Upload
phamdat
View
238
Download
15
Embed Size (px)
Citation preview
USER MANUAL FOR
EG1298 FIXED SPEED
CONTROLLER Product Manual Revision # 1.00
ABSTRACT This manual is intended as
an information guide for
operating SEDEMAC's
EG1298 fixed speed governing
solution.
Doc #SED-MAN-EG1298-002 Date: 11-Sep-2017
Copyright
All rights reserved. No part of this publication may be reproduced, distributed or transmitted
by any means (including photocopying or storing in any medium by electronic means or other)
without the prior written permission of the copyright holder. Any reference to trademarked
product names used within this publication is owned by their respective companies.
SEDEMAC Mechatronics Pvt. Ltd. reserves the right to change the contents of this document
without prior notice. For permission requests and applications to reproduce any part of this
publication should be addressed to SEDEMAC Mechatronics Pvt. Ltd at below mentioned
contact details.
SEDEMAC Mechatronics Pvt. Ltd. C9-10, C Block, MIDC Bhosari Pune 411026, INDIA Web Support: Email: [email protected] Website: www.sedemac.com Telephonic Support: +91-20-67313500 +91-8551039888 +91-8551041888 +91-8551043888
SEDEMACTM
Page 3 of 36
Safety Instructions
General Instructions ✓ This document includes important instructions that should be followed during installation and mainte-
nance of the Generator Set controller.
✓ For safety reasons, the manufacturer recommends that this equipment be installed and serviced by
an Authorized Service personnel. Follow all applicable state and local electrical codes.
✓ Efficient and safe operation of the controller can be acquired only if the equipment is correctly oper-
ated and maintained. Many accidents arise due to ignorance or illiteracy towards the elemental rules
of safety and precautions.
The following safety notations found throughout this document indicate potentially hazardous conditions to the
operator, service personnel or the equipment.
• Highlights an essential element of a procedure to ensure correctness
• Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment
• Indicates a procedure or practice, which could result in injuring personnel or loss of life, if not followed correctly
Electrical safety ✓ Electric shock can cause severe personal injury or death.
✓ Ensure the generator set must be grounded before performing any installation or service.
✓ Generators produce high electrical voltages direct contact with it can cause fatal electrical shock. Pre-
vent contact with terminals, bare wires, connections, etc., while the generator and related equipment
are running. Do not tamper with interlocks.
✓ To handle the maximum electrical current, sizes of wire gauge used for electrical connections and wir-
ings must be appropriate to which they will be subjected to.
In operation safety ✓ Before installing Genset controller, ensure that all power voltage supplies are positively turned off at
their source. Disconnect the generator’s battery cables and remove panel fuse to prevent accidental
start up. Disconnect the cable from the battery post, indicated by a NEGATIVE, NEG, or (–) first. Re-
connect the negative cable last. Failure to do so will result in hazardous and possibly fatal electrical
shock.
✓ Remove electric power supply before removing controller or touching other electrical parts.
✓ Use extreme caution when working on electrical components. High voltage can cause injury or death.
✓ Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when
working near Generator set or other electrical equipment.
✓ Do not wear damp clothing (Particularly wet shoes) or allow skin surface to be damp when handling
electrical equipment.
SEDEMACTM
Page 4 of 36
✓ Do not operate any electrical device or wires while standing in water, while barefoot, or while hands or
feet are wet. IT MAY RESULT IN SEVERE ELECTRICAL SHOCK.
✓ Do not wear jewellery. Jewellery can cause a short circuit within electrical contacts and cause shock
or burning.
✓ In case of an accident caused by electric shock, immediately shut down the electrical power source. If
this is not possible, try to release the victim from the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting object, like, a rope or wooden stick, to release the victim from the
live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
SEDEMACTM
Page 5 of 36
List of Abbreviation This list contains the list of acronyms used in this document and it can be used to refer their respective description. This List Does not contain units of measure.
Acronym Description
AC Alternating Current
ACK Acknowledge
ALT Alternator
AMF Auto Mains Failure
AUX Auxiliary
BTS Base Transceiver Station
CHG Charging
CKT Circuit
CT Ratio Current Transformer Ratio
DC Direct Current
DG Diesel Generator
DIG IN Digital Input
ENG TEMP Engine Temperature
GCU Genset Control Unit
Genset Generator Set
GND Ground
HMI Human Machine Interface
HSD High Side Driver
HWT High Water Temperature
LCD Liquid Crystal Display
LED Light Emitting Diode
LLOP Low Lube Oil Pressure
LOP Lube Oil Pressure
LVL Level
MCP Manual Control Panel
MPU Magnetic Pickup Unit
OV Over Voltage
PID Proportional Integral Derivative
PWM Pulse Width Modulation
RMS Root Mean Square
RPM Revolutions Per Minute
R-Y-B Red-Yellow-Blue
SCP Sensor Common Point
SMD State Machine Diagram
TEMP Temperature
USB Universal Serial Bus
UV Under Voltage
SEDEMACTM
Page 6 of 36
Table of Contents 1 Introduction .......................................................................................................................... 9
1.1 Features .......................................................................................................................... 9
2 System Components ........................................................................................................... 9
2.1 EG1298 Controller .......................................................................................................... 9
2.2 Actuator ......................................................................................................................... 10
2.3 O/E/N Relays: 741-12-1A-25A ...................................................................................... 10
3 Configurations ................................................................................................................... 11
3.1 Terminals diagram ......................................................................................................... 12
3.2 Circuit Diagram ............................................................................................................. 13
3.3 Specifications ................................................................................................................ 15
4 Module Display .................................................................................................................. 16
4.1 Monitoring Mode ........................................................................................................... 16
5 Description of Control Keys ............................................................................................. 19
6 Mode selection in EG1298................................................................................................. 20
7 Configuration Mode ........................................................................................................... 20
7.1 Configurable Parameters .............................................................................................. 21
8 Deep Sleep Mode ............................................................................................................... 25
9 Paralleling Mode ................................................................................................................ 25
9.1 Paralleling concept ........................................................................................................ 25
9.2 Speed Bias/ Paralleling Support Mode .......................................................................... 25
9.3 Configuration in EG1298 ............................................................................................... 25
10 Shutdown and Warning alarms ........................................................................................ 26
11 Do's and Don'ts .................................................................................................................. 27
12 Troubleshooting ................................................................................................................. 27
13 Maintenance ....................................................................................................................... 29
14 MODBUS Based Protocol ................................................................................................. 30
14.1 Connection Details ..................................................................................................... 30
14.2 Supported Functions .................................................................................................. 30
14.3 Register Map ............................................................................................................. 32
SEDEMACTM
Page 7 of 36
List of Figures Figure 1: Representative drawing of the EG1298 electronic governor’s front fascia .................... 9
Figure 2: ACTZ02A (Standard), ACTZ06A (Mid Torque), ACTZ11A (High Torque) ..................... 10
Figure 3: O/E/N Relays: 741-12-1A-25A .................................................................................... 10
Figure 4: O/E/N Relays: 741-12-1A-25A .................................................................................... 11
Figure 5: Representing configuration diagram of EG1298 ......................................................... 11
Figure 6: Terminals diagram ....................................................................................................... 12
Figure 7: Fixed speed governing for single phase genset. ......................................................... 13
Figure 8: Fixed speed governing for three phase genset. .......................................................... 14
Figure 9: Control keys function ................................................................................................... 19
Figure 10: Mode selection in EG1298 ........................................................................................ 20
Figure 11: Paralleling of genset .................................................................................................. 25
Figure 12: Representing analog voltage input terminal of EG1298 ............................................ 26
Figure 13 : Governor configuration screen in SEDEMAC's Smart Config .................................. 26
SEDEMACTM
Page 8 of 36
List of Tables Table 1: Environmental specifications ........................................................................................ 15
Table 2 : Technical specifications ............................................................................................... 15
Table 3 : Screens of engine status and operating mode............................................................. 16
Table 4 : Screens of configuration mode .................................................................................... 20
Table 5 : Configurable parameters ............................................................................................. 21
Table 6 : List of digital input sources selection ........................................................................... 24
Table 7 : List of digital output source selection ........................................................................... 24
Table 8 : Table for shutdown and warning alarms ....................................................................... 27
Table 9 : List of do's and don'ts .................................................................................................. 27
Table 10 : List of faults and remedial actions .............................................................................. 27
Table 11 : Command from MODBUS master for Function 4 ....................................................... 30
Table 12: Normal response from EG1298 slave for Function 4 .................................................. 30
Table 13 : Command from MODBUS master for function 16 ...................................................... 31
Table 14 : Normal response from EG1298 slave for function 16 ................................................ 31
Table 15: Command from MODBUS master for Function 3 ........................................................ 31
Table 16 : Normal response from EG1298 slave for Function 3 ................................................. 31
Table 17 : Register map for input registers ................................................................................. 32
Table 18 : Interpretation of alarm status results .......................................................................... 34
SEDEMACTM
Page 9 of 36
1 Introduction
This document presents the information necessary for operating SEDEMAC's EG1298 controller. It also provides the user with the necessary background for using EG1298 controller in an application that involves communication of the genset controller with an external system such as a server or a remote data communication system.
SEDEMAC's EG1298 is a modern and feature rich engine controller with user-friendly HMI and full graphics LCD. The EG1298 provides the Isochronous speed governing feature along with the option to switch over load based droop governing and paralleling support. The EG1298 also offers engine safety and load monitoring. The EG1298 controller comes bundled with highly versatile software & extensive I/O's and thereby supports a wide variety of industry standard features in diesel/gasoline engines. The EG1298 can be configured through SEDEMAC's Windows PC utility, (Refer section SEDEMAC Smart
Config). Also, all parameters can be configured using the keypad of the controller.
1.1 Features
• Isochronous speed governing with paralleling support
• Configurable load based droop governing
• Engine safety and load monitoring
• PC connectivity via USB port, RS485
• Real time clock based event logs
• RPM sensing using frequency & Magnetic Pickup
• Backlit and full graphics display with power saving feature
2 System Components
2.1 EG1298 Controller
Figure 1: Representative drawing of the EG1298 electronic governor’s front fascia
SEDEMACTM
Page 10 of 36
2.2 Actuator
Figure 2: ACTZ02A (Standard), ACTZ06A (Mid Torque), ACTZ11A (High Torque)
2.3 O/E/N Relays: 741-12-1A-25A
Figure 3: O/E/N Relays: 741-12-1A-25A
SEDEMACTM
Page 11 of 36
Figure 4: O/E/N Relays: 741-12-1A-25A
3 Configurations
Figure 5: Representing configuration diagram of EG1298
SEDEMACTM
Page 12 of 36
3.1 Terminals diagram
Figure 6: Terminals diagram
SEDEMACTM
Page 13 of 36
3.2 Circuit Diagram
Fixed Speed Application
Figure 7: Fixed speed governing for single phase genset.
SEDEMACTM
Page 14 of 36
Figure 8: Fixed speed governing for three phase genset.
SEDEMACTM
Page 15 of 36
3.3 Specifications
Table 1: Environmental specifications
Operating/Storage Temperature
-20 to 65˚C as per IEC 60068-2-1, 2
Vibration
2G in X, Y and Z as per IEC 60068-2-6
Humidity
0 to 95% RH as per IEC 60068-2-78
EMI/ EMC
Compliance as per IEC 61000-6-2, 4
Power Supply
8V – 32V DC continuous
Ingress Protection
IP65 for front face with optional gasket as per IEC 60529
Shock 15g for 11 ms, compliance as per IEC 60068-
2-27
Table 2 : Technical specifications
Power Consumption
~1.2A @12V or 24V DC
Digital Output
6 x 1A high-side drivers configurable for over speed, under speed, engine running etc.
Digital Input
5 switch-to-ground inputs configurable for engine start, engine stop, emergency stop
Analog Input 1 analog input (0V - 5V) for E-Gov speed bias
E-governor Module Interface
1A, 2-phase output for Rotary Actuator 0V – 5V input for target speed bias; 2.5V for zero bias
Genset Current Measurement
0A – 5A AC RMS for Current Transformer (CT) secondary
Magnetic Pickup Measurement
0.2V – 45V AC RMS @100 Hz – 10 kHz
EG1298 controller dimension External dimensions: 139 x 114 x 37.5 mm3 Mounting panel cut: 118 x 93 mm2
SEDEMACTM
Page 16 of 36
4 Module Display
4.1 Monitoring Mode
In monitoring mode, the screen will scroll automatically after a predefined time which can be configured in configuration menu or you can use the “Navigation Up/Down” keys to scroll/browse the screens.
Table 3 : Screens of engine status and operating mode
Screen 1: ENGINE STATUS Screen 2: ENGINE STATUS
Screen 3: ENGINE STATUS Screen 4: ENGINE STATUS
Screen 5: ENGINE STATUS Screen 6: ENGINE STATUS
(The controller will display engine status and the configured governing mode on ENGINE STATUS screen.)
Screen 7: GENERATOR L-N VOLT Screen 8: GENERATOR L-L VOLT
((L2 and L3) / (L2L3 and L3L1) / (PF2 and PF3) will be visible only if the controller is configured for 3 phase genset.
SEDEMACTM
Page 17 of 36
Screen 9: LOAD CURRENT Screen 10: GENERATOR LINE kW
Screen 11: GENERATOR TOTAL kW Screen 12: GENERATOR LINE kVA
Screen 13: GENERATOR TOTAL kVA Screen 14: GENERATOR LINE kVAr
Screen 15: GENERATOR TOTAL kVAr Screen 16: GEN LINE PF
Screen 17: GEN TOTAL PF Screen 18: GEN FREQ
SEDEMACTM
Page 18 of 36
Screen 19: GENERATOR POWER COUNT Screen 20: ENGINE SPEED
Screen 21: ENGINE RUN TIME Screen 22: DATE AND TIME
Screen 23: PRODUCT ID Screen 24: ENGINE SR NO.
Screen 25: ALARMS Screen 26: ENGINE STATUS
SEDEMACTM
Page 19 of 36
5 Description of Control Keys
Figure 9: Control keys function
1. Menu Navigation UP key
2. Menu Navigation DOWN key
3. Stop key
4. To acknowledge and clear the alarm
5. Mode select key
1
2
3
4
5
SEDEMACTM
Page 20 of 36
6 Mode selection in EG1298
Figure 10: Mode selection in EG1298
7 Configuration Mode
To configure the controller, please follow the below mentioned instructions.
To enter the configuration mode press and hold “Stop” and “Ack” keys simultaneously. Please note that, while pressing keys, press “Ack” key just before “Stop” key otherwise controller will start Stop Wait Delay.
Table 4 : Screens of configuration mode
Screen 27: Configuration Mode Screen 28: Configuration mode: Authentication Page
To enter the edit/write mode press “Mode/Select” key. If you wish to read the configuration, press “Stop” key (Refer Screen 27). To access the configuration menu, please enter your 4-Digit PIN here using “Navigation Up/Down” keys (Refer Screen 28). Once you enter the “EDIT” mode, scroll to the parameter that you wish to edit and press “Mode/Select” key to edit the parameter. At this moment, the parameter will start blinking and you can change the parameter value using “Up” and “Down” keys (Refer section
SEDEMACTM
Page 21 of 36
Configurable Parameters). After selecting the required value, press “Mode/Select” key to save parameter or “Stop” key to discard the value.
7.1 Configurable Parameters
* Level 2 names in sentence case are written how they display on Smart Config GUI and names in bracket with capital case are written how they display on controller
Table 5 : Configurable parameters
Level 0 Level 1 (On screen) Level 2 (On screen) * Possible Value (On screen)
Module (MODULE)
General (GENERAL)
Profile Name
Engine ID XXXXXXXXXXXX
Power on Lamp Test (POWER ON LAMP
TEST)
Disable, Enable
Deep Sleep Mode (DEEP SLEEP MODE)
Disable, Enable
Display (DISPLAY)
Contrast (CONTRAST)
0 – 100 %
Power Save Mode Enable (POWER SAVE MODE)
Disable, Enable
Communication (COMMUNICATION)
Communication Mode MODBUS
Slave ID (MODBUS SLAVE ID)
1 – 247
Baudrate (BAUDRATE)
1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200
Parity Bit (PARITY)
None, Even, Odd
Digital Inputs (INPUTS)
Digital Input A (DIG IN A)
Source (SOURCE)
Refer Table 6
Name Auxiliary Input A
Polarity (POLARITY)
Close to Activate, Open to Activate
Action (ACTION)
None, Warning, Shutdown
Activation (ACTIVATION)
Never, From Engine Start, From Monitoring On, Always
Activation delay (ACTIVATION DELAY)
1 – 60 Sec
Digital Input B (DIG IN B)
Source (SOURCE) Refer Table 6
Name Auxiliary Input B
Polarity (POLARITY)
Close to Activate, Open To Activate
Action (ACTION)
None, Warning, Shutdown
Activation (ACTIVATION)
Never, From Engine Start, From Monitoring On, Always
Activation delay (ACTIVATION DELAY)
1 – 60 Sec
Digital Input C (DIG IN C)
Source (SOURCE)
Refer Table 6
Name Auxiliary Input C
Polarity (POLARITY)
Close To Activate, Open To Activate
Action (ACTION)
None, Warning, Shutdown
SEDEMACTM
Page 22 of 36
Level 0 Level 1 (On screen) Level 2 (On screen) * Possible Value (On screen)
Activation (ACTIVATION)
Never, From Engine Start, From Monitoring On, Always
Activation delay (ACTIVATION DELAY)
1 – 60 Sec
Digital Input D (DIG IN D)
Source (SOURCE)
Refer Table 6
Name Auxiliary Input D
Polarity (POLARITY)
Close To Activate, Open To Activate
Action (ACTION)
None, Warning, Shutdown
Activation (ACTIVATION)
Never, From Engine Start, From Monitoring On, Always
Activation delay (ACTIVATION DELAY)
1 – 60 Sec
Digital Input E (DIG IN E)
Source (SOURCE)
Refer Table 6
Name Auxiliary Input E
Polarity (POLARITY)
Close To Activate, Open To Activate
Action (ACTION)
None, Warning, Shutdown
Activation (ACTIVATION)
Never, From Engine Start, From Monitoring On, Always
Activation delay (ACTIVATION DELAY)
1 – 60 Sec
Outputs (OUTPUTS)
Output A (OUT A)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Output B (OUT B)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Output C (OUT C)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Output D (OUT D)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Output E (OUT E)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Output F (OUT F)
Source (SOURCE)
Refer Table 7
On Activation (POLARITY)
De-energise, Energise
Timers (TIMERS)
General (GENERAL)
Safety Monitoring Delay (SAFETY MON DELAY)
10 – 60 Sec
Engine Stop Hold Delay (ENG STOP HOLD
DELAY)
0 – 120 Sec
Stop Action Delay (STOP ACTION TIME)
10 – 120 Sec
Power Save Mode Delay 5 – 1800 Sec
SEDEMACTM
Page 23 of 36
Level 0 Level 1 (On screen) Level 2 (On screen) * Possible Value (On screen)
(PWR SAVE MODE DELAY)
Screen Changeover Time (SCRN CHNGOVER
TIME)
1– 1800 Sec
Deep Sleep Mode Delay (DEEP SLP MODE
DELAY)
5 – 1800 Sec
Generator (GENERATOR)
Generator Configuration
(ALT CONFIG)
Number of Poles (NUMBER OF POLES)
2, 4, 6, 8 Poles
Alternator AC System (ALT AC SYSTEM)
1, 3 Phase
Current Monitoring (CURR MON)
CT Ratio (CT RATIO)
0 – 8000/5
Load Monitoring (LOAD MON)
Generator Rating (GEN RATING)
0.0 – 6000.0 kVA
Engine (ENGINE)
Speed Monitoring (SPEED MON)
Engine Speed Sense Source (SPEED SENSE
SOURCE)
Magnetic Pickup, Alternator frequency (Alt Freq)
Flywheel Teeth (FLYWHEEL TEETH)
1 – 300
Under-Speed Action (UNDER SPEED
ACTION)
None, Warning, Shutdown
Under-speed Threshold (UNDER SPEED THRESHOLD)
0 – 3600 RPM
Under-speed Delay (UNDER SPEED DELAY)
1 – 60 Sec
Over Speed Action (OVER SPEED ACTION)
Shutdown
Over-speed Threshold (OVER SPEED THRESHOLD)
1000 – 4000 RPM
Over-speed Delay (OVER SPEED DELAY)
1– 20 Sec
Rotary Actuator (ROTARY
ACTUATOR)
General (GENERAL)
Actuator speed (ACTUATOR SPEED)
1 – 10 x25 Hz
Actuator Direction (ACTUATOR DIRECTION)
Clockwise, Anti-Clockwise
Governing Mode (GOVERNING MODE)
PID Fixed Speed, Auto Tune Fixed Speed
Set Speed Selection (SET SPEED SELECTION)
Fixed Speed (0% Droop), Load Based Droop, Speed
Bias Input (0-5 V)
Cranking Steps (CRANKING STEPS)
50 – 5000
Load Droop (LOAD DROOP)
0 – 4 %
RPM Step-up Rate (RPM STEP UP RATE)
1 – 50 RPM/Sec
RPM Stepdown Rate (RPM STEP DOWN
RATE)
1 – 50 RPM/Sec
Target Speed (TARGET SPEED
500 – 4000 RPM
SEDEMACTM
Page 24 of 36
Level 0 Level 1 (On screen) Level 2 (On screen) * Possible Value (On screen)
/RECOVERY)
Generator Egov Configuration (GEN EGOV
CONFIG)
Proportional Gain (Kp) (PROPORTIONAL GAIN)
0 – 1000
Integral Gain (Ki) (INTEGRAL GAIN)
0 – 2000
Derivative Gain (Kd) (DERIVATIVE GAIN)
0 – 1000
Friction Setoff (FRICTION SETOFF)
0 – 1000
Gain Schedule Trigger (GAIN SCHEDULE
TRIGGER)
0.0 – 100.0 % RPM error
Loading Factor (LOADING FACTOR)
0 – 1000
Unloading Factor (UNLOADING FACTOR)
0 – 1000
Engine Start Strategy (ENG START
STRGY)
Initial Low Speed Delay (INIT LOW SPEED
DELAY)
0 – 180 Sec
Initial Low Speed (INIT LOW SPEED)
500 – 1800 RPM
PID Trigger Speed (CRANK SENSE SPEED)
20 – 2800 RPM
Ramp Up Time (RAMP UP TIME)
1 – 180 Sec
ID
Engine Sr. No. (ENGINE SR NO)
############ 0 – 9, A – Z for each digit
PIN 1 #### 0 – 9 for each digit
PIN 2 #### 0 – 9 for each digit
Active profile Active profile (ACTIVE PROFILE)
PROFILE NAME Profile 1
Table 6 : List of digital input sources selection
# Source (On screen) # Source (On screen)
1 Not Used 4 Engine Start
2 User Configured 5 Engine Stop
3 Emergency Stop (Emergency Stop)
Table 7 : List of digital output source selection
# Output source (On screen) # Output source (On screen)
1 Disable 6 Digital Input E
2 Digital Input A 7 Emergency Stop
3 Digital Input B 8 Over Speed
4 Digital Input C 9 Under Speed
5 Digital input D 10 Engine Running
SEDEMACTM
Page 25 of 36
8 Deep Sleep Mode
Deep Sleep Mode is a useful feature to prolong the battery life.
The controller goes in Deep Sleep Mode when engine is off and there is no user interaction for the pre-set Deep Sleep Mode Delay duration. To wake up controller from Deep Sleep Mode, press and hold “Stop” key for minimum one sec. The controller will wake up from Deep Sleep Mode, on reception of Engine Start or Engine Stop or Emergency Stop command. If engine is failed to start, the controller will enter the Deep Sleep Mode again.
9 Paralleling Mode
9.1 Paralleling concept
Figure 11: Paralleling of genset
Paralleling is the operation in which multiple gensets, usually two or more, are synchronized and then connected to a common bus. The frequency, voltage, phase angle and phase rotation of all the genset must match within prescribed limits before they can be paralleled. By considering linear relation between speed of the engine and frequency of the alternator output, the speed must be controlled until the genset is synchronized with the grid or other genset with the help of electronic governor. A Load Sharing Module controls the speed and the voltage of the genset by controlling the AVR and E-governor of the genset. To control these two devices the LSM provides the DC analog voltage signal to the both devices. The speed bias signal is generally in the range of 0-5 V-DC.
9.2 Speed Bias/ Paralleling Support Mode
This system can be configured in Fixed Speed mode with Speed Bias/Paralleling support. In this mode, EG1298 controller maintains the engine speed in accordance to the speed bias signal provided by Load Sharing Module (LSM).
9.3 Configuration in EG1298
Following is the stepwise procedure for configuring EG1298 for paralleling operation.
• Select Governing Mode as PID Fixed Speed or Auto Tune Fixed Speed.
• Select Set Speed Selection as Speed Bias Input (0-5 V).
SEDEMACTM
Page 26 of 36
• Select proper thresholds for over Speed and under Speed.
• Provide 0-5 V analog signal from the LSM to EG1298 controller at terminal no. 23, as a speed bias signal (Refer Figure 13).
Figure 12: Representing analog voltage input terminal of EG1298
Screenshot representing configuration of paralleling support mode using SEDEMAC's Smart Config
.
Figure 13 : Governor configuration screen in SEDEMAC's Smart Config
10 Shutdown and Warning alarms
The EG1298 controller allows to configure several shutdown and warning alarms.
An alarm condition occurs when the preconfigured parameters are outside the pre-set level. On initiation of an alarm, the Alarm LED will start blinking. The controller will display number of alarms and the nature of alarm on Alarms screen. All the alarms will be activated at the end of Safety Monitoring Start delay.
When Shutdown alarm occurs, controller commands genset to stop. Warning alarms serves to draw operators attention to an undesirable condition without affecting the operation of the genset. Different shutdown and warning alarms are as mentioned below.
SEDEMACTM
Page 27 of 36
Table 8 : Table for shutdown and warning alarms
Sr. No.
Shutdown / Warning Alarms
Description
1 Auxiliary Input/user defined name
Configured auxiliary input has triggered longer than pre-set duration
2 Emergency Stop Indicated that engine is required to stop immediately
3 Under Speed The engine speed has fallen below the preset RPM
4 Over Speed The engine speed has exceeded above the preset RPM
5 No Speed Signal Indicates that MPU connections are lost
11 Do's and Don'ts
Table 9 : List of do's and don'ts
Sr. No.
Do's Don'ts
1 SEDEMAC's EG1298 is auto tuned for engine. It is just plug and play type.
Do not change governing parameters without consulting SEDEMAC's experts.
2 FIP's stop lever is free to rotate. Do not disturb throttle setting for FIP.
3 Follow recommended wiring diagram for CT connections and alternator phase (R-Y-B) sequence.
Do not change CT connections and alternator phase sequence.
4 Follow Actuator fitment diagram for proper working.
Do not disturb Actuator setting.
5 Check engine high idle by pulling FIP's lever to full position.
Do not disturb engine high Idle setting.
12 Troubleshooting
This section explains the common faults and their remedial actions.
Table 10 : List of faults and remedial actions
Sr. No.
Fault Remedial Actions
1
Engine speed hunting OR Engine runs at wrong speed
• Check FIP throttle setting I. Start the engine.
II. Manually take the FIP's stop lever to full position. III. Check whether range for engine speed is correct. IV. If engine speed is wrong, adjust the FIP's throttle setting.
• Make sure that FIP's stop lever is free to rotate. Check whether grease is present in linkage bearings.
• Check floating link length is as per the design.
• Check whether FIP's fuel filter is clean. Check that
• FIP's stop lever spring is removed. Check FIP further.
• Check engine.
2 Engine cranks but does not start
• Check wiring of Actuator and MPU (if used) for loose connections: Refer connection diagrams.
• Check whether EG1298 controller is powered ON.
• If not, I. Check the battery voltage.
II. Check the fuse on the battery supply. III. Check continuity between battery positive and controller
terminal # 2. IV. Check continuity between battery ground and controller
terminal # 1.
• Check MPU (if used) on crank wheel I. Crank the engine. During cranking, check EG1298
SEDEMACTM
Page 28 of 36
Sr. No.
Fault Remedial Actions
controller's power. II. Check continuity between battery positive and controller
terminal # 42. III. Use multimeter in "AC voltage" mode. When engine is
running, check voltage at MPU terminal. IV. Check whether MPU voltage is in correct range. V. If MPU voltage is low, stop the engine. Remove the MPU
from flywheel housing & install it again. VI. If MPU voltage found to be zero, MPU is faulty. VII. If the MPU's voltage is correct and check wiring harness.
VIII. Check MPU configuration in EG1298.
• Check START signal wiring to EG1298 I. Check whether the MPU signal (if used) and main
alternator voltage signal (R phase) are received by the EG1298 controller's terminals. Check wiring harness.
II. If the reading of the voltage is found wrong, refer to the connection diagram.
• Check Actuator on FIP I. Keep multimeter in “resistance mode”. II. Remove the 4-pin Actuator connector. Check resistance
between Actuator wires- BLUE & ORANGE wires. III. Check resistance between Actuator wires- RED &
YELLOW. IV. Correct voltage range is as per design.
• If the resistance reads wrong, then Actuator is faulty. Replace the Actuator.
3 Engine starts, but automatically stops after some time or Engine runs properly, but does not stops
• Check STOP signal wiring to EG1298 I. Check whether EG1298 controller is powered ON. II. Check whether the MPU signal (if used) and main
alternator voltage signal (R phase) are received by the EG1298 controller's terminals. Check wiring harness.
III. If the voltage reading is wrong, refer connection diagram.
• Check Actuator on FIP I. Keep multimeter in “resistance mode”. II. Remove the 4-pin Actuator connector. Check resistance
between Actuator wires- BLUE & ORANGE wires. III. Check resistance between Actuator wires- RED &
YELLOW. IV. Correct voltage range is as per design.
• If wrong resistance is found in the reading, then Actuator is faulty. Replace the Actuator.
4 The controller displays incorrect PF value or kW or load current.
• Check wiring of the respective alternator phase voltage and the CT to the EG1298 controller.
• Check the CT ratio (if kW or current reading is faulty).
• Check generator current and load monitoring configuration in the controller.
5 The controller displays incorrect main alternator voltage.
• Check the wiring of the respective phase to the controller.
• Check mains configuration in the controller.
6 The controller displays incorrect engine RPM.
• Check MPU (if used) connection and configuration.
• Check the main alternator's voltage signal to the controller.
• Check wiring of the main alternator’s R phase and neutral to the controller.
• Check engine speed monitoring configuration in the EG1298 controller.
SEDEMACTM
Page 29 of 36
13 Maintenance
For the smooth functioning, following regular maintenance is needed after 3 month's run time.
• Greasing to spring, for Actuator with spring.
• All fasteners tightening
• Rod end bearing greasing
SEDEMACTM
Page 30 of 36
Communication protocol for EG1298
14 MODBUS Based Protocol
The EG1298 engine controller implement a custom protocol based on the standard MODBUS protocol.
This controller operates in a slave mode and responds to the commands received from an external MODBUS master. The EG1298 controller can send alarm messages and can receive operational commands over MODBUS communication.
14.1 Connection Details
The transmission mode used by EG1298 controller is MODBUS RTU (not MODBUS ASCII). The byte format for communication is 1 start bit, 8 data bits, with/without parity bit and 1 stop bit. The baud rate is selectable between 1200 kbps to 115200 kbps through the configuration options. For more details on how the baud rate can be set, please refer the section Configurable Parameters in this document. Similarly, the slave ID can be selected through the configuration options in EG1298 controller.
14.2 Supported Functions
The EG1298 controller operates as a MODBUS slave that responds to certain commands (or functions, as defined by MODBUS standard) received from the MOSBUS master in appropriate format. Supported functions and respective command-response structure is as shown below. If the command received from the MODBUS master is other than the three functions mentioned below, an exception message is generated.
Function 4 (0x04): Read Input Registers
This function is used to read measurement parameters and status from the EG1298 controller. The command-response pattern is as shown in Table 11 and Table 12.
Table 11 : Command from MODBUS master for Function 4
Table 12: Normal response from EG1298 slave for Function 4
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x04)
2 Byte count (n) Equals to number of registers to be read times two. 8-bit even number between 2 to 250
3 First register – high byte
4 First register – low byte
... ...
1+n Last register – high byte
2+n Last register – low byte
3+n/4+n Error check CRC
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x04)
2 First register address – high byte 16-bit register address, register address map is described in Table 23 3 First register address – low byte
4 Number of registers to read – high byte Number of registers to read must be between 1 to 255 5 Number of registers to read – low byte
6/7 Error check CRC
SEDEMACTM
Page 31 of 36
Function 16 (0x10): Write Holding Registers
This function is used to issue certain commands to the controller. The command-response pattern is as
shown in Table 13 and Table 14.
Table 13 : Command from MODBUS master for function 16
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x10)
2 First register address – high byte 16-bit register address, register address map is described in Table 23 3 First register address – low byte
4 Number of registers to write – high byte Number of registers to write must be between 1 to 255 5 Number of registers to write – low byte
6 Number of data bytes to follow (n)
7 Value at first register
... ...
6+n Value at last register
7+n/8+n Error check CRC
Table 14 : Normal response from EG1298 slave for function 16
Function 3 (0x03): Read Holding Registers
This function is used to read holding register to read the commands that have been issued to the controller. The command-response pattern is as shown in Table 15 and Table 16.
Table 15: Command from MODBUS master for Function 3
Table 16 : Normal response from EG1298 slave for Function 3
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x03)
2 Byte count (n) Equals to number of registers to be read times two. 8-bit even number between 2 to 250
3 First register – high byte
4 First register – low byte
... ...
1+n Last register – high byte
2+n Last register – low byte
3+n/4+n Error check CRC
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x10)
2 First register address – high byte 16-bit register address, register address map is described in Table 23 3 First register address – low byte
4 Number of registers written – high byte Number of registers that have been written
5 Number of registers written – low byte
6/7 Error check CRC
Byte Field Remarks
0 Slave address As configured in EG1298
1 Function code (0x03)
2 First register address – high byte 16-bit register address, register address map is described in Table 23 3 First register address – low byte
4 Number of registers to read – high byte Number of registers to read must be between 1 to 255 5 Number of registers to read – low byte
6/7 Error check CRC
SEDEMACTM
Page 32 of 36
14.3 Register Map
The register map for input registers is as shown in Table 17.
Table 17 : Register map for input registers
Register Offset
Value Scale Factor
Unit/Interpretation Bits/Sign
0 Protocol version 1 -- Unsigned
1 – 4 Reserved -- -- Unsigned
5 Battery voltage 0.1 V Unsigned
6 Number of starts 1 -- Unsigned
7 Number of trips 1 -- Unsigned
8 Engine run time 1 Hrs Unsigned
9 Engine speed 1 RPM Unsigned
10 Generator L1 frequency 0.1 Hz Unsigned
11 Generator L2 frequency 0.1 Hz Unsigned
12 Generator L3 frequency 0.1 Hz Unsigned
13 Generator L1-N voltage 0.1 V Unsigned
14 Generator L2-N voltage 0.1 V Unsigned
15 Generator L3-N voltage 0.1 V Unsigned
16 Generator L1-L2 voltage 0.1 V Unsigned
17 Generator L2-L3 voltage 0.1 V Unsigned
18 Generator L3- L1 voltage 0.1 V Unsigned
19 Generator L1 current 0.1 A Unsigned
20 Generator L2 current 0.1 A Unsigned
21 Generator L3 current 0.1 A Unsigned
22 Generator L1 power 0.1 KW Unsigned
23 Generator L2 power 0.1 KW Unsigned
24 Generator L3 power 0.1 KW Unsigned
25 Generator total power 0.1 KW Unsigned
26 Generator L1 apparent power
0.1 KVA Unsigned
27 Generator L2 apparent power
0.1 KVA Unsigned
28 Generator L3 apparent power
0.1 KVA Unsigned
29 Generator total apparent power
0.1 KVA Unsigned
30 Generator L1 reactive power 0.1 KVAr Unsigned
31 Generator L2 reactive power 0.1 KVAr Unsigned
32 Generator L3 reactive power 0.1 KVAr Unsigned
33 Generator total reactive power
0.1 KVAr Unsigned
34 Generator power factor L1 0.01 -- Unsigned
35 Generator power factor L2 0.01 -- Unsigned
36 Generator power factor L3 0.01 -- Unsigned
37 Generator average power factor
0.01 -- Unsigned
38 – 39 Generator cumulative energy
0.1 KWh Unsigned
40 – 41 Generator cumulative apparent energy
0.1 KVAh Unsigned
42 – 43 Generator cumulative reactive energy
0.1 KVArh Unsigned
44 – 52 Reserved -- -- Unsigned
53 Reserved -- --
54 Alarm 1 -- --
Reserved -- -- 13/16-16/16
SEDEMACTM
Page 33 of 36
Register Offset
Value Scale Factor
Unit/Interpretation Bits/Sign
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
55 Alarm 2 -- --
Under speed -- -- 13/16-16/16
Over speed -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
56 Alarm 3 -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
57 Alarm 4 -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Emergency stop -- -- 1/16-4/16
58 – 59 Alarm 5 – Alarm 6 -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
60 Alarm 7 -- --
Reserved -- -- 13/16-16/16
Magnetic pick-up fault -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
61 Alarm 8 -- --
Auxiliary Input A -- -- 13/16-16/16
Auxiliary Input B -- -- 9/16-12/16
Auxiliary Input C -- -- 5/16-8/16
Auxiliary Input D -- -- 1/16-4/16
62 Alarm 9 -- --
Auxiliary Input E -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
63 – 69 Alarm 10 – Alarm 16 -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
70 Reserved -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
71 Input Output Diagnostics -- --
Digital Input A -- -- 16/16
Digital Input B -- -- 15/16
Digital Input C -- -- 14/16
Digital Input D -- -- 13/16
Digital Input E -- -- 12/16
Reserved -- -- 9/16-11/16
SEDEMACTM
Page 34 of 36
Register Offset
Value Scale Factor
Unit/Interpretation Bits/Sign
Digital Output A -- -- 8/16
Digital Output B -- -- 7/16
Digital Output C -- -- 6/16
Digital Output D -- -- 5/16
Digital Output E -- -- 4/16
Reserved -- -- 3/16
Unimplemented -- -- 2/16
Unimplemented -- -- 1/16
72– 73 Reserved -- -- Unsigned
Actual value = Observed value on MODBUS interface multiplied with scale factor.
The interpretation of alarm status (registers 54-69 in Table 17) is as shown in Table 18
Table 18 : Interpretation of alarm status results
Value of Register
Interpretation
0 Alarm disabled
1 Alarm not active
2 Warning alarm active
3 Shutdown alarm active
4 Reserved
5 – 14 Reserved
15 Unimplemented
SEDEMACTM
Page 35 of 36
Notes
SEDEMACTM
Page 36 of 36
Disclaimer: Due to continuous development, the details provided in this document are subject to change without any prior notice.
SEDEMAC Mechatronics Pvt Ltd Technical Centre
C9-10, C Block, MIDC Bhosari Pune 411026, India
Manufacturing Plant
G-1, MIDC, Phase-III Chakan Industrial Area, Nighoje
Pune 410501, India
Manufacturing Plant Survey No. 64/5, Off Sinhagad Road
Vadgaon Budruk, Narhe Pune 411041, India