The operation and functions described in this manual are available from Software Version Mx5000-050-04 onwards.

Manual Mx-5000 Series

User Manual for MX-5100, MX-5200, MX-5400Fire Alarm Control Panels

Page 2: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 2 of 42

This page is intentionally blank

Page 3: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 3 of 42

Table of Contents 1 INTRODUCTION __________________________________________________________ 5

1.1 Standards ____________________________________________________________ 5 1.2 Cautions and Warnings _________________________________________________ 6 1.3 General Description ____________________________________________________ 6

1.3.1 Mx-5000 Series ____________________________________________________ 6 1.3.2 Mx-5000N Series___________________________________________________ 6

2 CONTROLS AND INDICATIONS _____________________________________________ 7 2.1 Graphical Display ______________________________________________________ 8 2.2 LED Status Indicators ___________________________________________________ 9 2.3 Zone LED Status Indicators ______________________________________________ 9 2.4 Control Buttons_______________________________________________________ 10 2.5 Navigation Buttons ____________________________________________________ 10 2.6 Number and Letter Buttons______________________________________________ 11 2.7 Buzzer______________________________________________________________ 11

3 OPERATION ____________________________________________________________ 11 3.1 Access Levels________________________________________________________ 11

3.1.1 Changing from Access Level 1 to Level 2 _______________________________ 12 3.1.1.1 Menu Access___________________________________________________________ 12 3.1.1.2 Control Buttons at Level 1_________________________________________________ 12

3.1.2 Changing from Access Level 2 to 1____________________________________ 12 3.2 Fire Alarm Condition ___________________________________________________ 13

3.2.1 Detailed Fire Alarm Information_______________________________________ 14 3.2.2 Investigation Delays _______________________________________________ 14

3.3 Fault Condition _______________________________________________________ 15 3.4 Disablement Condition _________________________________________________ 16

3.4.1 Disabled Inputs ___________________________________________________ 16 3.4.2 Disabled Outputs __________________________________________________ 17

3.5 Alarm Condition ______________________________________________________ 17 3.6 Supervisory Condition__________________________________________________ 18 3.7 Multiple Conditions ____________________________________________________ 18 3.8 Menu Functions ______________________________________________________ 19

3.8.1 Using the Buttons to Navigate Menus __________________________________ 20 3.8.1.1 Selecting Menu Options __________________________________________________ 20 3.8.1.2 Selecting Individual Zone Numbers _________________________________________ 20

3.9 Viewing _____________________________________________________________ 21 3.9.1 View - Fires ______________________________________________________ 21 3.9.2 View - Faults _____________________________________________________ 21 3.9.3 View - Alarms ____________________________________________________ 21 3.9.4 View - Disabled ___________________________________________________ 21 3.9.5 View - Inputs _____________________________________________________ 22 3.9.6 View - Outputs ____________________________________________________ 22 3.9.7 View - Panel _____________________________________________________ 23

3.9.7.1 Software ______________________________________________________________ 23 3.9.7.2 Local Hardware _________________________________________________________ 24 3.9.7.3 Network Hardware_______________________________________________________ 25

3.9.8 View - Log _______________________________________________________ 25 3.9.8.1 Event Log _____________________________________________________________ 25 3.9.8.2 Alarm Counter __________________________________________________________ 26

3.9.9 View - Network ___________________________________________________ 26 3.9.10 View - Warnings __________________________________________________ 26 3.9.11 View - Supervisory_________________________________________________ 26

3.10 Disabling____________________________________________________________ 27 3.10.1 Disable - Zones and Inputs __________________________________________ 27 3.10.2 Disable - Outputs__________________________________________________ 28

3.10.2.1 All Sounder Outputs _____________________________________________________ 28 3.10.2.2 All Beacon Outputs ______________________________________________________ 28 3.10.2.3 Fire Routing Outputs _____________________________________________________ 28 3.10.2.4 Fire Protection Outputs ___________________________________________________ 28 3.10.2.5 Fault Routing Outputs ____________________________________________________ 28 3.10.2.6 All Other Relay Outputs___________________________________________________ 29

Page 4: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 4 of 42

3.10.2.8 Pager _________________________________________________________________ 29 3.10.2.9 Only Selected Outputs ____________________________________________________ 29

3.10.3 Disable - Controls__________________________________________________ 29 3.10.4 Disable – User ID __________________________________________________ 30 3.10.5 Disable – Groups __________________________________________________ 30

3.11 Enabling ____________________________________________________________ 31 3.11.1 Enable - Zones and Inputs ___________________________________________ 31 3.11.2 Enable - Outputs __________________________________________________ 31 3.11.3 Enable - Groups ___________________________________________________ 31 3.11.4 Enable - Remote __________________________________________________ 31

3.12 Delays ______________________________________________________________ 32 3.12.1 Turn Off Delay Mode _______________________________________________ 32 3.12.2 Turn On Delay-Mode _______________________________________________ 32

3.12.2.1 Extend Delays __________________________________________________________ 33 3.12.2.2 Holiday / Inhibit__________________________________________________________ 33

3.13 Testing______________________________________________________________ 34 3.13.1 Test - Zones ______________________________________________________ 34 3.13.2 Test - Display _____________________________________________________ 35 3.13.3 Test - Buzzer _____________________________________________________ 35 3.13.4 Test - Printer _____________________________________________________ 36 3.13.5 Test - Outputs ____________________________________________________ 36

3.14 Tools _______________________________________________________________ 37 3.14.1 Printing __________________________________________________________ 37

3.14.1.1 Printer Communications Settings____________________________________________ 37 3.14.1.2 Set-up Printer ___________________________________________________________ 37 3.14.1.3 Print Inputs _____________________________________________________________ 38 3.14.1.4 Print Outputs ___________________________________________________________ 38 3.14.1.5 Print Faults _____________________________________________________________ 38 3.14.1.6 Print Disabled___________________________________________________________ 39 3.14.1.7 Print - Log______________________________________________________________ 39 3.14.1.8 Print - Feed Paper _______________________________________________________ 39

3.14.2 Change-Time _____________________________________________________ 40

Page 5: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 5 of 42

1 Introduction

1.1 Standards Advanced Electronics Ltd declare that the products identified below conform to the essential requirements specified in the Construction Products Directive 89/106/EEC:

0786-CPD-20952

EN54-2: 1997 +A1:2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Provided options: - Outputs to Fire Alarm Devices - Output to Fire Routing Equipment - Output to Fire Protection Equipment - Output to Fault Routing Equipment - Investigation Delays to Outputs - Dependency on more than one alarm signal - Fault Signals from Points - Disablement of Points - Alarm Counter - Test Condition - Standardised Input / Output EN54-4: 1997 +A1:2002 +A2:2006 Power supply equipment for fire detection and fire alarm systems for buildings Mx-5100, Mx-5200, Mx-5400 Mx-5100N, Mx-5200N, Mx-5400N

In addition, the products comply with the following:

Low Voltage Directive 2006/95/EC

BS EN60950-1: 2006 Safety of information technology equipment

Electromagnetic Compatibility Directive 2004/108/EC

BS EN55022: 1998 Emissions, Class B

BS EN50130-4: 1996 +A2: 2003 Immunity, Product Family Standard

Page 6: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 6 of 42

1.2 Cautions and Warnings

STOP

Before commencing with installation or operation of the panel, please read this manual carefully. If you are unclear on any point DO NOT proceed. Contact the manufacturer or supplier for clarification and guidance.

Only Trained service personnel should undertake the Installation, Programming and maintenance of this equipment.

This product has been designed to comply with the requirements of the Low Voltage Safety and the EMC Directives. Failure to follow the installation instructions may compromise its adherence to these standards.

This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2 and 4 (1998). Where appropriate, reference is made in this manual to the relevant sections of the EN54 standard for clarification and to ensure that the installation is compliant with the requirements of EN54.

1.3 General Description This manual covers the use and operation of the Mx-5000 & Mx-5000N Series Fire Alarm Control Panels. Refer to the Installation and Commissioning Manual (Document No. 680-165) for details of how to install and program the panel.

1.3.1 Mx-5000 Series The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel.

The Mx-5200 is a Two Loop, Analogue Addressable Fire Alarm Control Panel.

The Mx-5400 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to four loops.

All above models are designed for use with the Apollo (Discovery, Explorer, XP95 and Series 90), Hochiki (ESP) and Argus (VEGA) fire detection devices.

1.3.2 Mx-5000N Series The Mx-5100N is a Single Loop, Analogue Addressable Fire Alarm Control Panel.

The Mx-5200N is a Two Loop, Analogue Addressable Fire Alarm Control Panel.

The Mx-5400N is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to four loops.

All above models are designed for use with the Nittan Evolution fire detection devices.

All panel models are available in a range of enclosure sizes and with a range of alternative optional features.

Page 7: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 7 of 42

2 Controls and Indications The Mx-5000 and Mx-5000N series are provided with indications and control functions as shown in the diagram below and described in the following text.

The LED functions and BUTTON functions may be assigned and used differently in specific countries dependent on the market and standards requirements.

The layout shown below is for the UK version.

!

D E L A Y E D

P O W E R T E S T

F I R E

SYS T E M F A U L T SOU N D E R DIS A B L E D

FIR E P R O T E C T I O N ACT I V A T E D

EVACUATE

RESOUND

LED TEST

RESET

MUTE

SILENCE

ESC MENU

WXYZTUVPQRS

GHI JKL MNO

DEFABC

M O R E A L A R M S D I S A B L E F A U L T

F I R E R O U T I N G A C T I V A T E D F I R E R O U T I N G F A U L T F I R E R O U T I N G D I S A B L E D P R E - A L A R M

SOU N D E R SIL E N C E D SOU N D E R FAU L T

Graphical Liquid Crystal Display

Navigation Keys

Zone LED Indicators (Optional)

Number Keys

Control Keys

General Status Indicators

Slide-in labels are used to annotate Function Indicators and Programmable Control Keys and Indicators.

Page 8: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 8 of 42

The layout shown below is for the PENTA German version.

DIN E N 5 4 - 2 : 1 9 9 7 DIN E N 5 4 - 4 : 1 9 9 7

0Esc Menü

8 97

5 64

2 31

B E T R I E B

F E U E R S T Ö R U N G

AKUSTIK AN

AKUSTIK AUS

SUMMERAUS

RESET

N Ä C H S T E R A L A R M A B S C H A L T U N G R E V I S I O N

AKUST I K A U S STÖRU N G AKUST I K AKUST I K ABGES C H A L T E T SYSTE M S T Ö R U N G

ERKUNDEN STARTEN

Graphical Liquid Crystal Display

Navigation Keys

Number Keys

Control Keys

General Status Indicators

Slide-in labels are used to annotate specific General Status Indicators in addition to Function Indicators and Programmable Control Keys and Indicators.

2.1 Graphical Display The graphical display provides detailed information of the source of fire alarms, faults and warnings. It also shows menus for use when inspecting or programming the operation of the panel. Under normal conditions the panel display shows the access level, time, date and status: -

Mx-5000 LEVEL 2

16:05 04 MAR 2008

NORMAL PANEL OPERATION

(Press Menu to View)

Page 9: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 9 of 42

2.2 LED Status Indicators The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire alarm, fault, disabled or test condition.

Function Colour Description FIRE Red Indicates that the system has detected a fire alarm condition

MORE ALARMS Red Indicates that the system has detected a fire alarm condition (on steady) in more than one zone.

Fault Yellow Indicates that the system has detected a fault condition

Disable Yellow Indicates that part of the system has been disable (i.e. isolated)

Test Yellow Indicates that part of the system is in a test condition

Power Green Indicates the presence of power

Fire Routing Activated Red Indicates that the output to call the Fire Brigade has been Activated

Fire Routing Fault Yellow Indicates that there is a fault condition in the Fire Brigade signalling equipment.

Fire Routing Disabled Yellow Indicates that the output signal to the Fire Brigade is Disabled

Pre-Alarm Yellow Indicates that a smoke or heat detector has detected a change in the environment that may develop into a possible fire alarm condition.

Delayed Yellow Indicates that one or more output circuits are in a delayed operating condition

Fire Protection Activated Red Indicates that the circuit to fire extinguishing or other fire protection equipment has been activated or that the fire protection equipment itself has been activated.

Sounder Silenced Yellow Indicates that the sounders have been silenced

Sounder Fault Yellow Indicates the presence of a fault in one or more sounder wiring circuits

Sounder Disabled Yellow Indicates that one or more sounders have been disabled (i.e. isolated)

System Fault Yellow Indicates the presence of a system fault

Function 1 Red Spare function LED

Function 2 Yellow Spare function LED

Function 3 Yellow Spare function LED

Function 4 Yellow Spare function LED

Function 5 Yellow Spare function LED

The function LED Indicators are programmable and will have been configured and labelled accordingly during installation and commissioning of the system.

The arrangement and definition of the Status LED Indicators depend on the country and market requirements. The functions described are the same and the most common layout is shown.

2.3 Zone LED Status Indicators The Zone LED Status Indications can be included on the main display (up to 20 zones – fire alarm indication only) or can be included as plug in modules below the main display. These show the basic operational state of the zone and can indicate whether the zone is in a fire alarm, fault, disabled or test condition depending on the module installed.

Page 10: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 10 of 42

2.4 Control Buttons The following table contains a list of all of the control button functions available. The buttons available on each product depend on the country of installation and specific market requirements.

Button Description Access Level

More Alarms Press to scroll through Zones in Alarm. The LED indicator turns on to indicate if more than one zone is in alarm.

Available in both Level 1 and Level 2

Reset Press to reset the panel from a fire alarm or latched fault condition.

Only available with Level 2 Access.

!

Mute Press to mute the internal buzzer.

Available in both Level 1 and Level 2

Silence

Press to silence the sounders. Only available with Level 2 Access.

Resound

Press to re-activate the sounders. Only available with Level 2 Access.

Evacuate Press to initiate a manual evacuation and sound the alarms.

Only available with Level 2 Access.

LED Test Press to illuminate ALL LED indicators

Available in both Level 1 and Level 2

Disable Press to disable the zone or device in a fire alarm condition (Australia only).

Only available with Level 2 Access.

Function Button Programmable function – an associated LED indicator can also be programmed

Depends on Programming

2.5 Navigation Buttons

Press to scroll through Menu Options. Press to display more information. Press to scroll through lists of zones or devices.

Press to confirm entry of numeric or letter information entry. Press to confirm selection of a menu option. Press to change some of the configuration options.

Page 11: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 11 of 42

2.6 Number and Letter Buttons

E S C M E N U

W X Y Z T U V P Q R S

G H I J K L M N O

D E F A B C

Used to enter numbers or letters.

Esc

Press to return to a previous menu. Press to exit the menu functions and return to the normal display.

Menu

Press to show or return to Menu Functions.

2.7 Buzzer The buzzer produces two different sounds to differentiate between fire alarm conditions and fault conditions.

Condition Operation

Fire Alarm The buzzer operates with a continuous tone.

Fault The buzzer operates intermittently.

3 Operation

3.1 Access Levels The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These levels are as follows:

Level 1 Untrained user Level 2 Authorised User Level 3 Service and Maintenance Engineer Level 4 Service and Maintenance Engineer – Special Tools required

• A Level 1 Untrained User can view the current operational condition of the system and may

MUTE the internal buzzer. NOTE: Depending on the configuration settings, a Level 1 user may also be permitted to EVACUATE and/or SILENCE and/or RESET the system by pressing the appropriate button and entering a password.

• A Level 2 Authorised User can view the operational condition of the system and may MUTE the internal buzzer. In addition, the EVACUATE, SILENCE and RESET buttons are enabled and access to the Level 2 Menu functions is available. NOTE: There are up to 10 User ID codes available, each with its own password, which can be configured with varying permissions to specific menu function options.

• A Level 3 User has access to program and configure the operation of the panel. This is described in detail in the Installation and Commissioning Manual (Part Number 680-165).

Page 12: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 12 of 42

3.1.1 Changing from Access Level 1 to Level 2 If the panel has an access key switch fitted, use the key in preference to the menu options shown below.

3.1.1.1 Menu Access Press the ‘MENU’ button. The level 1 menu will be displayed as shown below:

[ CONTROLS DISABLED ]

ENABLE CONTROLS VIEW LED-TEST STATUS

To enable the controls, ensure the “Enable Controls” option is highlighted and then press the button. The display then requests entry of the Level 2 or 3 passwords as follows:

[ CONTROLS DISABLED ]

Please Enter Your Password

Enter the password using the number buttons and then press the button. As each number is entered, an asterisk (*) is shown on the display. For example:

[ CONTROLS DISABLED ]

Please Enter Your Password **

If the password is correct, the Level 2 Menu options will be shown.

If the password is incorrect, the display briefly shows the following message.

[ CONTROLS DISABLED ]

Please Enter Your Password Password Not Recognised !

3.1.1.2 Control Buttons at Level 1 If any of the control buttons (Reset, Silence / Resound or Evacuate) are pressed, the display automatically prompts for the password. Enter the password as above.

3.1.2 Changing from Access Level 2 to 1 If the panel has an access key switch fitted, use the key switch.

Alternatively, if passwords are used, select the “Disablement” menu and then select “Disable/Controls” – see section 3.10.3 for details.

Page 13: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 13 of 42

3.2 Fire Alarm Condition When the system registers a fire alarm condition the Red Fire Indicator illuminates, the internal buzzer sounds (continuously) and the display shows the zone in which the fire originated. The sounders, relays and other outputs will be turned on depending on the programming in the panel. An example of the display is shown below: -

FIRE STARTED IN ZONE 1/1 . < Header – Zone № / Device №1

BASEMENT WEST KITCHEN <CALL POINT >

< Location Text for First Zone < Location Text and Type of Device

[ 1 Zone in Fire. Zone 0001] BASEMENT WEST

< No. of Zones in Fire & Last Zone < Zone Description for Last Zone

The upper part of the display shows the origin of the fire. The lower part of the display shows the number of zones in a fire alarm condition and the last zone to enter the fire alarm condition.

If more than one fire alarm condition occurs, the total number of zones in an alarm condition and the last zone in an alarm condition will be updated on the display. If the sounders were silenced, they will sound again whenever the fire spreads to a new zone.

FIRE STARTED IN ZONE 1/1 . < Header – Zone № / Device № BASEMENT WEST KITCHEN <CALL POINT >

< Location Text for First Zone < Location Text and Type of Device

[ 2 Zones in Fire Last Zone 0005] BASEMENT EAST

< No. of Zones in Fire & Last Zone < Zone Description for Last Zone

Press the ‘MUTE’ button to silence the internal buzzer (the FIRE LED will change from flashing to steady illumination).

Press the ‘MORE ALARMS’ button to view an scroll through a full list of zones in a fire alarm condition.

When the panel is enabled for Level 2 Access or, if configured, by entering a password at Level 1, the following functions are available.

Press the ‘SILENCE’ button to silence the sounders.

Press the ‘RESOUND’ button again to re-activate the sounders.

Press the ‘RESET’ button to clear the alarm condition and restore the panel to normal operation.

Press the ‘EVACUATE’ button to initiate a manual evacuation and to activate the sounders. The display will show this fire alarm condition. For example:

FIRE STARTED IN ZONE 100 . MAIN RECEPTION Evacuation Key <SWITCH >

< Location Text for First Zone < Confirmation of Evacuation

[ 1 Zone in Fire. Zone 0100] MAIN RECEPTION

< No. of Zones in Fire & Last Zone < Zone Description for Last Zone

1 The Device Number is only shown on products for the German market – this is the number specifically assigned to the device to denote its number within the associated meldergruppe (Mld).

Page 14: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 14 of 42

3.2.1 Detailed Fire Alarm Information Press the ‘MORE ALARMS’ button to view the list of zones in a fire alarm condition. Press the ‘MORE ALARMS’ button again or use the buttons to scroll through the list. Each press highlights the next zone in the list and scrolls the zone list upwards.

Zone FIRE-LOCATION Scroll ↓ More> 0001 BASEMENT WEST 0005 BASEMENT EAST

< List of Zones in Alarm including < Zone No. and location text

If more detail regarding the source of any fires is required, press the ‘MORE ALARMS’ button or the

buttons to highlight the required zone in alarm and press the button to show further information. For example:

[ FIRES IN ZONE 0001] Scroll ↓ More>Mld Device Text /29 KITCHEN /32 Corridor

< List of devices within the Zone < that are in Alarm

This shows that the device(s) in a Fire Alarm condition in the zone. If there are more devices in alarm, these will be shown in the list (as shown above). Press the buttons to scroll through the devices. Press the button to show further information including state, type, value, loop, address, sector and node.

Press the button or the ‘Esc’ button to return to the previous display. If no button is pressed within 15-seconds, the display automatically reverts to the main display.

3.2.2 Investigation Delays

The Investigation Delay Function can be disabled or enabled as required by EN54: 2. Refer to Section 0.

If the Investigation Delay Function (Stage 1 / Stage 2 Investigation Delay) is enabled, a fire alarm is registered at the panel but does not immediately activate the sounders. On registering the alarm, the display shows:

FIRE STARTED IN ZONE 1/12 . < Header – Zone № / Device № BASEMENT WEST KITCHEN <TEMPERATURE> OUTPUT DELAY 30 s (Press 0 to extend)

< Location Text for First Zone < Location Text and Type of Device < Delay Timer (Stage 1)

[ 1 Zone in Fire. Zone 0001]BASEMENT WEST

The Output Delay Timer shows the amount of time left for investigation. If the alarm is not acknowledged before the Stage 1 timer elapses, the panel will enter a full alarm condition and will activate the sounders.

Pressing the ‘0’ button acknowledges the alarm. This extends the time allowed to investigate the source of the fire.

FIRE STARTED IN ZONE 1/12 . < Header – Zone № / Device № BASEMENT WEST KITCHEN <TEMPERATURE> OUTPUT DELAY 120 s

< Location Text for First Zone < Location Text and Type of Device < Delay Timer (Stage 2)

[ 1 Zone in Fire. Zone 0001]BASEMENT WEST

Page 15: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 15 of 42

The cause of the alarm can now be investigated. If the alarm is a false alarm, pressing the ‘RESET’ button will clear the alarm condition. This must be done before the Stage 2 timer has elapsed or the panel will enter a full alarm condition and will activate the sounders.

Note: The EVACUATION button will terminate the investigation delays and activate all programmed sounders.

3.3 Fault Condition When the system registers a fault condition the Yellow Fault Indicator is illuminated, the internal buzzer sounds intermittently and the display shows the cause of the fault in more detail.

An example of the display is shown below:

ZONE 0001 DEVICE MISSING BASEMENT WEST RESTAURANT (MULTI.SENSOR)

< Location Text for First Zone < Location Text and Type of Device

1 Zone In Fault More>

< No. of Zones in FAULT

If more than one fault condition occurs, these will be shown on the display. If the internal buzzer was muted, it will sound again when a new fault condition is registered.

When the fault condition is corrected, the panel automatically clears the appropriate fault Status Indicators and Display information.

Press the ‘MUTE’ button to silence the internal buzzer The display then shows the current time and date and service centre telephone number along with the indication of the fault.

FOR SERVICE CALL 01234 567890

LEVEL 2 16:05

04 MAR 2008

< Panel access level < Service Call Number < and Time / Date

1 Zone In Fault More>

< No. of Zones in FAULT

To obtain more detailed information about the faults, press the button. The display then presents a list of all of the zones in a fault condition with the first fault highlighted. For example:

[ 2 Zones in Fault] More> ZONE LOCATION 1 BASEMENT 100 RECEPTION

< Number of zones in fault < Zone #, Location Text for each < zone

Press the buttons to highlight the required fault and then press the button to show further information. For example:

[ Faults in Zone 0001 ] More> Mld Device Text /32 Room 112

< Device № (if applicable) & device text description

Press the button to show further information on device state, type, analogue/digital values and loop, address, sector and node, etc.

Press the ‘ESC’ key to return to the previous display.

If no button is pressed within a minute, the display automatically reverts to the main display.

Page 16: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 16 of 42

3.4 Disablement Condition If any zones, input devices or output devices have been disabled, the DISABLE Indicator is illuminated. In addition, the SOUNDER DISABLE Indicator is illuminated if one or more sounder circuits or devices have been disabled. The display indicates the presence of zone disablement conditions in the lower half of the display as follows:

Mx-5000 LEVEL 2

16:05 04 MAR 2006

4 Zones with Disablements More>

When the disablement conditions are removed, the appropriate indications are cleared from the display and from the Indicators. When all disablement conditions are removed, the DISABLE Indicator is also turned off.

To obtain more detailed information about the disablement conditions, press the button. The display will then present the disablement conditions in the following sequence:

♦ Zone / Individual Inputs. ♦ Outputs

[DISABLEMENTS] [ 2 ZONE(s)with INPUTS DISABLED] More> [ 2 ZONE(s)with OUTPUTS DISABLED] More>

< Zone, disablement condition and < location text

Press the buttons to highlight the required option and then press the button to view further information.

3.4.1 Disabled Inputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For example:

[ 2 Zones with Inputs Disabled] More> ZONE MODE LOCATION 0001 PART DISABLED BASEMENT WEST 0002 ALL DISABLED BASEMENT EAST

< Zone, disablement condition and < location text

The display shows the status as ALL DISABLED if every input device within the zone has been disabled and shows the status as PART DISABLED if there is at least one input device within the zone still active.

Press the buttons to highlight the required zone and then press the button to view the location text assigned to the zone in full. For example:

Press the button again to view the inputs within the zone and their status. For example:

[ Inputs in Zone 0001 ] <More> Mld Mode Device Text /32 Disabled Room 244

The display shows the Device Number, current disablement condition (mode) and the device text. Press the buttons to scroll through the inputs.

Page 17: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 17 of 42

Press the button to show further information on the state, type, analogue/digital values, the detection loop (LP) and address (ADRS), etc.

Press the ‘ESC’ key to return.

3.4.2 Disabled Outputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For example:

[ 2 Zone(s)with Outputs Disabled] More> Zone Mode Location 0001 ALL DISABLED BASEMENT WEST 0100 ALL DISABLED RECEPTION

< Zones with location text where < outputs are disabled

Press the buttons to highlight the required zone and then press the button to view the individual outputs and their disablement condition. For example:

[ Outputs in Zone 0100] More> Mode Device Text Disabled Sounder A Disabled Sounder B Disabled Sounder C Disabled Sounder D

The above example shows that the panel sounder circuits are disabled.

Press the button to view further information including type, value and state, etc.

[ Outputs in Zone 0100] <More> Mode Type Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER

Press the buttons to scroll through the list of individual outputs within the selected zone. Press the ‘Esc’ button to return to previous views and the main display.

3.5 Alarm Condition When the system registers a pre-alarm or plant alarm condition, the internal buzzer sounds intermittently and the display shows the cause of the fault in more detail. An example of the display is shown below:

ZONE 0001 PRE-ALARM BASEMENT WEST RESTAURANT (MULTI.SENSOR)

< Location Text for First Zone < Location Text and Type of Device

1 Zone In Alarm More>

< No. of Zones in Alarm

To obtain more detailed information about the alarms, press the button. The display then presents a list of all zones in an alarm condition.

Page 18: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 18 of 42

3.6 Supervisory Condition When the system registers a supervisory condition, the internal buzzer sounds intermittently and the display shows the cause of the fault in more detail. An example of the display is shown below:

ZONE 0011 SUPERVISORY PLANT ROOM SPRINKLER SHUT OFF (INPUT MON)

< Location Text for First Zone < Location Text and Type of Device

1 Zone In Supervisory More>

< No. of Zones in Supervisory

To obtain more detailed information about the alarms, press the button. The display then presents a list of all zones in an alarm condition.

Supervisory conditions are typically (although not exclusively) used to indicate the presence of operating conditions that could prevent the operation of sprinkler valves such as; frozen water, valve shut-off, low pressure, etc.

3.7 Multiple Conditions When the system registers alarm, pre-alarm, fault, disablement, warning, security and supervisory conditions simultaneously, the display shows these in the lower half in priority order. The detail of the most recent unacknowledged condition to occur, however, is shown at the top of the display. An example of the display is shown below:

ZONE 0011 SUPERVISORY PLANT ROOM SPRINKLER SHUT OFF (INPUT MON)

< Location Text for First Zone < Location Text and Type of Device

1 Zone In Alarm ↓ More> 1 Zone In Supervisory More> 1 Zone In Fault More>

< No. of Zones in Supervisory

An arrow is shown on the display to indicate the scroll options. ↓ (first row), ↕, ↑ (last row) are shown depending on the row highlighted.

Press the buttons to scroll through the list to highlight the required condition and then press the button to view more detail as described for each condition.

If the system registers a fire alarm condition, the display is totally devoted to the indication of the fire alarm. Use the View Menu option to display these other conditions.

Page 19: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 19 of 42

3.8 Menu Functions The following Menu Functions are available at Level 2. The display shows the primary Level 2 Menu and the Level 2 User as follows:

[Level 2 Menu] User 1 Node 1 VIEW DISABLE ENABLE TEST DELAY TOOLS STATUS

The following table gives a list of the Level 2 Menu Functions, the sub-functions available within each main function and a brief description for each function.

Main Menu Option Sub Menus Comments Fires View Zones and Inputs that are reporting a fire alarm condition.

Faults View Zones and Inputs that are reporting a fault condition.

Alarms View Zones and Inputs that are reporting an alarm condition.

Disabled View Zones, Inputs and Outputs that are disabled.

Inputs View the current state of Inputs.

Outputs View the current operational condition of all output circuits / devices.

Log View the Event Log / Alarm Counter

Panel View the operational state, voltage and current loading of the panel input and output circuits.

Network View Network diagnostics

Warnings View Zones and Inputs that are reporting a warning condition

VIEW

Supervisory View Zones and Inputs that are reporting a supervisory condition

Zone / Inputs 2 Disable a complete zone or an individual input.

Outputs 2 Disable sounder outputs or other devices.

Controls 3 Cancel Level 2 access.

User ID 3 Return Level 2 access to the default User 1

DISABLE

Groups Disable a user-defined disablement group

Zone / Inputs Enable a complete zone or an individual input.

Outputs Enable sounder outputs or other devices.

Groups Enable a user-defined disablement group

ENABLE

Remote Permits remote access controls

Zones 2 Configure one or more zones for walk test.

Display Test the Graphics Display, Status Indicators and Keyboard.

Buzzer Test the Internal Buzzer

Printer Test the connection to the Printer

TEST

Outputs Test Output Devices

DELAY -- Turn ON / OFF Investigation delays

COMMISSION Enter the Level 3 Commissioning and Panel Programming Functions

Inputs Print the status of inputs

Ouputs Print the status of outputs

Faults Print the fault conditions

Disabled Print the disabled conditions

Log Print the Event Log. (All Events of Fire Only Events Selectable).

Feed Paper Advance the paper in the printer

PRINT

Set-up 2 Configure the printer connection and automatic print options

TOOLS

CHANGE TIME2 Allows authorised level 2 users to change time.

2 This option can be configured per Level 2 User ID. User 1 does not have permission to change these options. 3 Not required if a key switch is fitted to change access levels.

Page 20: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 20 of 42

3.8.1 Using the Buttons to Navigate Menus Press the ‘Menu’ button to bring up the display menu.

3.8.1.1 Selecting Menu Options The Level 2 Menu is shown below:

[Level 2 Menu] User 1 Node 1 VIEW DISABLE ENABLE TEST DELAY TOOLS STATUS

Press the buttons to highlight the required menu option and then press the button to select it.

For example, press the button followed by the button to highlight the DELAY option (as shown below) and then press the button to select this option.

[Level 2 Menu] User 1 Node 1 VIEW DISABLE ENABLE TEST DELAY TOOLS STATUS

Press the ‘Esc’ button from within a menu option to return to the previous menu.

Press the ‘Esc’ button from the Main Level 2 Menu (shown above) to return to the normal operating display.

If a button is not pressed for one minute (15-seconds if the panel is in a fire alarm condition) the display will automatically revert to the normal operating display. Press the ‘Menu’ button to return directly to the Level 2 Menu display previously shown.

3.8.1.2 Selecting Individual Zone Numbers When the display is showing a list of Zone Numbers, it is possible to select a specific zone number by using the number keys. For example, if the display is showing a list of zones:

[ Inputs] More> Zone Mode Location 0001 Enabled BASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION AREA

To select a particular Zone, move to the zone number column. The existing zone number will then be highlighted.

Enter the required Zone Number using the number buttons, for example 12.

[ Inputs] More> Zone Mode Location # 12 Enabled BASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION AREA

Finally press the button to confirm. The display will then show a new list of Zones with the selected Zone highlighted at the top of the list.

If the number is entered incorrectly, press the ‘Esc’ button.

Page 21: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 21 of 42

3.9 Viewing The View menu is available on two pages. Highlight the “Next Menu” option and pres the button to select the next page.

[View Menu 1] User 1 Node 1 FIRES FAULTS ALARMS DISABLED INPUTS OUTPUTS Next Menu

[View Menu 2] User 1 Node 1 PANEL NETWORK WARNINGS SUPERVISORY LOG Next Menu

Note that Fires, Faults, Alarms, Disablements and Supervisory conditions are all normally shown without having to select the view menu. If, however, you wish to manually View any of these, they can be selected from this menu as required.

3.9.1 View - Fires This function shows the Zones and Inputs that are currently in a Fire Alarm condition.

The operation of the panel and the information that can be shown is identical to the views available from the main operating display. Refer to Section 3.2 for further information.

If there are no Zones or Inputs in a Fire Alarm condition, the display automatically reverts to the Main View Menu.

3.9.2 View - Faults This function shows the Zones, Inputs and Outputs that are currently in a Fault condition.

The operation of the panel and the information that can be shown is identical to the views available from the main operating display. Refer to Section 3.3 for further information.

3.9.3 View - Alarms This function shows the Zones and Inputs that are currently in an Alarm condition. These may occur if:

♦ The Zone or Input is currently in a Fire Test condition and / or ♦ Inputs that are configured to generate an alarm or pre-alarm condition when operated are active. The operation of the panel and the information that can be shown is identical to the views available from the main operating display.

3.9.4 View - Disabled This function shows only Inputs and Outputs that are currently in a Disabled condition.

The operation of the panel and the information that can be shown is identical to the views available from the main operating display. Refer to Section 3.4 for further information.

If there are both Inputs and Outputs in a Disabled condition, the display presents the inputs first followed by the outputs.

If there are no Inputs or Outputs in a Disabled condition, the display does not change and continues to show the Main View Menu.

Page 22: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 22 of 42

3.9.5 View - Inputs This function shows the current operational condition for all Zones and Individual Inputs. The display presents a list of all of the zones containing input devices, with the first zone highlighted. For example:

[Inputs] More> Zone Mode Location 0001 Enabled Kitchen 0002 Disabled Reception 0013 Enabled Lobby 0014 Enabled Corridor

Press the buttons to highlight the required zone and then press the button to view the individual inputs. For example:

[ Inputs in Zone 0001] <More> Mld Mode Device text / 1 Enabled Kitchen / 2 Disabled Reception

3.9.6 View - Outputs This function shows the current operational condition for all Outputs.

[Outputs] More> Zone Location 0002 Reception 0003 Ground Floor 0013 First Floor Corridor 0014 First Floor

Press the buttons to highlight the required zone and then press the button to view the individual outputs. For example:

[ Outputs in Zone 0003] <More> Mld Mode Device text Enabled Kitchen Disabled Reception

Press the button to view further information on each point, for example:

[ Outputs in Zone 0003] <More> Mld Mode State Type Enabled Off SOUNDER Disabled RELAY

A * symbol preceding the state (e.g. *On) indicates the device has been configured as an inverted output (e.g. a fault relay that is designed to de-energise when a fault occurs).

The state of an output that is disabled is not shown, as it will inherently be in the off condition.

Page 23: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 23 of 42

3.9.7 View - Panel The View Panel Option provides three items to view diagnostic on the panel.

[Panel Information] LOCAL-HARDWARE SOFTWARE NETWORK-HARDWARE

Press the buttons to highlight the required menu option and then press the button to select it.

• Local hardware provides information on the circuits of this panel.

• Network hardware provides information on the circuits of other panels / nodes on the network.

• Software provides information on the operating software of this panel and its optional interface cards.

3.9.7.1 Software [Software] PANEL DISPLAY LOOP CARDS NETWORK PSU PERIPHERAL PRINTER

Panel Software:

[Software] PROGRAM ID : MX5000-050-04 CHECKSUM : 92879016

Other Software:

Select the other options and the display shows the software version incorporated into these circuit cards / functions and the hardware build variant. An number of peripheral modules may be installed (up to 32) – press the buttons to scroll through the list if required.

[Software] ADRS.CARD TYPE VERSION BUILD 1 Display Card 1.03 00

If there are no devices installed of the type selected, the display shows:

[Software] ADRS.CARD TYPE VERSION BUILD NO DEVICES

Page 24: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 24 of 42

3.9.7.2 Local Hardware The Local Hardware Option provides a diagnostic readout of the operational condition and readings for the internal panel electronic circuits of this panel. When the option is selected, the display shows a list of the circuits. For example:

[Panel Circuits] DESCRIPTION VALUE STATE Sounder A 5.6V Normal Sounder B 5.6V Normal Sounder A Load 0mA Normal Sounder B Load 0mA Normal

The following table lists the internal panel circuits and indicates the values that can be displayed.

Description Value Range Normal Possible States

Sounder A

Sounder B 4 0V – 14V 5.5V Normal Open Circuit, Short Circuit

Sounder A Load

Sounder B Load 4 0mA – 1000mA 5 Normal Too High

Battery 0V – 30V 27.6V Normal Too High, Too Low

Charger 0V – 30V 28.0V Normal Too High, Too Low

Charger Current 0mA – 2000mA 5 Normal

Charger Temp (C) 0C – 50C 5 Normal

Earth Volts 0V – 30V 2.5V / 14.5V6

Normal Too High, Too Low

System Volts 19V – 30V 28.0V Normal

Aux Load 0mA – 500mA 5 Normal Too High

1st Loop Load 7 0mA – 500mA 5 Normal Open Circuit, Too High, Short Circuit

1st Loop V.Out 7 24V – 32V 5 Normal

1st Loop V.In 7 24V – 32V 5 Normal

L/H L Normal Programmable inputs

Normal Panel Switch Inputs 1-9

L/H L Normal

Relay 1 – – Normal

Relay 2 – – Normal

Relay 38 – – Normal

Relay 48 – – Normal

Main Supply – – Normal

Pager – – Normal

Press the buttons to scroll through the panel internal circuits. Press the ‘Esc’ button to return to the main view menu.

NOTE: Additional panel circuits may be shown depending on the system configuration and installed options.

4 The MX-5400 also displays Sounders C and D. 5 Depends on the panel configuration, installation and current operating condition (i.e. fire alarm). 6 Depends on configuration of the panel. 7 Loop Load, V.Out and V.In displayed for each loop driver (2 on MX-5200, 4 on Mx-5400). 8 Requires the installation of the 2-Way Relay card option.

Page 25: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 25 of 42

3.9.7.3 Network Hardware The Network Hardware Option provides a diagnostic readout of the operational condition and readings for the internal panel electronic circuits of other nodes / panels on the network. When the option is selected, the display shows a list of the nodes indexed by their assigned zone number. For example:

[HARDWARE] More> Zone Location 1700 Ground Floor Panel 1701→ Reception Panel 1702→ First Floor Panel 1703→ Second Floor Panel

Press the buttons to scroll through the panels to highlight the required panel.

Press the button to view the individual circuit information for the panel selected. The information includes the circuit text and current value as per the local hardware option. Press the buttons to scroll through the circuits on the selected panel. Additionally, the sector, node, circuit number and address information are also available.

3.9.8 View - Log After selecting to view the log option the display presents a pop-up window to allow selection between a view of all of the event history, a view of only the fire alarms that have occurred or a view of the fire alarm counter.

ALL EVENTS . FIRE EVENTS ONLY ALARM COUNTER

Press the buttons to highlight the required menu option and then press the button to select it. The display then shows the appropriate list of events.

3.9.8.1 Event Log The display will always show the most recent event to have occurred, e.g.

[View Fire Events] Entry 0076 Time/Date Node Lp:Addr Zone 10:54:23 1 1:001.0 001 14/03/06 FIRE ALARM 64 BASEMENT ROOM 10

< Number of Highlighted Event < Time, Origin and Zone < Date, Event and Analogue Value < Zone Text Description < Device Location Description

In the above example, the latest fire occurred (Event No. 76) at 10:54 am on March 14, 2006. This fire alarm originated at the device at address 001(Addr) on Loop 1 (Lp) on Panel No. 1 (Panel). The device was in Zone 001. The analogue value registered by the device (64) has also been recorded. The lower two lines show the zone and device location texts descriptions for ease of identification.

Press the buttons to scroll through the fire alarm events logged in the system. Press the button to show more recent events and press the button to show earlier events.

To view the details for a specific Log Entry Number, it is possible to select the record by typing in the required number using the number keys.

Press the button to confirm. The display will then display the required record.

Press the ‘Esc’ button to return to the main view menu.

Page 26: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 26 of 42

3.9.8.2 Alarm Counter

Section 7.13

Alarm Counter. The Panel records the number of times that the fire alarm condition has occurred at the panel.

[View Alarm Counter] 0000000033

In the above example, the panel has entered the fire alarm condition 33 times since it was installed.

The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm events do not increment the counter.

Press the ‘Esc’ button to return to the main view menu.

3.9.9 View - Network This Option can be used to obtain diagnostic information when a network is used to connect other panels or remote terminals. The access level of all panels on the network can be checked from this display:

[NETWORK – Press 0 to Clear] More> Node Status 1 LOCAL 2 Level-2 3 Level-1 4 -

Additional network diagnostics are available by selecting the “More>” option.

For further information, refer to the Ad-Net network manual (Document No. 680-502).

Pressing '0' allows the stored network status information to be cleared.

3.9.10 View - Warnings This Option can be used to obtain information about warning conditions on the panel.

A warning condition is created whenever a detector device reaches its limit drift of compensation. This does not affect the performance or operation of the panel in detecting and responding to fire alarm conditions from the device. It will mean the device is more sensitive and could react to lower levels smoke stimuli resulting in false alarms. This function is normally used by the service engineer to view which devices need to be cleaned and no indication is given of this condition on the normal displays. A fault condition will occur when the device becomes dirty.

3.9.11 View - Supervisory This Option can be used to obtain information about supervisory conditions on the panel.

The operation of the panel and the information that can be shown is identical to the views available from the main operating display. Refer to Section 3.6 for further information.

If there are no Zones or Inputs in a Supervisory condition, the display automatically reverts to the Main View Menu.

Page 27: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 27 of 42

3.10 Disabling On selecting the Disable Menu, the display shows five possible options. For example:

[Disable] User 1 Node 1 ZONE/INPUTS OUTPUTS GROUPS CONTROLS USER-ID

Press the buttons to highlight the required menu option and then press the button to select it.

3.10.1 Disable - Zones and Inputs This option provides the means to disable a complete zone, disable all input devices except call points or disable individual input devices.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

On selecting this option, the display shows a list of the current zones and their current disablement status. For example:

[ 0 Zones with Inputs Disabled] More> Zone Mode Location 0001 Enabled BASEMENT WEST 0002 Enabled BASEMENT EAST 0008 Enabled GROUND FLOOR 0009 Enabled MAIN RECEPTION AREA

Press the buttons to scroll through the available zones, or key in a specific zone number.

To disable the entire zone, move over to the Mode column and highlight the existing mode. Press the button and a pop-up window appears showing the possible options: -

ALL INPUTS . SELECTED INPUTS

Press the buttons to scroll through and highlight the required option and then press the button to select it.

If ALL INPUTS is chosen, the pop-up window disappears and the State of the Zone is changed to ALL DISABLED.

If SELECTED INPUTS is chosen, the pop-up window disappears and a list of the input devices within the selected zone is presented. For example:

[ Inputs in Zone 0001] More> Mld Mode Device Text / 1 Enabled Room 151 / 2 Disabled Room 152 / 3 Enabled Kitchen /14 Enabled Lobby

Press the button for more information on the inputs, including full state, type, analogue value etc.

Press the buttons to scroll through and highlight the required input and then press the button to disable it.

Press the ‘Esc’ button to return.

Page 28: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 28 of 42

3.10.2 Disable - Outputs The Disable Outputs Option enables the isolation of some or all of the outputs. If disabled, the outputs will not activate in the event of a fire alarm or other programmed event.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

[Disable]

Enter the password as normal. Once a valid password has been entered, a pop-up window is shown on the display to select the type of outputs to disable. Scroll down to view / select the available options. The list below details all of the possible options – the available options will have been configured by the installation engineer.

ALL OUTPUTS

ALL SOUNDERS ALL BEACONS FIRE ROUTING OUTPUTS FIRE PROTECTION OUTPUTS ↓ FAULT ROUTING OUTPUTS ALL OTHER RELAY OUTPUTS ONLY SELECTED OUTPUTS PAGERS

3.10.2.1 All Sounder Outputs Press the buttons to scroll through and highlight the ALL SOUNDERS Option and then press the button to disable them. The display automatically reverts to the Main Disable Menu.

The ‘Sounder Disabled’ Indicator will be illuminated.

3.10.2.2 All Beacon Outputs Press the buttons to scroll through and highlight the ALL BEACONS Option and then press the

button to disable them. The display automatically reverts to the Main Disable Menu.

NOTE: This only applies to individually addressable beacons. For some combined sounder/beacon devices, the beacon follows the operation of the sounder and it is only possible to disable both the sounder and the beacon together.

3.10.2.3 Fire Routing Outputs Press the buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then press the button to disable all fire routing outputs. The display automatically reverts to the Main Disable Menu.

The ‘Fire Routing Disabled’ Indicator will be illuminated.

3.10.2.4 Fire Protection Outputs Press the buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then press the button to disable all fire protection outputs. The display automatically reverts to the Main Disable Menu.

3.10.2.5 Fault Routing Outputs Press the buttons to scroll through and highlight the FAULT ROUTING OUTPUT Option and then press the button to disable all fault routing outputs. The display automatically reverts to the Main Disable Menu.

Please Enter Your Password

Page 29: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 29 of 42

3.10.2.6 All Other Relay Outputs Press the buttons to scroll through and highlight the ALL OTHER RELAY OUTPUTS Option and then press the button to disable them. The display automatically reverts to the Main Disable Menu.

3.10.2.8 Pager Press the buttons to scroll through and highlight the PAGER OUTPUT Option and then press the button to disable all pager outputs. The display automatically reverts to the Main Disable Menu.

3.10.2.9 Only Selected Outputs Allows selection of a single output.

3.10.3 Disable - Controls Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation.

If the panel has an access key switch fitted, use the key switch in preference to the menu option shown below.

[Disable] User 1 Node 1 ZONE/INPUTS OUTPUTS GROUPS CONTROLS USER-ID

Press the buttons to highlight the Controls option and then press the button to select it.

The display then prompts for password entry. Enter the password as normal.

When a valid password has been entered, the control button functions and menu functions are disabled and the level 1 menu display will be shown: -

[ CONTROLS DISABLED ]

ENABLE CONTROLS VIEW LED-TEST STATUS

The display will automatically revert to the normal operating display after a few seconds.

Page 30: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 30 of 42

3.10.4 Disable – User ID This operation will cancel the current User ID and return to the default User 1. User 1 can perform all actions except those defined as programmable (refer to the menu table).

[Disable] User 5 Node 1 ZONE/INPUTS OUTPUTS GROUPS CONTROLS USER-ID

Press the buttons to highlight the User-ID option and then press the button to select it.

[Disable] User 1 Node 1 ZONE/INPUTS OUTPUTS GROUPS CONTROLS USER-ID

NOTE: If configured to operate with a timeout and if there has been no user activity after the programmable period of time (default “No Timeout”), the panel will automatically cancel a User ID and return the panel to User 1 ID access. This is to ensure that access to restricted options is automatically cancelled.

3.10.5 Disable – Groups Disablement Groups are a means of disabling / enabling custom groups of devices. The commands are command across the network of panels and can be invoked from any panel. The installer will have configured these groups.

If no groups exist, selection of this option will show a NOT CONFIGURED message.

Some typical examples are:

Stage Smoke Detectors

Floor 2 Sounders

ALL Sounders

The display will show, for example:

[Disable Group] User 5 Node 1 Group Invoke Description 1 . - Stage Smoke Detectors 2 - Floor 2 Sounders 3 - ALL Sounders

Press the buttons to scroll through and highlight the required option and then press the button to disable it. The display will show that the command has been invoked (activated).

[Disable Group] User 5 Node 1 Group Invoke Description 1 . ok Stage Smoke Detectors 2 - Floor 2 Sounders 3 - ALL Sounders

The GENERAL DISABLE and any specific disable indicators will be illuminated on the panel(s).

Page 31: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 31 of 42

3.11 Enabling On selection of the Enable Menu Option, the display shows the available Enable Functions.

[Enable] User 1 Node 1 ZONE/INPUTS OUTPUTS GROUPS REMOTE

Press the buttons to highlight the required menu option and then press the button to select it.

3.11.1 Enable - Zones and Inputs Selecting this option will show a list of zones containing disabled input devices. Either the complete zone, or individual devices within the zone can then be enabled (Display format is virtually identical to the Disable displays).

3.11.2 Enable - Outputs When this option is selected, a pop-up menu appears asking if you want to enable ALL SOUNDERS, ALL BEACONS, FIRE ROUTING OUTPUTS, FIRE PROTECTION OUTPUTS, FAULT ROUTING OUTPUTS, ALL OTHER RELAY OUTPUTS, ONLY SELECTED OUTPUTS or the PAGER OUTPUT. If ONLY SELECTED OUTPUTS is selected, the display will list only zones containing outputs that have been disabled. The individual outputs within the zone can then be enabled.

(The display format is virtually identical to the Disable displays).

3.11.3 Enable - Groups This option allows the re-enabling of User-defined Disablement Groups. The display is identical to the disable option.

3.11.4 Enable - Remote Information on the detectors connected to the panel and on the condition of all zones can be obtained with an ipGateway interface.

In addition, the user can be assisted with operations such as disabling / enabling a detector from external commands over a TCP/IP system. In order to ensure this only happens with the consent of the user the REMOTE option must be enabled by the user.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

After selecting the option, a selection list is presented on the display as follows:

[Remote Access Options] DISABLE REMOTE ACCESS ALLOW REMOTE ACCESS .

Use the buttons to highlight the required option and then press the button to confirm.

Page 32: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 32 of 42

3.12 Delays

[Level 2 Menu] User 1 Node 1 VIEW DISABLE ENABLE TEST DELAY TOOLS STATUS

Press the buttons to highlight the Delay-Mode option and then press the button to select it. If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

If the delays are configured in the panel, the display shows the following pop-up window when the Delay-Mode Option is selected. (Note: This delay function can only be configured using the PC Programming Tool).

NO INVESTIGATION DELAY

ONCE ONLY AUTOMATIC

EXTENDED ↓

If the delays are not configured in the panel, the display briefly shows “NOT CONFIGURED” before returning to the Disable Menu Options.

3.12.1 Turn Off Delay Mode This operation will cancel the Investigation Delay mode.

With the option highlighted, press the button to select NO INVESTIGATION DELAYS and disable the operation of the Stage 1 / Stage 2 Investigation Function. Otherwise, press the ESC to cancel and keep the investigation delays in operation.

If the investigation delays are in operation then the “Delayed” LED Indicator is illuminated. When the investigation delays are turned off, the “Delayed” LED Indicator is turned off.

Press ‘Esc’ to cancel and make no change to the current operational setting.

3.12.2 Turn On Delay-Mode This option allows the operation of Investigation Delays and other related functions.

The Investigation Delays can be invoked as manual operation delays (Once Only), Automatic delays (configured to run with a time clock) and Extend delays. A further option is provided to Inhibit delays for holiday periods. The options that appear in the menu depend on the installation configuration programmed by the installer.

On selection of the DELAY option, the display will show a pop-up menu list. For example:

NO INVESTIGATION DELAY

ONCE ONLY . AUTOMATIC EXTENDED ↓

Press the buttons to scroll through and highlight the required option and then press the button to enable it.

The display will confirm the selection and indicate WORKING whilst it performs the operation. On completion, it reverts to the pop-up menu.

For Extended and Holiday/Inhibit, further menus are presented.

Page 33: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 33 of 42

3.12.2.1 Extend Delays To extend any current automatic delays (for example overtime working).

Extend Delays for : ..0 hour(s)

Use the number keys to enter the required number of hours beyond the current configured end time.

3.12.2.2 Holiday / Inhibit The panel can be enabled to prevent any pre-programmed daily automatic delays from activating during holiday periods. On selection, the display shows:

[Inhibit Delay End Date] TIME = 15:49 DATE = 02/07/08 WED 02 JUL 2008

Press the buttons to select the time / date fields. Enter the required time and date using the number buttons.

Any pre-configured automatic delays or manual delays will be immediately suspended and the panel will operate without any investigation delays.

On reaching the time / date programmed, the panel will automatically revert to use any investigation delays as programmed and configured.

Page 34: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 34 of 42

3.13 Testing [Test Menu] User 1 Node 1 ZONES DISPLAY BUZZER PRINTER OUTPUTS

Press the buttons to highlight the required menu option and then press the button to select it.

3.13.1 Test - Zones The Test Zones function provides the means to implement a one-person walk test in order to test specific call points or detectors in one or more zones.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

When the Test Zones option is selected, a pop-up window is shown on the display to select whether the sounders will activate (for about 10-seconds) when an input device is activated. For example:

WITHOUT SOUNDERS . WITH SOUNDERS

Press the buttons to scroll through and highlight the required option and then press the button to select it.

Note that the panel will have been programmed during commissioning to define which of the sounders are activated during a test.

The display then shows a list of the available Zones and their current test status. For example:

[ 0 Zones in Test ] Zone Test State Location >0001 - BASEMENT WEST 0002 - BASEMENT EAST 0100 - MAIN RECEPTION

Press the buttons to scroll through and highlight the required zone and then press the button to change the Test State. For example:

[ 1 Zone in Test ] Zone Test State Location 0001 IN TEST BASEMENT WEST 0002 - BASEMENT EAST 0008 - GROUND FLOOR 0009 - MAIN RECEPTION AREA

When one or more Zones are placed in a Test State, the Test Indicator will be illuminated. When an input device is activated (i.e. break glass test on a call point or introducing test smoke into a smoke detector), the bells will ring (if selected) and the display will indicate that a zone is registering a test condition by showing an exclamation mark (!) on the display.

[ 2 Zones in Test ] Zone Test State Location 0001 IN TEST ! BASEMENT WEST 0002 - BASEMENT EAST 0008 - GROUND FLOOR 0009 IN TEST MAIN RECEPTION AREA

Page 35: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 35 of 42

When the activating test key is removed from the call point or the smoke clears from the detector chamber, the panel will automatically reset and clear the test condition.

As an alternative to scrolling, a specific zone number can be entered by using the button to move to the zone number column, and then typing in the required number, followed by the button.

If several consecutive zones are to be tested, an alternative to selecting them all individually is to specify a range of zones as follows: -

Move to the zone number column and highlighting the first zone to test, then

Press the button – the display will then ask for the last zone to be tested.

Individual zones can then be toggled in or out of test by pressing the button.

To leave the Zone Test menu, press the ‘Esc’ button. If there are still any zones in a test condition a pop-up window with the following options: -

FINISHED TEST . KEEP ZONES IN TEST

Selecting the FINISHED TEST option will cancel all zone tests. The Test LED will then extinguish.

Alternatively, it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the KEEP ZONES IN TEST option. This will enable the inspection or use of other menu functions and return the display to the normal operating mode. The Test LED will stay illuminated if this option is selected.

3.13.2 Test - Display The Test Display option checks the operation of all the Indicators and the Graphic Display. All of the Indicators are turned on and the entire display is shown in reverse.

During this test, it is possible to test the operation of the , , , , and 0-9 buttons. When a button is pressed, it is indicated on the display. For example:

LCD & KEY TEST ←

Press the ‘Esc’ button to return to the Test Menu. If no button is pressed for 1-minute, the display will automatically revert to the normal operating display.

3.13.3 Test - Buzzer [Test Menu] User 1 Node 1 ZONES DISPLAY BUZZER PRINTER OUTPUTS

When the Test Buzzer option is selected, the internal buzzer will sound for about five seconds.

Page 36: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 36 of 42

3.13.4 Test - Printer To invoke the printing of a test print sequence, highlight the Test Print Option and press the button to confirm. The panel transmits 16 lines of test characters to the printer. The information sent is echoed on the display.

When the test print is completed, the display automatically reverts to the Test Options Menu.

Press the ‘Esc’ button at any time to cancel the test print.

3.13.5 Test - Outputs Output devices can be individually tested for operation.

To test an individual output device (sounder or relay), highlight the Test Outputs Option and press the button to confirm. The display will present a list of the zones that contain output devices.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent operation.

[Outputs] Zone Location 0001 BASEMENT WEST 0002 BASEMENT EAST 0037 EAST PLANT ROOM 0100 MAIN RECEPTION

Press the buttons to scroll and highlight the required zone (or key in the required zone number) and then press the button to show the output devices in that zone. For example:

[ Outputs in Zone 37] <More>Mode Device Text Enabled Room 151 Enabled Room 152

Press the buttons to scroll and highlight the required output and then press the button to test the output. The display will prompt to confirm the “Test this device”. Press the button again to accept. The output device will turn on and this will be confirmed on the display by the status changing from OFF to ON. Press the button to show further information on the output.

The general “TEST” LED will illuminate whenever an output is in test. The test is cancelled by either pressing the ESC button or by scrolling to the next / previous device in the list. If the display is left for one minute without pressing any buttons, the output will revert to its quiescent state.

On networked systems, the Test – Outputs option also supports testing of outputs connected to other panels.

Page 37: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 37 of 42

3.14 Tools [Tools] User 1 Node 1 COMMISSION PRINT CHANGE TIME

The TOOLS menu presents three options. Press the buttons to highlight the required menu option and then press the button to select it.

The COMMISSION Menu is only available to Level 3 Service Users.

3.14.1 Printing [Print Menu] User 1 Node 1 INPUTS OUTPUTS FAULTS DISABLED LOG FEED-PAPER SETUP PRINTER

3.14.1.1 Printer Communications Settings The information is sent to the printer in a serial form. If an external printer is used, ensure that the communications settings in the printer are set as follows:

Interface Type: RS232

Baud Rate: 9600

Parity: None

Data Bits: 8

Stop Bits: 1

3.14.1.2 Set-up Printer To enable or set-up the operating characteristics of the printer, highlight the Set-up Printer Option and press the button to confirm.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

Enter the password as normal. The display then shows a pop-up window giving programming options as follows:

[FIRES] [ALARMS] [FAULTS] [TESTS]

- -

( Printer: Internal External/Wide ) - -

The upper line of options determines whether the panel shall automatically print specific events as they occur.

The lower line of options determines whether a printer is connected and its type.

Use the , , , and buttons to highlight the required option and change its setting. Pressing the button turns the option on ( is shown) or off (- is shown) accordingly.

In the above option, an external printer is selected, with automatic printing of fires and alarms.

Setting the wide option will change the printing from the default 40 characters per line to 80 characters per line.

Note: Only faults registered on this panel are printed.

Page 38: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 38 of 42

3.14.1.3 Print Inputs To print information on any input, highlight the Inputs option and press the button to confirm. The display will show the following:

[Inputs] First Zone : 98 Last Zone : 98 (Press → to Start Print)

The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones used in the system. Use the arrow ( ) buttons to highlight the first and last zone number and use the number keys to change the zone number required.

Press the key to start printing.

The display will show the following whilst information is sent to the printer and printed.

WORKING ... (Press Esc to Stop)

After all information has been printed, the display will automatically revert to the Print Menu. Press the “Esc” key to stop printing if required.

The printout will show all input points for the zones selected. Information printed includes Device Text, Zone Number, Loop and address, current status and analogue value.

3.14.1.4 Print Outputs To print information on any output, highlight the Outputs option and press the button to confirm. The display will show the following:

[Outputs] First Zone : 98 Last Zone : 98 (Press → to Start Print)

The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones used in the system. Use the arrow ( ) buttons to highlight the first and last zone number and use the number keys to change the zone number required.

Press the key to start printing.

The printout will show all output points for the zones selected. Information printed includes Device Text, Zone Number, Loop and address, current status and analogue value.

3.14.1.5 Print Faults To print information on any faults, highlight the Faults option and press the button to confirm. The display will show the following:

[ 2 Zones in Fault] First Zone : 98 Last Zone : 99 (Press → to Start Print)

The panel analyses the network and the display will prompt the zones in a fault condition.

Page 39: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 39 of 42

Use the arrow ( ) buttons to highlight the first and last zone number and use the number keys to change the zone number as required.

Press the key to start printing.

The printout will show the location and state of all input and output points in a fault condition for the zones selected.

Note: If no fault conditions are present then selecting this menu option will no effect.

3.14.1.6 Print Disabled To print information on any disablement, highlight the Disabled option and press the button to confirm. The display will show the following depending on the disabled conditions present:

If there are zones with inputs disabled:

[ 2 Zone(s) with Inputs Disabled] First Zone : 98 Last Zone : 99 (Press → to Start Print)

If there are zones with outputs disabled:

[ 1 Zone(s) with Outputs Disabled] First Zone : 98 Last Zone : 98 (Press → to Start Print)

The panel analyses the network and the display will prompt the zones in a disabled condition.

Use the arrow ( ) buttons to highlight the first and last zone number and use the number keys to change the zone number as required.

Press the key to start printing.

The printout will show the location and state of all input and output points in a disabled condition for the zones selected.

The display always present the zones with inputs disabled first (if any exist). After printing the inputs the display will present the information on disabled outputs (if any exist).

Note: If there aren’t disabled conditions present then selecting this menu option will no effect.

3.14.1.7 Print - Log To print information from the History Log, highlight the Print Log Option and press the button to confirm. A pop-up window will be shown asking if all events, or just fires should be printed.

Highlight the required option using the buttons and press the button to confirm.

When the Log Print is completed, the display automatically reverts to the Print Options Menu.

Press the ‘Esc’ button at any time to cancel the log print.

Note: The pop-up window also allows selection of the Fire Alarm Counter. On selection, this is shown on the display but is not printed.

3.14.1.8 Print - Feed Paper Highlight the Feed Paper Option and press the button to confirm. The display does not change but a command is sent to the printer to advance the paper.

Page 40: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 40 of 42

3.14.2 Change-Time Allows the clock time to be changed.

If the current User ID does not have the necessary permission, the display prompts for entry of a password to guard against inadvertent changes.

For example:

[SET TIME/DATE] TIME = 15:28 DATE = 05/01/09 MON 5 JAN 2009

To change the settings, use the buttons to highlight the required option. Directly enter the new time or date using the number buttons. As soon as a number button is pressed, the display will clear the current setting and show the new value as it is entered. For example:

[SET TIME/DATE] TIME = 1-:-- DATE = 05/01/09 MON 5 JAN 2009

If this panel is connected to a network, ALL panels on the network will assume this new value.

Page 41: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Page 41 of 42

USER NOTES:

Page 42: User Manual for MX-5100, MX-5200, MX-5400 Fire Alarm ... Mx-5000 User Manual.pdf · The Mx-5100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel. The Mx-5200 is a Two

Advanced Electronics Limited 34 Moorland Way Nelson Park Cramlington Northumberland NE23 1WE Tel: +44 (0)1670 707 111 Fax: +44 (0)1670 707 222 Web: www.Advel.co.uk Email: [email protected]

Doc Number 680-166 Revision 03 First Issued 2010-01-19