F0313.ai

Figure 3.13 Integral Indicator Direction

IMPORTANTTheterminalboxcoverislockedbyanAllenheadbolt(ashroudingbolt)onATEXflameprooftypetransmitters.WhentheshroudingboltisdrivenclockwisebyanAllenwrench,itisgoinginandcoverlockisreleased,andthenthecovercanbeopened. Whenacoveriscloseditshouldbelockedbyashroudingboltwithoutfail.Tightentheshroudingbolttoatorqueof0.7N·m.

1) Removethecover.2) Whilesupportingtheintegralindicatorwithonehand,

loosen its two mounting screws.3) DismounttheLCDboardassemblyfromtheCPU

assembly.Whendoingthis,carefullypulltheLCDboardassemblystraightforwardsoasnottodamagetheconnectorpinsbetweenitandtheCPUassembly.

4) AfterrotatingtheLCD,alignboththeLCDboardassemblyandCPUassemblyconnectorsandengagethem.

5) Insertandtightenthetwomountingscrews.6) Replacethecover.

90°90°Integral

indicator

Mounting screw

Amplifier cover

LCD board assembly

CPU assembly

F0314.ai

Figure 3.14 Rotating Integral Indicator

Installation

3

Page 39: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<4. Installing Impulse Piping> 38

IM01C25A01-01E

4. Installing Impulse Piping4.1 Impulse Piping Installation

PrecautionsTheimpulsepipingthatconnectstheprocessoutputstothetransmittermustconveytheprocesspressureaccurately.If,forexample,gascollectsinaliquid-filledimpulseline,orthedrainofagas-filledimpulselinebecomesplugged,itwillnotconveythepressureaccurately.Sincethiswillcauseerrorsinthemeasurementoutput,selecttheproperpipingmethodfortheprocessfluid(gas,liquid,orsteam).Paycarefulattentiontothefollowingpointswhenroutingtheimpulsepipingandconnectingtheimpulsepipingtoatransmitter.

4.1.1 Connecting Impulse Piping to the Transmitter

(1) Check the High and Low Pressure Connections on the Transmitter (Figure 4.1)

Symbols“H”and“L”havebeenplacedonthecapsuleassemblytoindicatehighandlowpressureside.Withdifferentialpressuretransmitters,connectthehighpressuresideimpulselinetothe“H”side,andthelowpressuresideimpulselinetothe“L”side.

Withgauge/absolutepressuretransmitters,connecttheimpulselinetothe‘H’side.

F0401.ai

Process connection

“H” and “L” are shown

Process connection

Process connector

Bolt

Differential Pressure Transmitter

Figure 4.1 “H” and “L” Symbols on a Capsule Assembly

(2) Changing the Process Connector Piping Connections (for differential pressure transmitters)

Theimpulsepipingconnectiondistancescanbechangedbetween51mm,54mmand57mmbychangingtheorientationoftheprocessconnectors.Thisisconvenientforaligningtheimpulselinewithaprocess connectors.

57 mm 54 mm 51 mmF0402.ai

Figure 4.2 Process Connector Impulse Piping Connection Distances

(3) Tightening the Process Connector Mounting Bolts

Afterconnectinganimpulseline,tightentheprocessconnectormountingboltsuniformly.

(4) Removing the Impulse Piping Connecting Port Dustproof Cap

Theimpulsepipingconnectingportonthetransmitteriscoveredwithaplasticcaptokeepoutdust.Thiscapmustberemovedbeforeconnectingtheline.(Becarefulnottodamagethethreadswhenremovingthiscap.Neverinsertascrewdriverorothertoolbetweenthecapandportthreadstoremovethecap.)

(5) Connecting the Transmitter and 3-Valve Manifold (for differential pressure transmitters)

A3-valvemanifoldconsistsoftwostopvalvestoblockprocesspressureandanequalizingvalvetoequalizethepressuresonthehighandlowpressuresidesofthetransmitter.Suchamanifoldmakesiteasiertodisconnectthetransmitterfromtheimpulsepiping,andisconvenientwhenadjustingthetransmitterzeropoint.

Therearetwo3-valvemanifoldtyps:thepipe-mountingtypeandthedirect-mountingtype;careshouldbetakenwithrespecttothefollowingpointswhenconnectingthemanifoldtothetransmitter.

Pipe-Mounting Type 3-Valve Manifold

F0403.ai

Nipple

Nipple

Processconnector

Ball headlock nut

Pipe

Ball headlock nut

Process connector bolts

50 mm(2-inch) pipe

Pipes

3-valvemanifold

Impulse piping

Vent plug(optional)

Stop valve(low pressure side)

Equalizing valve(balancing)

Stop valve(high pressure side)

Figure 4.3 3-Valve Manifold (Pipe-Mounting Type)

Page 40: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<4. Installing Impulse Piping> 39

IM01C25A01-01E

1) Screwnipplesintotheconnectionportsonthetransmittersideofthe3-valvemanifold,andintotheimpulsepipingconnectingportsontheprocessconnectors.(Tomaintainpropersealing,windsealingtapearoundthenipplethreads.)

2) Mountthe3-valvemanifoldonthe50mm(2-inch)pipebyfasteningaU-bolttoitsmountingbracket.TightentheU-boltnutsonlylightlyatthistime.

3) Installthepipeassembliesbetweenthe3-valvemanifoldandtheprocessconnectorsandlightlytightentheballheadlocknuts.(Theball-shapedendsofthepipesmustbehandledcarefully,sincetheywillnotsealproperlyiftheballsurfaceisscratchedorotherwisedamaged.)

4) Nowtightenthenutsandboltssecurelyinthefollowingsequence: Processconnectorbolts→transmitter-endballheadlocknuts→3-valvemanifoldballheadlocknuts→ 3-valvemanifoldmountingbracketU-boltnuts

Direct-Mounting Type 3-Valve Manifold1) Mountthe3-valvemanifoldonthetransmitter.(When

mounting,usethetwogasketsandthefourboltsprovidedwiththe3-valvemanifold.Tightentheboltsevenly.)

2) Mounttheprocessconnectorsandgasketsonthetopofthe3-valvemanifold(thesideonwhichtheimpulsepipingwillbeconnected.)

BoltsProcess

connector

Gasket

GasketProcess

connector

Bolts

Stop valve

Stop valve

3-valvemanifold

3-valvemanifold

Equalizing valve

Equalizingvalve

Stop valveImpulsepiping

Impulsepiping

Stop valve

F0404.ai

Figure 4.4 3-Valve Manifold (Direct-Mounting Type)

NOTEAftercompletingtheconnectionofthetransmitterand3-valvemanifold,besuretoCLOSEthelowpressureandhighpressurestopvalves,OPENtheequalizingvalve,andleavethemanifoldwiththeequalizingvalveOPEN.Youmustdothisinordertoavoidoverloadingthetransmitterfromeitherthehighorthelowpressuresidewhenbeginningoperation.

4.1.2 Routing the Impulse Piping

(1) Process Pressure Tap AnglesIfcondensate,gas,sedimentorotherextraneousmaterialintheprocesspipinggetsintotheimpulsepiping,pressuremeasurementerrorsmayresult.Topreventsuchproblems,theprocesspressuretapsmustbeangledasshowninFigure4.5accordingtothekindoffluidbeingmeasured.

NOTE• Iftheprocessfluidisagas,thetapsmustbe

verticalorwithin45°eithersideofvertical.• Iftheprocessfluidisaliquid,thetapsmustbe

horizontalorbelowhorizontal,butnotmorethan45°belowhorizontal.

• Iftheprocessfluidissteamorothercondensingvapor,thetapsmustbehorizontalorabovehorizontal,butnotmorethan45°abovehorizontal.

[Gas]

Pressuretaps

Processpiping

[Steam][Liquid]

45°

45°

45° 45°

45°

45°

F0405.ai

Figure 4.5 Process Pressure Tap Angle (For Horizontal Piping)

(2) Position of Process Pressure Taps and Transmitter

Ifcondensate(orgas)accumulatesintheimpulsepiping,itshouldberemovedperiodicallybyopeningthedrain(orvent)plugs.However,thiswillgenerateatransientdisturbanceinthepressuremeasurement,andthereforeitisnecessarytopositionthetapsandroutetheimpulsepipingsothatanyextraneousliquidorgasgeneratedintheleadlinesreturnsnaturallytotheprocesspiping.• Iftheprocessfluidisagas,thenasarulethe

transmittermustbelocatedhigherthantheprocesspressure taps.

• Iftheprocessfluidisaliquidorsteam,thenasarulethetransmittermustbelocatedlowerthantheprocess pressure taps.

(3) Impulse Piping SlopeTheimpulsepipingmustberoutedwithonlyanupwardordownwardslope.Evenforhorizontalrouting,theimpulsepipingshouldhaveaslopeofatleast1/10topreventcondensate(orgases)fromaccumulatinginthepipes.

Installing Impulse Piping

4

Page 41: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<4. Installing Impulse Piping> 40

IM01C25A01-01E

(4) Temperature Difference Between Impulse Piping (for differential pressure transmitters)

Ifthereisatemperaturedifferencebetweenthehighandlowimpulselines,thedensitydifferenceofthefluidsinthetwolineswillcauseanerrorinthemeasurementpressure.Whenmeasuringflow,impulselinesmustberoutedtogethersothatthereisnotemperaturedifferencebetweenthem.

(5) Condensate Pots for Steam Flow Measurement (for differential pressure transmitters)

Iftheliquidintheimpulsepipingrepeatedlycondensesorvaporizesasaresultofchangesintheambientorprocesstemperature,thiswillcauseadifferenceinthefluidheadbetweenthehighpressureandlowpressuresides.Topreventmeasurementerrorsduetotheseheaddifferences,condensatepotsareusedwhenmeasuringsteamflow.

(6) Preventing Wind Speed Effects in Very Low Differential Pressure Measurement (for differential pressure transmitters)

IMPORTANTWhenusingadifferentialpressuretransmittertomeasureverylowpressures(draftpressure),thelowpressureconnectionportisleftopentoatmosphericpressure(thereferencepressure).Anywindaroundthedifferentialpressuretransmitterwillthereforecauseerrorsinthemeasurement.Topreventthis,itwillbenecessaryeithertoenclosethetransmitterinabox,ortoconnectaimpulselinetothelowpressuresideandinsertitsendintoawindexcludingpot(cylindricalwithabaseplate).

(7) Preventing Freezing

Ifthereisanyriskthattheprocessfluidintheimpulsepipingortransmittercouldfreeze,useasteamjacketorheatertomaintainthetemperatureofthefluid.

NOTEAftercompletingtheconnections,closethevalvesontheprocesspressuretaps(mainvalves),thevalvesatthetransmitter(stopvalves),andtheimpulsepipingdrainvalves,sothatcondensate,sediment,dustandotherextraneousmaterialcannotentertheimpulsepiping.

4.2 Impulse Piping Connection Examples

Figure4.6,4.7,and4.8showsexamplesoftypicalimpulsepipingconnections.Beforeconnectingthetransmittertotheprocess,studythetransmitterinstallationlocation,theprocesspipinglayout,andthecharacteristicsoftheprocessfluid(corrosiveness,toxicity,flammability,etc.),inordertomakeappropriatechangesandadditionstotheconnectionconfigurations.

Notethefollowingpointswhenreferringtothesepipingexamples.

• Iftheimpulselineislong,bracingorsupportsshouldbeprovidedtopreventvibration.

• Theimpulsepipingmaterialusedmustbecompatiblewiththeprocesspressure,temperature,andotherconditions.

• Avarietyofprocesspressuretapvalves(mainvalves)areavailableaccordingtothetypeofconnection(flanged,screwed,welded),construction(globe,gate,orballvalve),temperatureandpressure.Selectthetypeofvalvemostappropriatefortheapplication.

Tee

3-valvemanifold

Drain valve

Orifice

Drain plug

Tap valveUnion

or flange

Liguid Gas

Condensate pot

Steam

F0406.ai

Figure 4.6 Impulse Piping Connection Examples (for differential pressure transmitters)

F0407.ai

Pipe (opened to atmosphereat low pressure side)

Open Tank Closed Tank Tap valveUnion or flange

Vent plug

Tee

Drain valve

Drain plug

Figure 4.7 Impulse Piping Connection Examples (EJ210)

Page 42: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<4. Installing Impulse Piping> 41

IM01C25A01-01E

F0408.ai

Liquid Gas Steam

Union or flange

TeeTee

Drain plug

Drain valve

Drain valveDrain plug

Union or flange

Union or flange

Union or flange

Tap valve

Tap valve

Tee

Drain valveDrain plug

Tap valve

Figure 4.8 Impulse Piping Connection Examples (for gauge/absolute pressure transmitters)

4.3 Process Piping Installation Precautions (EJ115)

4.3.1 Connecting Process Piping to the Transmitter

(1) ConfirmingtheProcessFluidFlowDirection

Themark“ ”onthemanifoldindicatesthedirectioninwhichtheprocessfluidisflowed(fromrighttoleft).Whenconnectingtheprocesspipingtotheprocessconnector,confirmtheprocessfluidflowdirection.

F0409.ai

Flow direction (from right to left)Manifold

Orifice name plate

Process connector(low pressure side)

Process connector(high pressure side)

Process connection(outflow side)

Process connection(inflow side)

Figure 4.9 Manifold and Flow Direction Indication

(2) Tightening the Process Connector Mounting Bolts

Thetransmitterisshippedwiththeprocessconnectormountingboltsonlylooselytightened.Afterconnectingtheprocesspiping,tightentheseboltsuniformlytopreventleakswithatorqueof39to49N·m4to5kgf·m.

(3) Removing the Process Connector Port Dustproof Cap

Theprocessconnectorportthreadsarecoveredwithaplasticcaptoexcludedust.Thiscapmustberemovedbeforeconnectingthepiping.(Becarefulnottodamagethethreadswhenremovingthiscap.Neverinsertascrewdriverorothertoolbetweenthecapandportthreadstoremovethecap.)

4.3.2 Routing the Process Piping

(1) Relationship between Process Fluid and Manifold Locations (For the vertical impulse piping type)

Ifcondensate(orgas)generatedintheprocesspipingwereallowedtoaccumulate,thenitwouldbenecessarytoremoveitperiodicallybyopeningthedrain(orvent)plug.However,thiswouldgenerateatransientdisturbanceinthepressuremeasurement.Therefore,theprocesspipingmustberoutedsothatanycondensate(orgas)generatedintheprocesspipingwillnotaccumulateinthepressure-sensingassemblyofthetransmitter.

NOTE• Iftheprocessfluidisagas,thenasarulethe

manifoldmustbelocatedatthedownsideofthepressure-sensingassembly.

• Iftheprocessfluidisaliquid,thenasarulethemanifoldmustbelocatedattheupsideofthepressure-sensingassembly.

(2) Pipe Size for Process Piping

Usea15mm(1/2-inch)pipeforprocesspipingconnectiontotheprocessconnector.

(3) Preventing Freezing

Ifthereisanyriskthattheprocessfluidinthetransmitterpressure-sensingassemblycouldfreezeorsolidify,useasteamjacketorheatertomaintainthetemperatureofthefluid.

(4) Process Piping Connection Examples

Figure4.10showsexamplesoftypicalprocesspipingconnections.Beforeconnectingthetransmittertotheprocess,studythetransmitterinstallationlocation,theprocesspipinglayout,andthecharacteristicsoftheprocessfluid(corrosiveness,toxicity,flammability,etc.),inordertomakeappropriatechangesandadditionstotheconnectionconfigurations.

Notethefollowingpointswhenreferringtothesepipingexamples.

• Theprocesspipingmaterialusedmustbecompatiblewiththeprocesspressure,temperature,andotherconditions.

Installing Impulse Piping

4

Page 43: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<4. Installing Impulse Piping> 42

IM01C25A01-01E

• Avarietyofprocesspiping-mountedstopvalvesareavailableaccordingtothetypeofconnection(flanged,screwed,welded),construction(globe,gate,orballvalve),temperatureandpressure. Selectthetypeofvalvemostappropriatefortheapplication.

Gas flow measurement

Liquid flow measurement

Union or flange

Union or flange

Stop valve

Stop valve

Manifold

Manifold

Process piping

Process pipingF0410.ai

Figure 4.10 Process Piping Connection Examples (EJ115)

Page 44: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 43

IM01C25A01-01E

5. Wiring

NOTEFor FOUNDATIONFieldbus,PROFIBUSPA,andModbuscommunicationtypes,pleaserefertoeachcommunication manual.

5.1 Wiring Precautions

IMPORTANT• Laywiringasfaraspossiblefromelectricalnoise

sourcessuchaslargecapacitytransformers,motors,andpowersupplies.

• Removeelectricalconnectiondustcapbeforewiring.

• Allthreadedpartsmustbetreatedwithwaterproofingsealant.(Anon-hardeningsiliconegroup sealant is recommended.)

• Topreventnoisepickup,donotpasssignalandpowercablesthroughthesameducts.

• Explosion-protectedinstrumentsmustbewiredinaccordancewithspecificrequirements(and,incertaincountries,legalregulations)inordertopreservetheeffectivenessoftheirexplosion-protected features.

• TheterminalboxcoverislockedbyanAllenheadbolt(ashroudingbolt)onATEXflameprooftypetransmitters.WhentheshroudingboltisdrivenclockwiseusinganAllenwrench,itgosein.Thecoverlockcanthenbereleasedandthecovercanbeopenedbyhand. Whenacoveriscloseditshouldbelockedbyashroudingboltwithoutfail.Tightentheshroudingbolttoatorqueof0.7N·m.

Shrouding Bolt

Shrouding BoltF0501.ai

Figure 5.1 Shrouding Bolt

• Plugandsealanunusedconduitconnection.

5.2 Connections of External Wiring to Terminal Box

F0527.ai

RTD cable connection*

Terminal Configuration

1Terminal 2Terminal

3Terminal [A]

[B]*

*For EJX9A only.

4Terminal

Power supply and output terminals

External indicator (ammeter) terminals*1*2

orStatus contact output terminals*2

(when /AL is specified)

Terminal Wiring for 4 to 20 mA outputSUPPLY

CHECKor

ALARM

+–+– +–

Ground terminal

12

2

2

3

3

F0528.ai

SUPPLY

VOUT

+–+–

Terminal Wiring for 1 to 5 V output

Ground terminal

Power supply terminals

1 to 5 V DC with HART communication terminals

12

23

*1: When using an external indicator or check meter, the internal resistance must be 10 Ω or less. A check meter or indicator cannot be connected when /AL option is specified.

*2: Not available for FOUNDATION Fieldbus and PROFIBUS PA communication types.

SUPPLY

CHECK

PULSE

+–

*1: When using an external indicator or check meter, the internal resistance must be 10Ω or less.*2: Not available for FOUNDATION Fieldbus communication type.

+–+–

Terminal Wiring for 4 to 20 mA output [EJX9A]

Ground terminal

Power supply and output terminals

External indicator (ammeter) terminals *1*2

Pulse or status contact output terminals *2

12

23

24

Figure 5.2 Terminal

Wiring

5

Page 45: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 44

IM01C25A01-01E

5.2.1 Power Supply Wiring Connection

IMPORTANTConnectingwiththecommercialACpowersupplywilldamagethedevice.BesuretousetheDCpowersupplyinthepredeterminedrange.

ConnectthepowersupplywiringtotheSUPPLY+and–terminals.

Power supply–

+Transmitter terminal box

F0502.aiLoad resistance is not necessary for 1 to 5 V output.

Figure 5.3 Power Supply Wiring Connection

5.2.2 ConfigurationToolConnection

4to20mAoutput,BRAIN/HART

ConnecttheconfigurationtooltotheSUPPLY+and–terminals.(Usehooks.)

Transmitter terminal box

F0503.ai

Power supply

+

Ignore the polarity since the configuration tool is AC-coupled to the terminal box.

USBFieldMate Modem

PC/FieldMate

Figure5.4 ConfigurationToolConnection

1to5Voutput,HART

ConnecttheHARTcommunicatororconfigurationtooltotheSUPPLY-andVOUT(+)terminals.(Usehooks.)

Transmitter terminal box

F0532.ai

Voltmeter

+Power supply

+

USBFieldMate Modem

PC/FieldMate

Figure 5.5 Four wire connection

Transmitter terminal box

F0533.ai

Power supply

+

Voltmeter

+

USBFieldMate Modem

PC/FieldMate

Figure 5.6 Three wire connection

5.2.3 Status Output ConnectionWhenoptioncode/ALisspecified,connecttheexternalwiringasshowninFigure5.7.

Toconfigureandactivatetheprocessalarmfunctionandstatusoutput,itisnecessarytosetsomeparameters.Refertoeachcommunicationmanualforprocedures.

Transmitter terminal box

Magnetic valve

AC power supply

External power supply 30V DC, 120mA max

+

– 250Ω

24V DC

Use two-wire separately shielded cables.

Distributor

Shielded cable

F0504.ai

Figure 5.7 Status Output Connection

Page 46: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 45

IM01C25A01-01E

5.2.4 Connection Example for EJX910A and EJX930A

Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART protocol type)

250Ω

R +

–BPULSE

SUPPLY

Transmitter Electrical Terminal

Recorder or other instrument

This supply voltage requires a power sourse with a maximum output current of no less than E/R+25mA.

Electric counter

E(16.4 to 30V DC)

Counting input

Common

+

B

Transmitter Electrical Terminal

250Ω

24V DC

PULSE

SUPPLY+

Distributor

+–

BPULSE

SUPPLY

R

E

Transmitter Electrical Terminal Use the Three-wire shielded cable.

Use the Three-wire shielded cable.

Electric counter*1

*1

*1

*1

*2

*2

*2

*2

Shielded Cable

Shielded Cable

PULSE

SUPPLY +–

BMognetic

valve

AC power supply

External Power supply 30V DC, 120mA max(Contact Rating)

Transmitter Electrical Terminal

E

250Ω

R+

–BPULSE

SUPPLY

Counting inputCommon

For the shielded cables in this example of flowmeter installation, use two-wire separately shielded cables.This supply voltage requires a power sourse with a maximum output current of no less than E/R+25mA.

Recorder or other instrument

Electric counter

E(16.4 to 30V DC)

Shielded Cable

The supply voltage requires output impedance no more than 1/1000 of R (load resistance).Transmitter Electrical Terminal

250ΩRE(10.5 to 30V DC) Counting inputCommon

24V DC

PULSE

SUPPLY

For the shielded cables in this example of flowmeter installation, use two-wire separately shielded cables.

This supply voltage requires a power sourse with a maximum output current of no less than E/R.

Distributor (or communication medium : ex. EP card)

(or communication medium : ex. EP card)Electric counter

+–

B

Shielded Cable

Transmitter Electrical Terminal

When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to example 1 to 3.

Relay

* Either B or +*

* Either B or +

*

* Either B or +

* Either B or +

* Either B or +

* Either B or +

*

*

*

*

Analog Output

Pulse Output

Status Output

Simultaneous Analog

-Pulse Output *3

DescriptionConnection

0.1 C ( µF ) × f ( kHz )

≤ R (kΩ) ≤120

E (V)

The load resistance of pulse output should be used to 1kΩ, 2W.If no translation of the pulse output possible by the cable length or the frequency of the pluse output,the load resistance should be selected by calculation as shown below.

Example of CEV cable capacitance 0.1µF/km

WhereE = Supply voltage (V) f = Frequency of pulse output (kHz)R = Value of load resistance (kΩ)

C = Cable capacitance (µF) P = Power ratio of the load resistance (mW)

P (mW) =R (kΩ)E2 (V)

Example 3In this case, No communi-cation is possible (when shielded cable is not used).

The range of load resistance R for the pulse output.

Example 1In this case, Communica-tion is possible(up to adistance of 2km when aCEV cable is used).

Example 2In this case, Communica-tion is possible (up to adistance of 200m when a CEV cable is used) and R = 1kΩ).

In this case, Communication is possible (up to a distance of 2km when a CEV cable is used.)

In this case, No communication is possible.

In this case, No communication is possible.

F0531.ai*1: Toavoidtheinfluenceofexternalnoise,useanelectriccounterwhichfitstothepulsefrequency.*2: Resistorisnotnecessaryincaseofanelectriccounterwhichcanreceivecontactpulsesignaldirectly.*3:Whenusinganalogandpulseoutputsimultaneously,theHARTcommunicationmaybeinfluencedbynoisecomparinganalogoutputonly.Take

countermeasurefornoiseshownabove,e.g.useshieldcableetc.

Wiring

5

Page 47: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 46

IM01C25A01-01E

5.2.5 External Temperature Connection (for EJX910A and EJX930A)

ConnecttheRTDcableassemblytotheJuckTerminal.

F0505.ai

Figure 5.8 External Temperature Connection

5.3 Wiring5.3.1 LoopConfigurationSincetheDPharpusesatwo-wiretransmissionsystemfor4to20mAoutput,signalwiringisalsousedaspowerwiring.

DCpowerisrequiredforthetransmitterloop.Thetransmitteranddistributorareconnectedasshownbelow.Fordetailsofthepowersupplyvoltageandloadresistance,seeSection5.6.

For1to5Voutput,threeorfourwiresystemisused.See(4).

(1) General-use Type and Flameproof Type (4 to 20 mA output)

• AnalogOutput

Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor (Power supply unit)

Receiver instrument

F0506.ai

Figure 5.9 Connection between Transmitter and Distributor

• PulseoutputandAlarm,StatusOutputorSimultaneous Analog-Pulse Output (for EJX910A and EJX930A)

Hazardous Location Nonhazardous LocationTransmitter terminal box

Distributor (Power supply unit)

Receiver instrument

Receiver instrument

F0507.ai

Figure 5.10 Connection between Transmitter and Distributor

(2) Intrinsically Safe Type (4 to 20 mA output)

Withtheintrinsicallysafetype,asafetybarriermustbeincludedintheloop.

Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor (Power supply unit)

Receiver instrument

Safety barrier F0508.ai

Figure 5.11 Connection between Transmitter and Distributor

(3) Intrinsically Safe Type (for EJX910A and EJX930A)

• AnalogOutput

Hazardous Location Nonhazardous Location

Transmitter terminal box Receiver instrument(and power supply)Safety barreir

(Isolation type)

F0509.ai

Anaolg input

Powersupply

Page 48: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 47

IM01C25A01-01E

• SimultaneousAnalog-PulseOutputHazardous Location Nonhazardous Location

Transmitter terminal boxSafety barrier (Isolated type)

I/O module

F0510.ai

Safety barrier (Isolated type)

Power supply

Power supply

Analog input

Pulse input

Figure 5.12 Connection between Transmitter, barrier and receiver

(4) 1 to 5 V output

Eitherthreeorfourwiresystemcanbeused.Power supply line and 1 to 5 V signal line commonly use theSUPPLY-terminal.

NOTEWiththreewireconnection,thecablelengthmayaffectthemeasurementaccuracyoftheoutputsignal.Ineitherthree-wireorfour-wireconnection,recommendedwiringdistanceis200morless,andtheuseofshieldedcableisrecommended.

• Threewireconnection Anegativewiringshallbecommonlyusedforpower

supply and signal line.

F0529.ai

Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor (Power supply unit)

Receiver instrument

Figure 5.13 Connection between Transmitter, Distributor and Receiver

• Fourwireconnection Fastenthenegativesidewiringofbothpowersupply

andsignallinetotheSUPPLY-terminal.Hazardous Location Nonhazardous Location

Transmitter terminal boxDistributor (Power supply unit)

Receiver instrument

F0530.ai

Figure 5.14 Connection between Transmitter, Distributor and Receiver

5.3.2 Wiring Installation

(1) General-use Type and Intrinsically Safe Type

Withthecablewiring,useametallicconduitorwaterproofglands.

• Applyanon-hardeningsealanttotheterminalboxconnectionportandtothethreadsontheflexiblemetalconduitforwaterproofing.

F0511.ai

Flexible metal conduit

Wiring metalconduit

Tee

Drain plug

Apply a non-hardeningsealant to the threads forwaterproofing.

Figure 5.15 Typical Wiring Using Flexible Metal Conduit

Wiring

5

Page 49: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 48

IM01C25A01-01E

(2) Flameproof Type

Wirecablesthroughaflameproofpackingadapter,oruseaflameproofmetalconduit.

Wiringcablethroughflameproofpackingadapter.• Applyanon-hardeningsealanttotheterminalbox

connectionportandtothethreadsontheflameproofpackingadapterforwaterproofing.

Flameproof packing adapter

Flexible metal conduit

Wiring metalconduit

Tee

Drain plug

Apply a non-hardeningsealant to the threads forwaterproofing.

F0512.ai

Figure 5.16 Typical Cable Wiring Using Flameproof Packing Adapter

Flameproof metal conduit wiring• Asealfittingmustbeinstalledneartheterminalbox

connection port for a sealed construction.• Applyanon-hardeningsealanttothethreadsofthe

terminalboxconnectionport,flexiblemetalconduitandsealfittingforwaterproofing.

F0513.ai

Non-hazardous area

Hazardous areaFlameproofheavy-gaugesteel conduit

Tee

Drain plugSeal fitting

Gas sealing device

Flameproof flexiblemetal conduit

Apply a non-hardeningsealant to the threads ofthese fittings forwaterproofing

After wiring, impregnate the fittingwith a compound to seal tubing.

Figure 5.17 Typical Wiring Using Flameproof Metal Conduit

5.4 RTD Cable Connection (EJX910A/EJX930A)

ConnectionoftheRTDcableisalwaysrequiredtomeasureexternaltemperature.Followtheproceduresbelowtoconnectacablewhenacableglandoraconduitis used.

5.4.1 Connecting Shielded Cable with Cable Gland (External temperature input code: -1, -2, -3, and -4)

• RTDconnectioncomponents:EJXmultivariabletransmitter,twocableglands,andRTDcable. Twocableglandsareattached.

Transmitter

Cable gland

Electrical connection

RTD cable with connector

Detail of connector

F0514.ai

• MagnifiedviewoftheRTDconnectorinthetransmitter'sterminalbox.

ALARM ALARM

Protection Cap Connecting Port

F0515.ai

TheRTDcableconnectingportiscoveredwithacaptokeepoutdust.Thecapshouldnotberemoveduntilyouarereadytoinstallthecable.• ComponentsforthecableglandThecableglandassemblyconsistsofanentry,seal,runningcoupler,andbacknut.ConfirmthatthesealisattachedinsidetheentryandthatthethreadsizeofthecableglandisthesameasthatfortheRTDelectricalconnection.

F0516.ai

1/2NPT Type

M20 Type Gasket

Entry with Seal Running Coupler Backnut

Entry with Seal Running Coupler Backnut

CAUTIONInput/outputsignalisnon-isolated. Donotturnonpowersupplyuntilyoucompleteallthewiringwork.

Page 50: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 49

IM01C25A01-01E

Procedure

(1)Disassemblethecablegland:loosentherunningcouplertoseparatethebacknutfromtheentry.

(2)Removetheprotectioncapoverthetransmitterelectricalconnectionandinstalltheentryontheelectricalconnection.Notethatanon-hardeningsealantshouldbeappliedtothethreadsfora1/2NPTconnectionandagasketshouldbeusedforanM20connection.

F0517.ai

(3)PasstheRTDcablethroughtherunningcouplerandbacknutassembly.

F0518.ai

(4) InserttheRTDcableandfirmlyplugitsconnectorintotheconnectingportinthetransmitter'sterminalbox.

F0519.ai

(5)Aligntherunningcouplerontheentry.

F0520.ai

(6)TurntherunningcoupleruntilthesealintheentrycomesintocontactwiththeRTDcable.

F0521.ai

(7)RotatetherunningcoupleranotherhalfturntosecurelytightenthesealontheRTDcable.

(8)Useaprotectionconduit,ifnecessary.Inthiscase,insertthecablethroughtheconduitandattachittotheBacknut.

CAUTIONAfterthecableissecuredasexplainedabove,donottightentherunningcoupleranyfurther;todosocoulddamagetheRTDconnection. Donotpullthecableorsubjectittoexcessivemechanicalshock.

5.4.2 Connecting Shielded Cable for Con-duit Use (External temperature input code: -B, -C, and -D)

• RTDconnectioncomponents:EJXmultivariabletransmitterandRTDcable

F0522.ai

Procedure

(1)RemovetheprotectioncapprotectingtheRTDelectricalconnectionandinserttheRTDcable.

F0523.ai

(2)Removethecapprotectingtheconnectingport.TheninserttheRTDcableandfirmlyplugtheconnectorintotheconnectingportinthetransmitter'sterminalbox.

(3) InsertthecablethroughtheconduitandattachittotheRTDelectricalconnection.

CAUTIONDonotpullthecableorsubjectittoexcessivemechanicalshock.

Wiring

5

Page 51: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<5. Wiring> 50

IM01C25A01-01E

5.4.3 Cable Connection RTD Terminal Box Side

EJXmultivariabletransmitterRTDI/Fisfor3-wireTypeRTD,Pt100.HeedthefollowingwhenwiringanRTDofthe2-or4-wiretype.

NOTEPleasenotethatatemperatureerrorwilloccurwhenyouusea2-wireRTDbecauseofwiringresistance. PleasedonotgroundtheshieldontheRTDsideofthecable.

CAUTIONPleaseuseonlythecablesprovidedwiththisinstrument. Whenwiring,besurenottodamagethecable'sinsulation or its core. Allthecablecoresmusthavesufficientinsulationaroundthem. Donotletthesignallinecontacttheshieldline. Donotallowtheshieldlineorthesignallinetocometheearthpotentialvoltage.

2-Wire 3-Wire 4-Wire

A B A B b A B baF0524.ai

Figure 5.18 The Method of Wiring for the RTD Side

Table 5.2 The Method of Wiring for the RTD Side RTD Terminal

RTD Terminal A a B b

2-Wire White - Blue1andBlue2 -

3-Wire White - Blue1 Blue2

4-Wire White open Blue1 Blue2

NOTEThecolordisplayinthetableshowsthewhitelineofthecable. Thecablecolorcouldchangedependingonthecabletype. Blue1andblue2allowchangingplaces. For2-wireType,connecteitherwhichisblue1orblue2,andgiveothersideasOPEN.

5.5 GroundingGroundingisalwaysrequiredfortheproperoperationoftransmitters.Followthedomesticelectricalrequirementsasregulatedineachcountry.Foratransmitterwithabuilt-inlightningprotector,groundingshouldsatisfygroundresistanceof10Ωorless.

Groundterminalsarelocatedontheinsideandoutsideoftheterminalbox.Eitheroftheseterminalsmaybeused.

Ground terminal(inside)

Ground terminal(outside)

F0525.ai

Figure 5.19 Ground Terminals

5.6 Power Supply Voltage and Load Resistance

For 4 to 20 mA output only.Whenconfiguringtheloop,makesurethattheexternalloadresistanceiswithintherangeinthefigurebelow.

(Note) Incaseofanintrinsicallysafetransmitter,externalloadresistanceincludessafetybarrierresistance.

600

250

0 10.5 16.6 25.2 42

External load

resistanceR (Ω)

Power supply voltage E (V DC)F0526.ai

Communication applicable range BRAIN and HART

R= E–10.50.0244

Figure 5.20 Relationship between Power Supply Voltage and External Load Resistance

Page 52: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<6. Operation> 51

IM01C25A01-01E

6. Operation

NOTEFor FOUNDATIONFieldbus,PROFIBUSPAandModbuscommunication types and forthetransmitteroperatingconfirmationandzeroingbyanycommunicationmethod,refertoeachcommunicationmanual.

6.1 Preparation for Starting Operation

ConfirmingthatTransmitterisOperatingProperly

On the integral indicator

• Ifthewiringsystemisfaulty,thedisplaystaysblank.• Ifthetransmitterisfaulty,anerrorcodeisdisplayed.

Self-diagnostic error on the integral indicator(Faulty transmitter)

F0601.ai

Verify and Change Transmitter Parameter Setting and Values

Theparametersrelatedtothefollowingitemsaresetatfactoryasspecifiedinorder.• Calibrationrange• Integralindicatordisplay• Outputmode• Softwaredamping(optional)Otherparameterslikefollowingareshippedwiththedefault setting.• Low-cut• Processalarmsetting• Staticpressurerange• Signalcharacterizer• WriteprotectionToconfirmorchangethevalues,pleaserefertoeachcommunication manual.

Output Status Setting at CPU Failure and Hardware Write Protection

Settheswitchesasshowninthefigurebelowtosettheburn-outdirectionandwriteprotection.TheBurnoutswitchissettotheHsidefordelivery(unlessoptioncode/C1or/C2isspecifiedintheorder),andthehardwarewriteprotectionswitchissettoEsideexceptEJX910AandEJX930A.Thesettingoftheswitchescanbeconfirmedviacommunication.

F0602.ai

H L H L

Slide switch

CPU assembly

BO H L

WR E D

Burnout direction switch

Write protection switch

H L H L

E D E D

Hardware write protection switch (WR)

Write ProtectionSwitch Position

HIGH LOW

Burnout direction switch (BO)

Burnout Direction

Burnout DirectionSwitch Position

YES(Write disabled)

NO(Write enabled)Write Protection

Figure 6.1 Burn-out Direction and Hardware Write Protection Slide Switch

6.2 Zero Point AdjustmentAftercompletingpreparationsforoperatingthetransmitter,adjustthezeropoint.

Zeropointadjustmentcanbedonebyturningthetransmitter’szero-adjustmentscreworbyusingthecommunicator.Thissectiondescribestheprocedureforthezero-adjustmentscrew.Forthezero-adjustmentviacommunication,procedure,pleaserefertoeachcommunication manual.

IMPORTANTDonotturnoffthepowertothetransmitterimmediatelyafterperformingazeropointadjustment.Poweringoffwithin30secondsofperformingthisprocedurewillreturnthezeropointtoitsprevioussetting.

6.2.1 Adjusting Zero Point for Differential Pressure Transmitters

Beforeadjustingzeropoint,makesurethattheequalizingvalve is open.

Zero-adjustment screw coverF0603.ai

Figure 6.2 External Zero Adjustment Screw

Operation

6

Page 53: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<6. Operation> 52

IM01C25A01-01E

Thezero-adjustmentscrewislocatedinsidethecover. Useaslottedscrewdrivertoturnthezero-adjustmentscrew.Equalizethetransmitter,thenturnthescrewclockwisetoincreasetheoutputorcounterclockwisetodecreasetheoutput.Thezeropointadjustmentcanbemadewitharesolutionof0.01%ofthesettingrange.Thedegreeofzeroadjustmentsvarieswiththescrewturningspeed;turnthescrewslowlytomakeafineadjustment,quicklytomakearoughadjustment.

Whenusingdifferentialpressuretransmittersforlevelmeasurementandifyoucannotobtainthelowerrangevaluefromtheactualmeasurementvalueof0%,refertosubsection6.2.2(2).

6.2.2 Adjusting Zero Point for Gauge/Absolute Pressure Transmitters

(1) When you can obtain the Low Range Value from the actual measured value of 0% (0 kPa, atmospheric pressure);

For pressure measurement using gauge pressure transmitters,followthestepsbelowbeforeperformingzeropointadjustment.

1) Closethetapvalve(mainvalve).2) Loosenthefillplugsothatthepressureappliedtothe

transmitterisonlytheheadofthesealliquid.3) Adjustthezeropointatthisstatus.4) Aftertheadjustment,closethefillplugandthen

graduallyopenthetapvalve.

Useaslottedscrewdrivertoturnthezero-adjustmentscrew.Turnthescrewclockwisetoincreasetheoutputorcounterclockwisetodecreasetheoutput.Thezeropointadjustmentcanbemadewitharesolutionof0.01%ofthesettingrange.Sincethedegreeofthezeroadjustmentvarieswiththescrewturningspeed,turnthescrewslowlytomakeafineadjustmentandquicklytomakearoughadjustment.

(2) When you cannot obtain the Low Range Value from the actual measured value of 0%;

Adjustthetransmitteroutputtotheactualmeasuredvalueobtainedbyadigitalmanometeroraglassgauge.

[Example]

Themeasuringrangeof50to250kPa;theactualmeasuredvalueof130kPa.

130–50250–50

Actual measured value= x100=40.0%(=10.4mA)

Turnthescrewtomatchtheoutputsignaltotheactualmeasured value.

6.3 Local Parameter Setting

WARNING

Thelocalpushbuttonontheintegralindicatormustnotbeusedinahazardousarea.Whenitisnecessarytousethepushbutton,operateitinanon-hazardouslocation.

IMPORTANT• Donotturnoffthepowertothetransmitter

immediately after performing parameter setting. Poweringoffwithin30secondsofperformingthisprocedurewillreturntheparametertoitsprevioussetting.

• TheparameterofExtSWmustbe“Enabled”toperformthisconfiguration.Seetheuser’smanualIM01C25T(HART/BRAIN)forthesettingprocedure.

• TheLocalParameterSettingfunctionisavailablewithHARTorBRAINcommunicationtype.

6.3.1 Local Parameter Setting (LPS) Overview

Parameterconfigurationbytheexternaladjustmentscrewandpushbutton(integralindicatorcodeE)offerseasyandquicksetupforparametersofTagnumber,Unit,LRV,URV,Damping,Outputmode(linear/squareroot),Displayout1,andRe-rangebyapplyingactualpressure(LRV/URV).Thereisnoeffectonmeasurementsignal(analogoutputorcommunicationsignal)whenLocalParameter Setting is carried out.

External adjustment screw cover

F0604.ai

Figure 6.3 External Adjustment Screw

Integral indicator

Push-buttonF0605.ai

Figure 6.4 Range –Setting Switch (push button)

Page 54: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<6. Operation> 53

IM01C25A01-01E

F0606.ai

screw

push

push

push

push

push

push

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

Save/Cancel the value

6. Output Mode

2. Press Unit

1. Tag Number*

*

*

*

*

*

*

3. Press LRV

4. Press URV

7. Display Out1

8. LRV-Apply Press

9. URV-Apply Press

5. Damping Time

Select Output mode

Edit Press unit

Select Tag number

Edit Press LRV

Edit Press URV

Edit Display Out1

Set LRV

Set URV

Edit Damping time

ProcessMeasurement

Display Zero adjustment

ProcessMeasurement

Display

8, 9 : Re-range by applying actual pressure

10. Device Information

Activate LPS mode

*: Notethattheabove1to7parameterconfigurationsareavailablewiththesoftwarerevision(SOFTREV)2.03orlater. Softwarerevisioncanbecheckedviaafieldcommunicator(HART/BRAIN)orDTM.PleaserefertoIM01C25T01forHARTparameter“Softwarerev”andIM01C25T03forBRAIN“SOFTREV”.

Figure 6.5

Operation

6

Page 55: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<7. Errors and Countermeasures> 54

IM01C25A01-01E

7. Errors and CountermeasuresNOTE

ForHARTprotocolrevision7,FOUNDATIONFieldbus,PROFIBUSPAandModbuscommunicationtypes,pleaserefertoeachcommunicationmanual.

ThetablebelowshowsasummaryoferrormessagesforBRAINandHART(protocolrevision5)protocols.

Table 7.1 Alarm Message Summary (Except EJX910A and EJX930A)

Indicator Cause Output Operationduring Error Countermeasure

NoneAL. 01CAP. ERR

Sensorproblem. Outputsthesignal(Hold,High,orLow)setwithparameter.

Replacecapsulewhenerrorkeepsappearing even after restart.Capsuletemperaturesensorproblem.

CapsuleEEPROMproblem.AL. 02AMP. ERR

Amplifiertemperaturesensorproblem. Outputsthesignal(Hold,High,orLow)setwithparameter.

Replaceamplifier.AmplifierEEPROMproblem.Amplifierproblem.

AL. 10PRESS

Inputisoutsidemeasurementrangelimit of capsule.

Outputshighrangelimitvalueorlowrange limit value.

Checkinputorreplacecapsulewhennecessary.

AL. 11ST. PRSS

Staticpressureexceedslimit. Continuestooperateandoutput.

AL. 12CAP. TMP

Capsuletemperatureisoutsiderange(–50to130°C).

Useheatinsulationormakelaggingtokeeptemperaturewithinrange.

AL. 13AMP. TMP

Amplifiertemperatureisoutsiderange(–50to95°C).

AL. 30RANGE

Output is outside upper or lower range limit value.

Outputshighrangelimitvalueorlowrange limit value.

Checkinputandrangesetting,andchangethemasneeded.

AL. 31SP. RNG

Staticpressureexceedsspecifiedrange.

Continuestooperateandoutput.

AL. 35 *1

P. HIInputpressureexceedsspecifiedthreshold.

Checkinput.

AL. 36 *1

P. LOAL. 37 *1

SP. HIInputstaticpressureexceedsspecifiedthreshold.

AL. 38 *1

SP. LOAL. 39 *1

TMP. HIDetectedtemperatureexceedsspecifiedthreshold.

AL. 40 *1

TMP. LOAL. 50P. LRV

Specifiedvalueisoutsideofsettingrange.

Holdsoutputimmediatelybeforeerroroccurred.

Checksettingandchangethemasneeded.

AL. 51P. URVAL. 52P. SPNAL. 53P. ADJ

Continuestooperateandoutput. Checkinput.

AL. 54SP. RNG

Continuestooperateandoutputholdingstaticpressurein%.

Checksettingandchangethemasneeded.

AL. 55SP. ADJ

Continuestooperateandoutput. Checkinput.

AL. 60SC. CFG

Specifiedvaluesorsettingstodefinesignalcharacterizerfunctiondonotsatisfythecondition.

Checksettingandchangethemasneeded.

AL. 79OV. DISP

Displayedvalueexceedslimit.

*1:Thesealarmsmayappearonlywhenprocessalarmfunctionisactivated.

Page 56: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<7. Errors and Countermeasures> 55

IM01C25A01-01E

Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)

Integral indicator Cause 4-20mA Output

operation during error Countermeasure

AL. 01 CAP.ERR

Sensorproblem. Outputsthesignal(HighorLow)setwithburnoutdirectionswitch. [statusoutput:undefined]

Replacecapsuleiftheerrorrecursafterthetransmitterisrestarted.

Capsuletemperaturesensorproblem. Replace capsule. CapsuleEEPROMproblem.

AL. 02 AMP.ERR

Amplifiertemperaturesensorproblem. Replaceamplifier.AmplifierEEPROMproblem.Amplifierproblem.A/DConverterproblem.

AL. 03 ET.ERR

Externaltemperaturesensordisconnection.

Checkexternaltemperaturesensor.

— NodeviceIDisfound. Continuestooperateandoutput. Replaceamplifier.AL. 10 PRESS

Differential pressure is outside measurement range limit of capsule.

WhenPVisPresOutputAOupperlimitorAOLowerlimit.

Checkinputorreplacecapsulewhennecessary.

AL. 11 ST. PRSS

Staticpressureexceedslimit. WhenPVisSPOutputAOupperlimitorAOLowerlimit.

AL. 12 CAP.TMP

Capsuletemperatureisoutsiderange(–50to130°C).

Continuestooperateandoutput. Useheatinsulationormakelaggingtokeeptemperaturewithinrange.

AL. 13 AMP.TMP

Amplifiertemperatureisoutsiderange(–50to95°C).

AL. 14 EXT. TMP

Externaltemperatureisoutsiderange. WhenPVisETOutputAOupperlimitorAOLowerlimit.AL. 15

EXT. TMP Externaltemperaturesensorresistanceisoutspecification.

AL. 16 PLS Pulseoutputisoutspecification. Continuestooperateandoutput. Checksettingsandchangethem.AL. 30 PRS.RNG

Differentialpressureexceedsspecifiedrange.

WhenPVisPres.Output AO upper limit or lower limit.

Checkinputandrangesetting,andchangethemasneeded.

AL. 31 SP. RNG

Staticpressureexceedsspecifiedrange.

WhenPVisSPOutput AO upper limit or lower limit.

AL. 32 F. RNG

Flowexceedsspecifiedrange. WhenPVisFlowOutput AO upper limit or lower limit.

AL. 33 ET. RNG

Externaltemperatureexceedsspecifiedrange.

WhenPVisETOutput AO upper limit or lower limit.

AL. 35 P.HI Inputpressureexceedsspecifiedthreshold.

Continuestooperateandoutput. Checkinput.AL. 36 P.LO AL. 37 SP.HI Inputstaticpressureexceedsspecified

threshold.AL. 38 SP.LO AL. 41 F.HI Inputflowexceedsspecifiedthreshold.AL. 42 F.LO AL. 43 ET.HI Inputexternaltemperatureexceeds

specifiedthreshold.AL. 44 ET.LO AL. 50 P. LRV Specifiedvalueisoutsideofsetting

range. Holdsattheoutputvaluethatexistedimmediatelybeforetheerroroccurred.

Checksettingsandchangethemasneeded. AL. 51 P. URV

AL. 52 P. SPN AL. 53 P. ADJ Continuestooperateandoutput. Adjustsettingsandchangethemas

needed.AL. 54 SP. RNG

Holdsattheoutputvaluethatexistedimmediatelybeforetheerroroccurred.

Checksettingsandchangethemasneeded.

AL. 55 SP. ADJ

Continuestooperateandoutput. Adjustsettingsandchangethemasneeded.

AL. 56 ET. RNG

Holdsattheoutputvaluethatexistedimmediatelybeforetheerroroccurred.

Checksettingsandchangethemasneeded.

AL. 57 ET. ADJ

Continuestooperateandoutput. Adjustsettingsandchangethemasneeded.

AL. 58 FL. ADJ

Holdsattheoutputvaluethatexistedimmediatelybeforetheerroroccurred.

Checksettingsandchangethemasneeded.

AL. 59 PLS.ADJ

Specifiedvalueisoutsideofsettingpulse output.

Normalcalculation.

— UnderTemperatureFixMode.PVisET Temp.OutputFixat4mA. LeavefromTemperatureFixMode.

Errors and Counterm

easures

7

Page 57: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

<7. Errors and Countermeasures> 56

IM01C25A01-01E

Integral indicator Cause 4-20mA Output

operation during error Countermeasure

AL. 79 OV. DISP

Displayedvalueexceedslimit. Continuestooperateandoutput. Checksettingsandchangethemasneeded.

AL.87 FLG. HI

Flangetemperatureexceedsapresetupper limit.

ItdependsontheDiagOutOptionsetting.

Off:Continuetooperateandoutput.Burnout:OutputsAOupperlimitorAOlower limit.Fallback:OutputsDiagOutFixedVal.

Checktheheaterfailure.

Checkthecapsuletemp.andAmplifiertemp.

AdjustFlgTempCoef.

AL.87 FLG. LO

Flangetemperatureisbelowapresetlower limit.

AL.88 INVR.DP

Differentialpressure/pressurefluctuationdoesnotreachthereferencelevelrequiredtoblockagedetectionsothatnoblockagedetectioniscarriedout.

Continuetooperateandoutput. Checkprocesscondition.

AL.88 INVR.SL

Low-pressure-sidefluctuationdoesnotreachthereferencefluctuationlevelrequiredtoblockagedetection.

AL.88 INVR.SH

High-pressure-sidefluctuationdoesnotreachthereferencefluctuationlevelrequiredtoblockagedetection.

AL.88 INVR.F

BlkFcannotbeusedforblockagedetection for some reasons.

AL.89 ILBD.OV

Appointedthediagnosisrangeoutside.

AL.89 B BLK

BBlocking(both-sideblockage)isdetected.

ItdependsontheDiagOutOptionsetting.

Off:Continuetooperateandoutput.Burnout:OutputsAOupperlimitorAOlower limit.Fallback:OutputsDiagOutFixedVal.

Checkprocesscondition.

AL.89 H BLK

High-pressure-sideblockageisdetected.

AL.89 L BLK

Low-pressure-sideblockageisdetected.

AL.89 H LRG

Pressurefluctuationamplitudeofhigh-pressure side is large.

AL.89 L LRG

Pressurefluctuationamplitudeoflow-pressure side is large.

AL.89 A BLK

ABlocking(single-sideblockage)isdetected.

AL. 90 SIM UnderSimulationModeforflow. Simulate input output. CheckSimulationMode.AL. 91 F. SIM Under Simulation Mode for device

variables.OutputthesettingvalueofSimulate-Value.

CheckSimulationMode.AL. 91 P. SIMAL.91 SP. SIMAL. 91 ET. SIMAL. 91 TF. SIMAL. 91 PCT. SIMAL. 91 AO. SIM

Page 58: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

57

IM01C25A01-01E

Revision InformationTitle : EJXandEJA-ESeries DifferentialPressureandPressureTransmittersInstallationManualManualNo. : IM01C25A01-01E

Edition Date Page RevisedItem1st Aug.2009 Newpublication

2nd Apr. 2010 7 to 14 2.4 Addlimitationofambienttemperaturefor/HE.

3rd Oct. 2010 1,5and1512330 to 3141 to 43

AddEJX610AandEJX630A.1. Add HART 7 manual.1. Add note for wet location in (c).3. AddEJX630A.5.4 Modifypicturesofcablegland.8. AddparametersforEJX900A(Dev.rev.2).

4th Aug. 2011 1142728363740

1. ModifyTable1.1.2.4.3 Alterthenote(*1)fornameplate.5.2.2 Changethepictureofconfigurationtool.5.2.4 Add note (*3).7 AddHARTprotocolrevision7toNOTE.7 ModifyTable7.2.8 AddHARTprotocolrevision7andEJX910A/EJX930AtoNOTE. DeletetheMenuTreeforEJX910A/EJX930A.

5th Mar. 2012 ReviseCD-R(Ed5).

6th Aug.2012 ―110 to 151742-46

AddEJA-Eseries.AddtableforEJAtoTable1.1.Addnoteforrepresentationofmodelname.Revise ATEX approval.AddmodelstoPEDtable.Add parameters and notes.

7th Jun.2013 ―713 to 1416 and 1720

AddPROFIBUSPA.Add note for multiple approval option.ReplaceATEXtypenbyATEXExic.AddEJA110Ewith/HGtoPEDtable.Modifynoteforinstallationheight.

8th June2014 281728 to 342837 to 42

1. Addnoteforsymbols.2.4.2 RevisecategoryforCSANonincendive.2.7 Update safety requirement standard.5. Revisedrawingsandsymbolsforterminal.5.2.1 Add note for power supply.6.3 Add local parameter setting function.

9th Oct. 2014 8101316 to 17

17293033364041

42

2.4.1 Add information for 1 to 5 V output.2.4.2 Add information for 1 to 5 V output.2.4.3 Add information for 1 to 5 V output.2.4.5 AddEPLcode.Reviseapplicablestandard.Addinformationfor1to5

Voutput.Addnoteforelectrostaticcharge.Addelectricalconnection.2.5 AddstandardforPROFIBUS.5.2 Add Figure 5.2 Terminal. 5.2.1 Add information for 1 to 5 V output.5.3.1 Add information for 1 to 5 V output.5.6 Addapplicability.6.3.1 Add“10.Deviceinformation”6.3.3 Addnoteinthefigure.Addmethodofcancel/save.Delete6.3.4to

6.3.117. CorrectAL31outputoperation.

Page 59: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

58

IM01C25A01-01E

Edition Date Page RevisedItem10th Apr. 2015

1

2

356

7 to 28

283041,49,5251

RemovalofCD-R.1. Modifydescriptions.ReplaceCD-ROMinformationbythe

downloadinginformation.ModifystructureofTable1.1. DeletenoteaboutCD-ROM.1.1 AddWARNINGsign. Add(g)and(h).2. ModifyTable2.1.2.1 Replace Figure 2.2.2.4 DeleteNoteforCD-ROM.AddFieldbusintrinsicallysafetype. (2.4.1bandc,2.4.2b,2.4.3c,dandg,and2.4.4b.)2.5 forProfibus→forFieldbus2.7 AddC22.2standard.5,6and7ModifynoteforCD-ROM.Delete 6.3.2.

11th July2015 26 to 312653

2.4.4 AddSU21andSS26.Adda,b,candd. ReviseNote2.6.3.1 Delete note for 10. from Figure 6.5.

Page 60: User’s Manual EJX and EJA-E Series Differential Pressure ... · [EJX series Communication Manual] Models Document No. Style DPharp HART 5/HART 7 Communication Type IM 01C25T01-06EN

YOKOGAWA ELECTRIC CORPORATIONHeadquarters2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPANPhone : 81-422-52-5555

Branch Sales OfficesOsaka, Nagoya, Hiroshima, Kurashiki, Fukuoka, Kitakyusyu

YOKOGAWA CORPORATION OF AMERICAHead Office12530 West Airport Blvd, Sugar Land, Texas 77478, USAPhone : 1-281-340-3800 Fax : 1-281-340-3838

Georgia Office2 Dart Road, Newnan, Georgia 30265, USA Phone : 1-800-888-6400/ 1-770-253-7000 Fax : 1-770-254-0928

YOKOGAWA AMERICA DO SUL LTDA.Praca Acapulco, 31 - Santo Amaro, Sáo Paulo/SP, BRAZIL, CEP-04675-190Phone : 55-11-5681-2400 Fax : 55-11-5681-4434

YOKOGAWA EUROPE B. V.Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDSPhone : 31-88-4641000 Fax : 31-88-4641111

YOKOGAWA ELECTRIC CIS LTD.Grokholskiy per 13 Building 2, 4th Floor 129090, Moscow, RUSSIAPhone : 7-495-737-7868 Fax : 7-495-737-7869

YOKOGAWA CHINA CO., LTD.3F Tower D Cartelo Crocodile Building, No.568 West Tianshan Road, Shanghai 200335, CHINAPhone : 86-21-62396262 Fax : 86-21-62387866

YOKOGAWA ELECTRIC KOREA CO., LTD.(Yokogawa B/D, Yangpyeong-dong 4-Ga), 21, Seonyu-ro 45-gil, Yeongdeungpo-gu,Seoul, 150-866, KOREAPhone : 82-2-2628-6000 Fax : 82-2-2628-6400

YOKOGAWA ENGINEERING ASIA PTE. LTD.5 Bedok South Road, Singapore 469270, SINGAPOREPhone : 65-6241-9933 Fax : 65-6241-2606

YOKOGAWA INDIA LTD.Plot No.96, Electronic City Complex, Hosur Road, Bangalore - 560 100, INDIAPhone : 91-80-4158-6000 Fax : 91-80-2852-1442

YOKOGAWA AUSTRALIA PTY. LTD.Tower A, 112-118 Talavera Road, Macquarie Park NSW 2113, AUSTRALIAPhone : 61-2-8870-1100 Fax : 61-2-8870-1111

YOKOGAWA MIDDLE EAST & AFRICA B.S.C.(C)P.O. Box 10070, Manama, Building 577, Road 2516, Busaiteen 225, Muharraq,Kingdom of BAHRAINPhone : 973-17358100 Fax : 973-17336100 Apr. '15

Printed in Japan